455 street lighting systems
TRANSCRIPT
-
8/10/2019 455 Street Lighting Systems
1/6
TECHNICALSPECIFICATION455
STREETLIGHTINGSYSTEMS PAGE1of6
Rev.5/10
TECHNICALSPECIFICATION455
STREETLIGHTINGSYSTEMS
455.1 SCOPEOFWORK
This technical specification covers the furnishing of all labor, materials, testing, submittals,
tools,andequipmentnecessary to install lightdistribution fixtures,poles,meteredcontroller,
concretebases,wiring,andconduitof thetypeherein identified,completeand inplaceatthe
locationsandtothedimensionsanddetailsshownontheplansorasdirectedbytheEngineer.
This work includes miscellaneous items necessary for a complete installation including
excavation,backfilling,warningtapes,siterestoration,etc. Italsoincludesthecoordinationand
costsassociatedwithpublicutilitywork. This technical specification coversbothdecorative
andcommerciallightingsystems. ItistheintentionoftheTowntohaveconsistencyamongthe
typesof
fixtures
maintained
by
the
community.
455.2 MATERIALS
A. DecorativeStreetLightSystems
1. Fixtures
The mainframe assembly shall consist of cast aluminum upper and lower cage frames
weldedsecurelyto4slottedextrudedaluminumcagelegstoformaonepieceassemblyand
secured internally to aballast housing with four (4) 20 screws. (Product equivalent
HanoverLantern,Inc.DrawingNo.L49561).
2. Lenses
Thelensesshallbeofa0.125inchthickclearpolycarbonate.
3. Ballasts
Theballasthousingshallbemadeofcastaluminumwithaminimumwallthicknessof3/16
inches. The access door must have double concealed hinges and be secured by a
tamperproofstainlesssteelscrew. Theballastshallbe150watthighpressuresodium. Itshallbemountedonaslidetraywhichisequippedwithaquickdisconnectdeviceandcan
beremovedwithouttheuseoftools. Ballastshallbewiredfor120volts.
-
8/10/2019 455 Street Lighting Systems
2/6
TECHNICALSPECIFICATION455
STREETLIGHTINGSYSTEMS PAGE2of6
4. LightDistributionandElectricalRequirements
Thefixtureshallbewiredforamaximumwattageof150highpressuresodiumlamptypeS
55mogulbasewith a topmountedType IIIdistribution reflector (highpressure sodium
lampshallbeprovided). A#743/4frostedglasschimneyshallbeplacedinthefixturesbase
fordecorativepurposes.
5. Poles
Thepolesprovidedshallconsistofonepieceextrudedaluminumcastingsconstructedwith
aminimumwallthicknessof0.125inches. Poleshallbe120. Thealuminumpostshall
bewelded to an anchorbasewith fourboltopenings. A large conduitopening shallbe
provided as well as a wiring access door. The access door shallbe secured with four
stainlesssteelscrews. Thepolesshallbeprovidedwithfour(4)5/8inchdiameterby18inch
longanchorboltstobeembeddedaminimumof16inchesintotheconcretebase. Allbolts
andscrews
to
have
anti
seize
applied
to
threads.
(Product
equivalent
Hanover
Lantern,
Inc.
DrawingNo.316 7Thru18).
6. ExteriorFinish
Allfixturesandpolesshallbecleanedandrinsedinahotdipcleaningsolventorequivalent
to removeallgrease,dirtandblemishesbeforepainting. Thepolesand fixtures shallbe
factorypaintedsatinblack.
7. LightPoleBases
The lightpolebase(s) shallbeaminimumof4,000PSIprecast concreteas shownon the
Town of Windsor Standard Details and shall include PVC conduit, pole fasteners and
groundconduit. Thetopofthebaseshallbe15inchessquareandtapertoaminimumof20
inchessquareatthebottom. Thedepthshallbe48inches.
8. MeteredStreetlightController
Theelectricserviceshallbe100amp.,I phase,3wire,120V/240V. Thecontrollerassembly
shallincludethefollowing:
1EA MeterSocket
1EA MainCircuitBreaker, 100amp,2pole,GeneralElectricMoldedCaseModelNo.
