5500 power supply board typical application a installation …
TRANSCRIPT
Page #4
No Output Power @ No Output @
4321 Check input line power.
Check line fuse.Check F2 & F3 output fuses.Check FAC (If applicable) terminals1 & 2 must be wired to N/C contact.
Check jumper settings on CM/CMTD module(If applicable).Check jumper setting on DB-5/DB-10 card.Check for proper access switch contact status.Check load & external wiring for short condition.Reset Power Supply (With no load) bydisconnecting input power at for 2 minutes.
BA
ELECTROMAGNETIC LOCK
Access controllegal release
TYPICAL APPLICATION
Normally-closed drycontact from Fire AlarmControl panel (By others).
Fail Secure lockingFail Safe locking device.
TROUBLESHOOTING
120 VAC50/60 HZINPUT
A
B
A
Normally open access/egress controls.Normally closed access/egress controls.D
DB
E
E
C
C
1
Note: Start at ‘No Output Power @ A
67
5
89
FAC Option
BBU (Battery Back-Up) Option
12V BBU1-4 or BBU1-7
24V BBU2-7 or BBU2-7
5500 Enclosure
BA
C
Enclosure Options:
C
B
A -KLC, (Key Lock Cover)-FACMR, (FAC Manual Reset)-ATS, (Anti-Tamper Switch) Note: ATS Wiring on Page 3.
Primary Fuse1 Amp Slow Blow
PC (Power Cord) Option Prewired 6’ long
Output Fuses5 Amp slow blow
FAC JumperCut if FAC Moduleis installed in field
12/24V SelectionSwitch
Output PowerSwitchable from12VDC @ 3 amps.24VDC @ 2 amps.
DB-5 & DB- 10 (Distribution Board)Option connection.
5500 POWER SUPPLY BOARD
115
VAC
Inpu
t
5500 Manual 03/03
MODEL #5500 POWER SUPPLYINSTALLATION INSTRUCTIONS
DynaLock705 Emmett Street Bristol, CT 06011-2728Phone:(860) 582-4761 Fax:(860) 585-0338
5500 Manual 03/03
MODEL #5500 POWER SUPPLYINSTALLATION INSTRUCTIONS
DynaLock705 Emmett Street Bristol, CT 06011-2728Phone:(860) 582-4761 Fax:(860) 585-0338
Page #3
A
B
CMTD Option (Control Module with Time Delay)Same as CM Option with Relock Time Delay
Adjustable for 1-80Second delay onrelock time.
B
A Access Control Input, Dry Contacts Only.
SPDT Dry Contacts Rated 2A @ 24V.
ILB Option (Interlock Logic Board)Provides Four DPDT Relay Outputs
Common Negative TerminalPositive Inputs to EnergizeRelay Coils
Note: SeparateILB user manualshows typicalwiring diagrams.
Installation Information LOCK CAPACITY CHART
*This chart indicatess minimum recommended wire size, but local codes prevail
Single Full Size
Double Full Size
Single Double Single Delay Egress
Deadbolt
12VDC
24VDC
6
Voltage
24VDC
20 AWG 18 AWG 16 AWG 14 AWG 12 AWG 10 AWG
8
100Ft. 200Ft. 300Ft. 500Ft. 750Ft. 1500Ft.
3 6 3 3 3
4 8 4 3 4
CURRENT DRAW UP TO 1/2 AMP
12VDC 50Ft. 100Ft. 150Ft. 250Ft. 400Ft. 750Ft.
NOTE: ATS switch contactsrated .25A @ 24V.
ATS Option(Anti-Tamper Switch)
Contact held open withEnclosure cover closed.
Contact closed withEnclosure cover open.
White
White
White
White
Page #2
FAC Option (Fire Alarm Control)Kills all voltage outputs when interfacedwith emergency system dry contact.
Module supplied with jumperon terminals 1 & 2 as shown.
Typical Application
Normally-Closed Dry Contact fromFire Alarm Control Panel (By others).Cut Main Board Jumper when field installed.Refer to Page #1 (FAC Jumper).
FACMR Option(FAC Manual Reset)
Opening normally closed contact removesall output power until the normally open resetbutton is momentarily pressed.
120 VAC50/60 HZINPUT
*Resettable Fuse
DC Input from PowerSupply Main Board
With Control Module OptionWithout Control Module Option
OUTPUT JUMPERS
Connector forCM/CMTD Modules
DB-5 & DB-10 Option (Distribution Board)Two size distribution boards (5 or 10 position)are available to provide individually fusedoutput terminals for each lock zone.
*Resetting is done by first correcting the overload then disconnecting the load or turning off the line voltage for two minutes.
CM Option (Control Module)Accepts access/egress controldry contact input. ProvidesSPDT relay output.
Access Control Input,Dry Contacts Only.
SPDT Dry ContactsRated 2A @ 24V.A B
B
A
LINEINPUT
POWEROUTPUT
FACMODULE
LINENEUTGND
(Factory Setting)
123
e Reset Button
5500 Manual 03/03
MODEL #5500 POWER SUPPLYINSTALLATION INSTRUCTIONS
DynaLock705 Emmett Street Bristol, CT 06011-2728Phone:(860) 582-4761 Fax:(860) 585-0338
5500 Manual 03/03
MODEL #5500 POWER SUPPLYINSTALLATION INSTRUCTIONS
DynaLock705 Emmett Street Bristol, CT 06011-2728Phone:(860) 582-4761 Fax:(860) 585-0338
Page #3
A
B
CMTD Option (Control Module with Time Delay)Same as CM Option with Relock Time Delay
Adjustable for 1-80Second delay onrelock time.
