3b es gcs applications 1__ menu system12-4
TRANSCRIPT
C en tr ilift
1Centrilift
The GCS Menu systemThe GCS Menu system
GCSModules
AnalogSetup &Display
SCADA &Security
& System
CustomUser
Screen
ProgLogicFunct
Faults&
Undld
Datalog&
History
GCSDriveSetup
StatusAnalog Setup
Screens used to calibrateand display measured analog
signals including Volts andAmps
GCS ModulesScreens used to enable,calibrate or scale built-ininputs, outputs & optional
external I/O modulesincluding Tracker
GCS Drive SetupMenu group contains most ofthe parameters that need tobe set and maintained for a
basic VSC installation
Datalog & HistorySection provides screens toaccess the historical data
and graphs that are recordedwithin the GCS controller
Faults & UnderloadMenus used to enable ordisable & adjust timing of
most conditions that causemotor shutdowns
SCADA, Security& System
Menus to enable securitypasswords, set real-timeclock & adjust telemetry
parameters
ProgrammableLogic FunctionsMenus used to access
standard control algorithmsand create customized
functions based on availableinputs and outputs
Custom UserScreen
Provides access tocustomized user display
screens
C en tr ilift
2Centrilift
GCS DRIVE SETUPGCS DRIVE SETUP
• The Contrast Adjust screen is accessed by pressing the left and right arrows at the same time.
C en tr ilift
3Centrilift
GCS DRIVE SETUPGCS DRIVE SETUP
• The Utility menu screen is accessed by pressing the up and down arrows at the same time.
Utility Menu
Set Frequency , 310
Add to Custom User 01Screen Capture 00Rename this Parameter
Replaces one of the two STATUSmenu parameters with the parameterabove
Add parm to status 01
C en tr ilift
4Centrilift
GCS DRIVE SETUPGCS DRIVE SETUP
• This screen allows you to rename any parameter
C en tr ilift
5Centrilift
GCS DRIVE SETUPGCS DRIVE SETUP
• The GCS Setup menus provide access to most of the parameters that need adjustment during routine setup and maintenance
C en tr ilift
6Centrilift
GCS DRIVE SETUP 1GCS DRIVE SETUP 1
GCS Setup 1• Most of the
application specific setpoints are found within these menus
• Factory default values based on drive model number
C en tr ilift
7Centrilift
GCS DRIVE SETUP 2GCS DRIVE SETUP 2
GCS Setup 2• Second setup
screen is accessed by the left or right arrow keys from GCS setup 1
C en tr ilift
8Centrilift
GCS DRIVE SETUP 2GCS DRIVE SETUP 2
GCS Setup 2• Scroll down when
more parameters than can be shown at one time.• User password
setpoint located here
C en tr ilift
9Centrilift
GCS DRIVE SETUP 2GCS DRIVE SETUP 2
GCS Setup 2• Frequency
Avoidance Submenu
• Any frequencies entered are active
C en tr ilift
10Centrilift
GCS DRIVE SETUP 3GCS DRIVE SETUP 3
GCS Setup 3• Torque Control
Setup Parameters• Only visible with
PCM8.xx and higher• Nameplate current &
Magnetizing current must be set
C en tr ilift
11Centrilift
GCS DRIVE SETUP 3GCS DRIVE SETUP 3
30 % of Nameplate30 % of Nameplate
Ft-Lbs= HP X 5252 3500
For ESP and ESPCP Motors
C en tr ilift
12Centrilift
GCS DRIVE SETUPGCS DRIVE SETUP
STARTS• Fourth screen of
GCS Drive Setup menu group
• Automatic restart parameters and time delays
C en tr ilift
13Centrilift
Datalog and History
• Accesses the recorded history stored within the GCS controller
• Includes screens for SHUTDOWN , RUNNING, EVENT HISTORY AND GRAPHING
C en tr ilift
14Centrilift
Datalog and History
Shutdown History• Records the
cause, date and time of last 99 shutdowns.
