5303 271 v1 - viessmann-us.com · generalinformation 7 application example 1 (continued) system...
TRANSCRIPT
Service Instructionsfor use by heating contractor
Vitotronic 300
Model KW3
Weather-responsive indoor/outdoor, digital boiler controlfor heating systems with one or more heating circuits
VVVVIIIITTTTOOOOTTTTRRRROOOONNNNIIIICCCC 333300000000
Read and save these instructions
for future reference.
IMPORTANT
5303 271 v1.5 09/2011
Ple
ase
file
inS
ervic
eB
ind
er
Safety instructions
2
Safety Instructions
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation and operation. Failure to comply with
the instructions listed below and details printed in these instructions can cause product/property damage, severe personal injury,
and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual
subsections).
Licensed professional heating
contractor
The installation, adjustment, service,and maintenance of this equipmentmust be performed by a licensedprofessional heating contractor.Please see sections
entitled “Safety” and
“Important Regulatory and
Installation Requirements”.
Product documentation
Read all applicable documentation
before commencing installation. Storedocumentation near boiler in a readilyaccessible location for reference inthe future by service personnel.For a listing of applicable
literature, please see
section entitled “Important
Regulatory and Installation
Requirements”.
Advice to owner
Once the installation work iscomplete, the heating contractor mustfamiliarize the systemoperator/ultimate owner with allequipment, as well as safetyprecautions/requirements, shut-downprocedure, and the need forprofessional service annually beforethe heating season begins.
Warranty
Information contained in this andrelated product documentation mustbe read and followed. Failure to do so
renders warranty null and void.
Safety Terminology
One or more of the following terms are used throughout this manual to bring attention to the presence of potential hazards or
important product information. Please heed the advice given!
Helpful hints for installation, operation or
maintenance which pertain to the product.
5303271v1.5
Indicates an imminently hazardous
situation which, if not avoided, will
result in death, serious injury or
substantial product/property damage.
DANGER
Indicates an imminently hazardous
situation which, if not avoided, could
result in death, serious injury or
substantial product/property damage.
WARNING
Indicates an imminently hazardous
situation which, if not avoided, may
result in minor injury or product/property
damage.
CAUTION
IMPORTANT
Index
3
Page
Safety Instructions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information Overview of Boiler Coding Cards 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Example 1
System with one direct-connected heating circuitwithout mixing valve 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Example 2
System with one heating circuit with mixing valve 9. . . . . .
Application Example 3
System with one direct-connected heating circuitwithout mixing valve and one with mixing valve 13. . . . . . . . . . . .
Application Example 4
System with two heating circuits with mixing valves 17.
Application Example 5
System with one direct-connected heating circuitwithout mixing valve and two heating circuitswith mixing valves 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Information Controls and display elements 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview of Service Levels 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting heating curves 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating circuit control 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tank temperature control 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperatures, Boiler Coding Cards and Scans 34. . . . . . . . . . . . . . .
Scan 1 to 5 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Test 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning Operating Status Information 37. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning and Resetting Service Information 39. . . . . . . . . . . . . . . . . . .
Components Components from the parts list 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flue gas temperature sensor 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Extension kit for mixing valve circuit 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote control 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Room temperature sensor 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching module V 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
KM BUS expansion module 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input module extension 0-10V 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5303271v1.5
4
Troubleshooting Diagnosis
Fault with fault message on control unit 57. . . . . . . . . . . . . . . . . . . . . .
Retrieving fault codes from error log(fault history) 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Information Codings
Accessing coding level 1 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coding 1 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coding 2 information 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing coding level 2 67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting codings to factory default settings 67. . . . . . . . . . . . . .
Coding 2 68. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram 84. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List 86. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5303271v1.5
General Information
5
Overview of Boiler Coding Cards
Vitotronic 300, Part No. Z001 231,
in conjunction with
Required boiler coding
card
Vitola 200, VB2 Series E1
Vitogas 100, GS1 Series85 to 184 MBH /22 to 154 kW
255 to 515 MBH /72 to 144 kW
Vitogas 50, RS Series
F0
C6
C6
Vitorond 100, VR1 Series F1
5303271v1.5
General Information
6
Application Example 1
System with one direct-connected heating circuit without mixing valve
Boiler with Vitotronic 300Domestic hot water tankVitotrol, Switching Module-V,KM-BUS Expansion Module for theconnection of several KM-BUSparticipantsHeating circuit without mixing valvePower Pump ModuleLow water cut-off device
Connectors
Outdoor temperature sensorBoiler temperature sensorDHW tank temperature sensorKM-BUS participantsExtension fortwo-stage/modulating burner*1
Heating circuit pumpBoiler circuitDHW production pump(accessory)DHW recirculation pump(field supplied where required)Power supply(120 VAC, 60 Hz)Burner, single-stage*1
Burner, two-stage/modulating*1
Available System Accessories
Vitotrol remote controlRoom temperature sensorSwitching Module-V for expandingthe range of control functions
KM-BUS Expansion ModuleFlue gas temperature sensor
*1Included in standard boiler equipment.
5303271v1.5
General Information
7
Application Example 1 (continued)
System with one direct-connected heating circuit without mixing valve (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
System type 00: 1 ----- System without DHWtank 00: 1(factory default setting)
System with DHW tank00: 2 (setting changedautomatically)
Burner type 02: 0(single-stage)
02: 1 (two-stage)02: 2 (modulating)
The two-stage/modulatingextension is required fortwo-stage and modulatingburners (included in standardboiler equipment)
Vitotrol 200(accessory)
orVitotrol 300(accessory)
A0: 0
A0: 0
----------
----------
Coding ”A0: 0” is changedautomatically to ”A0: 1”.
Coding ”A0: 0” is changedautomatically to ”A0: 2”.
Room temperature sensor(accessory), only in conjunctionwith remote control
---------- ---------- For measuring roomtemperature when remotecontrol cannot be placed in asuitable location. The roomtemperature sensor isactivated via a coding switchon the remote control.
Sensor/Burner fault indicationmodule(included in standard equipment)
92: 1 ---------- For displaying and transmit-ting fault messageswhen fixed high limit isactivated
when additional safetyequipment operates
KM-BUS Expansion Module(accessory)
---------- ---------- Required when more thanone KM-BUS participant isconnected
Switching Module-V(accessory)
94: 0 ---------- Required for external burneractivation and disable. TheSwitching Module-V is auto-matically recognized.Coding ”94: 0” is changedautomatically to ”94: 2”.
5303271v1.5
General Information
8
Application Example 1 (continued)
System with one direct-connected heating circuit without mixing valve (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
Flue gas temperature sensor(accessory)
---------- ---------- For displaying the flue gastemperature and for monitoringhigh limit values. The flue gastemperature sensor isautomatically recognized.
Coding switch settings on Vitotrol 200 and Vitotrol 300
(Coding switch on rear of remote control)
The respective remote control must be assigned to a heating circuit via the coding switches.
Remote control effective for Vitotrol 200Coding switch S6
Vitotrol 300Coding switch S30
Heating circuit without mixing valve(factory default setting)
If separate room temperature sensor isconnected
Coding switch 3 to ”ON” Coding switch 3 to ”ON”
5303271v1.5
General Information
9
Application Example 2
System with one heating circuit with mixing valve
Boiler with Vitotronic 300Domestic hot water tankKM-BUS Expansion Module(accessory) for the connection ofseveral KM-BUS participantsHeating circuit with mixing valveMixing valve actuator accessory kitPower Pump ModuleLow water cut-off device
Connectors
Outdoor temperature sensorSupply temperature sensor(accessory)*2
Boiler temperature sensorDHW tank temperature sensorReturn water temperature sensor(accessory)*2,3
KM-BUS participantExtension fortwo-stage/modulating burner*4
M1 Heating circuit pump*2
Mixing valve circuitDHW production pump(accessory)DHW recirculation pump(installed on site)Power supply(120 VAC, 60 Hz)Burner, single-stage*4
Burner, two-stage/modulating*4
Available System Accessories
Vitotrol remote controlRoom temperature sensorReturn water temperature sensorSwitching Module-V for expandingthe range of control functions
KM-BUS Expansion ModuleFlue gas temperature sensor
*1 Supply check valve, only required if piping connection is made on one common boiler return.*2 To be connected in actuator accessory kit.*3 In connection with underfloor heating when control measures supply and return water temperature.*4 Included in standard boiler equipment.
5303271v1.5
General Information
10
Application Example 2 (continued)
System with one heating circuit with mixing valve (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
System type 00: 1 System without DHWtank 00: 3
System with DHWtank 00: 4
Coding is automaticallychanged to ”00: 5” or”00: 6”, must be resetmanually
Burner type 02: 0(single-stage)
02: 1 (two-stage)02: 2 (modulating)
The two-stage/modulatingburner extension is requiredfor two-stage andmodulating burners (includedin standard equipment)
Mixing valve actuator accessorykit (accessory)
---------- ---------- For assignment to heatingcircuit refer to page 12.
Vitotrol 200(accessory)
orVitotrol 300(accessory)
A0: 0
A0: 0
----------
----------
Coding ”A0: 0” is changedautomatically to ”A0: 1”.
Coding ”A0: 0” is changedautomatically to ”A0: 2”.
Room temperature sensor(accessory), only in conjunctionwith remote control
---------- ---------- For measuring the roomtemperature when theremote control cannot beplaced in a suitable location.The room temperaturesensor is activated via acoding switch on the remotecontrol.
Sensor/burner fault indicationmodule
92: 1 ---------- For displaying andtransmitting fault messageswhen fixed high limit hasopened
when additional safetyequipment operates
KM-BUS Expansion Module(accessory)
---------- ---------- Required when more thanone KM-BUS participant isconnected
Switching Module-V(accessory)
94: 0 ---------- Required for external burneractivation and disable. TheSwitching Module-V isautomatically recognized.Coding ”94: 0” is changedautomatically to ”94: 2”.
5303271v1.5
General Information
11
Application Example 2 (continued)
System with one heating circuit with mixing valve (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
Return water temperature sensor(accessory)
---------- ---------- For measuring the returnwater temperature. Thereturn water temperaturesensor is activated via acoding switch in actuatoraccessory kit (see followingpage).
Flue gas temperature sensor(accessory)
---------- ---------- For displaying the flue gastemperature and monitoringhigh limit values. The fluegas temperature sensor isautomatically recognized.
5303271v1.5
General Information
12
Application Example 2 (continued)
System with one heating circuit with mixing valve (continued)
Coding switch settings for mixing valve motor, part no. 7133 392 (old version)
(Coding switches on mother board of mixing valve motor)
Effective for heating circuit with mixingvalve
When connecting a return watertemperature sensor (accessory), thecoding switch must be reset.(Set coding switch 3 to ”ON”).
Coding switch settings on Vitotrol 200 or Vitotrol 300
(Coding switch on rear of remote control)The respective remote control must be assigned to the heating circuit via the coding switches.
Remote control effective for Vitotrol 200Coding switch S6
Vitotrol 300Coding switch S30
Heating circuit M1(mixing valve circuit)Heating circuit is assigned to heatingcircuit selector button
Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
Coding switch 1 to ”OFF”
Coding switch 2 to ”ON”
If separate room temperature sensor isconnected
Coding switch 3 to ”ON” Coding switch 3 to ”ON”
Coding switch settings for mixing valve motor, part no. 7837 524 (new version)
(the rotary sletector is located on the motherboard of the mixing valve controller)
Heating circuit that mixing valve affects Connected sensors Rotary selector position
Heating circuit with mixing valve, M2 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’2’ (factory set)
’3’
Heating circuit with mixing valve, M3 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’4’ (factory set)
’5’
5303271v1.5
Factory defaultsetting
General Information
13
Application Example 3
System with one direct-connected heating circuit without mixing valve and one heating circuit with mixing valve
Boiler with Vitotronic 300Domestic hot water tankHeating circuit without mixingvalveKM-BUS Expansion Module(accessory) for the connection ofseveral KM-BUS participantsHeating circuit with mixing valveMixing valve actuator accessory kitPower Pump ModuleLow water cut-off device
Connectors
Outdoor temperature sensorSupply temperature sensor(accessory)*2
Boiler temperature sensorDHW tank temperature sensorReturn water temperature sensor(accessory)*2,3
KM-BUS participantExtension fortwo-stage/modulating burner*4
Boiler circuit pumpM1 Mixing valve circuit pump*2
DHW production pump(accessory)DHW recirculation pump(field supplied where required)Power supply(120 VAC, 60 Hz)Burner, single-stage*4
Burner, two-stage/modulating*4
Available System Accessories
Vitotrol remote controlRoom temperature sensorReturn water temperature sensorSwitching Module-V for expandingthe range of control functions
KM-BUS Expansion ModuleFlue gas temperature sensor
*1 Supply check valve, only required if piping connection is made on one common header.*2 To be connected in actuator accessory kit.*3 In connection with underfloor heating when control measures supply and return water temperature.*4 Included in standard equipment.
5303271v1.5
General Information
14
Application Example 3 (continued)
System with one direct-connected heating circuit without mixing valve and one heating circuit with mixing valve (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
System type 00: 1 ---------- System without DHWtank 00: 5 (changedautomatically)
System with DHW tank00: 6 (changedautomatically)
Single-/Multi-family house 7F: 1The switching times for theDHW production pump, theDHW recirculation pump andthe holiday program areidentical for all heatingcircuits
7F: 0The switching times for theDHW production pump, theDHW recirculation pump andthe holiday program can beset separately for all heatingcircuits
Burner type 02: 0(single-stage)
02: 1 (two-stage)02: 2 (modulating)
The two-stage/modulatingburner extension is requiredfor two-stage andmodulating burners (includedin standard equipment)
Mixing valve actuatoraccessory kit (accessory)
---------- ---------- The mixing valve andstrap-on sensor arerecognized automaticallythrough the KM-BUS.For assignment to heatingcircuit refer to page 16.
Vitotrol 200(accessory)
orVitotrol 300(accessory)
A0: 0
A0: 0
----------
----------
Coding ”A0: 0” is changedautomatically to ”A0: 1”.
Coding ”A0: 0” is changedautomatically to ”A0: 2”.
Room temperature sensor(accessory)
---------- ---------- For measuring the room tem-perature when the remotecontrol cannot be installed ina suitable location. The roomtemperature sensor isactivated via a coding switchon the remote control.
Sensor/burner fault indicationmodule
92: 1 ---------- For displaying andtransmitting fault messageswhen the fixed high limithas opened
when additional safetyequipment operates
5303271v1.5
General Information
15
Application Example 3 (continued)
System with one direct-connected heating circuit without mixing valve and one heating circuit with mixing valve (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
KM-BUS Expansion Module(accessory)
---------- ---------- Required when more thanone KM-BUS participant isconnected
Switching Module-V(accessory)
94: 0 ---------- Required for external burneractivation and disable. TheSwitching Module-V isautomatically recognized.Coding ”94: 0” is changedautomatically to ”94: 2”.
Return water temperaturesensor (accessory)
---------- ---------- For measuring the returnwater temperature. Thereturn water temperaturesensor is activated via acoding switch in the actuatoraccessory kit.
