    User Rights (Authorizations)

    in SIMATIC PCS 7 OS V7.1SIMATIC PCS 7 V7.1

    FAQ May 2012

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    2/37

    Question

    This entry is from the Siemens Industry Online Support. The general terms of use(http://www.siemens.com/terms_of_use)apply.

    Clicking the link below directly displays the download page of this document.

    http://support.automarion.siemens.com/WW/view/en/60575347

    CautionThe functions and solutions described in this article confine themselves to therealization of the automation task predominantly. Please take into accountfurthermore that corresponding protective measures have to be taken up in thecontext of Industrial Security when connecting your equipment to other parts of theplant, the enterprise network or the Internet. Further information can be foundunder the Content-ID 50203404.

    http://support.automation.siemens.com/WW/view/en/50203404

    http://www.siemens.com/terms_of_usehttp://www.siemens.com/terms_of_usehttp://support.automarion.siemens.com/WW/view/en/60575347http://support.automarion.siemens.com/WW/view/en/60575347http://support.automation.siemens.com/WW/view/en/50203404http://support.automation.siemens.com/WW/view/en/50203404http://support.automation.siemens.com/WW/view/en/50203404http://support.automarion.siemens.com/WW/view/en/60575347http://www.siemens.com/terms_of_use
  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    3/37

    Table of content

    Table of Content

    1 How do user rights work?..............................................................................4

    1.1 Where to manage Usernames and Passwords...................................51.2 User rights workflow for SIMATIC PCS 7 OS .....................................61.3 User rights workflow for SIMATIC PCS 7 OS combined with

    Windows............................................................................................81.4 User rights workflow for PCS 7 OS Web Option...............................10

    1.5

    User rights applied to tags ...............................................................101.6 User rights mechanism ....................................................................11

    2 Appendix.......................................................................................................13

    2.1 Appendix 1 ...................................................................................... 132.2 Appendix 2 ...................................................................................... 142.3 Appendix 3 ...................................................................................... 14

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    4/37

    1 How do user rights work?

    1 How do user rights work?SIMATIC PCS 7 makes operation secure by means of assigning user rights tousers that log on to the system before they can monitor and operate the process.

    Levels of user rights

    SIMATIC PCS 7 supports the following user rights within the scope of the SIMATICPCS 7 Operator System (OS).

    Table 1-1

    No Function Description

    1 User Administration Right to create and modify users and groups in the HMI

    2 Authorization for Area Right to access and operate the process area and its relatedprocess graphics and tags

    3 System Change Right to deactivate the Runtime and gain access to the

    Windows desktop4 Monitoring Right to monitor the process and open other applications (which

    will apply user rights within their own scope) for exampleSIMATIC BATCH Client

    5 Process Controlling Right to operate the process and perform normal processadjustments, this includes starting and stopping equipment,opening and closing valves and making setpoint changes to PIDloops

    6 Higher Process Controlling Right to make adjustments to process critical parameters andtuning parameters like alarm limits, PID algorithm tuning

    parameters

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    5/37

    1 How do user rights work?

    Area and Station (computer) dependent user rights

    The user rights are assigned to individual users or groups of users and can beconfigured different per process area and operator station.

    Within the SIMATIC PCS 7 operator system, process graphics and Tags belong toprocess areas, the rights of a user within a process area are applicable to allgraphics and Tags that are assigned to the process area.

    You can also revoke access to specific process areas their process graphics andany Tag that belongs to that process area.

    Groups and Users

    To make configuration easier and help avoid mistakes, the SIMATIC PCS 7 OSeditor User Administrator supports Groups and Users. Users must always bemember of a Group.

    The group configuration can be inherited into a newly created User, but a User canalways have a different configuration compared to the group it is member of.

    There is an option to manage Usernames and Passwords in Windows and inheritthem into the SIMATIC PCS 7 OS. We recommend that method and explain how itworks in the next paragraph.

    1.1 Where to manage Usernames and Passwords

    Th t d d ft f ti SIMATIC L (i l d d i SIMATIC PCS 7

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    6/37

    1 How do user rights work?

    1.2 User rights workflow for SIMATIC PCS 7 OS

    If the Usernames and Passwords are managed in SIMATIC PCS 7 OS then youmust create each individual user on each OS Client. This is a single step activity,open the User Administrator and perform the task.

    Adding a new user

    There are two possibilities for adding a new user depended on whether single OSClients can be deactivated or not.

    1. Without de-activating the OS ClientsTo this the new user must be added on all OS Clients and in addition in alloffline OS Client projects on the Engineering System (ES).

    2. With de-activating the OS ClientsTo this the new user must be added in all OS Client projects on theEngineering System (ES) and the OS Client projects must be downloaded

    again, which can only occur by de-activating the runtime OS Client project.

    When Usernames and Passwords are managed in the OS client project, theworkflow is as follows:

    Add/modify/delete Users in the User Administration of the OS Client project(s)on the ES

    Add/modify/delete Users in the User Administration of the OS Client project(s)on the runtime Operator Systems

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    7/37

    1 How do user rights work?

    User AdministrationFigure 1-1

    Group

    User

    No SIMATIC Logon

    No Authorization

    Process control Monitoring OnlyHigher Process control

    Process areas

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    8/37

    1 How do user rights work?

    1.3 User rights workflow for SIMATIC PCS 7 OS combinedwith Windows

    If the Usernames and Passwords are managed in Windows then you must meetthe following prerequisites:

    Install SIMATIC Logon on each OS Computer, this includes the ES.

    Identify an existing or configure a new User in Windows and assign that user tothe Logon_Administrator Group in Windows, this user will be allowed to makechanges to settings in SIMATIC Logon itself.

    Create Groups in Windows User Administration (e.g. Operators, Engineers,Supervisors).

    Create identical Groups as in Windows User Administration on the OS Serverand OS Clients User Administration on the ES and in the OS runtime. AssignUser rights to the Groups.

    Check the box SIMATIC Logon in the OS User Administration in all OS; youcan only check/uncheck this box while the OS project is de-activated.

    If your Computers are part of a domain, then you will manage the Usernames andPasswords in the domain. Skip the next step.

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    9/37

    1 How do user rights work?

    To add/modify/delete Users in Windows do the following

    Open the Windows User Administration (check Windows documentation if youwant to learn how to do this)

    If your Computers are part of a domain you will manage Users in thedomain User Administration.

    If your Computers are part of a Workgroup then you will manage Users oneach Computer or once on the dedicated Computer for managing

    Usernames and Passwords.

    If you decide to manage Usernames and Passwords on each Computerthen you must repeat the steps below for each of these Computers.

    Create Groups that have an exact name match with the Groups you created inthe .OS project(s).

    Create Users, if desired, revoke all Group memberships that the User gets bydefault, and assign Group membership to one or more Groups that are known

    both in the Windows User Administration and in the OS User Administration.

    NOTE Do not create the Users in the OS projects; defining them in the Windows UserAdministration is sufficient.

    SIMATIC Logon Configuration dialog

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    10/37

    1 How do user rights work?

    1.4 User rights workflow for PCS 7 OS Web Option

    Web Client users have to authenticate themselves at the OS Web Server. Theconfiguration of the web users, respectively of SIMATIC Logon is done on the OSWeb Server, similar to the normal user configuration.

    You can carry out additionally the following adjustments for all web users:

    Display language on the Web Client

    Different start pictures

    Additional user right Web Access Monitoring only

    1.5 User rights applied to tags

    Once the users have been created they will be assigned the corresponding userRights every time they log in to a OS runtime on a specific Computer.

    Access and ability to operate in a process area has been defined in the OS UserAdministration, if a User has access to a process area, then the scope of his/herability to operate is defined by specific rights that have been granted to that user.

    The rights that have been granted must match the rights that are required forindividual actions in the Faceplate of a Tag within the process area.

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    11/37

    1 How do user rights work?

    1.6 User rights mechanism

    For operation in a Faceplate there are three levels of User Rights that are relevant,these three levels are defined in levels. The levels are numbered 1, 2 and 3.

    The default User Rights that are assigned to each slot are:

    Table 1-3

    Level User Right No. Name Description

    1 5 Processcontrolling

    Right to operate the process and perform normalprocess adjustments, this includes starting andstopping equipment, opening and closing valvesand making setpoint changes to PID loops

    2 6 Higher processcontrolling

    Right to make adjustments to process criticalparameters and tuning parameters like alarm limits,

    PID algorithm tuning parameters3 1100 Highest process

    controllingRight to operate tag settings that are exceptionallike switch a tag to or from simulation (used in APLFunction Blocks and Faceplates)

    Customization of User Rights in a Faceplate

    Y h th ti f t i ti f U Ri ht i F l t

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    12/37

    1 How do user rights work?

    User Rights adjusted from the symbol

    The symbol, from which the Faceplate is being called, can be configured to definea different User Right for each of the three levels.

    Each symbol has three properties: OperationLevel1_backup,OperationLevel2_backup, OperationLevel3_backup that have a User Rightassigned to them. You can assign a different User Right which will inherit into theFaceplate.

    Properties of a Symbol that support modification of a User Right for the threelevels:

    Figure 1-3

    Ability to apply a different

    User Right to each Level

    Tag (Symbol) where this setting applies

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    13/37

    2 Appendix

    2 Appendix

    2.1 Appendix 1

    The picture below shows the mechanism in a graphical way for users defined in theOS project (uniquely defined for each Operator Station).

