SHEET INDEX 1 AT ELECTRICAL LAYOUT AND DEVICES 2 AT DATA LAYOUT 3 ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4 ASL ELECTRICAL DEVICES MACDONALD HUMFREY 5 ASL DATA LAYOUT MACDONALD HUMFREY STANDALONE 6 ASL DATA LAYOUT MACDONALD HUMFREY CENTRALIZED SERVER 7 ASL ELECTRICAL LAYOUT VANDERLANDE INDUSTRIES 8 ASL ELECTRICAL DEVICES VANDERLANDE INDUSTRIES 9 ASL DATA LAYOUT VANDERLANDE INDUSTRIES STANDALONE 10 ASL DATA LAYOUT VANDERLANDE INDUSTRIES CENTRALIZED SERVER 11 ASL ELECTRICAL LAYOUT SCARABEE SYSTEMS 12 ASL ELECTRICAL DEVICES SCARABEE SYSTEMS 13 ASL DATA LAYOUT SCARABEE SYSTEMS STANDALONE 14 ASL DATA LAYOUT SCARABEE SYSTEMS CENTRALIZED SERVER 15 ASL ELECTRICAL LAYOUT SMITHS DETECTION 16 ASL ELECTRICAL DEVICES SMITHS DETECTION 17 ASL DATA LAYOUT SMITHS DETECTION STANDALONE 18 ASL DATA LAYOUT SMITHS DETECTION CENTRALIZED SERVER 19 ASL ELECTRICAL LAYOUT RAPISCAN SYSTEMS 20 ASL ELECTRICAL DEVICES RAPISCAN SYSTEMS 21 ASL DATA LAYOUT RAPISCAN SYSTEMS STANDALONE 22 ASL DATA LAYOUT RAPISCAN SYSTEMS CENTRALIZED SERVER 23 DATA CABLE REQUIREMENTS 24 DATA CABLE REQUIREMENTS OPTOSECURITY 25 NETWORK REQUIREMENTS 26 POWER DATA STANCHION 27 POWER DATA SURFACE MOUNT

