Differential Relays
Siemens LSA 2.2.6 . March 1995 1
Overview
Application Comment Climaticrequirementsaccording toformerDIN 40 040
Features
Matching currenttransformer
Multi–tap aux. current transformer to match different current transformer ratios.4AM51 70–7AA: Standard version, primarily for transformer overall differential
protection.4AM52 72–2AA: Version with double thermal withstand capability, e.g. when
connecting to wide–range current transformer (continuous rating2 x �N).
4AM52 72–3AA: Version with higher saturation factor (mainly for the busbardifferential protection).Greater overcurrent factor because of higher voltages
HKG
HKG
HKG
Numerous ratios can beselected using terminalconnections (see page2/31)fN = 45 to 60 Hz
Aux. C.T. for C.T.powered trippingcircuits
Auxiliary current transformer for C.T. powered trip coils in stations where no batterysupply can be made available.4AM50 65–2CB: For 1 A C.T.s4AM50 70–8AB: For 5 A C.T.sSuitable for tripping coils with �N � 0.5 A or 1 A, VN � 40 V or 20 V, P � 20 VA.
HKDHKD
Unlike transducers, nodefined rated power orclass accuracy required.fN = 45 to 60 Hz
Input and matchingcurrent transformer
Input and matching current transformer for phase selective busbar differential pro-tection.4AM51 20–1DA: For 1 A C.T.s4AM51 20–2DA: For 5 A C.T.s1)
HKGHKG
fN = 45 to 60 Hzwith varistor
3–phase summationinput C.T.
Input 3–phase summation current transformer for busbar differential protection.4AM51 20–3DA: For 1 A C.T.s4AM51 20–4DA: For 5 A C.T.s
HKGHKG
fN = 45 to 60 Hzwith varistor
Isolating transformer Isolating transformer for pilot–wire differential protection. Provides galvanic isolationbetween pilot wires and relays.7XR9 500: For differential protection relays 7SD10, 7SD74 and 7SD503
(for use with 3 wires of control cables or protection cables)7XR9 513: For pilot–wires differential relays 7SD24, 7SD76 and 7SD502
(for use with 1 pair of telephone wires).
HKG
HKG
7 kV insulation
20 kV insulation
Climatic requirements: HKG = –25 �C to +125 �Crelative humidity max. 75 %annual average <65 %on 60 days of the year up to 85 %(equally distributed over the year) condensation not permissible
HKD = –25 �C to +125 �Crelative humidity max. 90 %annual average <80 %on 30 days of the year up to 100%(equally distributed over the year) condensation permissible
1) If increased thermal withstand is required type 4AM51 20–4DA is recommended.
Auxiliary current transformers 4AM50, 4AM51, 4AM52 and isolating transformers 7XR95
Fig. 1
7XR9 5004AM5...–. with varistor fitted4AM5.
Siemens AG 1995�
Differential Relays
Siemens LSA 2.2.6 . March 19952
Order No. Windings of auxiliary current transformers Weight, approx.
Number of windings(in relation to each other)
B1
A D2
C F7
E H16
G K1
I M2
L O7
N Q16
P
4AM51 70–7AA Rated current �N1) A
Max. voltage V52
54
514
132
52
54
514
132
3.4 kg
4AM52 72–2AA Rated current �N1) A
Max. voltage V102
104
1014
232
102
104
1014
232
5 kg
4AM52 72–3AA Rated current �N1) A
Max. voltage V54
58
528
164
54
58
528
164
5 kg
4AM50 65–2CB Rated current �N1) A 1 1 1 1 2.4 kg
Number of windings 110
Ka
110
Kb LbLa Kc Lc Kd Ld110 110 Primary windings
Number of windings 88laka
88lbkb
Secondary windings
Rated current �N1) A 1.25 1.25
4AM50 70–8AB Rated current �N1) A 5 5 5 5 2.4 kg
Number of windings 22Ka
22Kb LbLa Kc Lc Kd Ld
22 22 Primary windings
Number of windings 88laka
88lbkb
Secondary windings
Rated current �N1) A 1.25 1.25
Number of windingsB
1A C
2E
4D F
8H
16G I
32500
ZY
4AM51 20–1DA Max. current, continuously AMax. voltage V
6.80.4 0.8
6.81.6 3.2
6.86.4 12.5
0.85200
3.5 kg
