5006 controller_1
TRANSCRIPT
-
7/31/2019 5006 Controller_1
1/2
25
Masibus' 5006H is simple, tough, reliable and cost effective yet
high performance indicating On/Off controller that has two programmable relay
outputs. Relays can be configured either for alarm or control purpose. Model
5006H has one 4 digit display for process variable. This large display facilitates
plant operator to read process value conveniently even from longer distance.
Control and programming of the unit is performed via the front panel tactile push
buttons which click when operated. All the programme functions are contained
in easy to understand menus. The front panel is robust, easy to clean, non
reflective membrane.
Model 5006H optionally provides transmitter power supply, eliminating the need
for an additional power supply to excite field transmitters. Retransmission output
can be provided for recording purpose or can work as cost effective signal
converter. Serial communication option makes it a smart controller that can
communicate with PC, either for remote configuration or data acquisition
application.
Model 5006H is truly smar t. While many programmable instruments do require
hardware access for input type selection and calibration, Model 5006H totally
eliminates any hardware access or switch settings by its unique single shot
digital calibration technique - all it requires is just a few key strokes at the front
panel keyboard. This unique feature enhances maintenance and operational
reliability of the instrument.
This model is packaged in 96mm x 48mm x 175mm plastic enclosure and can
also be packaged in weather proof IP 55 or flame proof enclosure in wall
mounted.
Model a and a
Micro-controller
based cost-effective
indicator/controller
High performance
Digital calibration
Large, 20mm (0.8")
Red LED display
Two relay output
On-site configurable
and universal
Options :
Transmitter
power supply
Retransmissionoutput (Isolated)
RS 485 serial
communication
Weather proofflame proofenclosure
?
?
?
? /
Features
Controller (Model 5006H)
5006H
AdvancedAutoma
tion-SureSolutions
-
7/31/2019 5006 Controller_1
2/2
Controller (Model 5006H)
26
5006H
TECHNICAL SPECIFICATIONS 5006H
Number of Inputs 1
Input Type, Measurement Range As per table 1& accuracy
Sampling Period 500 mS
Burn out detection Available
Input Impedance J, K , T TC : 77K ohms
R, S TC : 37K ohms
Voltage : 1.2 M ohms
Allowable Input Voltage TC / RTD: 10V DC, Linear: 20V DC
Noise Rejection Ratio
Common Mode > 120 dB (50 Hz)
Normal Mode > 40 dB (50 Hz)
Reference -junction compensation error 2 C (10 to 55C)
Response time
Input to relay o/p