Flue gas temperaturesensor (accessory)
---------- ---------- For displaying the flue gastemperature and formonitoring high limit values
5303271v1.5
General Information
16
Application Example 3 (continued)
System with one direct-connected heating circuit without mixing valve and one heating circuit with mixing valve (continued)
Coding switch settings for mixing valve motor, part no. 7133 392 (old version)
(Coding switches on mother board of mixing valve motor)
Effective for heating circuit with mixingvalve (M1)
When connecting a return watertemperature sensor (accessory), thecoding switch must be reset.(Set coding switch 3 to ”ON”).
Coding switch settings on Vitotrol 200 or Vitotrol 300
(Coding switch on rear of remote control)The respective remote control must be assigned to a heating circuit via the coding switches.
Remote control effective for Vitotrol 200Coding switch S6
Vitotrol 300Coding switch S30
Heating circuit(boiler circuit, factory default setting)Heating circuit is assigned to heatingcircuit selector button
Heating circuit M1(mixing valve circuit)Heating circuit is assigned to heatingcircuit selector button
Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
If separate room temperature sensor isconnected
Coding switch 3 to ”ON” Coding switch 3 to ”ON”
Coding switch settings for mixing valve motor, part no. 7837 524 (new version)
(the rotary sletector is located on the motherboard of the mixing valve controller)
Heating circuit that mixing valve affects Connected sensors Rotary selector position
Heating circuit with mixing valve, M2 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’2’ (factory set)
’3’
Heating circuit with mixing valve, M3 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’4’ (factory set)
’5’
5303271v1.5
Factory defaultsetting
General Information
17
Application Example 4
System with two heating circuits with mixing valves
Boiler with Vitotronic 300Domestic hot water tankHeating circuit with mixing valve 1Mixing valve actuator accessory kitHeating circuit with mixing valve 2Mixing valve actuator accessory kitKM-BUS Expansion Module(accessory) for the connection ofseveral KM-BUS participantsPower Pump Module
I Low water cut-off device
Connectors
Outdoor temperature sensorSupply temperature sensor(accessory)*2
Boiler temperature sensorDHW tank temperature sensorReturn water temperature sensor(accessory)*2,3
KM-BUS participantExtension fortwo-stage/modulating burner*4
M1 Mixing valve circuit pump 1*2
M2 Mixing valve circuit pump 2DHW production pump(accessory)DHW recirculation pump(field supplied where required)Power supply(120 VAC, 60 Hz)Burner, single-stage*4
Burner, two-stage/modulating*4
Available System Accessories
Vitotrol remote controlRoom temperature sensorReturn water temperature sensor
Switching Module-V for expandingthe range of control functionsKM-BUS Expansion Module
Flue gas temperature sensor
*1 Supply check valve, only required if piping connection is made on one common header.*2 To be connected in the actuator kit.*3 In connection with underfloor heating when control measures supply and return water temperature.*4 Included in standard equipment.
5303271v1.5
I
General Information
18
Application Example 4 (continued)
System with two heating circuits with mixing valves (continued)
Function/Component Coding Remarks
Factory default setting Settings changes
Remarks
System type 00: 1 System without DHWtank 00: 7
System with DHWtank 00: 8
Coding is automaticallychanged to ”00: 9” or”00: 10”, must be resetmanually
Single-/Multi-family house 7F: 1The switching times for theDHW production pump, theDHW recirculation pump andthe holiday program areidentical for all heatingcircuits
7F: 0The switching times for theDHW production pump, theDHW recirculation pump andthe holiday program can beset separately for all heatingcircuits
Burner type 02: 0(single-stage)
02: 1 (two-stage)02: 2 (modulating)
The two-stage/modulatingburner extension is requiredfor two-stage andmodulating burners (includedin standard equipment)
Mixing valve actuatoraccessory kit(accessory)
---------- ---------- The mixing valve andstrap-on sensor arerecognized automaticallythrough the KM-BUS.For assignment to heatingcircuit see page 20.
Vitotrol 200(accessory)
orVitotrol 300(accessory)
A0: 0
A0: 0
----------
----------
Coding ”A0: 0” is changedautomatically to ”A0: 1”.
Coding ”A0: 0” is changedautomatically to ”A0: 2”.
Room temperature sensor(accessory), in conjunctionwith remote control
---------- ---------- For measuring the roomtemperature when theremote control cannot beinstalled in a suitablelocation. The roomtemperature sensor isactivated via a coding switchon the remote control.
Sensor/burner fault indicationmodule
92: 1 ---------- For displaying andtransmitting fault messageswhen the fixed high limithas opened
when additional safetyequipment operates
KM-BUS Expansion Module(accessory)
---------- ---------- Required when more thanone KM-BUS participant isconnected
5303271v1.5
General Information
19
Application Example 4 (continued)
System with two heating circuits with mixing valves (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
Switching Module-V(accessory)
94: 0 ---------- Required for external burneractivation and disable. TheSwitching Module-V isautomatically recognized.Coding ”94: 0” is changedautomatically to ”94: 2”.
Return water temperaturesensor (accessory)
---------- ---------- For measuring the returnwater temperature. Thereturn water temperaturesensor is activated via acoding switch in the actuatoraccessory kit.
Flue gas temperaturesensor (accessory)
---------- ---------- For displaying the flue gastemperature and formonitoring high limit values.The flue gas temperaturesensor is automaticallyrecognized.
5303271v1.5
General Information
20
Application Example 4 (continued)
System with two heating circuits with mixing valves (continued)
Coding switch settings for mixing valve motor, part no. 7133 392 (old version)
(Coding switches on mother board of mixing valve motor)
Effective for heating circuit with mixingvalve 1, M1
Effective for heating circuit with mixingvalve 2, M2(Set coding switch 1 to ”ON”)
When connecting a return watertemperature sensor (accessory), thecoding switch must be reset.(Set coding switch 3 to ”ON”).
Coding switch settings on Vitotrol 200 or Vitotrol 300 (Coding switch on rear of remote control)The respective remote control must be assigned to a heating circuit via the coding switches.
Remote control effective for Vitotrol 200Coding switch S6
Vitotrol 300Coding switch S30
Heating circuit with mixing valve 1Heating circuit is assigned to heatingcircuit selector button
Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
Heating circuit with mixing valve 2Heating circuit is assigned to heatingcircuit selector button
Coding switch 2 to ”ON” Coding switch 2 to ”ON”
If separate room temperature sensor isconnected
Coding switch 3 to ”ON” Coding switch 3 to ”ON”
Coding switch settings for mixing valve motor, part no. 7837 524 (new version)
(the rotary sletector is located on the motherboard of the mixing valve controller)
Heating circuit that mixing valve affects Connected sensors Rotary selector position
Heating circuit with mixing valve, M2 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’2’ (factory set)
’3’
Heating circuit with mixing valve, M3 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’4’ (factory set)
’5’
5303271v1.5
Factory defaultsetting
General Information
21
Application Example 5
System with one direct-connected heating circuit without mixing valve and two heating circuits with mixing valves
Boiler with Vitotronic 300Domestic hot water tankHeating circuit with mixing valve 1Mixing valve actuator accessory kitHeating circuit with mixing valve 2Mixing valve actuator accessory kitKM-BUS Expansion Modulefor the connection of severalKM-BUS participantsHeating circuit without mixing valvePower Pump ModuleLow water cut-off device
Connectors
Outdoor temperature sensorSupply temperature sensor(accessory)*2
Boiler temperature sensorDHW tank temperature sensorReturn water temperature sensor(accessory)*2,3
KM-BUS participantExtension fortwo-stage/modulating burner*4
M1 Mixing valve circuit pump 1*2
M2 Mixing valve circuit pump 2Heating circuit pumpDHW production pump(accessory)DHW recirculation pump(field supplied where required)Power supply(120 VAC, 60 Hz)Burner, single-stage*4
Burner, two-stage/modulating*4
Available System Accessories
Vitotrol remote controlRoom temperature sensorReturn water temperature sensor
Switching Module-V for expandingthe range of control functions
KM-BUS Expansion ModuleFlue gas temperature sensor
*1 Supply check valve only required if piping connection is made on one common boiler return.*2 Connected in actuator accessory kit.*3 In connection with underfloor heating when control measures supply and return water temperature.*4 Included in standard delivery of boiler.
5303271v1.5
2
General Information
22
Application Example 5 (continued)
System with one direct-connected heating circuit without mixing valve and two heating circuits with mixing valves (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
System type 00: 1 ---------- System without DHWtank 00: 9(changed automatically)
System with DHWtank 00: 10(changed automatically)
Single-/Multi-family house 7F: 1The switching times for theDHW production pump, theDHW recirculation pump andthe holiday program areidentical for all heatingcircuits
7F: 0The switching times for theDHW production pump, theDHW recirculation pump andthe holiday program can beset separately for all heatingcircuits
Burner type 02: 0(single-stage)
02: 1 (two-stage)02: 2 (modulating)
The two-stage/modulatingburner extension is requiredfor two-stage andmodulating burners (includedin standard equipment)
Mixing valve actuatoraccessory kit (accessory)
---------- ---------- The mixing valve andstrap-on sensor arerecognized automaticallythrough the KM-BUS.For assignment to heatingcircuit see page 24.
Vitotrol 200(accessory)
orVitotrol 300(accessory)
A0: 0
A0: 0
----------
----------
Coding ”A0: 0” is changedautomatically to ”A0: 1”.
Coding ”A0: 0” is changedautomatically to ”A0: 2”.
Room temperature sensor(accessory), in conjunctionwith remote control
---------- ---------- For measuring the roomtemperature when theremote control cannot beinstalled in a suitablelocation. The roomtemperature sensor isactivated via a coding switchon the remote control.
Sensor/burner fault indicationmodule
92: 1 ---------- For displaying andtransmitting fault messageswhen the fixed high limit isactivated
when additional safetyequipment operates
5303271v1.5
General Information
23
Application Example 5 (continued)
System with one direct-connected heating circuit without mixing valve and two heating circuits with mixing valves (continued)
Function/Component Coding Remarks
Factory default setting Setting changes
Remarks
KM-BUS Expansion Module(accessory)
---------- ---------- Required when more thanone KM-BUS participant isconnected
Switching Module-V(accessory)
94: 0 ---------- Required for external burneractivation and disable. TheSwitching Module-V isautomatically recognized.Coding ”94: 0” is changedautomatically to ”94: 2”.
Return water temperaturesensor (accessory)
---------- ---------- For measuring the returnwater temperature. Thereturn water temperaturesensor is activated via acoding switch in the actuatoraccessory kit.
Flue gas temperaturesensor (accessory)
---------- ---------- For displaying the flue gastemperature and formonitoring limit values
5303271v1.5
General Information
24
Application Example 5 (continued)
System with one direct-connected heating circuit without mixing valve and two heating circuits with mixing valves (continued)
Coding switch settings for mixing valve motor, part # 7133 392 (old version)(Coding switches on mother board of mixing valve motor)
Effective for heating circuit with mixingvalve 1, M1
Effective for heating circuit with mixingvalve 2, M2(Set coding switch 1 to ”ON”)
When connecting a return watertemperature sensor (accessory), thecoding switch must be reset.(Set coding switch 3 to ”ON”).
Coding switch settings on Vitotrol 200 or Vitotrol 300 (Coding switch on rear of remote control)The respective remote control must be assigned to a heating circuit via the coding switches.
Remote control effective for Vitotrol 200Coding switch S6
Vitotrol 300Coding switch S30
Heating circuit without mixing valve(boiler circuit, factory default setting)
Heating circuit is assigned to heatingcircuit selector button
Heating circuit with mixing valve M1Heating circuit is assigned to heatingcircuit selector button
Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
Heating circuit with mixing valve M2Heating circuit is assigned to heatingcircuit selector button
Coding switch 2 to ”ON” Coding switch 1 to ”OFF”Coding switch 2 to ”ON”
If separate room temperature sensor isconnected
Coding switch 3 to ”ON” Coding switch 3 to ”ON”
Coding switch settings for mixing valve motor, part no. 7837 524 (new version)
(the rotary sletector is located on the motherboard of the mixing valve controller)
Heating circuit that mixing valve affects Connected sensors Rotary selector position
Heating circuit with mixing valve, M2 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’2’ (factory set)
’3’
Heating circuit with mixing valve, M3 Flow temperature sensor
Flow tremperature sensor and returntemperature sensor
’4’ (factory set)
’5’
5303271v1.5
Factory defaultsetting
Service Information
25
Controls and display elements
A Heating circuit selectionB Reduced room temperatureC DHW temperatureD Standard room temperatureE Standby modeF DHW only
G Heating and DHWH Economy modeK Party modeL InformationM Standard settingsN Acknowledgment/Confirmation
O Adjusting valuesP Time programsR Holiday programS Time/dateT Heating curve levelU Heating curve slope
Checking the heating circuit allocation
Check whether the label for heatingcircuit allocation has been affixed tothe corresponding field of theprogramming unit.
Check the corresponding key beforecommencing all adjustments
Checking the high limit safety cut-out
Hold down the ”TEST” key during thistest (position ”h”).The control thermostat ”R” has nowbeen bypassed. The burner remainsswitched ON until the boiler watertemperature has reached the safetytemperature and the high limit safetycut-out (FHL) has switched OFF.
After the Burner has been shut down bythe high limit safety cut-out:Release the “Test” keyWait until the boiler watertemperature has dropped 15-20Kbelow the selected safetytemperature, then reset the high limitsaftey cut-out by pressing “ E “.
Changing the display language
1.Press . This displays the outdoortemperature.
2. Select the required language with . 3. Confirm with .
5303271v1.5
Boiler temp.
Mo
ABC D E
U T S PR O
NM
L K H
F
G
Service Information
26
Overview of Service Levels
Function Button combination Access Exit
Diagnosis (see section entitled“Diagnosis”)
and Press both buttonssimultaneously for approx.2 seconds
Press
Coding level 1 and Press andsimultaneously for approx.1 second
Coding level 2 and , then Press andsimultaneously for approx. 1second
Reset codings to factory defaultsettings
and , then Press the orbutton to select ”Factorydefault setting? Yes” or”Factory default setting?No” and pressto confirm.
Calling up acknowledged faultmessages
Press for approx. 3seconds.
Press
Relay test and Press buttonssimultaneously for approx.
Press
Fault history and
simultaneously for approx.2 seconds
Press
Operating status Immediately Press
Fault search (see section entitled“Diagnosis”)
(if ”Fault” flashing) Press
Service scan (if ”Service” flashing) Press
Adjust display contrast and Display darkens
and Display brightens
5303271v1.5
Boiler temperture
Service Information
Slope
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
3.4
3.2
3.0
2.8
2.6
2.4
110/230
100/212
70/158
60/140
50/122
40/104
30/86
80/176
90/194
1050
541
032
-523
-20-4
-1014
-155
SupplytempertaureinºC
/ºF
Outdoor temperature in ºC / ºF
Set room temperature in ºC / ºF
3595
2577
3086
2068
541
1559 10
50
27
Adjusting heating curves
Adjusting the heating curve
The heating curves illustrate the relationship between the outdoor temperature and the boiler water or the supplytemperature. To put it simply: The lower the outdoor temperature, the higher the boiler water or supply temperature. Theroom temperature again depends on the boiler water or the supply temperature.
