6. combustion in ic engines
TRANSCRIPT
-
8/3/2019 6. Combustion in IC Engines
1/25
Dynamic simulation of an ammonia-waterabsorption refrigeration system
Weihua Cai1, Mihir Sen2 and Samuel Paolucci3
Department of Aerospace and Mechanical Engineering
University of Notre Dame, Notre Dame, IN 46556
July 1, 2010
Abstract
A dynamic model of a single-effect absorption refrigeration cycle has been developed. Mod-eling of the cycle performance requires thermodynamic properties which are obtained fromequations of state for refrigerant-absorbent mixtures. The transient response of the absorp-tion refrigeration cycle is investigated using mass, momentum and energy balances for the
different parts of the system. Some design and operation parameters that affect the cycleperformance are identified.
Keywords: absorption-refrigeration, ammonia-water, dynamics, equation of state
1 Introduction
A typical single-effect absorption refrigeration cycle consists of four basic components, an
evaporator, an absorber, a generator and a condenser, as shown in the schematic of Fig. 1.
The cooling cycle starts at the evaporator, where liquefied refrigerant boils and takes some
heat away with it from the evaporator, which produces the cold desired in the refrigerated
space. The refrigerant vapor releases its latent heat as it is absorbed by an liquid absorbent
in the absorber. It is necessary to separate the refrigerant from the absorbent, and this is
done in the generator. A pump drives the solution into the generator which is heated by a
heat source (e.g. steam, hot water, direct firing, solar cell). The solution is heated and the
refrigerant vapor driven out of it. Part of the solution is throttled back into the absorber.1Currently at Caterpiller, e-mail: [email protected] author, e-mail: [email protected]: [email protected]
1
-
8/3/2019 6. Combustion in IC Engines
2/25
A solution heat exchanger, normally located between the absorber and the generator, makes
the process more efficient without changing its basic operation. Subsequently, the condenser
cools the refrigerant vapor back into the liquid state. The cycle continues after the refrigerant
goes through an expansion valve.
There have been some papers published on the steady-state and dynamic simulations of
absorption refrigeration systems. A computer code ABSIM has been developed for steady-
state simulation of absorption systems in a flexible and modular form (Grossman and Zaltash,
2001). It has been employed by many users for performing cycle evaluations, testing control
strategies, and preliminary design optimization. Detailed distributed models of absorption
heat pumps using H2O/NH3 have been developed (Butz, 1989). Step change response of the
system has been investigated. In an advanced energy storage system using H2O/LiBr as the
working fluid (Xu et al., 2007b,a), dynamic models of the operation have been developed, and
the simulation results predicted the dynamic characteristics and performance of the system.
An object-oriented dynamic modeling library named ABSML has been designed (Fu et al.,
2006). Different absorption chiller models, including single-effect, double-effect, LiBr/H2O
and H2O/NH3 systems, have been successfully developed in the library. Simulation results on
transient behavior and during startup and shutdown show good match between experimental
data and simulations. Numerical simulation have been carried out to predict the transient
operating characteristics and performance of an absorption heat pump using H2O/LiBr to
recover waste heat (Jeonga et al., 1998). The simulation of absorption and refrigeration
systems is very helpful for understanding and evaluating the system as well as for system
design, operation and control, and device design or selection in detail (Lucas et al., 2007;
Sohel and Dawoud, 2006; Donate et al., 2006; Lucas et al., 2004; Atmaca et al., 2002; Vargas
et al., 1998; Yang and Guo, 1987).
Modeling the cycle performance requires thermodynamic properties. However, very
few papers utilize equations of state to obtain the thermodynamic properties. Yokozeki
2
-
8/3/2019 6. Combustion in IC Engines
3/25
(Yokozeki, 2005) is the first to perform the steady state modeling of an absorption-refrigeration
cycle using equations of state to calculate thermodynamic properties. In the present work we
develop a dynamical model for a single-stage absorption refrigeration cycle, where all ther-
modynamic properties have been consistently obtained from equations of state for mixtures.
The aim of this work is to study the effects of thermodynamic properties on the steady state
performance and dynamic response of an absorption refrigeration cycle. The modeling and
calculations are carried out for an ammonia-water system for which good data are available.
