60575347_pcs7_userrights_en.pdf
TRANSCRIPT
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
1/37
Cover
User Rights (Authorizations)
in SIMATIC PCS 7 OS V7.1SIMATIC PCS 7 V7.1
FAQ May 2012
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
2/37
Question
This entry is from the Siemens Industry Online Support. The general terms of use(http://www.siemens.com/terms_of_use)apply.
Clicking the link below directly displays the download page of this document.
http://support.automarion.siemens.com/WW/view/en/60575347
CautionThe functions and solutions described in this article confine themselves to therealization of the automation task predominantly. Please take into accountfurthermore that corresponding protective measures have to be taken up in thecontext of Industrial Security when connecting your equipment to other parts of theplant, the enterprise network or the Internet. Further information can be foundunder the Content-ID 50203404.
http://support.automation.siemens.com/WW/view/en/50203404
http://www.siemens.com/terms_of_usehttp://www.siemens.com/terms_of_usehttp://support.automarion.siemens.com/WW/view/en/60575347http://support.automarion.siemens.com/WW/view/en/60575347http://support.automation.siemens.com/WW/view/en/50203404http://support.automation.siemens.com/WW/view/en/50203404http://support.automation.siemens.com/WW/view/en/50203404http://support.automarion.siemens.com/WW/view/en/60575347http://www.siemens.com/terms_of_use -
8/10/2019 60575347_PCS7_UserRights_en.pdf
3/37
Table of content
Table of Content
1 How do user rights work?..............................................................................4
1.1 Where to manage Usernames and Passwords...................................51.2 User rights workflow for SIMATIC PCS 7 OS .....................................61.3 User rights workflow for SIMATIC PCS 7 OS combined with
Windows............................................................................................81.4 User rights workflow for PCS 7 OS Web Option...............................10
1.5
User rights applied to tags ...............................................................101.6 User rights mechanism ....................................................................11
2 Appendix.......................................................................................................13
2.1 Appendix 1 ...................................................................................... 132.2 Appendix 2 ...................................................................................... 142.3 Appendix 3 ...................................................................................... 14
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
4/37
1 How do user rights work?
1 How do user rights work?SIMATIC PCS 7 makes operation secure by means of assigning user rights tousers that log on to the system before they can monitor and operate the process.
Levels of user rights
SIMATIC PCS 7 supports the following user rights within the scope of the SIMATICPCS 7 Operator System (OS).
Table 1-1
No Function Description
1 User Administration Right to create and modify users and groups in the HMI
2 Authorization for Area Right to access and operate the process area and its relatedprocess graphics and tags
3 System Change Right to deactivate the Runtime and gain access to the
Windows desktop4 Monitoring Right to monitor the process and open other applications (which
will apply user rights within their own scope) for exampleSIMATIC BATCH Client
5 Process Controlling Right to operate the process and perform normal processadjustments, this includes starting and stopping equipment,opening and closing valves and making setpoint changes to PIDloops
6 Higher Process Controlling Right to make adjustments to process critical parameters andtuning parameters like alarm limits, PID algorithm tuning
parameters
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
5/37
1 How do user rights work?
Area and Station (computer) dependent user rights
The user rights are assigned to individual users or groups of users and can beconfigured different per process area and operator station.
Within the SIMATIC PCS 7 operator system, process graphics and Tags belong toprocess areas, the rights of a user within a process area are applicable to allgraphics and Tags that are assigned to the process area.
You can also revoke access to specific process areas their process graphics andany Tag that belongs to that process area.
Groups and Users
To make configuration easier and help avoid mistakes, the SIMATIC PCS 7 OSeditor User Administrator supports Groups and Users. Users must always bemember of a Group.
The group configuration can be inherited into a newly created User, but a User canalways have a different configuration compared to the group it is member of.
There is an option to manage Usernames and Passwords in Windows and inheritthem into the SIMATIC PCS 7 OS. We recommend that method and explain how itworks in the next paragraph.
1.1 Where to manage Usernames and Passwords
Th t d d ft f ti SIMATIC L (i l d d i SIMATIC PCS 7
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
6/37
1 How do user rights work?
1.2 User rights workflow for SIMATIC PCS 7 OS
If the Usernames and Passwords are managed in SIMATIC PCS 7 OS then youmust create each individual user on each OS Client. This is a single step activity,open the User Administrator and perform the task.
Adding a new user
There are two possibilities for adding a new user depended on whether single OSClients can be deactivated or not.
1. Without de-activating the OS ClientsTo this the new user must be added on all OS Clients and in addition in alloffline OS Client projects on the Engineering System (ES).
2. With de-activating the OS ClientsTo this the new user must be added in all OS Client projects on theEngineering System (ES) and the OS Client projects must be downloaded
again, which can only occur by de-activating the runtime OS Client project.
When Usernames and Passwords are managed in the OS client project, theworkflow is as follows:
Add/modify/delete Users in the User Administration of the OS Client project(s)on the ES
Add/modify/delete Users in the User Administration of the OS Client project(s)on the runtime Operator Systems
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
7/37
1 How do user rights work?
User AdministrationFigure 1-1
Group
User
No SIMATIC Logon
No Authorization
Process control Monitoring OnlyHigher Process control
Process areas
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
8/37
1 How do user rights work?
1.3 User rights workflow for SIMATIC PCS 7 OS combinedwith Windows
If the Usernames and Passwords are managed in Windows then you must meetthe following prerequisites:
Install SIMATIC Logon on each OS Computer, this includes the ES.
Identify an existing or configure a new User in Windows and assign that user tothe Logon_Administrator Group in Windows, this user will be allowed to makechanges to settings in SIMATIC Logon itself.
Create Groups in Windows User Administration (e.g. Operators, Engineers,Supervisors).
Create identical Groups as in Windows User Administration on the OS Serverand OS Clients User Administration on the ES and in the OS runtime. AssignUser rights to the Groups.
Check the box SIMATIC Logon in the OS User Administration in all OS; youcan only check/uncheck this box while the OS project is de-activated.
If your Computers are part of a domain, then you will manage the Usernames andPasswords in the domain. Skip the next step.
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
9/37
1 How do user rights work?
To add/modify/delete Users in Windows do the following
Open the Windows User Administration (check Windows documentation if youwant to learn how to do this)
If your Computers are part of a domain you will manage Users in thedomain User Administration.
If your Computers are part of a Workgroup then you will manage Users oneach Computer or once on the dedicated Computer for managing
Usernames and Passwords.
If you decide to manage Usernames and Passwords on each Computerthen you must repeat the steps below for each of these Computers.
Create Groups that have an exact name match with the Groups you created inthe .OS project(s).
Create Users, if desired, revoke all Group memberships that the User gets bydefault, and assign Group membership to one or more Groups that are known
both in the Windows User Administration and in the OS User Administration.
NOTE Do not create the Users in the OS projects; defining them in the Windows UserAdministration is sufficient.
SIMATIC Logon Configuration dialog
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
10/37
1 How do user rights work?
1.4 User rights workflow for PCS 7 OS Web Option
Web Client users have to authenticate themselves at the OS Web Server. Theconfiguration of the web users, respectively of SIMATIC Logon is done on the OSWeb Server, similar to the normal user configuration.
You can carry out additionally the following adjustments for all web users:
Display language on the Web Client
Different start pictures
Additional user right Web Access Monitoring only
1.5 User rights applied to tags
Once the users have been created they will be assigned the corresponding userRights every time they log in to a OS runtime on a specific Computer.
Access and ability to operate in a process area has been defined in the OS UserAdministration, if a User has access to a process area, then the scope of his/herability to operate is defined by specific rights that have been granted to that user.
The rights that have been granted must match the rights that are required forindividual actions in the Faceplate of a Tag within the process area.
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
11/37
1 How do user rights work?
1.6 User rights mechanism
For operation in a Faceplate there are three levels of User Rights that are relevant,these three levels are defined in levels. The levels are numbered 1, 2 and 3.
The default User Rights that are assigned to each slot are:
Table 1-3
Level User Right No. Name Description
1 5 Processcontrolling
Right to operate the process and perform normalprocess adjustments, this includes starting andstopping equipment, opening and closing valvesand making setpoint changes to PID loops
2 6 Higher processcontrolling
Right to make adjustments to process criticalparameters and tuning parameters like alarm limits,
PID algorithm tuning parameters3 1100 Highest process
controllingRight to operate tag settings that are exceptionallike switch a tag to or from simulation (used in APLFunction Blocks and Faceplates)
Customization of User Rights in a Faceplate
Y h th ti f t i ti f U Ri ht i F l t
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
12/37
1 How do user rights work?
User Rights adjusted from the symbol
The symbol, from which the Faceplate is being called, can be configured to definea different User Right for each of the three levels.
Each symbol has three properties: OperationLevel1_backup,OperationLevel2_backup, OperationLevel3_backup that have a User Rightassigned to them. You can assign a different User Right which will inherit into theFaceplate.
Properties of a Symbol that support modification of a User Right for the threelevels:
Figure 1-3
Ability to apply a different
User Right to each Level
Tag (Symbol) where this setting applies
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
13/37
2 Appendix
2 Appendix
2.1 Appendix 1
The picture below shows the mechanism in a graphical way for users defined in theOS project (uniquely defined for each Operator Station).