Factory default settings:Slope: = 1.4Shift: = 0
Generally, the heating curve is set:in range A for underfloor heating systems,in range B for low temperature heating systems (according to the Energy Savings Order),in range C for heating systems with boiler water temperatures above 75 ˚C / 167 ˚F.
5303271v1.5
Service Information
28
Adjusting heating curves (continued)
Adjusting the normal room temperature
(for every heating circuit separately)
Normal room temperature:Select the normal day temperature withthe set value adjuster.The value will be automaticallytransferred after approx. 2 seconds.
Reduced room temperature:1. Call up the reduced night temperaturewith tm.
2. Change the value with or .
3. Confirm the set value with .
Examples
Temperature conversion:
˚C ˚F-20 -45 4114 5720 6826 79110 230
Example 1:
Adjustment of the normal room
temperature from 20 to 26 ˚C /
68 to 79 ˚F.
A Boiler water temperature or supplytemperature in ˚C / ˚F
B Outdoor temperature in ˚C / ˚F
C Set room temperature in ˚C / ˚FD Heating circuit pump OFFE Heating circuit pump ON
Accordingly, the heating curve is adjusted along the set room temperature axis, which results in modified start/shutdowncharacteristics of the heating circuit pumps, if heating circuit pump logic is activated.
Changing slope and shift
(for every heating circuit separately)
1. Call up slope with ,adjustable value 0.2 to 3.5;call up shift with ;adjustable value –13 to +40 °C /8.6 to 104 °F.
2. Change the value with or .
3. Confirm the set value with .
A Change slopeB Change shift
5303271v1.5
D E D E
+20 / 68 -20 / -4
3.5
1.4
0.2
A
B
110
230
Outdoor temperature in °C / °F
Supplytemperaturein°C/°F
Service Information
29
Heating circuit control unit
Brief description
The control unit comprises controlcircuits for one heating circuit withoutmixing valve and two mixing valvecircuits. The set supply temperature ofeach heating circuit results from theoutdoor temperature, the set roomtemperature, the operating mode andthe heating curve.
The supply temperature of heatingcircuits without mixing valve is equal tothe boiler water temperature.The supply temperature of the mixingvalve circuit is regulated by a steppedopening or closing of the mixing valve.The mixing valve motor control changesthe actuating and pause times subjectto the control differential(control deviation).
Coding addresses which influence the
heating circuit control
A0 to FbFor a description, see the codingoverview.
Functions
The heating circuit without mixing valveis subject to the boiler watertemperature and its control range limits.The heating circuit pump is the onlyactuator. The supply temperaturesensor registers the supply temperatureof the mixing valve circuits.
Time program
The control unit time switch changes inaccordance with the times programmedin the ”Heating and DHW” programbetween ”Central heating with standardroom temperature” and ”Central heatingwith reduced room temperature”.Every operating mode has its own setlevel.
Outdoor temperature
A heating curve must be set up formatching the control unit to the buildingand the heating system.The heating curve characteristicsdetermine the set boiler watertemperature subject to outdoortemperature. An average outdoortemperature is used for controlpurposes. This comprises the actual andthe adjusted outdoor temperature.
Domestic hot water temperature
With DHW priority:The set supply temperature will be setto 0 ºC/ 32 ºF while the tank isheated up.The mixing valve closes, and theheating circuit pump is switched OFF.Without DHW priority:The heating circuit control unitcontinues to operate with the sameset value.With modulating priority(only in conjunction with a mixingvalve circuit):The heating circuit pump remainsswitched ON. The set supplytemperature of the heating circuitswill be reduced for as long as the setboiler water temperature has not beenreached while the tank is beingheated up.
The set supply temperature is subjectto the difference between the set andthe actual boiler water temperature, theoutdoor temperature, the heating curveslope and coding address ”A2”.
Heating circuit pump logic (economy
mode)
The heating circuit pump is switchedOFF (set supply temperature set to0 ºC), when the outdoor temperatureexceeds the value selected via codingaddress ”A5”.
Room temperature
In conjunction with remote control androom temperature hook-up (observecoding address ”b0”).Compared with the outdoortemperature, the room temperature hasa greater influence on the set boilerwater temperature. This influence maybe changed via coding address ”b2”.In conjunction with the mixing valvecircuit:For a control difference (deviation fromthe actual value) above 2 K roomtemperature, the influence can befurther increased (via coding address”b6”, quick heat-up/quick setback).
Quick heat-up:Only possible for weather-compensatedmode with room temperature hook-up.The set room temperature must beraised by a minimum of 2 K bypressing party key g
changing from reduced mode tostandard modestart-up time optimisation
Quick heat-up will stop when the setroom temperature has been reached.
Quick setback:Only possible for weather-compensatedmode with room temperature hook-up.The set room temperature must bereduced by a minimum of 2 K bypressing economy key û
changing from heating mode toreduced modeshutdown time optimisation
Quick setback will stop when the setroom temperature has been reached.
5303271v1.5
Service Information
30
Heating circuit control unit (continued)
Extended economy mode
The heating circuit pump is switchedOFF:if the outdoor temperature exceedsthe value selected via coding address”A6”if the set room temperature is reducedvia coding address ”A9”if the mixing valve has been closedfor 12 min. (mixing valve economyfunction, coding address ”A7”)if the actual room temperatureexceeds the value selected via codingaddress ”b5”
Slab curing function
In conjunction with the mixing valvecircuit
Note
Observe DIN 4725 part 4.
Four different temperature profiles can
be selected for drying the slab. These
profiles are activated via coding address
”F1”.
When the slab curing function isactivated, the heating circuit pump ofthe mixing valve circuit is switched ON,and the supply temperature will be heldat the selected profile. After completion(30 days), the mixing valve circuit willagain be regulated automatically via theset parameters.
Underfloor heating
In conjunction with the mixing valvecircuit
An additional return temperature sensorcan be connected to achieve anoptimum underfloor heating system.The control unit calculates a set returntemperature. Changes are implemented,if the actual return temperaturedeviates from the set returntemperature.The temperature differential may bechanged via coding address ”C7”.When changing from ”Central heatingwith reduced room temperature” to”Central heating with standardtemperature”, the set supplytemperature can be raised by20 % for one hour via code ”C9:1”.
System dynamics – mixing valve circuit
You can influence the controlcharacteristics of the mixing valve viacoding address ”C4”.
Frost protection
When the outdoor temperature reaches+1 ºC/ 34 ºF, a supply temperature of15 to 42 ºC/ 63 to 108 ºF will besafeguarded (two-point control).For changes see coding address ”A3”,variable frost limit.
Supply temperature control
Differential temperature:The differential temperature may beadjusted via coding address ”05”;delivered condition: 8 K.
The differential temperature is thatminimum value, by which the boilerwater temperature should be higherthan the currently required mixing valvecircuit supply temperature.
System with only one or two mixingvalve circuits:The set boiler water temperature willbe automatically held 8 K above theset supply temperature.
System with a heating circuit withoutmixing valve and with a mixing valvecircuit:The set boiler water temperatureoperates in accordance with a specialheating curve. The differentialtemperature of 8 K towards the setsupply temperature is set up at thefactory.
AMax. boiler water temperatureB Slope = 1.8 boiler circuit A1C Slope = 1.2 mixing valve circuit
M2D Boiler water temperature
(at a differential temperature of 8 K)E Lower boiler water temperature
Temperature conversion
°C °F
-20 -45 4114 5720 6826 79110 230
5303271v1.5
Boilerwatertemperatureor
flowtemperaturein°C
Outside temperature in °C
Service Information
31
Heating circuit control unit (continued)
Upper control limit
Electronic maximum limitSetting range: 1 to 127 ºC /34 to 261 ºFChanges via coding address “C6”.
Note
The maximum limit is no replacement
for the underfloor heating system
temperature limiter.
Temperature limiter for underfloorheating:The temperature limiter switches theheating circuit pump OFF, if the setvalue has been exceeded. In suchcases, the supply temperature reducesonly slowly, i.e. it may be several hoursbefore the system restarts againautomatically.
Lower control range limit
Electronic minimum limitSetting range: 1 to 127 ºC /34 to 261 ºFChanges via coding address “C5”.
Control sequence
Mixing valve circuit
The mixing valve motor will not beselected within the ”neutral zone”(±1 K).
Supply temperature drops
(set value –1 K)The mixing valve motor receives thesignal ”Mixing valve open”.
The signal duration lengthens with anincreasing control differential.
The duration of pauses reduces with anincreasing control differential.
5303271v1.5
Service Information
32
Tank temperature control
Brief description
The tank thermostat operates with aconstant temperature. It is the result ofstarting and stopping the tank primarypump.The switching differential is ±2.5K.
While the tank is being heated up, aconstant upper boiler water temperatureis set, and the central heating isswitched OFF (optional tank priority).
Coding addresses which influence the
tank thermostat
54, 55, 56, 58 to 62, 64, 66, 67, 70 to75, 7F, A2.For a description, see the codingoverview.
Functions
Time program
An automatic program or an individualtime program may be selected forheating DHW and the control of theDHW circulation pump.Compared with the heating circuitheat-up phase, DHW heating starts30 minutes earlier in automatic mode.The individual time program enables upto four switching periods per day to beset via the time switch to control theDHW heating and the DHW circulationpump.Any tank heating sequence will becompleted, independent of the timeprogram.
In conjunction with coding address ”7F”
“7F:1” Detached house:Automatic modeThe heating times for heating circuit 1are applied to systems with two orthree heating circuits.Individual time programThe switching times for DHW heatingand the DHW circulation pump havethe same effect on all heating circuits.
”7F:0” Apartment block:Automatic modeThe heating times for the respectiveheating circuit will be applied tosystems with two or three heatingcircuits.Individual time programThe switching times for DHW heatingcan be adjusted separately for eachheating circuit.
DHW priority
With DHW priority (code ”A2:2”):The set supply temperature will be setto 0 ºC / 32 ºF while the tank is beingheated up.The mixing valve closes, and theheating circuit pump is switched OFF.Without DHW priority:The heating circuit control unitcontinues to operate with the sameset value.With modulating priority(only in conjunction with a mixingvalve circuit):The heating circuit pump remainsswitched ON. The set supplytemperature of the heating circuitswill be reduced, for as long as the setboiler water temperature has not beenreached during tank heating. The setsupply temperature is subject to thedifference between the set and theactual boiler water temperature, theoutdoor temperature, the heatingcurve slope and coding address ”A2”.
Frost protection
The DHW tank will be heated to 20 ºC /68 ºF if the DHW temperature fallsbelow 10 ºC / 50 ºF.
Auxiliary function for DHW heating
This function is activated by providing asecond set DHW temperature viacoding address ”58”, and activating the4th DHW phase for DHW heating.
Set DHW temperature
The set DHW temperature can beadjusted between 10 and 60 ºC / 50and 140 ºF. The set range can beextended to 95 ºC / 203 ºF via codingaddress ”56”.The set default value of theprogramming unit and/or theVitotrol 300 remote control can beapplied via coding address “66”.
DHW circulation pump
It delivers hot water to the draw-offpoints at adjustable times.Up to four control periods can be set atthe time switch.
Auxiliary circuits
DHW heating can be blocked or enabledby changing over the heating program.An external contact in conjunction withswitching module V can be used tobriefly select the DHW circulationpump. The time may be adjusted viacoding address ”74”.
Systems with Vitosolic
A third set DHW temperature can bedefaulted via coding address ”67”.Re-heating will be suppressed above theselected temperature. The DHW tankwill only be heated by the solar heatingsystem.
5303271v1.5
Service Information
33
Tank temperature control (continued)
Control sequence
Pump run-on
The tank primary pump runs on aftertank heating, until the difference between the boilerwater and the DHW temperature isless than 7 Kor
until the weather-compensated setboiler water temperature has beenreachedor
until the actual temperature is 5 Khigher than the set DHWtemperatureor
until the maximum run-on time(adjustable via coding address ”62”)has been reached.
Without the tank primary pumprunning on (code “62:0”)
Code ”55:0”
Tank heating
DHW tank goes cold
(set value –2.5 K, adjustable via codingaddress “59”)The set boiler water temperature isadjusted 20 K higher than the set DHW(adjustable via coding address ”60”).Starting the tank primary pumpsubject to boiler temperature (code“61:0”):The pump starts when the boilerwater temperature is 7 K higher thanthe DHW temperature.Immediate start of the tank primarypump (code “61:1”).
The DHW tank is hot
(set value +2.5 K)The set boiler water temperature isreturned to the weather-compensatedvalue.
Code ”55:1”
Adaptive tank heating
With adaptive tank heating, the speedof the temperature rise during DHWheating is taken into account.Also taken into account is the question,whether the boiler will be required tosupply heat after the tank has beenheated up or whether residual boilerheat should be transferred to the DHWtank.Accordingly, the control unit determinesthe burner and circulation pumpshutdown points to prevent the setDHW temperature being substantiallyexceeded after the tank has beenheated up.
5303271v1.5
Service Information
34
Temperatures, Boiler Coding Cards and Scans
Select the heating circuit with theheating circuit selector buttons.
Each heating circuit is scanned
separately.
Press and simultaneously forapprox. 2 seconds.
Access diagnosis level.
Select the required data for scanningwith the or button.
Press . Exit diagnosis level.
The following values can be scanned:
Damped outdoor temp.
Current outdoor temp.
Desired supply temp.Current supply temp.
Slope A1/M2/M3.Shift A1/M2/M3.
Desired boiler temp.Current boiler temp.
Desired DHW temp.Current DHW temp.
Desired return temp.Current return temp.
Desired room temp.Current room temp.
Max. flue gas temp.
Current flue gas temp.
Boiler coding card
Scan 1 to Scan 5
The damped outdoor temperature can
be reset to the current outdoor
temperature by pressing .
Only displayed if supply temperature
sensor connected.
Only displayed if tank temperature
sensor connected.
Only displayed if return water
temperature sensor connected.
Only displayed if remote control or
separate room temperature sensor
connected.
Only displayed if flue gas temperature
sensor connected.
The max. flue gas temperature can be
reset to the current value by pressing
.
See “Overview of Boiler Coding
Cards”.
See following pages for scans 1 to 5.
5303271v1.5
Boiler temperature
Diagnosis
Outdoor temp.damped
ServiceInformation
35
Tem
pera
ture
s,Boile
rC
odin
gC
ard
sand
Scans
(contin
ued)
8
ann 2-wire BUS
Software version
switching module
V
Software version
remote control
mixing valve circuit
M3
Software version
variable speed
pump
mixing valve circuit
M3
Software version
Solar control unit
8
Number of Viessman
participants
Software version
extension kit
mixing valve circuit
M3
Operating mode
mixing valve circuit
M3
0 w/o remote
control
1 with
Vitotrol 200
2 with
Vitotrol 300
Variable speed
pump
mixing valve circuit
M3
0 excl.