    Figure 2-1

    User Administration

    User Group

    User Right Area1 Area2 Area3

    Is member of

    HasApplied to

    5 X X X

    6 X

    1100 X

    X

    Tag AreaIs part of

    User User Rightsdefines

    for

    Tag Faceplate

    Are tested by

    Tag Property

    Leveldefines As configured in

    Area specific

    User Rights

    Together define

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    14/37

    2 Appendix

    2.2 Appendix 2

    The picture below shows the mechanism in a graphical way for users defined inWindows.

    Figure 2-2

    Windows User Administration

    User Group

    User Right Area1 Area2 Area3

    Is member of

    Has a corresponding Group

    Applied to

    5 X X X

    6 X

    1100 X

    X

    Tag AreaIs part of

    User

    User Rightsdefines

    for

    Tag Faceplate

    Are tested byTag Property

    Leveldefines As configured in

    Symbol

    Area specific

    User Rights

    Together define

    Group

    Has

    Group

    Belongs to

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    15/37

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    .#StatusPermanent On 1 5 ~PG_APL_Memo.PDL _CheckBox_BLR

    .#StatusPermanent Of f 1 5 ~PG_APL_Memo.PDL _CheckBox_BLR

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    ConPerMon .Ov sAH_Lim 2 6 High alarm limit f or Ov ershoot [%] ~PG_ConPerMon_Limit.PDL csoIOAnaAH

    ConPerMon .CPI_AL_Lim 2 6 Low alarm limit f or CPI [%] ~PG_ConPerMon_Limit.PDL csoIOAnaAL

    ConPerMon .CPI_AlmHy st 2 6 CPI alarm hy steresis [%] ~PG_ConPerMon_Limit.PDL csoIOAnaHy s

    ConPerMon .Ov sWH_Lim 2 6 High warning limit f or Ov ershoot [%] ~PG_ConPerMon_Limit.PDL csoIOAnaWH

    ConPerMon .CPI_WL_Lim 2 6 Low warning limit f or CPI [%] ~PG_ConPerMon_Limit.PDL csoIOAnaWL

    C onPerMon . Init Ref Var I nit ialize 2 6 I nit ialize R ef Varianc e, PV_R ef and MV_R ef in s teady st at e of cont rol loop ~PG_C onPerMon_Param et er. PD L c soBt nI nit ialize

    ConPerMon .MV_Ref 2 6 In/out: MV v alue in ref erence steady state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaMVRef

    ConPerMon .PV_Ref 2 6 In/out: PV v alue in ref erence steady state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRef

    ConPerMon .Ref Variance 2 6 Ref erence v alue f or PV_Variance in proper state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRef Var

    ConPerMon .Ref StdDev #Value 2 6 Value ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRev Dev

    ConPerMon .TimeWindow 2 6 length [s] of mov ing time window f or statistical ev aluations ~PG_ConPerMon_Parameter.PDL csoIOAnaTimeWindow

    C onPerMon . Break Suppres s C anc el ev al. 2 6 Bre ak s uppres sion of CPI alarm s at t he end of clos ed loop s tep res po ns e ~PG _C onPerMon_S et point .PD L c soBt nC anc elEv al

    ConPerMon .OnOp On 1 5 Operator input to switch back to serv ice, 1= Block on, i.e. in serv ice ~PG_ConPerMon_Standard.PDL csoBtnMode

    ConPerMon .OosOp Out of serv ice 2 6 Operator input f or Out Of Serv ice, 1= Out Of Serv ice ~PG_ConPerMon_Standard.PDL csoBtnMode

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAH

    CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAH

    CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAH

    CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAL

    CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAL

    CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAL

    CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH

    CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH

    CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH

    CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH

    CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTL

    CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTL

    CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTL

    CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWH

    CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWH

    CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWL

    CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWL

    CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWLCountOh .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountOh_Parameter.PDL csoBtnMaintenance

    CountOh .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountOh_Parameter.PDL csoBtnMaintenance

    CountOh .PresetEn Preset 2 6 Preset Enable ~PG_CountOh_Parameter.PDL csoBtnPreset

    CountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetDay s

    CountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetHours

    CountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetMins

    CountOh .UpOp Up 1 5 1 = Up Counter ~PG_CountOh_Standard.PDL csoBtnCommand

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    16/37

    CountOh .DnOp Down 1 5 1 = Down Counter ~PG_CountOh_Standard.PDL csoBtnCommand

    CountOh .Of f Op Of f 1 5 Counter Of f by Operator: 1 = Counter is Of f ~PG_CountOh_Standard.PDL csoBtnCommand

    CountOh .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_CountOh_Standard.PDL csoBtnMode

    CountOh .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_CountOh_Standard.PDL csoBtnMode

    CountOh .Day s 2 6 Operating Day s ~PG_CountOh_Standard.PDL csoIOAnaDay s

    CountOh .Hours 2 6 Operating Hours ~PG_CountOh_Standard.PDL csoIOAnaHours

    CountOh .Minutes 2 6 Operating Minutes ~PG_CountOh_Standard.PDL csoIOAnaMins

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    CountScL .OutAH_Lim 2 6 Out Value High Alarm Limit ~PG_CountScL_Limit.PDL csoIOAnaAH

    CountScL .OutAL_Lim 2 6 Out Value Low Alarm Limit ~PG_CountScL_Limit.PDL csoIOAnaAL

    CountScL .OutTH_Lim 2 6 Out Value High Tolerance Limit ~PG_CountScL_Limit.PDL csoIOAnaTH

    CountScL .OutTL_Lim 2 6 Out Value Low Tolerance Limit ~PG_CountScL_Limit.PDL csoIOAnaTL

    CountScL .OutWH_Lim 2 6 Out Value High Warning Limit ~PG_CountScL_Limit.PDL csoIOAnaWH

    CountScL .OutWL_Lim 2 6 Out Value Low Warning Limit ~PG_CountScL_Limit.PDL csoIOAnaWL

    CountScL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountScL_Parameter.PDL csoBtnMaintenance

    CountScL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountScL_Parameter.PDL csoBtnMaintenance

    CountScL .PresetEn Preset 2 6 Preset Out ~PG_CountScL_Parameter.PDL csoBtnPreset

    CountScL .PresetVal 2 6 Preset Value ~PG_CountScL_Parameter.PDL csoIOAnaPresetVal

    CountScL .UpOp Up 1 5 1 = Up Counter ~PG_CountScL_Standard.PDL csoBtnCommand

    CountScL .DnOp Down 1 5 1 = Down Counter ~PG_CountScL_Standard.PDL csoBtnCommand

    CountScL .Of f Op Of f 1 5 Counter Of f by Operator: 1 = Counter is Of f ~PG_CountScL_Standard.PDL csoBtnCommand

    CountScL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_CountScL_Standard.PDL csoBtnMode

    CountScL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_CountScL_Standard.PDL csoBtnMode

    CountScL .Out 1 5 Counter Value ~PG_CountScL_Standard.PDL csoIOAnaOut

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    DoseL .PV_AH_Lim 2 6 PV - Flow rate high alarm limit (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaAHCoarse

    DoseL .CR_AH_Lim 2 6 Creep f low - High alarm limit ~PG_DoseL_Limit.PDL csoIOAnaAHCreep

    DoseL .PV_AH2_Lim 2 6 PV - Flow rate high alarm limit (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaAHFine

    DoseL .PV_AL_Lim 2 6 PV - Flow rate low alarm limit (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaALCoarse

    DoseL .PV_AL2_Lim 2 6 PV - Flow rate low alarm limit (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaALFine

    DoseL .PV_Hy st 2 6 PV - Flow rate hy steresis (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaHy sCoarse

    DoseL .CR_Hy st 2 6 Creep f low - Hy steresis ~PG_DoseL_Limit.PDL csoIOAnaHy sCreep

    DoseL .PV_Hy st2 2 6 PV - Flow rate hy steresis (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaHy sFine

    DoseL .DQ_AH_Tol 2 6 Quantity high alarm tolerance band (ov erdose) ~PG_DoseL_Limit.PDL csoIOAnaOv erdos

    DoseL .DQ_AL_Tol 2 6 Quantity lower alarm tolerance band (underdose) ~PG_DoseL_Limit.PDL csoIOAnaUnderdose

    DoseL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_DoseL_Parameter.PDL csoBtnMaint

    DoseL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_DoseL_Parameter.PDL csoBtnMaintDoseL .SimOn On 3 1100 Simulation on/of f ~PG_DoseL_Parameter.PDL csoBtnSimu

    DoseL .SimOn Of f 3 1100 Simulation on/of f ~PG_DoseL_Parameter.PDL csoBtnSimu

    DoseL .DribbCor On 2 6 Dribbling Correction On/Of f ~PG_DoseL_Parameter.PDL csoChkBoxAutoOn

    DoseL .DribbCor Of f 2 6 Dribbling Correction On/Of f ~PG_DoseL_Parameter.PDL csoChkBoxAutoOn

    DoseL .SP_TrkExt On 2 6 1: Internal SPs tracks to external SPs in external mode ~PG_DoseL_Parameter.PDL csoChkBoxSPTrk

    DoseL .SP_TrkExt Of f 2 6 1: Internal SPs tracks to external SPs in external mode ~PG_DoseL_Parameter.PDL csoChkBoxSPTrk

