tekmarNet ® Internet Gateway 485 485_D 02/16 Accessories Replaces: 11/15 Installation & Operation Manual 1 of 28 © 2016 485_D - 02/16 A Watts Water Technologies Company Features • WiFi or Ethernet connection to Internet • Built-in web server • Compatible with computer and mobile phone web browsers • View and adjust thermostat settings • Monitor hot water system • Supports multiple user accounts • Graph and export system data • Email notification of status and errors • Error and warning history log • Three alert inputs for equipment monitoring • Software updates Introduction The tekmarNet ® Internet Gateway 485 allows remote access to tekmarNet ® compatible controls through a web browser, either over the Internet or through a local area network. Users can view and change settings for each thermostat, including: temperature, heat/cool/auto, fan operation, relative humidity, schedules, and the away scene. In addition, the boiler system temperatures, firing rate, run times, and pump status can be viewed. All system data can be graphed on a chart or be exported to a data file. The 485 can send daily or weekly status reports, as well as error and warning notifications, through e-mail. The 485 includes three alert inputs that can be used to monitor auxiliary equipment. 34 12 WiFi / Ethernet Alert Inputs 123 123 tekmarNet ® Internet Gateway 485 Reset Power: 5 V (dc), 850 mA, Class 2 Alert Inputs: Short or 0 - 32 V (ac) Designed and assembled in Canada by tekmar Control Systems Ltd. 1068-01 tN4 Boiler Bus tN4 Bus 1 tN4 Bus 2 tN4 Bus 3 Power Alert Input 1 Alert Input 2 Alert Input 3 Date Code 1. Reset IP address: Press and hold 5 sec 2. Reset factory defaults: Press and hold 10 sec Gateway Ready LED must be on solid before resetting IP or factory defaults! WiFi and Ethernet factory default uses DHCP H2054A Power 5V (dc) 14 13 3 C1 Bus 1 4 tN4 1 C0 Boiler Bus 2 tN4 5 C2 Bus 2 6 tN4 7 C3 Bus 3 8 tN4 Do not apply power Alert Input 3 12 11 Alert Input 2 10 9 Alert Input 1 Ethernet Alert On Break Alert On Make Gateway Ready flashes during startup WiFi / Ethernet Benefits Reduce energy consumption by remotely controlling and monitoring a building's HVAC system Notifications can be sent to a service contractor immediately if a problem occurs • All data and information is stored locally on site • Pay no monthly or annual fees

Upload: others

Post on 31-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • tekmarNet® Internet Gateway 485485_D

    02/16

    Accessories Replaces: 11/15

    Installation & Operation Manual

    1of28 ©2016 485_D-02/16A Watts Water Technologies Company

    Features• WiFiorEthernetconnectiontoInternet• Built-inwebserver• Compatiblewithcomputerandmobilephonewebbrowsers• Viewandadjustthermostatsettings• Monitorhotwatersystem• Supportsmultipleuseraccounts• Graphandexportsystemdata• Emailnotificationofstatusanderrors• Errorandwarninghistorylog• Threealertinputsforequipmentmonitoring• Softwareupdates

    IntroductionThetekmarNet®InternetGateway485allowsremoteaccesstotekmarNet®compatiblecontrolsthroughawebbrowser,eitherovertheInternetorthroughalocalareanetwork.Userscanviewandchangesettingsforeachthermostat,including:temperature,heat/cool/auto,fanoperation,relativehumidity,schedules,andtheawayscene.Inaddition,theboilersystemtemperatures,firingrate,runtimes,andpumpstatuscanbeviewed.Allsystemdatacanbegraphedonachartorbeexportedtoadatafile.The485cansenddailyorweeklystatusreports,aswellaserrorandwarningnotifications,throughe-mail.The485includesthreealertinputsthatcanbeusedtomonitorauxiliaryequipment.

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3Da

    te C

    ode

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    Benefits• Reduceenergyconsumptionbyremotelycontrolling

    andmonitoringabuilding'sHVACsystem• Notificationscanbesenttoaservicecontractor

    immediatelyifaproblemoccurs• Alldataandinformationisstoredlocallyonsite• Paynomonthlyorannualfees

  • ©2016 485_D-02/162of28A Watts Water Technologies Company

    Important Safety Information

    ReadthisManualBEFOREusingthisequipment.Failuretoreadandfollowallsafetyanduseinformationcanresultindeath,seriouspersonalinjury,propertydamage,ordamagetotheequipment.KeepthisManualavailableforeasyaccessbyallusers.ReplacementManualsareavailableattekmarControls.com

    Installationmustbeperformedbyqualifiedpersons,inaccordancewithlocalcodes,ANSI/NFPA70(NECArticle424)andCECPart1Section62whereapplicable.Priortoinstallation,pleaseconsultthelocalcodesinordertounderstandwhatisacceptable.Totheextentthisinformationisnotconsistentwithlocalcodes,thelocalcodesshouldbefollowed.Pleasebeawarelocalcodesmayrequirethisproductand/orthecontroltobeinstalledbyanelectrician.

    Thisisasafety-alertsymbol.Thesafetyalertsymbolisshownaloneorusedwithasignalword(DANGER,WARNING,orCAUTION),apictorialand/orasafetymessagetoidentifyhazards.WhenyouseethissymbolaloneorwithasignalwordonyourequipmentorinthisManual,bealerttothepotentialfordeathorseriouspersonalinjury.

    Thispictorialalertsyoutoelectricity,electrocution,andshockhazards.

    Thissymbolidentifieshazardswhich,ifnotavoided,couldresultindeathorseriousinjury.

    Thissymbolidentifieshazardswhich,ifnotavoided,couldresultinminorormoderateinjury.

    Thissymbolidentifiespractices,actions,orfailuretoactwhichcouldresultinpropertydamageordamagetotheequipment.

    • Donotattempttoservicethecontrol.Therearenouserserviceablepartsinsidethecontrol.Attemptingtodosovoidswarranty.

    • Itisyourresponsibilitytoensurethatthiscontrolissafelyinstalledaccordingtoallapplicablecodesandstandards.tekmarisnotresponsiblefordamagesresultingfromimproperinstallationand/ormaintenance.

    To avoid serious personal injury and damage to the equipment:• Donotuseunlessyouknowthesafeandproperoperationofthisequipment.• Improperinstallationandoperationofthiscontrolcouldresultindamagetotheequipmentandpossiblyevenpersonal

    injuryordeath.• Thiselectroniccontrolisnotintendedforuseasaprimarylimitcontrol.Othercontrolsthatareintendedandcertifiedas

    safetylimitsmustbeplacedintothecontrolcircuit.

  • ©2016 485_D-02/163of28A Watts Water Technologies Company

    Table of Contents

    Getting Started

    ImportantSafetyInformation.............................................2Installation.........................................................................4

    Preparation.................................................................... 4PhysicalDimensions..................................................... 4InstallationLocation....................................................... 5BeforeYouStart............................................................ 6SwitchSettings.............................................................. 6StatusIndicatorLED...................................................... 6ResetButton.................................................................. 7Wiring............................................................................. 7WiringtoaThermostatNetwork.................................... 8WiringtoaHouseControl400,401,402,403or406... 9WiringtoaUniversalResetModule423...................... 10WiringtoaBoilerControl274or275............................ 11Logintothe485............................................................ 12

    NetworkingChecklist.................................................... 13RouterSetup................................................................ 14485Networking........................................................... 15DynamicDNS............................................................... 16CreatingaShortcutonAppleiPhoneoriPad.............. 17CreatingaShortcutonAndroidPhonesandTablets... 18

    UserInterface...................................................................19WebPageConfiguration.............................................. 19UsingtheWebPages................................................... 22

    Troubleshooting................................................................25TroubleReachingLoginPage...................................... 25TroubleViewingWebPages........................................ 26

    TechnicalData..................................................................28LimitedWarrantyandProductReturnProcedure............28

    CongratulationsonthepurchaseofyournewtekmarNet®InternetGateway!Thismanualcoversthecompleteinstallation,programmingandsequenceofoperationforthiscontrol.Youwillalsofindinstructionontesting,commissioning,andtroubleshootingthecontrolandsystemthatitoperates.

    ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferenceinaresidentialinstal-lation.Thisequipmentgenerates,usesandcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructions,maycauseharmfulinterferencetoradiocommunications.However,thereisnoguaranteethatinterfer-encewillnotoccurinaparticularinstallation.Ifthisequipmentdoescauseharmfulinterferencetoradioortelevisionreception,whichcanbedeterminedbyturningtheequipmentoffandon,theuserisencouragedtotrytocorrecttheinterferencebyoneormoreofthefollowingmeasures:

    • Reorientorrelocatethereceivingantenna.• Increasetheseparationbetweentheequipmentand

    receiver.• Connecttheequipmentintoanoutletonacircuitdifferent

    fromthattowhichthereceiverisconnected.• Consultthedealeroranexperiencedradio/TVtechnician

    forhelpCetappareilnumériquedelaclasseBrespectetouteslesexi-gencesduRèglementsurlematérielbrouilleurduCanada.

    Radio Frequency Interference

  • ©2016 485_D-02/164of28A Watts Water Technologies Company

    Preparation

    Tools Required-----------------------------------------------------------------------------------------• Phillipsheadscrewdriver• Needle-nosepliers

    • Wirestripper

    Materials Required-------------------------------------------------------------------------------------• 18AWGLVTSolidWire(LowVoltageConnections)• 4Woodscrews

    • TabletorLaptopcomputer(duringinstallation)

    Physical Dimensions

    Installation

    Contents-----------------------------------------------------------------------------------------------• tekmarNet®InternetGateway485• Wallplugpowersupply• 5'(1.5m)EthernetCat5-Ecable• Screwdriver

    • InstallationandOperationManual485_D• QuickSetupGuide485_Q

    Networking Requirements------------------------------------------------------------------------------The485mustbeconnectedtoarouteroranetworkswitch.Aninternetconnectionisrequireifaccessoutsideofthebuildingisrequired.TheroutermustsupportWiFi802.11n,2.4GHz,WPA2encryption.

    Web Browsers------------------------------------------------------------------------------------------The485requiresHTML5compatiblewebbrowsers.Thisincludesmostmodernwebbrowsers.

    Compatibility-------------------------------------------------------------------------------------------

    • tekmarNet®4Timer033• tekmarNet®4SetpointControl161,162• BoilerControl274,275,284• tN2WiringCenter313,314• tN4WiringCenter315,316• ZoneExpansionModule324,325,326• ZoneManager334,335,336,337• PowerManager345,346• tN2HouseControl400,401,402,403,406• BoilerResetControl420

    • MixingResetControl421• UniversalResetModule422,423• MixingExpansionModule440,441,444• tN4UserSwitch479,480,481• tekmarNet®2Thermostat527,528,529,530• tekmarNet®4Thermostat537,538,540• tekmarNet®4Thermostat541,542,543,544,545,546• tekmarNet®Thermostat532,552,553,554,557• SnowMeltControl654

    Front View Side View

    2–13/16"(72 mm)

    1/2" Knock-out (x 5 back) (x 5 bottom)

    Mounting Base

    CL CL

    1/2"(13 mm)

    7/8"(23 mm)

    6–5/8"(170 mm)

    7–9/16"(193 mm)

    1–7/8" (49 mm)

    1/2"(14 mm)

    Ø 3/16" (5 mm)

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    The485iscompatiblewiththefollowingtekmarNet®productsmanufacturedduringandafterDecember2014.Pleasecontacttekmarcustomerservicetocheckforcompatibilityofproductsmanufacturedpriortothisdate.The485softwareisdesignedtoupdate.Thisallowsthe485tobecompatiblewithnewlyreleasedproductsnotincludedinthislist.

  • ©2016 485_D-02/165of28A Watts Water Technologies Company

    Installation Location

    Whenchoosingthelocationforthecontrol,considerthefollowing:• InteriorWall.• Keepdry.Avoidpotentialleakageontothecontrol.• RelativeHumiditylessthan90%.Non-condensing

    environment.• Noexposuretoextremetemperaturesbeyond32to

    122°F(0to50°C).• Awayfromequipment,appliances,orothersourcesof

    electricalinterference.

    • Easyaccessforwiring,viewing.• Approximately5feet(1.5m)offthefinishedfloor.• Themaximumlengthofwireis500feet(150m).• Stripwireto3/8"(10mm)forallterminalconnections.• Usestandard8conductor,18AWGwire.• Ethernetcablemaximumlengthis328feet(100m).• WiFimaximumdistanceis100feet(30m)lineofsight

    withnowalls.WallsreduceWiFirange.

    Mounting

    ThecontrolcanbemountedonastandardDINrail.Firstremovethecontrolfromitsbaseandthen,usingthehooksandspringcliponthebackofthecontrol,mountitontotheDINrail.Thiswillbeapopularoptionforthosewhoprefertomountthecontrolinsidealargerelectricalpanel.

    Thewiringcanenterthebottomorthebackoftheenclosure.Knock-outsprovidedinthebaseallowthewiringtoberuninconduituptotheenclosure.Thebasealsohasholesthatlineupwiththemountingholesofmostcommonelectricalboxes.

    Pressdownatthefingertipgripsontopofthefrontcoverandpulloutanddown.

    Liftthefrontcoverupandawayfromthecontrol.

    Loosenthescrewsatthefrontofthewiringcover.

    Thewiringcoverpullsstraightoutfromthewiringchamber.

    Thebaseisreadyformounting.Thecontrolliftsupandawayfromthebase.

    Pressthecontrolreleasecliponthebaseinsidethewiringchamberandslidethecontrolupwards.

    Removethesafetydividersfromthewiringchamberbypullingthemstraightoutoftheirgrooves.

    Thereare10conduitknock-outsatthebackandbottomofthewiringchamber.

    13Mountingholes

    Controlrelease

    clip

    Controlreleaseclip

  • ©2016 485_D-02/166of28A Watts Water Technologies Company

    LEDs On Off

    Power Powerison Powerisoff

    Alert Input 1 Alertinput1ispresent Alertinput1isnotpresent

    Alert Input 2 Alertinput2ispresent Alertinput2isnotpresent

    Alert Input 3 Alertinput3ispresent Alertinput3isnotpresent

    Gateway Ready Webserveroperational Webserverisoffline

    WiFi / Ethernet Communicationtotherouter Nocommunicationtotherouter

    tN4 Boiler Bus tN4communicationontheboilerbus NotN4communicationontheboilerbus

    tN4 Bus 1 tN4communicationonbus1 NotN4communicationonbus1

    tN4 Bus 2 tN4communicationonbus2 NotN4communicationonbus2

    tN4 Bus 3 tN4communicationonbus3 NotN4communicationonbus3

    Status Indicator LED

    Before You Start

    BeforeconnectingthetekmarNet®InternetGateway485toatekmarNet®system,itisrecommendedthatthesystembefullycompleted,withnotekmarNet®thermostatsorsetpointcontrolsbeingaddedorremovedatalaterdate.Also,eachtekmarNet®thermostatandsetpointcontroldeviceisautomati-callyassignedatekmarNet®addresswhenconnectedtothesystem.Itisrecommendedthateachdevicebegivenamanual

    address.Thisaddressshouldbewrittendowntogetherwiththeroomlocationforfuturereference.ThegatewayrecordstheaddressofeachtekmarNet®thermostatandsetpointcontrol.Foreachaddress,theinstallercannametheroomlocationandbuildingareaforeachthermostatandsetpointcontrol.