1 Wilo pump
2 Grundfos pump
8
Number of KM BUS
participants
Software version
expansion module
Viessmann 2-wire
BUS
Software version
remote control
mixing valve circuit
M2
Software version
variable speed
pump
mixing valve circuit
M2
8
Burner type
0 single stage
1 two-stage
2 modulating
Software version
extension kit
mixing valve circuit
M2
Operating mode
mixing valve circuit
M2
0 w/o remote
control
1 with
Vitotrol 200
2 with
Vitotrol 300
Variable speed
pump
mixing valve circuit
M2
0 excl.
1 Wilo pump
2 Grundfos pump
N/A
SCAN8
s ”00”)
Software version
programming unit
Software version
remote control
boiler circuit
Software version
variable speed
pump
boiler circuit
BRIEF S8
System design
(see coding address
Software version
control unit
Operating mode
boiler circuit
0 w/o remote
control
1 with
Vitotrol 200
2 with
Vitotrol 300
Variable speed
pump
boiler circuit
0 excl.
1 Wilo pump
2 Grundfos pump
Brief scan
1
2
3
4
5
5303 271 v1.5
Service Information
36
Relay Test
Press and simultaneously forapprox. 2 seconds.
Relay test activated.
Select relay outputs with the orbutton.
Press .
Relay test terminated.
The following relay outputs can beselected:
Burner ON
Burner stage 1 ON
Burner stages 1 + 2 ON
Burner modulation up
Burner modulation hold
Burner modulation down
Heat pump ON
Heat pump M1 ON
Heat pump M2 ON
Mixing valve 1 open
Mixing valve 2 open
Mixing valve 1 closed
Mixing valve 2 closed
DHW tank pump ON
DHW recirculation pump ON
Compiled fault indicator ON
The following lists may differ
according to system equipment and
coding.
LED of selector button ON.
LED of selector button ON.
LED of selector button ON.
LED of selector button ON.
LED of selector button ON.
LED of selector button ON.
LED of selector button ON.
Only displayed if Switching Module-V
is connected.
The relay switches with a delay of up
to 1 minute.
5303271v1.5
Relay test
Burner ON
IMPORTANT
Service Information
37
Scanning Operating Status Information
Select the heating circuit with theheating circuit selector buttons.
Each heating circuit is scanned
separately.
Press . Operating status scanning mode is
activated.
Select the required operating statusdata for scanning with the or
button.
Press . Exit the operating status scanning
mode.
The following operating statusinformation can be scanned, subject tothe actual system equipment andcoding:
Heating circuits A1, M2 and M3
– Holiday program– Departure and return date– Current outdoor temperature– Current boiler water temperature– Actual DHW tempemperature– Supply temperature (actual value)(only for mixing valve circuits M2and M3)
– Return temperature (actual value)(only for mixing valve circuits M2and M3)
– Current flue gas temperature
– Current room temperature
– Burner operating hours– Number of burner starts– Fuel consumption
– Actual solar DHW temperature– Collector temperature– Solar energy in kWh– Time/ Date– Operating status of burner– Operating status of heating circuitpump
– Operating status of DHWproduction pump
– Operating status of DHWrecirculation pump
– Mixing valve open/closed– Solar circuit pump ON/OFF– Hours run – solar circuit pump– Different languages
The holiday program, departure and
return date are only displayed when
the holiday program is activated.
For coding address”C7” a value
greater than “0” must be set.
Only displayed if flue gas temperature
sensor is connected.
Only displayed if Vitotrol or separate
room temp. sensor is connected.
Reset burner operating hours, number
of burner starts and fuel consumption
after maintenance has been
performed. By pressing , the values
can be individually reset to zero.
Display only, if “26” or “29” is set via
the coding addresses.
In conj. with solar heating system.
In conj. with solar heating system.
In conj. with solar heating system.
In conj. with solar heating system.
In conj. with solar heating system.
5303271v1.5
Boiler temperature
Service Information
38
Scanning Operating Status Information (continued)
Heating circuit with mixing valve
(1 or 2)
– Holiday program– Departure date– Return date– Current outdoor temperature– Supply temperature– Current boiler water temperature– Domestic hot water temperature1st tank temperature sensor
– Domestic hot water temperature2nd tank temperature sensor
– Return water temperature– Current flue gas temperature
– Current room temperature
– Burner operating hours– Number of burner starts– Fuel consumption
– Time– Date– Operating status of burner– Operating status of heating circuitpump
– Operating status of DHW productionpump
– Operating status of DHWrecirculation pump
– Operating status of mixing valve– Different languages
The holiday program, departure and
return date are only displayed when
the holiday program is activated.
Only displayed if flue gas temperature
sensor is connected.
Only displayed if Vitotrol or separate
room temperature sensor is
connected.
Reset burner operating hours, number
of burner starts and fuel consumption
after maintenance has been
performed. By pressing , the values
can be individually reset to zero.
5303271v1.5
Service Information
39
Scanning and Resetting the Service Information
When the limit values selected via coding addresses ”1F”, ”21” and ”23” (see
“Additional Information” for individual coding addresses) are reached, “Service” will
appear on the display and the red fault indicator will flash.
1. Press . Service scan is activated.
2. Scan the individual serviceinformation (if more than onemessage is stored) with the or
button.
3. Press and confirm the display”Acknowledge: Yes” by pressing
.
The word “Service” will disappear and
the red fault indicator will continue to
flash.
An acknowledged service message
can be displayed again by pressing
(for approx. 4 seconds).
4. Press . Service scan is terminated.
5. After performing the maintenance,reset coding ”24:1” to ”24:0”.
Red fault indicator is turned off.
If coding address ”24” is not reset,
the word “Service” will reappear at
07:00 hrs on Monday.
6. After performing the maintenancePress .Reset burner operating hours,number of burner starts and fuelconsumption.
Press .
See ”Scanning Operating Status
Information”.
7. After performing the maintenancePress and simultaneously forapprox. 4 seconds.
Reset ”Max. flue gas temp.” to thecurrent value by pressing .
Press .
See ”Temperatures, Boiler Coding
Cards and Scans”.
5303271v1.5
Service
MFlue gas temperature
ºC180
IMPORTANT
Boiler temperature
IMPORTANT
Components
40
Components from the parts list
Boiler temperature sensor and tank temperature sensor
Check sensor
1. Pull plug 3 or from control.
2. Check the sensor resistance atterminals 1 and 2 of the plug.
3. Compare the measurement with theactual temperature displayed (forscanning.)Check the installation and replacesensor, if necessary, in case ofsevere deviation.
Specification
Protection: IP 32Permiss. ambienttemperatureduring operation– boilertemperaturesensor: 0 to +130 ºC
32 to 266 ºF– tanktemperaturesensor: 0 to +90 ºC
32 to 194 ºFduring storageand transport: –20 to + 70 ºC
-4 to 158 ºF
5303271v1.5
Resistancein
ΩΩ ΩΩ
Boiler water temperature32 68 104 140 176 212 248 284
ºCºF
Components
41
Components from the parts list (continued)
Outdoor temperature sensor
Checking the outdoor temperature
sensor
1. Pull plug from control.
2. Check the sensor resistance atterminals 1 and 2 of the plug.
3. Disconnect wires from the sensor, ifactual values deviate severely fromthe curve, repeat the sensor test andcompare with the actual temperature.
4. Depending on the result, replacecable or outdoor temperature sensor.
5. Scan actual temperature.
Specification
Protection: IP 43Permiss. ambienttemperatureduring operation,storage andtransport: –40 to +70 ºC
–40 to +158 ºF
5303271v1.5
Resistancein
400
420
440
460
480
500
520
540
560
580
600
-40 -30 -20 -10 0 10 20 30
Outdoor temperature in °C / °F
-40 -22 -4 14 32 50 68 86
Components
42
Flue gas temperature sensor
Connection
The sensor is plugged into socket ”15”at the control unit.
Checking the flue gas temperature
sensor
1. Pull plug 15 from control.
2. Check the sensor resistance atterminals 1 and 2 of the plug.
3. Compare the measurement with theactual temperature displayed.Check the installation and replacesensor, if necessary, in case ofsevere deviation.
Specification
Protection: IP 60Permiss. ambienttemperatureduring operation: 0 to + 600 ºC
32 to 1112 ºFduring storageand transport: –20 to + 70 ºC
-4 to 158 ºF
5303271v1.5
0500
40 80 120 160 200 240 280
540
580
620
660
700
740
780
820
860
900
940
980
1020
Resistancein
ΩΩ ΩΩ
Flue gas temperature in °C / °F
32 104 176 248 360 392 464 536
Components
43
Mixing valve circuit extension kit
For mixing valve installation, incl. mixing valve motor, part no. 7178 995For wall mounting, separate mixing valve motor, part no. 7178 996
Contact temperature sensor, part no. 7183 288
For recording the supply and return temperature.
Connection
The sensor is plugged into socket ”2”or ”17” at the mixing valve extension.
Check sensor
1. Pull plug or from control
2. Check the sensor resistance atterminals 1 and 2 of the plug.
3. Compare the measurement with theactual temperature displayed.Check the installation and replacesensor, if necessary, in case ofsevere deviation.
Specification
Protection: IP 32Permiss. ambienttemperatureduring operation: 0 to +100 ºC
32 to 212 ºFduring storageand transport: –20 to + 70 ºC
-4 to 158 ºF
5303271v1.5
30 40 50 60 7070 80 90540
560
580
600
620
640
660
680
700
720
740
20 100
Resistancein
68 86 104 122 140 158 176 194 212
Supply/Return temperature in °C / °F
Components
44
Extension kit for mixing valve circuit (continued)
Mixing valve extension
Summary of electrical connections,
part no. 7133 392 (old version)
AMixing valve extensionB Mixing valve motor,
part no. 7178 995Wall mounting base forpart no 7178 996
CMain PCBD Heating circuit pump socket via plug
120 VAC/ 60HzE Power supply socket via
plug 120 VAC/ 60HzF Fuse F1G ON/OFF switch
Low voltage connections
Supply temperature sensorReturn temperature sensor(accessories)No functionKM BUS
Pump 120 V~ connection5303271v1.5
CD EF G
141
14517 2
BA
M1~
20
A
Components
45
Extension kit for mixing valve circuit (continued)
Summary of electrical connections,
part no. 7837 524 (new version)
F1 FuseS1 Rotary selector
120V plugs
Heating circuit pump (on site)Power supply
Power supply for additionalcontroller for heating circuitwith mixing valve
Mixing valve motor
Low voltage connections
Supply temperature sensorReturn temperature sensor(optional accessory for Vitotronic300, type KW3)KM BUS
5303271v1.5
Components
46
Extension kit for mixing valve circuit (continued)
Changing the rotational direction, part no. 7133 392 (old version)
The rotational direction must be changed for the installation examples on page and for systems with Modular-Divicon.
A ON/OFF switchB Rotational direction switch on the
main PCB
1. Open mixing valve extension.Rotational direction switch:Position I:Delivered conditionPosition II:Changing the rotational direction
2. Close mixing valve extension.
3. Check the rotational direction:Switch ON the power supply and theON/OFF switch; the equipment thenimplements a relay test.
Relay test
The mixing valve runs for approx.150 s into position ”Close”; theheating circuit pump runs for approx.10 sThe mixing valve runs for approx.10 s into position ”Open”The mixing valve runs for approx.10 s into position ”Close”Standard control mode.
Note
A relay test is implemented every time
the system is switched ON.
Mixing valve insert conversion (if required), see mixing valve installation instructions.
Factory supplied
of the mixing valve motor rotationaldirection
Change the mixing valve motor rotationaldirection for these installation examples
HR Heating return KR Boiler returnHV Heating supply KV Boiler supply
5303271v1.5
An electric shock can be life
threatening.
When opening the equipment, switch
OFF the ON/OFF switch and mains
voltage, for example at the fuse or the
main electrical isolator.
DANGERB
A
I II
Components
47
Extension kit for mixing valve circuit (continued)
Changing the rotational direction, part no. 7837 524 (new version)
On systems with Modular-Divicon.
HR Heating return KR Boiler returnHV Heating supply KV Boiler supply
1. Switch OFF the power supply to the control unit.
2. Remove the mixing valve controller cover.
3. Interchange wires BN and BK at plug 52 to change therotational direction.
4.Connect the controller.5.Check the rotational direction
Note: If a fault occurs during commissioning, check themixing valve installation (see mixing valve installationinstructions).
5303271v1.5
Components
ON
1234
S1
48
Extension kit for mixing valve circuit (continued)
Coding
(DIP switch on the main PCB)
S1.4 must always be set to OFF.
Affects mixing valve circuit M2
Delivered condition
Affects mixing valve circuit M3S1.1 to ON
When connecting a return temperaturesensorS1.3 to ON
5303271v1.5
ON
1234
S1
ON
1234
S1
Components
49
Remote control
Vitotrol 200, part no. 7450 017
(with integral room temperature sensor for room temperature hook-up in conjunction with a mixing valve circuit)Settings:Day temperatureHeating programEconomy and party mode
Function changes can be made via coding addresses ”A0”, ”b0” to ”b9”, ”C0” to ”C2”, ”C8”, ”E1”, ”E2” and “F2” (seeoverview).
AWall mounting fixture forVitotrol 200
B To the control unit or to theKM BUS distributor
Connection
2-wire cable (total cable lengthmax. 50 m/ 164 ft)
C PCB DIP switches(back of the top casing).
Remote controlaffects
DIP switch setting
Heating circuitwithout mixingvalve A1(heating circuitselection key“1”)
Deliveredcondition
ON
123 4
Mixing valvecircuit M2(heating circuitselection key “2”)
ON
123 4
Mixing valvecircuit M3(heating circuitselection key “3”)
ON
123 4
When connecting a separate roomtemperature sensor, set DIP switch”S6.3” to ON.
Specification
Power supply via KM BUS.Safety class: IIIProtection: IP 30Permiss. ambienttemperatureduring operation: 0 to +40 ºC
32 to 104 ºFduring storageand transport: –20 to + 65 ºC
–40 to + 149 ºFSetting range forset room temp.: 10 to 30 ºC/
50 to 86 ºF;adjustable to3 to 23 ºC /37 to 73 ºF or17 to 37 ºC/63 to 98 ºFvia codingaddress “E1”
Reduced set room temperatureadjustment on the control unit.
5303271v1.5
A
B
145
ONS6
12 3 4
C
ON
123 4
Components
1234
ON
50
Remote control (continued)
Vitotrol 300, part no. 7179 060
(with integral room temperature sensor for room temperature hook-up in conjunction with a mixing valve circuit)Settings:Day and night temperatureDomestic hot water temperature
Heating programHoliday program
Switching timesEconomy and party mode
Function changes can be made via coding addresses ”A0”, ”b0” to ”b9”, ”C0” to ”C2”, ”C8”, ”E1”, ”E2” and “F2” (seeoverview).
AWall mounting fixture forVitotrol 300
B To the control unit or to theKM BUS distributor
Connection
2-wire cable (total cable lengthmax. 50 m/ 164 ft)
A PCB DIP switch (back of the topcasing).
Remote controlaffects
DIP switchsetting
Heating circuitwithout mixingvalve A1(heating circuitselection key “1”)
Delivered cond.