Figure 2-1
User Administration
User Group
User Right Area1 Area2 Area3
Is member of
HasApplied to
5 X X X
6 X
1100 X
X
Tag AreaIs part of
User User Rightsdefines
for
Tag Faceplate
Are tested by
Tag Property
Leveldefines As configured in
Area specific
User Rights
Together define
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
14/37
2 Appendix
2.2 Appendix 2
The picture below shows the mechanism in a graphical way for users defined inWindows.
Figure 2-2
Windows User Administration
User Group
User Right Area1 Area2 Area3
Is member of
Has a corresponding Group
Applied to
5 X X X
6 X
1100 X
X
Tag AreaIs part of
User
User Rightsdefines
for
Tag Faceplate
Are tested byTag Property
Leveldefines As configured in
Symbol
Area specific
User Rights
Together define
Group
Has
Group
Belongs to
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
15/37
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
.#StatusPermanent On 1 5 ~PG_APL_Memo.PDL _CheckBox_BLR
.#StatusPermanent Of f 1 5 ~PG_APL_Memo.PDL _CheckBox_BLR
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
ConPerMon .Ov sAH_Lim 2 6 High alarm limit f or Ov ershoot [%] ~PG_ConPerMon_Limit.PDL csoIOAnaAH
ConPerMon .CPI_AL_Lim 2 6 Low alarm limit f or CPI [%] ~PG_ConPerMon_Limit.PDL csoIOAnaAL
ConPerMon .CPI_AlmHy st 2 6 CPI alarm hy steresis [%] ~PG_ConPerMon_Limit.PDL csoIOAnaHy s
ConPerMon .Ov sWH_Lim 2 6 High warning limit f or Ov ershoot [%] ~PG_ConPerMon_Limit.PDL csoIOAnaWH
ConPerMon .CPI_WL_Lim 2 6 Low warning limit f or CPI [%] ~PG_ConPerMon_Limit.PDL csoIOAnaWL
C onPerMon . Init Ref Var I nit ialize 2 6 I nit ialize R ef Varianc e, PV_R ef and MV_R ef in s teady st at e of cont rol loop ~PG_C onPerMon_Param et er. PD L c soBt nI nit ialize
ConPerMon .MV_Ref 2 6 In/out: MV v alue in ref erence steady state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaMVRef
ConPerMon .PV_Ref 2 6 In/out: PV v alue in ref erence steady state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRef
ConPerMon .Ref Variance 2 6 Ref erence v alue f or PV_Variance in proper state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRef Var
ConPerMon .Ref StdDev #Value 2 6 Value ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRev Dev
ConPerMon .TimeWindow 2 6 length [s] of mov ing time window f or statistical ev aluations ~PG_ConPerMon_Parameter.PDL csoIOAnaTimeWindow
C onPerMon . Break Suppres s C anc el ev al. 2 6 Bre ak s uppres sion of CPI alarm s at t he end of clos ed loop s tep res po ns e ~PG _C onPerMon_S et point .PD L c soBt nC anc elEv al
ConPerMon .OnOp On 1 5 Operator input to switch back to serv ice, 1= Block on, i.e. in serv ice ~PG_ConPerMon_Standard.PDL csoBtnMode
ConPerMon .OosOp Out of serv ice 2 6 Operator input f or Out Of Serv ice, 1= Out Of Serv ice ~PG_ConPerMon_Standard.PDL csoBtnMode
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAH
CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAH
CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAH
CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAL
CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAL
CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAL
CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH
CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH
CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH
CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTH
CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTL
CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTL
CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTL
CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWH
CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWH
CountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWL
CountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWL
CountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWLCountOh .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountOh_Parameter.PDL csoBtnMaintenance
CountOh .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountOh_Parameter.PDL csoBtnMaintenance
CountOh .PresetEn Preset 2 6 Preset Enable ~PG_CountOh_Parameter.PDL csoBtnPreset
CountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetDay s
CountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetHours
CountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetMins
CountOh .UpOp Up 1 5 1 = Up Counter ~PG_CountOh_Standard.PDL csoBtnCommand
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
16/37
CountOh .DnOp Down 1 5 1 = Down Counter ~PG_CountOh_Standard.PDL csoBtnCommand
CountOh .Of f Op Of f 1 5 Counter Of f by Operator: 1 = Counter is Of f ~PG_CountOh_Standard.PDL csoBtnCommand
CountOh .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_CountOh_Standard.PDL csoBtnMode
CountOh .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_CountOh_Standard.PDL csoBtnMode
CountOh .Day s 2 6 Operating Day s ~PG_CountOh_Standard.PDL csoIOAnaDay s
CountOh .Hours 2 6 Operating Hours ~PG_CountOh_Standard.PDL csoIOAnaHours
CountOh .Minutes 2 6 Operating Minutes ~PG_CountOh_Standard.PDL csoIOAnaMins
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
CountScL .OutAH_Lim 2 6 Out Value High Alarm Limit ~PG_CountScL_Limit.PDL csoIOAnaAH
CountScL .OutAL_Lim 2 6 Out Value Low Alarm Limit ~PG_CountScL_Limit.PDL csoIOAnaAL
CountScL .OutTH_Lim 2 6 Out Value High Tolerance Limit ~PG_CountScL_Limit.PDL csoIOAnaTH
CountScL .OutTL_Lim 2 6 Out Value Low Tolerance Limit ~PG_CountScL_Limit.PDL csoIOAnaTL
CountScL .OutWH_Lim 2 6 Out Value High Warning Limit ~PG_CountScL_Limit.PDL csoIOAnaWH
CountScL .OutWL_Lim 2 6 Out Value Low Warning Limit ~PG_CountScL_Limit.PDL csoIOAnaWL
CountScL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountScL_Parameter.PDL csoBtnMaintenance
CountScL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountScL_Parameter.PDL csoBtnMaintenance
CountScL .PresetEn Preset 2 6 Preset Out ~PG_CountScL_Parameter.PDL csoBtnPreset
CountScL .PresetVal 2 6 Preset Value ~PG_CountScL_Parameter.PDL csoIOAnaPresetVal
CountScL .UpOp Up 1 5 1 = Up Counter ~PG_CountScL_Standard.PDL csoBtnCommand
CountScL .DnOp Down 1 5 1 = Down Counter ~PG_CountScL_Standard.PDL csoBtnCommand
CountScL .Of f Op Of f 1 5 Counter Of f by Operator: 1 = Counter is Of f ~PG_CountScL_Standard.PDL csoBtnCommand
CountScL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_CountScL_Standard.PDL csoBtnMode
CountScL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_CountScL_Standard.PDL csoBtnMode
CountScL .Out 1 5 Counter Value ~PG_CountScL_Standard.PDL csoIOAnaOut
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
DoseL .PV_AH_Lim 2 6 PV - Flow rate high alarm limit (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaAHCoarse
DoseL .CR_AH_Lim 2 6 Creep f low - High alarm limit ~PG_DoseL_Limit.PDL csoIOAnaAHCreep
DoseL .PV_AH2_Lim 2 6 PV - Flow rate high alarm limit (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaAHFine
DoseL .PV_AL_Lim 2 6 PV - Flow rate low alarm limit (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaALCoarse
DoseL .PV_AL2_Lim 2 6 PV - Flow rate low alarm limit (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaALFine
DoseL .PV_Hy st 2 6 PV - Flow rate hy steresis (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaHy sCoarse
DoseL .CR_Hy st 2 6 Creep f low - Hy steresis ~PG_DoseL_Limit.PDL csoIOAnaHy sCreep
DoseL .PV_Hy st2 2 6 PV - Flow rate hy steresis (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaHy sFine
DoseL .DQ_AH_Tol 2 6 Quantity high alarm tolerance band (ov erdose) ~PG_DoseL_Limit.PDL csoIOAnaOv erdos
DoseL .DQ_AL_Tol 2 6 Quantity lower alarm tolerance band (underdose) ~PG_DoseL_Limit.PDL csoIOAnaUnderdose
DoseL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_DoseL_Parameter.PDL csoBtnMaint
DoseL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_DoseL_Parameter.PDL csoBtnMaintDoseL .SimOn On 3 1100 Simulation on/of f ~PG_DoseL_Parameter.PDL csoBtnSimu
DoseL .SimOn Of f 3 1100 Simulation on/of f ~PG_DoseL_Parameter.PDL csoBtnSimu
DoseL .DribbCor On 2 6 Dribbling Correction On/Of f ~PG_DoseL_Parameter.PDL csoChkBoxAutoOn
DoseL .DribbCor Of f 2 6 Dribbling Correction On/Of f ~PG_DoseL_Parameter.PDL csoChkBoxAutoOn
DoseL .SP_TrkExt On 2 6 1: Internal SPs tracks to external SPs in external mode ~PG_DoseL_Parameter.PDL csoChkBoxSPTrk
DoseL .SP_TrkExt Of f 2 6 1: Internal SPs tracks to external SPs in external mode ~PG_DoseL_Parameter.PDL csoChkBoxSPTrk
DoseL .DribbMax 2 6 Dribble Value Maximum ~PG_DoseL_Parameter.PDL csoIOAnaDribbMax
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
17/37
DoseL .RelaxTime 2 6 Relax Time [s] ~PG_DoseL_Parameter.PDL csoIOAnaDribbTime
DoseL .DribbIn 2 6 Dribble Value ~PG_DoseL_Parameter.PDL csoIOAnaDribbValue
DoseL .P_DoseTime 2 6 Post dose time [s] ~PG_DoseL_Parameter.PDL csoIOAnaPostTime
DoseL .DCF 2 6 Dribbling Correction Factor [%] ~PG_DoseL_Parameter.PDL csoIOAnaWeightFact
DoseL .SP_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaHCoarse
DoseL .SP2_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaHFine
DoseL .SP_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaLCoarse
