5.1-msc-bschardware installation check standard_guidev2.1.ppt

Upload: pranshu-maithani

Post on 01-Mar-2016

7 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    1/110

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    2/110

    Internal Use Only

    Page2

    http://www.zte.com.cn

    Contents

    A. Installation of Racks, Supports, and Troughs.B. Power Supply and Ground Cale.

    C. Cale and Tail !ier.

    ". #aels.

    $. $%uip&ent Roo&, Control Cha&er'(etwork)anage&ent $%uip&ent.

    !. Cla&ping *ire In )"!.

    G. Base Station BTS Installation.+. !inal Asse&ly.

    I. $%uip&ent Roo& $niron&ent Conditions.-. $ecution /f The S/P Standard operating

    Procedure and Security Regulations.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    3/110

    Internal Use Only

    Page3

    http://www.zte.com.cn

    PPT\WORD !"#$%&'

    !" ()*+ ,-./0 4 ) 5674 ) 8 ) 9

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    4/110

    Internal Use Only

    Page:

    http://www.zte.com.cn

    A ; Equipment Room

    Environment Conditions

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    5/110

    Internal Use Only

    Page

    http://www.zte.com.cn

    Standard An e%uip&ent roo& should

    not e littered with piles of

    packing oes or oards, utshould e clean, orderly, and

    dustproof. The spare o2ects

    re&aining after installation

    should e stacked

    properly 9

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    8/110

    Internal Use Only

    Page?

    http://www.zte.com.cn

    Standard The door and windows of

    the equipment room, as well

    as the cable-through holes

    leading outside, should be

    sealed properly.

    The equipment room is not

    allowed to store flammable,

    explosive, corrosive, or heat

    producing object (such as

    paint, gasoline, and electriccooker).

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    9/110

    Internal Use Only

    Page@

    http://www.zte.com.cn

    Outdoor grounding nuts

    should be provided withanti-rust and anti-corrosion

    treatment.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    10/110

    Internal Use Only

    Page1A

    http://www.zte.com.cn

    B. Installation of Racks, Supports,and Troughs

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    11/110

    Internal Use Only

    Page11

    http://www.zte.com.cn

    The rack must be installed according to the design file, and the deviation

    of installation position must fall into the design deviation scope The installation position of a cabling trough should not have a deviation

    over 50mm.

    The indoor cabling troughs and racks should be smooth and clean, without

    any burr.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    12/110

    Internal Use Only

    Page12

    http://www.zte.com.cn

    Standard 3. When multiple racks are

    arranged side by side, the main

    walkway side should be in one

    line, and the sides of the whole rowof racks are on the same plane,

    with a deviation not more than

    5mm.

    4. The rack (equipment) should

    have a solid base, which isunshakable.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    13/110

    Internal Use Only

    Page13

    http://www.zte.com.cn

    Gap Between Racks

    Standard The adjacent racks should be

    pressed compact, without anyspacing over 3mm.

    The adjacent racks of the

    same type should be uniform

    in height, with a deviation notmore than 2mm.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    14/110

    Internal Use Only

    Page1:

    http://www.zte.com.cn

    Rack Vertical Deviation

    The rack (cable distribution

    frame, or power cabinet)

    should not have a vertical

    error exceeding 1 of its

    height.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    15/110

    Internal Use Only

    Page1

    http://www.zte.com.cn

    Installation of Pressure FootSide pressure at the foot of insulation can not be omitted, and

    ensure that the insulation of expansion bolts and rack is properly

    done.In turn set screw into the insulating gaskets, plain film, shrapnel,

    nuts, fixed when the shrapnel compress.4 rack screw at the base can be used for leveling the rack.Pressure Foot should always be fixed inwards.Locking Nut should be properly tightened.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    18/110

    Internal Use Only

    Page1?

    http://www.zte.com.cn

    The base should have anti-corrosive and anti-rust treatment

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    19/110

    Internal Use Only

    Page1@

    http://www.zte.com.cn

    There are complete bolts for combining

    cabinets, flat washers, and spring washers. Thespring washers are pressed flat between nuts and

    flat washers

    The same type of screws should be mounted in

    the same way, and the exposed nuts should have

    the same length

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    20/110

    Internal Use Only

    Page2A

    http://www.zte.com.cn

    Any rack (equipment) should have earthquake prevention treatment if

    required, and the earthquake resistant feet should have complete accessories,

    which are installed properly

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    21/110

    Internal Use Only

    Page21

    http://www.zte.com.cn

    C: Power Supply and Ground Cable

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    22/110

    Internal Use Only

    Page22

    http://www.zte.com.cn

    The power cable and ground cable terminals should be crimped firmly, and the springwashers should be pressed flat when crimping a bolt.