1234
ON
Mixing valvecircuit M2(heating circuitselection key “2”)
1234
ON
Mixing valvecircuit M3(heating circuitselection key “3”)
1234
ON
When connecting a separate roomtemperature sensor, set DIP switch”S3.3” to ON.
Specification
Power supply via KM BUS.Safety class: IIIProtection: IP 30Permiss. ambient temperatureduring operation: 0 to +40 ºC
32 to 104 ºFduring storageand transport: –20 to + 65 ºC
–40 to + 149 ºFSetting range forset room temp.: 10 to 30 ºC/
50 to 86 ºF;adjustable to3 to 23 ºC /37 to 73 ºFor17 to 37 ºC/63 to 98 ºFvia codingaddress “E1”
Red. set room temp: 3 to 37 ºC37 to 98 ºF
5303271v1.5
A
B
145
Components
51
Remote control (continued)
Connecting several remote control units
When connecting several remote controls to the control unit, install a terminal box on site.
Version 1
A To control unitB Terminal box (on site)C Vitotrol 1D Vitotrol 2E Vitotrol 3
On-site connection via terminal box:Connect in accordance with thediagram
The total length of all KM BUS cablesshould be limited to 50 m / 164 ft
5303271v1.5
145A
B
max.15 m / 50 ft
D
max.15 m / 50 ft
E
max.15 m / 50 ft
C
Components
52
Remote control (continued)
Version 2
A To control unitB Terminal box (on site)C Vitotrol 1D Vitotrol 2E Vitotrol 3F Further BUS participants
If several remote control units andadditional KM BUS participants areconnected, make the connections viaa terminal box (on-site) as shown inthe diagram
The total length of all KM BUS cablesshould be limited to 50 m / 164 ft
5303271v1.5
145A
max.
15 m / 50 ft
B
C D
F
E
max. 15 m / 50 ftmax. 15 m / 50 ft
Components
53
Room temperature sensor
The room temperature sensor measures the actual room temperature, if the remote control unit cannot be installed in asuitable location.
A Remote controlB To the control unitC Room temperature sensor
Connection
Two-wire cable with a maximumlength of 35 m / 115 ft and across-section of 1.5 mm2 (copper).Set DIP switch 3 on the remotecontrol to ON.
Check the room temperature sensor
1. Disconnect the wires from thesensor.
2. Check the sensor resistance atterminals ”9” and ”13b”.
3. Compare the measurement with theactual temperature displayed.Check the installation and replacesensor, if necessary, in case ofsevere deviation.
Specification
Protection: IP 30Permiss. ambienttemperatureduring operation: 0 to + 40 ºC
32 to 104 ºFduring storageand transport: –20 to +65 º C
–4 to +149 ºF
5303271v1.5
145
C
3 41 2
A
B
0
Resistancein
5005 10 15 20 25 30 35 40
510
520
530
540
550
560
570
580
600
590
Room temperature in °C / °F
32 41 50 59 68 77 86 95 104
Components
54
Switching module V
Switching module V for extending the control unit functions.Observe the coding addresses “32”, “33” and “74” (see overview).Switching module V is recognised automatically by the control unit(code “94:2”).
A Switching module V wiring chamberB To the control unit
Please note:
Trouble-free operation cannot beassured if connectors are incorrectlypositioned.Never alter the allocation ofconnections to sockets in switchingmodule V.
DE1 External heating programchangeover for heating circuitwithout mixing valve (also seecoding address “d5”)
DE2 External heating programchangeover for mixing valvecircuit M2
DE3 External burner blockingDE4 External burner demand
(set minimum boiler watertemperature)
DE5 External burner demand(stage 2)
DE6 External fault message inputDE7 Short-term operation of the DHW
circulation pumpKM BUS
Central fault messageNominal relay rating:1(0.5) A 24 V~/120VAC10 mA 24 V–
5303271v1.5
B
A
X3 X4 X5 X6 X7 X8 X9 X1 X2
Components
55
KM BUS expansion module
The connection between the control unit and the remote controls, the remote monitoring equipment and switching module Vis provided by the KM BUS distributor.
A KM BUS distributor, wiringarrangement area
B Terminals for the connection ofadditional KM BUS participants(connection to terminals ”X8.1”
and ”X8.2”,”X8.3” and ”X8.4” or”X8.5” and ”X8.6”)
C KM BUS user connections (sockets”X2” to ”X7”)
D To the control unit
Boiler coding card
To match the control unit function to the boiler.
5303271v1.5
3 2 16 5 4
X1 X2 X3 X4 X5 X6 X7
Components
56
Input extension module 0-10V
To default an additional set boiler temperature via a 0 to 10 V input in the range 10 to 100 ºC / 50 to 212 ºF or 30 to 120 ºC/86 to 248 ºF.To signal reduced mode and regulate a heating circuit pump to a lower speed.
Power supply 120 V/60 HzaVF 0 to 10 V input
KM BUS to control unit
Potential free contact
AMains isolator (if required)B DIP switch (see table)
DIP switch Function
12344
ONONONONOFF
Reduced mode – heating circuit A1Reduced mode – mixing valve circuit M2Reduced mode – mixing valve circuit M3Set value default 10 to 100 ºC/ 50 to 212 ºFSet value default 30 to 120 ºC / 86 to 248 ºF
Note
Out of switches 1 to 3, only one switch may be set to ON.
5303271v1.5
OFF
A
Electronics24V
5V
L1
40
120V
157 144 145
N S Ö P 1 2 3 1 2 3
1 2 3 4
ONF1T250mA
B
– +
Troubleshooting
57
Diagnosis
Fault with fault message on the programming unit
When an fault message is transmitted,- Fault -flashes in the display 1 of theprogramming unit.The red fault indicator 2 flashes.
Refer to fault code tables in this
section for fault code analysis.
Search fault
Open the hinged cover on the pro-gramming unit and press .
Other fault codes which may bestored can be called up by pressingthe or button.
The fault can be acknowledged by
pressing . The fault message in
the display will disappear; the red
fault indicator continues to flash. If
an acknowledged fault is not
corrected by 07:00 hrs on the
following day, the fault message will
reappear in the display.
To retrieve an acknowledged fault
message
Press for approx. 2 seconds.
Select the acknowledged fault bypressing the or button.
Fault is displayed.
5303271v1.5
Fault
MFault
MoºC57
MFault
- 2 b7
Acknowledge? Yes
Outdoor sensor
- 1 10IMPORTANT
Troubleshooting
58
Diagnosis (continued)
Display The red fault indicator will flash
whenever a fault has been detected.
Fault indicator
Fault with fault message on control unit
Fault
code
display
Faultindicator(red)
Behavior of system Cause Corrective action
00 Off Normal operation No Fault No action required
0f Off Normal operation Maintenance required Perform maintenance
10 Flashes Operates on basis of 32 ºF / 0 ºCoutdoor temperature
Short circuitOutdoor temperature sensor
Check outdoor temperaturesensor
18 Flashes Operates on basis of 32 ºF / 0 ºCoutdoor temperature
Open circuitOutdoor temperature sensor
Check outdoor temperaturesensor
20 Flashes Mixing valve is closed Short circuitSupply temperature sensor ofmixing valve circuit 1
Check supply temperature sensor
21 Flashes Operation without influence ofreturn water temperature
Short circuitReturn water temperature sensorof mixing valve circuit 1
Check return water temperaturesensor
28 Flashes Mixing valve is closed Open circuitSupply temperature sensor ofmixing valve circuit 1
Check supply temperature sensor
29 Flashes Operation without accounting forreturn water temperature
Open circuitReturn water temperature sensorof mixing valve circuit 1
Check return water temperaturesensor
30 Flashes With DHW tank:DHW production pump ON,boiler kept at desired tank temp.
Without DHW tank:Boiler controlled on basis of AHL
Short circuitBoiler temperature sensor
Check boiler temperature sensor
38 Flashes With DHW tank:DHW production pump ON,boiler kept at desired tank temp.
Without DHW tank:Boiler controlled on basis of AHL
Open circuitBoiler temperature sensor
Check boiler temperature sensor
5303271v1.5
Fault
TEST
IMPORTANT
Troubleshooting
59
Diagnosis (continued)
Fault with fault message on control unit (continued)
Fault
code
display
Faultindicator(red)
Behavior of system Cause Corrective action
40 Flashes Mixing valve is closed Short circuitSupply temperature sensor ofmixing valve circuit 2
Check supply temperature sensor
41 Flashes Operation without accounting forreturn water temperature
Short circuitReturn water temperature sensorof mixing valve circuit 2
Check return water temperaturesensor
48 Flashes Mixing valve is closed Open circuitSupply temperature sensor ofmixing valve circuit 2
Check supply temperature sensor
49 Flashes Controlled without influence ofreturn water temperature
Open circuitReturn water temperature sensorof mixing valve circuit 2
Check return water temperaturesensor
50 Flashes DHW production pump ON:Desired boiler temperature =desired tank temperature,priority control cancelled
Short circuitTank temperature sensor 1
Check tank temperaturesensor 1
51 Flashes Controlled on basis of tanktemperature sensor 1
Short circuitTank temperature sensor 2
Check tank temperaturesensor 2
58 Flashes DHW pump ON:Desired boiler temperature =desired tank temperature,priority control cancelled
Open circuitTank temperature sensor 1
Check tank temperaturesensor 1
59 Flashes Controlled on basis of tanktemperature sensor 2
Open circuitTank temperature sensor 2
Check tank temperaturesensor 2
92 Flashes Control ModeOnly the solar control unit faultcodes will be displayed
Short circuit, collector temp.sensor, connects to Vitosolic S1
Check the solar control unitsensor
93 Flashes
Only the solar control unit faultcodes will be displayed
Short circuit, collector temp.sensor, connects to Vitosolic S2
sensor
94 Flashes Short circuit, collector temp.sensor, connects to Vitosolic S3
9AAa Flashes Lead broken, collector temp.sensor, connects to Vitosolic S1
96 Flashes Lead broken, collector temp.sensor, connects to Vitosolic S2
9c Flashes Lead broken, collector temp.sensor, connects to Vitosolic S3
9f Flashes Error Solar control unit; displayedif an error without fault codeoccurs at the solar control unit
Check the solar control unit
b0 Flashes Normal operation Short circuitFlue gas temperature sensor
Check flue gas temperaturesensor
b1 Flashes Normal operation Communication errorProgramming unit
Check connections, if necessaryreplace programming unit
b4 Flashes Constant temperature mode Internal fault Check electronics board
5303271v1.5
Troubleshooting
60
Diagnosis (continued)
Fault with fault message on control unit (continued)
Fault
code
display
Fault
indicator
(red)
Behaviour of system Cause Corrective action
b5 Flashes Normal operation Internal fault Check electronics board
b6*1 Flashes Constant temperature mode Invalid hardware code Check mother board
b7 Flashes Boiler controlled on basis ofadjustable high limit
Internal faultBoiler coding card
Insert boiler coding card orreplace if defective
b8 Flashes Normal operation Open circuitFlue gas temperature sensor
Check flue gas temperaturesensor
b9 Flashes Normal operation Internal fault Acknowledge fault, repeat datainput
bAa Flashes Mixing valve 1 continuesin normal control mode
Communication errorMixing valve actuator accessorykit
Check connections
bb*2 Flashes Mixing valve 2 continuesin normal control mode
Communication errorMixing valve actuator accessorykit
Check connections
bCc Flashes Normal operation without remotecontrol
Communication errorVitotrol remote control,boiler circuit
Check connections and Vitotrolremote control
bd Flashes Normal operation without remotecontrol
Communication errorVitotrol remote control,mixing valve circuit 1
Check connections and Vitotrolremote control
be Flashes Controlled operation withoutremote control
Communication errorVitotrol remote control,mixing valve circuit 2
Check connections and Vitotrolremote control
Cc1 Flashes Boiler is cooling down External safety equipment Check connection of connector
Check external safetyequipment
Check fault indication module
c2 Flashes Control Mode, normal operation Lead broken, KM BUS to thesolar control unit
Check the KM BUS cable and thesolar control unitWithout solar control unit:Set code “54:0”
Cc4 Flashes Communication error, inputextension module 0 to 10V
Check connections and cables orleads, if required replace the inputextension module.Without input extension module:Set code “9d:0”
Cc5 Flashes Normal operation, max. pumpspeed
Communication errorVariable speed pump, boilercircuit
Check setting of coding address”E5”; check coding switchsetting of heating circuit pump
Cc6 Flashes Normal operation, max. pumpspeed
Communication errorVariable speed pump, mixingvalve circuit 1
Check setting of coding address”E5”; check coding switchsetting of heating circuit pump
*1 Read carefully. See bb below. *2 Read carefully. See b6 above.
5303271v1.5
Troubleshooting
61
Diagnosis (continued)
Fault with fault message on control unit (continued)
Fault
code
display
Faultindicator(red)
Behavior of system Cause Corrective action
c7 Flashes Normal operation, max. pumpspeed
Communication errorVariable speed pump, mixingvalve circuit 2
Check setting of coding address”E5”; check coding switchsetting of heating circuit pump
c9 Flashes Control Mode, normal operation Fault message input activeon Switching Module-V
Check fault message input
Ccd Flashes Communication error, Vitocom100
Check connections andVitocom 100:Set code “95:0”
ce Flashes Communication errorSwitching Module-V
Check connectionsand Switching Module-V
cf Flashes Communication errorViessmann two-wire BUSexpansion module
Check expansion module andconnecting cable
d1 Flashes Boiler is cooling down Burner fault Check burner
d4 Flashes Boiler is cooling down Fixed high limit is open or faultindication module notinserted correctly.
Check fixed high limit or faultindication module
dAa Flashes Normal operation withoutroom temperature feedback
Short circuitRoom temperature sensor,boiler circuit
Check room temperature sensor
db Flashes Normal operation withoutroom temperature feedback
Short circuitRoom temperature sensor,mixing valve circuit 1
Check room temperature sensor
dCc Flashes Controlled operation withoutroom temperature feedback
Short circuitRoom temperature sensor,mixing valve circuit 2
Check room temperature sensor
dd Flashes Normal operation withoutroom temperature feedback
Open circuitRoom temperature sensor,boiler circuit
Check room temperature sensor
de Flashes Normal operation withoutroom temperature feedback
Open circuitRoom temperature sensor,mixing valve circuit 1
Check room temperature sensor
df Flashes Normal operation withoutroom temperature feedback
Open circuitRoom temperature sensor,mixing valve circuit 2
Check room temperature sensor
e0to
ef
Flashes Normal operation Error at HV-BUS participant
f0to
ff
Flashes Normal operation Error at HV-BUS participant
5303271v1.5
Troubleshooting
62
Diagnosis (continued)
Retrieving fault codes from error log (fault history)
All faults which have occurred are stored and can be scanned. The scanning
sequence starts with the most recently stored fault code.
1. Press and simultaneously forapprox. 2 seconds.
Scanning of fault history is activated.
Error history
1 18
.
.
.
Error history
10 d4
2. Access the individual fault codes bypressing the or button.
Sequence of
stored fault
codes
Fault code
1 Last (most recent)error code
.
.
....
10 10th last faultcode
3. Press .
All error messages can be reset to ”0”
by pressing .
Scanning of fault history is
terminated.
