9- protection basics

Upload: alaasaq

Post on 02-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 9- Protection Basics

    1/18

    Protection Fundamentals

  • 8/10/2019 9- Protection Basics

    2/18

    Selection of protective relays requires compromises:

    Maximum and Reliable protection at minimum

    equipment cost

    High Sensitivity to faults and insensitivity to maximum

    load currents

    High-speed fault clearance with correct selectivity

    Selectivity in isolating small faulty area

    Ability to operate correctly under all predictable power

    system conditions

    Art & Science of Protection

  • 8/10/2019 9- Protection Basics

    3/18

    Cost of protective relays should be balancedagainst risks involved if protection is not

    sufficient and not enough redundancy.

    Primary objectives is to have faulted zones

    primary protection operate first, but if there are

    protective relays failures, some form of backup

    protection is provided.

    Backup protection is local (if local primaryprotection fails to clear fault) and remote (if

    localprotection fails to operate to clear fault)

    Art & Science of Protection

  • 8/10/2019 9- Protection Basics

    4/18

    Primary Equipment & Components

    Transformers - to step up or step down voltage level

    Breakers - to energize equipment and interrupt fault current

    to isolate faulted equipment

    Insulators - to insulate equipment from ground and other

    phases

    Isolators (switches) - to create a visible and permanent

    isolation of primary equipment for maintenance purposes

    and route power flow over certain buses.

    Bus - to allow multiple connections (feeders) to the same

    source of power (transformer).

  • 8/10/2019 9- Protection Basics

    5/18

    Primary Equipment & Components Grounding - to operate and maintain equipment safely

    Arrester - to protect primary equipment of sudden

    overvoltage (lightning strike).

    Switchgear integrated components to switch, protect,

    meter and control power flow

    Reactors - to limit fault current (series) or compensate for

    charge current (shunt)

    VT and CT - to measure primary current and voltage and

    supply scaled down values to PC, metering, SCADA, etc.

    Regulators - voltage, current, VAR, phase angle, etc.

  • 8/10/2019 9- Protection Basics

    6/18

    Types of Protection

    Overcurrent Uses current to determine magnitude of fault

    Differential current in = current out

  • 8/10/2019 9- Protection Basics

    7/18

    Differential

    Note CT polarity

    dots

    This is athrough-current

    representation

    Perfect

    waveforms, nosaturation

    IP

    IS

    IR-X

    IP

    IS

    IR-Y

    Relay

    CT-X CT-Y

    1 + (-1) = 0

    +1

    -1

    0

    Current,pu

    DIFF CURRENT

    1 pu

  • 8/10/2019 9- Protection Basics

    8/18

    Differential

    Note CT

    polarity dots

    This is aninternal fault

    representation

    Perfectwaveforms, no

    saturation

    FaultIP

    IS

    IR-X

    IP

    IS

    IR-Y

    Relay

    2 + (+2) = 4

    +2

    -2

    0

    Current,pu

    X

    2 pu 2 pu

    CT-X CT-Y

    DIFF CURRENT

  • 8/10/2019 9- Protection Basics

    9/18

    Types of Protection

    Voltage Uses voltage to infer fault or abnormal

    condition

    May also be used for undervoltage load

    shedding

  • 8/10/2019 9- Protection Basics

    10/18

    Types of Protection

    Frequency Uses frequency of voltage to detect power

    balance condition

    Used for load shedding & machinery

    under/overspeed protection

  • 8/10/2019 9- Protection Basics

    11/18

    Types of Protection

    Power Uses voltage and current to determine

    power flow magnitude and direction

  • 8/10/2019 9- Protection Basics

    12/18

    Types of Protection

    Distance (Impedance) Uses voltage and current to determine impedance of

    fault

    Set on impedance [R-X] plane

    Impedance related to distance from relay Complicated

    Fast

    Expensive

  • 8/10/2019 9- Protection Basics

    13/18

    Generation-typically at 4-20kV

    Transmission-typically at 230-765kV

    Subtransmission-typically at 69-161kV

    Receives power from transmission system and

    transforms into subtransmission level

    Receives power from subtransmission system

    and transforms into primary feeder voltage

    Distribution network-typically 2.4-69kV

    Low voltage (service)-typically 120-600V

    Typical

    Bulk

    PowerSystem

    13

  • 8/10/2019 9- Protection Basics

    14/18

    1. Generator or Generator-Transformer Units

    2. Transformers

    3. Buses

    4. Lines (transmission and distribution)

    5. Utilization equipment (motors, static loads, etc.)

    6. Capacitor or reactor (when separately protected)

    Unit Generator-Tx zone

    Bus zone

    Line zone

    Bus zone

    Transformer zoneTransformer zone

    Bus zone

    Generator

    ~

    XFMR Bus Line Bus XFMR Bus Motor

    Motor zone

    ProtectionZones

  • 8/10/2019 9- Protection Basics

    15/18

    C37.2:

    Device

    Numbers

    Partial listing

    15GE Consumer & Industrialultilin

  • 8/10/2019 9- Protection Basics

    16/18

    CT/VT Circuit vs. Casing Ground

    Case ground made at IT location

    Secondary circuit ground made at first point of

    use

    Case

    Secondary Circuit

  • 8/10/2019 9- Protection Basics

    17/18

    A Good Day in System

    Protection

    CTs and VTs bring electrical info to relays

    Relays sense current and voltage and declare

    fault

    Relays send signals through control circuits tocircuit breakers

    Circuit breaker(s) correctly trip

    What Cou ld Go Wrong Here????

  • 8/10/2019 9- Protection Basics

    18/18

    A Bad Day in System

    Protection

    CTs or VTs are shorted, opened, or their wiring is

    Relays do not declare fault due to setting errors,

    faulty relay, CT saturation

    Control wires cut or batteries dead so no signal issent from relay to circuit breaker

    Circuit breakers do not have power, burnt trip coil

    or otherwise fail to trip

    Protect ion Sys tems Typ ical ly are

    Designed fo r N-1