THQL 21100,orapprovedequal
1EA CircuitBreaker,60amp.,2pole,GeneralElectricMoldedCaseModelNo.THQL
2160orapprovedequal
1EA Contactor,electricallyheld,60amp120vcoil,2pole,CutlerHammerModel#C30
DN2ABorapprovedequal
-
8/10/2019 455 Street Lighting Systems
3/6
TECHNICALSPECIFICATION455
STREETLIGHTINGSYSTEMS PAGE3of6
1EA Photocell,cabinetmounted1800watt,120v
1EA GFCIReceptacle,20amp.,125volt,incontrolpanel
1EA Incandescentlampholderwithpullchain
1EA 100amp.mainlugonly,singlephase,12circuitsurfaceloadcenter,GeneralElectric
TypeTLM1612C,orapprovedequal
1EA Timer,60minuteswithholdfeature,IntermaticModelNo.FF60MH(servesas on
andoff testoverrideswitch),orapprovedequal
Thecontroller shallhaveappropriatecontactors,circuitbreakers,groundingbars,wiring,
andappurtenancesforproperoperation. An onandoff overridetimershallbeprovided
fortestingpurposes. Ifthelightsareoffandthetimerisplacedintheonmodethenthe
lightsshallcomeonandoverridethephotocell. Thecontrollercircuitpanelshallcontaina
20amp.,125voltGFCIreceptacleandanincandescentlampholderwitha60wattlampand
apullchain located inanupperquadrantof thepanel. Thecontroller is tobe furnished
withonelightingcontactorcontrolledbythephotocell.
9. Cabinet
ThecabinetshallbeaNEMAstandardsizeMcabinetmadeofinchthickaluminumand
shallhaveoveralldimensionsof50incheshighby30incheswideby18inchesdeepunless
otherwise approved by the Engineer. The cabinet finish shall be natural aluminum
(unpainted). No auxiliary switchpaneldoor shallbeprovided. Themaindoor shallbe
equippedwithaCorbinNo.15481 tumbler type lock (industry#2 lock)and two (2)keys
shallbefurnishedtotheTown.
10.
ControllerBase
ThebaseshallconformtothedrawingsasshownontheTownofWindsorStandardDetails.
ThebaseshallbemadeofClass C concreteandmaybeprecast. Itshall includeone (1)
dedicated2 inchPVCelectricalgradeconduit sweep for theutilitycompanypower feed,
one5/8inchby8footcoppergroundrod,aminimumof42inchpolyvinylchloridesweeps
forwiringtothelightpoles,and23/4by18inchgalvanizedanchorbolts.
11.ConduitandWiring
Conduitshallbe2inch,schedule40PVCelectricalgradeconduit. Wiringshallconsistof3
1/0 THW aluminum wire, and a #6 copper ground unless otherwise approved by the
Engineer.
-
8/10/2019 455 Street Lighting Systems
4/6
TECHNICALSPECIFICATION455
STREETLIGHTINGSYSTEMS PAGE4of6
B. CommercialStreetLightSystems
The commercial light standards and luminaire shall conform to Form 816, SectionsM15.01
throughM15.05,withthefollowingexceptions:
1.
TheCommercialLuminaireshallbeofaGEtypeM250A2POWR/DOORLuminaireWithCutoffOpticsorapprovedequal.
2. Mountingheightoflightfixturesshallbe326feetabovegrade.
3. On commercial lighting systems, contactor number one is to control even numbered
light poles and contactor number two is to control odd numbered light poles. A
separate 2 pole, 60 amp circuit breaker, shall power each contactor. The normal
operationofalllightsistobecontrolledbythephotocell.
4.
Cabinetand
Controller
Base
shall
meet
the
above
requirements
of
Section
455.2.A.9
and
455.2.A.10unlessotherwiseapprovedbytheEngineer.