Upload: trinhdien

Post on 21-Apr-2018

227 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

SHEET INDEX

1

AT ELECTRICAL LAYOUT AND DEVICES

2

AT DATA LAYOUT

3

ASL ELECTRICAL LAYOUT MACDONALD HUMFREY

4

ASL ELECTRICAL DEVICES MACDONALD HUMFREY

5

ASL DATA LAYOUT MACDONALD HUMFREY STANDALONE

6

ASL DATA LAYOUT MACDONALD HUMFREY CENTRALIZED SERVER

7

ASL ELECTRICAL LAYOUT VANDERLANDE INDUSTRIES

8

ASL ELECTRICAL DEVICES VANDERLANDE INDUSTRIES

9

ASL DATA LAYOUT VANDERLANDE INDUSTRIES STANDALONE

10

ASL DATA LAYOUT VANDERLANDE INDUSTRIES CENTRALIZED SERVER

11

ASL ELECTRICAL LAYOUT SCARABEE SYSTEMS

12

ASL ELECTRICAL DEVICES SCARABEE SYSTEMS

13

ASL DATA LAYOUT SCARABEE SYSTEMS STANDALONE

14

ASL DATA LAYOUT SCARABEE SYSTEMS CENTRALIZED SERVER

15

ASL ELECTRICAL LAYOUT SMITHS DETECTION

16

ASL ELECTRICAL DEVICES SMITHS DETECTION

17

ASL DATA LAYOUT SMITHS DETECTION STANDALONE

18

ASL DATA LAYOUT SMITHS DETECTION CENTRALIZED SERVER

19

ASL ELECTRICAL LAYOUT RAPISCAN SYSTEMS

20

ASL ELECTRICAL DEVICES RAPISCAN SYSTEMS

21

ASL DATA LAYOUT RAPISCAN SYSTEMS STANDALONE

22

ASL DATA LAYOUT RAPISCAN SYSTEMS CENTRALIZED SERVER

23DATA CABLE REQUIREMENTS

24DATA CABLE REQUIREMENTS OPTOSECURITY

25NETWORK REQUIREMENTS

26

POWER DATA STANCHION

27

POWER DATA SURFACE MOUNT

AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL AND DATA DESIGN-COVER
AutoCAD SHX Text
NOTE: REFERENCE CHECKPOINT DESIGN GUIDE 6.1 FOR ADDITIONAL ELECTRICAL AND DATA REQUIREMENTS FOR A COMPLETE CHECKPOINT INSTALLATION.
Page 2: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
3
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
R
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
L
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
2
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT2
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
ETD
AutoCAD SHX Text
BLS
AutoCAD SHX Text
AVS
AutoCAD SHX Text
ETD
AutoCAD SHX Text
BLS
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040 aTiX
AutoCAD SHX Text
AVS
AutoCAD SHX Text
AVS
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
FRONT X-RAY OUTLET (A)(A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A)(A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A)(A)
AutoCAD SHX Text
REAR X-RAY OUTLET (B) (B)
AutoCAD SHX Text
REAR X-RAY FLOOR OUTLET (B) (B)
AutoCAD SHX Text
REAR X-RAY OUTLET (B) (B)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
PRIVATE SCREENING ROOM OUTLET & POWER POLE (E) (E)
AutoCAD SHX Text
SINGLE LANE WALL OUTLET (D) (D)
AutoCAD SHX Text
STSO WALL OUTLET (MAY BE FLUSH MOUNTED)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
IT ROOM LOCATION VARIES
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A)(A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A)(A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A)(A)
AutoCAD SHX Text
AVS/ETD/BLS POWER POLE (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS POWER POLE (C) (C)
AutoCAD SHX Text
SINGLE LANE POWER POLE (D) (D)
AutoCAD SHX Text
STSO POWER POLE
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
IT RACK POWER POLE
AutoCAD SHX Text
IT RACK OUTLET
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL WALL OUTLET (F) (F) (GENERAL LOCATION TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL POWER POLE (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL WALL OUTLET (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
POTS PHONE LINE (GENERAL LOCATION TBD)
AutoCAD SHX Text
DATA LINE FOR CHRONOS CLOCK (F) (F) (GENERAL LOCATION TBD)
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
*NOTE: MORE THAN ONE REPEATER MAY BE NECESSARY PER CHECKPOINT
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
BINS
AutoCAD SHX Text
EMPTY
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040 aTiX
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
BLANK/ EXPANDABLE
AutoCAD SHX Text
FRONT XRAY OUTLET (A)
AutoCAD SHX Text
REAR XRAY OUTLET (B)
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
QUEUE CONV.
AutoCAD SHX Text
CONVENIENCE
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
AIT
AutoCAD SHX Text
AT XRAY
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
AT 1
AutoCAD SHX Text
AT 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
AIT 1
AutoCAD SHX Text
AIT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
BLANK/ EXPANDABLE
AutoCAD SHX Text
AVS/ETD/BLS/AVS/AVS (C)
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
BLS 1
AutoCAD SHX Text
BLS 2
AutoCAD SHX Text
PRIVATE SCREENING ROOM (E)
AutoCAD SHX Text
PSR 1
AutoCAD SHX Text
PSR 2
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED ETD & QUEUE ONLY
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
DEDICATED ETD & QUEUE ONLY
AutoCAD SHX Text
DUPLEX DEDICATED FOR PSR ONLY
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
DEDICATED POWER STRIP ONLY
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
TDC/CAT & STSO (G)
AutoCAD SHX Text
DEDICATED TDC/ MOBILE ETD ONLY (4 MAX)
AutoCAD SHX Text
TDC1 A
AutoCAD SHX Text
TDC2 B
AutoCAD SHX Text
TDC2 B
AutoCAD SHX Text
TDC2 A
AutoCAD SHX Text
TDC/ ETD
AutoCAD SHX Text
TDC/ ETD
AutoCAD SHX Text
AIT
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SINGLE LANE WALL (D)
AutoCAD SHX Text
REPEATER
AutoCAD SHX Text
DURESS ALARM & CHRONOS CLOCK (F)
AutoCAD SHX Text
DEDICATED REPEATER ONLY
AutoCAD SHX Text
POTS
AutoCAD SHX Text
PHONE LINE
AutoCAD SHX Text
DEDICATED RECEIVER ONLY
AutoCAD SHX Text
RECEIVER
AutoCAD SHX Text
CHRONOS CLOCK
AutoCAD SHX Text
DATA LINES
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
ETD1
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
POWER REQUIREMENTS
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
MAX NUMBER OF EQUIPMENT ALLOWED PER DEDICATED CIRCUIT
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
4
AutoCAD SHX Text
PROVIDE FLUSH MOUNTED DEVICE, OUTLET IS DESIGNED TO SERVE (2) MOBILE ETD UNITS
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
10
AutoCAD SHX Text
L5-15R SIMPLEX RECEPTACLE
AutoCAD SHX Text
AT X-RAY
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE
AutoCAD SHX Text
QUEUING CONVEYOR
AutoCAD SHX Text
2
AutoCAD SHX Text
MAY BE SHARED WITH CO-LOCATED ETD OUTLET WITHIN THE SAME MODULE SET
AutoCAD SHX Text
AIT
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
MAY BE SHARED WITH QUEUING CONVEYOR OUTLET WITHIN THE SAME MODULE SET
AutoCAD SHX Text
AVS/ETD/BLS/AVS
AutoCAD SHX Text
1 SHARED LOCATION
AutoCAD SHX Text
OUTLET(S) POWERS RELOCATEABLE POWER TAP
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
ONE OUTLET INSIDE AND ONE OUTLET OUTSIDE OF PRIVATE SCREENING ROOM
AutoCAD SHX Text
STSO PODIUM
AutoCAD SHX Text
2
AutoCAD SHX Text
PROVIDE DUPLEX OUTLET
AutoCAD SHX Text
IT CABINET
AutoCAD SHX Text
1
AutoCAD SHX Text
30A L5-30R RECEPTACLE
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO REPEATERS PER DUPLEX
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO PER DUPLEX
AutoCAD SHX Text
ALL CIRCUITS TO HAVE 20 AMP SERVICE WITH EXCEPTION TO IT CABINET WHICH SHALL HAVE 30 AMP SERVICE
AutoCAD SHX Text
GENERIC POWER POLE DEVICE SYMBOL
AutoCAD SHX Text
GENERIC RECESSED FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC MODULAR FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL POTS PHONE LINE SYMBOL
AutoCAD SHX Text
GENERIC WALL DATA DEVICE SYMBOL
AutoCAD SHX Text
OR
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.)
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DESIGN-AT2
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 1
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 3: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
3
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
R
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
TABLE630
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
L
AutoCAD SHX Text
2
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT2
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
ETD
AutoCAD SHX Text
BLS
AutoCAD SHX Text
AVS
AutoCAD SHX Text
ETD
AutoCAD SHX Text
BLS
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040 aTiX
AutoCAD SHX Text
AVS
AutoCAD SHX Text
AVS
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
"POTS PHONE LINE"
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040 aTiX
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. AVS DATA LINES FROM THE REAR XRAY OUTLET MAY ROUTE THRU THE IT ROOM IF AVS DATA LINES FROM THE REAR XRAY OUTLET MAY ROUTE THRU THE IT ROOM IF NECESSARY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY -AT2
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 2
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 4: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
PRIVATE SCREENING ROOM OUTLET & POWER POLE (E)
AutoCAD SHX Text
SINGLE LANE WALL OUTLET (D) (D)
AutoCAD SHX Text
STSO WALL OUTLET (MAY BE FLUSH MOUNTED IN FLOOR)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
AVS/ETD/BLS POWER POLE (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS POWER POLE (C) (C)
AutoCAD SHX Text
SINGLE LANE POWER POLE (D) (D)
AutoCAD SHX Text
STSO POWER POLE
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
IT RACK POWER POLE
AutoCAD SHX Text
IT RACK OUTLET
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL WALL OUTLET (C) (C) (GENERAL LOCATION TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL POWER POLE (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL WALL OUTLET (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
POTS PHONE LINE (GENERAL LOCATION TBD)
AutoCAD SHX Text
*NOTE: MORE THAN ONE REPEATER MAY BE NECESSARY PER CHECKPOINT
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
I/O ROOM OUTLET WHERE APPLICABLE (J) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (M)(M)
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
POSSIBLE FUTURE E-GATE LOCATION (K) (K)
AutoCAD SHX Text
POSSIBLE FUTURE VIDEO OR AVATAR DIVEST COACHING LOCATION (L) (L)
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
4
AutoCAD SHX Text
NOTE:IN OPTIMAL LAYOUTS WITH THE AIT IN OPTIMAL LAYOUTS WITH THE AIT PLACED FORWARD OF THE X-RAY BODY, THE REAR OUTLETS MUST BE PROVIDED IN FRONT OF THE AT BODY.
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
DATA LINE FOR CHRONOS CLOCK (F) (F) (GENERAL LOCATION TBD)
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
IT ROOM LOCATION VARIES
AutoCAD SHX Text
I/O ROOM
AutoCAD SHX Text
GENERIC POWER POLE DEVICE SYMBOL
AutoCAD SHX Text
GENERIC RECESSED FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC MODULAR FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL POTS PHONE LINE SYMBOL
AutoCAD SHX Text
GENERIC WALL DATA DEVICE SYMBOL
AutoCAD SHX Text
OR
AutoCAD SHX Text
HATCH PATTERN INDICATES WHERE NO OUTLET DEVICES MAY BE LOCATED.
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL LAYOUT -MACDONALD HUMFREY
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 3
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 5: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
ASL SUPERVISOR CONTROL LOCATION LOCATED AT SUPERVISOR OFFICE (H)
AutoCAD SHX Text
DEDICATED SEMS CLIENT PC ONLY (2 MAX)
AutoCAD SHX Text
SEMS CLIENT
AutoCAD SHX Text
I/O ROOM (J)
AutoCAD SHX Text
DEDICATED WORK STATIONS ONLY (4 MAX)
AutoCAD SHX Text
WRK STATION
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
SPARE 1
AutoCAD SHX Text
SPARE 2
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
POWER REQUIREMENTS
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
MAX NUMBER OF EQUIPMENT ALLOWED PER DEDICATED CIRCUIT
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
TDC/CAT/E GATE/BAT
AutoCAD SHX Text
1
AutoCAD SHX Text
1 20A CIRCUIT PER LANE
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