    Alert InputsThe485has3alertinputs.Eachalertinputhasacorre-spondingalertinputswitchsetting.

    Alert on MakeWhensettoAlertonMake,the485willtriggeranemailnotificationwhenthealertdemandinputhasacontactclosureoravoltagefrom0to32V(ac).Thealertisclearedwhenthealertinputhasanopencontactorthevoltageisremoved.

    Alert on BreakWhensettoAlertonBreak,the485willtriggeranemailnotificationwhenthealertinputhasanopencontact.Thealertisclearedwhenthealertinputhasacontactclosureoravoltagefrom0to32V(ac)isapplied.

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    Unlock / LockTheUnlock/LockswitchallowstheuseofafactorydefaultuserIDandpasswordforthe485loginwebpage.When set to Unlock (switch setting in up position), the user ID is “installer” and the password is “tekmar”.AfterloggingintothetekmarNet®gatewayloginwebpage,createpersonalaccountsforyourselfandyourcustomerthroughtheconfigurationpage.Oncethepersonalaccountsarecompleted,theUnlock/LockswitchcanbesettoLock.ThedefaultuserIDandpasswordarethennolongeraccepted.ShouldthepersonalaccountuserIDorpasswordsbeforgot-ten,theUnlock/LockswitchcanbesettoUnlockandthedefaultuserIDandpasswordcanbeusedtocreatenewpersonalaccounts.

    Switch Settings

    OncethetekmarNet®Gatewayinstallationiscomplete,itisimportantthattheswitchsettingbeleftintheLockpositioninordertopreventunauthorizedaccess.

  • ©2016 485_D-02/167of28A Watts Water Technologies Company

    Ethernet------------------------------------------------------------------------------------------------

    The485mustbeconnectedtoarouterduringtheinitialinstallation.Aftersetuphasbeencompleted,the485maybeconnectedtoaWiFiwirelessnetwork.

    Power--------------------------------------------------------------------------------------------------

    The485includesawallplugpowersupply.

    • Connectthesmallroundendintothepowerreceptacleonthe485.

    • Plugthewallplugintoa120V(ac)powerreceptacle.

    ThePowerstatusLEDwillbeilluminatedgreen.

    TheResetbuttonhastwooperationsbaseduponthelengthoftimethebuttonishelddown.The"GatewayReady"LEDmustbeoninorderfortheresettofunction.

    Reset IP SettingsPressandholdtheresetbuttonfor5seconds.TheresetLEDwillturnred.The485defaultstouseDHCP(automaticaddressing)providedbytherouter.AfterresettingtheIPtothefactorydefault,the485restarts.Itmaytakeupto5minutesbeforewebpagesareavailable.

    Reset Factory DefaultsPressandholdtheresetbuttonfor10seconds.The485willeraseallmemoryandallfileswillberesettotheirfactorydefaults.Itmaytakeupto5minutesbeforewebpagesareavailable.

    tekmarNet® Bus----------------------------------------------------------------------------------------The485includesfourtekmarNet®businputs.ThetN4businputsallowcommunicationbetweenthe485andthetekmarNet®system.EachtN4busonthetekmarNet®systemmustbewiredtothetN4businputsonthe485.ThetN4busmaybewiredbeforeorafterthecontrolispoweredonandsetup.

    Alert Inputs--------------------------------------------------------------------------------------------The485includesthreealertinputs.Thealertinputscanbeusedtomonitorheatingequipmentforproblemssuchas:

    • Lowwatercutoff• Heatingoilorpropanetanklowtanklevel• Lossofutilityelectricalpower• Boilerflamefailurelockout

    Reset Button

    Wiring

    Switch

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power17

    5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    Switch

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power17

    5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / EthernetDIP Switch: Alert on Make• Switchisnormally

    open• Alertissentwhen

    switchisclosed

    DIP Switch: Alert on Break• Switchisnormally

    closed• Alertissentwhen

    switchisopened

    NetworkConnected

    WiFi

    Alert Demand

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Restart

    Power: 5V(dc), Class 2Demands: Short, 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.tektra 1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertDemand1

    AlertDemand2

    AlertDemand3

    Date

    Cod

    e

    Push and release to restart 485Push and hold 5 sec to reset IP addressPush and hold 10 sec to restore factory defaults

    NetworkingFactory default uses DHCP

    Power17

    5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertDemand 3

    1211Alert

    Demand 2

    109Alert

    Demand 1

    Ethernet

    On Break

    On Make

    StatusOK

    C tN4

    Disconnectallpowerbeforeopeningthecontrol.Topreventtheriskofpersonalinjuryand/ordeath,makesurepowerisnotappliedtotheproductuntilitisfullyinstalledandreadyforfinaltesting.Allworkmustbedonewithpowerturnedofftothecircuitbeingworkedon.

    AllavailabletN4busesmustbewiredtothe485whetherornottherearethermostatsconnectedtothebus.

    DonotdisconnectpowerwhenresettingtheIPaddressorresettingthefactorydefaults.Thiswillresultinpermanentdamagetothe485.

  • ©2016 485_D-02/168of28A Watts Water Technologies Company

    Wiring to a Thermostat Network

    RC

    LN

    TT

    PowerZone 1

    Zone 2

    Zone 3

    Zone 4

    Zone 5

    Zone 6

    End Switch/ Zone Group Pump

    CZone 2

    WtN4 R CZone 3

    WtN4 R CZone 4

    WtN4 R

    tN4 Wiring Center 315Six Zone Valves

    WtN4

    CtN4

    CX

    Zone 1Expansion

    VlvCZone 1

    VlvCZone 2

    VlvCZone 3

    VlvCZone 4

    VlvCZone 5

    VlvCZone 6

    XC

    Input PowerR

    R

    WtN

    4C

    Zone

    5R

    WtN

    4C

    Zone

    6R

    H8001B

    End Switch

    Use

    at le

    ast 1

    67°F

    (75°

    C) c

    ondu

    ctor

    s

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    Thermostats

    ZoneValves

    Transformer

    Boiler

  • ©2016 485_D-02/169of28A Watts Water Technologies Company

    Wiring to a House Control 400, 401, 402, 403 or 406

    RC

    LN

    1

    Menu

    House Control 402

    Item

    +

    Mix

    ComBoil

    Out

    DHW

    VlvC VlvC VlvCZone 3Zone 1 Zone 2 Zone 4

    Made in Canada

    VlvC

    Com

    Zone 1

    H8007B

    Zone 2 Zone 3 Zone 4tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 C

    Floating ActionClsOpn

    Sensors - No PowerCall

    Call

    tN4

    tN4

    CC

    Mod

    dc/

    mA

    Boil E

    xp.

    Mix

    Exp.