DoseL .SP2_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaLFine
DoseL .SimPV 1 5 PV Simulation Value, tracks when not in simulation ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaPV
DoseL .SP_Int 1 5 Flow rate internal setpoint ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaSPCoarse
DoseL .SP2_Int 1 5 Flow rate internal setpoint (f ine dose) ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaSPFine
DoseL .DQ2_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaHFine
DoseL .DQ_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaHTotal
DoseL .DQ2_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaLFine
DoseL .DQ_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaLTotal
DoseL .DQ1_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPCoarse
DoseL .DQ2_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPFine
DoseL .DQ2_Int 1 5 Quantity setpoint f actor internal (f ine dose) ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPFineFactor
DoseL .DQ_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPTotal
DoseL .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand
DoseL .ContMan Continue 1 5 1=Continue: Continue Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand
DoseL .PauseMan Pause 1 5 1=Pause: Pause Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand
DoseL .CancelMan Cancel 1 5 1=Cancel: Cancel Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommand
DoseL .AutModOp Automatic 1 5 1=Auto mode: auto mode by operator ~PG_DoseL_Standard.PDL csoBtnModeDoseL .ManModOp Manual 1 5 1=Manual mode: manual mode by operator ~PG_DoseL_Standard.PDL csoBtnMode
DoseL .LocalOp Local 1 5 1=Local Mode: Local operation by operator ~PG_DoseL_Standard.PDL csoBtnMode
DoseL .OosOp Out of serv ice 2 6 1=Oos mode: Oos mode by operator ~PG_DoseL_Standard.PDL csoBtnMode
DoseL .RstOp Reset 1 5 Operator reset signal ~PG_DoseL_Standard.PDL csoBtnReset
DoseL .RstDQ_Op Reset 1 5 Operator signal to reset dosed quantity ~PG_DoseL_Standard.PDL csoBtnResetQuantity
DoseL .U_AckOp Acknowledge 1 5 Underdose acknowledge operator ~PG_DoseL_Standard.PDL csoBtnResetUnderdose
DoseL .SP_ExtOp External 1 5 Operator Input to Select External Setpoint ~PG_DoseL_Standard.PDL csoBtnSPMode
DoseL .SP_IntOp Internal 1 5 Operator Input to Select Internal Setpoint ~PG_DoseL_Standard.PDL csoBtnSPMode
DoseL .SimDQ 1 5 Dosing quantity simulation v alue, tracks when not in simulation ~PG_DoseL_Standard.PDL csoIOAnaPV
DoseL .DQ_Int 1 5 Quantity setpoint internal ~PG_DoseL_Standard.PDL csoIOAnaSP
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
FmCont .PV_AH_Lim 2 6 PV alarm high limit ~PG_FmCont_Limit.PDL csoIOAnaAH
FmCont .PV_AL_Lim 2 6 PV alarm low limit ~PG_FmCont_Limit.PDL csoIOAnaAL
FmCont .ER_AH_Lim 2 6 ER alarm high limit ~PG_FmCont_Limit.PDL csoIOAnaErrHFmCont .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_FmCont_Limit.PDL csoIOAnaErrHy s
FmCont .ER_AL_Lim 2 6 ER alarm low limit ~PG_FmCont_Limit.PDL csoIOAnaErrL
FmCont .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_FmCont_Limit.PDL csoIOAnaHy s
FmCont .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_FmCont_Limit.PDL csoIOAnaMVH
FmCont .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_FmCont_Limit.PDL csoIOAnaMVL
FmCont .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_FmCont_Limit.PDL csoIOAnaRbkH
FmCont .RbkHy st 2 6 Rbk - Hy steresis ~PG_FmCont_Limit.PDL csoIOAnaRbkHy s
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
18/37
FmCont .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_FmCont_Limit.PDL csoIOAnaRbkL
FmCont .SP_InHiLim 2 6 High limit of internal setpoint ~PG_FmCont_Limit.PDL csoIOAnaSPH
FmCont .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_FmCont_Limit.PDL csoIOAnaSPL
FmCont .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_FmCont_Limit.PDL csoIOAnaTH
FmCont .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_FmCont_Limit.PDL csoIOAnaTL
FmCont .PV_WH_Lim 2 6 PV warning high limit ~PG_FmCont_Limit.PDL csoIOAnaWH
FmCont .PV_WL_Lim 2 6 PV warning low limit ~PG_FmCont_Limit.PDL csoIOAnaWL
FmCont .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_FmCont_Parameter.PDL csoBtnMaint
FmCont .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_FmCont_Parameter.PDL csoBtnMaint
FmCont .SimOn On 3 1100 1 = Simulation activ ated ~PG_FmCont_Parameter.PDL csoBtnSimu
FmCont .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_FmCont_Parameter.PDL csoBtnSimu
FmCont .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmCont_Parameter.PDL csoChkBoxPVTrk
FmCont .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmCont_Parameter.PDL csoChkBoxPVTrk
FmCont .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmCont_Parameter.PDL csoChkBoxSPTrk
FmCont .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmCont_Parameter.PDL csoChkBoxSPTrk
FmCont .BreakTime 2 6 Minimum Break Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaBreakT
FmCont .DeadBand 2 6 Width of deadband ~PG_FmCont_Parameter.PDL csoIOAnaDeadB
FmCont .Gain#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaGain
FmCont .Dif f Gain#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaGainD
FmCont .MotorTime 2 6 Motor Actuating Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaMotorT
FmCont .PulseTime 2 6 Minimum Pulse Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaPulseT
FmCont .TD#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaTD
FmCont .TI#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaTI
FmCont .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmCont_Ramp.PDL csoBtnRampFmCont .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmCont_Ramp.PDL csoBtnRamp
F mC ont . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mC ont _R am p. PD L c soBt nR am pMode
F mC ont . SP_R mpModTim e Gradient 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mC ont _R am p. PD L c soBt nR am pMode
FmCont .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmCont_Ramp.PDL csoChkBoxGrd
FmCont .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmCont_Ramp.PDL csoChkBoxGrd
FmCont .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_FmCont_Ramp.PDL csoIOAnaDuration
FmCont .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_FmCont_Ramp.PDL csoIOAnaGrdDown
FmCont .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_FmCont_Ramp.PDL csoIOAnaGrdUp
FmCont .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_FmCont_Ramp.PDL csoIOAnaTargetSP
FmCont .OpenOp Open 1 5 Manual Signal Open by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignals
FmCont .CloseOp Close 1 5 Manual Signal Close by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignals
FmCont .StopOp Stop 1 5 Manual Signal Stop by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignals
FmCont .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_FmCont_Standard.PDL csoBtnMode
FmCont .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_FmCont_Standard.PDL csoBtnMode
FmCont .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_FmCont_Standard.PDL csoBtnModeFmCont .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_FmCont_Standard.PDL csoBtnMode
FmCont .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_FmCont_Standard.PDL csoBtnSPMode
FmCont .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_FmCont_Standard.PDL csoBtnSPMode
FmCont .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_FmCont_Standard.PDL csoIOAnaMV
FmCont .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_FmCont_Standard.PDL csoIOAnaPV
FmCont .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_FmCont_Standard.PDL csoIOAnaRbk
FmCont .SP_Int 1 5 Internal setpoint f or operation ~PG_FmCont_Standard.PDL csoIOAnaSP
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
19/37
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
FmTemp .PV_AH_Lim 2 6 PV alarm high limit ~PG_FmTemp_Limit.PDL csoIOAnaAH
FmTemp .PV_AL_Lim 2 6 PV alarm low limit ~PG_FmTemp_Limit.PDL csoIOAnaAL
FmTemp .ER_AH_Lim 2 6 ER alarm high limit ~PG_FmTemp_Limit.PDL csoIOAnaErrH
FmTemp .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_FmTemp_Limit.PDL csoIOAnaErrHy s
FmTemp .ER_AL_Lim 2 6 ER alarm low limit ~PG_FmTemp_Limit.PDL csoIOAnaErrL
FmTemp .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_FmTemp_Limit.PDL csoIOAnaHy s
FmTemp .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_FmTemp_Limit.PDL csoIOAnaMVH
FmTemp .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_FmTemp_Limit.PDL csoIOAnaMVL
FmTemp .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_FmTemp_Limit.PDL csoIOAnaRbkH
FmTemp .RbkHy st 2 6 Rbk - Hy steresis ~PG_FmTemp_Limit.PDL csoIOAnaRbkHy s
FmTemp .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_FmTemp_Limit.PDL csoIOAnaRbkL
FmTemp .SP_InHiLim 2 6 High limit of internal setpoint ~PG_FmTemp_Limit.PDL csoIOAnaSPH
FmTemp .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_FmTemp_Limit.PDL csoIOAnaSPL
FmTemp .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_FmTemp_Limit.PDL csoIOAnaTH
FmTemp .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_FmTemp_Limit.PDL csoIOAnaTL
