132 KV Nokhar / Folder / 7SA611 V4.6 MLFB: 7SA61114AB227PR7 Parameter set version: V04.65.01 Device path: C:\Siemens\Digsi4\D4PROJ\132_kv_n\P7DI\GV\SD\00000001 Author: Creation date: 13.08.14 10:06:41 Last modified: 13.08.14 10:06:52 Operating mode: Offline Comment: Setting values in: Secondary value description P R I N T - C O N T E N T S 1 Device Configuration 2 2 General Device Settings 3 2.1 Group Device 3 3 Power System Data 1 4 3.1 Group Power System Data 1; Group Transformers 4 3.2 Group Power System Data 1; Group Power System 4 3.3 Group Power System Data 1; Group Breaker 4 4 Settings groups 5 4.1 Group Power System Data 2; Group Power System 5 4.2 Group Power System Data 2; Group Line Status 5 4.3 Group Power System Data 2; Group Trip 1-/3-pole 5 4.4 Group Distance protection, general settings; Group General 5 4.5 Group Distance protection, general settings; Group Earth faults 6 4.6 Group Distance protection, general settings; Group Time Delays 6 4.7 Group Distance zones (quadrilateral); Group Zone Z1 6 4.8 Group Distance zones (quadrilateral); Group Zone Z1B-exten. 6 4.9 Group Distance zones (quadrilateral); Group Zone Z2 7 4.10 Group Distance zones (quadrilateral); Group Zone Z3 7 4.11 Group Distance zones (quadrilateral); Group Zone Z4 7 4.12 Group Distance zones (quadrilateral); Group Zone Z5 7 4.13 Group Backup overcurrent; Group General 7 4.14 Group Backup overcurrent; Group I>> 8 4.15 Group Backup overcurrent; Group I> 8 4.16 Group Backup overcurrent; Group Inverse 8 4.17 Group Backup overcurrent; Group I - STUB 8 4.18 Group Demand Measurement Setup; Group Measurement 8 4.19 Group Min/Max Measurement Setup; Group Measurement 9 4.20 Group Measurement Supervision; Group Balance / Summ. 9 4.21 Group Measurement Supervision; Group Fuse Fail. Mon. 9 4.22 Group Measurement Supervision; Group VT mcb 9 4.23 Group Measurement Supervision; Group Load Angle 9 4.24 Group Fault Locator; Group Fault Locator 9 SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31 Page 1 of 10

Upload: cuami

Post on 22-Nov-2015

133 views

Category:

Documents


4 download

DESCRIPTION

System Protection

TRANSCRIPT

  • 132 KV Nokhar / Folder / 7SA611 V4.6

    MLFB: 7SA61114AB227PR7Parameter set version: V04.65.01Device path: C:\Siemens\Digsi4\D4PROJ\132_kv_n\P7DI\GV\SD\00000001Author:Creation date: 13.08.14 10:06:41Last modified: 13.08.14 10:06:52Operating mode: OfflineComment:Setting values in: Secondary value description

    P R I N T - C O N T E N T S1 Device Configuration 22 General Device Settings 32.1 Group Device 33 Power System Data 1 43.1 Group Power System Data 1; Group Transformers 43.2 Group Power System Data 1; Group Power System 43.3 Group Power System Data 1; Group Breaker 44 Settings groups 54.1 Group Power System Data 2; Group Power System 54.2 Group Power System Data 2; Group Line Status 54.3 Group Power System Data 2; Group Trip 1-/3-pole 54.4 Group Distance protection, general settings; Group General 54.5 Group Distance protection, general settings; Group Earth faults 64.6 Group Distance protection, general settings; Group Time Delays 64.7 Group Distance zones (quadrilateral); Group Zone Z1 64.8 Group Distance zones (quadrilateral); Group Zone Z1B-exten. 64.9 Group Distance zones (quadrilateral); Group Zone Z2 74.10 Group Distance zones (quadrilateral); Group Zone Z3 74.11 Group Distance zones (quadrilateral); Group Zone Z4 74.12 Group Distance zones (quadrilateral); Group Zone Z5 74.13 Group Backup overcurrent; Group General 74.14 Group Backup overcurrent; Group I>> 84.15 Group Backup overcurrent; Group I> 84.16 Group Backup overcurrent; Group Inverse 84.17 Group Backup overcurrent; Group I - STUB 84.18 Group Demand Measurement Setup; Group Measurement 84.19 Group Min/Max Measurement Setup; Group Measurement 94.20 Group Measurement Supervision; Group Balance / Summ. 94.21 Group Measurement Supervision; Group Fuse Fail. Mon. 94.22 Group Measurement Supervision; Group VT mcb 94.23 Group Measurement Supervision; Group Load Angle 94.24 Group Fault Locator; Group Fault Locator 9

