GENERATOR 8 kW 11 kW 16kW 20kW 22kW
Rated Maximum Continuous Power Capacity (LP) 8,000 Watts 11,000 Watts 16,000 Watts 20,000 Watts 22,000 Watts
Rated Maximum Continuous Power Capacity (NG) 7,000 Watts 10,000 Watts 16,000 Watts 18,000 Watts 19,500 Watts
Rated Voltage 120/240 120/240 120/240 120/240 120/240
Rated Maximum Continuous Load Current 240 Volts 33.3 LP/29.2 NG 41.6 LP/37.5 NG 66.6 LP/66.6 NG 83.3 LP/75 NG 91.6 LP/81.3 NG
Phase 1 1 1 1 1
Number of Rotor Poles 2 2 2 2 2
Rated AC Frequency 60Hz 60Hz 60Hz 60Hz 60Hz
Power Factor 1 1 1 1 1
Main Line Circuit Breaker 35 Amp 50 Amp 65 Amp 90 Amp 100 Amp
Battery Specifications (not included) Group 26R Group 26R Group 26R Group 26R Group 26R
12 Volts and 12 Volts and 12 Volts and 12 Volts and 12 Volts and
350 Cold-cranking 525 Cold-cranking 525 Cold-cranking 525 Cold-cranking 525 Cold-cranking
Amperes Minimum Amperes Minimum Amperes Minimum Amperes Minimum Amperes Minimum
Unit Weight 360 Pounds 407 Pounds 513 Pounds 516 Pounds 526 Pounds
Dimensions (L” x W” x H”) 48 x 25 x 29 48 x 25 x 29 48 x 25 x 29 48 x 25 x 29 48 x 25 x 29
Sound output in dB(A) at 23 ft. 62 63 66 (60 Quiet Test) 66 (60 Quiet test) 67 (58 Quiet test)
ENGINE 8 kW 11 kW 16kW 20kW 22kw
Type of Engine OHVI OHVI V-TWIN OHVI V-TWIN OHVI V-TWIN OHVI V-TWIN
Number of Cylinders 1 2 2 2 2
Displacement 410cc 530cc 992cc 999cc 999cc
Cylinder Block Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast
Iron Sleeve Iron Sleeve Iron Sleeve Iron Sleeve Iron Sleeve
Oil Capacity Including Filter Approx. 1.5 Qts. Approx. 1.7 Qts. Approx. 1.9 Qts. Approx. 1.9 Qts. Approx. 1.9 Qts.
Operating RPM 3,600 3,600 3,600 3,600 3,600
Fuel Consumption
Natural Gas 1/2 Load 78 124 193 205 184
Full Load 121 195 312 308 281
Liquid Propane 1/2 Load 32 (0.87) 43 (1.18) 72 (1.99) 76 (2.08) 83 (2.16)
Full Load 52 (1.42) 71 (1.92) 130 (3.57) 140 (3.85) 127 (3.68)
Required fuel pressure to generator fuel inlet at all load ranges 3.5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
CONTROLS (8kW, 11kW, 16kW, 20kW & 22kW)
2-Line Plain Text LCD Display Simple user interface for ease of operation
Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser. Programmeable on 16kW and larger to weekly, bi-weekly, or monthly. (Requires product registration to run in Auto mode.)
-Off Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Automatic Voltage Regulator w/Overvoltage Protection Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard, 72Hz
High Temperature Shutdown Standard
Overcrank Protection Standard
Safety Fuse Standard
Engine Start Sequence Transition time utility to generator approximately 30 seconds
Battery Charger Standard