2 Dynamic modeling
2.1 Governing equations
Fig. 1 shows a schematic of the absorption refrigeration cycle. The principal components
of a conventional absorption refrigeration system are generator, condenser, evaporator, and
absorber. In the present study, some assumptions are made in developing the dynamic
modeling. In the lumped-parameter approach, each component is characterized by a single
temperature, pressure, and concentration. The flow in the pipes is assumed to be one-
dimensional, and no diffusion of heat occurs in the flow direction. In addition, there is no
heat loss from generator to the surroundings nor heat gain by the evaporator from the sur-
roundings, and the expansion process in the valve is assumed to occur at constant enthalpy.
We write the coupled governing equations for the complete absorption refrigeration cycle
by examining the balances of mass, energy, and momentum for the different components in
the cycle. We take Mi(t) to correspond to the mass within component i, and mi(t) the mass
flow rate between components, as labeled in Fig. 1. Subsequently, the overall mass balances
for each component are given by
dMCdt
= m1 m2 , (1)dME
dt= m3 m4 , (2)
3
-
8/3/2019 6. Combustion in IC Engines
4/25
dMAdt
= m4 + m10 m5 , (3)dMG
dt= m7 m8 m1 (4)
m2 = m3 , (5)
m5 = m6 = m7 , (6)
m8 = m9 = m10 . (7)
Here we take Ci(t) to be the mass fraction of the absorbent coming out of a component.
Subsequently, we have the following absorbent mass balances
d
dt(MACA) = m10C10 m5C5 , (8)
d
dt(MGCG) = m7C7 m8C8 , (9)
C5 = C6 = C7 = CA , (10)
C8 = C9 = C10 = CG . (11)
The momentum equations between the components are given by
dm1dt
+1
2f1
m1|m1|1A1D1
=A1L1
(PG PC) , (12)dm2
dt+
1
2f2
m2|m2|2A2D2
=A2L2 PC P
iV1 , (13)
1
21
1
2A2V1m2|m2| = PiV1 PoV1 , (14)
dm3dt
+1
2f3
m3|m3|3A3D3
=A3L3
PoV1 PE
, (15)
dm4dt
+1
2f4
m4|m4|4A4D4
=A4L4
(PE PA) , (16)dm5
dt+
1
2f5
m5|m5|5A5D5
=A5L5
PA PiP
, (17)
P = PoP PiP , (18)dm6
dt+ 1
2f6
m6|m6|6A6D6
= A6
L6(PoP PG) , (19)
dm9dt
+1
2f9
m9|m9|9A9D9
=A9L9
PG PiV2
, (20)
4
-
8/3/2019 6. Combustion in IC Engines
5/25
1
22
1
9A2V2m9|m9| = PiV2 PoV2 , (21)
dm10dt
+1
2f10
m10|m10|10A10D10
=A10L10
PoV2 PA
, (22)
where fi is the pipe friction factor (a single correlation relating pipe friction loss to Reynolds
number and surface roughness for laminar, transitional and turbulent flow alike is used
(Churchill, 1977)), i is the expansion valve friction factor, Li and Di are pipe length and
diameter respectively, Ai is the pipe cross-sectional area, and AVi is the smallest cross-
sectional area of the expansion valve, i is the density, and Pi is the pressure. The superscripts
i and o stand for the inlet and outlet of a component, respectively.
The performance of a pump, which is the prime mover that increases the pressure of the
solution, is given by empirically-determined characteristic curves. This can be conveniently
represented as a low order polynomial
P = PoP PiP = a1 + a2m5 + a3m25, (23)
where a1, a2 and a3 are parameters determined from the manufacturers technical data. For
the current study, we assume that they are constant.
Letting hi(t) be the specific enthalpy, the energy balances for the components are given
by
d
dt(MChC) = m1h1 m2h2 QC , (24)
d
dt(MEhE) = m3h3 m4h4 + QE , (25)
d
dt(MAhA) = m4h4 + m10h10 m5h5 QA , (26)
d
dt(MGhG) = m7h7 m8h8 m1h1 + QG , (27)
Qx
= m7h7
m6h6 = m8h8
m9h9 , (28)
m6h6 = m5h5 + WP , (29)
h2 = h3 , (30)
5
-
8/3/2019 6. Combustion in IC Engines
6/25
h9 = h10 , (31)
where Qi = FiUiTi, Fi the total heat transfer area, Ui is the overall heat transfer coefficient,
Ti = TiTi,, Ti is the temperature of the component, Ti, is the temperature surroundingthe component, and WP is from Eq. (73). Note that convective heat losses have been
neglected in the above model.
