1 Last Update ALLU 18/11/2015 NORTH AMERICAN EDITION HEADQUARTERS - www.deltalight.com - USA - www.deltalight.us - CANADA - www.deltalight.ca Installation instruction SPY FOCUS CLIP Application Ceiling recessed mounted Finishing section to be used with DELTA LIGHT rough-in housing, plasterframe For indoor use only Color Finish W - White B - Black Light source One 10,4W max POWERLED WHITE (500mA) ( Typical forward voltage: 20,7V ) 1x ADJUSTABLE REFLECTOR 11°- 44° INCLUDED Power Supply Remote current controled class 2 power supply required. (not supplied) Max 500mA, typical forward voltage 11,9V. Do not interconnect in parallel! Specification features Powder coated aluminum assembly Pre-installed springs for easy installation Suitable for damp locations Dimensions Height: 111mm = 4”-3/8 Width: ø62mm = 2”-7/16 Ceiling Cut out: 50,8mm = 2” Required options for non-class 2 power limited circuits Housing for IC and/or airtight applications Plasterframe for IC applications 2 = 3000K 3 = 2700K Color temperature 7 - IC AT Housing S 6 202 00 - Plate D50 0 1 - Bar hangers standard 1 - Bar hangers standard 0 - No bar hangers 1 - 120V 2 - 277V 3 - 120-277V Range Installation type Lamp Source Opening Voltage Mounting Option 1 - Bar hangers standard 0 - No bar hangers 1 - 120V 2 - 277V 3 - 120-277V Range Installation type Voltage Mounting Option 6 202 Plate D50 1 - Bar hangers standard 06 - IC Plasterframe S 6 00 - 0 Lamp Source Opening NIC IC AT SPY FOCUS CLIP 927 6 414 345 811 92 = W-W / B-B / W-B SPY FOCUS CLIP 930 6 414 345 811 93 = W-W / B-B / W-B SPY FOCUS CLIP 935 6 414 345 811 95 = W-W / B-B / W-B 35mm 1”-3/8 2mm 1/16" Conforms to ANSI/UL Std. 2108 Cert. to CAN/CSA Std. 22.2 No. 250.0 Ø58mm Ø2”-5/16 0-90° 355° 108mm 4”-1/4 Ø62mm Ø2”7/16

Upload: others

Post on 05-May-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 6 414 345 811 XX HAND - Delta Light...- DELTA LIGHT recommands to use the power supplies that are indicated in the Lighting Bible. - Respect polarity - Don’t test LED luminaires

1Last Update ALLU 18/11/2015

NORTH AMERICAN EDITION

HEADQUARTERS - www.deltalight.com - USA - www.deltalight.us - CANADA - www.deltalight.ca

Installation instruction SPY FOCUS CLIP

Application Ceiling recessed mounted

Finishing section to be used with DELTA LIGHT rough-in housing, plasterframeFor indoor use only

Color FinishW - White

B - Black

Light sourceOne 10,4W max POWERLED WHITE (500mA) ( Typical forward voltage: 20,7V )

1x ADJUSTABLE REFLECTOR 11°- 44° INCLUDED

Power SupplyRemote current controled class 2 power supply required. (not supplied)

Max 500mA, typical forward voltage 11,9V.

Do not interconnect in parallel!

Specification featuresPowder coated aluminum assembly

Pre-installed springs for easy installation

Suitable for damp locations

DimensionsHeight: 111mm = 4”-3/8

Width: ø62mm = 2”-7/16

Ceiling Cut out: 50,8mm = 2”

Required options for non-class 2 power limited circuitsHousing for IC and/or airtight applications

Plasterframe for IC applications

2 = 3000K

3 = 2700K

Color temperature

7 - IC AT Housing S6 202 00 - Plate D50 0 1 - Bar hangers standard

1 - Bar hangers standard0 - No bar hangers

1 - 120V2 - 277V3 - 120-277V

Range Installation type

Lamp Source Opening

Voltage Mounting Option

1 - Bar hangers standard0 - No bar hangers

1 - 120V2 - 277V3 - 120-277V

Range Installation type

Voltage Mounting Option

6 202 Plate D50 1 - Bar hangers standard06 - IC Plasterframe S6 00 - 0

Lamp Source Opening

NICICATSPY FOCUS CLIP 927

6 414 345 811 92 = W-W / B-B / W-BSPY FOCUS CLIP 9306 414 345 811 93 = W-W / B-B / W-BSPY FOCUS CLIP 9356 414 345 811 95 = W-W / B-B / W-B