    SetpointDHW

    Use at least 167°F(75°C) conductorsRC

    Input Power

    Stag

    e 2

    Stag

    e 1

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    Thermostats

    BoilerTransformer

    ZoneValvesDHWTank

    OutdoorSensor

    MixSensor

    BoilerSensor

  • ©2016 485_D-02/1610of28A Watts Water Technologies Company

    Wiring to a Universal Reset Module 423

    50 51 52 53

    Stage1/ Stage 2/Boil Enbl Setp Enbl

    75 76 77 78

    Demand DemandDHW Setpoint

    54 55

    DHW Primary

    10 Amax79 80 81 82

    NPump NPump

    tN4Made in Canada

    8 VA 1 VA

    Boil Sens Sup / Ret

    H7010A

    Off / DHW SensorOff / tekmar StagerBoilers On-Off / ModOff / Rotation

    Meets Class B: CanadianICES & FCC Part 15

    PoweredOutputs24 V (ac)

    Universal Reset Module 423

    Item

    Menu

    tektra1006-01

    Demands: 20 - 260 V (ac)Relay Rating: 115 V (ac) 5 A

    71 72 73 74DHW 24 V (ac)

    /

    57 58 59 60 6156

    C

    C

    tN4Mod2 (dc)Mod1 (dc)

    6564

    C3C1+ –

    C

    + – tN4

    62 63

    C2 tN4 tN4

    66 67

    DHW ComBoiler

    68 69

    Boil Com

    70

    Out

    Do not apply power

    Test

    1 2 3

    Vlv R

    Zone Manager 335

    Meets Class B:Canadian ICES &FCC Part 15

    Made in Canada

    Zone A1

    Zone A2

    Power

    Zone Group Pump A

    Zone A3

    Zone A4

    Zone A5

    Zone A6

    tN4

    tektra996-01

    For product instructions, see brochureInput Power: 115 V (ac) ±10% 60 Hz 12 ARelay Rating: 115 V (ac) 5 A All Loads Using Input Power: 11.5 A

    Caution! Disconnect AllPower before Opening

    Limitedpoweravailable,seewiringbrochure

    For product literature:www.tekmarcontrols.com

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 20

    H700

    3B32 33 34 35 36 37 38 39 40 41 42 43

    17 18 19 21 22 23 24 25 26 27

    24 V (ac) Fuse: T2.5 A 250 V

    28 29 30 31

    On/Off

    Zone GroupPump A Delay

    Zone GroupPump A

    A1A2A3A4A5A6A1A2A3A4A5A6

    tN4 C C CW WR RPmp tN4 tN4 C WRtN4 C WR RtN4 C WtN4 RC WtN4

    Input Power Zone Group Zone A1 Zone A2 Zone A3 Zone A4 Zone A5 Zone A6

    Zn Grp A A tNt Zone A1 tNt Zone A2 tNt Zone A3 tNt Zone A4 tNt Zone A5 tNt Zone A6

    NL NPmp A C Vlv C Vlv C Vlv C Vlv C Vlv C Vlv

    Supply /signal wires 90°C min.

    Sta

    ge

    Mod

    ulat

    ing

    + –T T

    L115V(ac)

    N

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    Thermostats

    Boiler

    ZoneValves

    OutdoorSensor

    BoilerSensor

    PrimaryPump

  • ©2016 485_D-02/1611of28A Watts Water Technologies Company

    Wiring to a Boiler Control 274 or 275

    Setback

    Boiler Control 275One tN4, Four Modulating Boiler & DHW / Setpoint

    Menu Item

    Test

    BoilerDemand

    DHW/SetpointDemand

    ProofDemand

    EMSInputSignal

    PriorityOverride

    Power 115 V ±10% 60 Hz 7 VA, 1150 VA max.Relays 230 V (ac) 5 A 1/3 hpDemands 20 to 260 V (ac) 2 VA

    Designed and assembled in Canada bytekmar Control Systems Ltdtektra 1020-01

    Meets Class B:Canadian ICESFCC Part 15

    For maximum heat,press and hold Testbutton for 3 seconds.

    not testingtestingtesting paused

    offredred

    BTC I

    Off

    EMSRotate Fixed Last

    Pump Sequencer

    Exercise

    Off

    Demands

    Date

    Cod

    eH

    2048

    B

    Signal wiring must be rated at least 300 V.

    DHW29

    /SetpCom30

    DemPr.31

    Dem

    2

    5

    –Mod1

    1

    +Mod2

    3

    +– +Mod3

    4

    +Mod4

    6

    +BRet/

    7Com

    8tN4

    12Boil

    9Out

    10Com

    11PrimP1 L N

    26Power

    28271413Do not apply power

    24DHW/ P2

    23 251615 1817 2019 2221

    Fixed LeadFirst On / Last Off

    First On / First Off

    Relay1

    Relay2

    Relay3

    Relay4

    C.A. /Alert

    BoilerDemandSup DHW

    ZoneLoadShedding

    T T-+ L115V(ac)

    N

    3 41 2

    WiFi/EthernetAlert Inputs

    1 2 3

    1 2 3

    tekmarNet® Internet Gateway 485

    Reset

    Power: 5 V (dc), 850 mA, Class 2Alert Inputs: Short or 0 - 32 V (ac)

    Designed and assembled in Canada bytekmar Control Systems Ltd.1068-01

    tN4BoilerBus

    tN4Bus1

    tN4Bus2

    tN4Bus3

    Power

    AlertInput1

    AlertInput2

    AlertInput3

    Date

    Cod

    e

    1. Reset IP address: Press and hold 5 sec2. Reset factory defaults: Press and hold 10 secGateway Ready LED must be on solid before resetting IP or factory defaults!WiFi and Ethernet factory default uses DHCP

    H205

    4A

    Power5V (dc)

    14133

    C1Bus 1

    4

    tN4

    1

    C0Boiler Bus

    2

    tN4

    5

    C2Bus 2

    6

    tN4

    7

    C3Bus 3

    8

    tN4

    Do not apply power

    AlertInput 3

    1211Alert

    Input 2

    109Alert

    Input 1

    Ethernet

    Alert On Break

    Alert On Make

    GatewayReadyflashes during startup

    WiFi / Ethernet

    Boiler

    OutdoorSensor

    BoilerSupplySensor

  • ©2016 485_D-02/1612of28A Watts Water Technologies Company

    When the power is first turned on, the 485 may take up to 5 minutes to start up. The web pages are available once the Gateway Ready and WiFi / Ethernet LEDs are on.

    Web Address-------------------------------------------------------------------------------------------

    Onacomputer,tablet,orphoneconnectedtotheLocalAreaNetwork(LAN),openawebbrowser.Inthewebbrowseraddressbar,enterthefollowingaddress:http://tekmargateway.localThetekmarGatewayloginpagewillappear.

    Login---------------------------------------------------------------------------------------------------MakesuretheUnlock/LockswitchissettoUnlock.Thisenablestheuseofthedefaultloginandpassword.Nowenterthedefaultloginandpassword.•Thedefaultloginisinstaller•ThedefaultpasswordistekmarAftercreatingpersonalizeduserloginaccounts,itishighlyrecommendedtosettheUnlock/LockswitchtotheLockpositiontopreventunauthorizedaccess.Makesuretorecordyourloginandpasswordforfuturereference.

    Login to the 485

    Gateway Ready

    WiFi / Ethernet

    Multiple Gateways--------------------------------------------------------------------------------------

    Gateway Startup Sequence Web Address (on LAN only)1sttostart tekmargateway.local

    2ndtostart tekmargateway-2.local

    3rdtostart tekmargateway-3.local

    Network and Power------------------------------------------------------------------------------------UsingthesuppliedEthernetcable,plugthe485intooneoftheLANportsonarouter.Then,usingthesuppliedwallpowersupply,plugthesmallendintothe485powerjack.Lastly,connectthewallpowersupplyintoawallpoweroutlet.