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 1 of 10

  • 1 Device ConfigurationNo. Function Scope

    0103 Setting Group Change Option Disabled0110 Trip mode 1-/3pole0114 Distance protection pickup program Z< (quadrilateral)0120 Power Swing detection Disabled0121 Teleprotection for Distance prot. Disabled0122 DTT Direct Transfer Trip Disabled0124 Instantaneous HighSpeed SOTF Overcurrent Disabled0125 Weak Infeed (Trip and/or Echo) Disabled0126 Backup overcurrent Time Overcurrent Curve IEC0130 Sensitive Earth Flt.(comp/ isol. starp.) Disabled0131 Earth fault overcurrent Disabled0132 Teleprotection for Earth fault overcurr. Disabled0133 Auto-Reclose Function Disabled0134 Auto-Reclose control mode with Trip and Action time0135 Synchronism and Voltage Check Disabled0136 Over / Underfrequency Protection Disabled0137 Under / Overvoltage Protection Disabled0138 Fault Locator Enabled0139 Breaker Failure Protection Disabled0140 Trip Circuit Supervision Disabled0142 Thermal overload protection Disabled

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 2 of 10

  • 2 General Device Settings2.1 Group Device

    No. Settings Value Group

    0610 Fault Display on LED / LCD Display Targets on TRIP only All0625A Minimum hold time of lachted LEDs 0 min All0640 Start image Default Display image 1 All

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 3 of 10

  • 3 Power System Data 13.1 Group Power System Data 1; Group TransformersNo. Settings Value Group

    0201 CT Starpoint towards Line All0203 Rated Primary Voltage 132.0 kV All0204 Rated Secondary Voltage (Ph-Ph) 110 V All0205 CT Rated Primary Current 800 A All0206 CT Rated Secondary Current 1A All0210 U4 voltage transformer is not connected All0211 Matching ratio Phase-VT To Open-Delta-VT 1.73 All0215 Matching ratio Usy1 / Usy2 1.00 All0220 I4 current transformer is Neutral Current (of the protected line) All0221 Matching ratio I4/Iph for CT's 1.000 All

    3.2 Group Power System Data 1; Group Power SystemNo. Settings Value Group

    0207 System Starpoint is Solid Earthed All0230 Rated Frequency 50 Hz All0235 Phase Sequence L1 L2 L3 All0236 Distance measurement unit km All0237 Setting format for zero seq.comp. format Zero seq. comp. factors RE/RL and XE/XL All

    3.3 Group Power System Data 1; Group BreakerNo. Settings Value Group

    0240A Minimum TRIP Command Duration 0.10 sec All0241A Maximum Close Command Duration 0.10 sec All0242 Dead Time for CB test-autoreclosure 0.10 sec All

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 4 of 10

  • 4 Settings groups4.1 Group Power System Data 2; Group Power SystemNo. Settings Value Group

    1103 Measurement: Full Scale Voltage (100%) 132.0 kV A1104 Measurement: Full Scale Current (100%) 800 A A1105 Line Angle 81 A1211 Angle of inclination, distance charact. 81 A1107 P,Q operational measured values sign not reversed A1110 x' - Line Reactance per length unit 0.3921 Ohm / km A1111 Line Length 22.2 km A1116 Zero seq. comp. factor RE/RL for Z1 3.97 A1117 Zero seq. comp. factor XE/XL for Z1 0.60 A1118 Zero seq. comp.factor RE/RL for Z1B...Z5 3.97 A1119 Zero seq. comp.factor XE/XL for Z1B...Z5 0.60 A

    4.2 Group Power System Data 2; Group Line StatusNo. Settings Value Group

    1130A Pole Open Current Threshold 0.10 A A1131A Pole Open Voltage Threshold 30 V A1132A Seal-in Time after ALL closures 0.05 sec A1133A minimal time for line open before SOTF 0.25 sec A1134 Recognition of Line Closures with Manual Close BI only A1135 RESET of Trip Command with Pole Open Current Threshold only A1136 open pole detector with measurement (U/I,trip,pickup,CBaux) A1140A CT Saturation Threshold 20.0 A A1150A Seal-in Time after MANUAL closures 0.30 sec A1151 Manual CLOSE COMMAND generation NO A1152 MANUAL Closure Impulse after CONTROL All

    4.3 Group Power System Data 2; Group Trip 1-/3-poleNo. Settings Value Group

    1155 3 pole coupling with Trip A1156A Trip type with 2phase faults 3pole A

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 5 of 10

  • 4.4 Group Distance protection, general settings; Group GeneralNo. Settings Value Group