FmTemp .PV_WH_Lim 2 6 PV warning high limit ~PG_FmTemp_Limit.PDL csoIOAnaWH
FmTemp .PV_WL_Lim 2 6 PV warning low limit ~PG_FmTemp_Limit.PDL csoIOAnaWL
FmTemp .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_FmTemp_Parameter.PDL csoBtnMaint
FmTemp .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_FmTemp_Parameter.PDL csoBtnMaint
FmTemp .SimOn On 3 1100 1 = Simulation activ ated ~PG_FmTemp_Parameter.PDL csoBtnSimu
FmTemp .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_FmTemp_Parameter.PDL csoBtnSimu
FmTemp .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmTemp_Parameter.PDL csoChkBoxPVTrkFmTemp .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmTemp_Parameter.PDL csoChkBoxPVTrk
FmTemp .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmTemp_Parameter.PDL csoChkBoxSPTrk
FmTemp .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmTemp_Parameter.PDL csoChkBoxSPTrk
FmTemp .BreakTime 2 6 Minimum Break Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaBreakT
FmTemp .DeadBand 2 6 Width of deadband ~PG_FmTemp_Parameter.PDL csoIOAnaDeadB
FmTemp .Gain#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaGain
FmTemp .Dif f Gain#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaGainD
FmTemp .MotorTime 2 6 Motor Actuating Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaMotorT
FmTemp .PulseTime 2 6 Minimum Pulse Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaPulseT
FmTemp .TD#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaTD
FmTemp .TI#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaTI
FmTemp .ConZone 2 6 Control zone ~PG_FmTemp_Parameter.PDL csoIOAnaZoneC
FmTemp .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoBtnRamp
FmTemp .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoBtnRamp
F mTem p . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mTem p_R am p. PD L c soBt nR am pModeF mTem p . SP_R mpModTim e Gradient 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_F mTem p_R am p. PD L c soBt nR am pMode
FmTemp .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoChkBoxGrd
FmTemp .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoChkBoxGrd
FmTemp .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoIOAnaDuration
FmTemp .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_FmTemp_Ramp.PDL csoIOAnaGrdDown
FmTemp .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_FmTemp_Ramp.PDL csoIOAnaGrdUp
FmTemp .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_FmTemp_Ramp.PDL csoIOAnaTargetSP
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
20/37
FmTemp .OpenOp Open 1 5 Manual Signal Open by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignals
FmTemp .CloseOp Close 1 5 Manual Signal Close by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignals
FmTemp .StopOp Stop 1 5 Manual Signal Stop by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignals
FmTemp .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_FmTemp_Standard.PDL csoBtnMode
FmTemp .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_FmTemp_Standard.PDL csoBtnMode
FmTemp .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_FmTemp_Standard.PDL csoBtnMode
FmTemp .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_FmTemp_Standard.PDL csoBtnMode
FmTemp .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_FmTemp_Standard.PDL csoBtnSPMode
FmTemp .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_FmTemp_Standard.PDL csoBtnSPMode
FmTemp .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_FmTemp_Standard.PDL csoIOAnaMV
FmTemp .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_FmTemp_Standard.PDL csoIOAnaPV
FmTemp .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_FmTemp_Standard.PDL csoIOAnaRbk
FmTemp .SP_Int 1 5 Internal setpoint f or operation ~PG_FmTemp_Standard.PDL csoIOAnaSP
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
GainSched .Gain1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain1
GainSched .Gain2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain2
GainSched .Gain3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain3
GainSched .GainOp#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGainOp
GainSched .TD_Op#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD_Op
GainSched .TD1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD1
GainSched .TD2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD2
GainSched .TD3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD3
GainSched .TI_Op#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI_OpGainSched .TI1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI1
GainSched .TI2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI2
GainSched .TI3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI3
GainSched .X1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX1
GainSched .X2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX2
GainSched .X3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX3
GainSched .ManParOn#Value Automatic 1 5 Value ~PG_GainSched_Standard.PDL csoBtnMode
GainSched .ManParOn#Value Manual 1 5 Value ~PG_GainSched_Standard.PDL csoBtnMode
GainSched .GainOp#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaGain
GainSched .TD_Op#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaTD
GainSched .TI_Op#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaTI
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
Intlk02 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk02_Standard.PDL csoBtnBy p1
Intlk02 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk02_Standard.PDL csoBtnBy p1Intlk02 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk02_Standard.PDL csoBtnBy p2
Intlk02 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk02_Standard.PDL csoBtnBy p2
Intlk02 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk02_Standard.PDL csoBtnReset
Intlk02 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk02_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
Intlk04 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk04_Standard.PDL csoBtnBy p1
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
21/37
Intlk04 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk04_Standard.PDL csoBtnBy p1
Intlk04 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk04_Standard.PDL csoBtnBy p2
Intlk04 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk04_Standard.PDL csoBtnBy p2
Intlk04 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk04_Standard.PDL csoBtnBy p3
Intlk04 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk04_Standard.PDL csoBtnBy p3
Intlk04 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk04_Standard.PDL csoBtnBy p4
Intlk04 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk04_Standard.PDL csoBtnBy p4
Intlk04 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk04_Standard.PDL csoBtnReset
Intlk04 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk04_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
Intlk08 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk08_Standard.PDL csoBtnBy p1
Intlk08 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk08_Standard.PDL csoBtnBy p1
Intlk08 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk08_Standard.PDL csoBtnBy p2
Intlk08 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk08_Standard.PDL csoBtnBy p2
Intlk08 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk08_Standard.PDL csoBtnBy p3
Intlk08 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk08_Standard.PDL csoBtnBy p3
Intlk08 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk08_Standard.PDL csoBtnBy p4
Intlk08 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk08_Standard.PDL csoBtnBy p4
Intlk08 .By pIn05 Set 2 6 By pass In05 ~PG_Intlk08_Standard.PDL csoBtnBy p5
Intlk08 .By pIn05 Reset 2 6 By pass In05 ~PG_Intlk08_Standard.PDL csoBtnBy p5
Intlk08 .By pIn06 Set 2 6 By pass In06 ~PG_Intlk08_Standard.PDL csoBtnBy p6
Intlk08 .By pIn06 Reset 2 6 By pass In06 ~PG_Intlk08_Standard.PDL csoBtnBy p6
Intlk08 .By pIn07 Set 2 6 By pass In07 ~PG_Intlk08_Standard.PDL csoBtnBy p7Intlk08 .By pIn07 Reset 2 6 By pass In07 ~PG_Intlk08_Standard.PDL csoBtnBy p7
Intlk08 .By pIn08 Set 2 6 By pass In08 ~PG_Intlk08_Standard.PDL csoBtnBy p8
Intlk08 .By pIn08 Reset 2 6 By pass In08 ~PG_Intlk08_Standard.PDL csoBtnBy p8
Intlk08 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk08_Standard.PDL csoBtnReset
Intlk08 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk08_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
Intlk16 .By pIn09 Set 2 6 By pass In09 ~PG_Intlk16_Screen2.PDL csoBtnBy p1
Intlk16 .By pIn09 Reset 2 6 By pass In09 ~PG_Intlk16_Screen2.PDL csoBtnBy p1
Intlk16 .By pIn10 Set 2 6 By pass In10 ~PG_Intlk16_Screen2.PDL csoBtnBy p2
Intlk16 .By pIn10 Reset 2 6 By pass In10 ~PG_Intlk16_Screen2.PDL csoBtnBy p2
Intlk16 .By pIn11 Set 2 6 By pass In11 ~PG_Intlk16_Screen2.PDL csoBtnBy p3
Intlk16 .By pIn11 Reset 2 6 By pass In11 ~PG_Intlk16_Screen2.PDL csoBtnBy p3
Intlk16 .By pIn12 Set 2 6 By pass In12 ~PG_Intlk16_Screen2.PDL csoBtnBy p4