455.3 SUBMITTALS
The followingsubmittalsshallbesubmitted to theEngineer forreviewandapprovalprior to
installation:
Manufacturer(s)cutsheet(s)onfixtures
Manufacturer(s)cutsheet(s)onlightpoles
Manufacturer(s)cutsheet(s)onlightpolebases
Manufacturer(s)cutsheet(s)oncontrollercabinet
Manufacturer(s)cutsheet(s)oncontrollerbase
455.4 CONSTRUCTIONMETHODS
A. DecorativeStreetLightSystems
1. Cabinet
Ainchblackplywoodbackboardshallbemountedontheinsidebackwallofthecabinet
andshallserveasthemainpanelforthemountingofcontrollercomponents.Thephotocellshallbe installedon theupperportionof thecabinet. Thephotocellshallbemountedso
thatthecabinetretainsitsweatherproofcharacteristicsaroundthemountingarea. Autility
company approvedmeter socket shallbemountedon the right sideof the cabinetwhen
viewed from the front. Adedicated2 inchPVCpipeshallrun from theconcretecabinet
baseoutsidethecabinettothemetersocketfortheutilitycompanyservicewires.
-
8/10/2019 455 Street Lighting Systems
5/6
TECHNICALSPECIFICATION455
STREETLIGHTINGSYSTEMS PAGE5of6
2. LightPoleandControllerBases
TheContractorshallinstallandlevelthebasesasshownontheplans. Thebasesshallbeset
on8inchesofcompactedprocessedaggregateonastablepreparedsubgrade.
3. ConduitandWiring
Conduitshallbeinstalledaminimumof24inchesbelowgrade. Conduitshallbeconnected
with approved couplings to the base sleeves incorporated within the light pole bases.
Electricalwiringwillextendthroughthebasesforconnectiontoeachpole. Theworkshall
includeallexcavation,backfill,materials, laborandsurfacerestoration, including loaming
and seeding,and temporaryandpermanentpavement replacement. Where such surface
restorationisrequired,allworkshallbeperformedinaccordancewiththeTownStandards.
Warningtapeshallbeinstalledaminimumof1footaboveallelectricalconduit. Standoffs
shallbeused in accordancewith the servingpublicutility companyor asdirected. The
Contractorshallalsosupplyandinstallall itemsnecessaryto insureproperfunctioningof
thelighting
system,
including
photocell(s),
ground
wire
to
be
made
to
the
ground
lug
in
the
polebaseasshownontheelectricaldiagram,inlinefusesandholders,nondelay5amp300
volt capacity for each pole, and appropriate connectors, miscellaneous wiring and
appurtenantitems.
4. MeteredStreetlightController
All construction methods for this item shall be in accordance with the manufacturers
constructionmethodsandtheNationalElectricalCode (NEC). Eachstreet lightcontroller
installationshallbe locatedandmountedasdirectedby theEngineerorasshownon the
plans.
B. CommercialStreetLightSystems
The installationofcommercial street light systems shallconform toForm816,Sections10.03,
10.04,and10.08. Theinstallationofthecabinetshallconformtotheabove455.4.A.1. Allother
installationshallconformtoapplicableAASHTO,CTDOT,andNECstandards.
C. PublicUtilityWork
Wherepublicutilityworkisrequired,theContractorshallmakearrangementstoensureproper
coordinationofwork. If required, theContractor shallprovide all excavation,backfillingofserviceconduit,labor,surfacerestorationandanyappurtenantwork,fromthepowersourceto
theservicemeternecessaryforreceivingelectricalserviceasdescribed. Costofthisworkshall
beincludedinthelumpsumpriceforthecontroller.
-
8/10/2019 455 Street Lighting Systems
6/6
TECHNICALSPECIFICATION455
STREETLIGHTINGSYSTEMS PAGE6of6
455.5 MEASUREMENT
Measurement for lightpoles, fixtures, controllers andbases,willbebasedon thenumberof
poles,fixtures,controllers,andbasesofthetypespecified,completedandinplace.
Measurementforconduitandwiringwillbebasedonthenumberoflinearfeetofconduitandwiringinstalledandcompleted.
455.6 PAYMENT
PaymentforthisitemwillbeatthecontractunitpricesperEachfordecorativeandcommercial
light poles, fixtures, controllers and bases and per Linear Foot for conduit and wiring,
completedandaccepted inplace includingall labor,materials, testing, submittals, tools,and
equipmentnecessarytocompletetheworkasspecified.
PAY
ITEM
PAY
UNIT
DecorativeLightPoleandBase EA
CommercialLightPoleandBase EA
Conduit L.F.
Wiring L.F.
ControllerandBase EA