5303271v1.5
Boiler temperature
Error history
Boiler temperature
IMPORTANT
Additional Information
63
Codings
Accessing coding level 1
The most important codings can be set in plain language in coding level 1.
Press and simultaneously forapprox. 2 seconds.
Access coding level 1.
Call up the required coding address withthe or button;press to confirm.
Change the value with the orbutton;press to confirm.
Address flashes.
Value flashes.
”Accepted” appears briefly in the
display, then the address flashes
again. Further addresses can now be
selected with the or button.
The following addresses can bechanged in coding level 1:
System typeBurner typeBoiler max. temp.DHW priority boiler circuitSummer energy saving mode, boilercircuit
DHW priority mixing valve circuitSummer energy saving mode, mixingvalve circuit
Min. supply temp. mixing valvecircuit 1
Max. supply temp. mixing valvecircuit 1
DHW priority mixing valve circuit 2Summer energy saving mode mixingvalve circuit 2
Min. supply temp. mixing valvecircuit 2
Max. supply temp. mixing valvecircuit 2
Press and simultaneously forapprox. 1 second.
The list shown on the left can vary
according to the system equipment
specifications.
Exit coding level 1.
5303271v1.5
Coding 1
System type
Coding 1
IMPORTANT
Additional Information
64
Codings (continued)
Coding 1
See ”Coding 2” for further coding information.
Function Coding (factory default setting)
Address: Value
Possible change
System type 00 : 11 heating circuit without mixing valve
00 : 2 1 heating circuit without mixing valve,with domestic hot water heating1 heating circuit without mixing valve
00 : 3 1 heating circuit with mixing valve
00 : 4 1 heating circuit with mixing valve anddomestic hot water heating
00 : 5 1 heating circuit without mixing valve and1 heating circuit with mixing valve
00 : 6 1 heating circuit without mixing valve and1 heating circuit with mixing valve anddomestic hot water heating
00 : 7 2 heating circuits with mixing valve
00 : 8 2 heating circuits with mixing valve anddomestic hot water heating
00 : 9 1 heating circuit without mixing valve and2 heating circuits with mixing valve
00 : 10 1 heating circuit without mixing valve and2 heating circuits with mixing valve anddomestic hot water heating
Burner type 02 : 0Single-stage
02 : 1 Two-stageBurner type 02 : 0Single-stage 02 : 2 Modulating
Max. boiler temp. 06 : 85Max. boiler water temperature limited to185 ºF / 85 ºC
06 : 20to06 : 130
Maximum boiler water temperature limitvariable between 68 ºF and 266 ºF /20 and 130 ºC
DHW priority (boiler circuit) A2 : 2Tank priority over heating circuit pump
A2 : 0 Without tank priority over heating circuitpumpTank priority over heating circuit pump
A2 : 1A2 : 3toA2 : 15
No function assigned
Summer energysaving function (boilercircuit)
A5 : 5With heating circuit pump logic function(HPL function)
A5 : 0 Without heating circuit pump logicfunction (HPL function)
DHW priority (mixing valvecircuit 1)
A2 : 2Tank priority over heating circuit pumpand mixing valve
A2 : 0 Without tank priority over heating circuitpump and mixing valvecircuit 1) Tank priority over heating circuit pump
and mixing valve A2 : 1 No function assigned
A2 : 3toA2 : 15
No function assigned
Summer energysaving function (mixingvalve circuit 1)
A5 : 5With heating circuit pump logic function(HPL function)
A5 : 0 Without heating circuit pump logic func-tion (HPL function)
Min. temp. (mixing valvecircuit 1)
C5 : 20Electronic minimum supply temperaturelimit 68 ºF / 20 ºC
C5 : 1toC5 127
Electronic minimum supply temperaturelimit variable between 34 ºF and 261 ºF /1 and 127 ºC
5303271v1.5
Additional Information
65
Codings (continued)
Coding 1 (continued)
Function Coding (factory default setting)
Address: Value
Possible change
Max. temp. (mixing valvecircuit 1)
C6 : 75Maximum supply temperature limited to167 ºF / 75 ºC
C6 : 10toC6 : 127
Maximum supply temperature limitvariable between 50 and 261 ºF /10 and 127 ºC
DHW priority A2 : 2Tank priority over heating circuit pumpand mixing valve
A2 : 0 Without tank priority over heating circuitpump and mixing valveTank priority over heating circuit pump
and mixing valve A2 : 1 No function assigned
A2 : 3toA2 : 15
No function assigned
Summer energysaving function
A5 : 5With heating circuit pump logic function(HPL function)
A5 : 0 Without heating circuit pump logicfunction (HPL function)
Min. temp. C5 : 20Electronic minimum supply temperaturelimit 68 ºF / 20 ºC
C5 : 1toC5 : 127
Electronic minimum supply temperaturelimit variable between 34 and 261 ºF /1 and 127 ºC
Max. temp. C6 : 75Maximum supply temperature limited to167 ºF / 75 ºC
C6 : 10toC6 : 127
Maximum supply temperature limitvariable between 50 and 261 ºF /10 and 127 ºC
5303271v1.5
Additional Information
66
Codings (continued)
Coding 2 Information
The following overview lists all possible coding addresses.
Only those coding addresses corresponding to the system type and equipment
specifications are shown and can be changed accordingly.
The coding addresses are structured asillustrated on the left.
In the case of system type 3 (boilercircuit and one mixing valve circuit), thepossible coding addresses ”A0” to ”FF”for the heating circuit without mixingvalve (boiler circuit) are scanned first,then those for the mixing valve circuit,starting again at coding address ”A0”.
In the case of system type 4 (mixingvalve circuit 1 and 2), the possiblecoding addresses ”A0” to ”FF” for themixing valve circuit 1 are scanned first,then those for the mixing valve circuit 2,starting again at coding address ”A0”.
In the case of system type 5 (boilercircuit and mixing valve circuits 1 and2), the possible coding addresses ”A0”to ”FF” for the heating circuit withoutmixing valve (boiler circuit) are scannedfirst, then those for the mixing valvecircuit 1, and then those for the mixingvalve circuit 2, in each case startingagain at coding address ”A0”.
5303271v1.5
System typeCod. 00
Boiler / BurnerCod. 01 to 54
Domestic hot waterCod. 55 to 75
GeneralCod. 76 to 9F
Boiler circuitCod. A0 to FF
Mixing valve circuit 1Cod. A0 to FF
Mixing valve circuit 2Cod. A0 to FF
Additional Information
67
Codings (continued)
Accessing coding level 2
All codings can be changed in coding level 2.
Press and simultaneously forapprox. 2 seconds;press to confirm.
Access coding level 2.
Call up the required coding address withthe or button;press to confirm.
Change the value with the orbutton;press to confirm.
Coding address flashes.
”Accepted” appears briefly in the
display, then the address flashes
again. Further addresses can now be
selected with the or button.
Press and simultaneously forapprox. 1 second.
Exit coding level 2.
Resetting codings to factory default settings
Press and simultaneously forapprox. 2 seconds.
Access coding level 2.
Press .
Press to confirm ”Factory defaultsetting? Yes”.
Codings are reset to the factory
default settings.
The display changes and shows the
boiler water temperature.
”Factory default setting? Yes” or
”Factory default setting? No” can be
selected with the or button.
5303271v1.5
Coding 2
System type
Coding 2
Coding 2
factory default
setting? Yes
IMPORTANT
Additional Information
68
Codings (continued)
Coding 2
Coding
(factory default
setting)
Address: Value
Function New coding
Address:
Value
Possible change
00 : 1 Boiler System type 1 (boiler circuit) withoutdomestic hot water heating
00 : 12 System type 1 (boiler circuit)with domestic hot water heatingdomestic hot water heating
00 : 13 System type 2 (mixing valve circuit 1)without domestic hot water heating
00 : 14 System type 2 (mixing valve circuit 1)with domestic hot water heating
00 : 15 System type 3 (boiler circuit andmixing valve circuit 1)without domestic hot water heating
00 : 16 System type 3 (boiler circuit andmixing valve circuit 1)with domestic hot water heating
00 : 17 System type 4 (mixing valve circuits1 and 2) without domestic hot waterheating
00 : 18 System type 4(mixing valve circuits 1 and 2)with domestic hot water heating
00 : 19 System type 5 (boiler circuit, mixingvalve circuits 1 and 2)without domestic hot water heating
00 : 10 System type 5 (boiler circuit, mixingvalve circuits 1 and 2)with domestic hot water heating
02 : 0 Boiler/
burner
Operation with single-stage burner 02 : 1 Operation with two-stage burner02 : 0 Boiler/
burner
Operation with single-stage burner
02 : 2 Operation with modulating burner
03 : 0 Boiler/
burner
Gas-fired operation 03 : 1 Oil-fired operation
5303271v1.5
Additional Information
69
Codings (continued)
Coding 2 (continued)
Coding
(factory default
setting)
Address: Value
Function New coding
Address:
Value
Possible change
04 : 0 Boiler/
burner
Switching hysteresis7.2 ºF / 4 ºC
Burner ON
OFF
Set-point
J
+2
–2
Lowheat demand
Mediumheat demand
Highheat demand
Time
04 : 1
04 : 2
Switching hysteresis heat demand-
controlled
ERB50 function
Values between 10.8 and 21.6 ºF /6 and 12 ºC are set, depending onthe heat demand.
orERB80 function
Values between 10.8 and 36 ºF /6 and 20 ºC are set, depending onthe heat demand.
The heat demand-controlledswitching hysteresis takes intoaccount the boiler load.The switching hysteresis, i.e. theburner operating time, is varied inrelation to the current heat demand.
Burner
J Set-J point
Lowheat demand
Mediumheat demand
Highheat demand
Time
ON
OFF
+9+3
–3
Burner
J Set-J point
+17
+3
–3
Time
Lowheat demand
Mediumheat demand
Highheat demand
ON
OFF
05 : 8 Boiler/
burner
Differential temperature 14.4 ºF /8 ºC (only adjustable with systemtypes 3 to 10)
05 : 0to05 : 40
Differential temperature variable from0 to 72 ºF / 0 to 40 ºC
06 : 85 Boiler/
burner
Max. limit of boiler water temperatureset to 185 ºF / 85 ºC
06 : 20to06 : 130
Max. limit of the boiler water tempera-ture variable between 68 and 266 ºF /20 and 130 ºC
10 : 20 Boiler/
burner
(two-
stage)
Switch-on delay (integral) = 2560 Cs(Celsius x seconds)
10 : 0to10 : 199
Switch-on delay for release of 2ndstage (to 1st stage) during the heatingmode variable; 1 increment = 128 CsRange: 0 to 25472 Cs
11 : 20 Boiler/
burner
(two-
stage)
Switch-on delay (integral) = 2560 Cs(Celsius x seconds)
11 : 0to11 : 199
Switch-on delay for release of 2ndstage (to 1st stage) during tank heat-ing variable; 1 increment = 128 CsRange: 0 to 25472 Cs
5303271v1.5
Additional Information
70
Codings (continued)
Coding 2 (continued)
Coding
(factory default
setting)
Address: Value
Function New coding
Address:
Value
Possible change
12 : 20 Boiler/
burner
(two-
stage)
Switch-off delay (integral) = 2560 Cs(Celsius x seconds)
12 : 0to12 : 199
Switch-off delay for burner disable 1ststage (from 2nd stage) variable;1 increment = 128 CsRange: 0 to 25472 Cs
13 : 6 Boiler/
burner
Switch-off differential 10.8 ºF / 6 ºCThe burner is switched off when the
13 : 0 Without switch-off differential13 : 6 Boiler/
burner
(two-stage
/mod.)
Switch-off differential 10.8 ºF / 6 ºCThe burner is switched off when theboiler water temperature rises 10.8 ºF/ 6 ºC above the desired value
13 : 1to13 : 20
Switch-off differential adjustablebetween 1.8 and 36 ºF /1 and 20 ºC
15 : 15 Boiler/
burner
(two-stage
/mod.)
Operating time of actuator drive15 seconds
15 : 7to15 : 180
Operating time adjustable between7 and 180 seconds
16 : 6 (Mod.)
burner
Mod. burner offset 10.8 ºF / 6 ºC 16 : 0to16 : 15
Offset during optimized start-upadjustable from 0 and 27 ºF /0 to 15 ºC
17 : 12 (Mod.)
burner
Control gain 12 17 : 0to17 : 255
Setting according to matching ofmodulating burner to the boiler typeconcerned
18 : 300 (Mod.)
burner
Integral time 300 18 : 1to18 : 1000
Setting according to matching ofmodulating burner to the boiler typeconcerned
1A : 6 (Mod.)
burner
Optimized start-up 6 minutes 1A : 0to1A : 60
Duration of optimized start-upadjustable from 0 to 60 minutes
1F : 0 Boiler/
burner
No monitoring of flue gas temperature(only with flue gas temperaturesensor connected)
1F : 1to1F0 : 500
When the flue gas temp. exceedsthe preselected limit value (select-able between 36 to 932 ºF / 2 to500 ºC), ”SERVICE” is displayed
21 : 0 Boiler/
burner
No service display for burner 21 : 1to21 : 9999
The number of burner operatinghours before the ”Service” displayappears can be set between 1 and9999 hours
23 : 0 Boiler/
burner
No time interval for burnermaintenance
23 : 1to23 : 24
Time interval variable between 1and 24 months
24 : 0 Boiler/
burner
No ”Service” display 24 : 1 The ”Service” display appears(address is set automatically andmust be reset manually after main-tenance has been performed)
26 : 0 Boiler/
burner
Fuel consumption of burner(1st stage) not counted
26 : 1to26 : 9999
Input from 1 to 9999, wherebyeach increment = 0.1 liter orgallon/hourExample: 20 = 2.0 liters/gallonsper hour
28 : 0 Boiler/
burner
No burner cycling 28 : 1 Burner is automatically switched onfor 30 seconds after 5 hours
5303271v1.5
Additional Information
71
Codings (continued)
Coding 2 (continued)
29 : 0 Boiler/
burner
Fuel consumption of burner(2nd stage) not counted
29 : 1to29 : 9999
Input from 1 to 9999, wherebyeach increment = 0.1 liter orgallon/hourExample: 20 = 2.0 liters/gallonsper hour
32 : 70 Boiler/
burner
Only in conjunction with SwitchingModule-V:Min. boiler water temperature setpointvalue 158 ºF / 70 ºC with externalburner activation
32 : 0to32 : 127
Minimum boiler water temp. set-point variable between 32 and261 ºF / 0 and 127 ºC; note adjust-ment of adjustable high limit ” ”.
33 : 0 Boiler/
burner
Only in conjunction with SwitchingModule-V:Pumps and mixing valve remain incontrol mode with external burneractivation
33 : 1 All pumps OFFMixing valve closed
55 : 0 DHW Tank heating, hysteresis +/- 4.5 ºF /2.5 ºC
55 : 1 Adaptive tank heating active(takes into account the rate atwhich the tank temperatureincreases during domestic hotwater heating)
55 : 0 DHW Tank heating, hysteresis +/- 4.5 ºF /2.5 ºC
55 : 2 2nd tank temperature sensorconnected
56 : 0 DHW Setting range of domestic hot watertemperature 50 to 140 ºF /10 to 60 ºC
56 : 1 Setting range of domestic hot watertemperature 50 to 203 ºF / 10 to95 ºC
Observe max. DHW temperature
Adjust adjustable high limit ” ”
IMPORTANT
58 : 0 DHW Without additional function fordomestic hot water heating
58 : 1to58 : 95
Input of a 2nd desired DHW tem-perature value; variable between34 and 140 ºF / 1 and 60 ºCwith coding ”56: 0”,
34 and 203 ºF / 1 and 95 ºCwith coding ”56: 1”.