4AM51 20–2DA Max. current, continuously AMax. voltage V
260.4 0.8
261.6 3.2
notfitted
0.85200
3.5 kg
4AM51 20–3DA Number of windingsB
3A D
6C F
9E H
18G K
24I M
36L O
90N
500
ZY
3.5 kg
Max. current, continuously AMax. voltage V
41.2
42.4
43.6
47.2
49.6
414.4
236
0.85200
4AM51 20–4DA Number of windingsB
1A D
2C F
3E H
4G K
6I M
8L O
12N
500
ZY
3.5 kg
Max. current, continuously AMax. voltage V
17.50.4
17.50.8
17.51.2
17.51.6
17.52.4
17.53.2
84.8
0.85200
7XR9 500 Isolating transformer for differential protection with threepilot–wires
a10a9 a8
b10 b8b9
Isolating transformer 1 : 1for voltages up to 4,2 kVtest voltage 7 kV
approx. 15 kg
7XR9 513 Isolating transformer for differential protection with two pilot–wires
M1K1 L1
M2 L2K2
Isolating transformer 1 : 1, max. 550 V0,4 A continously, 3 A 10 s, 10 A 1 stest voltage 20 kV, 50 Hz, 1 min
approx. 5 kg
1) Thermal withstand with simultaneous loading of all the windings:1.2 x �N/continuously; 10 x �N/10 s; 25 x �N/1 s.
Auxiliary current transformers 4AM50, 4AM51, 4AM52 and isolating transformers 7XR95
Fig. 2Connection of windings
A B C D E F G H KaLaKbLb ka la
J K L M N O P Q
A B C D E F
G H J Y Z
A B C D E F
Y Z
A B C D E F G H
J K L M N O Y ZKcLcKdLd kb lb
4AM51 70–7AA4AM52 72–2AA4AM52 72–3AA
4AM50 70–8AB4AM50 65–2CB
4AM51 20–1DA 4AM51 20–2DA 4AM51 20–3DA4AM51 20–4DA
Differential Relays
Siemens LSA 2.2.6 . March 1995 3
Isolation transformer 7XR95
Dimension drawings in mm
Fig. 3Auxiliary current transformers 4AM50, 4AM51, 4AM52 without varistor
Type
4AM50
4AM51
4AM52
a
84
84
90
b
96
96
120
c
102
116
110
d
70
84
83
e
88
103
102
f
106
106
123ed
c
f
5.8
ba
g
Fig. 4Auxiliary current transformer 4AM51 with varistor
84
106
7258
11
102.5
5.8
399684
Fig. 5Isolation transformer 7XR9513
100 86
292
220
204
181.
5ca
.55
122
8.5
∅ 6.5
Fig. 6Isolation transformer 7XR9500
143
77
8 220
90
40172
108
162
108
Differential Relays
Siemens LSA 2.2.6 . March 19954
Conditions of Sale and Delivery
Subject to theGeneral Conditions of Supply and Deliveryfor Products and Services of theElectrical and Electronic Industryand to any other conditions agreed uponwith the recipients of catalogs.
�
The technical data, dimensions and weights are subject to change unlessotherwise stated on the individual pagesof this catalog.
The illustrations are for reference only.
We reserve the right to adjust the pricesand shall charge the price applying onthe date of delivery.
Export Regulations
In accordance with present German andUS export regulations export licences (da-ted 02.95) are not required for the prod-ucts listed in this catalog.Export and re–export are therefore
permissible without the approval of therelevant authorities except where currentGerman export regulations contain coun-try–specific restrictions.
Subject to change.Relevant are the criteria stated in the delivery note and in the invoice.An export licence may be required due to country–specific application of theproduct.
Trademarks
All product designations used are trade-marks or product names of Siemens AGor of suppliers.
Dimensions
All dimensions in this catalog are given inmm
Responsible for
Technical contents: Norbert Schuster,Siemens AG, EV S T11, Nürnberg
General editing: Claudia Kühn–Sutiono,Siemens AG, EV MK 2, Erlangen
Conditions of Sale and Delivery � Export Regulations � Trademarks � Dimensions
A 9.91 a
Siemens Aktiengesellschaft
BereichEnergieübertragung und -verteilungGeschäftsgebietZähler, Sekundär- und NetzleittechnikP. O. Box 48 06D-90026 Nürnberg
Order No.: E50001-K5722–A161–A1–7600Printed in the Federal Republic of Germany
PowerTransmissionand Distribution