774 sample

Upload: luis-murillo

Post on 04-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 774 Sample

    1/11

    Introduction v

    TABLE OF CONTENTS

    Chapter 1 Transformer Concepts

    Introduction to Distribution Transformers . . . . . . . . . . . . . . . 1The Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Formulas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Power Triangle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Transformer Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Transformer Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Transformer Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Transformer Terminal Designations . . . . . . . . . . . . . . . . . . . . . 9Polarity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Wye, Delta Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Transformer Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Completely Self-Protected Transformers . . . . . . . . . . . . . . . . . . 17Ferroresonance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Vectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Why , or 1.73? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Angular Displacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Paralleling Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    Chapter 2 Transformer Connections

    Index to the Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Notes to the Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . 28Single-Phase Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Transformer BanksWye - Wye . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Wye - Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Open Wye - Open Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Delta - Wye . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Delta - Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    Three-Phase Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    3

  • 7/29/2019 774 Sample

    2/11

    vi Distribution Transformer Handbook

    Chapter 3 Installing Transformers

    Lifting and Handling Transformers . . . . . . . . . . . . . . . . . . . . . . 45Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    Safety Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Installation Procedure for Overhead Transformers . . . . . . . . . 50Backfeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Single-Phase Transformer Loads . . . . . . . . . . . . . . . . . . . . . . . . 52Load Checks on Single-Phase Transformers . . . . . . . . . . . . . . . 53Three-Phase Bank Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Load Checks on Delta, Wye Banks . . . . . . . . . . . . . . . . . . . . . . . 55Make or Break Parallel Circuits at Transformer Banks . . . . . . 57

    Phasing and Paralleling Three-Phase Installations . . . . . . . . . . 58Minimum Pole Class Guidelines . . . . . . . . . . . . . . . . . . . . . . . . 62Strength of Wood Poles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Grounding Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Fusing Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Padmounted Transformer Installations . . . . . . . . . . . . . . . . . . . 73Safety Clearances Around Padmount Transformers . . . . . . . . 77Work Clearances Around Padmount Transformers . . . . . . . . . . 78Guard Posts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

  • 7/29/2019 774 Sample

    3/11

    16 Distribution Transformer Handbook

    Arresters create a safe, low-resistance path for lightning to get toground, that bypasses the transformer. Lightning strikes can exceedone million volts, so the connections at the arrester must be tight,

    and the ground wire properly sized for surge currents that accompanythese high voltages.

    Transformer protective devices.

    CutoutArrester

    Shunts lightning andother high voltagespikes to ground

    Discourages wildlife fromresting on a transformer

    primary wire and shorting a high-side

    line to ground

    Fuse opens theprimary line when

    current is excessive

    Allows excessive tankpressure to escape to

    the atmosphere

    Wildlife protector Pressure relief valve

  • 7/29/2019 774 Sample

    4/11

    32 Distribution Transformer Handbook

    C

    N

    n

    B

    A

    c

    b

    a

    A

    B

    CN

    a

    x3 x1x2

    b

    c

    n

    A

    B

    C

    N

    n

    a

    b

    c

    Three-phase, four-wirewye primary

    Three-phase, four-wirewye secondary

    0

    angular displacement

    Wye-Wye

    Three-phase, four-wire wye primaryThree-phase, four-wire wye secondary

    Secondary services120 volts, phase-to-neutral208 volts, phase-to-phase

    H1

    H2 H2

    x3 x1x2

    H1

    x3 x1x2

    H1

    H2

  • 7/29/2019 774 Sample

    5/11

    Transformer Connections 35

    C

    B

    A

    b

    n

    c

    a

    A

    N

    B

    C

    -a

    H1

    x2x1x3

    -b

    -c208 V

    n

    AB

    C

    -a

    -b

    -c

    n

    Three-phase, three-wirewye primary

    Three-phase, four-wiredelta secondary

    210 angular displacement

    H2

    Do notpermanently ground

    H1

    x2x1x3

    H2H1

    x2x1x3

    H2

    Wye-Delta

    Three-phase, three-wire wye primaryThree-phase, four-wire delta secondary

    Secondary services240 volts, phase-to-phase120 volts, b-to-neutral, c-to-neutral208 volts, a-to-neutral

    Float the primary neutral

    When concerned about ferroresonance, install a

    temporary grounding jumper between the floatingprimary neutral and ground, when switching thetransformer bank in or out of service.

  • 7/29/2019 774 Sample

    6/11

    40 Distribution Transformer Handbook

    A

    BC

    a

    H1

    x2x1x3

    b

    c

    n

    A

    B

    C

    a

    b

    c

    n

    H2H1

    x2x1x3

    H2H1

    x2x1x3

    H2

    Delta-DeltaThree-phase, three-wire delta primaryThree-phase, four-wire delta secondary

    Secondary services240 volts, phase-to-phase120 volts, a-to-neutral, b-to-neutral208 volts, c-to-neutral

    Three-phase,four-wire delta secondary

    0 angular displacement

    a

    n

    c

    b

    Three-phase,three-wire delta primary

    A C

    B

    208 V

  • 7/29/2019 774 Sample

    7/11

    45

    CHAPTER

    INSTALLING TRANSFORMERS

    LIFTING AND HANDLING TRANSFORMERS

    Lift overhead transformers by their lifting lugs only, using a nylon

    web sling or a rope sling. Sling angles of greater than 45 arepreferred. Avoid sling angles of less than 30 because of the hightension in the sling. If the vertical clearance above the transformer islimited, use a spreader bar in place of a sling, and install cover-up onany energized conductors nearby.

