7. technical data

Upload: sbanerjee

Post on 03-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 7. Technical Data

    1/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444

    TECHNICAL DATA

  • 7/28/2019 7. Technical Data

    2/32

  • 7/28/2019 7. Technical Data

    3/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 1/30

    CONTENT

    1. RATINGS 5

    1.1 Currents 5

    1.2 Voltages 5

    1.3 Auxiliary Voltage 6

    1.4 Frequency 6

    1.5 Logic inputs 6

    1.6 Output Relay Contacts 7

    1.7 Field Voltage 7

    1.8 Loop through connections 7

    1.9 Wiring requirements 7

    2. BURDENS 8

    2.1 Current Circuit 8

    2.2 Voltage Circuit 8

    2.3 Auxiliary Supply 8

    2.4 Optically-Isolated Inputs 8

    3. ACCURACY 9

    3.1 Reference Conditions 9

    3.2 Measurement Accuracy 9

    3.3 Protection accuracy 10

    3.4 Influencing Quantities 12

    3.5 High Voltage Withstand IEC60255-5:1977 12

    3.5.1 Dielectric Withstand 12

    3.5.2 Impulse 12

    3.5.3 Insulation Resistance 12

    4. ENVIRONMENTAL COMPLIANCE 13

    4.1 Electrical Environment 13

    4.1.1 DC Supply Interruptions IEC60255-11:1979 13

    4.1.2 AC Ripple on DC Supply IEC60255-11:1979 13

    4.1.3 Disturbances on AC Supply - EN61000-4-11:1994 13

    4.1.4 High Frequency Disturbance IEC60255-22-1:1988 13

    4.1.5 Fast Transient IEC60255-22-4:1992 13

    4.1.6 Electrostatic Discharge IEC60255-22-2:1996 13

    4.1.7 Conducted Emissions EN 55011:1991 134.1.8 Radiated Emissions EN 55011:1991 13

    4.1.9 Radiated Immunity IEC60255-22-3:1989 14

  • 7/28/2019 7. Technical Data

    4/32

    P44x/EN TD/E33 Technical Data

    Page 2/30 MiCOM P441/P442 & P444

    4.1.10 Conducted Immunity IEC61000-4-6:1996 14

    4.1.11 Surge Immunity IEC61000-4-5:1995 14

    4.1.12 EMC Compliance 14

    4.1.13 Power Frequency Interference - Electricity Association (UK) 14

    4.2 Atmospheric Environment 14

    4.2.1 Temperature IEC60255-6:1988 14

    4.2.2 Humidity IEC60068-2-3:1969 14

    4.2.3 Enclosure Protection IEC60529:1989 14

    4.2.4 Pollution degree IEC61010-1:1990/A2:1995 14

    4.3 Mechanical Environment 15

    4.3.1 Vibration IEC60255-21-1:1988 15

    4.3.2 Shock and Bump IEC60255-21-2:1988 15

    4.3.3 Seismic IEC60255-21-3:1993 15

    5. ANSI TEST REQUIREMENTS 16

    5.1 ANSI / IEEE C37.90.1989 16

    5.2 ANSI / IEEE C37.90.1: 1989 16

    5.3 ANSI / IEEE C37.90.2: 1995 16

    6. PROTECTION SETTING RANGES 17

    6.1 Distance Protection 17

    6.1.1 Line Settings 17

    6.1.2 Zones settings 17

    6.1.3 Power-swing settings 18

    6.2 Distance protection schemes 18

    6.2.1 Programmable distance schemes 19

    6.2.2 Distance schemes settings 19

    6.2.3 Weak infeed settings 19

    6.2.4 Loss of load settings 19

    6.3 Back-up Overcurrent Protection 20

    6.3.1 Threshold Settings 20

    6.3.2 Time Delay Settings 20

    6.3.3 Inverse Time (IDMT) Characteristic 20

    6.4 Negative sequence overcurrent protection 22

    6.5 Broken Conductor Protection 22

    6.6 Earth Fault Overcurrent Protection 22

    6.6.1 Threshold Settings 22

    6.6.2 Polarising Quantities For Earth Fault Measuring Elements 22

    6.6.3

    Time Delay Characteristics 22

    6.7 Zero sequence Power Protection (since B1.0) 23

  • 7/28/2019 7. Technical Data

    5/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 3/30

    6.8 Channel Aided Directional Earth Fault Protection 23

    6.8.1 Threshold Settings 23

    6.9 Under Voltage Protection 23

    6.9.1 Threshold Settings 23

    6.9.2 Under Voltage Protection Time Delay Characteristics 23

    6.10 Over Voltage Protection 24

    6.10.1 Threshold Settings 24

    6.10.2 Time Delay Characteristics 24

    6.11 Voltage Transformer Supervision 24

    6.12 Capacitive Voltage Transformer Supervision (since B1.0) 24

    6.13 Current Transformer Supervision 25

    6.14 Undercurrent Element 25

    6.15

    Breaker Fail Timers (TBF1 and TBF2) 25

    7. MEASUREMENT SETTINGS 26

    7.1 Disturbance Recorder Settings 26

    7.2 Fault Locator Settings 26

    8. CONTROL FUNCTION SETTINGS 27

    8.1 Communications Settings 27

    8.2 Auto-Reclose 27

    8.2.1

    Options 27

    8.2.2 Auto-recloser settings 27

    8.3 Circuit Breaker State Monitoring 28

    8.4 Circuit Breaker Control 29

    8.5 Circuit Breaker Condition Monitoring 29

    8.5.1 Maintenance alarm settings 29

    8.5.2 Lockout Alarm Settings 29

    8.6 Programmable Logic 30

    8.7 CT and VT Ratio Settings 30

  • 7/28/2019 7. Technical Data

    6/32

    P44x/EN TD/E33 Technical Data

    Page 4/30 MiCOM P441/P442 & P444

    BLANK PAGE

  • 7/28/2019 7. Technical Data

    7/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 5/30

    1. RATINGS

    1.1 Currents

    In = 1A or 5A ac rms (dual rated).

