    TECHNICALSPECIFICATION455

    STREETLIGHTINGSYSTEMS PAGE1of6

    Rev.5/10

    TECHNICALSPECIFICATION455

    STREETLIGHTINGSYSTEMS

    455.1 SCOPEOFWORK

    This technical specification covers the furnishing of all labor, materials, testing, submittals,

    tools,andequipmentnecessary to install lightdistribution fixtures,poles,meteredcontroller,

    concretebases,wiring,andconduitof thetypeherein identified,completeand inplaceatthe

    locationsandtothedimensionsanddetailsshownontheplansorasdirectedbytheEngineer.

    This work includes miscellaneous items necessary for a complete installation including

    excavation,backfilling,warningtapes,siterestoration,etc. Italsoincludesthecoordinationand

    costsassociatedwithpublicutilitywork. This technical specification coversbothdecorative

    andcommerciallightingsystems. ItistheintentionoftheTowntohaveconsistencyamongthe

    typesof

    fixtures

    maintained

    by

    the

    community.

    455.2 MATERIALS

    A. DecorativeStreetLightSystems

    1. Fixtures

    The mainframe assembly shall consist of cast aluminum upper and lower cage frames

    weldedsecurelyto4slottedextrudedaluminumcagelegstoformaonepieceassemblyand

    secured internally to aballast housing with four (4) 20 screws. (Product equivalent

    HanoverLantern,Inc.DrawingNo.L49561).

    2. Lenses

    Thelensesshallbeofa0.125inchthickclearpolycarbonate.

    3. Ballasts

    Theballasthousingshallbemadeofcastaluminumwithaminimumwallthicknessof3/16

    inches. The access door must have double concealed hinges and be secured by a

    tamperproofstainlesssteelscrew. Theballastshallbe150watthighpressuresodium. Itshallbemountedonaslidetraywhichisequippedwithaquickdisconnectdeviceandcan

    beremovedwithouttheuseoftools. Ballastshallbewiredfor120volts.

  • 8/10/2019 455 Street Lighting Systems

    2/6

    TECHNICALSPECIFICATION455

    STREETLIGHTINGSYSTEMS PAGE2of6

    4. LightDistributionandElectricalRequirements

    Thefixtureshallbewiredforamaximumwattageof150highpressuresodiumlamptypeS

    55mogulbasewith a topmountedType IIIdistribution reflector (highpressure sodium

    lampshallbeprovided). A#743/4frostedglasschimneyshallbeplacedinthefixturesbase

    fordecorativepurposes.

    5. Poles

    Thepolesprovidedshallconsistofonepieceextrudedaluminumcastingsconstructedwith

    aminimumwallthicknessof0.125inches. Poleshallbe120. Thealuminumpostshall

    bewelded to an anchorbasewith fourboltopenings. A large conduitopening shallbe

    provided as well as a wiring access door. The access door shallbe secured with four

    stainlesssteelscrews. Thepolesshallbeprovidedwithfour(4)5/8inchdiameterby18inch

    longanchorboltstobeembeddedaminimumof16inchesintotheconcretebase. Allbolts

    andscrews

    to

    have

    anti

    seize

    applied

    to

    threads.

    (Product

    equivalent

    Hanover

    Lantern,

    Inc.

    DrawingNo.316 7Thru18).

    6. ExteriorFinish

    Allfixturesandpolesshallbecleanedandrinsedinahotdipcleaningsolventorequivalent

    to removeallgrease,dirtandblemishesbeforepainting. Thepolesand fixtures shallbe

    factorypaintedsatinblack.

    7. LightPoleBases

    The lightpolebase(s) shallbeaminimumof4,000PSIprecast concreteas shownon the

    Town of Windsor Standard Details and shall include PVC conduit, pole fasteners and

    groundconduit. Thetopofthebaseshallbe15inchessquareandtapertoaminimumof20

    inchessquareatthebottom. Thedepthshallbe48inches.

    8. MeteredStreetlightController

    Theelectricserviceshallbe100amp.,I phase,3wire,120V/240V. Thecontrollerassembly

    shallincludethefollowing:

    1EA MeterSocket

    1EA MainCircuitBreaker, 100amp,2pole,GeneralElectricMoldedCaseModelNo.