    Do not lift a transformer from beneath a bushing, pressure reliefvalve, drain plug, or any other attachment not specifically designedfor lifting.

    Do not move or shift a transformer by grasping the bushings, fins,or plugs. Porcelain bushings can be damaged during handling in waysnot visually obvious, then fail when the unit is put into service.

    The windings can be damaged if the transformer is dropped or

    severely jolted.When handling a transformer, take care to not damage the tankfinish. Paint scratches can lead to rust.

    Slingangle

    3

  • 7/29/2019 774 Sample

    8/11

    46 Distribution Transformer Handbook

    NAMEPLATES

    Each transformer has a manufacturers nameplate with importanttechnical information.

    The nameplate shown here is for an overhead single-phasetransformer.

    1 HV High-voltage (primary) winding. The low number (7200)is the phase-to-neutral (coil) voltage. The high number (12470)is the phase-to-phase voltage. This transformer is for installationin a wye system. Note: On nameplates for padmount transform-ers and single-bushing overhead transformers, the low numberappears last instead of first.

    2 LV Low-voltage (secondary) winding delivers 120 and 240volts.

    HV TAP POSIT ION

    100%

    97.5%

    95%

    92.5%

    90%

    1 OR A

    2 OR B

    3 OR C

    4 OR D

    5 OR E

    NON-PCB MINERAL OIL

    WHEN MANUFACTURED CONTAINED

    LESS THAN 1PPM PCB

    GAL 11%IZ WT 202 LBHV AL 95 BIL

    HV

    CUSTI.D.

    LV

    10 60 HZ

    CLASS OA

    READ INSTALLATION AND OPERATION INSTRUCTIONS S201-10-1

    LV AL 50 BIL 65 C RISE

    A D D P O L . 1.8

    E 211072 05W5

    7200 / 12470Y

    120/240 CP123456790

    000000556MFG DATE AUG 98MS 85C

    NOTES:

    CAT

    SER

    MFG

    KVA

    TK

    5

    CP

    C B C B

    DA D IA

    x1x2x3 x1

    H1 H2

    x2x3

    SW

    1

    4

    5

    6

    7

    2 9

    14

    3

    10

    11

    12

    13

    8

  • 7/29/2019 774 Sample

    9/11

    Installing Transformers 53

    LOAD CHECKS ON SINGLE-PHASE TRANSFORMERS

    Quick Check

    To determine the approximate kVAload on a single-phase transformer:

    1. Measure the current in the twoline conductors

    2. Add the amps together3. Multiply by 1204. Move the decimal point three

    places to the leftExample: If the readings are55A and 60A:

    55A+60A

    115A

    115 120 = 13800

    The load is 13.8 kVA

    Complete Calculation

    Calculate the load on each half of the transformer separately, thenadd them together to determine the full load.

    Example: The readings on a 25 kVA transformer are 30A and 160A:

    The total load is within the transformer rating, but one secondarywinding exceeds 12.5 kVA and is severely overloaded.

    30 120

    1,000+

    160 120

    1,000

    = 3.6 + 19.2

    =22.8 kVA

    Total load in kVA =

    Total load in kVA =current a voltage a-to-n

    1,000

    current b voltage b-to-n1,000

    +

    120V

    240V

    120V

    an

    b

    Note: Dont use this quick check if there isconsiderable imbalance between the twocurrent readings. Instead, use the CompleteCalculation, and verify that each load is less

    than half the kVA rating of the transformer.

  • 7/29/2019 774 Sample

    10/11

    Grounding Single-Phase Two-Bushing Transformers,Neutral on the Crossarm

    Recommendation: Keep the primary neutral separate and distinct fromthe many other connections at the secondary rack. Failure to keep the

    primary neutral separated introduces the high risk of inadvertentlycutting the primary neutral while the transformer is energized. This will

    result in a primary voltage across the cut!

    68 Distribution Transformer Handbook

    Tankgrounding

    lug

    Poleground

    Secondary neutral

    Connect

    serviceneutralto tail

  • 7/29/2019 774 Sample

    11/11

    Installing Transformers 73

    PADMOUNT TRANSFORMER INSTALLATIONS

    The transformers illustrated here are typical, but many differentconfigurations exist.

    All padmount transformers have primary connections on the leftside of the panel, secondary connections on the right.

    Single-phase minipad transformer labeling.

    Single-phase minipad transformer layout.

    75kVA rating

    Company ID

    Landscaping

    suggestions

    Grid number

    Warning High Voltage

    Secondaryvoltage

    Used onreducedflammablity

    transformersonly

    Lock

    Removable sill

    Flip-top hoodopens 180

    NEMA safety labelsLock mechanism

    E e for adlock

    X1

    X3

    X2

    H1B

    H1A

    Removable ground strap

    Low voltage threadedstud bushings

    Fill plug

    Pressure relief valve

    k ground provision

    Drain plug

    High voltagebushing wells

    Parking stand forelbow connectors

    Externally accessibleexpulsion fusewith drip cup

    X3

    X1

    X2

    H1B

    H1A