10
AutoCAD SHX Text
L5-15R SIMPLEX RECEPTACLE
AutoCAD SHX Text
AT X-RAY
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
1
AutoCAD SHX Text
RECEPTACLE TO BE DETERMINED, PROVIDE DEDICATED 208/240 1PHASE UP TO 50AMP
AutoCAD SHX Text
ASL Supply 1
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DEDICATED 20A SPLIT WIRED DUPLEX RECEPTACLE
AutoCAD SHX Text
ASL Supply 2
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DEDICATED 20A SPLIT WIRED DUPLEX RECEPTACLE
AutoCAD SHX Text
AIT
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE DEDICATED AT EACH LANE
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
AVS/AVS/ETD/BLS/AVS
AutoCAD SHX Text
1 SHARED LOCATION/ DEDICATED
AutoCAD SHX Text
OUTLET(S) POWERS RELOCATEABLE POWER TAP/ PROVIDE 2 20AMP CIRCUITS
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
ONE OUTLET INSIDE AND ONE OUTLET OUTSIDE OF PRIVATE SCREENING ROOM
AutoCAD SHX Text
STSO PODIUM
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DUPLEX OUTLET
AutoCAD SHX Text
IT CABINET
AutoCAD SHX Text
1
AutoCAD SHX Text
30A L5-30R RECEPTACLE
AutoCAD SHX Text
ASL SEMS SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED
AutoCAD SHX Text
ASL SEMS REDUNDANT SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED, NOT ON SAME PANEL AS THE MAIN SERVER, ON BACKUP POWER
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO REPEATERS PER DUPLEX
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO PER DUPLEX
AutoCAD SHX Text
E-GATE/BATT
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
PASSENGER PREP/AVATAR
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ALL CIRCUITS TO HAVE 20 AMP SERVICE WITH EXCEPTION TO IT CABINET AND ASL SERVER CABINET WHICH SHALL HAVE 30 AMP SERVICE
AutoCAD SHX Text
DEVICE LOCATIONS ARE SUBJECT TO CHANGE AND SHOULD BE VERIFIED PRIOR TO INSTALL
AutoCAD SHX Text
ALL ASL LANE INSTALLATIONS SHALL INCLUDE TSA HQ IT IN PLANNING AND INSTALLATION
AutoCAD SHX Text
THE IT CABINET SHALL BE A STANDARD DESIGNED 26U TYPE WALL OR FLOOR MOUNT RACK ENCLOSURE, RECOMMENDED DEPTH OF 32"
AutoCAD SHX Text
AIT
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SINGLE LANE WALL (D)
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
ETD1
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
REAR XRAY ASL SUPPLY OUTLET (B)
AutoCAD SHX Text
AIT
AutoCAD SHX Text
AT XRAY
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
AT 1
AutoCAD SHX Text
AT 2
AutoCAD SHX Text
AVS1/AT 1
AutoCAD SHX Text
AVS1/AT 2
AutoCAD SHX Text
AIT 1
AutoCAD SHX Text
AIT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
ASL SUPPLY 2
AutoCAD SHX Text
ASL SUPPLY 1
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
FRONT XRAY OUTLET (A)
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
DEDICATED DEVICE TBD
AutoCAD SHX Text
208/240 1PHASE UP TO 50 AMP
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
AVS1/AT 3
AutoCAD SHX Text
AVS/ETD/BLS/AVS/AVS (C)
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
BLS 1
AutoCAD SHX Text
BLS 2
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
DEDICATED POWER STRIP ONLY
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
FUTURE E-GATE/BAT (K)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
FUTURE PASSENGER PREP/AVATAR (L)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
ASL SEMS SERVER - CENTRALIZED (N)
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
DATA FROM ALL CHECKPOINTS, 2X SINGLE MODE FIBER OPTIC OR 2X CAT 6A, FROM EACH CHECKPOINT SERVED
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
TDC/CAT & STSO PODIUM (G)
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
TDC1 A
AutoCAD SHX Text
TDC1 B
AutoCAD SHX Text
TDC2 B
AutoCAD SHX Text
TDC2 A
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
PRIVATE SCREENING ROOM (E)
AutoCAD SHX Text
PSR 1
AutoCAD SHX Text
PSR 2
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
DUPLEX DEDICATED FOR PSR ONLY
AutoCAD SHX Text
REPEATER
AutoCAD SHX Text
DURESS ALARM & CHRONOS CLOCK (F)
AutoCAD SHX Text
DEDICATED REPEATER ONLY
AutoCAD SHX Text
POTS
AutoCAD SHX Text
PHONE LINE
AutoCAD SHX Text
DEDICATED RECEIVER ONLY
AutoCAD SHX Text
RECEIVER
AutoCAD SHX Text
CHRONOS CLOCK
AutoCAD SHX Text
DATA LINES
AutoCAD SHX Text
ASL IT ROOM SEMS COLLOCATED SERVER OR MANAGED SWITCH FOR CENTRAL SERVER-- (M)
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
2 DATA CABELS FROM EACH LANE SERVERD
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DEVICES-MACDONALD HUMFREY
AutoCAD SHX Text
SHEET 4
AutoCAD SHX Text
NOTE: 1. UP TO 6 208/220V 30A CIRCUITS PER BACK UP TO 6 208/220V 30A CIRCUITS PER BACK TO BACK LANE SETS. POWER SUPPLY CONDUIT SHOULD BE INSTALLED FOR FUTURE EQUIPMENT DEPLOYMENTS. 2. POWER SUPPLY WILL BE AN ISSUE WHEN POWER SUPPLY WILL BE AN ISSUE WHEN ADDING APPROXIMATELY 100AMPS PER LANE. POWER SUPPLY IN THE VICINITY OF THE CHECKPOINT SHOULD BE VERIFIED AND REQUIRED UPGRADES PLANNED. THIS INCLUDES BUT NOT LIMITED TO ADDITIONAL ROOM FOR TRANSFORMERS, DISTRIBUTION PANELS AND UPGRADES TO FACILITY ELECTRICAL SERVICE. 3. VERIFY OUTLET DEVICE TYPE FOR DEDICATED VERIFY OUTLET DEVICE TYPE FOR DEDICATED CIRCUITS WITH OEM VENDOR, TYP.
AutoCAD SHX Text
FOR CENTRAL SEMS SERVER SOLUTION CAT6 OR SINGLE MODE FIBER
Page 6: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
4
AutoCAD SHX Text
I/O ROOM
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
ASL SEMS WORK STATIONS
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
SEMS CLIENT PC REQUIRED AT EACH CHECKPOINT, LOCATION AT EACH CHECKPOINT WILL VARY
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY. 11. AVS DATA LINES FROM THE REAR XRAY OUTLET MAY ROUTE THRU THE IT ROOM IF NECESSARY.AVS DATA LINES FROM THE REAR XRAY OUTLET MAY ROUTE THRU THE IT ROOM IF NECESSARY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- MH - COLLOCATED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 5
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 7: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
4
AutoCAD SHX Text
I/O ROOM
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
ASL SEMS WORK STATIONS
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC RUN TO EACH CONNECTED CHECKPOINT
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (N) (N)
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
SEMS CLIENT PC REQUIRED AT EACH CHECKPOINT, LOCATION AT EACH CHECKPOINT WILL VARY
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY. 11. AVS DATA LINES FROM THE REAR XRAY OUTLET MAY ROUTE THRU THE IT ROOM IF NECESSARY.AVS DATA LINES FROM THE REAR XRAY OUTLET MAY ROUTE THRU THE IT ROOM IF NECESSARY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- MH - CENTRALIZED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 6
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 8: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
PRIVATE SCREENING ROOM OUTLET & POWER POLE (E)
AutoCAD SHX Text
SINGLE LANE WALL OUTLET (D) (D)
AutoCAD SHX Text
STSO WALL OUTLET (MAY BE FLUSH MOUNTED IN FLOOR)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
AVS/ETD/BLS POWER POLE (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS POWER POLE (C) (C)
AutoCAD SHX Text
SINGLE LANE POWER POLE (D) (D)
AutoCAD SHX Text
STSO POWER POLE
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
IT RACK POWER POLE
AutoCAD SHX Text
IT RACK OUTLET
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL WALL OUTLET (C) (C) (GENERAL LOCATION TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL POWER POLE (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL WALL OUTLET (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
POTS PHONE LINE (GENERAL LOCATION TBD)
AutoCAD SHX Text
*NOTE: MORE THAN ONE REPEATER MAY BE NECESSARY PER CHECKPOINT
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
I/O ROOM OUTLET WHERE APPLICABLE (J) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (M)(M)
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
POSSIBLE FUTURE E-GATE LOCATION (K) (K)
AutoCAD SHX Text
POSSIBLE FUTURE VIDEO OR AVATAR DIVEST COACHING LOCATION (L) (L)
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
4
AutoCAD SHX Text
NOTE:IN OPTIMAL LAYOUTS WITH THE AIT IN OPTIMAL LAYOUTS WITH THE AIT PLACED FORWARD OF THE X-RAY BODY, THE REAR OUTLETS MUST BE PROVIDED IN FRONT OF THE AT BODY.
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
DATA LINE FOR CHRONOS CLOCK (F) (F) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
IT ROOM LOCATION VARIES
AutoCAD SHX Text
I/O ROOM
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
GENERIC POWER POLE DEVICE SYMBOL
AutoCAD SHX Text
GENERIC RECESSED FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC MODULAR FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL POTS PHONE LINE SYMBOL
AutoCAD SHX Text
GENERIC WALL DATA DEVICE SYMBOL
AutoCAD SHX Text
OR
AutoCAD SHX Text
HATCH PATTERN INDICATES WHERE NO OUTLET DEVICES MAY BE LOCATED.
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL LAYOUT - VANDERLANDE IND.
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 7
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 9: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
ASL SUPERVISOR CONTROL LOCATION LOCATED AT SUPERVISOR OFFICE (H)
AutoCAD SHX Text
DEDICATED SEMS CLIENT PC ONLY (2 MAX)
AutoCAD SHX Text
SEMS CLIENT
AutoCAD SHX Text
I/O ROOM (J)
AutoCAD SHX Text
DEDICATED WORK STATIONS ONLY (4 MAX)
AutoCAD SHX Text
WRK STATION
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
SPARE 1
AutoCAD SHX Text
SPARE 2
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
POWER REQUIREMENTS
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
MAX NUMBER OF EQUIPMENT ALLOWED PER DEDICATED CIRCUIT
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
TDC/CAT/E GATE/BAT
AutoCAD SHX Text
1
AutoCAD SHX Text
1 20A CIRCUIT PER LANE
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
10
AutoCAD SHX Text
L5-15R SIMPLEX RECEPTACLE
AutoCAD SHX Text
AT X-RAY
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
1
AutoCAD SHX Text
RECEPTACLE TO BE DETERMINED, PROVIDE DEDICATED 208/240 1PHASE UP TO 50AMP
AutoCAD SHX Text
ASL Supply
AutoCAD SHX Text
1
AutoCAD SHX Text
DEDICATED 208/240 1PHASE 30AMP
AutoCAD SHX Text
ASL SCREENING COMPUTER
AutoCAD SHX Text
1
AutoCAD SHX Text
1 20A CIRCUIT PER LANE
AutoCAD SHX Text
AIT
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE DEDICATED AT EACH LANE
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
AVS/AVS/ETD/BLS/AVS
AutoCAD SHX Text
1 SHARED LOCATION/ DEDICATED
AutoCAD SHX Text
OUTLET(S) POWERS RELOCATEABLE POWER TAP/ PROVIDE 2 20AMP CIRCUITS
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
ONE OUTLET INSIDE AND ONE OUTLET OUTSIDE OF PRIVATE SCREENING ROOM
AutoCAD SHX Text
STSO PODIUM
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DUPLEX OUTLET
AutoCAD SHX Text
IT CABINET
AutoCAD SHX Text
1
AutoCAD SHX Text
30A L5-30R RECEPTACLE
AutoCAD SHX Text
ASL SEMS SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
NEMA L6-30 3OA DEDICATED
AutoCAD SHX Text
ASL SEMS REDUNDANT SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED, NOT ON SAME PANEL AS THE MAIN SERVER, ON BACKUP POWER
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO REPEATERS PER DUPLEX
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO PER DUPLEX
AutoCAD SHX Text
E-GATE/BATT
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
PASSENGER PREP/AVATAR
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ALL CIRCUITS TO HAVE 20 AMP SERVICE WITH EXCEPTION TO IT CABINET AND ASL SERVER CABINET WHICH SHALL HAVE 30 AMP SERVICE
AutoCAD SHX Text
DEVICE LOCATIONS ARE SUBJECT TO CHANGE AND SHOULD BE VERIFIED PRIOR TO INSTALL
AutoCAD SHX Text
ALL ASL LANE INSTALLATIONS SHALL INCLUDE TSA HQ IT IN PLANNING AND INSTALLATION