    THQL 21100,orapprovedequal

    1EA CircuitBreaker,60amp.,2pole,GeneralElectricMoldedCaseModelNo.THQL

    2160orapprovedequal

    1EA Contactor,electricallyheld,60amp120vcoil,2pole,CutlerHammerModel#C30

    DN2ABorapprovedequal

  • 8/10/2019 455 Street Lighting Systems

    3/6

    TECHNICALSPECIFICATION455

    STREETLIGHTINGSYSTEMS PAGE3of6

    1EA Photocell,cabinetmounted1800watt,120v

    1EA GFCIReceptacle,20amp.,125volt,incontrolpanel

    1EA Incandescentlampholderwithpullchain

    1EA 100amp.mainlugonly,singlephase,12circuitsurfaceloadcenter,GeneralElectric

    TypeTLM1612C,orapprovedequal

    1EA Timer,60minuteswithholdfeature,IntermaticModelNo.FF60MH(servesas on

    andoff testoverrideswitch),orapprovedequal

    Thecontroller shallhaveappropriatecontactors,circuitbreakers,groundingbars,wiring,

    andappurtenancesforproperoperation. An onandoff overridetimershallbeprovided

    fortestingpurposes. Ifthelightsareoffandthetimerisplacedintheonmodethenthe

    lightsshallcomeonandoverridethephotocell. Thecontrollercircuitpanelshallcontaina

    20amp.,125voltGFCIreceptacleandanincandescentlampholderwitha60wattlampand

    apullchain located inanupperquadrantof thepanel. Thecontroller is tobe furnished

    withonelightingcontactorcontrolledbythephotocell.

    9. Cabinet

    ThecabinetshallbeaNEMAstandardsizeMcabinetmadeofinchthickaluminumand

    shallhaveoveralldimensionsof50incheshighby30incheswideby18inchesdeepunless

    otherwise approved by the Engineer. The cabinet finish shall be natural aluminum

    (unpainted). No auxiliary switchpaneldoor shallbeprovided. Themaindoor shallbe

    equippedwithaCorbinNo.15481 tumbler type lock (industry#2 lock)and two (2)keys

    shallbefurnishedtotheTown.

    10.

    ControllerBase

    ThebaseshallconformtothedrawingsasshownontheTownofWindsorStandardDetails.

    ThebaseshallbemadeofClass C concreteandmaybeprecast. Itshall includeone (1)

    dedicated2 inchPVCelectricalgradeconduit sweep for theutilitycompanypower feed,

    one5/8inchby8footcoppergroundrod,aminimumof42inchpolyvinylchloridesweeps

    forwiringtothelightpoles,and23/4by18inchgalvanizedanchorbolts.

    11.ConduitandWiring

    Conduitshallbe2inch,schedule40PVCelectricalgradeconduit. Wiringshallconsistof3

    1/0 THW aluminum wire, and a #6 copper ground unless otherwise approved by the

    Engineer.

  • 8/10/2019 455 Street Lighting Systems

    4/6

    TECHNICALSPECIFICATION455

    STREETLIGHTINGSYSTEMS PAGE4of6

    B. CommercialStreetLightSystems

    The commercial light standards and luminaire shall conform to Form 816, SectionsM15.01

    throughM15.05,withthefollowingexceptions:

    1.

    TheCommercialLuminaireshallbeofaGEtypeM250A2POWR/DOORLuminaireWithCutoffOpticsorapprovedequal.

    2. Mountingheightoflightfixturesshallbe326feetabovegrade.

    3. On commercial lighting systems, contactor number one is to control even numbered

    light poles and contactor number two is to control odd numbered light poles. A

    separate 2 pole, 60 amp circuit breaker, shall power each contactor. The normal

    operationofalllightsistobecontrolledbythephotocell.

    4.

    Cabinetand

    Controller

    Base

    shall

    meet

    the

    above

    requirements

    of

    Section

    455.2.A.9

    and

    455.2.A.10unlessotherwiseapprovedbytheEngineer.