    Separate terminals are provided for the 1A and 5A windings, with the neutral input of eachwinding sharing one terminal.

    CT Type Operating range

    Standard 0 to 64In

    Sensitive 0 to 2In

    All current inputs will withstand the following, with any current function setting:

    Withstand Duration

    4 n Continuous rating

    4.5 n 10 minutes

    5 n 5 minutes

    6 n 3 minutes

    7 n 2 minutes

    30 n 10 seconds

    50 n 3 seconds

    100 n 1 second

    Pass Criteria Winding temperatures

  • 7/28/2019 7. Technical Data

    8/32

    P44x/EN TD/E33 Technical Data

    Page 6/30 MiCOM P441/P442 & P444

    1.3 Auxiliary Voltage

    The relay is available in three auxiliary voltage versions, these are specified in the tablebelow:

    Nominal Ranges Operative dc range Operative ac range

    24-48V dc 19 - 65 V Not available

    48-110 V dc (30 / 100 V ac rms) ** 37 - 150 V 24 - 110 V

    110-250 V dc (100 / 240 V ac rms) ** 87 - 300 V 80 - 265 V

    ** rated for AC or DC operation.

    Pass Criteria All functions operate as specifiedwithin the operative ranges

    All power supplies operatecontinuously over their operativeranges, and environmental

    conditions

    1.4 Frequency

    The nominal frequency (Fn) is dual rated at 50/60Hz, the operate range is 45Hz to 65Hz.

    1.5 Logic inputs

    All the logic inputs are independent and isolated, relay types P441 provide 8 inputs, 16inputs are provided by the P442.

    Rating Range

    Logical off 0Vdc 0 - 12Vdc

    Logical on 50Vdc 30 - 60Vdc

    Higher voltages can be used in conjunction with an external resistor, value of the resistor isdetermined by the following equation:

    Resistor = (Required Input Level - 50) x 200.

    Hardware ref P441/442B or C or P444A or C (Universal Opto) :

    All the logic inputs are independent and isolated, relay types P441 provide 8 inputs, 16inputs are provided by the P442 and 24 inputs for P444.

    Battery Voltage (V dc) Logical off (V dc) Logical on (V dc)

    24/27 19.2

    30/34 24

    48/54 38.4

    110/125 88

    220/250 176

    REMARK: Control the version compatibility in P44x/EN VC chapter

  • 7/28/2019 7. Technical Data

    9/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 7/30

    1.6 Output Relay Contacts

    Make & Carry 30A for 3s

    Carry 250A for 30ms10A continuous

    Break DC: 50W resistiveDC: 37.5W inductive (L/R = 40ms)AC: 1250VAAC: 1250VA inductive (P.F. = 0.7)

    Maxima: 10A and 300V

    Loaded contact: 10,000 operations minimum

    Unloaded contact: 100,000 operations minimum

    Watchdog Contact

    Break DC: 30W resistiveDC: 15W inductive (L/R = 40ms)AC: 275W inductive (P.F. = 0.7)

    The maximum number of output relays that should be configured to be permanentlyenergized is 50% of those available (minimum 4).

    1.7 Field Voltage

    The field voltage provided by the relay is nominally 48V dc with a current limit of 112mA. Theoperating range shall be 40V to 60V with an alarm raised at

  • 7/28/2019 7. Technical Data

    10/32

    P44x/EN TD/E33 Technical Data

    Page 8/30 MiCOM P441/P442 & P444

    2. BURDENS

    2.1 Current Circuit

    CT burden (at nominal current)

    1A

  • 7/28/2019 7. Technical Data

    11/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 9/30

    3. ACCURACY

    For all accuracies specified, the repeatability is 2.5% unless otherwise specified.

    If no range is specified for the validity of the accuracy, then the specified accuracy shall bevalid over the full setting range.