AutoCAD SHX Text
THE IT CABINET SHALL BE A STANDARD DESIGNED 26U TYPE WALL OR FLOOR MOUNT RACK ENCLOSURE, RECOMMENDED DEPTH OF 32"
AutoCAD SHX Text
AIT
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SINGLE LANE WALL (D)
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
ETD1
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
FRONT XRAY OUTLET (A)
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
AVS/ETD/BLS/AVS/AVS (C)
AutoCAD SHX Text
ASL WK STN
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
DEDICATED POWER STRIPS ONLY
AutoCAD SHX Text
ASL WK STN
AutoCAD SHX Text
ASL WK STN
AutoCAD SHX Text
VGA CABLE PORT LANE 1
AutoCAD SHX Text
VGA CABLE PORT LANE 2
AutoCAD SHX Text
VGA CABLE PORT LANE 1
AutoCAD SHX Text
VGA CABLE PORT LANE 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
BLS 1
AutoCAD SHX Text
BLS 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
ASL SVR 2
AutoCAD SHX Text
ASL SVR 1
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
VGA CABLE PORT LANE 1
AutoCAD SHX Text
VGA CABLE PORT LANE 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
FUTURE E-GATE/BAT (K)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
FUTURE PASSENGER PREP/AVATAR (L)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
ASL SEMS SERVER - CENTRALIZED (N)
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
DATA FROM ALL CHECKPOINTS, 2X SINGLE MODE FIBER OPTIC OR 2X CAT 6A, FROM EACH CHECKPOINT SERVED
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
TDC/CAT & STSO PODIUM (G)
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
TDC1 A
AutoCAD SHX Text
TDC1 B
AutoCAD SHX Text
TDC2 B
AutoCAD SHX Text
TDC2 A
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
PRIVATE SCREENING ROOM (E)
AutoCAD SHX Text
PSR 1
AutoCAD SHX Text
PSR 2
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
DUPLEX DEDICATED FOR PSR ONLY
AutoCAD SHX Text
REPEATER
AutoCAD SHX Text
DURESS ALARM & CHRONOS CLOCK (F)
AutoCAD SHX Text
DEDICATED REPEATER ONLY
AutoCAD SHX Text
POTS
AutoCAD SHX Text
PHONE LINE
AutoCAD SHX Text
DEDICATED RECEIVER ONLY
AutoCAD SHX Text
RECEIVER
AutoCAD SHX Text
CHRONOS CLOCK
AutoCAD SHX Text
DATA LINES
AutoCAD SHX Text
REAR XRAY ASL SUPPLY OUTLET (B)
AutoCAD SHX Text
AIT
AutoCAD SHX Text
AT XRAY
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
AT 1
AutoCAD SHX Text
AT 2
AutoCAD SHX Text
AIT 1
AutoCAD SHX Text
AIT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
DEDICATED DEVICE TBD
AutoCAD SHX Text
208/240 1PHASE UP TO 50 AMP
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
ASL SUPPLY
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
208/240 1PHASE UP TO 30 AMP
AutoCAD SHX Text
ASL SCREENING COMPUTER
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
AVS1/AT 1
AutoCAD SHX Text
AVS1/AT 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
AVS VGA CABLE PORT
AutoCAD SHX Text
AVS VGA CABLE PORT
AutoCAD SHX Text
AVS VGA CABLE PORT
AutoCAD SHX Text
AVS2/AT 3
AutoCAD SHX Text
ASL IT ROOM SEMS COLLOCATED SERVER OR MANAGED SWITCH FOR CENTRAL SERVER- (M)
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
2 DATA CABELS FROM EACH LANE SERVERD
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
REDUNDANT SEMS
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
NEMA L6-30
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
NEMA L6-30
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DEVICES -VANDERLANDE IND.
AutoCAD SHX Text
SHEET 8
AutoCAD SHX Text
NOTE: 1. UP TO 6 208/220V 30A CIRCUITS PER BACK UP TO 6 208/220V 30A CIRCUITS PER BACK TO BACK LANE SETS. POWER SUPPLY CONDUIT SHOULD BE INSTALLED FOR FUTURE EQUIPMENT DEPLOYMENTS. 2. POWER SUPPLY WILL BE AN ISSUE WHEN POWER SUPPLY WILL BE AN ISSUE WHEN ADDING APPROXIMATELY 100AMPS PER LANE. POWER SUPPLY IN THE VICINITY OF THE CHECKPOINT SHOULD BE VERIFIED AND REQUIRED UPGRADES PLANNED. THIS INCLUDES BUT NOT LIMITED TO ADDITIONAL ROOM FOR TRANSFORMERS, DISTRIBUTION PANELS AND UPGRADES TO FACILITY ELECTRICAL SERVICE. 3. VERIFY OUTLET DEVICE TYPE FOR DEDICATED VERIFY OUTLET DEVICE TYPE FOR DEDICATED CIRCUITS WITH OEM VENDOR, TYP.
AutoCAD SHX Text
FOR CENTRAL SEMS SERVER SOLUTION CAT6 OR SINGLE MODE FIBER
Page 10: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
4
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- VI - COLLOCATED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 9
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 11: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
4
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6A
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC RUN TO EACH CONNECTED CHECKPOINT
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (N)
AutoCAD SHX Text
2 x CAT 6A
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- VI - CENTRALIZED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 10
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 12: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
PRIVATE SCREENING ROOM OUTLET & POWER POLE (E)
AutoCAD SHX Text
SINGLE LANE WALL OUTLET (D) (D)
AutoCAD SHX Text
STSO WALL OUTLET (MAY BE FLUSH MOUNTED IN FLOOR)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
AVS/ETD/BLS POWER POLE (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS POWER POLE (C) (C)
AutoCAD SHX Text
SINGLE LANE POWER POLE (D) (D)
AutoCAD SHX Text
STSO POWER POLE
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
IT RACK POWER POLE
AutoCAD SHX Text
IT RACK OUTLET
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL WALL OUTLET (C) (C) (GENERAL LOCATION TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL POWER POLE (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL WALL OUTLET (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
POTS PHONE LINE (GENERAL LOCATION TBD)
AutoCAD SHX Text
*NOTE: MORE THAN ONE REPEATER MAY BE NECESSARY PER CHECKPOINT
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
I/O ROOM OUTLET WHERE APPLICABLE (J) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (M)(M)
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
POSSIBLE FUTURE E-GATE LOCATION (K) (K)
AutoCAD SHX Text
POSSIBLE FUTURE VIDEO OR AVATAR DIVEST COACHING LOCATION (L) (L)
AutoCAD SHX Text
3
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
NOTE:IN OPTIMAL LAYOUTS WITH THE AIT IN OPTIMAL LAYOUTS WITH THE AIT PLACED FORWARD OF THE X-RAY BODY, THE REAR OUTLETS MUST BE PROVIDED IN FRONT OF THE AT BODY.
AutoCAD SHX Text
DATA LINE FOR CHRONOS CLOCK (F) (F) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
IT ROOM LOCATION VARIES
AutoCAD SHX Text
I/O ROOM
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
GENERIC POWER POLE DEVICE SYMBOL
AutoCAD SHX Text
GENERIC RECESSED FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC MODULAR FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL POTS PHONE LINE SYMBOL
AutoCAD SHX Text
GENERIC WALL DATA DEVICE SYMBOL
AutoCAD SHX Text
OR
AutoCAD SHX Text
HATCH PATTERN INDICATES WHERE NO OUTLET DEVICES MAY BE LOCATED.
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL LAYOUT - SCARABEE SYSTEMS
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 11
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 13: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
ASL SUPERVISOR CONTROL LOCATION LOCATED AT SUPERVISOR OFFICE (H)
AutoCAD SHX Text
DEDICATED SEMS CLIENT PC ONLY (2 MAX)
AutoCAD SHX Text
SEMS CLIENT
AutoCAD SHX Text
I/O ROOM (J)
AutoCAD SHX Text
DEDICATED WORK STATIONS ONLY (4 MAX)
AutoCAD SHX Text
WRK STATION
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
SPARE 1
AutoCAD SHX Text
SPARE 2
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
AIT
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SINGLE LANE WALL (D)
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
ETD1
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
FRONT XRAY OUTLET (A)
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
AVS/ETD/BLS/AVS/AVS (C)
AutoCAD SHX Text
ASL WK STN
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
DEDICATED POWER STRIPS ONLY
AutoCAD SHX Text
ASL WK STN
AutoCAD SHX Text
ASL WK STN
AutoCAD SHX Text
VGA CABLE PORT LANE 1
AutoCAD SHX Text
VGA CABLE PORT LANE 2
AutoCAD SHX Text
VGA CABLE PORT LANE 1
AutoCAD SHX Text
VGA CABLE PORT LANE 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
BLS 1
AutoCAD SHX Text
BLS 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
ASL SVR 2
AutoCAD SHX Text
ASL SVR 1
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
VGA CABLE PORT LANE 1
AutoCAD SHX Text
VGA CABLE PORT LANE 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
FUTURE E-GATE/BAT (K)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
FUTURE PASSENGER PREP/AVATAR (L)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
ASL SEMS SERVER - CENTRALIZED (N)
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
DATA FROM ALL CHECKPOINTS, 2X SINGLE MODE FIBER OPTIC OR 2X CAT 6A, FROM EACH CHECKPOINT SERVED
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
TDC/CAT & STSO PODIUM (G)
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
TDC1 A
AutoCAD SHX Text
TDC1 B
AutoCAD SHX Text
TDC2 B
AutoCAD SHX Text
TDC2 A
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
PRIVATE SCREENING ROOM (E)
AutoCAD SHX Text
PSR 1
AutoCAD SHX Text
PSR 2
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
DUPLEX DEDICATED FOR PSR ONLY
AutoCAD SHX Text
REPEATER
AutoCAD SHX Text
DURESS ALARM & CHRONOS CLOCK (F)
AutoCAD SHX Text
DEDICATED REPEATER ONLY
AutoCAD SHX Text
POTS
AutoCAD SHX Text
PHONE LINE
AutoCAD SHX Text
DEDICATED RECEIVER ONLY
AutoCAD SHX Text
RECEIVER
AutoCAD SHX Text
CHRONOS CLOCK
AutoCAD SHX Text
DATA LINES
AutoCAD SHX Text
ASL IT ROOM SEMS COLLOCATED SERVER OR MANAGED SWITCH FOR CENTRAL SERVER- (M)
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
2 DATA CABELS FROM EACH LANE SERVERD
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
REDUNDANT SEMS
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
NEMA L6-30
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
NEMA L6-30
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
POWER REQUIREMENTS
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
MAX NUMBER OF EQUIPMENT ALLOWED PER DEDICATED CIRCUIT
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
TDC/CAT/E GATE/BAT
AutoCAD SHX Text
1
AutoCAD SHX Text
1 20A CIRCUIT PER LANE
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
10
AutoCAD SHX Text
L5-15R SIMPLEX RECEPTACLE
AutoCAD SHX Text
AT X-RAY
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
1
AutoCAD SHX Text
RECEPTACLE TO BE DETERMINED, PROVIDE DEDICATED 208/240 1PHASE UP TO 50AMP
AutoCAD SHX Text
ASL Supply
AutoCAD SHX Text
1
AutoCAD SHX Text
2 x DEDICATED 20AMP PER LANE
AutoCAD SHX Text
ASL SCREENING COMPUTER
AutoCAD SHX Text
1
AutoCAD SHX Text
1 20A CIRCUIT PER LANE
AutoCAD SHX Text
AIT
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE DEDICATED AT EACH LANE
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
AVS/AVS/ETD/BLS/AVS
AutoCAD SHX Text
1 SHARED LOCATION/ DEDICATED
AutoCAD SHX Text
OUTLET(S) POWERS RELOCATEABLE POWER TAP/ PROVIDE 2 20AMP CIRCUITS
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
ONE OUTLET INSIDE AND ONE OUTLET OUTSIDE OF PRIVATE SCREENING ROOM
AutoCAD SHX Text
STSO PODIUM
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DUPLEX OUTLET
AutoCAD SHX Text
IT CABINET
AutoCAD SHX Text
1
AutoCAD SHX Text
30A L5-30R RECEPTACLE
AutoCAD SHX Text
ASL SEMS SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
NEMA L6-30 3OA DEDICATED
AutoCAD SHX Text
ASL SEMS REDUNDANT SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED, NOT ON SAME PANEL AS THE MAIN SERVER, ON BACKUP POWER