    TheremaybecaseswheretherearetwoormoregatewaysinstalledonthesameLAN.

    Unicastroutersdonotsupportthismethodoflocatingthe485onthenetwork.Inthiscase,logintotherouter'ssetuppageandtherouterwilllisttekmargatewayasoneofthedevicesonthenetwork.ClickthislinkorenterthisIPaddressintothewebbrowsertoaccessthe485loginpage.

    http://tekmargateway.local

  • ©2016 485_D-02/1613of28A Watts Water Technologies Company

    Networking Checklist

    It is recommended to read the networking steps on pages 14, 15 and 16 and fill out this checklist prior to installation.

    IT Department

    IT Company �����������������������������������������������������������������������������������

    IT Contact and Phone # �������������������������������������������������������������������������

    Internet Service Provider (ISP)

    ISP Name �������������������������������������������������������������������������������������

    Technical support phone # �����������������������������������������������������������������������

    Is the IP address static or dynamic? ���������������������������������������������������������������

    Is port 80 blocked by the ISP? ��������������������������������������������������������������������

    Is port 3000 blocked by the ISP? ������������������������������������������������������������������

    Modem

    Manufacturer, Model, Serial # ��������������������������������������������������������������������

    Is the modem cellular or land-line? ����������������������������������������������������������������

    Router

    Manufacturer, Model, Serial # ��������������������������������������������������������������������

    Router IP Address ������������������������������������������������������������������������������

    Router Username ������������������������������������������������������������������������������

    Router Password �������������������������������������������������������������������������������

    WiFi SSID �������������������������������������������������������������������������������������

    WiFi Password ���������������������������������������������������������������������������������

    Gateway 485

    485 LAN IP Address ����������������������������������������������������������������������������

    485 Username ���������������������������������������������������������������������������������

    485 Password ���������������������������������������������������������������������������������

    Dynamic DNS (not required when ISP provides Static IP)

    Host name �������������������������������������������������������������������������������������

    Login name �����������������������������������������������������������������������������������

    Password �������������������������������������������������������������������������������������

  • ©2016 485_D-02/1614of28A Watts Water Technologies Company

    Router Setup

    The485mustbeconnectedtoarouter.Therouterdirectscomputernetworktrafficfromonecomputingdevicetoanother.AllthedevicesontheinsideofabuildingformaLocalAreaNetwork(LAN).TherouterbridgestheLANtotheinternetandprotectstheLANfromunauthorizedaccessfromtheinternetusingafirewall.MostroutersuseaDHCPserverthatautomaticallyassignsanIPaddresstoacomputer.Theseaddressesaredynamic,whichmeansthatparticularcomputercanbegivenanewIPaddresseachtimeitisturnedon.Sinceothercomputersmustlocatethe485onthenetwork,itisimportantthatthe485begivenastaticLANIPaddress.

    Internal IP

    Router

    External IP

    RemoteComputer

    NetworkedComputer

    Internal IP

    Por

    t For

    war

    ding

    Gateway

    Router Overview---------------------------------------------------------------------------------------

    Login to Router Setup Page----------------------------------------------------------------------------

    Logintotherouterusingtherouter'susernameandpassword.Consultwiththerouter'smanualorchecktherouterforastickertolocatethisinformation.

    These directions are provided as a guide to a typical router. If the router does not follow these setup steps contact the router manufacturer, router supplier or qualified IT technician for assistance.FirstlocatetheroutersetupwebpageontheLAN.Todothisfollowthesesteps:• Logintothe485usingacomputer,tabletorsmartphone.• Click"Configuration".• Click"Network".The485willlisttherouter'sIPaddress.• Createanewtabonthewebbrowserandentertherouter's

    IPaddressintothewebbrowseraddressbar.Twocommonrouteraddressesare:192.168.0.1or192.168.1.1

    Intheroutersettings,locatetheDHCPsettings.SettheDHCPIPrangesothatthereareeightfreeIPaddressesavailable.Forexample,iftherouteraddressis192.168.0.1,thentheDHCPrangeshouldbesettostartat192.168.0.10.ThisallowseightstaticIPaddressestobeavailable(192.168.0.2to192.168.0.9).Theroutermayneedtorestartwhenthissettingissaved.

    AppleAirportExtremeandExpressroutersrequiretheAirPortUtilitysoftwareprogramtosetuptherouter.Followtheinstructions:http://www.apple.com/support/airport

    Intheroutersettings,locatetherouterportforwardingrules.Thisfeaturecanhaveothernamesdependingonthemanufactureroftherouter.Othernamesincludeportaddresstranslation,networkaddresstranslation(NAT)orapplicationsandgaming.• Nametheportforwardingrule"tekmar".• OpenexternalTCPandUDPport80.• Insomecases,internetserviceprovidersblockport80.In

    thiscaseopenexternalport3000.• OpeninternalTCPandUDPport80.• EnterthestaticLANIPaddressofthe485typically192.168.0.2

    or192.168.1.2

    Router DHCP Settings----------------------------------------------------------------------------------

    Router Port Forwarding--------------------------------------------------------------------------------

  • ©2016 485_D-02/1615of28A Watts Water Technologies Company

    • ClicktheDNS/Porttab.• IntheDNS1fieldentertheIPaddressoftherouter.• IntheDNS2fieldenter208.67.222.222.Thisdirectsthe485touse

    OpenDNS.comtoresolveDNSsearchesontheInternet.• Fornewinstallations,settheportnumberto80.• WhenreplacingaGateway483,settheportnumberto3000.• ClicktheSavebutton.Thisrequiresarebootofthe485.

    ClickOK.

    FirstselecttheWiFinetwork• ClicktheWiFitab.• ClicktheNetworktab.• ScanforavailableWiFinetworks.• SelectaWiFinetwork,entertheWiFipasswordandpress

    theConnectbutton

    Network - DNS and Port--------------------------------------------------------------------------------

    485 Network Settings using WiFi (wireless)-------------------------------------------------------------

    485 Network Settings using Ethernet (wired)-----------------------------------------------------------Setupthe485tohaveastaticIPaddress• ClicktheEthernettab.• SettheDHCPsettingtoDisabled.• EnterthestaticIPaddress.Iftherouteraddressis192.168.0.1

    thenthe485IPcanbesetto192.168.0.2.• EntertheSubnetmask.Typicallythisissetto255.255.255.0• EntertheRouterIPaddress.Checktherouter'smanualfor

    therouter'sdefaultIPaddress.• PresstheSavebutton.Thisrequiresarebootofthe485.

    ClickOK.

    • DonotsetupEthernetandWiFitobothhaveastaticIPaddressatthesametime.Thismayresultinnetworkingproblems.

    • AftersetupofWiFi,disconnecttheEthernetcable.ConnectionofbothWiFiandEthernetmayresultinnet-workingproblems.

    • Powertherouteroff,thenpowerbackon.

    Secondly,setupthe485tohaveastaticIPaddress• ClicktheTCP/IPtab.• SettheDHCPsettingtoDisabled.• EnterthestaticIPaddress.Iftherouteraddressis192.168.0.1

    thenthe485IPcanbesetto192.168.0.2.• EntertheSubnetmask.Typicallythisissetto255.255.255.0• EntertheRouterIPaddress.Checktherouter'smanualfor

    therouter'sdefaultIPaddress.• PresstheSavebutton.Thisrequiresarebootofthe485.