    3.1 Reference Conditions

    Quantity Reference conditions Test tolerance

    General

    Ambient temperature 20 C 2C

    Atmospheric pressure 86kPa to 106kPa -

    Relative humidity 45 to 75 % -

    Input energising quantity

    Current In 5%

    Voltage Vn 5%

    Frequency 50 or 60Hz 0.5%

    Auxiliary supply DC 48V or 110VAC 63.5V or 110V

    5%

    3.2 Measurement Accuracy

    Quantity Range Accuracy

    Current 0.1 to 64In 10mA or 1%

    Voltage 1.0 Vn 1%

    Frequency 45 - 65Hz 0.025Hz

    Phase 0 - 360 2

  • 7/28/2019 7. Technical Data

    12/32

    P44x/EN TD/E33

    Page 10/30

    3.3 Protection accuracy

    Element Range Trigger Res

    Distance elements: Zone 1

    ResistanceImpedance 0 to 400/In0.001/In to 500/In

    Accuracy: 5%

    Distance elements: Other zonesResistanceImpedance

    0 to 400/In0.001/In to 500/In

    Accuracy: 10%

    Phase Overcurrent elements (I>1, I>2, I>3, I>4) 2 to 20 Is [1] DT: Is5%IDMT: 1.05Is5%

    0.95

    0.95

    Relay characteristic angle -95 to +95 Accuracy: 2 1

    Earth fault measuring elements (IN>1,I

    N>2, I

    N>) 2 to 20 Is [2] DT: Is5%

    IDMT: 1.05Is5%0.95

    Zero sequence voltage polarisation (Vop>)

    Vn = 100/120 V 0.5 - 25VAccuracy:

    10% at RCA 90 -

    Negative sequence Polarisation: Voltage threshold (V2p>)

    Vn = 100/120 V 0.5 - 25VAccuracy:

    5% -

    Negative sequence Polarisation: Current threshold (I2p>) 0.08 - 1.0In Accuracy:

    5%0.95

    Negative Sequence Overcurrent (I2>) 2 to 20 Is [1] Is5% 0.95

    Under Current element (I>)Vn = 100/120 V 60 - 185V

    DT: Vs5%IDMT: 1.05Vs5% 0.95

    Directional Operating Boundary 0 - 360 Accuracy:2

    -

  • 7/28/2019 7. Technical Data

    13/32

    Technical Data

    MiCOM P441/P442 & P444

    Element Range Trigger Res

    Broken conductor protectionI

    I

    2

    1

    0.2 to 1.0

    I

    I

    2

    1

    5% 0.95

    Transient Overreach 2 to 20 Is

  • 7/28/2019 7. Technical Data

    14/32

    P44x/EN TD/E33 Technical Data

    Page 12/30 MiCOM P441/P442 & P444

    3.4 Influencing Quantities

    No additional errors will be incurred for any of the following influencing quantities:

    Quantity Operative range (typical only)

    Environmental

    Temperature -25C to +55C

    Mechanical (Vibration, Shock, Bump,Seismic)

    According toIEC 60255-21-1:1988IEC 60255-21-2:1988IEC 60255-21-3:1995

    Quantity Operative range

    Electrical

    Frequency 45 Hz to 65 HzHarmonics (single) 5% over the range 2nd to 17th

    Auxiliary voltage range 0.8 LV to 1.2 HV (dc)0.8 LV to 1.1 HV (ac)

    Aux. supply ripple 12% Vn with a frequency of 2.fn

    Point on wave of fault waveform 0 - 360

    DC offset of fault waveform No offset to fully offset

    Phase angle -90 to + 90

    Magnetising inrush No operation with OC elements set to 35% of

    peak anticipated inrush level.

    3.5 High Voltage Withstand IEC60255-5:1977

    3.5.1 Dielectric Withstand

    2.0kVrms for one minute between all terminals and case earth.

    2.0kVrms for one minute between all terminals of each independent circuit grouped togetherand all other terminals. This includes the output contacts and loop through connectionsD17/D18 and E17/E18.

    1.5kVrms for one minute across dedicated normally open contacts of output relays.

    1.0kVrms for 1 minute across normally open contacts of changeover pairs and watchdogoutputs.

    3.5.2 Impulse

    The product will withstand without damage impulses of 5kV peak, 1.2/50s, 0.5J across:

    Each independent circuit and the case with the terminals of each independent circuitconnected together.

    Independent circuits with the terminals of each independent circuit connected together.

    Terminals of the same circuit except normally open metallic contacts.

    3.5.3 Insulation Resistance

    The insulation resistance is greater than 100 M at 500Vdc.

  • 7/28/2019 7. Technical Data

    15/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 13/30

    4. ENVIRONMENTAL COMPLIANCE

    The product complies with the following specifications :

    4.1 Electrical Environment

    4.1.1 DC Supply Interruptions IEC60255-11:1979

    The product will withstand a 20ms interruption in the auxiliary voltage in its quiescentcondition.

    4.1.2 AC Ripple on DC Supply IEC60255-11:1979

    The product will operate with 12% AC ripple on the DC auxiliary supply without anyadditional measurement errors.

    4.1.3 Disturbances on AC Supply - EN61000-4-11:1994

    The products satisfies the requirements of EN61000-4-11 for voltage dips and shortinterruptions.

    4.1.4 High Frequency Disturbance IEC60255-22-1:1988

    The product complies with Class III 2.5kV common mode and 1kV differential mode for 2

    seconds at 1MHz with 200 source impedance, without any mal-operations or additionalmeasurement errors.

    4.1.5 Fast Transient IEC60255-22-4:1992

    The product complies with all classes up to and including class IV/4kV without any mal-operations or additional measurement errors.

    Fast transient disturbances on power supply(common mode only)

    4kV, 5ns rise time, 50ns decay time, 5kHzrepetition time, 15ms burst, repeated every

    300ms for 1min in each polarity, with a 50source impedance.

    Fast transient disturbances on I/O signal,data and control lines (common mode only)

    4kV, 5ns rise time, 50ns decay time, 5kHzrepetition time, 15ms burst, repeated every

    300ms for 1min in each polarity, with a 50source impedance.