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO REPEATERS PER DUPLEX
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO PER DUPLEX
AutoCAD SHX Text
E-GATE/BATT
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
PASSENGER PREP/AVATAR
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ALL CIRCUITS TO HAVE 20 AMP SERVICE WITH EXCEPTION TO IT CABINET AND ASL SERVER CABINET WHICH SHALL HAVE 30 AMP SERVICE
AutoCAD SHX Text
DEVICE LOCATIONS ARE SUBJECT TO CHANGE AND SHOULD BE VERIFIED PRIOR TO INSTALL
AutoCAD SHX Text
ALL ASL LANE INSTALLATIONS SHALL INCLUDE TSA HQ IT IN PLANNING AND INSTALLATION
AutoCAD SHX Text
THE IT CABINET SHALL BE A STANDARD DESIGNED 26U TYPE WALL OR FLOOR MOUNT RACK ENCLOSURE, RECOMMENDED DEPTH OF 32"
AutoCAD SHX Text
REAR XRAY ASL SUPPLY OUTLET (B)
AutoCAD SHX Text
AIT
AutoCAD SHX Text
AT XRAY
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
AT 1
AutoCAD SHX Text
AT 2
AutoCAD SHX Text
AIT 1
AutoCAD SHX Text
AIT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
DEDICATED DEVICE TBD
AutoCAD SHX Text
208/240 1PHASE UP TO 50 AMP
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
ASL SCREENING COMPUTER
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
AVS1/AT 1
AutoCAD SHX Text
AVS1/AT 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
ASL SUPPLY 2
AutoCAD SHX Text
ASL SUPPLY 1
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
AVS VGA CABLE PORT
AutoCAD SHX Text
AVS VGA CABLE PORT
AutoCAD SHX Text
AVS VGA CABLE PORT
AutoCAD SHX Text
AVS1/AT 3
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DEVICES -SCARABEE SYSTEMS
AutoCAD SHX Text
SHEET 12
AutoCAD SHX Text
NOTE: 1. UP TO 6 208/220V 30A CIRCUITS PER BACK UP TO 6 208/220V 30A CIRCUITS PER BACK TO BACK LANE SETS. POWER SUPPLY CONDUIT SHOULD BE INSTALLED FOR FUTURE EQUIPMENT DEPLOYMENTS. 2. POWER SUPPLY WILL BE AN ISSUE WHEN POWER SUPPLY WILL BE AN ISSUE WHEN ADDING APPROXIMATELY 100AMPS PER LANE. POWER SUPPLY IN THE VICINITY OF THE CHECKPOINT SHOULD BE VERIFIED AND REQUIRED UPGRADES PLANNED. THIS INCLUDES BUT NOT LIMITED TO ADDITIONAL ROOM FOR TRANSFORMERS, DISTRIBUTION PANELS AND UPGRADES TO FACILITY ELECTRICAL SERVICE. 3. VERIFY OUTLET DEVICE TYPE FOR DEDICATED VERIFY OUTLET DEVICE TYPE FOR DEDICATED CIRCUITS WITH OEM VENDOR, TYP.
AutoCAD SHX Text
FOR CENTRAL SEMS SERVER SOLUTION CAT6 OR SINGLE MODE FIBER
Page 14: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
3
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- SC - COLLOCATED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 13
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 15: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x VGA + 3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC RUN TO EACH CONNECTED CHECKPOINT
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
ASL SEMS SERVERS
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (N)
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
3
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- SC - CENTRALIZED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 14
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 16: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
PRIVATE SCREENING ROOM OUTLET & POWER POLE (E)
AutoCAD SHX Text
SINGLE LANE WALL OUTLET (D) (D)
AutoCAD SHX Text
STSO WALL OUTLET (MAY BE FLUSH MOUNTED IN FLOOR)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
AVS/ETD/BLS POWER POLE (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS POWER POLE (C) (C)
AutoCAD SHX Text
SINGLE LANE POWER POLE (D) (D)
AutoCAD SHX Text
STSO POWER POLE
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
IT RACK POWER POLE
AutoCAD SHX Text
IT RACK OUTLET
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL WALL OUTLET (C) (C) (GENERAL LOCATION TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL POWER POLE (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL WALL OUTLET (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
POTS PHONE LINE (GENERAL LOCATION TBD)
AutoCAD SHX Text
*NOTE: MORE THAN ONE REPEATER MAY BE NECESSARY PER CHECKPOINT
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
I/O ROOM OUTLET WHERE APPLICABLE (J) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (M)(M)
AutoCAD SHX Text
ASL MATRIX SERVERS
AutoCAD SHX Text
POSSIBLE FUTURE E-GATE LOCATION (K) (K)
AutoCAD SHX Text
POSSIBLE FUTURE VIDEO OR AVATAR DIVEST COACHING LOCATION (L) (L)
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
NOTE:IN OPTIMAL LAYOUTS WITH THE AIT IN OPTIMAL LAYOUTS WITH THE AIT PLACED FORWARD OF THE X-RAY BODY, THE REAR OUTLETS MUST BE PROVIDED IN FRONT OF THE AT BODY.
AutoCAD SHX Text
DATA LINE FOR CHRONOS CLOCK (F) (F) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
IT ROOM LOCATION VARIES
AutoCAD SHX Text
I/O ROOM
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
GENERIC POWER POLE DEVICE SYMBOL
AutoCAD SHX Text
GENERIC RECESSED FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC MODULAR FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL POTS PHONE LINE SYMBOL
AutoCAD SHX Text
GENERIC WALL DATA DEVICE SYMBOL
AutoCAD SHX Text
OR
AutoCAD SHX Text
HATCH PATTERN INDICATES WHERE NO OUTLET DEVICES MAY BE LOCATED.
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL LAYOUT - SMITHS DETECTION
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 15
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 17: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
ASL SUPERVISOR CONTROL LOCATION LOCATED AT SUPERVISOR OFFICE (H)
AutoCAD SHX Text
DEDICATED SEMS CLIENT PC ONLY (2 MAX)
AutoCAD SHX Text
SEMS CLIENT
AutoCAD SHX Text
I/O ROOM (J)
AutoCAD SHX Text
DEDICATED WORK STATIONS ONLY (4 MAX)
AutoCAD SHX Text
WRK STATION
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
SPARE 1
AutoCAD SHX Text
SPARE 2
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
POWER REQUIREMENTS
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
MAX NUMBER OF EQUIPMENT ALLOWED PER DEDICATED CIRCUIT
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
TDC/CAT/E GATE/BAT
AutoCAD SHX Text
1
AutoCAD SHX Text
1 20A CIRCUIT PER LANE
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
10
AutoCAD SHX Text
L5-15R SIMPLEX RECEPTACLE
AutoCAD SHX Text
AT X-RAY
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
1
AutoCAD SHX Text
RECEPTACLE TO BE DETERMINED, PROVIDE DEDICATED 208/240 1PHASE UP TO 50AMP
AutoCAD SHX Text
ASL Supply 1
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DEDICATED 20A SPLIT WIRED DUPLEX RECEPTACLE
AutoCAD SHX Text
ASL Supply 2
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DEDICATED 20A SPLIT WIRED DUPLEX RECEPTACLE
AutoCAD SHX Text
AIT
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE DEDICATED AT EACH LANE
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
AVS/AVS/ETD/BLS/AVS
AutoCAD SHX Text
1 SHARED LOCATION/ DEDICATED
AutoCAD SHX Text
OUTLET(S) POWERS RELOCATEABLE POWER TAP/ PROVIDE 2 20AMP CIRCUITS
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
ONE OUTLET INSIDE AND ONE OUTLET OUTSIDE OF PRIVATE SCREENING ROOM
AutoCAD SHX Text
STSO PODIUM
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DUPLEX OUTLET
AutoCAD SHX Text
IT CABINET
AutoCAD SHX Text
1
AutoCAD SHX Text
30A L5-30R RECEPTACLE
AutoCAD SHX Text
ASL SEMS SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED
AutoCAD SHX Text
ASL SEMS REDUNDANT SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED, NOT ON SAME PANEL AS THE MAIN SERVER, ON BACKUP POWER
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO REPEATERS PER DUPLEX
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO PER DUPLEX
AutoCAD SHX Text
E-GATE/BATT
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
PASSENGER PREP/AVATAR
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ALL CIRCUITS TO HAVE 20 AMP SERVICE WITH EXCEPTION TO IT CABINET AND ASL SERVER CABINET WHICH SHALL HAVE 30 AMP SERVICE
AutoCAD SHX Text
DEVICE LOCATIONS ARE SUBJECT TO CHANGE AND SHOULD BE VERIFIED PRIOR TO INSTALL
AutoCAD SHX Text
ALL ASL LANE INSTALLATIONS SHALL INCLUDE TSA HQ IT IN PLANNING AND INSTALLATION
AutoCAD SHX Text
THE IT CABINET SHALL BE A STANDARD DESIGNED 26U TYPE WALL OR FLOOR MOUNT RACK ENCLOSURE, RECOMMENDED DEPTH OF 32"
AutoCAD SHX Text
AIT
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SINGLE LANE WALL (D)
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
ETD1
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
REAR XRAY ASL SUPPLY OUTLET (B)
AutoCAD SHX Text
AIT
AutoCAD SHX Text
AT XRAY
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
AT 1
AutoCAD SHX Text
AT 2
AutoCAD SHX Text
AVS1/AT 1
AutoCAD SHX Text
AVS1/AT 2
AutoCAD SHX Text
AIT 1
AutoCAD SHX Text
AIT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
ASL SUPPLY 2
AutoCAD SHX Text
ASL SUPPLY 1
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
FRONT XRAY OUTLET (A)
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
DEDICATED DEVICE TBD
AutoCAD SHX Text
208/240 1PHASE UP TO 50 AMP
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
AVS1/AT 3
AutoCAD SHX Text
AVS/ETD/BLS/AVS/AVS (C)
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
BLS 1
AutoCAD SHX Text
BLS 2
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
DEDICATED POWER STRIP ONLY
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
FUTURE E-GATE/BAT (K)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
FUTURE PASSENGER PREP/AVATAR (L)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
ASL SEMS SERVER - CENTRALIZED (N)
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
DATA FROM ALL CHECKPOINTS, 2X SINGLE MODE FIBER OPTIC OR 2X CAT 6A, FROM EACH CHECKPOINT SERVED
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
TDC/CAT & STSO PODIUM (G)
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
TDC1 A
AutoCAD SHX Text
TDC1 B
AutoCAD SHX Text
TDC2 B
AutoCAD SHX Text
TDC2 A
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
PRIVATE SCREENING ROOM (E)
AutoCAD SHX Text
PSR 1
AutoCAD SHX Text
PSR 2
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
DUPLEX DEDICATED FOR PSR ONLY
AutoCAD SHX Text
REPEATER
AutoCAD SHX Text
DURESS ALARM & CHRONOS CLOCK (F)
AutoCAD SHX Text
DEDICATED REPEATER ONLY
AutoCAD SHX Text
POTS
AutoCAD SHX Text
PHONE LINE
AutoCAD SHX Text
DEDICATED RECEIVER ONLY
AutoCAD SHX Text
RECEIVER
AutoCAD SHX Text
CHRONOS CLOCK
AutoCAD SHX Text
DATA LINES
AutoCAD SHX Text
ASL IT ROOM SEMS COLLOCATED SERVER OR MANAGED SWITCH FOR CENTRAL SERVER-- (M)
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
2 DATA CABELS FROM EACH LANE SERVERD
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DEVICES - SMITHS DETECTION
AutoCAD SHX Text
SHEET 16
AutoCAD SHX Text
FOR CENTRAL SEMS SERVER SOLUTION CAT6 OR SINGLE MODE FIBER
AutoCAD SHX Text
NOTE: 1. UP TO 6 208/220V 30A CIRCUITS PER BACK UP TO 6 208/220V 30A CIRCUITS PER BACK TO BACK LANE SETS. POWER SUPPLY CONDUIT SHOULD BE INSTALLED FOR FUTURE EQUIPMENT DEPLOYMENTS. 2. POWER SUPPLY WILL BE AN ISSUE WHEN POWER SUPPLY WILL BE AN ISSUE WHEN ADDING APPROXIMATELY 100AMPS PER LANE. POWER SUPPLY IN THE VICINITY OF THE CHECKPOINT SHOULD BE VERIFIED AND REQUIRED UPGRADES PLANNED. THIS INCLUDES BUT NOT LIMITED TO ADDITIONAL ROOM FOR TRANSFORMERS, DISTRIBUTION PANELS AND UPGRADES TO FACILITY ELECTRICAL SERVICE. 3. VERIFY OUTLET DEVICE TYPE FOR DEDICATED VERIFY OUTLET DEVICE TYPE FOR DEDICATED CIRCUITS WITH OEM VENDOR, TYP.
Page 18: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
ASL MATRIX SERVERS
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
ETD
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- SM - COLLOCATED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 17
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 19: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

