F6MCP Control Panel for MW/MVAR
Meter/Transducer TestingKamin Dave
Application Engineer (Protective Relaying)
DOBLE ENGINEERING COMPANY
![Page 2: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/2.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
MW/MVAR Transducer Testing with F6150
F6MCP: CASE 1
![Page 3: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/3.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Configuration: 3V X 3IMeter/Transducer Configuration: 3V X 3I
F6MCP: 3V X 3I
![Page 4: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/4.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: 3V X 3I Connection diagram
I3
VAVA
VB
VC
I1
I2
I3
F6150
Meter/Transducer
VB
VC
I1
I2
63.5V@0o
63.5V@240o
63.5V@120o
1A@0o
1A@240o
1A@120o
![Page 5: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/5.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: 3V X 3I software view
Input: 191w
Output: based on Transducer output
![Page 6: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/6.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Configuration: 3V X 3IMeter/Transducer Configuration: 3V X 3IPower in secondary side:Vsec = 110V (L-L) & 63.5V (L-N)Isec = 1APower factor = unity = 1Psec = 1.3725*Vsec (L-L)*Isec*cos(0o)
= 1.7325*110*1*1 = 190.52 watts
F6MCP: 3V X 3I Power Calculation
![Page 7: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/7.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Software display shows: Input: 190.52 watts based on F6150 input
Output: 190.52 watts based on Transducer output
F6MCP: CASE 1
![Page 8: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/8.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
MW/MVAR Transducer Testing with F6150
F6MCP: CASE 2
![Page 9: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/9.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Configuration: 3V X 3IMeter/Transducer Configuration: 3V X 2IMeter/Transducer calculating 3-phasePower output
F6MCP: 3V X 2I
![Page 10: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/10.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: 3V X 2I Connection diagram
I3
VAVA
VB
VC
I1
I2
I3
F6150
Meter/Transducer
VB
VC
I1
63.5V@0o
63.5V@240o
63.5V@120o
1A@0o
1A@240o
1A@120o
![Page 11: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/11.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Short link “Red” & “Black” terminals of Source “I2”Magnitude of I2 = 1A@240o
F6MCP: 3V X 2I
![Page 12: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/12.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: 3V X 2I software view
Input: 191w
Output: based on Transducer output
![Page 13: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/13.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Configuration: 3V X 3IMeter/Transducer Configuration: 3V X 3IPower in secondary side:Vsec = 110V (L-L) & 63.5V (L-N)Isec = 1APower factor = unity = 1Psec = 1.3725*Vsec (L-L)*Isec*cos(0o)
= 1.7325*110*1*1 = 190.52 watts
F6MCP: 3V X 2I Power Calculation
![Page 14: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/14.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Software display shows: Input: 190.52 watts based on F6150 input
Output: 190.52 watts based on Transducer output
F6MCP: CASE 2
![Page 15: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/15.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
MW/MVAR Transducer Testing with F6150
F6MCP: CASE 3
![Page 16: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/16.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Configuration: 3V X 2IMeter/Transducer Configuration: 3V X 2IMeter/Transducer calculating 3-phasePower output
F6MCP: 3V X 2I
![Page 17: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/17.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: 3V X 2I Connection diagram
I3
VAVA
VB
VC
I1
I2
I3
F6150
Meter/Transducer
VB
VC
I1
63.5V@0o
63.5V@240o
63.5V@120o
1A@0o
0A@240o
1A@120o
![Page 18: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/18.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Short link “Red” & “Black” terminals of Source “I2”Magnitude of I2 = 0A@240o
F6MCP: 3V X 2I
![Page 19: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/19.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: 3V X 2I software view
Input: 127w
Output: based on Transducer output
![Page 20: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/20.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Configuration: 3V X 2IMeter/Transducer Configuration: 3V X 3IPower in secondary side:Vsec = 110V (L-L) & 63.5V (L-N)Isec = 1APower factor = unity = 1Psec = (2/1.3725)*Vsec (L-L)*Isec*cos(0o)
= (2/1.7325)*110*1*1 = 127 watts
F6MCP: 3V X 2I Power Calculation
![Page 21: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/21.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Software display shows: Input: 127 watts based on F6150 input
Output: 190.52 watts based on Transducer output
In this case Input & Output will not match because transducer calculating 3-ph power & software calculating 2-ph power based on F6150 source configurations
F6MCP: CASE 3
![Page 22: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/22.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
How to set the values in Primary?
F6MCP: CASE 3
![Page 23: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/23.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: CASE 3
![Page 24: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/24.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: CASE 3
![Page 25: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/25.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6MCP: CASE 3
![Page 26: 6A MW&MVAR Transducer Testing](https://reader030.vdocument.in/reader030/viewer/2022013104/53fdb242dab5ca004a8b45b6/html5/thumbnails/26.jpg)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Configuration: 3V X 2IMeter/Transducer Configuration: 3V X 3IPower in secondary side:Vsec = 110V (L-L) & 63.5V (L-N)Isec = 1AVTR = 11500 / 110V = 104.54CTR = 100 / 1 = 100 Power factor = unity = 1PPri = (2/1.3725)*Vsec (L-L)*Isec*cos(0o)*CTR*VTR
= (2/1.7325)*110*1*1*(104.54)*(100) = 1.327 Mwatts