    DoseL .DribbMax 2 6 Dribble Value Maximum ~PG_DoseL_Parameter.PDL csoIOAnaDribbMax

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    17/37

    DoseL .RelaxTime 2 6 Relax Time [s] ~PG_DoseL_Parameter.PDL csoIOAnaDribbTime

    DoseL .DribbIn 2 6 Dribble Value ~PG_DoseL_Parameter.PDL csoIOAnaDribbValue

    DoseL .P_DoseTime 2 6 Post dose time [s] ~PG_DoseL_Parameter.PDL csoIOAnaPostTime

    DoseL .DCF 2 6 Dribbling Correction Factor [%] ~PG_DoseL_Parameter.PDL csoIOAnaWeightFact

    DoseL .SP_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaHCoarse

    DoseL .SP2_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaHFine

    DoseL .SP_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaLCoarse

    DoseL .SP2_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaLFine

    DoseL .SimPV 1 5 PV Simulation Value, tracks when not in simulation ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaPV

    DoseL .SP_Int 1 5 Flow rate internal setpoint ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaSPCoarse

    DoseL .SP2_Int 1 5 Flow rate internal setpoint (f ine dose) ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaSPFine

    DoseL .DQ2_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaHFine

    DoseL .DQ_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaHTotal

    DoseL .DQ2_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaLFine

    DoseL .DQ_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaLTotal

    DoseL .DQ1_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPCoarse

    DoseL .DQ2_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPFine

    DoseL .DQ2_Int 1 5 Quantity setpoint f actor internal (f ine dose) ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPFineFactor

    DoseL .DQ_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPTotal

    DoseL .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand

    DoseL .ContMan Continue 1 5 1=Continue: Continue Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand

    DoseL .PauseMan Pause 1 5 1=Pause: Pause Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand

    DoseL .CancelMan Cancel 1 5 1=Cancel: Cancel Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand

    DoseL .AutModOp Automatic 1 5 1=Auto mode: auto mode by operator ~PG_DoseL_Standard.PDL csoBtnModeDoseL .ManModOp Manual 1 5 1=Manual mode: manual mode by operator ~PG_DoseL_Standard.PDL csoBtnMode

    DoseL .LocalOp Local 1 5 1=Local Mode: Local operation by operator ~PG_DoseL_Standard.PDL csoBtnMode

    DoseL .OosOp Out of serv ice 2 6 1=Oos mode: Oos mode by operator ~PG_DoseL_Standard.PDL csoBtnMode

    DoseL .RstOp Reset 1 5 Operator reset signal ~PG_DoseL_Standard.PDL csoBtnReset

    DoseL .RstDQ_Op Reset 1 5 Operator signal to reset dosed quantity ~PG_DoseL_Standard.PDL csoBtnResetQuantity

    DoseL .U_AckOp Acknowledge 1 5 Underdose acknowledge operator ~PG_DoseL_Standard.PDL csoBtnResetUnderdose

    DoseL .SP_ExtOp External 1 5 Operator Input to Select External Setpoint ~PG_DoseL_Standard.PDL csoBtnSPMode

    DoseL .SP_IntOp Internal 1 5 Operator Input to Select Internal Setpoint ~PG_DoseL_Standard.PDL csoBtnSPMode

    DoseL .SimDQ 1 5 Dosing quantity simulation v alue, tracks when not in simulation ~PG_DoseL_Standard.PDL csoIOAnaPV

    DoseL .DQ_Int 1 5 Quantity setpoint internal ~PG_DoseL_Standard.PDL csoIOAnaSP

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    FmCont .PV_AH_Lim 2 6 PV alarm high limit ~PG_FmCont_Limit.PDL csoIOAnaAH

    FmCont .PV_AL_Lim 2 6 PV alarm low limit ~PG_FmCont_Limit.PDL csoIOAnaAL

    FmCont .ER_AH_Lim 2 6 ER alarm high limit ~PG_FmCont_Limit.PDL csoIOAnaErrHFmCont .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_FmCont_Limit.PDL csoIOAnaErrHy s

    FmCont .ER_AL_Lim 2 6 ER alarm low limit ~PG_FmCont_Limit.PDL csoIOAnaErrL

    FmCont .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_FmCont_Limit.PDL csoIOAnaHy s

    FmCont .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_FmCont_Limit.PDL csoIOAnaMVH

    FmCont .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_FmCont_Limit.PDL csoIOAnaMVL

    FmCont .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_FmCont_Limit.PDL csoIOAnaRbkH

    FmCont .RbkHy st 2 6 Rbk - Hy steresis ~PG_FmCont_Limit.PDL csoIOAnaRbkHy s

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    18/37

    FmCont .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_FmCont_Limit.PDL csoIOAnaRbkL

    FmCont .SP_InHiLim 2 6 High limit of internal setpoint ~PG_FmCont_Limit.PDL csoIOAnaSPH

    FmCont .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_FmCont_Limit.PDL csoIOAnaSPL

    FmCont .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_FmCont_Limit.PDL csoIOAnaTH

    FmCont .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_FmCont_Limit.PDL csoIOAnaTL

    FmCont .PV_WH_Lim 2 6 PV warning high limit ~PG_FmCont_Limit.PDL csoIOAnaWH

    FmCont .PV_WL_Lim 2 6 PV warning low limit ~PG_FmCont_Limit.PDL csoIOAnaWL

    FmCont .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_FmCont_Parameter.PDL csoBtnMaint

    FmCont .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_FmCont_Parameter.PDL csoBtnMaint

    FmCont .SimOn On 3 1100 1 = Simulation activ ated ~PG_FmCont_Parameter.PDL csoBtnSimu

    FmCont .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_FmCont_Parameter.PDL csoBtnSimu

    FmCont .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmCont_Parameter.PDL csoChkBoxPVTrk

    FmCont .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmCont_Parameter.PDL csoChkBoxPVTrk

    FmCont .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmCont_Parameter.PDL csoChkBoxSPTrk

    FmCont .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmCont_Parameter.PDL csoChkBoxSPTrk

    FmCont .BreakTime 2 6 Minimum Break Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaBreakT

    FmCont .DeadBand 2 6 Width of deadband ~PG_FmCont_Parameter.PDL csoIOAnaDeadB

    FmCont .Gain#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaGain

    FmCont .Dif f Gain#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaGainD

    FmCont .MotorTime 2 6 Motor Actuating Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaMotorT

    FmCont .PulseTime 2 6 Minimum Pulse Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaPulseT

    FmCont .TD#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaTD

    FmCont .TI#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaTI

    FmCont .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmCont_Ramp.PDL csoBtnRampFmCont .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmCont_Ramp.PDL csoBtnRamp

    F mC ont . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mC ont _R am p. PD L c soBt nR am pMode

    F mC ont . SP_R mpModTim e Gradient 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mC ont _R am p. PD L c soBt nR am pMode

    FmCont .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmCont_Ramp.PDL csoChkBoxGrd

    FmCont .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmCont_Ramp.PDL csoChkBoxGrd

    FmCont .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_FmCont_Ramp.PDL csoIOAnaDuration

    FmCont .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_FmCont_Ramp.PDL csoIOAnaGrdDown

    FmCont .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_FmCont_Ramp.PDL csoIOAnaGrdUp

    FmCont .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_FmCont_Ramp.PDL csoIOAnaTargetSP

    FmCont .OpenOp Open 1 5 Manual Signal Open by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignals

    FmCont .CloseOp Close 1 5 Manual Signal Close by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignals

    FmCont .StopOp Stop 1 5 Manual Signal Stop by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignals

    FmCont .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_FmCont_Standard.PDL csoBtnMode

    FmCont .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_FmCont_Standard.PDL csoBtnMode

    FmCont .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_FmCont_Standard.PDL csoBtnModeFmCont .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_FmCont_Standard.PDL csoBtnMode

    FmCont .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_FmCont_Standard.PDL csoBtnSPMode

    FmCont .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_FmCont_Standard.PDL csoBtnSPMode

    FmCont .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_FmCont_Standard.PDL csoIOAnaMV

    FmCont .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_FmCont_Standard.PDL csoIOAnaPV

    FmCont .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_FmCont_Standard.PDL csoIOAnaRbk

    FmCont .SP_Int 1 5 Internal setpoint f or operation ~PG_FmCont_Standard.PDL csoIOAnaSP

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    19/37

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    FmTemp .PV_AH_Lim 2 6 PV alarm high limit ~PG_FmTemp_Limit.PDL csoIOAnaAH

    FmTemp .PV_AL_Lim 2 6 PV alarm low limit ~PG_FmTemp_Limit.PDL csoIOAnaAL

    FmTemp .ER_AH_Lim 2 6 ER alarm high limit ~PG_FmTemp_Limit.PDL csoIOAnaErrH

    FmTemp .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_FmTemp_Limit.PDL csoIOAnaErrHy s

    FmTemp .ER_AL_Lim 2 6 ER alarm low limit ~PG_FmTemp_Limit.PDL csoIOAnaErrL

    FmTemp .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_FmTemp_Limit.PDL csoIOAnaHy s

    FmTemp .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_FmTemp_Limit.PDL csoIOAnaMVH

    FmTemp .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_FmTemp_Limit.PDL csoIOAnaMVL

    FmTemp .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_FmTemp_Limit.PDL csoIOAnaRbkH