    ClickOK.

    • Powertherouteroff,thenpowerbackon.

    485 Networking

    • WPA2encryptionisrequiredforWiFiconnections.WEPandnoencryptionoptionsarenotsupportedbythe485.

  • ©2016 485_D-02/1616of28A Watts Water Technologies Company

    Dynamic DNS

    ToaccesstheGateway485ontheinternet,youmayrequireadynamicDNSservice.IfastaticIPaddresshasbeenprovidedbyyouInternetServiceProvider,thenadynamicDNSisnotrequired.tekmarprovidesafreedynamicDNSservicewiththehostname“mylabel.tekmargateway.com”wheremylabeliscustomizedwithyournameoraddress.ThishostnamethenlinkstoyourGateway485.

    Tocreateanaccount:Sendanemailtotekmar.customerservice@wattswater.comwiththefollowinginformation:• Yourcustomer'sname• Yourchosenhostname

    tekmarcustomerservicewillreplytoyouremailwiththefollowinginformation:• Hostname• Loginname• PasswordPleaseallowupto1businessdayforaresponse.RecordthisinformationintheNetworkingChecklistforfuturereference.OntheGateway485:• ClickConfiguration• ClickNetwork• ClicktheDynamic-DNStab• IntheServiceProviderdropdownmenuselect“DynDNS”• EntertheHostName• EntertheLogin• EnterthePassword.• Click“Update&Test”Themessage“DNSclientconfigurationhasupdatedsuccess-fully!”willappearifthesettingsarecorrect.

    CustomersmayalternativelyselectthepaidserviceNo-IPastheirdynamicDNSprovider.

  • ©2016 485_D-02/1617of28A Watts Water Technologies Company

    Creating a Shortcut on Apple iPhone or iPad

    AshortcuttotheGateway485canbecreatedonanAppleiPhoneoriPad.Step1• OpentheSafariwebbrowser

    Step2• EntertheGateway'shostnameorstaticIPaddress• Press"Go"• PresstheUploadsymbol

    Step3• Press"AddtoHomeScreen"

    Step4• Press"Add"

    Step5• AshortcuticonwillbeaddedtotheiPhoneoriPad'shome

    screen.

  • ©2016 485_D-02/1618of28A Watts Water Technologies Company

    Creating a Shortcut on Android Phones and Tablets

    AshortcuttotheGateway485canbecreatedonanAndroidphoneortablet.Step1• OpenChromewebbrowser.• EntertheGateway'shostnameorstaticIPaddress• Press"Go"• PressSettings

    Step2• Press"AddtoHomescreen"

    Step3• PressAdd.

    Step4• AshortcuticonwillbeaddedtotheAndroiddevice'shome

    screen.

  • ©2016 485_D-02/1619of28A Watts Water Technologies Company

    User InterfaceWeb Page Configuration

    Configuration------------------------------------------------------------------------------------------The485requiresinformationtobeenteredabouttheheating,cooling,ventilationandairconditioning(HVAC)system.Toenterthisinformation,click"Configuration".

    Configuration - Job Site Information--------------------------------------------------------------------TheJobSitepagecontainsasummaryofthebuilding'slocation,thebuildingownerormanagerandtheinstallingheatingcontractor.ThisallowsforsupportshouldtheHVACsystemneedservicework.Aphotoofthebuildingcanbeuploadedtopersonalizethehomepagefortheuser.

    Configuration - General Settings-----------------------------------------------------------------------

    The485supportsdifferenttemperatureandtimeformats.Selecttheunitsdesiredbythebuildingowners:• TemperatureunitsineitherFahrenheitorCelsius• 12or24hourtimeformat• TimezoneThe485synchronizesitstimeclockfromtheinternet.Ifthe485isconnectedtoaLANbutisunabletoreachtheinternet,the485willcontinuetousethetimesetatthefactory.

    Configuration - Areas----------------------------------------------------------------------------------Anareaisagroupofroomsthatareneartooneanother.Afloororwingisanexampleofanarea.Enterupto12areasthatthermostatscanbelongto.

  • ©2016 485_D-02/1620of28A Watts Water Technologies Company

    Configuration - Devices--------------------------------------------------------------------------------

    Eachthermostatcanbegivenaroomname.EachthermostatislistedusingitstekmarNet®address.Locatetheaddressoneachthermostatdisplayandentertheroomname.Assignanareanametothethermostatusingthedrop-downmenu.

    Configuration - Scenes and Setpoint Enable-----------------------------------------------------------Scenesarebuildingwideoverridesthatallowtheusertochangethebuildingtemperaturefromcomforttoeconomyoperation.ThetekmarNet®systemcanoperateinoneofeightscenes.Eachscenecanbegivenacustomnameandeachscenecanbeselectedwhetherornotitisvisibletotheuser.

    TheSetpointEnableisusedtoactivateordisableasetpointorsnowmeltcontrol.Thiscanbeusedtoremotelyactivatesnowmeltsystems,hottubs,andpatioheaters.

    Configuration - Users----------------------------------------------------------------------------------ClickonNewUsertocreatealoginforeachpersonthatwillhaveaccesstothe485.Foreachloginaccount,selecttheaccesslevelthatthepersonhastothe485.Theinstalleraccesslevelallowsaccesstoallofthe485webpages.TheuseraccesslevelonlyallowsaccesstotheHome,Temperatures,andScenewebpages.Thisaccessisrecommendedfortheaveragehomeowner.Providetheaccountwithaname,loginname,emailaddressandpassword.Click‘AddUser’tocreatetheaccount.Theloginandpasswordarecasesensitive.Theloginmustbeatleast3charactersandthepasswordmustbeatleast4characters.

  • ©2016 485_D-02/1621of28A Watts Water Technologies Company

    Configuration - Email-----------------------------------------------------------------------------------

    Inordertosendemailtouseraccounts,the485mustconnecttoamailserver.Gmail&Hotmailaccountsrequireausernameandpassword.SomeInternetserviceproviders(ISP’s)onlyrequiretheSMTPserveraddress,otherswillrequireadditionalsettings.ContactyourISPtodeterminethefollowingadvancedemailsettings:• SMTPServerAddress• SMTPServerPort• Emailaccountusername• Emailaccountpassword• HELOdomain• AuthenticationmodePlain,LoginorCRAMMD5• IfTLS/SSLisusedOncetheemailserversettingshavebeenentered,clickSave&Continue.Clickingthetestbuttonsendsatestmessagetotheemailaccount.Pleasenotethetestbuttondoesnotsavethepasswordoremailsettings.

    Configuration - Alerts----------------------------------------------------------------------------------TheAlertspageprovidesaformforashortmessagetobeincludedinanotificationemailwheneveranAlertInputisactivated.RoomhotandcoldwarningthresholdscanbesetontheAlertspage.Shouldthetemperatureexceedthehotroomsettingorfallbelowthecoldroomsetting,anemailcanbesent.Thefollowingitemscanbeselectedtonotifyindividualuserswhentheyoccur:• Alertinputs-sentimmediately• Hotroomwarning-senteachhouronthehour• Coldroomwarning-senteachhouronthehour• Errormessages-senteachhouronthehour• Dailystatusreports-senteachdayatmidnight• Weeklystatusreports-senteachSundayatmidnight

    Configuration - Software Update-----------------------------------------------------------------------

    The485softwarecanbeupdated.ClicktheUpdateSoftwarebuttontocheckifnewsoftwareisavailable.