727272

72

72

72

72

72

727272

60

60

48

AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC RUN TO EACH CONNECTED CHECKPOINT
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
ASL MATRIX SERVERS
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (N)
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
ETD
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- SM - CENTRALIZED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 18
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 20: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

606060

72

72

72

72

72

606060

60

60

48

AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
FRONT X-RAY OUTLET (A) (A)
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
TDC/CAT OUTLET (G) (G)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS OUTLET (C) (C)
AutoCAD SHX Text
PRIVATE SCREENING ROOM OUTLET & POWER POLE (E)
AutoCAD SHX Text
SINGLE LANE WALL OUTLET (D) (D)
AutoCAD SHX Text
STSO WALL OUTLET (MAY BE FLUSH MOUNTED IN FLOOR)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
REAR X-RAY POWER POLE (B) (B)
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
IT ROOM LOCATION VARIES
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
FRONT X-RAY POWER POLE (A) (A)
AutoCAD SHX Text
AVS/ETD/BLS POWER POLE (C) (C)
AutoCAD SHX Text
AVS/ETD/BLS/AVS POWER POLE (C) (C)
AutoCAD SHX Text
SINGLE LANE POWER POLE (D) (D)
AutoCAD SHX Text
STSO POWER POLE
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
TDC/CAT POWER POLE (G) (G)
AutoCAD SHX Text
IT RACK POWER POLE
AutoCAD SHX Text
IT RACK OUTLET
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL WALL OUTLET (C) (C) (GENERAL LOCATION TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL POWER POLE (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL WALL OUTLET (GENERAL LOCATION AND QUANTITY PER CHECKPOINT TBD)
AutoCAD SHX Text
POTS PHONE LINE (GENERAL LOCATION TBD)
AutoCAD SHX Text
*NOTE: MORE THAN ONE REPEATER MAY BE NECESSARY PER CHECKPOINT
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
I/O ROOM
AutoCAD SHX Text
REAR X-RAY OUTLET, ASL SUPPLY (B) (B)
AutoCAD SHX Text
I/O ROOM OUTLET WHERE APPLICABLE (J) (GENERAL LOCATION TBD)
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (M)(M)
AutoCAD SHX Text
ASL SERVERS
AutoCAD SHX Text
POSSIBLE FUTURE E-GATE LOCATION (K) (K)
AutoCAD SHX Text
POSSIBLE FUTURE VIDEO OR AVATAR DIVEST COACHING LOCATION (L) (L)
AutoCAD SHX Text
3
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
NOTE:IN OPTIMAL LAYOUTS WITH THE AIT IN OPTIMAL LAYOUTS WITH THE AIT PLACED FORWARD OF THE X-RAY BODY, THE REAR OUTLETS MUST BE PROVIDED IN FRONT OF THE AT BODY.
AutoCAD SHX Text
DATA LINE FOR CHRONOS CLOCK (F) (F) (GENERAL LOCATION TBD)
AutoCAD SHX Text
SUPERVISOR OFFICE
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
GENERIC POWER POLE DEVICE SYMBOL
AutoCAD SHX Text
GENERIC RECESSED FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC MODULAR FLOOR DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL DEVICE SYMBOL
AutoCAD SHX Text
GENERIC WALL POTS PHONE LINE SYMBOL
AutoCAD SHX Text
GENERIC WALL DATA DEVICE SYMBOL
AutoCAD SHX Text
OR
AutoCAD SHX Text
HATCH PATTERN INDICATES WHERE NO OUTLET DEVICES MAY BE LOCATED.
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL LAYOUT - RAPISCAN SYSTEMS
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 19
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 21: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
ASL SUPERVISOR CONTROL LOCATION LOCATED AT SUPERVISOR OFFICE (H)
AutoCAD SHX Text
DEDICATED SEMS CLIENT PC ONLY (2 MAX)
AutoCAD SHX Text
SEMS CLIENT
AutoCAD SHX Text
I/O ROOM (J)
AutoCAD SHX Text
DEDICATED WORK STATIONS ONLY (4 MAX)
AutoCAD SHX Text
WRK STATION
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
SPARE 1
AutoCAD SHX Text
SPARE 2
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
POWER REQUIREMENTS
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
MAX NUMBER OF EQUIPMENT ALLOWED PER DEDICATED CIRCUIT
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
TDC/CAT/E GATE/BAT
AutoCAD SHX Text
1
AutoCAD SHX Text
1 20A CIRCUIT PER LANE
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
10
AutoCAD SHX Text
L5-15R SIMPLEX RECEPTACLE
AutoCAD SHX Text
AT X-RAY
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
1
AutoCAD SHX Text
RECEPTACLE TO BE DETERMINED, PROVIDE DEDICATED 208/240 1PHASE UP TO 50AMP
AutoCAD SHX Text
ASL Supply 1
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DEDICATED 20A SPLIT WIRED DUPLEX RECEPTACLE
AutoCAD SHX Text
ASL Supply 2
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DEDICATED 20A SPLIT WIRED DUPLEX RECEPTACLE
AutoCAD SHX Text
AIT
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE SIMPLEX RECEPTACLE DEDICATED AT EACH LANE
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
AVS/AVS/ETD/BLS/AVS
AutoCAD SHX Text
1 SHARED LOCATION/ DEDICATED
AutoCAD SHX Text
OUTLET(S) POWERS RELOCATEABLE POWER TAP/ PROVIDE 2 20AMP CIRCUITS
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
1
AutoCAD SHX Text
ONE OUTLET INSIDE AND ONE OUTLET OUTSIDE OF PRIVATE SCREENING ROOM
AutoCAD SHX Text
STSO PODIUM
AutoCAD SHX Text
1
AutoCAD SHX Text
PROVIDE DUPLEX OUTLET
AutoCAD SHX Text
IT CABINET
AutoCAD SHX Text
1
AutoCAD SHX Text
30A L5-30R RECEPTACLE
AutoCAD SHX Text
ASL SEMS SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED
AutoCAD SHX Text
ASL SEMS REDUNDANT SERVER
AutoCAD SHX Text
1
AutoCAD SHX Text
3OA DEDICATED, NOT ON SAME PANEL AS THE MAIN SERVER, ON BACKUP POWER
AutoCAD SHX Text
DURESS ALARM RECEIVER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO REPEATERS PER DUPLEX
AutoCAD SHX Text
DURESS ALARM REPEATER PANEL
AutoCAD SHX Text
2
AutoCAD SHX Text
CIRCUITS SHARED CAN BE MORE THAN TWO THROUGHOUT CHECKPOINT BUT ONLY CAN INSTALL TWO PER DUPLEX
AutoCAD SHX Text
E-GATE/BATT
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
PASSENGER PREP/AVATAR
AutoCAD SHX Text
TBD
AutoCAD SHX Text
TBD
AutoCAD SHX Text
ALL CIRCUITS TO HAVE 20 AMP SERVICE WITH EXCEPTION TO IT CABINET AND ASL SERVER CABINET WHICH SHALL HAVE 30 AMP SERVICE
AutoCAD SHX Text
DEVICE LOCATIONS ARE SUBJECT TO CHANGE AND SHOULD BE VERIFIED PRIOR TO INSTALL
AutoCAD SHX Text
ALL ASL LANE INSTALLATIONS SHALL INCLUDE TSA HQ IT IN PLANNING AND INSTALLATION
AutoCAD SHX Text
THE IT CABINET SHALL BE A STANDARD DESIGNED 26U TYPE WALL OR FLOOR MOUNT RACK ENCLOSURE, RECOMMENDED DEPTH OF 32"
AutoCAD SHX Text
AIT
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SINGLE LANE WALL (D)
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
ETD1
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
REAR XRAY ASL SUPPLY OUTLET (B)
AutoCAD SHX Text
AIT
AutoCAD SHX Text
AT XRAY
AutoCAD SHX Text
CO-LOCATED ETD
AutoCAD SHX Text
AT 1
AutoCAD SHX Text
AT 2
AutoCAD SHX Text
AVS1/AT 1
AutoCAD SHX Text
AVS1/AT 2
AutoCAD SHX Text
AIT 1
AutoCAD SHX Text
AIT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
ASL SUPPLY 2
AutoCAD SHX Text
ASL SUPPLY 1
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
WTMD 1
AutoCAD SHX Text
FRONT XRAY OUTLET (A)
AutoCAD SHX Text
WTMD 2
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
DEDICATED WTMD ONLY
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
CT SCANNER
AutoCAD SHX Text
DEDICATED DEVICE TBD
AutoCAD SHX Text
208/240 1PHASE UP TO 50 AMP
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
BLANK/EXPANDABLE OR ALTERNATE LOCATION FOR
AutoCAD SHX Text
ASL SERVER 1
AutoCAD SHX Text
ASL SERVER 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
AVS1/AT 3
AutoCAD SHX Text
AVS/ETD/BLS/AVS/AVS (C)
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
ETD 1
AutoCAD SHX Text
ETD 2
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
BLS 1
AutoCAD SHX Text
BLS 2
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
ETD/BLS/AVS TO POWER STRIP
AutoCAD SHX Text
DEDICATED POWER STRIP ONLY
AutoCAD SHX Text
AVS/AT 1
AutoCAD SHX Text
AVS/AT 2
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
FUTURE E-GATE/BAT (K)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
FUTURE PASSENGER PREP/AVATAR (L)
AutoCAD SHX Text
DEDICATED MAX GATES PER TBD
AutoCAD SHX Text
IT CAB 1
AutoCAD SHX Text
IT CAB 2
AutoCAD SHX Text
E-GATE
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
AUDIO SPKR
AutoCAD SHX Text
ASL SEMS SERVER - CENTRALIZED (N)
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 1
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
CP 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
DATA FROM ALL CHECKPOINTS, 2X SINGLE MODE FIBER OPTIC OR 2X CAT 6A, FROM EACH CHECKPOINT SERVED
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
CP 3
AutoCAD SHX Text
TDC/CAT & STSO PODIUM (G)
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
TDC1 A
AutoCAD SHX Text
TDC1 B
AutoCAD SHX Text
TDC2 B
AutoCAD SHX Text
TDC2 A
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
DEDICATED
AutoCAD SHX Text
PRIVATE SCREENING ROOM (E)
AutoCAD SHX Text
PSR 1
AutoCAD SHX Text
PSR 2
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
BLANK
AutoCAD SHX Text
PRIVATE SCREENING ROOM
AutoCAD SHX Text
DUPLEX DEDICATED FOR PSR ONLY
AutoCAD SHX Text
REPEATER
AutoCAD SHX Text
DURESS ALARM & CHRONOS CLOCK (F)
AutoCAD SHX Text
DEDICATED REPEATER ONLY
AutoCAD SHX Text
POTS
AutoCAD SHX Text
PHONE LINE
AutoCAD SHX Text
DEDICATED RECEIVER ONLY
AutoCAD SHX Text
RECEIVER
AutoCAD SHX Text
CHRONOS CLOCK
AutoCAD SHX Text
DATA LINES
AutoCAD SHX Text
ASL IT ROOM SEMS COLLOCATED SERVER OR MANAGED SWITCH FOR CENTRAL SERVER-- (M)
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 1
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
LANE 2
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS SERVER
AutoCAD SHX Text
2 DATA CABELS FROM EACH LANE SERVERD
AutoCAD SHX Text
SEMS ROUTER
AutoCAD SHX Text
ASL SUPERVSR
AutoCAD SHX Text
I/O RM
AutoCAD SHX Text
DEDICATED SERVER ONLY
AutoCAD SHX Text
SEMS REDUNDANT SERVER
AutoCAD SHX Text
SPARE SEMS
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
TSA IT CAB
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
LANE 3
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
CENTRAL SEMS SERVER
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DEVICES -RAPISCAN SYSTEMS
AutoCAD SHX Text
SHEET 20
AutoCAD SHX Text
FOR CENTRAL SEMS SERVER SOLUTION CAT6 OR SINGLE MODE FIBER
AutoCAD SHX Text
NOTE: 1. UP TO 6 208/220V 30A CIRCUITS PER BACK UP TO 6 208/220V 30A CIRCUITS PER BACK TO BACK LANE SETS. POWER SUPPLY CONDUIT SHOULD BE INSTALLED FOR FUTURE EQUIPMENT DEPLOYMENTS. 2. POWER SUPPLY WILL BE AN ISSUE WHEN POWER SUPPLY WILL BE AN ISSUE WHEN ADDING APPROXIMATELY 100AMPS PER LANE. POWER SUPPLY IN THE VICINITY OF THE CHECKPOINT SHOULD BE VERIFIED AND REQUIRED UPGRADES PLANNED. THIS INCLUDES BUT NOT LIMITED TO ADDITIONAL ROOM FOR TRANSFORMERS, DISTRIBUTION PANELS AND UPGRADES TO FACILITY ELECTRICAL SERVICE. 3. VERIFY OUTLET DEVICE TYPE FOR DEDICATED VERIFY OUTLET DEVICE TYPE FOR DEDICATED CIRCUITS WITH OEM VENDOR, TYP.
Page 22: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