C en tr ilift
15Centrilift
Datalog and History
Shutdown Detail• Records a
“snapshot” of the volt, amp and analog measurements at shutdown
C en tr ilift
16Centrilift
Datalog and History
EVENT RECORDS
• Records all “events” that occur
• Events include: Start UpsSetpoint ChangesShutdowns
C en tr ilift
17Centrilift
Datalog and HistoryBFC BIT FIELD CHANGE (ONE BIT OF A STATUS WORD)
CFN CHANGE FROM NORMAL (POTENTIAL FAULT)
CNL CITIBUS NODE LOSS (SERIAL COMMUNICATION FAILURE)
CNR CITIBUS NODE RECOVERY (SERIAL COMMUNICATION RESTARTED)
EXC EXPONENT CHANGE
FDC FACTOR DEFAULT CHANGE (CHANGE OF INITIAL FACTORY SETTING)
IPL INITIAL PROGRAM LOAD (POWER UP)
MNC MINIMUM CHANGE
MXC MAXIMUM CHANGE
C en tr ilift
18Centrilift
Datalog and HistoryRTC REAL TIME CLOCK CHANGE
RTN RETURN TO NORMAL
SDE SHUT DOWN EVENT (STOP)
SPC SETPOINT CHANGE
SPR SETPOINT RELOAD (POWER UP)
SUE START UP EVENT
UNC UNITS CHANGE
UNE UNKNOWN ERROR
C en tr ilift
19Centrilift
Datalog and History
Running History• Accumulates
and records runtime statistics
C en tr ilift
20Centrilift
Datalog and History
Datalogging Setup
• Enables / Disables logging data to PC Card
• Entry to data log configuration screens
C en tr ilift
21Centrilift
Datalog and History
Graphing• GCS controller records
motor current for seven day period
• Minimum, Maximum and average current recorded every 1 min.
• Stored every week on memory card
C en tr ilift
22Centrilift
Datalog and History
Graphing• Graph time from 3hr
to 1 week• Choice of Graph
End, Graph Beginning, or Crsr for reference
C en tr ilift
23Centrilift
Datalog and HistoryPhase B amp
chart24 hrB Ampchart
0
80
Strt00/02/01
Crsr00/02/01
Min: 40Max: 45
][...................................................
C en tr ilift
24Centrilift
Datalog and History
Graphing (VORTEX GCS ONLY)
• Vortex GCS records 3 current and voltages at 600 samples/sec. for two seconds after startup
C en tr ilift
25Centrilift
Faults and AlarmsFaults and Alarms
• Access to system protection setpoints, thresholds and time delays
• Contents of menus vary depending on type of GCS controller
C en tr ilift
26Centrilift
Faults and AlarmsFaults and Alarms
Overload• Setpoint represents
the maximum amount of current allowed
• Highest amps is the maximum current on any phase
C en tr ilift
27Centrilift
Faults and AlarmsFaults and Alarms
1.5 2 2.5 3 3.5 40
1
2
3
4
P.U
. Tim
e
P.U. Current
Overload Trip Characteristics
C en tr ilift
28Centrilift
Faults and AlarmsFaults and Alarms
Aux Restart Parms• Use Instead of Global
Settings• Number of Restarts• Restart Delay
C en tr ilift
29Centrilift
Faults and AlarmsFaults and Alarms
Underload• Setpoint
represents the least amount of current allowed
C en tr ilift
30Centrilift
Faults and AlarmsFaults and Alarms
Input Over Voltage• Monitors maximum input
voltage• Customer scaleable input
voltages
C en tr ilift
31Centrilift
Faults and AlarmsFaults and Alarms
Input Under Voltage• Monitors minimum input
voltage• Customer scaleable input
voltages
C en tr ilift
32Centrilift
Faults and AlarmsFaults and Alarms
Input Voltage Unbal.• Monitors input voltage for
unbalance• Setpoint 0-100%
C en tr ilift
33Centrilift
Faults and AlarmsFaults and Alarms
Low Speed Trip• Protects against
operating the motor & pumping system below a safe running frequency
C en tr ilift
34Centrilift
Faults and AlarmsFaults and Alarms
Temperature Sensors
• The GCS Electrospeed has seven sensor inputs
• Shutdown thresholds are all factory set, except “auxiliary”
C en tr ilift
35Centrilift
Faults and AlarmsFaults and Alarms
Temperature Sensors• The auxiliary sensor
input can be used to measure the temperature of a users selected location
C en tr ilift
36Centrilift
Faults and AlarmsFaults and Alarms
Telemetry Fail• When enabled,