Intlk16 .By pIn12 Reset 2 6 By pass In12 ~PG_Intlk16_Screen2.PDL csoBtnBy p4Intlk16 .By pIn13 Set 2 6 By pass In13 ~PG_Intlk16_Screen2.PDL csoBtnBy p5
Intlk16 .By pIn13 Reset 2 6 By pass In13 ~PG_Intlk16_Screen2.PDL csoBtnBy p5
Intlk16 .By pIn14 Set 2 6 By pass In14 ~PG_Intlk16_Screen2.PDL csoBtnBy p6
Intlk16 .By pIn14 Reset 2 6 By pass In14 ~PG_Intlk16_Screen2.PDL csoBtnBy p6
Intlk16 .By pIn15 Set 2 6 By pass In15 ~PG_Intlk16_Screen2.PDL csoBtnBy p7
Intlk16 .By pIn15 Reset 2 6 By pass In15 ~PG_Intlk16_Screen2.PDL csoBtnBy p7
Intlk16 .By pIn16 Set 2 6 By pass In16 ~PG_Intlk16_Screen2.PDL csoBtnBy p8
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
22/37
Intlk16 .By pIn16 Reset 2 6 By pass In16 ~PG_Intlk16_Screen2.PDL csoBtnBy p8
Intlk16 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk16_Screen2.PDL csoBtnReset
Intlk16 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk16_Screen2.PDL csoBtnReset
Intlk16 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk16_Standard.PDL csoBtnBy p1
Intlk16 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk16_Standard.PDL csoBtnBy p1
Intlk16 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk16_Standard.PDL csoBtnBy p2
Intlk16 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk16_Standard.PDL csoBtnBy p2
Intlk16 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk16_Standard.PDL csoBtnBy p3
Intlk16 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk16_Standard.PDL csoBtnBy p3
Intlk16 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk16_Standard.PDL csoBtnBy p4
Intlk16 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk16_Standard.PDL csoBtnBy p4
Intlk16 .By pIn05 Set 2 6 By pass In05 ~PG_Intlk16_Standard.PDL csoBtnBy p5
Intlk16 .By pIn05 Reset 2 6 By pass In05 ~PG_Intlk16_Standard.PDL csoBtnBy p5
Intlk16 .By pIn06 Set 2 6 By pass In06 ~PG_Intlk16_Standard.PDL csoBtnBy p6
Intlk16 .By pIn06 Reset 2 6 By pass In06 ~PG_Intlk16_Standard.PDL csoBtnBy p6
Intlk16 .By pIn07 Set 2 6 By pass In07 ~PG_Intlk16_Standard.PDL csoBtnBy p7
Intlk16 .By pIn07 Reset 2 6 By pass In07 ~PG_Intlk16_Standard.PDL csoBtnBy p7
Intlk16 .By pIn08 Set 2 6 By pass In08 ~PG_Intlk16_Standard.PDL csoBtnBy p8
Intlk16 .By pIn08 Reset 2 6 By pass In08 ~PG_Intlk16_Standard.PDL csoBtnBy p8
Intlk16 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk16_Standard.PDL csoBtnReset
Intlk16 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk16_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
ModPreCon .SP1DeadBand 2 6 Radius (deadband) f or range control of CV1 ~PG_ModPreCon_C hannel1.PDL csoIOAnaDeadBModPreCon .MV1RaLim 2 6 Manipulated v ariable 1 rate limit per sample ~PG_ModPreCon_Channel1.PDL csoIOAnaGrad
ModPreCon .MV1HiLim 2 6 Manipulated v ariable 1 high limit ~PG_ModPreCon_Channel1.PDL csoIOAnaMVH
ModPreCon .MV1LoLim 2 6 Manipulated v ariable 1 low limit ~PG_ModPreCon_Channel1.PDL csoIOAnaMVL
ModPreCon .PreFilt1 2 6 Setpoint 1 pref ilter settling time [s] ~PG_ModPreCon_Channel1.PDL csoIOAnaPref il
ModPreCon .SP1HiLim 2 6 High limit f or operator setpoint 1 ~PG_ModPreCon_Channel1.PDL csoIOAnaSPH
ModPreCon .SP1LoLim 2 6 Low limit f or operator setpoint 1 ~PG_ModPreCon_Channel1.PDL csoIOAnaSPL
ModPreCon .SP2DeadBand 2 6 Radius (deadband) f or range control of CV2 ~PG_ModPreCon_C hannel2.PDL csoIOAnaDeadB
ModPreCon .MV2RaLim 2 6 Manipulated v ariable 2 rate limit per sample ~PG_ModPreCon_Channel2.PDL csoIOAnaGrad
ModPreCon .MV2HiLim 2 6 Manipulated v ariable 2 high limit ~PG_ModPreCon_Channel2.PDL csoIOAnaMVH
ModPreCon .MV2LoLim 2 6 Manipulated v ariable 2 low limit ~PG_ModPreCon_Channel2.PDL csoIOAnaMVL
ModPreCon .PreFilt2 2 6 Setpoint 2 pref ilter settling time [s] ~PG_ModPreCon_Channel2.PDL csoIOAnaPref il
ModPreCon .SP2HiLim 2 6 High limit f or operator setpoint 2 ~PG_ModPreCon_Channel2.PDL csoIOAnaSPH
ModPreCon .SP2LoLim 2 6 Low limit f or operator setpoint 2 ~PG_ModPreCon_Channel2.PDL csoIOAnaSPL
ModPreCon .SP3DeadBand 2 6 Radius (deadband) f or range control of CV3 ~PG_ModPreCon_C hannel3.PDL csoIOAnaDeadB
ModPreCon .MV3RaLim 2 6 Manipulated v ariable 3 rate limit per sample ~PG_ModPreCon_Channel3.PDL csoIOAnaGradModPreCon .MV3HiLim 2 6 Manipulated v ariable 3 high limit ~PG_ModPreCon_Channel3.PDL csoIOAnaMVH
ModPreCon .MV3LoLim 2 6 Manipulated v ariable 3 low limit ~PG_ModPreCon_Channel3.PDL csoIOAnaMVL
ModPreCon .PreFilt3 2 6 Setpoint 3 pref ilter settling time [s] ~PG_ModPreCon_Channel3.PDL csoIOAnaPref il
ModPreCon .SP3HiLim 2 6 High limit f or operator setpoint 3 ~PG_ModPreCon_Channel3.PDL csoIOAnaSPH
ModPreCon .SP3LoLim 2 6 Low limit f or operator setpoint 3 ~PG_ModPreCon_Channel3.PDL csoIOAnaSPL
ModPreCon .SP4DeadBand 2 6 Radius (deadband) f or range control of CV4 ~PG_ModPreCon_C hannel4.PDL csoIOAnaDeadB
ModPreCon .MV4RaLim 2 6 Manipulated v ariable 4 rate limit per sample ~PG_ModPreCon_Channel4.PDL csoIOAnaGrad
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
23/37
ModPreCon .MV4HiLim 2 6 Manipulated v ariable 4 high limit ~PG_ModPreCon_Channel4.PDL csoIOAnaMVH
ModPreCon .MV4LoLim 2 6 Manipulated v ariable 4 low limit ~PG_ModPreCon_Channel4.PDL csoIOAnaMVL
ModPreCon .PreFilt4 2 6 Setpoint 4 pref ilter settling time [s] ~PG_ModPreCon_Channel4.PDL csoIOAnaPref il
ModPreCon .SP4HiLim 2 6 High limit f or operator setpoint 4 ~PG_ModPreCon_Channel4.PDL csoIOAnaSPH
ModPreCon .SP4LoLim 2 6 Low limit f or operator setpoint 4 ~PG_ModPreCon_Channel4.PDL csoIOAnaSPL
ModPreC on . MS_R elOp Y es 3 1100 Op erat or input f or MS R eleas e, 1= MS releas e requirem ent ~PG _ModPreC on_P aram et er. PD L c soBt nMaint
ModPreC on . MS_R elOp N o 3 1100 Op erat or input f or MS R eleas e, 1= MS releas e requirem ent ~PG _ModPreC on_P aram et er. PD L c soBt nMaint
ModPreCon .SimOn On 3 1100 Simulation On/Of f ~PG_ModPreCon_Parameter.PDL csoBtnSimu
ModPreCon .SimOn Of f 3 1100 Simulation On/Of f ~PG_ModPreCon_Parameter.PDL csoBtnSimu
ModPreCon .DV_On On 2 6 1 = Activ ate disturbance f eedf orward of DV1 ~PG_ModPreCon_Parameter.PDL csoChkBoxDisturb
ModPreCon .DV_On Of f 2 6 1 = Activ ate disturbance f eedf orward of DV1 ~PG_ModPreCon_Parameter.PDL csoChkBoxDisturb
ModPreCon .SP_TrkCV On 2 6 SPs track CVs in manual mode and in tracking mode ~PG_ModPreCon_Parameter.PDL csoChkBoxPVTrk
ModPreCon .SP_TrkCV Of f 2 6 SPs track CVs in manual mode and in tracking mode ~PG_ModPreCon_Parameter.PDL csoChkBoxPVTrk
ModPreCon .DV1#Value 2 6 Value ~PG_ModPreCon_Parameter.PDL csoIOAnaDisturb
ModPreCon . AutModOp Automatic 1 5 Operator input f or automatic mode, 1= Automatic ~PG_ModPreCon_Standard.PDL csoBtnMode
ModPreCon .ManModOp Manual 1 5 Operator input f or manual mode, 1= Manual ~PG_ModPreCon_Standard.PDL csoBtnMode
ModPreCon .OosOp Out of serv ice 2 6 Operator input f or Out Of Serv ice, 1= Out Of Serv ice ~PG_ModPreCon_Standard.PDL csoBtnMode
ModPreCon . SimCV1 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV1
ModPreCon . SimCV2 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV2
ModPreCon . SimCV3 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV3
ModPreCon . SimCV4 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV4
ModPreCon .MV1Man 1 5 Manual setting of manipulated v ariable MV1 ~PG_ModPreCon_Standard.PDL csoIOAnaMV1
ModPreCon .MV2Man 1 5 Manual setting of manipulated v ariable MV2 ~PG_ModPreCon_Standard.PDL csoIOAnaMV2
ModPreCon .MV3Man 1 5 Manual setting of manipulated v ariable MV3 ~PG_ModPreCon_Standard.PDL csoIOAnaMV3ModPreCon .MV4Man 1 5 Manual setting of manipulated v ariable MV4 ~PG_ModPreCon_Standard.PDL csoIOAnaMV4
ModPreCon .SP1#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP1
ModPreCon .SP2#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP2
ModPreCon .SP3#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP3
ModPreCon .SP4#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP4
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
MonAnL .PV_AH_Lim 2 6 PV - High Alarm Limit ~PG_MonAnL_Limit.PDL csoIOAnaAH
MonAnL .PV_AL_Lim 2 6 PV - Low Alarm Limit ~PG_MonAnL_Limit.PDL csoIOAnaAL
MonAnL .PV_Hy st 2 6 PV - Alarm Hy steresis ~PG_MonAnL_Limit.PDL csoIOAnaHy s
MonAnL .PV_TH_Lim 2 6 PV - High Tolerance Limit ~PG_MonAnL_Limit.PDL csoIOAnaTH
MonAnL .PV_TL_Lim 2 6 PV - Low Tolerance Limit ~PG_MonAnL_Limit.PDL csoIOAnaTL
MonAnL .PV_WH_Lim 2 6 PV - High Warning Limit ~PG_MonAnL_Limit.PDL csoIOAnaWH
MonAnL .PV_WL_Lim 2 6 PV - Low Warning Limit ~PG_MonAnL_Limit.PDL csoIOAnaWL
MonAnL .GradLLim 2 6 Low alarm limit f or positiv e and negativ e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGAMonAnL .GradHUpLim 2 6 High alarm limit f or positiv e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGH
MonAnL .GradHDnLim 2 6 High alarm limit f or negativ e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGL
MonAnL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnL_Parameter.PDL csoBtnMaintenance
MonAnL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnL_Parameter.PDL csoBtnMaintenance
MonAnL .SimOn On 3 1100 Simulation On/Of f ~PG_MonAnL_Parameter.PDL csoBtnSim
MonAnL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonAnL_Parameter.PDL csoBtnSim