606060

72

72

72

72

72

606060

60

60

48

AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
ASL SERVERS
AutoCAD SHX Text
3
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- RS - COLLOCATED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 21
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 23: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

606060

72

72

72

72

72

606060

60

60

48

AutoCAD SHX Text
ASL SEMS CLIENT PC
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
3 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
4 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
8 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC
AutoCAD SHX Text
2 x CAT 6 OR 2 x SINGLE MODE FIBER OPTIC RUN TO EACH CONNECTED CHECKPOINT
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
6 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
2 x CAT 6
AutoCAD SHX Text
REVISED 10/27/1710/27/17
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
R
AutoCAD SHX Text
L
AutoCAD SHX Text
L3
AutoCAD SHX Text
AIT
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
TCOP
AutoCAD SHX Text
L
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ETD
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
TDC/CAT
AutoCAD SHX Text
STSO
AutoCAD SHX Text
IT
AutoCAD SHX Text
RACK
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
6040aTiX
AutoCAD SHX Text
HEIMANN
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
3
AutoCAD SHX Text
ETD
AutoCAD SHX Text
ETD
AutoCAD SHX Text
2
AutoCAD SHX Text
R
AutoCAD SHX Text
ADA GATE
AutoCAD SHX Text
WTMD CEIA
AutoCAD SHX Text
X-RAY
AutoCAD SHX Text
620DV AT1
AutoCAD SHX Text
RAPISCAN
AutoCAD SHX Text
L3 PROVISION2 AIT2
AutoCAD SHX Text
ENTER
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
ETD
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
ASL CENT. SERVERS
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
ASL SEMS SERVER AND REDUNDANT SERVER OUTLETS (N)
AutoCAD SHX Text
ASL MANAGED SWITCH
AutoCAD SHX Text
STANDARD POWER/DATA LAYOUT FOR AUTOMATED SCREENING LANES
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
NOTES: 1. EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET EQUIPMENT SHOWN REPRESENTS TWO DIFFERENT X-RAY MANUFACTURERS FOR EXAMPLE OF OUTLET PLACEMENT, EACH CHECKPOINT TYPICALLY INCLUDES ONLY ONE MANUFACTURER. 2. EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH EACH EQUIPMENT LOCATION SHALL UTILIZE EITHER FLOOR OUTLETS OR POWER POLES, BUT NOT BOTH TYPES OF POWER/DATA DEVICES (SELECTION DEPENDS ON AIRPORT BUILDING CONSTRUCTION.) 3. IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT IT IS RECOMMENDED THAT THE PRIVATE SCREENING ROOM, IT ROOM, AND THE STSO PODIUM BE BUILT INTO THE SPACE OF THE AIRPORT. 4. POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE POWER/DATA DEVICES SHOWN ARE REPRESENTATIVE OF THE TYPICAL OUTLETS REQUIRED, REFER TO THE CHECKPOINT DESIGN GUIDE FOR ALTERNATIVE TYPES OF POWER/DATA DEVICES (POWER POLES, MODULAR BOXES, ETC.) 5. "ASL" REFERS TO AUTOMATED SCREENING LANES. "ASL" REFERS TO AUTOMATED SCREENING LANES. 6. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. ON SCREEN RESOLUTION, I/O, ROOM TO HAVE 1.4 WORK STATIONS PER LANE ROUNDED UP. 7. ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL ASL SEMS SERVER TO BE LOCATED IN THE TSA IT ROOM. PROVIDE 2 CAT 6 DATA CABLES FROM ASL SEMS SERVER TO THE TSA IT CABINET FOR FUTURE USE. 8. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. PROVIDE GENERAL CONVENIENCE OUTLETS IN THE BEGINNING, MIDDLE AND END OF PASSENGER QUEUE. 9. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. LOCATION OF THE E-GATE TURNSTILES WILL BE AT BEGINNING OF THE PASSENGER QUEUE. 10. AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS AUTOMATIC WAIT TIME INFRASTRUCTURE SHALL BE INSTALLED BASED ON THE OEM REQUIREMENTS AS SELECTED BY THE AIRPORT AUTHORITY.
AutoCAD SHX Text
TSA CHECKPOINT DATA TYPOLOGY- RS - CENTRALIZED SERVER
AutoCAD SHX Text
SPECIAL SCOPE NOTE: PLEASE NOTE THAN ANY COSTS ASSOCIATED WITH THE PLANNING, DESIGN AND/OR OTHER ASPECTS OF THIS PROJECT ARE THE SOLE RESPONSIBILITY OF THE AIRPORT AND/OR AIRLINE AND TSA WILL NOT BE LIABLE FOR ANY COSTS OR REIMBURSEMENT FOR ANY ASPECT OF THE PROJECT.
AutoCAD SHX Text
SHEET 22
AutoCAD SHX Text
SPECIAL IT NOTE: ALL IT ROOMS, I/O ROOMS AND PRIVATE SCREENING ROOMS ARE NON-LEASED SPACE. ALL IT ROOMS NEED TO BE CLEARED THROUGH LOCAL/TSA HQ IT AND TSA HQ OFFICE OF REAL ESTATE FOR AWARENESS. THE LOCAL TSA IS RESPONSIBLE TO MAKE ALL NOTIFICATIONS.
Page 24: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

ASL CHECKPOINT DATA CABLING REQUIREMENTS - MACDONALD HUMFREY, SMITHS DETECTION, RAPISCANCABLE REQUIREMENTS CABLE DESTINATION NOTES