    Configuration - History---------------------------------------------------------------------------------Allerrorandwarningmessagesarestoredinalistandaretimestamped.Individualerrororwarningmessagescanbeclearedbytheuser.

    SendingemailsrequiresthattheDNSsettingsbeenteredontheconfiguration-networkpage.EmailswillnotsendiftheDNSfieldisleftemptyorareincorrect.

  • ©2016 485_D-02/1622of28A Watts Water Technologies Company

    Home Page---------------------------------------------------------------------------------------------TheHomepageshowsaphotographofthebuildingandasummaryoftheheatingsystemincluding:• Scene• Errormessagespresent• Outdoorairtemperature• Warmestandcoldestroomtemperatures• Outdoorhighsandlows• Boilerplantoutputaveragedoverthelast24hours

    Temperatures Page-------------------------------------------------------------------------------------TheTemperaturespagelistallthermostat'stemperaturemeasurementandthecurrentheatingandcoolingsetting.Inaddition,setpointcontrolsandsnowmeltcontrolsarealsolisted.Clicktheupordownbuttonstoadjustthetemperature.Theheatsettingautomaticallyincreasesthecoolingsettingifadjustedwithin3°F(1.5°C)ofthecoolingsetting.Likewise,thecoolingsettingautomaticallydecreasestheheatingsettingifadjustedwithin3°F(1.5°C)oftheheatingsetting.Thispreventscyclingbetweenheatingandcoolingonthethermostat.Anorangeboxindicatesthatthethermostatisheatingandablueboxindicatesthatthethermostatiscooling.Loading...TheTemperaturespageshows"Loading..."insteadofthethermostattemperaturewhilethe485isdownloadingthethermostatsettings.Thisonlyoccurswhenthe485ispoweredonforthefirsttimeandcantakeupto5to10minutesperthermostatdependingonthetekmarNet®networkactivity.

    Temperatures - Individual Thermostat------------------------------------------------------------------Clickonthethermostatnametoaccesstheindividualthermostatorsetpointcontrolsettings.Thecurrenttemperature,relativehumidity,sceneandschedulestatusareshown.ThemodecanbesettoAuto,Heat,Cool,orOff.Theoptionsavailablearedeterminedbythethermostatmodel.TheHeatsetpointsareavailablewhenmodeissettoHeatorAuto.TheCoolsetpointsareavailablewhenmodeissettoCoolorAuto.TheFansettingsareavailablewhenafanisavailableonthethermostat.TheHeat,Cool,andFanmayhavemultiplesettingsdependingifasetbackscheduleisusedonthethermostat.IfnoscheduleisusedthenonlytheOccupiedsettingisavailable.Ifatwoeventscheduleisused,thentheOccupiedandUnoccupiedsettingsareavailable.Ifafoureventscheduleisused,thentheWake,Unoccupied,Occupied,andSleepsettingsareavailable.Agreenboxaroundasettingindicatesthecurrentscheduleeventofthedevice.

    Using the Web Pages

  • ©2016 485_D-02/1623of28A Watts Water Technologies Company

    Scenes Page-------------------------------------------------------------------------------------------TheScenespageallowstheusertoselectthesceneforthebuilding.Forexample,thescenecouldbesettoNormalwhilethebuildingisoccupied,andthensettoAwaywhilethebuildingoccupantsareawayonvacation.Thesetpointenableallowshottubs,patioheatingandsnowmeltsystemstoberemotelyactivated.Setpointcontrolsthatareusingthesetpointdeviceenablefeaturecanbeactivatedorplacedinstandbyoperationusingthescenespage.ClickontheActivebuttontohavethesetpointcontroloperateattheOccupiedtemperaturesetting.ClicktheStandbybuttontohavethesetpointcontroloperateatthestandbysetting.Thestandbytemperaturesettingissetbytheapplicationmodeconfiguredonthesetpointcontrol.

    Scenes - Scene Details---------------------------------------------------------------------------------TheScenesDetailsliststheresponseofeachthermostatinaparticularscene.Adjustabilityofeachsceneisdependentontheparticularthermostatmodelandhowthethermostatisconfigured.Consultthethermostatinstallationandoperationmanualfordetailedinformation.

    Schedule Page-----------------------------------------------------------------------------------------TheSchedulepageliststheschedulesonthetekmarNet®system,thelocationoftheschedulemasterthermostat,andthethermostatsthataremembersofthisschedule.Thermostatsthathavetheirownprogrammableschedulewhicharenotsharedarelistedas"zone".

    Schedule - Schedule Details----------------------------------------------------------------------------

    OntheSchedulespages,clicktheschedulenametoaccesstheschedulesettings.Foreachscheduleeventtime,enterthetimefortheeventtostart,roundedtothenearesttenminutes.ClickontheUploadTimesbuttontosendthesettingstothethermostat.

    System Details Page-----------------------------------------------------------------------------------TheSystemDetailspageprovidesinformationonthehotwaterheatingsystem.Detailssuchasthepresenceofaheatdemandsignal,boilerandmixtargettemperatures,actualboilerandmixtemperaturesandboilerandmixpercentoutputlevelsareshownindetail.

  • ©2016 485_D-02/1624of28A Watts Water Technologies Company

    System Details - Device Inventory----------------------------------------------------------------------TheDeviceInventorypageliststhetekmarNet®addressofeachdeviceinthetekmarNet®system,theareaname,thethermostatorsetpointcontrolname,theproductmodelnumber,productnameanddescription,andthesoftwareversion.Insomecases,adevicemayhavebeenconnectedtoatekmarNet®busandthenremoved.ClicktheForgetbuttontoremovethedevicefromthedatabase.IfthedeviceisstillonthetekmarNet®bus,thegatewaywillautomaticallydetectandaddthedevicetothedatabase.Ifadeviceshows"Loading..."ontheTemperaturespageforseveralhours,thenthedevicemaynolongerbeinstalledonthesystemorthedatabasemayhavebeencorrupted.SelectthedeviceonthedeviceinventorypageandclicktheForgetSelectedbuttontoremoveitfromthedatabase.

    Graphs Page-------------------------------------------------------------------------------------------The485capturesandlogsdataata15secondintervalandstoresdataforupto13months.Thedatacanthenbegraphedorexportedtocomparethepreviousyear'sdatawiththecurrentyear'sdata.Thefollowingdataisavailable:• Outdoortemperature• Roomtemperature• Heatingandcoolingtemperaturesetpoints• Relativehumidity• Relativehumiditysetpoints• Floortemperature• Floorsetpoint• Boilertemperature• Boilertarget• Boilerpercentoutput(firingrate)• Boilerdemand• Mixingtemperature• Mixingtarget• Mixingdemand• Heatpumptanktemperature• Snowmeltoperationalstatus• Snowmeltsensorwetordrystatus

    Insteadofgraphingdata,the485supportstheexportofdatatoaCommaSeparatedValue(CSV)documentformatthatcanbeopenedbymostspreadsheetprograms.Themaximumnumberofdatapointsthatcanbeexportedis1024.

    Graphs - Exporting Data--------------------------------------------------------------------------------

  • ©2016 485_D-02/1625of28A Watts Water Technologies Company

    TroubleshootingTrouble Reaching Login Page

    Yes

    No

    Checkthe485staticIPaddressontheLAN.Thenchecktherouterportforwardingrule.• Forwardto485IPaddress• Externalport80• Internalport80• BothTCPandUDPprotocols

    IstheNO-IP.com

    accountactive?