    1201 Distance protection ON A1202 Phase Current threshold for dist. meas. 0.10 A A1211 Angle of inclination, distance charact. 81 A1208 Series compensated line NO A1232 Instantaneous trip after SwitchOnToFault Inactive A1241 R load, minimum Load Impedance (ph-e) 43.200 Ohm A1242 PHI load, maximum Load Angle (ph-e) 45 A1243 R load, minimum Load Impedance (ph-ph) 43.200 Ohm A1244 PHI load, maximum Load Angle (ph-ph) 45 A1317A Single pole trip for faults in Z2 NO A1357 Z1B enabled before 1st AR (int. or ext.) NO A

    4.5 Group Distance protection, general settings; Group Earth faults

    No. Settings Value Group

    1203 3I0 threshold for neutral current pickup 0.10 A A1204 3U0 threshold zero seq. voltage pickup 5 V A1207A 3I0>-pickup-stabilisation (3I0> /Iphmax) 0.10 A1209A criterion of earth fault recognition 3I0> OR 3U0> A1221A Loop selection with 2Ph-E faults block leading ph-e loop A

    4.6 Group Distance protection, general settings; Group Time DelaysNo. Settings Value Group

    1210 Condition for zone timer start with distance pickup A1305 T1-1phase, delay for single phase faults 0.00 sec A1306 T1multi-ph, delay for multi phase faults 0.00 sec A1315 T2-1phase, delay for single phase faults 0.30 sec A1316 T2multi-ph, delay for multi phase faults 0.30 sec A1325 T3 delay 0.70 sec A1335 T4 delay 0.90 sec A1345 T5 delay 1.20 sec A1355 T1B-1phase, delay for single ph. faults 0.00 sec A1356 T1B-multi-ph, delay for multi ph. faults 0.00 sec A

    4.7 Group Distance zones (quadrilateral); Group Zone Z1No. Settings Value Group

    1301 Operating mode Z1 Forward A1302 R(Z1), Resistance for ph-ph-faults 0.679 Ohm A1303 X(Z1), Reactance 4.440 Ohm A1304 RE(Z1), Resistance for ph-e faults 12.679 Ohm A1305 T1-1phase, delay for single phase faults 0.00 sec A1306 T1multi-ph, delay for multi phase faults 0.00 sec A1307 Zone Reduction Angle (load compensation) 0 A

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 6 of 10

  • 4.8 Group Distance zones (quadrilateral); Group Zone Z1B-exten.No. Settings Value Group

    1351 Operating mode Z1B (overrreach zone) Forward A1352 R(Z1B), Resistance for ph-ph-faults 0.959 Ohm A1353 X(Z1B), Reactance 6.268 Ohm A1354 RE(Z1B), Resistance for ph-e faults 12.959 Ohm A1355 T1B-1phase, delay for single ph. faults 0.00 sec A1356 T1B-multi-ph, delay for multi ph. faults 0.00 sec A1357 Z1B enabled before 1st AR (int. or ext.) NO A

    4.9 Group Distance zones (quadrilateral); Group Zone Z2No. Settings Value Group

    1311 Operating mode Z2 Forward A1312 R(Z2), Resistance for ph-ph-faults 0.959 Ohm A1313 X(Z2), Reactance 6.268 Ohm A1314 RE(Z2), Resistance for ph-e faults 12.959 Ohm A1315 T2-1phase, delay for single phase faults 0.30 sec A1316 T2multi-ph, delay for multi phase faults 0.30 sec A1317A Single pole trip for faults in Z2 NO A

    4.10 Group Distance zones (quadrilateral); Group Zone Z3No. Settings Value Group

    1321 Operating mode Z3 Forward A1322 R(Z3), Resistance for ph-ph-faults 1.200 Ohm A1323 X(Z3), Reactance 7.835 Ohm A1324 RE(Z3), Resistance for ph-e faults 13.300 Ohm A1325 T3 delay 0.70 sec A

    4.11 Group Distance zones (quadrilateral); Group Zone Z4No. Settings Value Group

    1331 Operating mode Z4 Inactive A1332 R(Z4), Resistance for ph-ph-faults 12.000 Ohm A1333 X(Z4), Reactance 12.000 Ohm A1334 RE(Z4), Resistance for ph-e faults 12.000 Ohm A1335 T4 delay 0.90 sec A