The above equations are complemented by an equation of state (EOS)
P = P(T , V , x) , (32)
where V = V /n is the molar volume, V is the total volume, x xr = nr/n is the molefraction of the refrigerant, n = nr + na is the total number of moles, and nr and na are the
number of moles of the refrigerant and absorbent respectively. In addition, we note that the
total mass M is given by
M = V , (33)
where is the total density given by
=1
V[xMr + (1 x)Ma] , (34)
where Mr and Ma are the molecular masses of the refrigerant and absorbent respectively.Lastly, the mass fraction y of the absorbent is given by
y =Ma(1 x)
xMr + (1 x)Ma . (35)
Note that
x = Ma(1
y)
yMr + (1 y)Ma . (36)
6
-
8/3/2019 6. Combustion in IC Engines
7/25
2.2 Equation of state
The theoretical performance of a vapor-absorption refrigeration cycle can be determined
once the equation of state is given. A generic Redlich-Kwong (RK) EOS (Yokozeki, 2005)
for the mixture is
P =RT
V b a
V(V + b), (37)
where R is the universal gas constant.
For a pure specie i, parameters ai and bi are given as
ai = 0.42748R2T2ci
Pcii , bi = 0.08664
RTciPci
, (38)
where Tci and Pci are the critical temperature and pressure, and
i =3
j=0
j
TciT T
Tci
j. (39)
The subscripts are 1 for NH3 and 2 for H2O. The critical parameters and EOS constants of
the pure refrigerant and absorbent are shown in Table 1.
For the mixture, the following rules are used
a = ij
xixj
aiaj [1 gij(T)kij] , (40)
b =i
j
xixjbi + bj
2(1 nij) , (41)
where
gij = 1 + cijT , (42)
cij = cji, cii = 0 , (43)
kij =lijlji(xi + xj)
ljixi + lijxj, kii = 0 , (44)
and where cij = cji, lij = lji, and nij = nji are empirical interaction parameters given in
Table 2.
7
-
8/3/2019 6. Combustion in IC Engines
8/25
The enthalpy h is a thermodynamically derived variable given by
h =
k
C0pkxkdT h , (45)
where
h = RT2
V
ZT
V
dV
VRT(Z 1) , (46)
and
Z = P V /RT (47)
is the compressibility. The ideal gas heat capacity at constant pressure for each component
is modeled as a polynomial
C0p = C0 + C1T + C2T2 + C3T
3 , (48)
where the coefficients are given in Table 3.
3 Results and discussion
3.1 Steady state
Let mr denote the refrigerant mass flow rate, and ms the solution mass flow rate, and r the
mass flow rate recirculation factor. After a sufficiently long time the system relaxes to the
following steady state
m1 = m2 = m3 = m4 = mr , (49)
m5 = m6 = m7 = ms , (50)
m8 = m9 = m10 = ms mr , (51)
r msmr
= yG
yG yA , (52)
mr|mr| = 2 1A2
1D1
f1L1(PG PC) , (53)
8
-
8/3/2019 6. Combustion in IC Engines
9/25
= 22A
2
2D2
f2L2(PC PiV1) , (54)
= 22A
2
V1
1(PiV1 PoV1) , (55)
= 23A
2
3D3
f3L3(PoV1 PE) , (56)
= 2 4A2
4D4f4L4
(PE PA) , (57)
ms|ms| = 2 5A2
5D5
f5L5(PA PiP) , (58)
= 26A
2
6D6
f6L6(PoP PG) , (59)
P = PoP PiP , (60)
ms mr = 2 9A2
9D9
f9L9(PG PiV2) , (61)
= 2 9A2
V2
2(PiV2 PoV2) , (62)
= 210A
2
10D10
f10L10(PoV2 PA) , (63)
QC/mr = (h1 h2) , (64)
QE/mr = (h4 h3) , (65)
QA/mr = h4 + (r 1)h10 rh5 , (66)
QG/mr = h1
rh7 + (r
1)h8 , (67)
Qx/mr = r(h7 h6) = (r 1)(h8 h9) , (68)
WP/mr = r(h6 h5) , (69)
h2 = h3 , (70)
h9 = h10 . (71)
Substituting Eqs. (68) and (69) into Eq. (67) gives
QG/mr = h1 + (r 1)h10 rh5 WP/mr . (72)
9
-
8/3/2019 6. Combustion in IC Engines
10/25
The pump power is given by
WP = m5P/5 . (73)