    Use copper lugs according to the core diameters and bolt diameters. It is not allowed to

    cut off partial core to suit a small copper lug or cut open a copper lug to suit a large bolt.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    23/110

    Internal Use Only

    Page23

    http://www.zte.com.cn

    The copper lugs and the

    bare part of connected

    wire should be wrapped

    tightly with insulating

    tape or shrinkable tubes.

    When insulating tape is

    applied, its color should

    conform to the color

    label requirements.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    24/110

    Internal Use Only

    Page2:

    http://www.zte.com.cn

    When there are redundant crimping

    positions on a power busbar and a

    ground busbar, one bolt can only

    crimp one terminal. When there are

    inadequate crimping positions on a

    power busbar and a ground busbar,one bolt can crimp two terminals at

    most.

    A flat washer and spring washer should be used to crimp a copper lug

    bolt, and the spring washer should be placed between the flat washer

    and the nut.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    25/110

    Internal Use Only

    Page2

    http://www.zte.com.cn

    The power cable, signal cable, and tail fiber should be bundled and wired separately.

    The power cable and signal cable outside a cabinet should be spaced over 5cm apart,

    without overlapping and mixture.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    28/110

    Internal Use Only

    Page2?

    http://www.zte.com.cn

    The racks and cable distribution frames should have complete ground

    cables installed, and the protection ground cables for multiple racks with

    different module numbers should not be connected serially.

    Follow the product

    installation manual to

    use the power cable

    and working ground

    cable with required

    core diameters, and

    the same color orjust follow the design

    requirements.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    29/110

    Internal Use Only

    Page2@

    http://www.zte.com.cn

    Its not

    allowed

    Label directions

    are inconsistent

    Irregular cabling

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    30/110

    Internal Use Only

    Page3A

    http://www.zte.com.cn

    D: Cable and Tail Fiber

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    31/110

    Internal Use Only

    Page31

    http://www.zte.com.cn

    In the case of upward

    cabling, the cables should

    be mounted directly along

    the cabling rack, and should

    not be laid tightly against

    the heat-sink panel on thetop of the cabinet. When

    cabling along the upper part

    of the cabinet is necessary,

    the cables should be spaced

    10cm away from the heat-

    sink panel on the top of thecabinet.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    32/110

    Internal Use Only

    Page32

    http://www.zte.com.cn

    The downward cables, when piled up on the floor, cannot exceed of

    the floor height, or ventilation and heat dissipation may be affected

    For the cables outside a cabinet, the part over one meter away from the

    cabinet is not allowed to intercross

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    33/110

    Internal Use Only

    Page33

    http://www.zte.com.cn

    The power cable, signal cable, andtail fiber should be bundled and

    wired separately .The power

    cable and signal cable outside a

    cabinet should be spaced over

    5cm apart, without overlapping

    and mixture

    The insulating jacket of a cable is

    in good condition, without core

    exposed

    The cables on a cabling rack

    should be bound

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    34/110

    Internal Use Only

    Page3:

    http://www.zte.com.cn

    In a cabinet, the cables on the two sides should be wired in a correct

    sequence. That is, the cables wired farther should be bundled on the

    side far from the connection position, and the cables wired nearer

    should be bundled on the side closer to the connection position.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    35/110

    Internal Use Only

    Page3

    http://www.zte.com.cn

    Its wrong!

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    38/110

    Internal Use Only

    Page3?

    http://www.zte.com.cn

    cabling and straping in racks

    Distance betweencable tie should be

    consistent

    !trunk cables

    subscriber cables

    (single racks )

    subscriber cables

    (multiple racks )