MonAnL .DeadBand 2 6 Dead band width ~PG_MonAnL_Parameter.PDL csoIOAnaDeadB
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
24/37
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
25/37
MonDiL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonDiL_Standard.PDL csoBtnMode
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
MonDiS .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiS_Parameter.PDL csoBtnMaintenance
MonDiS .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiS_Parameter.PDL csoBtnMaintenance
MonDiS .SimOn On 3 1100 Simulation On/Of f ~PG_MonDiS_Parameter.PDL csoBtnSim
MonDiS .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonDiS_Parameter.PDL csoBtnSim
MonDiS .Out_DC 2 6 Out Delay Time Coming [s] ~PG_MonDiS_Parameter.PDL csoIOAnaControlMon
MonDiS .SimIn Activ e 1 5 Simulation Value ~PG_MonDiS_Standard.PDL csoBtnCommand
MonDiS .SimIn Inactiv e 1 5 Simulation Value ~PG_MonDiS_Standard.PDL csoBtnCommand
MonDiS .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_MonDiS_Standard.PDL csoBtnMode
MonDiS .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonDiS_Standard.PDL csoBtnMode
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
MotL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotL_Limit.PDL csoIOAnaAH
MotL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotL_Limit.PDL csoIOAnaAL
MotL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotL_Limit.PDL csoIOAnaAV
MotL .AV_Hy st 2 6 AV - Hy steresis ~PG_MotL_Limit.PDL csoIOAnaHy s
MotL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotL_Limit.PDL csoIOAnaTH
MotL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotL_Limit.PDL csoIOAnaTL
MotL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotL_Limit.PDL csoIOAnaWH
MotL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotL_Limit.PDL csoIOAnaWL
MotL .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotL_Parameter.PDL chkMonitor
MotL .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotL_Parameter.PDL chkMonitor MotL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotL_Parameter.PDL csoBtnMaintenance
MotL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotL_Parameter.PDL csoBtnMaintenance
MotL .SimOn On 3 1100 Simulation On/Of f ~PG_MotL_Parameter.PDL csoBtnSim
MotL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotL_Parameter.PDL csoBtnSim
MotL .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotL_Parameter.PDL csoIOAnaDy nMonTime
MotL .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotL_Parameter.PDL csoIOAnaStaMonTime
MotL .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_MotL_Standard.PDL csoBtnCommand
MotL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotL_Standard.PDL csoBtnCommand
MotL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotL_Standard.PDL csoBtnCommand
MotL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotL_Standard.PDL csoBtnMode
MotL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotL_Standard.PDL csoBtnMode
MotL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotL_Standard.PDL csoBtnMode
MotL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotL_Standard.PDL csoBtnMode
MotL .RstOp Reset 1 5 Operator Reset Signal ~PG_MotL_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
MotRev L .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotRev L_Limit.PDL csoIOAnaAH
MotRev L .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotRev L_Limit.PDL csoIOAnaAL
MotRev L .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotRev L_Limit.PDL csoIOAnaAV
MotRev L .AV_Hy st 2 6 AV - Hy steresis ~PG_MotRev L_Limit.PDL csoIOAnaHy s
MotRev L .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotRev L_Limit.PDL csoIOAnaTH
MotRev L .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotRev L_Limit.PDL csoIOAnaTL
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
26/37
MotRev L .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotRev L_Limit.PDL csoIOAnaWH
MotRev L .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotRev L_Limit.PDL csoIOAnaWL
MotRev L .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotRev L_Parameter.PDL chkMonitor
MotRev L .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotRev L_Parameter.PDL chkMonitor
MotRev L .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotRev L_Parameter.PDL csoBtnMaintenance
MotRev L .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotRev L_Parameter.PDL csoBtnMaintenance
MotRev L .SimOn On 3 1100 Simulation On/Of f ~PG_MotRev L_Parameter.PDL csoBtnSim
MotRev L .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotRev L_Parameter.PDL csoBtnSim
MotRev L .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotRev L_Parameter.PDL csoIOAnaDy nMonTimeMotRev L .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotRev L_Parameter.PDL csoIOAnaStaMonTime
MotRev L .FwdMan Forward 1 5 1=Start: Forward Start Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommand
MotRev L .Rev Man Rev erse 1 5 1=Start: Rev erse Start Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommand
MotRev L .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommand
MotRev L .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotRev L_Standard.PDL csoBtnCommand
MotRev L .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnMode
MotRev L .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnMode
MotRev L .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotRev L_Standard.PDL csoBtnMode
MotRev L .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnMode
MotRev L .RstOp Reset 1 5 Operator Reset Signal ~PG_MotRev L_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
MotS .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotS_Parameter.PDL chkMonitor
MotS .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotS_Parameter.PDL chkMonitor
MotS .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotS_Parameter.PDL csoBtnMaintenanceMotS .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotS_Parameter.PDL csoBtnMaintenance
MotS .SimOn On 3 1100 Simulation On/Of f ~PG_MotS_Parameter.PDL csoBtnSim
MotS .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotS_Parameter.PDL csoBtnSim
MotS .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotS_Parameter.PDL csoIOAnaDy nMonTime
MotS .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_MotS_Standard.PDL csoBtnCommand
MotS .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotS_Standard.PDL csoBtnCommand
MotS .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotS_Standard.PDL csoBtnMode
MotS .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotS_Standard.PDL csoBtnMode
MotS .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotS_Standard.PDL csoBtnMode
MotS .RstOp Reset 1 5 Operator Reset Signal ~PG_MotS_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
MotSpdCL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaAH
MotSpdCL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaAL
MotSpdCL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotSpdCL_Limit.PDL csoIOAnaAVMotSpdCL .AV_Hy st 2 6 AV - Hy steresis ~PG_MotSpdCL_Limit.PDL csoIOAnaHy s
MotSpdCL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTH
MotSpdCL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTL
MotSpdCL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWH
MotSpdCL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWL
MotSpdCL .ER_AH_Lim 2 6 ER alarm high limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaAH
MotSpdCL .ER_AL_Lim 2 6 ER alarm low limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaAL
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
27/37
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
28/37
MotSpdCL .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotSpdCL_Parameter.PDL chkMonitor
MotSpdCL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenance
MotSpdCL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenance
MotSpdCL . SimOn On 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSim
MotSpdCL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSim
MotSpdCL .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaDy nMonTime
MotSpdCL .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaStaMonTime
MotSpdCL .Spd1Man Slow 1 5 ~PG_MotSpdCL_Standard.PDL csoBtnCommand
MotSpdCL .Spd2Man Fast 1 5 ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotSpdCL_Standard.PDL csoBtnCommand
MotSpdCL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotSpdCL_Standard.PDL csoBtnCommand
MotSpdCL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode
MotSpdCL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode
MotSpdCL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode
MotSpdCL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnMode
MotSpdCL . RstOp Reset 1 5 Operator Reset Signal ~PG_MotSpdCL_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
OpAnL .SP_TrkExt On 2 6 1: SP_Int tracks SP_Ext in External ~PG_OpAnL_Parameter.PDL chkBumpless
OpAnL .SP_TrkExt Of f 2 6 1: SP_Int tracks SP_Ext in External ~PG_OpAnL_Parameter.PDL chkBumpless