To calculate the coefficient of performance (COP), we make following assumptions: (1)
the condition at Point 4 in Fig. 1 (exit of evaporator) is that of a saturated vapor; (2) the
condition at Point 2 (exit of condenser) is that of a saturated liquid; (3) the condition at Point
1 (inlet to condenser) is a superheated state; (4) the condition at Point 10 (solution inlet to
the absorber) is a solution bubble point. The first step is to obtain PC and PE as saturated
vapor pressures of a pure refrigerant at given temperatures of TC and TE. Then, given the
pipe geometry and expansion valve specifics, the refrigerant flow rate mr is obtained from
Eqs. (54)(56). The pressures PG and PA are obtained from Eqs. (53) and (57). Using a
method, such as flash calculation (Yokozeki, 2005; Ness and Abbott, 1982), xG, xA, VG and
VA are obtained at the given temperatures TG and TA and pressures PG and PA. Given the
constants a1, a2 and a3 from eq. (23), m5 is first calculated from Eqs. (58)(60), and then
the mass circulation ratio r can be calculated. The thermodynamic properties at point 10
are determined using the bubble-point T-method (Yokozeki, 2005; Ness and Abbott, 1982).
Enthalpies at other points are obtained from the equation of state with known T , P , V and
x. Now it can be readily shown that the COP for the steady state cycle operation is given
by
COP =QE
QG + WP=
h4 h3h1 + (r 1)h10 rh5 . (74)
To calculate the COP, we make the following assumptions: (1) the condition at Point 4
in Fig. 1 (exit of evaporator) is a pure refrigerant dew point with T = TE; (2) the condition
at Point 2 is a refrigerant bubble point and there is no subcooled (saturated) liquid; (3) the
condition at Point 1 (inlet to condenser) is a superheated state of a pure refrigerant with
T = TG; (4) the condition at Point 10 (solution inlet to the absorber) is a solutions bubble
10
-
8/3/2019 6. Combustion in IC Engines
11/25
point specified with the absorber pressure PA and a solution concentration of the generator
CG.
Taking TG = 100C, TC = 40
C, TA = 30C, TE = 10
C, and assuming mr = 1 kg/s
without loss of generality, the performance of the absorption refrigeration cycle is shown in
Table 4. For the NH3/H2O pair, the calculated performance agrees with that of (Yokozeki,
2005). Keeping other temperatures constant, the COP decreases nearly linearly as the
temperature of the generator or absorber increases, as shown in Figs. 2 and 3. The decrease
in COP means that, in the present example, the generators heat-input increases while the
evaporator heat (at a fixed temperature) is constant.
However, the mass-flow-rate ratio r behaves in opposite trends between the generator and
absorber and in a highly non-linear fashion, as shown in Figs. 4 and 5. The steep increase
in r at low TG or high TA can be easily understood. The decrease of temperature difference
between TG and TA results in a smaller solubility difference between xG and xA. As a result,
the mass flow rate ratio r increases steeply, which can be seen in Eq. (52).
3.2 Dynamic response under step change
Now we study the dynamics of the NH3/H2O pair. Initially, the absorption refrigeration
cycle is at steady state operation with TG = 100
C, TC = 40
C, TA = 30
C, TE = 10
C.