    455.3 SUBMITTALS

    The followingsubmittalsshallbesubmitted to theEngineer forreviewandapprovalprior to

    installation:

    Manufacturer(s)cutsheet(s)onfixtures

    Manufacturer(s)cutsheet(s)onlightpoles

    Manufacturer(s)cutsheet(s)onlightpolebases

    Manufacturer(s)cutsheet(s)oncontrollercabinet

    Manufacturer(s)cutsheet(s)oncontrollerbase

    455.4 CONSTRUCTIONMETHODS

    A. DecorativeStreetLightSystems

    1. Cabinet

    Ainchblackplywoodbackboardshallbemountedontheinsidebackwallofthecabinet

    andshallserveasthemainpanelforthemountingofcontrollercomponents.Thephotocellshallbe installedon theupperportionof thecabinet. Thephotocellshallbemountedso

    thatthecabinetretainsitsweatherproofcharacteristicsaroundthemountingarea. Autility

    company approvedmeter socket shallbemountedon the right sideof the cabinetwhen

    viewed from the front. Adedicated2 inchPVCpipeshallrun from theconcretecabinet

    baseoutsidethecabinettothemetersocketfortheutilitycompanyservicewires.

  • 8/10/2019 455 Street Lighting Systems

    5/6

    TECHNICALSPECIFICATION455

    STREETLIGHTINGSYSTEMS PAGE5of6

    2. LightPoleandControllerBases

    TheContractorshallinstallandlevelthebasesasshownontheplans. Thebasesshallbeset

    on8inchesofcompactedprocessedaggregateonastablepreparedsubgrade.

    3. ConduitandWiring

    Conduitshallbeinstalledaminimumof24inchesbelowgrade. Conduitshallbeconnected

    with approved couplings to the base sleeves incorporated within the light pole bases.

    Electricalwiringwillextendthroughthebasesforconnectiontoeachpole. Theworkshall

    includeallexcavation,backfill,materials, laborandsurfacerestoration, including loaming

    and seeding,and temporaryandpermanentpavement replacement. Where such surface

    restorationisrequired,allworkshallbeperformedinaccordancewiththeTownStandards.

    Warningtapeshallbeinstalledaminimumof1footaboveallelectricalconduit. Standoffs

    shallbeused in accordancewith the servingpublicutility companyor asdirected. The

    Contractorshallalsosupplyandinstallall itemsnecessaryto insureproperfunctioningof

    thelighting

    system,

    including

    photocell(s),

    ground

    wire

    to

    be

    made

    to

    the

    ground

    lug

    in

    the

    polebaseasshownontheelectricaldiagram,inlinefusesandholders,nondelay5amp300

    volt capacity for each pole, and appropriate connectors, miscellaneous wiring and

    appurtenantitems.

    4. MeteredStreetlightController

    All construction methods for this item shall be in accordance with the manufacturers

    constructionmethodsandtheNationalElectricalCode (NEC). Eachstreet lightcontroller

    installationshallbe locatedandmountedasdirectedby theEngineerorasshownon the

    plans.

    B. CommercialStreetLightSystems

    The installationofcommercial street light systems shallconform toForm816,Sections10.03,

    10.04,and10.08. Theinstallationofthecabinetshallconformtotheabove455.4.A.1. Allother

    installationshallconformtoapplicableAASHTO,CTDOT,andNECstandards.

    C. PublicUtilityWork

    Wherepublicutilityworkisrequired,theContractorshallmakearrangementstoensureproper

    coordinationofwork. If required, theContractor shallprovide all excavation,backfillingofserviceconduit,labor,surfacerestorationandanyappurtenantwork,fromthepowersourceto

    theservicemeternecessaryforreceivingelectricalserviceasdescribed. Costofthisworkshall

    beincludedinthelumpsumpriceforthecontroller.

  • 8/10/2019 455 Street Lighting Systems

    6/6

    TECHNICALSPECIFICATION455

    STREETLIGHTINGSYSTEMS PAGE6of6

    455.5 MEASUREMENT

    Measurement for lightpoles, fixtures, controllers andbases,willbebasedon thenumberof

    poles,fixtures,controllers,andbasesofthetypespecified,completedandinplace.

    Measurementforconduitandwiringwillbebasedonthenumberoflinearfeetofconduitandwiringinstalledandcompleted.

    455.6 PAYMENT

    PaymentforthisitemwillbeatthecontractunitpricesperEachfordecorativeandcommercial

    light poles, fixtures, controllers and bases and per Linear Foot for conduit and wiring,

    completedandaccepted inplace includingall labor,materials, testing, submittals, tools,and

    equipmentnecessarytocompletetheworkasspecified.

    PAY

    ITEM

    PAY

    UNIT

    DecorativeLightPoleandBase EA

    CommercialLightPoleandBase EA

    Conduit L.F.

    Wiring L.F.

    ControllerandBase EA