The DHW tank is heated to the 2nd
setpoint value during the 4th activa-
tion period for DHW heating (for
settings see operating instructions).
IMPORTANT
5303271v1.5
Additional Information
72
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
59 : 0 DHW Tank heating:Switch-on point – 4.5 ºF / – 2.5 ºCSwitch-off point + 4.5 ºF / +2.5 ºC
59 : 1to59 : 10
Switch-on point variable between1.8 and 18 ºF / 1 and 10 ºC belowsetpoint value
60 : 20 DHW When domestic hot water is beingheated, the boiler water temperatureis a max. of 36 ºF / 20 ºC higher thanthe desired domestic hot watertemperature
60 : 10to60 : 50
Differential between boiler watertemperature and desired DHW tem-perature adjustable between 18 and90 ºF / 10 and 50 ºC
61 : 0 DHW Recirculation pump activationdependent upon boiler watertemperature
61 : 1 Recirculation pump switches onimmediately
62 : 10 DHW Circulation pump with max. run-ontime of 10 minutes
62 : 0 Circulation pump without run-ontimetime of 10 minutes
62 : 1to62 : 15
Run-on time variable from 1 to 15minutes
64 : 2 DHW During the party mode:Continuous domestic hot water heat-ing and DHW recirculation pump ON
64 : 0 During the party mode:No domestic hot water heating,DHW recirculation pump OFFing and DHW recirculation pump ON
64 : 1 During the party mode:Domestic hot water heating andDHW recirculation pump accordingto preset time program
66 : 4 DHW Input of DHW temperature setpoint onthe programming unit of the controlunit and on all installed Vitotrol 300remote controls
66 : 0 Input of DHW temperature setpointonly on the programming unit of thecontrol unitunit and on all installed Vitotrol 300
remote controls 66 : 1 Input of DHW temperature setpointon the programming unit of thecontrol unit and on the remote con-trol (boiler circuit)
66 : 2 Input of DHW temperature setpointon the programming unit of thecontrol unit and on the remote con-trol (mixing valve circuit 1)
66 : 3 Input of DHW temperature setpointon the programming unit of thecontrol unit and on the remote con-trol (mixing valve circuit 2)
66 : 5 Input of DHW temperature setpointonly on the remote control (boilercircuit)
66 : 6 Input of DHW temperature setpointonly on the remote control (mixingvalve circuit 1)
66 : 7 Input of DHW temperature setpointonly on the remote control (mixingvalve circuit 2)
5303271v1.5
Additional Information
73
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
67 : 40 DHW With Vitosolic:3rd set DHW temperature at 40 ºC/104 ºF. Re-heating will be suppressed
67 : 0 Without 3rd set DHW temperature
104 ºF. Re-heating will be suppressedabove the selected temperature. TheDHW tank is heated exclusively bythe solar heating system.
67 : 1to67 : 95
Input of a 3rd set DHWtemperature; adjustable from 1 to95 ºC/ 203 ºF
68 : 8 DHW Factor for switch-off point 0.8(effective with coding address ”55”)
68 : 2to68 : 10
Factor for switch-off point variablebetween 0.2 and 1.0
69 : 7 DHW Factor for switch-on point 0.7(effective with coding address ”55”)
69 : 1to69 : 9
Factor for switch-on point variablebetween 0.1 and 0.9
70 : 0 DHW DHW recirculation pump ON accordingto preset time program when DHWheating is released
70 : 1 DHW recirculation pump ONaccording to preset time program
71 : 0 DHW DHW recirculation pump ON with tankheating according to preset time pro-gram
71 : 1 DHW recirculation pump OFF duringdomestic hot water heating to the1st setpoint valuegram
71 : 2 DHW recirculation pump ON duringdomestic hot water heating to the1st setpoint value
72 : 0 DHW DHW recirculation pump ON with ac-tive additional function for domestichot water heating according to presettime program (see coding address”58”)
72 : 1 DHW recirculation pump OFF duringdomestic hot water heating to the2nd setpoint value(see coding address ”58”)time program (see coding address
”58”) 72 : 2 DHW recirculation pump ON duringdomestic hot water heating to the2nd setpoint value(see also coding address ”58”)
73 : 0 DHW DHW recirculation pump ON accordingto preset time program
73 : 1to73 : 6
During the time program for theDHW recirculation pumpON for 5 minutes once per hourtoON for 5 minutes 6 times per hour
73 : 7 DHW recirculation pump ONcontinuously
74 : 5 DHW In conjunction with SwitchingModule-V: The DHW recirculationpump can be switched on for 5 min-utes via potential-free contact
74 : 0to74 : 15
Switch-on time adjustable from 0 to15 minutes
5303271v1.5
Additional Information
74
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
75 : 0 DHW During energy saving mode:DHW recirculation pump ON accordingto preset time program
75 : 1 During energy saving mode:DHW recirculation pump OFF
7F : 1 General Single-family house 7F : 0 Multi-family house
80 : 1 General Fault messages are displayed with5 seconds time delay
80 : 0 Without time delay80 : 1 General Fault messages are displayed with5 seconds time delay 80 : 2
to80 : 199
Time delay adjustable between 2and 199 (selected value x 5 s)
81 : 1 General Automatic resetting to summer/wintertime
IMPORTANT
81 : 0 Manual resetting to summer/wintertime
Coding addresses ”82” to ”87” are
only possible if address ”81: 1” is
coded.
IMPORTANT
81 : 2 No function assigned
82 : 3 General Start of summer time: March 82 : 1to82 : 12
JanuarytoDecember
83 : 5 General Start of summer time: last weekof month
83 : 1to83 : 5
Week 1toWeek 5 of the selected month
84 : 7 General Start of summer time: last dayof week(Sunday)
84 : 1to84 : 7
MondaytoSunday
85 : 10 General Start of winter time: October 85 : 1to85 : 12
JanuarytoDecember
86 : 5 General Start of winter time: last weekof month
86 : 1to 86 : 5
Week 1to Week 5 of the selected month
87 : 7 General Start of winter time: last dayof week(Sunday)
87 : 1to87 : 7
MondaytoSunday
88 : 0 General ºC Temperature display 88 : 1 ºF Temperature display
89 : 1 General Automatic recognition of KM-BUSparticipant
89 : 0 No participant recognition
8A : 175 General Display conditions active 8A : 176 All codings visible
5303271v1.5
Additional Information
75
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
8E : 4 General Fault display and confirmation on theprogramming unit and on all installedVitotrol 300 remote controls
8E : 0 Fault display and confirmation onlyon the programming unit of thecontrol unitVitotrol 300 remote controls
8E : 1 Fault display and confirmation onthe programming unit of the controlunit and on the remote control(boiler circuit 1)
8E : 2 Fault display and confirmation onthe programming unit of the controlunit and on the remote control(mixing valve circuit 1)
8E : 3 Fault display and confirmation onthe programming unit of the controlunit and on the remote control(mixing valve circuit 2)
90 : 128 General Time constant for calculating the out-door temperature change 21.3 hours(selected value x 10 minutes)
90 : 1to90 : 199
Fast matching (lower values) or slowmatching (higher values) of thesupply temperature to the change inthe outdoor temperature (selectedvalue x 10 minutes)
91 : 7 General External switching of heatingprograms:
91 : 0 Without switching heating programs91 : 7 General External switching of heatingprograms:Switching effective for all heating cir-cuits (boiler and mixing valve circuits)(Connection via connector )
91 : 1Switching effective for:Heating circuit without mixing valve(boiler circuit)
(Connection via connector )91 : 2 Heating circuit with mixing valve
(mixing valve circuit 1)
91 : 3 Heating circuit without mixing valve(boiler circuit) and heating circuitwith mixing valve (mixing valvecircuit 1)
91 : 4 Heating circuit with mixing valve(mixing valve circuit 2)
91 : 5 Heating circuit without mixing valve(boiler circuit) and heating circuitwith mixing valve (mixing valvecircuit 2)
91 : 6 Heating circuits with mixing valve(mixing valve circuits 1 and 2)
92 : 1 General With fault indication module
93 : 0 General Emissions test mode/service displaynot effective for compiled faultindicator
93 : 1 Emissions test mode/servicedisplay effective for compiled faultindicator
94 : 0 General Without Switching Module-V 94 : 2 With Switching Module-V(recognized automatically)
95 : 0 General Without communication interfaceVitocom 100
95 : 1 With communication interfaceVitocom 100(recognized automatically)
5303271v1.5
Additional Information
76
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
98 : 0 General Without expansion moduleViessmann 2-wire-BUS
98 : 1 With expansion moduleViessmann 2-wire-BUS(recognized automatically)
9d : 0 General Without Input extension module0 to 10V
9d : 1 With Input extension module0 to 10V(recognized automatically)
A0 : 0 Boiler circuit/
mixing valve
Without remote control A0 : 1 With Vitotrol 200 remote controlmixing valve
circuitA0 : 2 With Vitotrol 300 remote control
A2 : 2 Boiler circuit/
mixing valve
circuit
With DHW tank priority control overheating circuit pump and mixingvalve
A2 : 0 Without DHW tank priority overheating circuit pump and mixingvalvecircuit valve
A2 : 1*1 Mixing valve closed, heating circuitpump ON while tank is being heated
A2 : 3*1
toA2 : 15
Reduced tank priority over mixingvalve; i.e. the heating circuit issupplied with a reduced amount ofheat
A3 : 2 Boiler circuit/
mixing valve
circuit
The heating circuit pump is switchedon at outdoor temperatures below34 ºF / 1 ºC.The heating circuit pump (boilercircuit) is switched off at outdoortemperatures above 37 ºF / 3 ºC.
At settings below 34 ºF / 1 ºC there
is a risk that piping outdoor the
insulation of the building may freeze,
e.g. pipes in the roof space, to the
garage, in radiator alcoves etc. Pay
particular attention to the stand-by
mode, e.g. during holiday periods.
IMPORTANT
A3 : –9A3 : –8A3 : –7A3 : –6A3 : –5A3 : –4A3 : –3A3 : –2A3 : –1A3 : –0A3 : –1A3 : –2.
.
.
A3 : 15
Heating circuit pumpON at OFF at14 ºF / –10 ºC 18 ºF / –8 ºC16 ºF / –19 ºC 19 ºF / –7 ºC18 ºF / –18 ºC 21 ºF / –6 ºC19 ºF / –17 ºC 23 ºF / –5 ºC21 ºF / –16 ºC 25 ºF / –4 ºC23 ºF / –15 ºC 27 ºF / –3 ºC25 ºF / –14 ºC 28 ºF / –2 ºC27 ºF / –13 ºC 30 ºF / –1 ºC28 ºF / –12 ºC 32 ºF / –0 ºC30 ºF / –11 ºC 34 ºF / –1 ºC32 ºF / –10 ºC 36 ºF / –2 ºC34 ºF / –11 ºC 37 ºF / –3 ºC.
.
.
57ºF / 14 ºC 61 ºF / 16 ºC
5303271v1.5
Additional Information
77
Codings (continued)
Coding 2 (continued)
A4 : 0 Boiler circuit/
mixing valve
circuit
With frost protection A4 : 1 No frost protection, setting onlypossible when coding ”A3 : –9” isset
A5 : 5 Boiler circuit/
mixing valve
circuit
With the heating circuit pump logicfunction (HPL function), the heatingcircuit pump is switched off whenthe outdoor temperature (OT) rises1.8 ºF / 1 ºC above the desired roomtemperature (RTdes).OT > RTdes + 1.8 ºF / + 1 ºC
A5 : 0
A5 : 1A5 : 2A5 : 3A5 : 4A5 : 5A5 : 6A5 : 7.
.
.
A5 : 15
Without heating circuit pump logicfunction (HPL function). Theheating circuit pump is switchedoff ifOT > RTdes + 9 ºF / + 5 ºCOT > RTdes + 7.2 ºF / + 4 ºCOT > RTdes + 5.4 ºF / + 3 ºCOT > RTdes + 3.6 ºF / + 2 ºCOT > RTdes + 1.8 ºF / + 1 ºCOT = RTdesOT > RTdes – 1.8 ºF / – 1 ºC.
.
.
OT > RTdes – 16.2 ºF / – 9 ºC
A6 : 36 Boiler circuit/
mixing valve
circuit
Automatic switching from normalheating to summer operation not
active
A6 : 5toA6 : 35
Automatic switching from normalheating to summer operation*1 at avariable setting value from 41 to95 ºF / 5 to 35 ºC plus 1.8 ºF /1 ºC at which the burner and heat-ing circuit pump are switched offand the mixing valve is closed
A7 : 0 Mixing valve
circuit
Without mixing valve energy savingfunction
A7 : 1 With mixing valve energy savingfunction (extended heating circuitpump logic)The heating circuit pump can beswitched off additionally when themixing valve has been closed forlonger than 12 minutes.The heating circuit pump isswitched on againwhen the mixing valve switchesto the control mode
after the tank has been heated(for 20 minutes)
when there is a risk of freezing
A9 : 0 Boiler circuit/
mixing valve
circuit
Without pump off time A9 : 1toA9 : 15
With pump off time:Heating circuit pump logic functionwith change of setpoint (throughchanging the operating mode orchanges on the ” „? ” selectorknob or ” „?” button).
*1Only selectable for the heating circuit with mixing valve
5303271v1.5
Additional Information
78
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
b0 : 0*2 Boiler circuit/
mixing valve
circuit
In conjunction with remote control:Weather-responsive operation only innormal heating mode and in reducedheating mode
b0 : 1 Weather-responsive operation innormal heating mode and with roomtemperature dependent control inreduced heating modeheating mode
b0 : 2 Room temperature dependentcontrol in normal heating mode andweather-responsiveoperation in reduced heating mode
b0 : 3 Room temperature dependentcontrol in normal heating mode andin reduced heating mode
b1 : 0*2 Boiler circuit/
mixing valve
circuit
In conjunction with remote control:Without pure room temperaturecontrol
b1 : 1 Heating circuit with roomtemperature dependent control
b2 : 8*2 Boiler circuit/
mixing valve
In conjunction with remote control:Room influence factor: 8
b2 : 0 Without room temperature inputmixing valve
circuit
Room influence factor: 8Operation with room temperaturecontrol (feedback) must be coded forthis heating circuit.
b2 : 1tob2 : 31
Room influence factor adjustablefrom 1 to 31
b3 : 0*2 Boiler circuit/
mixing valve
circuit
In conjunction with remote control:Basic value: 127 ºF / 53 ºCOperation with room temperaturecontrol must be coded for theheating circuit.
b3 : 1 Basic value: 100 ºF / 8 ºC
b5 : 0*1 Boiler circuit/
mixing valve
circuit
In conjunction with remote control:No room temperature controlled heat-ing circuit pump logic function
b5 : 1 Heating circuit pump OFF ifactual room temperature (RTact)is 1.8 ºF / 1 ºC higher than de-sired room temperature (RTdes)RTact > RTdes + 1.8 ºF / 1 ºC
Heating circuit pump ON if actualroom temperature (RTact) is1.8 ºF / 1 ºC lower than desiredroom temperature (RTdes)RTact < RTdes + 1.8 ºF / 1 ºC
*1 Based on the damped outdoor temperature which is calculated from the current outdoor temperature and a time constant which takes into account the
cooling characteristics of an average building.*2 Coding changes for boiler circuit only on boilers without low limit or for the heating circuit with mixing valve if the remote
control is effective for this heating circuit.