The bulk concentration and temperature of a mixture determine its pressure. A step change
is introduced by increasing the pressure rise P across the pump by one percent. As a
result, the mass flow rate m5 quickly increases, as shown in Fig. 6. It is seen that the system
quickly reaches a new steady state. But as the flow rate increase, the frictional loss also
increases. The combined result of pressure force and friction results in an overshoot of the
flow rate. When more solution flows into the generator, more heat is gained from the high-
temperature source, which explains the evolution ofQG in Fig. 7. As more solution flows into
the generator, more refrigerant m4 is generated, as shown in Fig. 8. When more refrigerant
11
-
8/3/2019 6. Combustion in IC Engines
12/25
is generated, more heat is gained from the refrigerated space, which explains the increase
of QE in Fig. 9. The evolution of the COP is shown in Fig. 10. This can be explained
by the evolution of QE and QG. Both QE and QG increase while more heat goes into the
evaporator.
4 Conclusions
A lumped-parameter dynamic model has been developed for a absorption refrigeration cycle.
All thermodynamic properties have been consistently calculated based on an equation of state
for mixtures. We have successfully demonstrated the usefulness of the EOS model for the
absorption refrigeration cycle process. We have shown that the coefficient of performance of
the cycle increases when the generator temperature or absorber temperature decreases.
The dynamical response to a step change is also investigated. The system quickly reaches
a steady state given the operation parameters for this specific example. The increase of pump
pressure rise results in an increase in the system performance. The instantaneous flow rate,
heat rates, and COP are also observed to oscillate in time before reaching steady state.
Acknowledgment
The authors thank the U.S. Department of Energy for support of this work, and Mr. G.
Puliti and Drs. J.F. Brennecke, E.J. Maginn and M. Stadtherr for discussions.
References
I. Atmaca, A. Yigit, and M. Kilic. The effect of input temperatures on the absorber pa-
rameters. International Communications in Heat and Mass Transfer, 29(8):11771186,
2002.
D. Butz. Dynamic behaviour of an absorption heat pump. International Journal of Refrig-
eration, 12(4):204212, 1989.
12
-
8/3/2019 6. Combustion in IC Engines
13/25
S.W. Churchill. Friction-factor equation spans all fluid-flow regimes. Chemical Engineering,
84(24):9192, 1977.
M. Donate, L. Rodriguez, A. De Lucas, and J.F. Rodriguez. Thermodynamic evaluation of
new absorbent mixtures of lithium bromide and organic salts for absorption refrigeration
machines. International journal of refrigeration, 29(1):3035, 2006.
D.G. Fu, G. Poncia, and Z. Lu. Implementation of an object-oriented dynamic modeling
library for absorption refrigeration systems. Applied Thermal Engineering, 26(2-3):217
225, 2006.
G. Grossman and A. Zaltash. ABSIM - modular simulation of advanced absorption systems.
International Journal of Refrigeration, 24(6):531543, 2001.
S. Jeonga, B.H. Kangb, and S.W. Karngb. Dynamic simulation of an absorption heat pump
for recovering low grade waste heat. Applied Thermal Engineering, 18(1-2):112, 1998.
A. De Lucas, M. Donate, C. Molero, J. Villasenor, and J.F. Rodriguez. Performance evalu-
ation and simulation of a new absorbent for an absorption refrigeration system. Interna-
tional Journal of Refrigeration, 27(4):324330, 2004.
A. De Lucas, M. Donate, and J.F. Rodriguez. Absorption of water vapor into new working
fluids for absorption refrigeration systems. Industrial & Engineering Chemistry Research,
46:345350, 2007.
H.C. Van Ness and M.M. Abbott. Classical Thermodynamics of Non-Electrolyte Solutions
with Applications to Phase Equilibria. McGraw-Hill, New York, 1982.
Y.U. Paulechka, G.J. Kabo, A.V. Blokhin, O.A. Vydrov, J.W. Magee, and M. Frenkel.
Thermodynamic properties of 1-butyl-3-methylimidazolium hexafluorophosphate in the
ideal gas state. J. Chem. Eng. Data, 48:457462, 2003.
13
-
8/3/2019 6. Combustion in IC Engines
14/25
R.C. Reid, J. Prausnitz, and B.E. Poling. The Properties of Gases & Liquids. McGraw-Hill,
New York, 4 edition, 1987.
M.B. Shiflett and A. Yokozeki. Absorption cycle utilizing ionic liquid as working fluid. In
US Patent 20060197053A1. 2006.
