8.5 high rise residential heat recovery ventilation hrv-af...

2
Key Features • PSC or ECM motors available • Core and filters easily removed for cleaning • Variety of optional controls • Reliable economical air flow design • Horizontal or vertical mounting • Full anti-freeze protection Cabinet Galvanized steel construction, lined with 1" fiberglass insulation backed with aluminum protective coating. Duct diameter 5" (127 mm), drain connection 3/8" (10 mm). Cabinet dimensions – 36" x 20" x 9" Mounting Vertical or horizontal mounting, suspended above ceiling or mounted with access panel. Ceiling mounting kits available. Thermal Recovery Core Polypropylene, washable core. Blowers Blowers are single inlet centrifugal impeller types with forward curved blades. Motors Unilux has designs for either Permanent Split Capacitor (PSC) motors or Electronically Commutated Modulation (ECM) motors. These motors are IP-44, shielded bearing, high efficiency types with internal thermal overload protection. Motors meet CSA and UL. Electrical Requirements 115 vac, 60 hz, 155 watts Anti Freeze High speed temperature sensors, trigger motorized spring return damper to isolate core and introduce exhaust air to ensure temperature above 32 degrees Fahrenheit (0 degrees celsius). Controls PSC motors with zero crossing phase control. ECM motors using pulse width modulation. Motor speed is controlled using either manual push button (+/-) or optional auxiliary controls. Filters 2 washable foam filters. Warranty Limited 2 year warranty. Product Description The ideal in-suite ventilation solution for high rise construction, Unilux delivers top performance in a compact and flexible, easy to install product that is only 9" thick. Easily concealed in a drop ceiling or boxed in drywall location, the Unilux product has been engineered for apartments, condos, seniors living establishments and hotels. The Unilux HRV produces 120 cfm at 0.11 in w.c., enough to provide sufficient fresh air for even the largest suites. Unilux has developed a unique anti-freeze ducting bypass system that utilizes high speed temperature sensors and motorized dampers to ensure that the core does not freeze, no matter how cold it is outside. The Unilux HRV has been designed so that the HRV air flow system is configured to ensure sufficient fresh air is provided while maximizing efficiency in energy use. Approvals Meets standard c22.2, no113 and ul1812. High Rise Residential Heat Recovery Ventilation HRV-AF Minimizing energy loss through the introduction of fresh air. Product Specifications and Technical Data Fresh Air Intake Stale Unit Intake Exhaust Air

Upload: others

Post on 23-Aug-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 8.5 High Rise Residential Heat Recovery Ventilation HRV-AF ...uniluxvfc.com/wp-content/uploads/2017/06/Unilux-HRV-SellSheet.pdf · The Unilux HRV has been designed so that the HRV

Key Features• PSC or ECM motors available• Core and filters easily removed for cleaning• Variety of optional controls• Reliable economical air flow design• Horizontal or vertical mounting• Full anti-freeze protection

CabinetGalvanized steel construction, lined with 1" fiberglass insulation backed with aluminum protective coating. Duct diameter 5" (127 mm), drain connection 3/8" (10 mm). Cabinet dimensions – 36" x 20" x 9"

MountingVertical or horizontal mounting, suspended above ceiling or mounted with access panel. Ceiling mounting kits available.

Thermal Recovery CorePolypropylene, washable core.

BlowersBlowers are single inlet centrifugal impeller types with forward curved blades.

MotorsUnilux has designs for either Permanent Split Capacitor (PSC) motors or Electronically Commutated Modulation (ECM) motors. These motors are IP-44, shielded bearing, high efficiency types with internal thermal overload protection. Motors meet CSA and UL.

Electrical Requirements115 vac, 60 hz, 155 watts

Anti FreezeHigh speed temperature sensors, trigger motorized spring return damper to isolate core and introduce exhaust air to ensure temperature above 32 degrees Fahrenheit (0 degrees celsius).