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    39/110

    Internal Use Only

    Page3@

    http://www.zte.com.cn

    Cabling and Straping in DDF

    The reserved wires at the rear side of the DDF,

    MDF and ODF terminal boards should be

    orderly, with basically uniform radian and

    length. The reserved wires are long enough

    when they will not prevent the terminal boards

    from turnover during debugging

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    40/110

    Internal Use Only

    Page:A

    http://www.zte.com.cn

    cabling and straping on cabling rack

    "ower cables subscriber cables

    Trunk cables

    When the bundled cables make a turn, the

    straps should be applied to the two sides ofthe turn to avoid breaking the cores by

    excessive force on the turn

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    41/110

    Internal Use Only

    Page:1

    http://www.zte.com.cn

    Cable surface should be clean without construction marks, and the

    insulating layer of a jacket is undamaged

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    42/110

    Internal Use Only

    Page:2

    http://www.zte.com.cn

    When the straps are tightened,

    the redundant part should be cut

    off from the root, leaving no

    burr. When used outdoors, the

    strap end can be reserved

    properly without any burr, but

    there should not be more than 10

    holes

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    43/110

    Internal Use Only

    Page:3

    http://www.zte.com.cn

    When the strapped cables are laid, the

    straps of the harnesses running in thesame direction should face their heads

    in the same direction

    In the case of wiring outside a rack, the

    straps of the cables laid on the floor

    should be spaced at intervals of 3-4times the diameter of the cable bundle.

    The maximum spacing between the

    straps on a horizontal cabling rack

    should not be over two times the

    spacing of horizontal iron bars of this

    cabling rack. On a vertical cabling

    rack, the cables should be strapped at

    each horizontal iron bar

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    44/110

    Internal Use Only

    Page::

    http://www.zte.com.cn

    he spacing between

    straps along cables in a

    horizontal cabling

    trough: the cables should

    be strapped once behind

    the upper horizontalholder, and the spacing

    between the straps in the

    horizontal direction

    should not be larger than

    20cm

    For subscriber line cables or jacketed twisted-pair cables, any crack on the insulating

    layer of their jackets must be bound and sealed with insulating tape

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    45/110

    Internal Use Only

    Page:

    http://www.zte.com.cn

    The tail fiber that leaves a fiber

    splitting box or is wired

    outside a rack or between a

    rack and a tail fiber trough

    should wear a protection tube

    As for the protection tube oftail fiber, its end that enters a

    rack or tail fiber trough should

    extend inside the rack or tail

    fiber and is fixed. There should

    be no heavy object crossing

    through the protection tube

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    48/110

    Internal Use Only

    Page:?

    http://www.zte.com.cn

    The cut at the end of a tail fiber tube should be neat without burr, and thejoint or end of a tube should be bound with electrical insulating tape toprevent cutting the tail fiber

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    49/110

    Internal Use Only

    Page:@

    http://www.zte.com.cn

    The tail fiber should wear a protection tube.

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    50/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    51/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    52/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    53/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    54/110

    l O l

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    55/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    56/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    57/110

    Internal Use Only

    Page

    http://www.zte.com.cn

    For exposed pigtail usethe yellow tape wrapped

    to ensure the appearance

    I l U O l

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    58/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    59/110

    Internal Use Only

    Page

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    60/110

    Internal Use Only

    Page=A

    http://www.zte.com.cn

    Cable Routing

    I t l U O l

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    61/110

    Internal Use Only

    Page=1

    http://www.zte.com.cn

    E: Label

    I t l U O l

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    62/110

    Internal Use Only

    Page=2

    http://www.zte.com.cn

    Label

    $ach power cale, ground cale, signal cale, tail fier, and &icro coaialcale should e &arked with one lael. !or the &ulti0core coaialtrunk cales, the laels should e applied to a unit of &ulti0corecoaial cales instead of the cores if there are serial nu&ers printedon the cores, and one lael should e applied to each pair of 346oh&trunk cales. A lael should e pasted 4c& away fro& the end of a

    cale or the pro2ecting orifice of a &ulti0core coaial cale. It isunnecessary to lael a ground cale of a cainet door or a protectionground cale of a side panel

    A lael should e written neatly and printed in Arial typeface. Ifcircu&stances do not per&it, technical lettering should e applied.The content for&at should confor& to product specifications, and

    indicate local and re&ote positions, which should not e &arkedsi&ply with nu&erals.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    63/110

    Internal Use Only

    Page=3

    http://www.zte.com.cn

    The labels should use ZTE dedicated pasters, which should be applied to

    the positions required by the product manuals. the installation position

    and the direction should be consistent.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    64/110

