CLIENT: - M/S PEPSICO HOLDING PVT. LTD. PROJECT: - AQUFINA (PHASE-III) PLANT AT MAHUL- MUMBAI. Bus Bar Calculation for Main LT Panel A. Bus Bar size calculation for 3200A Rating Panel: - CONDITIONS Rating Current: 3200Amp. System: 415Vac, TPN, 50Hz. Fault Level: 50KA. For 1 Sec. Operation Temp: 40° C rise over 45° C ambient. CONSIDERATION Enclosure size: 1400mm. wide X 400mm. height Bus bar Size: 2:200x10 per Ph., 1:200x10 for Neutral. Bus bar material: Electrolytic gr. Al. (IS 63401/AA6101) CALCULATION 1. AC Current rating for Dual Al. Flats 200x10mm considered = 4750Amp. (As per Table – 8.4 as INDAL hand book) 2. Ambient correction factor (k1) 45° C rise over 35° C (ambient) = .88 (As per Table – 5 as INDAL hand book) If ambient Temp. 45° C instead of 35° C than De-rating Factor = 1-θ° C x α θ = Temp difference = 45° C - 35° C = 10 α = Resistance-Temp. Coefficient for Al. Bus= 0.00403 k1A = 1-10 x 0.00403 = 0.96 MILESTONES SWITCHGEARS PVT. LTD. Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.

Upload: merrel-ross

Post on 29-Oct-2014

308 views

Category:

Documents


18 download

TRANSCRIPT

Page 1: 52189101 Busbar Calculation

CLIENT: - M/S PEPSICO HOLDING PVT. LTD.

PROJECT: - AQUFINA (PHASE-III) PLANT AT MAHUL- MUMBAI.

Bus Bar Calculation for Main LT Panel

A. Bus Bar size calculation for 3200A Rating Panel: - CONDITIONS

Rating Current: 3200Amp.

System: 415Vac, TPN, 50Hz.

Fault Level: 50KA. For 1 Sec.

Operation Temp: 40°C rise over 45°C ambient.

CONSIDERATION

Enclosure size: 1400mm. wide X 400mm. height

Bus bar Size: 2:200x10 per Ph., 1:200x10 for Neutral.

Bus bar material: Electrolytic gr. Al. (IS 63401/AA6101)

CALCULATION

1. AC Current rating for Dual Al. Flats 200x10mm considered = 4750Amp.(As per Table – 8.4 as INDAL hand

book)

2. Ambient correction factor (k1) 45°C rise over 35°C (ambient) = .88(As per Table – 5 as INDAL hand book)

If ambient Temp. 45°C instead of 35°C than De-rating Factor = 1-θ° C x αθ = Temp difference = 45°C - 35°C = 10α = Resistance-Temp. Coefficient for Al. Bus= 0.00403

k1A = 1-10 x 0.00403 = 0.96

MILESTONES SWITCHGEARS PVT. LTD.Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.

Page 2: 52189101 Busbar Calculation

3. Enclosure correction factor (k2) ratio of total conductor bus bar cross-section to enclosure cross-section.

(3 x 2 x 200 x 10) x 100--------------------------------- = 2%

1400 x 400De-rating factor for enclosure = 0.82

(As per Table – 5 as INDAL hand book)

4. Correction factor (k3) for busbar material = 15. Up-rating factor (k4) for PVC Sleeving bus bar = 1

6. Total Combined De-Rating factor = k1xK1Axk2xk3xk4= 0.88 x 0.96 x 0.82 x 1 x 1= 0.693

So, actual rating of considered busbar = 4750 x 0.693 = 3291Amp.

Conclusion: -It means 2:200x10mm Al. Bus Bar is much sufficient for 3200A Rating as per actual operating conditions.

B. Minimum Conductor size for Stand 50KA Fault : -

While considering short circuit condition, assuming a steady state average temperature of 75°C and final temperature of 160°C then required bus section:

CALCULATION: (As per table – 17)

Let θ f =Final conductor temp after the fault = 160°C.θ I = Initial conductor temp before the fault = 75°C.A = Cross sectional area of conductor (Sq. inch) =?T = Duration of fault (sec.) = 1 Sec.Isc = Short circuit current = 50KA.

A θ f + 258

Or Isc = 14 x 10 ------ log10 ----------------

T θ I + 258

MILESTONES SWITCHGEARS PVT. LTD.Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.

