7th international fire sprinkler conference & exhibition, copenhagen, 24-25 june 2008 protection...
TRANSCRIPT
![Page 1: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/1.jpg)
7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008
Protection of Cultural Resources
Sprinkler Protection for Historic Wood churches
Magnus Arvidson
Department of Fire Technology
SP Technical Research Institute of Sweden
![Page 2: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/2.jpg)
The objective of the project
Gather relevant fire statistics and examples of illustrative fires or attempts to start fires.
Summarize lessons learned and practical experience from recent fire sprinkler installations.
Identify issues where additional research, testing or development work is needed.
The full report, ”An overview of fire protection of Swedish wooden churches”, SP Report 2006:42 may be downloaded from www.sp.se.
![Page 3: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/3.jpg)
Fire is historically the main reason for damage
During almost 800 years, 1193 – 1984, a total of 524 churches and chapels in Sweden were damaged by fire, war, plundering, collapse, storm, snow, etc.
In total, 447 (85%) were damaged or destroyed by fire.
A total of 106 of these fires
occurred due to lightning.
![Page 4: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/4.jpg)
Examples from recent years
Katarina church (1990)Rörbäcksnsäs (1992)Salabacke (1993)Lundby (1993)Trönö (1998)Sura old church (1998)Skaga chapel (2000)Bäckaby old church (2000)Södra Råda (2001)Ryssby (2001)Ledsjö (2004)Ramnäs (2006)Älvestad (2007)Öjebyns kyrkstad, Piteå (2007)
Älvestads church March 29, 2007Photo: Johnny Gustavsson
![Page 5: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/5.jpg)
Example: The Södra Råda church (erected c. 1310)
Photos: The Swedish National Heritage Board
![Page 6: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/6.jpg)
Unique and invaluable wall- and ceiling paintings
![Page 7: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/7.jpg)
Highest artistic quality (paintings from 1323 and 1494)
![Page 8: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/8.jpg)
Destroyed in a fire in November 2001
The fire was deliberately started.
![Page 9: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/9.jpg)
System installation case studies in nine churches
Hedareds stave church Frödinge church Älgarås church Habo church Fröskog Skållerud + three additional churches
Objective: Summarise lessons learned and practical experience.
![Page 10: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/10.jpg)
Six of the studied churches (year of installation)
Hedareds Stave Church (2004) Frödinge (2007) Älgarås (2005)
Habo (2006) Fröskog (2006) Skållerud (2006)
![Page 11: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/11.jpg)
The ’typical’ system installation
Water supply: Pump unit and water reservoir positioned in a separate building adjacent to the church.
Complete protection of the interior.
Complete protection inside attics, bell towers and other concealed spaces.
Protection of the exterior. Primarily facades, in some cases also the roof.
![Page 12: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/12.jpg)
Separate buildings house the water supply
Hedareds stave church Habo church
Fröskog church Älgarås church
![Page 13: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/13.jpg)
Water supply equipment
Fröskog church
Habo church Habo church
Fröskog church
![Page 14: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/14.jpg)
Älgarås church (interior)
![Page 15: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/15.jpg)
Habo church (interior)
![Page 16: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/16.jpg)
Frödinge church (attic)
![Page 17: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/17.jpg)
Fire detection systems for facades and roofs
Habo church
Fröskog churchFröskog church
Hedared stave church
![Page 18: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/18.jpg)
Sprinkler protection of facades and roofs
Älgarås church
![Page 19: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/19.jpg)
Sprinkler protection of facades and roofs
Habo church
![Page 20: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/20.jpg)
Sprinkler protection of facades and roofs
Skållerud church
![Page 21: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/21.jpg)
Sprinkler protection of facades and roofs
Photo: Jan G Andersson
Älgarås church
![Page 22: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/22.jpg)
Sprinkler protection of facades and roofs
Habo church
![Page 23: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/23.jpg)
Experiences from the installations
Aesthetical aspects important. All installations are impressively discreet.
The level of system complexity is in some cases high.
The use of antifreeze solutions may be questioned.
Functional tests are essential to discover troubles.
Unintentional activations are quite common.
Unintentional fire alarms are quite common.
Inspection, tests and maintenance are expensive.
![Page 24: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/24.jpg)
Discreet installations
Älgarås church
Habo church
Habo church
Hedareds stave church
![Page 25: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/25.jpg)
The level of system complexity in some cases high
Different systems for interior vs. exterior.
Different system types; wet-pipe with antifreeze, dry-pipe, deluge, etc for different parts of the churches.
Different fire detection techniques; aspirating systems, linear heat detection wires, etc.
New technical solutions, previously not used; gas driven pump units, flushing of piping with compressed air, new nozzle designs, etc.
![Page 26: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/26.jpg)
The level of system complexity in some cases high
The attic of Habo church
![Page 27: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/27.jpg)
Drainage of the system - special solutions.
Y-connections instead of T-connections for pendent nozzles. Compressed air is used to flush the system piping.
Fröskog churchFrödinge church
![Page 28: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/28.jpg)
The use of antifreeze solutions may be questioned
Careless use of antifreeze in Habo church.
![Page 29: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/29.jpg)
Functional tests essential to discover troubles
Several cases documented where systems have failed to operate during functional tests:
1. Pressure drop inside pneumatic pilot line not high enough to open a deluge valve.
2. Component failure in alarm panel = solenoid valve of a pre-action system never opened.
3. Electrical motor protector activated and stopped a pump during fill-up of the system piping.
4. Mechanical problems with the deluge valves.
![Page 30: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/30.jpg)
Unintentional activations quite common
Six cases (totally four churches) of unintentional activations were documented. All cases involved facade protection:
1. Rain water got inside a junction box of the detection system.
2. Unknown reason (same church)
3. Too low temperature rating of heat detection wire on facade.
4. As case 3.
5. As case 3.
6. Manufacturing defect of a component in the fire alarm panel.
![Page 31: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/31.jpg)
Unintentional fire alarms quite common
Several cases of unintentional activations of fire detection systems have been documented:
1. Water leaking during a hydrostatic test found its way in to a smoke detector. False alarm some weeks later.
2. Leaves were burnt outdoors – activated detection system inside attic space.
3. Too low temperature rating of linear heat detection system installed on facades.
![Page 32: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/32.jpg)
Inspection, tests and maintenance are expensive
Example from Habo church, cost per year:
Own personnel: $5,000 (3 hours / week). Service agreement (the system): $8,250. Service agreement (the power generator): $1,500. Annual, third party inspection: $3,800.
Totally: $18,550+ VAT = $23,200 per year.
Important: Statistics shows that regular inspection, tests and maintenance is the key to high reliability.
![Page 33: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/33.jpg)
Issues where additional research, testing or development work is desired
Water discharge densities and design areas relevant for heritage buildings.
The protection of facades and roofs. Fire detection for facades and roofs. Flashover prevention systems. Water exposure to vulnerable paintings and décor. The use of antifreeze. System reliability. Streaming of water in cold sprinkler piping – the risk for clogging.
![Page 34: 7th International Fire Sprinkler Conference & Exhibition, Copenhagen, 24-25 June 2008 Protection of Cultural Resources Sprinkler Protection for Historic](https://reader030.vdocument.in/reader030/viewer/2022020320/56649de75503460f94ae0697/html5/thumbnails/34.jpg)
Thank you!