    Internal Use Only

    Page=:

    http://www.zte.com.cn

    The rows and columns

    of racks should be

    labeled in an orderly,

    uniform, and unrepeated

    manner in conformity

    with the engineering

    design requirements or

    the planning of the ZTE

    devices in a whole

    equipment room

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    65/110

    Internal Use Only

    Page=

    http://www.zte.com.cn

    The specifications of a trunk cable label: rack number (RSM, RSU or SDH) 7 layer

    number7slot number7the sequence number (00~15) of PCM port T or R; DDF - rack

    number 7 layer number (usually represented by 1, 2, 3 86) 7 the sequence number

    (00~09) of PCM port T or R

    #o data

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    68/110

    Internal Use Only

    Page=?

    http://www.zte.com.cn

    The specifications of thecontent of a power cable

    label: remote end: rack

    number 7 device type 7

    power cable property;

    local end: rack number 7

    device type7power cableproperty; row number &

    rack number: A01,

    A02...B01, B028; device

    type: ZXJ10, ZXA10. For

    a DC distribution frame

    or a head of a cabinetcolumn, the power cable

    property: -48V, GND and

    PE.

    #o

    label

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    69/110

    Internal Use Only

    Page=@

    http://www.zte.com.cn

    A label about application

    specifications of a circuit breaker in a

    power cabinet should indicate the

    connecting direction, that is, thecabinet number

    In a power distribution cabinet, the

    breakers should be labeled in a neat

    manner

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    70/110

    Internal Use Only

    Page>A

    http://www.zte.com.cn

    The specifications of a tailfiber label: In a rack, single-optical-interface board (FBIand SDT): rack number(RSM, RSU or SDH) 7layer number7slot number7 T or R; multi-optical-interface board (CFBI): racknumber (RSM, RSU or

    SDH)7layer number7slotnumber 7 the sequencenumber of port T or R; arack externally connected:rack number (RSM, RSU orSDH)7layer number7slotnumber 7 T or R; ODF 7

    rack number7layer number7 the sequence number ofPCM port T or R

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    71/110

    Internal Use Only

    Page>1

    http://www.zte.com.cn

    "roper labeling re$uired

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    72/110

    Internal Use Only

    Page>2

    http://www.zte.com.cn

    Labeling should be done

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    73/110

    Internal Use Only

    Page>3

    http://www.zte.com.cn

    F Equipment Room Control

    Chamber/Network Management Equipment

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    74/110

    Internal Use Only

    Page>:

    http://www.zte.com.cn

    When the power cable and signal

    cable of an alarm box are wiredbelow the floor and along thewall surface or pass through awall, they should be laid in a tubeor cabling trough, and the surpluspart should be coiled and placedbelow the floor or on a cablingladder at the alarm box side

    The alarm box should be installedin a proper position, so that itsbase can be parallel with thefloor. The cabling trough should

    be mounted against the leading-out side of the alarm box, withoutexposing the head of a cable.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    75/110

    Internal Use Only

    Page>=

    http://www.zte.com.cn

    The surface of a computer, peripherals, and

    alarm box should be clean without any

    stain. There are no sundries and other

    objects around that may affect security of

    these devices.

    When the network management terminal case

    and the mental cases of some devices like

    an inverter are connected to the protection

    ground of the directly linked

    communication devices, the neutral line

    ground of the AC network must be

    disconnected

    The network management equipment and

    accessories (like power busbar) should be

    fixed and placed for the needs of security

    in an effort to avoid any disoperation.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    77/110

    Internal Use Only

    Page>>

    http://www.zte.com.cn

    The RJ-45 connector of a network cable is crimped firmly and connectedcorrectly and reliably.

    The fixture of a

    computer and itsperipheral components

    should be firm.

    The dust-proof baffles

    and their componentsof a computer and its

    peripherals should be

    complete.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    78/110

    Internal Use Only

    Page>?

    http://www.zte.com.cn

    Equipment Room Control Chamber

    Standard The wired network cables

    should be tied with proper

    force in a neat and orderly

    manner without

    intersection.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    79/110

    a U O y

    Page>@

    http://www.zte.com.cn

    G Clamping Wire In DDF MDF

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    80/110

    y

    Page?A

    http://www.zte.com.cn

    A horizontal or vertical clamping

    bar should avoid overlapping

    during threading, and its insulating

    part should be in good condition

    The accessories of DDF, MDF and

    ODF terminal boards should be

    fixed firmly and orderly

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    81/110

    y

    Page?1

    http://www.zte.com.cn

    The accessories, like alocator card, of a

    connector should be

    installed completely

    All connectors are in

    good contact, and are

    wrapped with heat-

    shrinkable tubes or

    insulating tape

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    82/110

    y

    Page?2

    http://www.zte.com.cn

    I Final Assembly

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    83/110

    y

    Page?3

    http://www.zte.com.cn

    The racks, doors, and top baffles are

    not seriously damaged or transformed,

    without scratch or paint peeling off

    (over 20mm2 metal exposed). The

    peeled paint, if any, should be redone.In the case of damage during

    transport, it is required to notify

    immediately the project manager of

    the regional office and start the re-

    shipment procedure.