Page 3: 52189101 Busbar Calculation

Isc x TOr A = ----------------------------------------------

θ f + 258

14 x 10 log10 ----------------

θ I + 258

50,000 x 1

Or A = ---------------------------------------------- = 0.93 in 160 + 258

14 x 10 log10 ---------------- 75 + 258

Or A = 600 mm. Considered bus section = 2x200x10 = 4000mm.

Conclusion: -It means 2:200x10mm Al. Bus Bar is much sufficient for stand 50KA Fault Current for 1Sec.

C. TEMPERATURE RISE CALCULATION OF CONDUCTORS : -

Max. Temperature at full Load condition: - i.e. When 3200Amp. Flows thru steady state temperature of 45C.

Full Load Current T max = Ambient X ------------------------------------------------------- X Allow T rise

Actual Current Rating of used Conductors

45 + (3200 / 3291) x 40 = 82.8C which is within the limit of 85C [45+40].

Summary: Hence the designed bus bar for Main Panel is OK & within the safe limit.

Reference: INDAL hand bookAnd IS: 8623 (Part – 1) of 1993.

MILESTONES SWITCHGEARS PVT. LTD.Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.

Page 4: 52189101 Busbar Calculation

Bus Bar Calculation for Bus Duct

A. Bus Bar size calculation for 3200A Rating Bus Duct: - CONDITIONS

Rating Current: 3200Amp.

System: 415Vac, TPN, 50Hz.

Fault Level: 50KA. For 1 Sec.

Operation Temp: 40°C rise over 45°C ambient.

CONSIDERATION

Enclosure size: 750mm. wide X 450mm. height

Bus bar Size: 2:200x10 per Ph., 1:200x10 for Neutral.

Bus bar material: Electrolytic gr. Al. (IS 63401/AA6101)

CALCULATION

1. AC Current rating for Dual Al. Flats 200x10mm considered = 4750Amp.(As per Table – 8.4 as INDAL hand book)

2. Ambient correction factor (k1) 45°C rise over 35°C (ambient) = .88(As per Table – 5 as INDAL hand book)

If ambient Temp. 45°C instead of 35°C than De-rating Factor = 1-θ° C x αθ = Temp difference = 45°C - 35°C = 10α = Resistance-Temp. Coefficient for Al. Bus= 0.00403

k1A = 1-10 x 0.00403 = 0.96

MILESTONES SWITCHGEARS PVT. LTD.Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.

Page 5: 52189101 Busbar Calculation

3. Enclosure correction factor (k2) ratio of total conductor bus bar cross-section to enclosure cross-section.

(3 x 2 x 200 x 10) x 100--------------------------------- = 3.5%

750 x 450De-rating factor for enclosure = 0.78

(As per Table – 5 as INDAL hand book)

4. Correction factor (k3) for bus bar material = 15. Up-rating factor (k4) for Black Matt Painted bus bar = 1.2

6. Total Combined De-Rating factor = k1xK1Axk2xk3xk4= 0.88 x 0.96 x 0.78 x 1 x 1.2= 0.79

So, actual rating of considered bus bar = 4750 x 0.79 = 3752Amp.

Conclusion: -It means 2:200x10mm Al. Bus Bar is much sufficient for 3200A Rating as per actual operating conditions.

Summary: Hence the designed bus bar for Bus Duct is OK & within the safe limit.

Reference: INDAL hand bookAnd IS: 8623 (Part – 1) of 1993.

Bus Bar Calculation for Other Panels [Main Bus]

Sl. No.

Used Current

Rating in Amp.

Used Bus Bar Size:

Current Rating as per INDAL-

Hand Book Table No. 8.4

in Amp.

Max.[Approx] Total De-

Rating Factor

Actual Current Rating

1.0 1600Amp.

2x100x10 – For Ph.

1x100x10 – For N.2650Amp. 0.7 1855Amp

2.0 800Amp. 100x10 – For Ph.100x6 – For N. 1565Amp. 0.7 1095Amp

3.0 630Amp. 80x10 – For Ph.80x6 – For N. 1250Amp. 0.7 875Amp

MILESTONES SWITCHGEARS PVT. LTD.Tel: (0124) 4002970, 5002971, Telefax: (0124) 4002973.