    4.1.6 Electrostatic Discharge IEC60255-22-2:1996

    The product will withstand application of all discharge levels up to the following without mal-operation:

    Class IV 15kV discharge in air to the user interface, display and exposed metal work.

    Class III 8kV discharge in air to all communication ports, 6kV point contact discharge to anypart of the front of the product.

    4.1.7 Conducted Emissions EN 55011:1991

    Group 1 Class A limits.

    0.15 - 0.5MHz, 79dBV (quasi peak) 66dBV (average).

    0.5 - 30MHz, 73dBV (quasi peak) 60dBV (average).

    4.1.8 Radiated Emissions EN 55011:1991

    Group 1 Class A limits.

    30 - 230MHz, 40dBV/m at 10m measurement distance.

    230 - 1000MHz, 47dBV/m at 10m measurement distance.

  • 7/28/2019 7. Technical Data

    16/32

    P44x/EN TD/E33 Technical Data

    Page 14/30 MiCOM P441/P442 & P444

    4.1.9 Radiated Immunity IEC60255-22-3:1989

    Class/Level III/3 - 10V/m at 1kHz 80% am., 20MHz to 1GHz.

    4.1.10 Conducted Immunity IEC61000-4-6:1996

    Level 3 - 10Vrms at 1kHz 80% am.- 0.15 to 80MHz.

    4.1.11 Surge Immunity IEC61000-4-5:1995

    Level 4 - 4kV peak, 1.2/50s between all groups and case earth

    2kV peak, 1.2/50s between terminals of each group.

    4.1.12 EMC Compliance

    Compliance to the European Community Directive 89/336/EEC on EMC is claimed via theTechnical Construction File route.

    Generic Standards EN 50081-2 :1994 and EN 50082-2 :1995 are used to establishconformity.

    4.1.13 Power Frequency Interference - Electricity Association (UK)

    EA PAP Document, Environmental Test Requirements for Protection Relays and SystemsIssue I, Draft 4.2.1 1995.

    Class Length of commscircuit

    UnbalancedComms V rms

    Balanced Comms(Unbalance 1%)Vrms

    Balanced Comms(Unbalance 0.1%)Vrms

    1 1 to 10 metres 0.5 0.005 0.0005

    2 10 to 100 metres 5 0.05 0.005

    3 100 to 1000 metres 50 0.5 0.05

    4 1000 to 10,000m or > 500 5 0.5

    4.2 Atmospheric Environment

    4.2.1 Temperature IEC60255-6:1988

    Storage and transit 25C to +70C.

    Operating 25C to +55C.

    IEC60068-2-1:1990 Cold

    IEC60068-2-2:1974 Dry heat

    4.2.2 Humidity IEC60068-2-3:1969

    56 days at 93% relative humidity and 40C.

    4.2.3 Enclosure Protection IEC60529:1989

    IP52 - Protected against dust and dripping water at 15 to the vertical.

    4.2.4 Pollution degree IEC61010-1:1990/A2:1995

    Normally only non conductive pollution occurs. Occasionally a temporary conductivitycaused by condensation must be expected.

  • 7/28/2019 7. Technical Data

    17/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 15/30

    4.3 Mechanical Environment

    4.3.1 Vibration IEC60255-21-1:1988

    Vibration Response Class 2 - 1g

    Vibration Endurance Class 2 - 2g.

    4.3.2 Shock and Bump IEC60255-21-2:1988

    Shock response Class 2 - 10g

    Shock withstand Class 1 - 15g

    Bump Class 1 - 10g

    4.3.3 Seismic IEC60255-21-3:1993

    Class 2.

  • 7/28/2019 7. Technical Data

    18/32

    P44x/EN TD/E33 Technical Data

    Page 16/30 MiCOM P441/P442 & P444

    5. ANSI TEST REQUIREMENTS

    The products shall meet the ANSI / IEEE requirements as follows:-

    5.1 ANSI / IEEE C37.90.1989

    Standards for relays and relay systems associated with electric power apparatus.

    5.2 ANSI / IEEE C37.90.1: 1989

    Surge withstand capability (SWC) tests for protective relays and relay systems:-

    Oscillatory test - 1MHz to 1.5MHz, 2.5kV to 3.0kV,

    Fast transient test 4kV to 5kV

    5.3 ANSI / IEEE C37.90.2: 1995

    Standard for withstand capability of relay systems to radiated electromagnetic interferencefrom transceivers: 35V/m, 25 to 1000Mhz.