5303271v1.5
Additional Information
79
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
b6 : 0*1 Boiler circuit/
mixing valve
circuit
In conjunction with remote controlwith room temperature controlWithout boost heating/rapid setback
b6 : 1 With boost heating/rapid setback
Rapid setback:Only possible withweather-responsive operation withthe room temperature sensor orwith room temperature dependentcontrol.The desired room temperature valuemust be reduced by at least 3.6 ºF /2 ºC bypressing the energy savingbutton ”S”
switching over from normal toreduced operation
optimized switch-off.Rapid setback ceases when thedesired room temperature isreached.
Boost heating:Only possible withweather-responsive operation withthe room temperature sensor orwith room temperature dependentcontrol.The desired room temperature valuemust be increased by at least3.6 ºF / 2 ºC bypressing the party buttonswitching over from reduced tonormal operation
optimized switch-on.Boost heating ceases when the de-sired room temperature is reached.
*1Coding changes for the boiler circuit only on boilers without low limit or for the heating circuit with mixing valve if the remote control
is effective for this heating circuit.
5303271v1.5
Additional Information
80
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
b7 : 0*1 Boiler circuit/mixing valvecircuit
In conjunction with remote control inroom sensing modeWithout optimized switch-on time
b7 : 1
b7 : 2
With optimized switch-on time(max. time shift 2 hours 30minutes)
With optimized switch-on time(max. time shift 15 hours 50minutes)
b8 : 10*1 Boiler circuit/mixing valvecircuit
Heat-up gradient:Optimized switch-on time10 minutes/Celsius
b8 : 11tob8 : 255
Heat-up gradient for optimizedswitch-on time variable between11 and 255 minutes/Celsius
b9 : 0*1 Boiler circuit/mixing valvecircuit
Without learning optimized switch-ontime
b9 : 1 With learning optimized switch-ontime
C0 : 0*1 Boiler circuit/mixing valvecircuit
In conjunction with remote control:Without optimized switch-off time C0 : 1
In conjunction with remote control:With optimized switch-off time(max. time shift 1 hour)circuit
C0 : 2In conjunction with remote control:With optimized switch-off time(max. time shift 2 hours)
C1 : 0*1 Boiler circuit/mixing valvecircuit
In conjunction with remote control:Without optimized switch-off time
C1 : 1toC1 : 12
In conjunction with remotecontrol:With optimized switch-off time(max. time shift from 10 to 120minutes)
C2 : 0*1 Boiler circuit/mixing valvecircuit
Without learning optimized switch-offtime
C2 : 1 With learning optimized switch-offtime
C4 : 1 Mixing valvecircuit
System dynamics - mixing valvecontrol characteristics
C4 : 0toC4 : 3
Controller responds too quickly(cycles between “open” and“closed”):Select a lower valueController responds too slowly(temperature is not heldsufficiently):Select a higher value
C5 : 20 Boiler circuit/
mixing valve
circuit
Electronic minimum supplytemperature limit 68 ºF / 20 ºC
C5 : 1toC5 : 127
Electronic minimum supplytemperature limit variable between34 and 261 ºF / 1 and 127 ºC
C6 : 75 Mixing valve
circuit
Maximum supply temperature limitset to 167 ºF / 75 ºC
C6 : 10toC6 : 127
Max. supply temperature limitvariable between 50 and 261ºF /10 and 127 ºC
C7 : 0 Mixing valve
circuit
In conjunction with return watertemperature sensor:Without influence of return watertemperature sensor
C7 : 1toC7 : 31
Spread variable from 1.8 to 68 ºF /1 to 31 ºCSpread = temperature differencebetween supply and return at sys-tem point - 50 ºF / - 10 ºC
C8 : 31 Boiler circuit/mixing valvecircuit
In conjunction with remote control:Without limit on room temperatureinput
C8 : 1toC8 : 30
Limit on room influence variablefrom 1.8 to 54 ºF / 1 to 30 ºC
*1Coding changes for the boiler circuit only on boilers without low limit or for the heating circuit with mixing valve if the remote
control is effective for this heating circuit.
5303271v1.5
Additional Information
81
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
C9 : 0 Mixing valve
circuit
Underfloor heating systemcontrolled by supply temperaturesensor and mixing valve
C9 : 1 Optimized control of underfloorheating system with supply andreturn water temperature sensor(effective with coding address”C7”)
d3 : 14 Boiler circuit/
mixing valve
circuit
Do not adjust
d4 : 0
mixing valve
circuit
E1 : 1 Boiler circuit/
mixing valve
circuit
In conjunction with remote control:Day setpoint value variable from50 to 86 ºF / 10 to 30 ºC
E1 : 0 Day setpoint value variable from37 to 73 ºF / 3 to 23 ºCmixing valve
circuit
Day setpoint value variable from50 to 86 ºF / 10 to 30 ºC E1 : 2 Day setpoint value variable from
63 to 99 ºF / 17 to 37 ºC
E2 : 50 Boiler circuit/
mixing valve
circuit
In conjunction with remote control:No display correction for currentroom temperature value
E2 : 0toE2 : 49
Display correction – 9 ºF / – 5 ºCtoDisplay correction – 0.18 ºF /
– 0.1 ºC
E2 : 51toE2 : 99
Display correction + 0.18 ºF/ ++ 0.1 ºC
toDisplay correction + 8.8 ºF /
+ 4.9 ºC
E5 : 0 Boiler circuit/
mixing valve
circuit
Without variable speedheating circuit pump
E5 : 1 With variable speed heating circuitpump (recognized automatically)
E6 : 100 Boiler circuit/
mixing valve
circuit
Maximum speed of variable speedpump 100 % of max. speed in normaloperation
E6 : 0toE6 : 100
Maximum speed variable between0 and 99 % of max. speed
E7 : 20 Boiler circuit/
mixing valve
circuit
Minimum speed of variable speedpump 20 % of max. speed
E7 : 0toE7 : 100
Minimum speed variable between0 and 100 % of max. speed
E8 : 0 Boiler circuit/
mixing valve
circuit
Minimum speed according to settingin coding address ”E7”
E8 : 1 Speed according to setting incoding address ”E9”
E9 : 20 Boiler circuit/
mixing valve
circuit
Speed of variable speed pump 20 %of max. speed in reduced operation
E9 : 0toE9 : 100
Speed variable between 0 and100 % of max. speed
F0 : 0 Without function, do not change
5303271v1.5
Additional Information
82
Codings (continued)
Coding 2 (continued)
Coding factorydefault setting)Address: Value
Function New codingAddress:Value
Possible change
F1 : 0 Mixing valvecircuit
Slab curing function not active
F1 : 1
F1 : 2
F1 : 3
F1 : 4
The service report to be completedby the heating contractor must con-tain the following data:Heating data for the corresponding
supply temperaturesMax. supply temperature reachedOperating status and outdoor tem-
perature after completion ofinstallation
Slab curing function selectable onbasis of four temperature/timecurves:Temperature/time curve 1:
Temperature/time curve 2:
Temperature/time curve 3:
Temperature/time curve 4:
The function is resumed after apower outage or after the controlunit is switched off.When the slab curing function hasterminated or the address is resetmanually to 0, the ” ” heatingprogram is switched on.
Supplytemperature
Supplytemperature
Supplytemperature
Supplytemperature
Days
Days
Days
Days
122
104
86
68
50
122
104
86
68
50
122
104
86
68
50
122
104
86
68
50
ºF / ºC
ºF / ºC
ºF / ºC
ºF / ºC5303271v1.5
Additional Information
83
Codings (continued)
Coding 2 (continued)
Coding (factory
default setting)
Address: Value
Function New coding
Address:
Value
Possible change
F2 : 0 Boiler circuit/mixing valvecircuit
No time limit for party mode F2 : 1toF2 : 12
Time limit for party mode variablebetween one and twelve hours
F8 : -5 Boiler circuit/mixing valvecircuit
Below an outdoor temperature of-5 ºC/ 23 ºF, the set roomtemperature in operation withreduced room temperature is raisedto a temperature which is subject tothe outdoor temperature (up to thetemperature limit in accordance with
F8: +10toF8: -60
Temperature limit for raising thetemperature in reduced mode,adjustable from +10 to -60 ºC/+50 to -76 ºF
temperature limit in accordance withcoding address “F9”).Observe the setting of codingaddress “A3”.
F8: -61 Function disabled
F9 :-14 Boiler circuit/mixing valvecircuit
Below an outdoor temperature of-14 ºC/ 7 ºF the set roomtemperature will be raised to thevalue selected as set roomtemperature, if the system is instandard room temperature mode.
F9 : +10toF9 : -60
Temperature limit for raising theset room temperature to the valueselected for standard modeadjustable from +10 to -60 ºC/+50 to -76 ºF
FA : 20 Boiler circuit/mixing valvecircuit
Raising the set supply temperaturefor the transition from reducedtemperature mode to standard roomtemperature mode by about 20%
FA : 0toF9 : 50
Raising the set supply temperaturefor the transition from reducedroom temperature mode tostandard room temperature mode,adjustable from 0 to 50%
Fb : 30 Boiler circuit/mixing valvecircuit
Duration for raising the set supplytemperature (see coding address“FA”): 60 min
Fb : 0toFb : 150
Duration for raising the set supplytemperature, adjustable from 0 to300 min; 1 step = 2 min.
5303271v1.5
Additio
nalInformation
84
Wirin
gD
iagra
m
5303 271 v1.5
Selector buttons Programming unit
Mother board
Electronics board
Expansionmodule
BoilercodingcardPower
supplyunit
ON ON
Boiler circuit
Additional Information
85
Wiring Diagram (continued)
Legend
A1 Mother boardA2 Power supply boardA3 Electronics boardA4 Heating circuit selector button boardA5 Programming unitA6 Boiler coding cardA7 Fault indication module (accessory)A11 Optolink/emissions test switch boardA12 Expansion module Viessmann 2-wire-BUS (accessory)F1, F2 FusesF6 Fixed high limit ” ” 230 ºF / 110 ºC (212 ºF / 100 ºC)F7 Adjustable high limit ” ” 167 ºF / 75 ºC (203 ºF / 95 ºC,
212 ºF / 100ºC, 230 ºF / 110 ºC)K1-K5 RelaysS1 Heating system on/off switch ” ”S2 FHL test switchS3 Emissions test switch ” ”V1 Fault indicator (red)V2 Operating status indicator (green)
120 VAC connectors
Interconnections Power Pump Control ModulePower supply connection, 60 HzOil / Gas burner connectionCentral fault indicatorExternal equipment:
External safety devices(remove jumper when connecting)External control switch-off(remove jumper when connecting)External burner activation (1st stage)
Power supply connection for accessories, 60 Hz
Low voltage connectors
Outdoor temperature sensorBoiler temperature sensorDHW tank temperature sensor(only connected if DHW tank installed)Flue gas temperature sensor (accessory)Telephone connectionKM-BUS participant, e.g. Vitotrol remote control2nd stage burner / burner modulation
Type / Model Timeconstant
Adjustable high limit RAK 51.1/3382, Etheco or TR 97.55180.251, EGO tt 45 sec
Fixed high limit RAK 75.4/3412, Etheco or STW 56.10525.400, EGO tt 45 sec
The wiring diagram on the previous page applies only when Viessmann products are used.
5303271v1.5
Additional Information
86
Parts List
VVVVIIIITTTTOOOOTTTTRRRROOOONNNNIIIICCCC 333300000000
KW3 SeriesSerial No. 7187091
Ordering Replacement Parts:
Please provide Model and Serial Numberfrom rating plate A when orderingreplacement parts. Order replacementcomponents from your Viessmanndistributor.
Parts
001 Cable clip004 Adjustable high limit dial ” ”005 Cover for fixed high limit ” ”010 Front flip-down cover011 Control panel, bottom right013 Housing, top (drawer)014 Circuit board cover assembly015 Flip-down cover of programming unit016 Housing, bottom017 Control housing, rear018 Programming unit019 Front cover for heating circuit
selector buttons020 Flat cable, 14-pole023 Fuse holder024 Fuse holder cover030 Fixed high limit ” ”031 Adjustable high limit ” ”033 Adjustable high limit rotary knob ” ”035 Switch, 1-pole (FHL test switch)036 Switch, 2-pole (ON/OFF switch ” ”)040 Outdoor temperature sensor042 Boiler temperature sensor with
plug-in connector043 DHW tank temperature sensor with
plug-in connector050 Circuit board control (software)051 Optolink circuit board052 Motherboard053 Fault indication module (accessory)054 Power supply circuit board056 Viessmann 2-wire BUS
Expansion Module (accessory)065 Control cable074 Connecting cable090 Fuse T 4 A / 250 VAC091 Fuse T 6.3 A / 250 VAC092 Fuse holder098 Pack of strain relief clamp parts
Other Parts (not illustrated)099 Pack of mounting screws120 Power/Pump Module121 Installation Instructions122 Service Instructions123 Operating Instructions124 Parts ListA Rating plate 5303271v1.5
Additional Information
87
Parts List (continued)
5303271v1.5
074018
015
013 042
043
065
040
074
014
017
098
016
005
035
024091
023
004
033
036011 030 031
051
053
050 054
052
092
090
020019
010
001
056
Viessmann Manufacturing Company Inc.750 McMurray RoadWaterloo, Ontario • N2V 2G5 • Canada1-800-387-7373 • Fax (519) 885-0887www.viessmann.ca • [email protected]
Viessmann Manufacturing Company (U.S.) Inc.45 Access RoadWarwick, Rhode Island • 02886 • USA1-800-288-0667 • Fax (401) 732-0590www.viessmann-us.com • [email protected]
88
Quick Reference
°C °F
-40 -40-35 -31-25 -13-20 -4-18 0-16 +3-14 +7-12 +10-10 +14-9 +16-8 +18-7 +19-6 +21-5 +23-4 +25-3 +27-2 +28-1 +300 +32
+1 +34+2 +36+3 +37+4 +39+5 +41+6 +43+7 +45+8 +46+9 +48+10 +50+12 +54+14 +57+16 +61+18 +64+20 +68+25 +77+30 +86+35 +95+40 +104+50 +122+60 +140+70 +158+80 +176+90 +194+100 +212+110 +230
Technicalinformationsubjectto
changewithoutnotice.
Printedonenvironmentally
friendly
(recycledandrecyclable)paper.
5303271v1.5