    FmTemp .RbkHy st 2 6 Rbk - Hy steresis ~PG_FmTemp_Limit.PDL csoIOAnaRbkHy s

    FmTemp .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_FmTemp_Limit.PDL csoIOAnaRbkL

    FmTemp .SP_InHiLim 2 6 High limit of internal setpoint ~PG_FmTemp_Limit.PDL csoIOAnaSPH

    FmTemp .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_FmTemp_Limit.PDL csoIOAnaSPL

    FmTemp .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_FmTemp_Limit.PDL csoIOAnaTH

    FmTemp .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_FmTemp_Limit.PDL csoIOAnaTL

    FmTemp .PV_WH_Lim 2 6 PV warning high limit ~PG_FmTemp_Limit.PDL csoIOAnaWH

    FmTemp .PV_WL_Lim 2 6 PV warning low limit ~PG_FmTemp_Limit.PDL csoIOAnaWL

    FmTemp .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_FmTemp_Parameter.PDL csoBtnMaint

    FmTemp .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_FmTemp_Parameter.PDL csoBtnMaint

    FmTemp .SimOn On 3 1100 1 = Simulation activ ated ~PG_FmTemp_Parameter.PDL csoBtnSimu

    FmTemp .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_FmTemp_Parameter.PDL csoBtnSimu

    FmTemp .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmTemp_Parameter.PDL csoChkBoxPVTrkFmTemp .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmTemp_Parameter.PDL csoChkBoxPVTrk

    FmTemp .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmTemp_Parameter.PDL csoChkBoxSPTrk

    FmTemp .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmTemp_Parameter.PDL csoChkBoxSPTrk

    FmTemp .BreakTime 2 6 Minimum Break Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaBreakT

    FmTemp .DeadBand 2 6 Width of deadband ~PG_FmTemp_Parameter.PDL csoIOAnaDeadB

    FmTemp .Gain#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaGain

    FmTemp .Dif f Gain#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaGainD

    FmTemp .MotorTime 2 6 Motor Actuating Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaMotorT

    FmTemp .PulseTime 2 6 Minimum Pulse Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaPulseT

    FmTemp .TD#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaTD

    FmTemp .TI#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaTI

    FmTemp .ConZone 2 6 Control zone ~PG_FmTemp_Parameter.PDL csoIOAnaZoneC

    FmTemp .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoBtnRamp

    FmTemp .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoBtnRamp

    F mTem p . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mTem p_R am p. PD L c soBt nR am pModeF mTem p . SP_R mpModTim e Gradient 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mTem p_R am p. PD L c soBt nR am pMode

    FmTemp .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoChkBoxGrd

    FmTemp .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoChkBoxGrd

    FmTemp .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoIOAnaDuration

    FmTemp .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_FmTemp_Ramp.PDL csoIOAnaGrdDown

    FmTemp .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_FmTemp_Ramp.PDL csoIOAnaGrdUp

    FmTemp .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_FmTemp_Ramp.PDL csoIOAnaTargetSP

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    20/37

    FmTemp .OpenOp Open 1 5 Manual Signal Open by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignals

    FmTemp .CloseOp Close 1 5 Manual Signal Close by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignals

    FmTemp .StopOp Stop 1 5 Manual Signal Stop by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignals

    FmTemp .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_FmTemp_Standard.PDL csoBtnMode

    FmTemp .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_FmTemp_Standard.PDL csoBtnMode

    FmTemp .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_FmTemp_Standard.PDL csoBtnMode

    FmTemp .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_FmTemp_Standard.PDL csoBtnMode

    FmTemp .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_FmTemp_Standard.PDL csoBtnSPMode

    FmTemp .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_FmTemp_Standard.PDL csoBtnSPMode

    FmTemp .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_FmTemp_Standard.PDL csoIOAnaMV

    FmTemp .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_FmTemp_Standard.PDL csoIOAnaPV

    FmTemp .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_FmTemp_Standard.PDL csoIOAnaRbk

    FmTemp .SP_Int 1 5 Internal setpoint f or operation ~PG_FmTemp_Standard.PDL csoIOAnaSP

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    GainSched .Gain1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain1

    GainSched .Gain2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain2

    GainSched .Gain3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain3

    GainSched .GainOp#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGainOp

    GainSched .TD_Op#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD_Op

    GainSched .TD1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD1

    GainSched .TD2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD2

    GainSched .TD3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD3

    GainSched .TI_Op#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI_OpGainSched .TI1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI1

    GainSched .TI2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI2

    GainSched .TI3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI3

    GainSched .X1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX1

    GainSched .X2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX2

    GainSched .X3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX3

    GainSched .ManParOn#Value Automatic 1 5 Value ~PG_GainSched_Standard.PDL csoBtnMode

    GainSched .ManParOn#Value Manual 1 5 Value ~PG_GainSched_Standard.PDL csoBtnMode

    GainSched .GainOp#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaGain

    GainSched .TD_Op#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaTD

    GainSched .TI_Op#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaTI

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    Intlk02 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk02_Standard.PDL csoBtnBy p1

    Intlk02 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk02_Standard.PDL csoBtnBy p1Intlk02 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk02_Standard.PDL csoBtnBy p2

    Intlk02 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk02_Standard.PDL csoBtnBy p2

    Intlk02 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk02_Standard.PDL csoBtnReset

    Intlk02 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk02_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    Intlk04 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk04_Standard.PDL csoBtnBy p1

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    21/37

    Intlk04 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk04_Standard.PDL csoBtnBy p1

    Intlk04 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk04_Standard.PDL csoBtnBy p2

    Intlk04 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk04_Standard.PDL csoBtnBy p2

    Intlk04 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk04_Standard.PDL csoBtnBy p3

    Intlk04 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk04_Standard.PDL csoBtnBy p3

    Intlk04 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk04_Standard.PDL csoBtnBy p4

    Intlk04 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk04_Standard.PDL csoBtnBy p4

    Intlk04 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk04_Standard.PDL csoBtnReset

    Intlk04 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk04_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    Intlk08 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk08_Standard.PDL csoBtnBy p1

    Intlk08 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk08_Standard.PDL csoBtnBy p1

    Intlk08 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk08_Standard.PDL csoBtnBy p2

    Intlk08 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk08_Standard.PDL csoBtnBy p2

    Intlk08 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk08_Standard.PDL csoBtnBy p3

    Intlk08 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk08_Standard.PDL csoBtnBy p3

    Intlk08 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk08_Standard.PDL csoBtnBy p4

    Intlk08 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk08_Standard.PDL csoBtnBy p4

    Intlk08 .By pIn05 Set 2 6 By pass In05 ~PG_Intlk08_Standard.PDL csoBtnBy p5

    Intlk08 .By pIn05 Reset 2 6 By pass In05 ~PG_Intlk08_Standard.PDL csoBtnBy p5

    Intlk08 .By pIn06 Set 2 6 By pass In06 ~PG_Intlk08_Standard.PDL csoBtnBy p6

    Intlk08 .By pIn06 Reset 2 6 By pass In06 ~PG_Intlk08_Standard.PDL csoBtnBy p6

    Intlk08 .By pIn07 Set 2 6 By pass In07 ~PG_Intlk08_Standard.PDL csoBtnBy p7Intlk08 .By pIn07 Reset 2 6 By pass In07 ~PG_Intlk08_Standard.PDL csoBtnBy p7

    Intlk08 .By pIn08 Set 2 6 By pass In08 ~PG_Intlk08_Standard.PDL csoBtnBy p8

    Intlk08 .By pIn08 Reset 2 6 By pass In08 ~PG_Intlk08_Standard.PDL csoBtnBy p8

    Intlk08 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk08_Standard.PDL csoBtnReset

    Intlk08 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk08_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    Intlk16 .By pIn09 Set 2 6 By pass In09 ~PG_Intlk16_Screen2.PDL csoBtnBy p1

    Intlk16 .By pIn09 Reset 2 6 By pass In09 ~PG_Intlk16_Screen2.PDL csoBtnBy p1

    Intlk16 .By pIn10 Set 2 6 By pass In10 ~PG_Intlk16_Screen2.PDL csoBtnBy p2

    Intlk16 .By pIn10 Reset 2 6 By pass In10 ~PG_Intlk16_Screen2.PDL csoBtnBy p2

    Intlk16 .By pIn11 Set 2 6 By pass In11 ~PG_Intlk16_Screen2.PDL csoBtnBy p3

    Intlk16 .By pIn11 Reset 2 6 By pass In11 ~PG_Intlk16_Screen2.PDL csoBtnBy p3

    Intlk16 .By pIn12 Set 2 6 By pass In12 ~PG_Intlk16_Screen2.PDL csoBtnBy p4

    Intlk16 .By pIn12 Reset 2 6 By pass In12 ~PG_Intlk16_Screen2.PDL csoBtnBy p4Intlk16 .By pIn13 Set 2 6 By pass In13 ~PG_Intlk16_Screen2.PDL csoBtnBy p5