  • 7/28/2019 7. Technical Data

    19/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 17/30

    6. PROTECTION SETTING RANGES

    6.1 Distance Protection

    6.1.1 Line Settings

    Setting Range Step size

    Length of line (Ln) 0.3 - 1000 km0.2 - 625 miles

    0.010 km0.005 miles

    Positive sequence angle (1) 90 - 90 0.1

    In = 1 A In = 5 A

    Setting Range Step size Range Step size

    Positive sequence impedance

    (Z1)

    0.001 - 500 0.001 0.002 -

    199,8

    0.002

    6.1.2 Zones settings

    Setting In = 1 A In = 5 A

    Range Step size Range Step size

    Impedance reaches(Zone 1, Zone 2, Zone 3, Zone P,Zone 4)

    0.001 - 500 0.001 0.0002 -100

    0.0002

    Resistive reaches for phase -earth faults

    (Zone 1, Zone 2, Zones 3 & 4,Zone P)

    0 - 400 0.01 0 - 80 0.002

    Resistive reaches for phase -earth faults(Zone 1, Zone 2, Zones 3 & 4,Zone P)

    0 - 400 0.01 0 - 80 0.002

    Setting Range Step size

    Residual compensation angles(Zone 1, Zone 2, Zones 3 & 4,

    Zone P)

    180-180 0.1

    Residual compensation factors(Zone 1, Zone 2, Zones 3 & 4,Zone P)

    0 - 7 0.001

    Timer for zone 1/1X 0 - 10s 0.002s

    Timers for zone 2, Zone 3,Zone P, Zone 4

    0 - 10s 0.01s

  • 7/28/2019 7. Technical Data

    20/32

    P44x/EN TD/E33 Technical Data

    Page 18/30 MiCOM P441/P442 & P444

    6.1.3 Power-swing settings

    In = 1 A In = 5 A

    Setting Range Step size Range Step size

    Powerswing detection boundaries:Delta RDelta X

    0 - 400 0 - 400

    0.01 0.01

    0 - 80 0 - 80

    0.002 0.002

    Setting Range Step size

    Imax line In - 20 In 0.01 In

    IN threshold 10 - 100 % Imax 1%Imax

    I2 threshold 10 - 100 % Imax 1%Imax

    Trip mode Single/Three pole -

    Unblocking time delay 0 - 30s 0.1s

    Power-swing detection boundary 0 - 25 0.01

    Block zones Bit 0: Z1&Z1X-Block, Bit 1: Z2 blockBit 2: Z3 block, Bit 3: Zp block, Bit 4:Z4block

    6.2 Distance protection schemes

    Basic scheme functions: Instantaneous zone 1 tripping

    Time delayed tripping for all zones

    Directional earth fault protection

    Zero sequence Power protection (since B1.0)

    Switch on to fault logic

    Trip on reclose logic

    Loss of load logic

    Conversion to three pole tripping

    Channel-aided distance schemes: Permissive Overreach Protection withOverreaching Zone 1 (POP Z1)

    Permissive Overreach Protection withOverreaching Zone 2 (POP Z2)

    Permissive Underreach Protection, AcceleratingZone 2 (PUP Z2)

    Permissive Underreach Protection Tripping viaForward Start (PUP Fwd)

    Blocking Overreach Protection with OverreachingZone 1 (BOP Z1)

    Blocking Overreach Protection with OverreachingZone 2 (BOP Z2)

    Permissive Scheme Unblocking Logic

    Permissive Overreach Schemes Weak Infeed

    Features

    Permissive Overreach Schemes Current ReversalGuard

    Blocking Scheme Current Reversal Guard

  • 7/28/2019 7. Technical Data

    21/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 19/30

    6.2.1 Programmable distance schemes

    Setting Range

    Signal Send Zone No Signal Send/Signal send on Z1/ Signal send on Z2/Signal send on Z4

    Type of Scheme on signalReceive

    None/None+Z1X/Aided scheme for Z1 faults/Aidedscheme for Z2 faults/ Aided scheme for forward faults/Blocking scheme for Z1 faults/ Blocking scheme for Z2faults

    6.2.2 Distance schemes settings

    Setting Range Step size

    Fault Type/Signal Send Zone Phase-to-Ground Fault Enabled/Phase-to-Phase Fault Enabled/BothEnabled

    -

    Trip mode for the distance

    protection

    Force 3 Pole Trip for all zones/1

    Pole Trip for zone Z1/1 Pole trip forzones Z1 and Z2

    -

    Signal Receive Time-Delay forBlocking Schemes (Tp)

    0 - 1s 0,002s

    Time Delay for Reversal Guard 0 - 0,15s 0,002s

    Unblocking Logic/Type of TACReceive

    None (no control of SignalReceive)/Loss of carrier/Loss ofGuard (HF Presence)

    -

    SOTF Delay 10 3600 s 1.000 s

    TOR-SOTF Mode TOR

    Z1 enable/Z2 enable/Z3 enable/All zones enable/Distance scheme enable

    SOTF

    AllZones/Lev.Detect./Z1 enable/Z2enable/Z3 enable/Z1+Reven/Z2+Rev en/Dist Scheme/Disable

    -

    6.2.3 Weak infeed settings

    Setting Range Step size

    WI :Mode Status Disabled/Echo/Trip&Echo -

    WI : Single Pole Trip Disabled/Enabled -

    WI : V< Thres. 10 - 70V 5V

    WI : Trip Time Delay 0 - 1s 0,002s

    6.2.4 Loss of load settings

    Setting Range Step Size

    Mode status Disabled or enabled

    Chan. Fail Disabled or enabled

    I< 0.05 x In - 1 x In 0.05 In

    Window 0.01s - 0.1s 0.01s

    NOTE: For detailed information on distance schemes, please refer to ChapterP44x/EN AP - Application notes.