OUTLET

FRONT X-RAY OUTLET - A

4 X CAT6 TSA IT RACK

REAR X-RAY OUTLET - B

8 X CAT6 TSA IT RACK

2 X CAT6 ASL SEMS SERVER - M

3 X CAT6 AVS/ETD/BLS/AVS/AVS - C

AVS/ETD/BLS/AVS/AVS - C

6 X CAT6 TSA IT RACK

3 X CAT6 REAR X-RAY OUTLET - B PER LANE SERVED

SINGLE LANE WALL - D

4 X CAT6 TSA IT RACK

PRIVATE SCREENING ROOM - E

2 X CAT6 TSA IT RACK 2 OUTLETS PER SCREENING ROOM

DURESS ALARM AND CHRONOS CLOCK - F

2 X CAT6 TSA IT RACK

TDC/CAT AND STSO PODIUM - G

4 X CAT6 TSA IT RACK

ASL IT ROOM SEMS SERVER - M (ALSO AS ASL MANAGED SWITCH FOR CENTRALIZED SERVER SOLUTION)

2 X CAT6 TSA IT RACK

2 X CAT6 I/O ROOM - J

2 X CAT6 ASL SUPERVISOR CONTROL LOCATION - H

2 X CAT6 PER EACH REAR X-RAY ASL SUPPLY OUTLET - B

ADDITIONAL REQUIREMENTS FOR CENTRALIZED ASL SEMS SERVER

2 X CAT6PER EACH CHECKPOINT ASL MANAGED SWITCH TO CENTRALIZED SEMS SERVER

MAX CABLE RUN 275 FEET

2 X SINGLE MODE FIBER OPTIC CABLE RUNS OVER 275 FEET

ASL SUPERVISOR CONTROL LOCATION - H

2 X CAT6 TSA IT RACK

2 X CAT6 ASL SEMS SERVER - M

I/O ROOM - J

2 X CAT6 ASL SEMS SERVER - M

FUTURE E-GATE/BAT - K

2 X CAT6 TSA IT RACK AIRPORT OR AIRLINE SUPPLIED

FUTURE PASSENGER PREP/AVATAR - L

2 X CAT6 TSA IT RACK AIRPORT OR AIRLINE SUPPLIED

2 X AUDIO CABLE LOCATION OF HEAD END TBD AIRPORT OR AIRLINE SUPPLIED

ASL IT ROOM SEMS SERVER - M (CENTRALIZED SERVER SOLUTION ONLY)

2 X CAT6PER EACH CHECKPOINT ASL MANAGED SWITCH

MAX CABLE RUN 275 FEET

2 X SINGLE MODE FIBER OPTIC CABLE RUNS OVER 275 FEET

AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DESIGN-DATA CABLE REQ. - MACDONALD HUMFREY, SMITHS DETECTION, RAPISCAN SYSTEMS
AutoCAD SHX Text
SHEET 23
Page 25: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

ASL CHECKPOINT DATA CABLING REQUIREMENTS - VANDERLANDE, SCARABEECABLE REQUIREMENTS CABLE DESTINATION NOTES

OUTLET

FRONT X-RAY OUTLET - A

4 X CAT6 TSA IT RACK

REAR X-RAY OUTLET - B

8 X CAT6 TSA IT RACK

2 X CAT6 ASL SEMS SERVER - M

3 X CAT6 AVS/ETD/BLS/AVS/AVS - C

3 X VGA CABLE AVS/ETD/BLS/AVS/AVS - C

AVS/ETD/BLS/AVS/AVS - C

6 X CAT6 TSA IT RACK

3 X CAT6 REAR X-RAY OUTLET - B PER LANE SERVED

3 X VGA CABLE REAR X-RAY OUTLET - B PER LANE SERVED

SINGLE LANE WALL - D

4 X CAT6 TSA IT RACK

PRIVATE SCREENING ROOM - E

2 X CAT6 TSA IT RACK 2 OUTLETS PER SCREENING ROOM

DURESS ALARM AND CHRONOS CLOCK - F

2 X CAT6 TSA IT RACK

TDC/CAT AND STSO PODIUM - G

4 X CAT6 TSA IT RACK

ASL IT ROOM SEMS SERVER - M (ALSO AS ASL MANAGED SWITCH FOR CENTRALIZED SERVER SOLUTION)

2 X CAT6 TSA IT RACK

2 X CAT6 I/O ROOM - J

2 X CAT6 ASL SUPERVISOR CONTROL LOCATION - H

2 X CAT6 PER EACH REAR X-RAY ASL SUPPLY OUTLET - B

ADDITIONAL REQUIREMENTS FOR CENTRALIZED ASL SEMS SERVER

2 X CAT6PER EACH CHECKPOINT ASL MANAGED SWITCH TO CENTRALIZED SEMS SERVER

MAX CABLE RUN 275 FEET

2 X SINGLE MODE FIBER OPTIC CABLE RUNS OVER 275 FEET

ASL SUPERVISOR CONTROL LOCATION - H

2 X CAT6 TSA IT RACK

2 X CAT6 ASL SEMS SERVER - M

I/O ROOM - J

2 X CAT6 ASL SEMS SERVER - M

FUTURE E-GATE/BAT - K

2 X CAT6 TSA IT RACK AIRPORT OR AIRLINE SUPPLIED

FUTURE PASSENGER PREP/AVATAR - L

2 X CAT6 TSA IT RACK AIRPORT OR AIRLINE SUPPLIED

2 X AUDIO CABLE LOCATION OF HEAD END TBD AIRPORT OR AIRLINE SUPPLIED

ASL IT ROOM SEMS SERVER - M (CENTRALIZED SERVER SOLUTION ONLY)

2 X CAT6PER EACH CHECKPOINT ASL MANAGED SWITCH

MAX CABLE RUN 275 FEET

2 X SINGLE MODE FIBER OPTIC CABLE RUNS OVER 275 FEET

AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DESIGN-DATA CABLE REQ. - VANDERLANDE SCARABEE
AutoCAD SHX Text
SHEET 24
Page 26: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

• SEMS Server is to be located in a TSA IT Room or a shared Comm. room with the airport in a locked cabinet that shall provided

by ASL vendor. If neither are available TSA HQ IT and TSA HQ Checkpoint design agreed space.

• SEMS Client PC to be located in a TSA Office at the respective checkpoint. Alternate location is at the TSA STSO podium in an

approved securable computer cabinet.

• Project Sponsor provided managed switch must be located in a secure location in the checkpoint.

• Fiber optic to be single mode.

• All cable runs to be 100% redundant.

• The fiber infrastructure from the nearest communication room adjacent to each SSCP to the TSA CMF in each terminal will be

provided by the airport/airlines at its sole cost and expense. The fiber will be dedicated for TSA use for as long as needed and

any maintenance, repair or replacement will be the sole responsibility of the airport/airline. There shall be no cost to TSA for its

use of the above referenced fiber infrastructure and its components. This will be a “closed network” at the airport for the TSA

ASL only.

• TSA Approved Network switches:

Cisco C3560CX-12PC

• 12 Gigabit Ethernet ports

• 2 x 1 GE copper uplinks

• 2 x 1 GE SFP uplinks

• IP base (IP services with RTU license)

• PoE+ support with up to 240 W of PoE budget

Cisco 3850-12S-S

• 12 x Gigabit Gigabit Ethernet SFP

• Port transmission speed, port duplex mode, system, status, PoE

• IPv4 routes

Cisco WS-C3850-48P

Cisco WS-C3850-24S

AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DESIGN-NETWORK REQUIREMENTS
AutoCAD SHX Text
SHEET 25
Page 27: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical

VISTA COLUMN DETAIL

1

AutoCAD SHX Text
36" VISTA COLUMN
AutoCAD SHX Text
EXISTING FLOOR COVERING
AutoCAD SHX Text
POWER
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
DATA
AutoCAD SHX Text
SCALE: NOT TO SCALE
AutoCAD SHX Text
CORE DRILL THROUGH FLOOR FOR 1" EMT AS RECOMMENDED BY MANUFACTURER. PROVIDE FIRE RATED SEALANT
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DESIGN-STANCHION
AutoCAD SHX Text
SHEET 26
Page 28: 3ASL ELECTRICAL LAYOUT MACDONALD HUMFREY 4ASL ELECTRICAL ... · sheet index 1at electrical layout and devices 2at data layout 3asl electrical layout macdonald humfrey 4asl electrical
AutoCAD SHX Text
AT
AutoCAD SHX Text
5-20R SPLIT WIRED DUPLEX
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
INFEED CONV.
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
W
AutoCAD SHX Text
G
AutoCAD SHX Text
DATA CABLE PATH W/GROMMET
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
AIT
AutoCAD SHX Text
DATA CABLE PATH W/GROMMET
AutoCAD SHX Text
AT
AutoCAD SHX Text
5-20R SPLIT WIRED DUPLEX
AutoCAD SHX Text
AIT
AutoCAD SHX Text
INFEED CONV.
AutoCAD SHX Text
L5-15R SIMPLEX
AutoCAD SHX Text
WTMD
AutoCAD SHX Text
W
AutoCAD SHX Text
G
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
CAT 6 DATA PORT
AutoCAD SHX Text
U.S DEPARTMENT OF HOMELAND SECURITY
AutoCAD SHX Text
D:\TEDS\!CDG\Electrical Diagram.dwg
AutoCAD SHX Text
601 SOUTH 12TH STREET, ARLINGTON, VA 22202
AutoCAD SHX Text
REVISION 16 - ISSUED OCTOBER 25, 2017
AutoCAD SHX Text
TSA CHECKPOINT ELECTRICAL DESIGN-SURFACE MOUNT
AutoCAD SHX Text
SPECIAL NOTE: SURFACE MOUNTING OF ELECTRICAL CONDUIT IS TO BE USED ONLY WERE RELOCATING FLOOR PENETRATIONS IS NOT FEASIBLE YET REQUIRED DUE TO THE LOCATIONS OF TSE. CONDUIT AND SURFACE MOUNTED DEVICES ARE TO BE COMPLETELY UNDER THE EQUIPMENT AND NOT EXPOSED TO FOOT TRAFFIC.
AutoCAD SHX Text
EXAMPLE DEVICE
AutoCAD SHX Text
SHEET 27