M.I. Sohel and B. Dawoud. Dynamic modelling and simulation of a gravity-assisted so-
lution pump of a novel ammonia-water absorption refrigeration unit. Applied Thermal
Engineering, 26(7):688699, 2006.
J.V.C. Vargas, I. Horuz, T.M.S. Callander, J.S. Fleming, and J.A.R. Parise. Simulation of
the transient response of heat driven refrigerators with continuous temperature control.
International Journal of Refrigeration, 21(8):648660, 1998.
S.M. Xu, L. Zhang, C.H. Xu, J. Liang, and R. Du. Numerical simulation of an advanced en-
ergy storage system using H2O-LiBr as working fluid, Part 1: System design and modeling.
International Journal of Refrigeration, 30(2):354363, 2007a.
S.M. Xu, L. Zhang, C.H. Xu, J. Liang, and R. Du. Numerical simulation of an advanced
energy storage system using H2O-LiBr as working fluid, Part 2: System simulation and
analysis. International Journal of Refrigeration, 30(2):364376, 2007b.
W.-J. Yang and K.H. Guo. Solar-assisted lithium-bromide absorption cooling systems. In
Proceedings of the NATO Advanced Study Institute, pages 409423, 1987.
A. Yokozeki. Theoretical performances of various refrigerant-absorbent pairs in a vapor-
absorption refrigeration cycle by the use of equations of state. Applied Energy, 80:383399,
2005.
14
-
8/3/2019 6. Combustion in IC Engines
15/25
-
8/3/2019 6. Combustion in IC Engines
16/25
A
C
V
E
C G
A
P
Heat exchanger
Q
Q
RefrigerantQx
Solution
2
3
4
1
8
10
9
7
6
5
A: Absorber E: Evaporator G: Generator
QE
Refrigerated space
QG
Hightemperature source
1
Wp2V
C: Condenser
V : Valves1,2 P: Pump
Figure 1: Schematic of absorption refrigeration cycle.
16
-
8/3/2019 6. Combustion in IC Engines
17/25
340 360 380 400 420 4400.5
0.55
0.6
0.65
0.7
0.75
TG
COP
Figure 2: COP vs. generator temperature.
17
-
8/3/2019 6. Combustion in IC Engines
18/25
290 295 300 305 310 315 320 3250.58
0.6
0.62
0.64
0.66
0.68
0.7
Figure 3: COP vs. absorber temperature.
18
-
8/3/2019 6. Combustion in IC Engines
19/25
340 360 380 400 420 4401
2
3
4
5
6
7
8
9
TG
r
Figure 4: Mass flow rate ratio vs. generator temperature.
19
-
8/3/2019 6. Combustion in IC Engines
20/25
290 295 300 305 310 315 320 3251
2
3
4
5
6
7
TA
r
Figure 5: Mass flow rate ratio vs. absorber temperature.
20
-
8/3/2019 6. Combustion in IC Engines
21/25
0 20 40 60 80 1000.5
1
1.5
2
2.5
t (s)
Flow
rate
m5
(kg/s)
Figure 6: Response of mass flow rate of weak solution for step change.
21
-
8/3/2019 6. Combustion in IC Engines
22/25
1 20 40 60 80 1005.0408
5.0408
5.0409
5.0409
5.041
5.0411
5.0411
5.0412
5.0412x 10
5
t (s)
QG
(J/s)
Figure 7: Heat transfer rate at generator for step change.
22
-
8/3/2019 6. Combustion in IC Engines
23/25
1 20 40 60 80 100
0.2912
0.2913
0.2914
0.2915
0.2916
0.2917
t (s)
Flow
rate
m1
(kg/s)
Figure 8: Response of mass flow rate of refrigerant for step change.
23
-
8/3/2019 6. Combustion in IC Engines
24/25
1 20 40 60 80 1003.234
3.2345
3.235
3.2355
3.236
3.2365
3.237x 10
5
t (s)
QE
(J/s)
Figure 9: Heat transfer rate at evaporator for step change.
24
-
8/3/2019 6. Combustion in IC Engines
25/25
1 20 40 60 80 1000.6416
0.6417
0.6418
0.6419
0.642
0.6421
t (s)
COP
Figure 10: Coefficient of performance for step change.
25