monitors loss of serial communication
C en tr ilift
37Centrilift
Faults and Alarms and Alarms
Alarm Setup• Provides a
convenient way to determine which alarms are enabled
• Use individual alarm screens to edit other parameters
C en tr ilift
38Centrilift
Programmable Logic Functions
• This menu group provides access to any available programmable functions
C en tr ilift
39Centrilift
Programmable Logic Functions
Programmable Function Setup
• Two programmable functions are included in basic drive
C en tr ilift
40Centrilift
Programmable Logic Functions
PID controller setup
• Proportional-Integral-Derivative closed loop control is a commonly used industrial algorithm
C en tr ilift
41Centrilift
Custom User Screen
Customer enters up to eleven parameters of particular interest
C en tr ilift
42Centrilift
Custom User Screen
Example of Custom User Screen
C en tr ilift
43Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
• Provides access to a variety of system maintenance, security, communications and time keeping functions
C en tr ilift
44Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
System• Reset setpoints &
prepares controller for re-deployment
• Some setpoints are not accessible in the field
C en tr ilift
45Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
SCADA Setup• This menu
screen allows the user to adjust the parameters controlling serial communications
C en tr ilift
46Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
Serial Com Diagnostic Screen• Receive Buffer• Transmit Buffer• Com stats
C en tr ilift
47Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
Provisions for three levels of password protection and security time out setting
C en tr ilift
48Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
Level 1: Start Stop Set Frequency Data Logging En. Resetable Run Time
Level 2:
Most Others
Code Enable:
Reset History Database
RTClock Alarm Enable
Security Level Access
C en tr ilift
49Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
Current Time• Menu displays the
present value of the onboard, real time, battery backed clock
C en tr ilift
50Centrilift
SCADA & SECURITY & SCADA & SECURITY & SYSTEMSYSTEM
Set Time• This screen is
used to edit and correct the setting of the real time clock
C en tr ilift
51Centrilift
Analog Setup & DisplayAnalog Setup & Display
• Access to the parameters related to the default analog measurements:
CurrentVoltagePower Factor
C en tr ilift
52Centrilift
Analog Setup & DisplayAnalog Setup & Display
Analog Setup• Electrospeed GCS is
factory calibrated for finite model ranges
• Vortex GCS allows the flexibility to accommodate a wide variety of load sizes
C en tr ilift
53Centrilift
GCS ModulesGCS Modules
• Access to calibration and setup of built-in general purpose analog & digital i/o
• Expansion modules are calibrated via these menus
C en tr ilift
54Centrilift
GCS ModulesGCS Modules• Onboard I/O is
built-in general purpose analog and digital inputs
• Expansion I/O cards will provide a simple method to expand any system
C en tr ilift
55Centrilift
GCS ModulesGCS Modules
• Status screen shows all detected slaves on CITIBus
C en tr ilift
56Centrilift
GCS ModulesGCS Modules
• Trident status screen if present
C en tr ilift
57Centrilift
GCS ModulesGCS Modules
Onboard I/O• Electrospeed and
Vortex GCS both provide two general purpose analog input channels
C en tr ilift
58Centrilift
GCS ModulesGCS Modules
Hi Threshold Setup• Similar to Fault Setup• Aux Restart Params
available
C en tr ilift
59Centrilift
GCS ModulesGCS Modules
Lo Threshold Setup• Similar to Fault Setup• Aux Restart Params
available
C en tr ilift
60Centrilift
GCS ModulesGCS Modules
Onboard I/O• Electrospeed GCS
has three general purpose digital (status) inputs
• Vortex GCS has two status inputs