    4.12 Group Distance zones (quadrilateral); Group Zone Z5No. Settings Value Group

    1341 Operating mode Z5 Non-Directional A1342 R(Z5), Resistance for ph-ph-faults 1.758 Ohm A1343 X(Z5)+, Reactance for Forward direction 11.491 Ohm A1344 RE(Z5), Resistance for ph-e faults 13.758 Ohm A1345 T5 delay 1.20 sec A1346 X(Z5)-, Reactance for Reverse direction 0.400 Ohm A

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 7 of 10

  • 4.13 Group Backup overcurrent; Group GeneralNo. Settings Value Group

    2601 Operating mode ON:only active with Loss of VT sec. cir. A2680 Trip time delay after SOTF 0.00 sec A

    4.14 Group Backup overcurrent; Group I>>No. Settings Value Group

    2610 Iph>> Pickup 2.00 A A2611 T Iph>> Time delay 0.30 sec A2612 3I0>> Pickup 0.50 A A2613 T 3I0>> Time delay 2.00 sec A2614 Instantaneous trip via Teleprot./BI YES A2615 Instantaneous trip after SwitchOnToFault NO A

    4.15 Group Backup overcurrent; Group I>No. Settings Value Group

    2620 Iph> Pickup 1.50 A A2621 T Iph> Time delay 0.50 sec A2622 3I0> Pickup 0.20 A A2623 T 3I0> Time delay 2.00 sec A2624 Instantaneous trip via Teleprot./BI NO A2625 Instantaneous trip after SwitchOnToFault NO A

    4.16 Group Backup overcurrent; Group InverseNo. Settings Value Group

    2640 Ip> Pickup oo A A2642 T Ip Time Dial 0.50 sec A2646 T Ip Additional Time Delay 0.00 sec A2650 3I0p Pickup oo A A2652 T 3I0p Time Dial 0.50 sec A2656 T 3I0p Additional Time Delay 0.00 sec A2660 IEC Curve Normal Inverse A2670 Instantaneous trip via Teleprot./BI NO A2671 Instantaneous trip after SwitchOnToFault NO A

    4.17 Group Backup overcurrent; Group I - STUBNo. Settings Value Group

    2630 Iph> STUB Pickup 1.50 A A2631 T Iph STUB Time delay 0.30 sec A2632 3I0> STUB Pickup 0.20 A A2633 T 3I0 STUB Time delay 2.00 sec A2634 Instantaneous trip via Teleprot./BI NO A2635 Instantaneous trip after SwitchOnToFault NO A

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 8 of 10

  • 4.18 Group Demand Measurement Setup; Group MeasurementNo. Settings Value Group

    2801 Demand Calculation Intervals 60 Min per., 1 Sub. A2802 Demand Synchronization Time On the Hour A

    4.19 Group Min/Max Measurement Setup; Group MeasurementNo. Settings Value Group

    2811 Automatic Cyclic Reset Function YES A2812 MinMax Reset Timer 0 min A2813 MinMax Reset Cycle Period 7 day(s) A2814 MinMax Start Reset Cycle in 1 Days A

    4.20 Group Measurement Supervision; Group Balance / Summ.No. Settings Value Group

    2901 Measurement Supervision ON A2902A Voltage Threshold for Balance Monitoring 50 V A2903A Balance Factor for Voltage Monitor 0.75 A2904A Current Balance Monitor 0.50 A A2905A Balance Factor for Current Monitor 0.50 A2906A Summated Current Monitoring Threshold 0.10 A A2907A Summated Current Monitoring Factor 0.10 A2908A T Balance Factor for Voltage Monitor 5 sec A2909A T Current Balance Monitor 5 sec A

    4.21 Group Measurement Supervision; Group Fuse Fail. Mon.No. Settings Value Group

    2910 Fuse Failure Monitor ON A2911A Minimum Voltage Threshold U> 30 V A2912A Maximum Current Threshold I< 0.10 A A2913A Maximum Voltage Threshold U< (3phase) 5 V A2914A Delta Current Threshold (3phase) 0.10 A A2915 Voltage Failure Supervision with current supervision A2916A Delay Voltage Failure Supervision 3.00 sec A

    4.22 Group Measurement Supervision; Group VT mcbNo. Settings Value Group

    2921 VT mcb operating time 0 ms A

    4.23 Group Measurement Supervision; Group Load AngleNo. Settings Value Group

    2941 Limit setting PhiA 200 A2942 Limit setting PhiB 340 A2943 Minimum value I1> 0.05 A A2944 Minimum value U1> 20 V A

    SIMATIC 132 KV Nokhar / Folder / 7SA611 V4.6/7SA611 13.08.14 12:15:31

    Page 9 of 10

  • 4.24 Group Fault Locator; Group Fault LocatorNo. Settings Value Group

    3802 Start fault locator with Pickup A3806 Load Compensation NO A