  • 7/28/2019 7. Technical Data

    22/32

    P44x/EN TD/E33 Technical Data

    Page 20/30 MiCOM P441/P442 & P444

    6.3 Back-up Overcurrent Protection

    6.3.1 Threshold Settings

    Setting Stage Range Step size

    I>1 Current Set 1st Stage 0.08 - 4.0In 0.01In

    I>2 Current Set 2nd Stage 0.08 - 4.0In 0.01In

    I>3 Current Set TOR/SOTF protection 0.08 - 32In 0.01In

    I>4 Current Set Stub bus protection 0.08 - 32In 0.01In

    6.3.2 Time Delay Settings

    Each overcurrent element has an independent time setting and each time delay can beblocked by an optically isolated input:

    Element Time delay type

    1st Stage Definite Time (DT) or IDMT(IEC/UK/IEEE/UScurves)

    2nd Stage DT or IDMT

    3rd Stage DT

    4th Stage DT

    6.3.3 Inverse Time (IDMT) Characteristic

    IDMT characteristics are selectable from a choice of four IEC/UK and five IEEE/US curvesas shown in the table below.

    The IEC/UK IDMT curves conform to the following formula:

    t = TMS K

    (I/Is)1

    The IEEE/US IDMT curves conform to the following formula:

    t=TD7

    ( )

    +

    L

    1I/I

    K

    S

    Where

    t = operation time

    K = constant

    I = measured current

    IS

    = current threshold setting

    = constant

    L = ANSI/IEEE constant (zero for IEC/UK curves)

    TMS = Time Multiplier Setting for IEC/UK curves

    TD = Time Dial Setting for IEEE/US curves

  • 7/28/2019 7. Technical Data

    23/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 21/30

    IDMT Curve description Standard K Constant Constant L Constant

    Standard Inverse IEC 0.14 0.02

    Very Inverse IEC 13.5 1

    Extremely Inverse IEC 80 2

    Long Time Inverse UK 120 1

    Moderately Inverse IEEE 0.0515 0.02 0.114

    Very Inverse IEEE 19.61 2 0.491

    Extremely Inverse IEEE 28.2 2 0.1217

    Inverse US-C08 5.95 2 0.18

    Short Time Inverse US-C02 0.02394 0.02 0.01694

    IDMT Characteristics

    Name Range Step Size

    TMS 0.025 to 1.2 0.025

    Time Multiplier Settings for IEC/UK curves

    Name Range Step Size

    TD 0.5 to 15 0.1

    Time Dial Settings for IEEE/US curves

    6.3.3.1 Definite Time Characteristic

    Element Range Step Size

    All stages 0 to 100s 10ms

    6.3.3.2 Reset Characteristics

    Reset options for IDMT stages:

    Curve type Reset time delay

    IEC / UK curves DT only

    All other IDMT or DT

    The Inverse Reset characteristics are dependent upon the selected IEEE/US IDMT curve asshown in the table below. Thus if IDMT reset is selected the curve selection and Time Dialsetting will apply to both operate and reset.

    All inverse reset curves conform to the following formula:

    ( )t

    TD tr

    I Iset

    S

    Re=

    7 1

    Where

    tReset

    = reset time

    tr = constant

    I = measured current

    IS

    = current threshold setting

    = constant

    TD = Time Dial Setting (Same setting as that employed by IDMT curve)

  • 7/28/2019 7. Technical Data

    24/32

    P44x/EN TD/E33 Technical Data

    Page 22/30 MiCOM P441/P442 & P444

    IEEE/US IDMT Curve description Standard tr Constant Constant

    Moderately Inverse IEEE 0.0515 0.02

    Very Inverse IEEE 19.61 2

    Extremely Inverse IEEE 28.2 2

    Inverse US-C08 5.95 2

    Short Time Inverse US-C02 0.02394 0.02

    Inverse Reset Characteristics

    6.4 Negative sequence overcurrent protection

    Setting Range Step size

    I2> Current Set 0.08 - 4.0In 0.01In

    I2> time Delay 0 - 100s 0.01s

    Directional None/Fwd/Rev

    I2> Char Angle 95 - +95 1

    6.5 Broken Conductor Protection

    Settings Range Step size

    I2/I1 Setting 0.2 - 1.0 0.01

    I2/I1 Time Delay 0 - 100s 0.1s

    I2/I1 Trip Enabled / Disabled

    6.6 Earth Fault Overcurrent Protection

    6.6.1 Threshold Settings

    Setting Range Step Size

    IN>1 Current Set 0.08 - 4.0In 0.01In

    IN>2 Current Set 0.08 - 32In 0.01In

    6.6.2 Polarising Quantities For Earth Fault Measuring Elements

    The polarising quantity for earth fault elements can be either zero sequence or negativesequence values.