OpAnL .SP_RateOn On 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_OpAnL_Ramp.PDL chkRampOn
OpAnL .SP_RateOn Of f 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_OpAnL_Ramp.PDL chkRampOn
OpAnL . SP_R mpModTim e D urat ion 1 5 1: S P ram ped ov er SP_R mpTim e, 0 : SP ram ped by r at es SP_U pR aLi m, SP_D nR aLim ~PG_OpAnL_R am p. PD L c soBt nR am pMode
OpAnL . SP_R mpModTim e Gradient 1 5 1: S P ram ped ov er SP_R mpTim e, 0 : SP ram ped by r at es SP_U pR aLi m, SP_D nR aLim ~PG_OpAnL_R am p. PD L c soBt nR am pModeOpAnL .SP_RmpOn Activ e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_OpAnL_Ramp.PDL csoBtnRampOn
OpAnL .SP_RmpOn Inactiv e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_OpAnL_Ramp.PDL csoBtnRampOn
OpAnL .SP_RmpTime 1 5 Setpoint ramp time [s] ~PG_OpAnL_Ramp.PDL csoIOAnaDuration
OpAnL .SP_DnRaLim 1 5 Downward rate limit f or setpoint changes or ramping ~PG_OpAnL_Ramp.PDL csoIOAnaRampDn
OpAnL .SP_UpRaLim 1 5 Upward rate limit f or setpoint changes or ramping ~PG_OpAnL_Ramp.PDL csoIOAnaRampUp
OpAnL .SP_RmpTarget 1 5 Setpoint ramp target ~PG_OpAnL_Ramp.PDL csoIOAnaTargetSP
OpAnL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpAnL_Standard.PDL csoBtnMode
OpAnL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpAnL_Standard.PDL csoBtnMode
OpAnL .SP_ExtOp External 1 5 Operator input to select external setpoint ~PG_OpAnL_Standard.PDL csoBtnSetpoint
OpAnL .SP_IntOp Internal 1 5 Operator input to select internal setpoint ~PG_OpAnL_Standard.PDL csoBtnSetpoint
OpAnL .PV_In#Value 1 5 Value ~PG_OpAnL_Standard.PDL csoIOAnaPV
OpAnL .SP_Int 1 5 Internal Analog setpoint ~PG_OpAnL_Standard.PDL csoIOAnaSP
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
OpDi01 .SetOp On 1 5 Operator Set Signal ~PG_OpDi01_Standard.PDL csoBtnCommandOpDi01 .RstOp Of f 1 5 Operator Reset Signal ~PG_OpDi01_Standard.PDL csoBtnCommand
OpDi01 .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpDi01_Standard.PDL csoBtnMode
OpDi01 .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpDi01_Standard.PDL csoBtnMode
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
OpDi03 .SetOp1 On 1 5 Operator Digital Input 1 ~PG_OpDi03_Standard.PDL csoBtnCommand1
OpDi03 .SetOp2 On 1 5 Operator Digital Input 2 ~PG_OpDi03_Standard.PDL csoBtnCommand2
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
29/37
OpDi03 .SetOp3 On 1 5 Operator Digital Input 3 ~PG_OpDi03_Standard.PDL csoBtnCommand3
OpDi03 .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpDi03_Standard.PDL csoBtnMode
OpDi03 .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpDi03_Standard.PDL csoBtnMode
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
OpStations .In0 Enable 3 1100 1='Enable operator station 1 ~PG_OpStations_Standard.PDL csoChkBoxIn0
OpStations .In0 Disable 3 1100 1='Enable operator station 1 ~PG_OpStations_Standard.PDL csoChkBoxIn0
OpStations .In1 Enable 3 1100 1='Enable operator station 2 ~PG_OpStations_Standard.PDL csoChkBoxIn1
OpStations .In1 Disable 3 1100 1='Enable operator station 2 ~PG_OpStations_Standard.PDL csoChkBoxIn1OpStations .In10 Enable 3 1100 1='Enable operator s tation 11 ~PG_OpStations_Standard.PDL csoChkBox In10
OpStations .In10 Disable 3 1100 1='Enable operator s tation 11 ~PG_OpStations_Standard.PDL csoChkBox In10
OpStations .In11 Enable 3 1100 1='Enable operator s tation 12 ~PG_OpStations_Standard.PDL csoChkBox In11
OpStations .In11 Disable 3 1100 1='Enable operator s tation 12 ~PG_OpStations_Standard.PDL csoChkBox In11
OpStations .In12 Enable 3 1100 1='Enable operator s tation 13 ~PG_OpStations_Standard.PDL csoChkBox In12
OpStations .In12 Disable 3 1100 1='Enable operator s tation 13 ~PG_OpStations_Standard.PDL csoChkBox In12
OpStations .In13 Enable 3 1100 1='Enable operator station 14 ~PG_OpStations_Standard.PDL csoChkBoxIn13
OpStations .In13 Disable 3 1100 1='Enable operator station 14 ~PG_OpStations_Standard.PDL csoChkBoxIn13
OpStations .In14 Enable 3 1100 1='Enable operator s tation 15 ~PG_OpStations_Standard.PDL csoChkBox In14
OpStations .In14 Disable 3 1100 1='Enable operator s tation 15 ~PG_OpStations_Standard.PDL csoChkBox In14
OpStations .In15 Enable 3 1100 1='Enable operator station 16 ~PG_OpStations_Standard.PDL csoChkBoxIn15
OpStations .In15 Disable 3 1100 1='Enable operator station 16 ~PG_OpStations_Standard.PDL csoChkBoxIn15
OpStations .In2 Enable 3 1100 1='Enable operator station 3 ~PG_OpStations_Standard.PDL csoChkBoxIn2
OpStations .In2 Disable 3 1100 1='Enable operator station 3 ~PG_OpStations_Standard.PDL csoChkBoxIn2
OpStations .In3 Enable 3 1100 1='Enable operator station 4 ~PG_OpStations_Standard.PDL csoChkBoxIn3OpStations .In3 Disable 3 1100 1='Enable operator station 4 ~PG_OpStations_Standard.PDL csoChkBoxIn3
OpStations .In4 Enable 3 1100 1='Enable operator station 5 ~PG_OpStations_Standard.PDL csoChkBoxIn4
OpStations .In4 Disable 3 1100 1='Enable operator station 5 ~PG_OpStations_Standard.PDL csoChkBoxIn4
OpStations .In5 Enable 3 1100 1='Enable operator station 6 ~PG_OpStations_Standard.PDL csoChkBoxIn5
OpStations .In5 Disable 3 1100 1='Enable operator station 6 ~PG_OpStations_Standard.PDL csoChkBoxIn5
OpStations .In6 Enable 3 1100 1='Enable operator station 7 ~PG_OpStations_Standard.PDL csoChkBoxIn6
OpStations .In6 Disable 3 1100 1='Enable operator station 7 ~PG_OpStations_Standard.PDL csoChkBoxIn6
OpStations .In7 Enable 3 1100 1='Enable operator station 8 ~PG_OpStations_Standard.PDL csoChkBoxIn7
OpStations .In7 Disable 3 1100 1='Enable operator station 8 ~PG_OpStations_Standard.PDL csoChkBoxIn7
OpStations .In8 Enable 3 1100 1='Enable operator station 9 ~PG_OpStations_Standard.PDL csoChkBoxIn8
OpStations .In8 Disable 3 1100 1='Enable operator station 9 ~PG_OpStations_Standard.PDL csoChkBoxIn8
OpStations .In9 Enable 3 1100 1='Enable operator station 10 ~PG_OpStations_Standard.PDL csoChkBoxIn9
OpStations . In9 Disable 3 1100 1='Enable operator station 10 ~PG_OpStations_Standard.PDL csoChkBoxIn9
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameOpTrig .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpTrig_Standard.PDL csoBtnMode
OpTrig .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpTrig_Standard.PDL csoBtnMode
OpTrig .InOp Set 1 5 Operator Binary Input ~PG_OpTrig_Standard.PDL csoBtnReset
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
PIDConL .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDConL_Limit.PDL csoIOAnaAH
PIDConL .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDConL_Limit.PDL csoIOAnaAL
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
30/37
PIDConL .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDConL_Limit.PDL csoIOAnaErrH
PIDConL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDConL_Limit.PDL csoIOAnaErrHy s
PIDConL .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDConL_Limit.PDL csoIOAnaErrL
PIDConL .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDConL_Limit.PDL csoIOAnaHy s
PIDConL .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDConL_Limit.PDL csoIOAnaMVH
PIDConL .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDConL_Limit.PDL csoIOAnaMVL
PIDConL .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDConL_Limit.PDL csoIOAnaRbkH
PIDConL .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDConL_Limit.PDL csoIOAnaRbkHy s
PIDConL .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDConL_Limit.PDL csoIOAnaRbkLPIDConL .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDConL_Limit.PDL csoIOAnaSPH
PIDConL .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDConL_Limit.PDL csoIOAnaSPL
PIDConL .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDConL_Limit.PDL csoIOAnaTH
PIDConL .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDConL_Limit.PDL csoIOAnaTL
PIDConL .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDConL_Limit.PDL csoIOAnaWH
PIDConL .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDConL_Limit.PDL csoIOAnaWL
PIDConL .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDConL_Parameter.PDL csoBtnMaint
PIDConL .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDConL_Parameter.PDL csoBtnMaint
PIDConL .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDConL_Parameter.PDL csoBtnSimu
PIDConL .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDConL_Parameter.PDL csoBtnSimu
PIDConL .OptimEn On 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConL_Parameter.PDL csoChkBoxOpti
PIDConL .OptimEn Of f 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConL_Parameter.PDL csoChkBoxOpti
PIDConL .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConL_Parameter.PDL csoChkBoxPVTrk
PIDConL .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConL_Parameter.PDL csoChkBoxPVTrk
PIDConL .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConL_Parameter.PDL csoChkBoxSPTrkPIDConL .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConL_Parameter.PDL csoChkBoxSPTrk
PIDConL .DeadBand 2 6 Width of deadband ~PG_PIDConL_Parameter.PDL csoIOAnaDeadB
PIDConL .Gain#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaGain
PIDConL .Dif f Gain#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaGainD
PIDConL .TD#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaTD
PIDConL .TI#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaTI
PIDConL .ConZone 2 6 Width of control zone ~PG_PIDConL_Parameter.PDL csoIOAnaZoneC
PIDConL .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoBtnRamp
PIDConL .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoBtnRamp
PI DC onL . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onL_R am p. PD L c soBt nR am pMode
PI DC onL . SP_R mpModTim e Gradient 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onL_R am p. PD L c soBt nR am pMode
PIDConL .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoChkBoxGrd
PIDConL .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoChkBoxGrd
PIDConL .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoIOAnaDuration
PIDConL .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_PIDConL_Ramp.PDL csoIOAnaGrdDownPIDConL .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_PIDConL_Ramp.PDL csoIOAnaGrdUp
PIDConL .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_PIDConL_Ramp.PDL csoIOAnaTargetSP
PIDConL .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_PIDConL_Standard.PDL csoBtnMode
PIDConL .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_PIDConL_Standard.PDL csoBtnMode
PIDConL .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_PIDConL_Standard.PDL csoBtnMode
PIDConL .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_PIDConL_Standard.PDL csoBtnMode
PIDConL .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_PIDConL_Standard.PDL csoBtnSPMode
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
31/37
PIDConL .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_PIDConL_Standard.PDL csoBtnSPMode
PIDConL .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_PIDConL_Standard.PDL csoIOAnaMV
PIDConL .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_PIDConL_Standard.PDL csoIOAnaPV
PIDConL .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_PIDConL_Standard.PDL csoIOAnaRbk
PIDConL .SP_Int 1 5 Internal setpoint f or operation ~PG_PIDConL_Standard.PDL csoIOAnaSP
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
PIDConR .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDConR_Limit.PDL csoIOAnaAH
PIDConR .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDConR_Limit.PDL csoIOAnaALPIDConR .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDConR_Limit.PDL csoIOAnaErrH
PIDConR .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDConR_Limit.PDL csoIOAnaErrHy s
PIDConR .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDConR_Limit.PDL csoIOAnaErrL
PIDConR .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDConR_Limit.PDL csoIOAnaHy s
PIDConR .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDConR_Limit.PDL csoIOAnaMVH
PIDConR .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDConR_Limit.PDL csoIOAnaMVL
PIDConR .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDConR_Limit.PDL csoIOAnaRbkH
PIDConR .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDConR_Limit.PDL csoIOAnaRbkHy s
PIDConR .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDConR_Limit.PDL csoIOAnaRbkL
PIDConR .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDConR_Limit.PDL csoIOAnaSPH
PIDConR .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDConR_Limit.PDL csoIOAnaSPL
PIDConR .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDConR_Limit.PDL csoIOAnaTH
PIDConR .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDConR_Limit.PDL csoIOAnaTL
PIDConR .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDConR_Limit.PDL csoIOAnaWH
PIDConR .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDConR_Limit.PDL csoIOAnaWLPIDConR .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDConR_Parameter.PDL csoBtnMaint
PIDConR .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDConR_Parameter.PDL csoBtnMaint
PIDConR .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDConR_Parameter.PDL csoBtnSimu
PIDConR .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDConR_Parameter.PDL csoBtnSimu
PIDConR .OptimEn On 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConR_Parameter.PDL csoChkBoxOpti
PIDConR .OptimEn Of f 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConR_Parameter.PDL csoChkBoxOpti
PIDConR .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConR_Parameter.PDL csoChkBoxPVTrk
PIDConR .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConR_Parameter.PDL csoChkBoxPVTrk
PIDConR .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConR_Parameter.PDL csoChkBoxSPTrk
PIDConR .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConR_Parameter.PDL csoChkBoxSPTrk
PIDConR .DeadBand 2 6 Width of deadband ~PG_PIDConR_Parameter.PDL csoIOAnaDeadB
PIDConR .Gain#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaGain
PIDConR .Dif f Gain#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaGainD
PIDConR .TD#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaTD
PIDConR .TI#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaTIPIDConR .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoBtnRamp
PIDConR .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoBtnRamp
PI DC onR . SP_R mpModTim e D urat ion 1 5 1= U se t im e (SP_R mpTim e) f or ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onR _R am p. PD L c soBt nR am pMode
PI DC onR . SP_R mpModTim e Gradient 1 5 1= Us e t im e (SP_R mpTim e) for ram p, 0= U se rat es SP_U pR aLim , SP_D nR aLim ~PG_PI DC onR _R am p. PD L c soBt nR am pMode
PIDConR .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoChkBoxGrd
PIDConR .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoChkBoxGrd
PIDConR .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoIOAnaDuration
-
8/10/2019 60575347_PCS7_UserRights_en.pdf
32/37
PIDConR .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_PIDConR_Ramp.PDL csoIOAnaGrdDown
PIDConR .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_PIDConR_Ramp.PDL csoIOAnaGrdUp
PIDConR .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_PIDConR_Ramp.PDL csoIOAnaTargetSP
PIDConR .AutModOp Automatic 1 5 1 = Automatic mode by operator ~PG_PIDConR_Standard.PDL csoBtnMode
PIDConR .ManModOp Manual 1 5 1 = Manual mode by operator ~PG_PIDConR_Standard.PDL csoBtnMode
PIDConR .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_PIDConR_Standard.PDL csoBtnMode
PIDConR .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_PIDConR_Standard.PDL csoBtnMode
PIDConR .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_PIDConR_Standard.PDL csoBtnSPMode
PIDConR .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_PIDConR_Standard.PDL csoBtnSPModePIDConR .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_PIDConR_Standard.PDL csoIOAnaMV
PIDConR .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_PIDConR_Standard.PDL csoIOAnaPV
PIDConR .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_PIDConR_Standard.PDL csoIOAnaRbk
PIDConR .SP_Int 1 5 Internal setpoint f or operation ~PG_PIDConR_Standard.PDL csoIOAnaSP
BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName
PIDStepL .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDStepL_Limit.PDL csoIOAnaAH
PIDStepL .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDStepL_Limit.PDL csoIOAnaAL
PIDStepL .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDStepL_Limit.PDL csoIOAnaErrH
PIDStepL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDStepL_Limit.PDL csoIOAnaErrHy s
PIDStepL .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDStepL_Limit.PDL csoIOAnaErrL
PIDStepL .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDStepL_Limit.PDL csoIOAnaHy s
PIDStepL .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDStepL_Limit.PDL csoIOAnaMVH
PIDStepL .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDStepL_Limit.PDL csoIOAnaMVL
PIDStepL .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDStepL_Limit.PDL csoIOAnaRbkHPIDStepL .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDStepL_Limit.PDL csoIOAnaRbkHy s
PIDStepL .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDStepL_Limit.PDL csoIOAnaRbkL
PIDStepL .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDStepL_Limit.PDL csoIOAnaSPH
PIDStepL .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDStepL_Limit.PDL csoIOAnaSPL
PIDStepL .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDStepL_Limit.PDL csoIOAnaTH
PIDStepL .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDStepL_Limit.PDL csoIOAnaTL
PIDStepL .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDStepL_Limit.PDL csoIOAnaWH
PIDStepL .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDStepL_Limit.PDL csoIOAnaWL
PIDStepL .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDStepL_Parameter.PDL csoBtnMaint
PIDStepL .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDStepL_Parameter.PDL csoBtnMaint
PIDStepL .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDStepL_Parameter.PDL csoBtnSimu
PIDStepL .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDStepL_Parameter.PDL csoBtnSimu
PIDStepL .OptimEn On 2 6 1 = Enable optimization of PID