    Intlk16 .By pIn13 Reset 2 6 By pass In13 ~PG_Intlk16_Screen2.PDL csoBtnBy p5

    Intlk16 .By pIn14 Set 2 6 By pass In14 ~PG_Intlk16_Screen2.PDL csoBtnBy p6

    Intlk16 .By pIn14 Reset 2 6 By pass In14 ~PG_Intlk16_Screen2.PDL csoBtnBy p6

    Intlk16 .By pIn15 Set 2 6 By pass In15 ~PG_Intlk16_Screen2.PDL csoBtnBy p7

    Intlk16 .By pIn15 Reset 2 6 By pass In15 ~PG_Intlk16_Screen2.PDL csoBtnBy p7

    Intlk16 .By pIn16 Set 2 6 By pass In16 ~PG_Intlk16_Screen2.PDL csoBtnBy p8

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    22/37

    Intlk16 .By pIn16 Reset 2 6 By pass In16 ~PG_Intlk16_Screen2.PDL csoBtnBy p8

    Intlk16 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk16_Screen2.PDL csoBtnReset

    Intlk16 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk16_Screen2.PDL csoBtnReset

    Intlk16 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk16_Standard.PDL csoBtnBy p1

    Intlk16 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk16_Standard.PDL csoBtnBy p1

    Intlk16 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk16_Standard.PDL csoBtnBy p2

    Intlk16 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk16_Standard.PDL csoBtnBy p2

    Intlk16 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk16_Standard.PDL csoBtnBy p3

    Intlk16 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk16_Standard.PDL csoBtnBy p3

    Intlk16 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk16_Standard.PDL csoBtnBy p4

    Intlk16 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk16_Standard.PDL csoBtnBy p4

    Intlk16 .By pIn05 Set 2 6 By pass In05 ~PG_Intlk16_Standard.PDL csoBtnBy p5

    Intlk16 .By pIn05 Reset 2 6 By pass In05 ~PG_Intlk16_Standard.PDL csoBtnBy p5

    Intlk16 .By pIn06 Set 2 6 By pass In06 ~PG_Intlk16_Standard.PDL csoBtnBy p6

    Intlk16 .By pIn06 Reset 2 6 By pass In06 ~PG_Intlk16_Standard.PDL csoBtnBy p6

    Intlk16 .By pIn07 Set 2 6 By pass In07 ~PG_Intlk16_Standard.PDL csoBtnBy p7

    Intlk16 .By pIn07 Reset 2 6 By pass In07 ~PG_Intlk16_Standard.PDL csoBtnBy p7

    Intlk16 .By pIn08 Set 2 6 By pass In08 ~PG_Intlk16_Standard.PDL csoBtnBy p8

    Intlk16 .By pIn08 Reset 2 6 By pass In08 ~PG_Intlk16_Standard.PDL csoBtnBy p8

    Intlk16 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk16_Standard.PDL csoBtnReset

    Intlk16 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk16_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    ModPreCon .SP1DeadBand 2 6 Radius (deadband) f or range control of CV1 ~PG_ModPreCon_C hannel1.PDL csoIOAnaDeadBModPreCon .MV1RaLim 2 6 Manipulated v ariable 1 rate limit per sample ~PG_ModPreCon_Channel1.PDL csoIOAnaGrad

    ModPreCon .MV1HiLim 2 6 Manipulated v ariable 1 high limit ~PG_ModPreCon_Channel1.PDL csoIOAnaMVH

    ModPreCon .MV1LoLim 2 6 Manipulated v ariable 1 low limit ~PG_ModPreCon_Channel1.PDL csoIOAnaMVL

    ModPreCon .PreFilt1 2 6 Setpoint 1 pref ilter settling time [s] ~PG_ModPreCon_Channel1.PDL csoIOAnaPref il

    ModPreCon .SP1HiLim 2 6 High limit f or operator setpoint 1 ~PG_ModPreCon_Channel1.PDL csoIOAnaSPH

    ModPreCon .SP1LoLim 2 6 Low limit f or operator setpoint 1 ~PG_ModPreCon_Channel1.PDL csoIOAnaSPL

    ModPreCon .SP2DeadBand 2 6 Radius (deadband) f or range control of CV2 ~PG_ModPreCon_C hannel2.PDL csoIOAnaDeadB

    ModPreCon .MV2RaLim 2 6 Manipulated v ariable 2 rate limit per sample ~PG_ModPreCon_Channel2.PDL csoIOAnaGrad

    ModPreCon .MV2HiLim 2 6 Manipulated v ariable 2 high limit ~PG_ModPreCon_Channel2.PDL csoIOAnaMVH

    ModPreCon .MV2LoLim 2 6 Manipulated v ariable 2 low limit ~PG_ModPreCon_Channel2.PDL csoIOAnaMVL

    ModPreCon .PreFilt2 2 6 Setpoint 2 pref ilter settling time [s] ~PG_ModPreCon_Channel2.PDL csoIOAnaPref il

    ModPreCon .SP2HiLim 2 6 High limit f or operator setpoint 2 ~PG_ModPreCon_Channel2.PDL csoIOAnaSPH

    ModPreCon .SP2LoLim 2 6 Low limit f or operator setpoint 2 ~PG_ModPreCon_Channel2.PDL csoIOAnaSPL

    ModPreCon .SP3DeadBand 2 6 Radius (deadband) f or range control of CV3 ~PG_ModPreCon_C hannel3.PDL csoIOAnaDeadB

    ModPreCon .MV3RaLim 2 6 Manipulated v ariable 3 rate limit per sample ~PG_ModPreCon_Channel3.PDL csoIOAnaGradModPreCon .MV3HiLim 2 6 Manipulated v ariable 3 high limit ~PG_ModPreCon_Channel3.PDL csoIOAnaMVH

    ModPreCon .MV3LoLim 2 6 Manipulated v ariable 3 low limit ~PG_ModPreCon_Channel3.PDL csoIOAnaMVL

    ModPreCon .PreFilt3 2 6 Setpoint 3 pref ilter settling time [s] ~PG_ModPreCon_Channel3.PDL csoIOAnaPref il

    ModPreCon .SP3HiLim 2 6 High limit f or operator setpoint 3 ~PG_ModPreCon_Channel3.PDL csoIOAnaSPH

    ModPreCon .SP3LoLim 2 6 Low limit f or operator setpoint 3 ~PG_ModPreCon_Channel3.PDL csoIOAnaSPL

    ModPreCon .SP4DeadBand 2 6 Radius (deadband) f or range control of CV4 ~PG_ModPreCon_C hannel4.PDL csoIOAnaDeadB

    ModPreCon .MV4RaLim 2 6 Manipulated v ariable 4 rate limit per sample ~PG_ModPreCon_Channel4.PDL csoIOAnaGrad

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    23/37

    ModPreCon .MV4HiLim 2 6 Manipulated v ariable 4 high limit ~PG_ModPreCon_Channel4.PDL csoIOAnaMVH

    ModPreCon .MV4LoLim 2 6 Manipulated v ariable 4 low limit ~PG_ModPreCon_Channel4.PDL csoIOAnaMVL

    ModPreCon .PreFilt4 2 6 Setpoint 4 pref ilter settling time [s] ~PG_ModPreCon_Channel4.PDL csoIOAnaPref il

    ModPreCon .SP4HiLim 2 6 High limit f or operator setpoint 4 ~PG_ModPreCon_Channel4.PDL csoIOAnaSPH

    ModPreCon .SP4LoLim 2 6 Low limit f or operator setpoint 4 ~PG_ModPreCon_Channel4.PDL csoIOAnaSPL

    ModPreC on . MS_R elOp Y es 3 1100 Op erat or input f or MS R eleas e, 1= MS releas e requirem ent ~PG _ModPreC on_P aram et er. PD L c soBt nMaint

    ModPreC on . MS_R elOp N o 3 1100 Op erat or input f or MS R eleas e, 1= MS releas e requirem ent ~PG _ModPreC on_P aram et er. PD L c soBt nMaint

    ModPreCon .SimOn On 3 1100 Simulation On/Of f ~PG_ModPreCon_Parameter.PDL csoBtnSimu

    ModPreCon .SimOn Of f 3 1100 Simulation On/Of f ~PG_ModPreCon_Parameter.PDL csoBtnSimu

    ModPreCon .DV_On On 2 6 1 = Activ ate disturbance f eedf orward of DV1 ~PG_ModPreCon_Parameter.PDL csoChkBoxDisturb

    ModPreCon .DV_On Of f 2 6 1 = Activ ate disturbance f eedf orward of DV1 ~PG_ModPreCon_Parameter.PDL csoChkBoxDisturb

    ModPreCon .SP_TrkCV On 2 6 SPs track CVs in manual mode and in tracking mode ~PG_ModPreCon_Parameter.PDL csoChkBoxPVTrk

    ModPreCon .SP_TrkCV Of f 2 6 SPs track CVs in manual mode and in tracking mode ~PG_ModPreCon_Parameter.PDL csoChkBoxPVTrk

    ModPreCon .DV1#Value 2 6 Value ~PG_ModPreCon_Parameter.PDL csoIOAnaDisturb

    ModPreCon . AutModOp Automatic 1 5 Operator input f or automatic mode, 1= Automatic ~PG_ModPreCon_Standard.PDL csoBtnMode

    ModPreCon .ManModOp Manual 1 5 Operator input f or manual mode, 1= Manual ~PG_ModPreCon_Standard.PDL csoBtnMode

    ModPreCon .OosOp Out of serv ice 2 6 Operator input f or Out Of Serv ice, 1= Out Of Serv ice ~PG_ModPreCon_Standard.PDL csoBtnMode