ControlsPSC motors with zero crossing phase control.ECM motors using pulse width modulation.Motor speed is controlled using either manual push button (+/-) or optional auxiliary controls.

Filters2 washable foam filters.

WarrantyLimited 2 year warranty.

Product DescriptionThe ideal in-suite ventilation solution for high rise construction, Unilux delivers top performance in a compact and flexible, easy to install product that is only 9" thick. Easily concealed in a drop ceiling or boxed in drywall location, the Unilux product has been engineered for apartments, condos, seniors living establishments and hotels. The Unilux HRV produces 120 cfm at 0.11 in w.c., enough to provide sufficient fresh air for even the largest suites.

Unilux has developed a unique anti-freeze ducting bypass system that utilizes high speed temperature sensors and motorized dampers to ensure that the core does not freeze, no matter how cold it is outside.

The Unilux HRV has been designed so that the HRV air flow system is configured to ensure sufficient fresh air is provided while maximizing efficiency in energy use.

ApprovalsMeets standard c22.2, no113 and ul1812.

High Rise Residential Heat Recovery Ventilation HRV-AF Minimizing energy loss through the introduction of fresh air.

Product Specifications and Technical Data

Fresh AirIntake

Stale UnitIntake

Exhaust Air

Project: Unilux HRV Sell Sheet

Client: Unilux

Branton Job #: BA-16-21102

Division:

Director: Ken Branton

Designer: Joe Kormendi

Date: 03•03•2016

1057 oxford street west, london, ontario N6H 1V6 www.branton.ca t. 519 471 . 6778 ext. 226 f. 519 471 . 0430 e. [email protected]

Colours:

Cyan

Magenta

Yellow

Black

Scale:

100%

DO NOT PRINT DIE LINES OR FOLD LINES

IF THIS UPC CODE DOES NOT MEET THE NEEDS OF THE PRINTING PROCESS OR EQUIPMENT TO BE USED, THE PRINTER IS RESPONSIBLE TO RECREATE THE FILE USING THE APPROPRIATE BAR WIDTH ADJUSTMENT WHILE MEETING 3M QUALITY REQUIREMENTS.

brantonadvertising

8.5"

11"

Page 2: 8.5 High Rise Residential Heat Recovery Ventilation HRV-AF ...uniluxvfc.com/wp-content/uploads/2017/06/Unilux-HRV-SellSheet.pdf · The Unilux HRV has been designed so that the HRV

MANUFACTURED IN CANADA

DimensionsFront View Top View

Side View

9.43

37.38

35.54

19.50

12.02

4.90

7.87

1.86 1.86

Ø

WinterSummer

Effectiveness(cooling)

Effectiveness(heating)CFM

40

60

80

100

120

74.7

69

64.6

61

58

75.5

68.7

62.6

59.9

58.2

75.1

68.85

63.6

60.45

58.1

0.1

0.15

0.2

0.29

0.45

0.04

0.05

0.07

0.09

0.11

Mean Effectiveness PD Supply PD Exhaust

Performance

High Rise Residential Heat Recovery Ventilation HRV-AF Minimizing energy loss through the introduction of fresh air.

Product Specifications and Technical Data

7930 Huntington Rd, Unit A, Woodbridge, ON L4H 4M8 Office: 905.851.3981 Parts & Service: 905.851.3981 Fx. 905.851.3987 [email protected] WWW.UNILUXVFC.COM

HRV Core Effectiveness (%) vs Airflow (CFM)

40 50 60 70 80 90 100 110 120

80

75

70

65

60

55

Airflow (CFM)

Sens

ible

Eff

ecti

vene

ss (%

)

HRV Core Pressure Drops (W.C.) vs Airflow (CFM)

40 50 60 70 80 90 100 110 120

0.50.45

0.40.35

0.30.25

0.20.15

0.10.05

0

Airflow (CFM)

Pre

ssur

e D

rop

(W.C

.)

Supply PD Exhaust PD

8.5"

11"