    The surface of a rack should be clean

    without any scratch.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    84/110

    y

    Page?:

    http://www.zte.com.cn

    If the power distribution

    cabinets are arranged

    side by side with other

    types of cabinets, side

    panels are needed for

    inter-rack isolation

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    85/110

    y

    Page?

    http://www.zte.com.cn

    Labeling and proper routing should be done.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    88/110

    Page??

    http://www.zte.com.cn

    An empty optical

    loop interface and

    empty socket should

    wear a protection cap

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    89/110

    Page?@

    http://www.zte.com.cn

    Any unused connector

    should be put into a cabling

    trough .

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    90/110

    Page@A

    http://www.zte.com.cn

    The racks are not allowed to serve

    as stores to keep sundries like tools

    and parts .

    A rack should contain noengineering remainders and wastes,

    like surplus cable ties and bolts.

    The interior of a cabinet and the

    base floor have no apparent dust .

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    91/110

    Page@1

    http://www.zte.com.cn

    Improper labeling

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    92/110

    Page@2

    http://www.zte.com.cn

    Generally not allowed

    to label here, if indeedit is necessary, but also

    standardize writing

    (printing), and pasted

    them neatly

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    93/110

    Page@3

    http://www.zte.com.cn

    Labeling not done according to the standard

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    94/110

    Page@:

    http://www.zte.com.cn

    Writing on panel itself is strictly not allowed

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    95/110

    Page@

    http://www.zte.com.cn

    Each operation plane of a rack

    should be equipped with one

    antistatic handle ring, and the

    antistatic mounting base must

    be installed firmly. The frames

    that are not in a rack but stand

    alone with pluggable boards

    also need handle rings, which

    are clamped on the case

    grounded

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    98/110

    Page@?

    http://www.zte.com.cn

    antistatic handle ring 2

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    99/110

    Page@@

    http://www.zte.com.cn

    After a device is installed,

    the nearby antistatic floor

    should be installed smooth

    and firm, and the base

    should be in tight contactwith the floor. The floor

    removed during

    construction must be re-

    installed smooth and firm

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    100/110

    Page1AA

    http://www.zte.com.cn

    The floor removed during construction must be re-installed

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    101/110

    Page1A1

    http://www.zte.com.cn

    Rack and the floor is not flush

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    102/110

    Page1A2

    http://www.zte.com.cn

    Rack out of line I (off-

    line hole) protection

    section (or sleeves) is

    not installed or installedincorrectly

    Off-line holes of the

    cuffs is to protect the

    cable to use and can

    only be broken cross,

    can not be dismantled

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    103/110

    Page1A3

    http://www.zte.com.cn

    The rodent-resistant anddustproof sealing boards at

    the cable inlet and outlet of

    a rack should be preserved

    well and installed correctly

    and firmly. The cable inlet

    and outlet should be sealed

    as perfectly as possible to

    minimize the gap. On the

    site, it is allowed to use

    neat, good-looking,

    insulating, and fire-resistant

    materials for reliable

    enclosure

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    104/110

    Page1A:

    http://www.zte.com.cn

    The rodent-resistant and dustproof sealing boards at the cable inlet and outlet of a rack

    should be installed.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    105/110

    Page1A

    http://www.zte.com.cn

    A board is unpackedand plugged/unpluggedin conformity with theantistatic operationspecifications. Theoperator must wearantistatic wrist straps,and avoid touchingdirectly the rear of acomponent or a circuitboard.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    108/110

    Page1A?

    http://www.zte.com.cn

    Antistatic handle ring5s should be used

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    109/110

    Page1A@

    http://www.zte.com.cn

    An equipment room

    should not be littered

    with piles of packing

    boxes or boards, but

    should be clean, orderly,

    and dustproof. The spare

    objects remaining after

    installation should be

    stacked properly.

    Internal Use Only

  • 7/18/2019 5.1-MSC-BSCHardware Installation Check Standard_GuideV2.1.ppt

    110/110

    During drilling, use

    a cleaner to absorb

    the dusts.