    ModPreCon . SimCV1 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV1

    ModPreCon . SimCV2 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV2

    ModPreCon . SimCV3 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV3

    ModPreCon . SimCV4 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV4

    ModPreCon .MV1Man 1 5 Manual setting of manipulated v ariable MV1 ~PG_ModPreCon_Standard.PDL csoIOAnaMV1

    ModPreCon .MV2Man 1 5 Manual setting of manipulated v ariable MV2 ~PG_ModPreCon_Standard.PDL csoIOAnaMV2

    ModPreCon .MV3Man 1 5 Manual setting of manipulated v ariable MV3 ~PG_ModPreCon_Standard.PDL csoIOAnaMV3ModPreCon .MV4Man 1 5 Manual setting of manipulated v ariable MV4 ~PG_ModPreCon_Standard.PDL csoIOAnaMV4

    ModPreCon .SP1#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP1

    ModPreCon .SP2#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP2

    ModPreCon .SP3#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP3

    ModPreCon .SP4#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP4

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    MonAnL .PV_AH_Lim 2 6 PV - High Alarm Limit ~PG_MonAnL_Limit.PDL csoIOAnaAH

    MonAnL .PV_AL_Lim 2 6 PV - Low Alarm Limit ~PG_MonAnL_Limit.PDL csoIOAnaAL

    MonAnL .PV_Hy st 2 6 PV - Alarm Hy steresis ~PG_MonAnL_Limit.PDL csoIOAnaHy s

    MonAnL .PV_TH_Lim 2 6 PV - High Tolerance Limit ~PG_MonAnL_Limit.PDL csoIOAnaTH

    MonAnL .PV_TL_Lim 2 6 PV - Low Tolerance Limit ~PG_MonAnL_Limit.PDL csoIOAnaTL

    MonAnL .PV_WH_Lim 2 6 PV - High Warning Limit ~PG_MonAnL_Limit.PDL csoIOAnaWH

    MonAnL .PV_WL_Lim 2 6 PV - Low Warning Limit ~PG_MonAnL_Limit.PDL csoIOAnaWL

    MonAnL .GradLLim 2 6 Low alarm limit f or positiv e and negativ e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGAMonAnL .GradHUpLim 2 6 High alarm limit f or positiv e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGH

    MonAnL .GradHDnLim 2 6 High alarm limit f or negativ e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGL

    MonAnL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnL_Parameter.PDL csoBtnMaintenance

    MonAnL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnL_Parameter.PDL csoBtnMaintenance

    MonAnL .SimOn On 3 1100 Simulation On/Of f ~PG_MonAnL_Parameter.PDL csoBtnSim

    MonAnL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonAnL_Parameter.PDL csoBtnSim

    MonAnL .DeadBand 2 6 Dead band width ~PG_MonAnL_Parameter.PDL csoIOAnaDeadB

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    24/37

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    25/37

    MonDiL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonDiL_Standard.PDL csoBtnMode

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    MonDiS .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiS_Parameter.PDL csoBtnMaintenance

    MonDiS .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiS_Parameter.PDL csoBtnMaintenance

    MonDiS .SimOn On 3 1100 Simulation On/Of f ~PG_MonDiS_Parameter.PDL csoBtnSim

    MonDiS .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonDiS_Parameter.PDL csoBtnSim

    MonDiS .Out_DC 2 6 Out Delay Time Coming [s] ~PG_MonDiS_Parameter.PDL csoIOAnaControlMon

    MonDiS .SimIn Activ e 1 5 Simulation Value ~PG_MonDiS_Standard.PDL csoBtnCommand

    MonDiS .SimIn Inactiv e 1 5 Simulation Value ~PG_MonDiS_Standard.PDL csoBtnCommand

    MonDiS .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_MonDiS_Standard.PDL csoBtnMode

    MonDiS .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonDiS_Standard.PDL csoBtnMode

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    MotL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotL_Limit.PDL csoIOAnaAH

    MotL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotL_Limit.PDL csoIOAnaAL

    MotL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotL_Limit.PDL csoIOAnaAV

    MotL .AV_Hy st 2 6 AV - Hy steresis ~PG_MotL_Limit.PDL csoIOAnaHy s

    MotL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotL_Limit.PDL csoIOAnaTH

    MotL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotL_Limit.PDL csoIOAnaTL

    MotL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotL_Limit.PDL csoIOAnaWH

    MotL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotL_Limit.PDL csoIOAnaWL

    MotL .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotL_Parameter.PDL chkMonitor

    MotL .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotL_Parameter.PDL chkMonitor MotL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotL_Parameter.PDL csoBtnMaintenance

    MotL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotL_Parameter.PDL csoBtnMaintenance

    MotL .SimOn On 3 1100 Simulation On/Of f ~PG_MotL_Parameter.PDL csoBtnSim

    MotL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotL_Parameter.PDL csoBtnSim

    MotL .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotL_Parameter.PDL csoIOAnaDy nMonTime

    MotL .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotL_Parameter.PDL csoIOAnaStaMonTime

    MotL .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_MotL_Standard.PDL csoBtnCommand

    MotL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotL_Standard.PDL csoBtnCommand

    MotL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotL_Standard.PDL csoBtnCommand

    MotL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotL_Standard.PDL csoBtnMode

    MotL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotL_Standard.PDL csoBtnMode

    MotL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotL_Standard.PDL csoBtnMode

    MotL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotL_Standard.PDL csoBtnMode

    MotL .RstOp Reset 1 5 Operator Reset Signal ~PG_MotL_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    MotRev L .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotRev L_Limit.PDL csoIOAnaAH

    MotRev L .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotRev L_Limit.PDL csoIOAnaAL

    MotRev L .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotRev L_Limit.PDL csoIOAnaAV

    MotRev L .AV_Hy st 2 6 AV - Hy steresis ~PG_MotRev L_Limit.PDL csoIOAnaHy s

    MotRev L .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotRev L_Limit.PDL csoIOAnaTH

    MotRev L .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotRev L_Limit.PDL csoIOAnaTL

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    26/37

    MotRev L .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotRev L_Limit.PDL csoIOAnaWH

    MotRev L .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotRev L_Limit.PDL csoIOAnaWL

    MotRev L .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotRev L_Parameter.PDL chkMonitor

    MotRev L .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotRev L_Parameter.PDL chkMonitor

    MotRev L .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotRev L_Parameter.PDL csoBtnMaintenance

    MotRev L .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotRev L_Parameter.PDL csoBtnMaintenance

    MotRev L .SimOn On 3 1100 Simulation On/Of f ~PG_MotRev L_Parameter.PDL csoBtnSim

    MotRev L .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotRev L_Parameter.PDL csoBtnSim

    MotRev L .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotRev L_Parameter.PDL csoIOAnaDy nMonTimeMotRev L .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotRev L_Parameter.PDL csoIOAnaStaMonTime

    MotRev L .FwdMan Forward 1 5 1=Start: Forward Start Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommand

    MotRev L .Rev Man Rev erse 1 5 1=Start: Rev erse Start Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommand

    MotRev L .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommand

    MotRev L .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotRev L_Standard.PDL csoBtnCommand

    MotRev L .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnMode

    MotRev L .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnMode

    MotRev L .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotRev L_Standard.PDL csoBtnMode

    MotRev L .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnMode

    MotRev L .RstOp Reset 1 5 Operator Reset Signal ~PG_MotRev L_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    MotS .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotS_Parameter.PDL chkMonitor

    MotS .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotS_Parameter.PDL chkMonitor

    MotS .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotS_Parameter.PDL csoBtnMaintenanceMotS .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotS_Parameter.PDL csoBtnMaintenance

    MotS .SimOn On 3 1100 Simulation On/Of f ~PG_MotS_Parameter.PDL csoBtnSim

    MotS .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotS_Parameter.PDL csoBtnSim

    MotS .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotS_Parameter.PDL csoIOAnaDy nMonTime

    MotS .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_MotS_Standard.PDL csoBtnCommand

    MotS .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotS_Standard.PDL csoBtnCommand

    MotS .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotS_Standard.PDL csoBtnMode

    MotS .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotS_Standard.PDL csoBtnMode

    MotS .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotS_Standard.PDL csoBtnMode

    MotS .RstOp Reset 1 5 Operator Reset Signal ~PG_MotS_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    MotSpdCL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaAH

    MotSpdCL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaAL

    MotSpdCL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotSpdCL_Limit.PDL csoIOAnaAVMotSpdCL .AV_Hy st 2 6 AV - Hy steresis ~PG_MotSpdCL_Limit.PDL csoIOAnaHy s

    MotSpdCL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTH

    MotSpdCL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTL

    MotSpdCL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWH

    MotSpdCL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWL

    MotSpdCL .ER_AH_Lim 2 6 ER alarm high limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaAH

    MotSpdCL .ER_AL_Lim 2 6 ER alarm low limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaAL

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    27/37

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    28/37

    MotSpdCL .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotSpdCL_Parameter.PDL chkMonitor

    MotSpdCL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenance

    MotSpdCL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenance

    MotSpdCL . SimOn On 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSim

    MotSpdCL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSim

    MotSpdCL .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaDy nMonTime

    MotSpdCL .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaStaMonTime

    MotSpdCL .Spd1Man Slow 1 5 ~PG_MotSpdCL_Standard.PDL csoBtnCommand

    MotSpdCL .Spd2Man Fast 1 5 ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotSpdCL_Standard.PDL csoBtnCommand