35mm

1”-3/8

2mm

1/16"

Conforms to ANSI/UL Std. 2108

Cert. to CAN/CSA Std. 22.2 No. 250.0

Ø58mm

Ø2”-5/16

0-90°355°

108mm

4”-1/4Ø62mm

Ø2”7/16

Page 2: 6 414 345 811 XX HAND - Delta Light...- DELTA LIGHT recommands to use the power supplies that are indicated in the Lighting Bible. - Respect polarity - Don’t test LED luminaires

Installation instruction

2

NORTH AMERICAN EDITION

HEADQUARTERS - www.deltalight.com - USA - www.deltalight.us - CANADA - www.deltalight.ca

A

B

A

B

SAVE!

B

A

INSTALLATION LUMINAIRE

SPY FOCUS CLIP

if not installed in a class 2 power limited circuit

NICICAT

HOUSING PLASTERFRAME

Not Supplied Rough-in Housing or Plasterframe

Required

Accessories

2X

NIC

MOUNTING KIT

1

4

5

2

6

CAUTION!

CLASS 2 POWER LIMITED CIRCUITS ONLY

ATTENTION!

SEULEMENT POUR RESEAUS CLASS 2,

A PUISSANCE LIMITE

MAX 500mA DC (red/rouge: +, black/noir: -)

1/2”1 3 4

2

MAX 2 x 14-18AWG 50L/STR

REDROUGE

REDROUGE

BLACKNOIR

BLACKNOIR

+ +

--

Page 3: 6 414 345 811 XX HAND - Delta Light...- DELTA LIGHT recommands to use the power supplies that are indicated in the Lighting Bible. - Respect polarity - Don’t test LED luminaires

3

NORTH AMERICAN EDITION

HEADQUARTERS - www.deltalight.com - USA - www.deltalight.us - CANADA - www.deltalight.ca

Installation instruction

INSTALLATION LUMINAIRE

SPY FOCUS CLIP

on

off

10

355°

90

- Use only power supplies that are certified according to the applicable IEC or UL safety standards.

- Use only SELV power supplies.

- Check the ratings of the power supply with those of the luminaire.

The maximum current rating must be taken into account.

The indicated typical voltage must not be used to select a constant voltage power supply but is indented to used

to select a constant current power supply that is able to cover that typical voltage.

- Take appropriate ESD measures. Avoid touching bare conductors.

- Leds or led luminaires that require a current controlled power supply must never be connected in parallel.

- Leds can be damaged by the contact with certain chemicals or chemical gasses.

Therefore led domes or led engines should never be cleaned with chemical substances.

The following substances have proven to have a negative influence on the performance and

must not be used in the direct environment of a led luminaire.

Methyl acetate or ethyl acetate (i.e., nail polish remover)

Cyanoacrylates (i.e., “Superglue”)

Glycol ethers (including Radio Shack® Precision Electronics Cleaner - dipropylene glycol monomethyl ether)

Formaldehyde or butadiene (including Ashland PLIOBOND® adhesive)

Dymax 984-LVUF conformal coating

Loctite Sumo Glue

Gorilla Glue

Bleach, Bleach-containing cleaners, sprays

Loctite 384 adhesive

Loctite 7387 activator

Loctite 242 threadlocker

- Remove insulation and/or provide sufficient ventilation so that the indicated max Tc is not surpassed.

- Leds are susceptible to switching transients. Therefore switching must be done in the primary circuit

of the power supply.

- DELTA LIGHT recommands to use the power supplies that are indicated in the Lighting Bible.

- Respect polarity

- Don’t test LED luminaires one by one on a powersupply that is switched on.

DO NOT TOUCH OR CLEAN THE LED ARRAY!

!

NO SECONDARY SWITCHING

AC DC

AC DC

ATTENTION

OBSERVE PRECAUTIONS FOR

HANDLING ELECTROSTATIC

DISCHARGE SENSITIVE

DEVICES

7 8

Min 11°

Max 44°

Min 11°

Max 44°