    Setting Range Step Size

    IN> Char angle 95 to +95 1

    6.6.3 Time Delay Characteristics

    The time delay options for the two earth fault elements are identical, stage 1 may beselected to be either IDMT or definite time. Stage 2 will provide a definite time delay. Thesettings and IDMT characteristics are identical to those specified for the phase overcurrentelements. The setting range for the definite time delayed element is as specified below:

    Definite Time Characteristic

    Element Range Step Size

    All stages 0 to 200s 0.01s

  • 7/28/2019 7. Technical Data

    25/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 23/30

    6.7 Zero sequence Power Protection (since B1.0)

    Threshold Settings

    Setting Range Step Size

    Po Status Enabled/Disabled. -

    Time Delay Fact. 0 2s 0.200s

    Fix Time Delay 0 10s 0.010s

    IN current set 0.05 - 4 In 0.01 In

    P0 Threshold 0.05IN - IN 0.1IN

    6.8 Channel Aided Directional Earth Fault Protection

    6.8.1 Threshold Settings

    Setting Range Step Size

    Polarisation Zero seq. / Neg. seq. -

    V> Voltage Set(Vn=100/120 V)

    0.500 - 20 V 0.010 V

    IN Forward 0.05 - 4 In 0.01 In

    Teleprotection Time delay 0 - 10s 0.1s

    Scheme logic Shared / Blocking / Permissive

    Tripping Any Phase / Three Phases

    6.9 Under Voltage Protection

    6.9.1 Threshold Settings

    Setting Range Step Size

    V

  • 7/28/2019 7. Technical Data

    26/32

    P44x/EN TD/E33 Technical Data

    Page 24/30 MiCOM P441/P442 & P444

    Setting Range Step Size

    DT setting 0 - 100s 0.01s

    TMS Setting (K) 0.5 - 100 0.5

    Definite time and TMS setting ranges

    6.10 Over Voltage Protection

    6.10.1 Threshold Settings

    Setting Range Step Size

    V>1 Voltage Set(Vn = 100/120V)

    60 - 185V 1V

    V>2 Voltage Set(Vn = 100/120V)

    60 - 185V 1V

    6.10.2 Time Delay Characteristics

    The Overvoltage measuring elements are followed by an independently selectable timedelay. The first stage has a time delay characteristics selectable as either Inverse Time orDefinite Time. The second stage has an associated Definite Time delay setting.

    Each measuring element time delay can be blocked by the operation of a user defined logic(optical isolated) input.

    The inverse characteristic is defined by the following formula :

    ( )t

    K

    M=

    1

    Where

    K = Time Multiplier Setting

    T = Operating time in seconds

    M = Applied input voltage / Relay setting voltage (Vs)

    Setting Range Step Size

    DT setting 0 - 100s 0.01s

    TMS Setting (K) 0.5 - 100s 0.5

    Definite time and TMS setting ranges

    6.11 Voltage Transformer Supervision

    Setting Range Step Size

    VTS Time Delay 1.0 - 20s 1s

    3 phase undervoltage threshold 10-70V 1V

    VTS I2> & I0> Inhibit 0 - In 0.01In

    Superimposed current Delta I> 0.01 - 5A 0.01 A

    6.12 Capacitive Voltage Transformer Supervision (since B1.0)

    Setting Range Step Size

    CVTS status Enabled / Disabled

    CVTS VN> 0.500 - 22V 0.500V

    CVTS Time Delay 0 300s 1s

  • 7/28/2019 7. Technical Data

    27/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 25/30

    6.13 Current Transformer Supervision

    Setting Range Step size

    CTS VN< Inhibit 0.5 - 22V (for Vn = 100/120V) 0.5V

    CTS IN> Set 0.08In - 4In 0.01In

    CTS Time Delay 0 - 10s 1s

    6.14 Undercurrent Element

    This element is used by the breaker fail and circuit breaker monitoring functions of the relay.

    Name Range Step size

    I< Current Set 0.05 3.2In 0.050In

    6.15 Breaker Fail Timers (TBF1 and TBF2)

    There are two stages of breaker fail that can be used to re-trip the breaker and back trip inthe case of a circuit breaker fail. The timers are reset if the breaker opens, this is generallydetected by the undercurrent elements. Other methods of detection can be employed forcertain types of trip (see Application notes Volume 1 Chapter 2).

    Timer Setting range Step

    tBF1 0 to 10s 0.005s

    tBF2 0 to 10s 0.005s

    CBF non Current reset I

  • 7/28/2019 7. Technical Data

    28/32

    P44x/EN TD/E33 Technical Data

    Page 26/30 MiCOM P441/P442 & P444

    7. MEASUREMENT SETTINGS

    7.1 Disturbance Recorder Settings

    Setting Range Step

    Record Length 0 - 10.5s 0.1s

    Trigger position 0 - 100% 0.1%

    Trigger mode Single / Extended

    Sample Rate 12 Samples/Cycle Fixed

    Digital Signals Selectable from logic inputs and outputs and internalsignals

    Trigger Logic Each of the digital inputs can be selected to trigger arecord

    7.2 Fault Locator Settings

    Setting Range Step size

    Mutual compensation factor 0 to 7.000 0.001

    Mutual compensation angle 0 to 360 1

  • 7/28/2019 7. Technical Data

    29/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 27/30

    8. CONTROL FUNCTION SETTINGS

    8.1 Communications Settings

    Front port Communication Parameters (Fixed)

    Protocol Courier

    Address 1

    Message format IEC60870FT1.2

    Baud rate 19200 bits/s

    Rear port settings Setting options Setting available for:

    Physical link RS485 or Fibre optic IEC only

    Remote address 0 - 255 (step 1) IEC / Courier

    Modbus address 1 - 247 (step 1) Modbus only

    Baud rate 9 600 or 19 200 bits/s IEC only

    Baud rate 9 600, 19 200 or 38 400 bits/s Modbus only

    Inactivity timer 1 - 30 minutes (step 1) All

    Parity Odd, Even or None Modbus only

    Measurement period 1 - 60 minutes (step 1) IEC only

    8.2 Auto-Reclose

    8.2.1 Options

    The Auto-recloser in the distance protection allows either single* or three pole for the firstshot. The following shots are three pole only. Due to the complexity of the logic theApplication notes should be referred to.