    End

    Yes

    No

    Yes

    No

    Yes

    UsingacomputerorphoneconnectedtotheInternet,openawebbrowserandenterthe485’sstaticIP

    addressortheno-ip.comhostname.

    GotoNo-IP.comandlogin.

    CreateanewNo-IP.comaccount.

    OpentheNo-IPdynamicupdateclient(DUC)onthecomputerorrouterandcheckitssettings.

    Start

    Accessingthe485fromtheinternet

    orthebuildingLAN?

    IsthePowerLEDon?

    Internet

    BuildingLAN

    IstheGatewayReadyLEDonsolid?

    IstheWiFi/EthernetLED

    on?

    Checkifthewallplugpowersupplyispluggedintothe485andtothewallpoweroutlet.

    The485takesupto5minutestostart.

    After5minutes,isStatusOK

    LEDon?

    Unplugwallplugpowersupply,wait10seconds,thenreconnectwallplugpowersupply.

    485isnotconnectedtoEthernet(wired)orWiFi(wireless).

    CheckthattheEthernetcableisconnectedtothe485andtotherouter.

    TherouterhasanindicatorLEDtoshowthattheEthernetcableisconnected.

    Waitfor30secondsifcablereconnected.

    Pressandholdtherestartbuttonfor5seconds.This

    restoresthe485tothefactorydefaultusingDHCP

    (automatic)addressing.Waitfor5minutesfor485

    torestart.

    Wired

    Yes

    Yes

    WirelessIsthe485usingwiredorwireless

    networking?

    Openawebbrowserandenterhttp://tekmargateway.local

    Doestheloginwebpageappear?

    Yes

    Yes

    Doestheloginwebpageappear?

    Doestheloginwebpageappear?

    Doestheloginwebpageappear?

    Gotothe485

    No

    No

    No

    No

    Yes

    No

    No

    IstheWiFi/EthernetLED

    on?

    Yes No

    Logintotherouter'sconfigurationpage.TherouterDHCPclientlistwillshow

    tekmargatewayasadeviceonthenetwork.

    Clickonthelinkorenterthetekmar

    gateway'sIPaddressintothewebbrowser

    addressbar.

    Poweroffthe485andpowerbackon.

    Powerofftherouterandpowerbackon.

    WaitforGatewayReadyandWiFi/

    EthernetLEDtoturnbackon.

    Doestheloginwebpageappear?

    No

    Yes

  • ©2016 485_D-02/1626of28A Watts Water Technologies Company

    Trouble Viewing Web Pages

    RedBannerwith:

    “Communicationerroronbus…”erroronweb

    page?

    Thermostatpageshowing“loading”

    TemperaturespagemissingUpandDownarrows?

    “Somethingwentwrong,calltekmarcustomerservice”errormessage?

    AtN4busisnotcommunicatingwiththe485.AlltN4busesonacontrolmustbewiredtothe485.ThisincludestN4buseswithno

    thermostatsconnected.

    The485mustgatherdatafromeachthermostat.Allow5minutesperthermostat

    timesthenumberofthermostatinthesystem.

    GotoSystemDetails>DeviceInventory,checkmarktheproblemthermostatandclick

    “ForgetSelected”.

    Thermostatstillshows“loading”

    afterseveralhours?

    Thermostatstillshows“loading”

    afterseveralhours?

    Unplugwallplugpowersupply,wait10seconds,thenreconnectwallplugpower

    supply.

    Javascripthasbeendisabledonthecustomerswebbrowser.Recommend

    enablingJavascript.InternetExplorer:

    Tools>Options>Security>SettoMedium-High(notHigh)Firefox:

    Tools>Options>Content>EnableJavascriptChrome:

    Settings>AdvancedSettings>PrivacyContentSettings>Allowallsitestorun

    JavaScript

    Isthisanewinstallation?

    DoestheerroroccurwhileontheGraphingpage?

    GotoSystemDetailspage>DeviceInventory>clickAll,thenclick

    “ForgetSelected”.

    UnabletoviewGateway485web

    pagesoniPhone?

    UnabletoviewGraphingpage?

    Istheresomethingelse

    onthewebpagenotworking?

    End

    The485mustgatherdatafromeachthermostat.Allow5minutesperthermostat

    timesthenumberofthermostatsinthesystem.

    Clearthecomputer’swebbrowsercache.

    InternetExplorer:Tools>InternetOptions>General>Browsing

    history>Delete

    Firefox:Tools>Options>Privacy>History>Clear

    yourrecenthistory

    Chrome:ControlChromebutton>History,selectClear

    browsingdata

    Unplugwallplugpowersupply,wait10seconds,thenreconnectwallplugpower

    supply.

    Resetfactorydefaultsbypressingandholdingtherestartbuttonfor10seconds.

    “Somethingwentwrong,calltekmarcustomer

    service”errorcontinues?

    “Somethingwentwrong,calltekmarcustomer

    service”errorcontinues?

    iPhoneneedstosupport“Cookies”Oniphone,Settings>Safari>Accept

    Cookies,choose“FromVisited”

    GraphingrequiresawebbrowserthatsupportsHTML5

    Contacttekmarcustomerservice

    Start

    No

    Yes

    No

    Yes

    No

    Yes

    No

    Yes

    Yes

    No

    Yes

    No

    Yes

    No

    Yes

    No

    Yes

    No

    Yes

    No

    Yes

    Yes

    Yes

    No

    No

  • ©2016 485_D-02/1627of28A Watts Water Technologies Company

    Thispageisintentionallyleftblank.

  • Limited Warranty The liability of tekmar under this warranty is lim-ited. The Purchaser, by taking receipt of any tekmar product (“Prod-uct”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the docu-mented date of installation if installed within twenty-four (24) months from the production date.The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and/or workmanship of the defective prod-uct; or to the exchange of the defective product for a warranty replace-ment product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liabil-ity, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in work-manship or materials, including any liability for fundamental breach of contract.The pass-through Limited Warranty applies only to those defective Prod-ucts returned to tekmar during the warranty period. This Limited War-ranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.

    Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Lim-ited Warranty are the Purchaser’s sole responsibility and obligation. Pur-chaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or warranties by Pur-chaser to its customers.The pass-through Limited Warranty does not apply if the returned Prod-uct has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and/or the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLA-TION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUC-TION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW. Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact informa-tion regarding the appropriate Representative.

    Product design, software and literature are Copyright ©2016 by tekmar Control Systems Ltd., A Watts Water Technologies Company

    28 of 28 All specifications are subject to change without notice. Printed in Canada. 485_D - 02/16.

    tekmar Control Systems Ltd., A Watts Water Technologies Company. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-984-0815 Web Site: tekmarControls.com

    Technical DatatekmarNet® Internet Gateway 485 WiFi / EthernetLiterature 485_C,485_D,485_Q,485_B

    Control Microprocessorcontrol.Thisisnotasafety(limit)control

    Packagedweight 2.9lb.(1300g)

    Dimensions 6-5/8"Hx7-9/16"Wx2-13/16"D(170x193x72mm)

    Enclosure BluePVCplastic,NEMAtype1

    Approvals ClassB:ICES&FCCPart15

    Ambientconditions Indooruseonly,32to122°F(0to50°C),RHmaximum90%,non-condensing

    Powersupply 5V(dc)regulated,1A,Class2,FCCcertified

    Alertinputs Short,0-32V(ac)

    Ethernet 10/100BASE-T

    WiFi 802.11n,2.4GHz,WPA2encryption

    Warranty Limited3Year