    MotSpdCL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotSpdCL_Standard.PDL csoBtnCommand

    MotSpdCL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode

    MotSpdCL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode

    MotSpdCL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode

    MotSpdCL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode

    MotSpdCL . RstOp Reset 1 5 Operator Reset Signal ~PG_MotSpdCL_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    OpAnL .SP_TrkExt On 2 6 1: SP_Int tracks SP_Ext in External ~PG_OpAnL_Parameter.PDL chkBumpless

    OpAnL .SP_TrkExt Of f 2 6 1: SP_Int tracks SP_Ext in External ~PG_OpAnL_Parameter.PDL chkBumpless

    OpAnL .SP_RateOn On 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_OpAnL_Ramp.PDL chkRampOn

    OpAnL .SP_RateOn Of f 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_OpAnL_Ramp.PDL chkRampOn

    OpAnL . SP_R mpModTim e D urat ion 1 5 1: S P ram ped ov er SP_R mpTim e, 0 : SP ram ped by r at es SP_U pR aLi m, SP_D nR aLim ~PG_OpAnL_R am p. PD L c soBt nR am pMode

    OpAnL . SP_R mpModTim e Gradient 1 5 1: S P ram ped ov er SP_R mpTim e, 0 : SP ram ped by r at es SP_U pR aLi m, SP_D nR aLim ~PG_OpAnL_R am p. PD L c soBt nR am pModeOpAnL .SP_RmpOn Activ e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_OpAnL_Ramp.PDL csoBtnRampOn

    OpAnL .SP_RmpOn Inactiv e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_OpAnL_Ramp.PDL csoBtnRampOn

    OpAnL .SP_RmpTime 1 5 Setpoint ramp time [s] ~PG_OpAnL_Ramp.PDL csoIOAnaDuration

    OpAnL .SP_DnRaLim 1 5 Downward rate limit f or setpoint changes or ramping ~PG_OpAnL_Ramp.PDL csoIOAnaRampDn

    OpAnL .SP_UpRaLim 1 5 Upward rate limit f or setpoint changes or ramping ~PG_OpAnL_Ramp.PDL csoIOAnaRampUp

    OpAnL .SP_RmpTarget 1 5 Setpoint ramp target ~PG_OpAnL_Ramp.PDL csoIOAnaTargetSP

    OpAnL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpAnL_Standard.PDL csoBtnMode

    OpAnL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpAnL_Standard.PDL csoBtnMode

    OpAnL .SP_ExtOp External 1 5 Operator input to select external setpoint ~PG_OpAnL_Standard.PDL csoBtnSetpoint

    OpAnL .SP_IntOp Internal 1 5 Operator input to select internal setpoint ~PG_OpAnL_Standard.PDL csoBtnSetpoint

    OpAnL .PV_In#Value 1 5 Value ~PG_OpAnL_Standard.PDL csoIOAnaPV

    OpAnL .SP_Int 1 5 Internal Analog setpoint ~PG_OpAnL_Standard.PDL csoIOAnaSP

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    OpDi01 .SetOp On 1 5 Operator Set Signal ~PG_OpDi01_Standard.PDL csoBtnCommandOpDi01 .RstOp Of f 1 5 Operator Reset Signal ~PG_OpDi01_Standard.PDL csoBtnCommand

    OpDi01 .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpDi01_Standard.PDL csoBtnMode

    OpDi01 .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpDi01_Standard.PDL csoBtnMode

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    OpDi03 .SetOp1 On 1 5 Operator Digital Input 1 ~PG_OpDi03_Standard.PDL csoBtnCommand1

    OpDi03 .SetOp2 On 1 5 Operator Digital Input 2 ~PG_OpDi03_Standard.PDL csoBtnCommand2

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    29/37

    OpDi03 .SetOp3 On 1 5 Operator Digital Input 3 ~PG_OpDi03_Standard.PDL csoBtnCommand3

    OpDi03 .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpDi03_Standard.PDL csoBtnMode

    OpDi03 .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpDi03_Standard.PDL csoBtnMode

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    OpStations .In0 Enable 3 1100 1='Enable operator station 1 ~PG_OpStations_Standard.PDL csoChkBoxIn0

    OpStations .In0 Disable 3 1100 1='Enable operator station 1 ~PG_OpStations_Standard.PDL csoChkBoxIn0

    OpStations .In1 Enable 3 1100 1='Enable operator station 2 ~PG_OpStations_Standard.PDL csoChkBoxIn1

    OpStations .In1 Disable 3 1100 1='Enable operator station 2 ~PG_OpStations_Standard.PDL csoChkBoxIn1OpStations .In10 Enable 3 1100 1='Enable operator s tation 11 ~PG_OpStations_Standard.PDL csoChkBox In10

    OpStations .In10 Disable 3 1100 1='Enable operator s tation 11 ~PG_OpStations_Standard.PDL csoChkBox In10

    OpStations .In11 Enable 3 1100 1='Enable operator s tation 12 ~PG_OpStations_Standard.PDL csoChkBox In11

    OpStations .In11 Disable 3 1100 1='Enable operator s tation 12 ~PG_OpStations_Standard.PDL csoChkBox In11

    OpStations .In12 Enable 3 1100 1='Enable operator s tation 13 ~PG_OpStations_Standard.PDL csoChkBox In12

    OpStations .In12 Disable 3 1100 1='Enable operator s tation 13 ~PG_OpStations_Standard.PDL csoChkBox In12

    OpStations .In13 Enable 3 1100 1='Enable operator station 14 ~PG_OpStations_Standard.PDL csoChkBoxIn13

    OpStations .In13 Disable 3 1100 1='Enable operator station 14 ~PG_OpStations_Standard.PDL csoChkBoxIn13

    OpStations .In14 Enable 3 1100 1='Enable operator s tation 15 ~PG_OpStations_Standard.PDL csoChkBox In14

    OpStations .In14 Disable 3 1100 1='Enable operator s tation 15 ~PG_OpStations_Standard.PDL csoChkBox In14

    OpStations .In15 Enable 3 1100 1='Enable operator station 16 ~PG_OpStations_Standard.PDL csoChkBoxIn15

    OpStations .In15 Disable 3 1100 1='Enable operator station 16 ~PG_OpStations_Standard.PDL csoChkBoxIn15

    OpStations .In2 Enable 3 1100 1='Enable operator station 3 ~PG_OpStations_Standard.PDL csoChkBoxIn2

    OpStations .In2 Disable 3 1100 1='Enable operator station 3 ~PG_OpStations_Standard.PDL csoChkBoxIn2

    OpStations .In3 Enable 3 1100 1='Enable operator station 4 ~PG_OpStations_Standard.PDL csoChkBoxIn3OpStations .In3 Disable 3 1100 1='Enable operator station 4 ~PG_OpStations_Standard.PDL csoChkBoxIn3

    OpStations .In4 Enable 3 1100 1='Enable operator station 5 ~PG_OpStations_Standard.PDL csoChkBoxIn4

    OpStations .In4 Disable 3 1100 1='Enable operator station 5 ~PG_OpStations_Standard.PDL csoChkBoxIn4

    OpStations .In5 Enable 3 1100 1='Enable operator station 6 ~PG_OpStations_Standard.PDL csoChkBoxIn5

    OpStations .In5 Disable 3 1100 1='Enable operator station 6 ~PG_OpStations_Standard.PDL csoChkBoxIn5

    OpStations .In6 Enable 3 1100 1='Enable operator station 7 ~PG_OpStations_Standard.PDL csoChkBoxIn6

    OpStations .In6 Disable 3 1100 1='Enable operator station 7 ~PG_OpStations_Standard.PDL csoChkBoxIn6

    OpStations .In7 Enable 3 1100 1='Enable operator station 8 ~PG_OpStations_Standard.PDL csoChkBoxIn7

    OpStations .In7 Disable 3 1100 1='Enable operator station 8 ~PG_OpStations_Standard.PDL csoChkBoxIn7

    OpStations .In8 Enable 3 1100 1='Enable operator station 9 ~PG_OpStations_Standard.PDL csoChkBoxIn8

    OpStations .In8 Disable 3 1100 1='Enable operator station 9 ~PG_OpStations_Standard.PDL csoChkBoxIn8

    OpStations .In9 Enable 3 1100 1='Enable operator station 10 ~PG_OpStations_Standard.PDL csoChkBoxIn9

    OpStations . In9 Disable 3 1100 1='Enable operator station 10 ~PG_OpStations_Standard.PDL csoChkBoxIn9

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameOpTrig .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpTrig_Standard.PDL csoBtnMode

    OpTrig .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpTrig_Standard.PDL csoBtnMode

    OpTrig .InOp Set 1 5 Operator Binary Input ~PG_OpTrig_Standard.PDL csoBtnReset

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    PIDConL .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDConL_Limit.PDL csoIOAnaAH

    PIDConL .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDConL_Limit.PDL csoIOAnaAL

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    30/37

    PIDConL .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDConL_Limit.PDL csoIOAnaErrH

    PIDConL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDConL_Limit.PDL csoIOAnaErrHy s

    PIDConL .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDConL_Limit.PDL csoIOAnaErrL

    PIDConL .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDConL_Limit.PDL csoIOAnaHy s

    PIDConL .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDConL_Limit.PDL csoIOAnaMVH