    NOTE: *P442 and P444 only

    8.2.2 Auto-recloser settings

    Setting Range Step Size

    AUTORECLOSE(Configuration Setting)

    ENABLE/DISABLE

    Number of Shots 1, 1/3, 1/3/3, 1/3/3/33, 3/3, 3/3/3, 3/3/3/3 1

    1P Dead Time 0.1 to 5s 0.01s

    3P Dead Time 0. 1 to 60s 0.01s

    Dead Time 2 1 to 3600s 1s

    Dead Time 3 1 to 3600s 1s

    Dead Time 4 1 to 3600s 1s

    Healthy Window 0.01 to 9999s 0.01s (in CB control)

    Reclaim Time 1 to 600s 1s

    Discrimination time 0.1 to 5s 0.01s

    A/R Inhibit Window 1 to 3600s 1s

  • 7/28/2019 7. Technical Data

    30/32

    P44x/EN TD/E33 Technical Data

    Page 28/30 MiCOM P441/P442 & P444

    Setting Range Step Size

    Block auto-recloser At T2At T3At TzpLoL Trip

    I2> TripI>1 TripI>2 TripV2 tripIN>1 TripIN>2 TripAided D.E.F Trip

    AR Close pulse length 0.1 to 10s 0.1s

    Check synchronic settings

    Setting Range Step Size

    C/S Check Scheme for A/R Bit 0: Live Bus/Dead Line,Bit 1: Dead Bus/Live LineBit 2: Live Bus/Live Line.

    Dead Bus/Dead Line with special PSL

    C/S Check Scheme for ManCB

    Bit 0: Live Bus/Dead Line,Bit 1: Dead Bus/Live LineBit 2: Live Bus/Live Line.

    Dead Bus/Dead Line with special PSL

    V< Dead Line 5-30V 1V

    V> Live Line 30-120V 1V

    V< Dead Bus 5-30V 1V

    V> Live Bus 30-120V 1V

    Diff Voltage 0.5-40V 0.1V

    Diff Frequency 0.02-1Hz 0.01Hz

    Diff Phase 5-90 2.5

    Bus-Line Delay 0.1 to 2s 0.1s

    8.3 Circuit Breaker State Monitoring

    The relay can monitor the state of the circuit breaker using either a 52a or 52b signal, it ispossible to select which of these is being used on the relay menu. If the menu is used toselect the Both 52a and 52b option is selected then a discrepancy alarm can be detected. Ifthese contacts remain simultaneously open or simultaneously closed for >5s, then the CBStatus alarm will be indicated.

  • 7/28/2019 7. Technical Data

    31/32

    Technical Data P44x/EN TD/E33

    MiCOM P441/P442 & P444 Page 29/30

    8.4 Circuit Breaker Control

    Name Range Step size

    CB Control by Disabled/Local/

    Remote/Local+Remote/Opto/Opto+local/Opto+Remote/Opto+Rem+local

    Manual close pulse time 0.1 to 10s 0.01s

    Trip pulse time 0.1 to 5s 0.01s

    Man Close Delay 0.01 to 600s 0.01s

    Healthy Windows 0.01 to 9999 0.01

    C/S Window 0.01 to 9999 0.01AR single pole Disabled/Enabled -

    AR three pole Disabled/Enabled -

    8.5 Circuit Breaker Condition Monitoring

    8.5.1 Maintenance alarm settings

    Name Range Step size

    I^ Maintenance 1 to 25000A 1 Summatedbroken current

    No. of CB Ops Maint 1- 10000 1

    CB Time Maint 5 - 500ms 1ms Circuit breakeropening time

    8.5.2 Lockout Alarm Settings

    Name Range Step size

    I^ threshold 1 to 25000 1

    No. of CB Ops Lock 1- 10000 1

    CB Time Lockout 5 - 500ms 1ms

    Fault Freq Count 0 to 9999 1Fault Freq Time 0 to 9999s 1s

    Lockout reset by: CB close, User Interface

    Manual close reset delay 0.01 to 600s 0.01s

  • 7/28/2019 7. Technical Data

    32/32

    P44x/EN TD/E33 Technical Data

    Page 30/30 MiCOM P441/P442 & P444

    8.6 Programmable Logic

    The programmable logic is not editable from the relay menu, a dedicated support package isprovided as part of the MiCOM S1 support software. This is a graphical editor for theprogrammable logic. The features of the programmable logic are more fully described withinthe application section of the user manual. As part of the logic each output contact has a

    programmable conditioner/timer, there are also eight general purpose timers for use in thelogic.

    The output conditioners and the general-purpose timers have the following setting range:

    Time Range Step size

    t1 to t8 0 to 4 hours 0.001s

    8.7 CT and VT Ratio Settings

    The primary and secondary rating can be independently set for each set of CT or VT inputs,for example the earth fault CT ratio can be different to that used for the phase currents.

    Primary range Secondary range

    Current transformer 1 - 30000 Ampsstep size 1 A

    1 or 5 Amps

    Voltage transformer 100 V - 1000 kVstep size 1 V

    80 - 140 Vstep size 1 V