B
A Access Control Input, Dry Contacts Only.
SPDT Dry Contacts Rated 2A @ 24V.
ILB Option (Interlock Logic Board)Provides Four DPDT Relay Outputs
Common Negative TerminalPositive Inputs to EnergizeRelay Coils
Note: SeparateILB user manualshows typicalwiring diagrams.
Installation Information LOCK CAPACITY CHART
*This chart indicatess minimum recommended wire size, but local codes prevail
Single Full Size
Double Full Size
Single Double Single Delay Egress
Deadbolt
12VDC
24VDC
6
Voltage
24VDC
20 AWG 18 AWG 16 AWG 14 AWG 12 AWG 10 AWG
8
100Ft. 200Ft. 300Ft. 500Ft. 750Ft. 1500Ft.
3 6 3 3 3
4 8 4 3 4
CURRENT DRAW UP TO 1/2 AMP
12VDC 50Ft. 100Ft. 150Ft. 250Ft. 400Ft. 750Ft.
NOTE: ATS switch contactsrated .25A @ 24V.
ATS Option(Anti-Tamper Switch)
Contact held open withEnclosure cover closed.
Contact closed withEnclosure cover open.
White
White
White
White
Page #2
FAC Option (Fire Alarm Control)Kills all voltage outputs when interfacedwith emergency system dry contact.
Module supplied with jumperon terminals 1 & 2 as shown.
Typical Application
Normally-Closed Dry Contact fromFire Alarm Control Panel (By others).Cut Main Board Jumper when field installed.Refer to Page #1 (FAC Jumper).
FACMR Option(FAC Manual Reset)
Opening normally closed contact removesall output power until the normally open resetbutton is momentarily pressed.
120 VAC50/60 HZINPUT
*Resettable Fuse
DC Input from PowerSupply Main Board
With Control Module OptionWithout Control Module Option
OUTPUT JUMPERS
Connector forCM/CMTD Modules
DB-5 & DB-10 Option (Distribution Board)Two size distribution boards (5 or 10 position)are available to provide individually fusedoutput terminals for each lock zone.
*Resetting is done by first correcting the overload then disconnecting the load or turning off the line voltage for two minutes.
CM Option (Control Module)Accepts access/egress controldry contact input. ProvidesSPDT relay output.
Access Control Input,Dry Contacts Only.
SPDT Dry ContactsRated 2A @ 24V.A B
B
A
LINEINPUT
POWEROUTPUT
FACMODULE
LINENEUTGND
(Factory Setting)
123
e Reset Button
5500 Manual 03/03
MODEL #5500 POWER SUPPLYINSTALLATION INSTRUCTIONS
DynaLock705 Emmett Street Bristol, CT 06011-2728Phone:(860) 582-4761 Fax:(860) 585-0338
5500 Manual 03/03
MODEL #5500 POWER SUPPLYINSTALLATION INSTRUCTIONS
DynaLock705 Emmett Street Bristol, CT 06011-2728Phone:(860) 582-4761 Fax:(860) 585-0338
Page #4
No Output Power @ No Output @
4321 Check input line power.
Check line fuse.Check F2 & F3 output fuses.Check FAC (If applicable) terminals1 & 2 must be wired to N/C contact.
Check jumper settings on CM/CMTD module(If applicable).Check jumper setting on DB-5/DB-10 card.Check for proper access switch contact status.Check load & external wiring for short condition.Reset Power Supply (With no load) bydisconnecting input power at for 2 minutes.
BA
ELECTROMAGNETIC LOCK
Access controllegal release
TYPICAL APPLICATION
Normally-closed drycontact from Fire AlarmControl panel (By others).
Fail Secure lockingFail Safe locking device.
TROUBLESHOOTING
120 VAC50/60 HZINPUT
A
B
A
Normally open access/egress controls.Normally closed access/egress controls.D
DB
E
E
C
C
1
Note: Start at ‘No Output Power @ A
67
5
89
FAC Option
BBU (Battery Back-Up) Option
12V BBU1-4 or BBU1-7
24V BBU2-7 or BBU2-7
5500 Enclosure
BA
C
Enclosure Options:
C
B
A -KLC, (Key Lock Cover)-FACMR, (FAC Manual Reset)-ATS, (Anti-Tamper Switch) Note: ATS Wiring on Page 3.
Primary Fuse1 Amp Slow Blow
PC (Power Cord) Option Prewired 6’ long
Output Fuses5 Amp slow blow
FAC JumperCut if FAC Moduleis installed in field
12/24V SelectionSwitch
Output PowerSwitchable from12VDC @ 3 amps.24VDC @ 2 amps.
DB-5 & DB- 10 (Distribution Board)Option connection.
5500 POWER SUPPLY BOARD
115
VAC
Inpu
t
5500 Manual 03/03
MODEL #5500 POWER SUPPLYINSTALLATION INSTRUCTIONS