    PIDConL .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDConL_Limit.PDL csoIOAnaMVL

    PIDConL .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDConL_Limit.PDL csoIOAnaRbkH

    PIDConL .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDConL_Limit.PDL csoIOAnaRbkHy s

    PIDConL .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDConL_Limit.PDL csoIOAnaRbkLPIDConL .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDConL_Limit.PDL csoIOAnaSPH

    PIDConL .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDConL_Limit.PDL csoIOAnaSPL

    PIDConL .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDConL_Limit.PDL csoIOAnaTH

    PIDConL .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDConL_Limit.PDL csoIOAnaTL

    PIDConL .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDConL_Limit.PDL csoIOAnaWH

    PIDConL .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDConL_Limit.PDL csoIOAnaWL

    PIDConL .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDConL_Parameter.PDL csoBtnMaint

    PIDConL .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDConL_Parameter.PDL csoBtnMaint

    PIDConL .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDConL_Parameter.PDL csoBtnSimu

    PIDConL .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDConL_Parameter.PDL csoBtnSimu

    PIDConL .OptimEn On 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConL_Parameter.PDL csoChkBoxOpti

    PIDConL .OptimEn Of f 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConL_Parameter.PDL csoChkBoxOpti

    PIDConL .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConL_Parameter.PDL csoChkBoxPVTrk

    PIDConL .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConL_Parameter.PDL csoChkBoxPVTrk

    PIDConL .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConL_Parameter.PDL csoChkBoxSPTrkPIDConL .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConL_Parameter.PDL csoChkBoxSPTrk

    PIDConL .DeadBand 2 6 Width of deadband ~PG_PIDConL_Parameter.PDL csoIOAnaDeadB

    PIDConL .Gain#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaGain

    PIDConL .Dif f Gain#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaGainD

    PIDConL .TD#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaTD

    PIDConL .TI#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaTI

    PIDConL .ConZone 2 6 Width of control zone ~PG_PIDConL_Parameter.PDL csoIOAnaZoneC

    PIDConL .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoBtnRamp

    PIDConL .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoBtnRamp

    PI DC onL . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onL_R am p. PD L c soBt nR am pMode

    PI DC onL . SP_R mpModTim e Gradient 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onL_R am p. PD L c soBt nR am pMode

    PIDConL .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoChkBoxGrd

    PIDConL .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoChkBoxGrd

    PIDConL .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoIOAnaDuration

    PIDConL .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_PIDConL_Ramp.PDL csoIOAnaGrdDownPIDConL .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_PIDConL_Ramp.PDL csoIOAnaGrdUp

    PIDConL .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_PIDConL_Ramp.PDL csoIOAnaTargetSP

    PIDConL .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_PIDConL_Standard.PDL csoBtnMode

    PIDConL .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_PIDConL_Standard.PDL csoBtnMode

    PIDConL .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_PIDConL_Standard.PDL csoBtnMode

    PIDConL .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_PIDConL_Standard.PDL csoBtnMode

    PIDConL .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_PIDConL_Standard.PDL csoBtnSPMode

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    31/37

    PIDConL .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_PIDConL_Standard.PDL csoBtnSPMode

    PIDConL .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_PIDConL_Standard.PDL csoIOAnaMV

    PIDConL .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_PIDConL_Standard.PDL csoIOAnaPV

    PIDConL .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_PIDConL_Standard.PDL csoIOAnaRbk

    PIDConL .SP_Int 1 5 Internal setpoint f or operation ~PG_PIDConL_Standard.PDL csoIOAnaSP

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    PIDConR .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDConR_Limit.PDL csoIOAnaAH

    PIDConR .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDConR_Limit.PDL csoIOAnaALPIDConR .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDConR_Limit.PDL csoIOAnaErrH

    PIDConR .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDConR_Limit.PDL csoIOAnaErrHy s

    PIDConR .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDConR_Limit.PDL csoIOAnaErrL

    PIDConR .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDConR_Limit.PDL csoIOAnaHy s

    PIDConR .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDConR_Limit.PDL csoIOAnaMVH

    PIDConR .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDConR_Limit.PDL csoIOAnaMVL

    PIDConR .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDConR_Limit.PDL csoIOAnaRbkH

    PIDConR .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDConR_Limit.PDL csoIOAnaRbkHy s

    PIDConR .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDConR_Limit.PDL csoIOAnaRbkL

    PIDConR .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDConR_Limit.PDL csoIOAnaSPH

    PIDConR .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDConR_Limit.PDL csoIOAnaSPL

    PIDConR .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDConR_Limit.PDL csoIOAnaTH

    PIDConR .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDConR_Limit.PDL csoIOAnaTL

    PIDConR .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDConR_Limit.PDL csoIOAnaWH

    PIDConR .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDConR_Limit.PDL csoIOAnaWLPIDConR .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDConR_Parameter.PDL csoBtnMaint

    PIDConR .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDConR_Parameter.PDL csoBtnMaint

    PIDConR .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDConR_Parameter.PDL csoBtnSimu

    PIDConR .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDConR_Parameter.PDL csoBtnSimu

    PIDConR .OptimEn On 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConR_Parameter.PDL csoChkBoxOpti

    PIDConR .OptimEn Of f 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConR_Parameter.PDL csoChkBoxOpti

    PIDConR .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConR_Parameter.PDL csoChkBoxPVTrk

    PIDConR .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConR_Parameter.PDL csoChkBoxPVTrk

    PIDConR .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConR_Parameter.PDL csoChkBoxSPTrk

    PIDConR .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConR_Parameter.PDL csoChkBoxSPTrk

    PIDConR .DeadBand 2 6 Width of deadband ~PG_PIDConR_Parameter.PDL csoIOAnaDeadB

    PIDConR .Gain#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaGain

    PIDConR .Dif f Gain#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaGainD

    PIDConR .TD#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaTD

    PIDConR .TI#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaTIPIDConR .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoBtnRamp

    PIDConR .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoBtnRamp

    PI DC onR . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onR _R am p. PD L c soBt nR am pMode

    PI DC onR . SP_R mpModTim e Gradient 1 5 1= Us e t im e (SP_R mpTim e) for ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onR _R am p. PD L c soBt nR am pMode

    PIDConR .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoChkBoxGrd

    PIDConR .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoChkBoxGrd

    PIDConR .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoIOAnaDuration

  • 8/10/2019 60575347_PCS7_UserRights_en.pdf

    32/37

    PIDConR .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_PIDConR_Ramp.PDL csoIOAnaGrdDown

    PIDConR .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_PIDConR_Ramp.PDL csoIOAnaGrdUp

    PIDConR .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_PIDConR_Ramp.PDL csoIOAnaTargetSP

    PIDConR .AutModOp Automatic 1 5 1 = Automatic mode by operator ~PG_PIDConR_Standard.PDL csoBtnMode

    PIDConR .ManModOp Manual 1 5 1 = Manual mode by operator ~PG_PIDConR_Standard.PDL csoBtnMode

    PIDConR .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_PIDConR_Standard.PDL csoBtnMode

    PIDConR .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_PIDConR_Standard.PDL csoBtnMode

    PIDConR .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_PIDConR_Standard.PDL csoBtnSPMode

    PIDConR .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_PIDConR_Standard.PDL csoBtnSPModePIDConR .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_PIDConR_Standard.PDL csoIOAnaMV

    PIDConR .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_PIDConR_Standard.PDL csoIOAnaPV

    PIDConR .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_PIDConR_Standard.PDL csoIOAnaRbk

    PIDConR .SP_Int 1 5 Internal setpoint f or operation ~PG_PIDConR_Standard.PDL csoIOAnaSP

    BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName

    PIDStepL .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDStepL_Limit.PDL csoIOAnaAH

    PIDStepL .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDStepL_Limit.PDL csoIOAnaAL

    PIDStepL .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDStepL_Limit.PDL csoIOAnaErrH

    PIDStepL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDStepL_Limit.PDL csoIOAnaErrHy s

    PIDStepL .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDStepL_Limit.PDL csoIOAnaErrL

    PIDStepL .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDStepL_Limit.PDL csoIOAnaHy s

    PIDStepL .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDStepL_Limit.PDL csoIOAnaMVH

    PIDStepL .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDStepL_Limit.PDL csoIOAnaMVL

    PIDStepL .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDStepL_Limit.PDL csoIOAnaRbkHPIDStepL .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDStepL_Limit.PDL csoIOAnaRbkHy s

    PIDStepL .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDStepL_Limit.PDL csoIOAnaRbkL

    PIDStepL .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDStepL_Limit.PDL csoIOAnaSPH

    PIDStepL .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDStepL_Limit.PDL csoIOAnaSPL

    PIDStepL .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDStepL_Limit.PDL csoIOAnaTH

    PIDStepL .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDStepL_Limit.PDL csoIOAnaTL

    PIDStepL .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDStepL_Limit.PDL csoIOAnaWH

    PIDStepL .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDStepL_Limit.PDL csoIOAnaWL

    PIDStepL .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDStepL_Parameter.PDL csoBtnMaint

    PIDStepL .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDStepL_Parameter.PDL csoBtnMaint

    PIDStepL .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDStepL_Parameter.PDL csoBtnSimu

    PIDStepL .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDStepL_Parameter.PDL csoBtnSimu

    PIDStepL .OptimEn On 2 6 1 = Enable optimization of PID