    Technical data for auxiliarycontacts and releasesFor i DPN (DPN), C60, C120, ID, I-NA

    MN, MN s , MX + OF, MX, MNx releases

    Releases MN MN sCat. no. 26960 26961 26959 26963Nominal line voltage (V) (+10, -20 %) 220 to 240 48 48 115 220 to 240

    alternating current (AC) b b - b b

    direct current (DC) - - b - -Operating frequency 50/60 Hz b b - - b

    400 Hz - - - b -Min. cut-in voltage (V) 187 40.8 40.8 98 187Min. tripping voltage (V) between 0.35 and 0.70 Un between 0.35 and 0.70 UnHolding current (A) 0.014 0.034 0.022 0.017 0.015Power consumption (VA) 3.3 1.6 1.1 2 3.4Min. voltage dip time (ms) 30 8 8 30 > 300

    Releases MX + OFCat. no. 26946 26947 26948Nominal line voltage (V) (+10, -20 %) 100 230 415 100 130 48 48 12 12 24 24

    alternating current (AC) b b b - - b - b - b -

    direct current (DC) - - - b b - b - b - bOperating frequency 50/60 Hz b b b - - b - b - b -Min. cut-out voltage (V) 77 77 77 77 77 33.6 33.6 8.4 8.4 8.4 8.4Inrush current (A) 0.4 0.8 1.5 0.3 0.3 1 0.7 4 2.5 7.7 5.6Inrush power (VA) 44 184 625 38 45 48 33.6 48 30 185 135Min. control impulse duration (ms) 8 8 8Power circuit breaking time (ms) 18 18 18OF contact rated operational current Ie (A) see the auxiliary contact table on the next page

    Releases MXCat. no. 26476 26477 26478Nominal line voltage (V) (+10, -20 %) 100 230 415 100 130 48 48 12 12 24 24

    alternating current (AC) b b b - - b - b - b -direct current (DC) - - - b b - b - b - b

    Operating frequency 50/60 Hz b b b - - b - b - b -Min. cut-out voltage (V) 77 77 77 77 77 33.6 33.6 8.4 8.4 8.4 8.4Inrush current (A) 0.4 0.8 1.5 0.3 0.3 1 0.7 4 2.5 7.7 5.6Inrush power (VA) 44 184 625 38 45 48 33.6 48 30 185 135Min. control impulse duration (ms) 8 8 8Power circuit breaking time (ms) 18 18 18

    Releases MNx MNx C60 MNx MNx C60Cat. no. 26969 26977 26971 26991Nominal line voltage (V) (+10, -20 %) 230 230 400 400

    alternating current (AC) b b b bdirect current (DC) - - - -

    Operating frequency 50/60 Hz b b b bMin. tripping voltage (V) 100 100 280 280Holding current (A) 0.014 0.014 0.014 0.014Power consumption (VA) 3.3 3.3 5.6 5.6Breaking time (ms) 20 20 20 20Min. control circuit opening time (ms) 30 30 30 30

  • 8/7/2019 92605e (web)

    2/2version: 7.192605E.indd 3

    ServicesPractical advice

    Technical data for auxiliarycontacts and releasesFor i DPN (DPN), C60, C120, ID, I-NA

    MSU releasesReleases M&SUCat. no. 26479 26979Nominal line voltage (V) (+10, -20 %) 230 230

    alternating current (AC) b bdirect current (DC) - -

    Operating frequency 50/60 Hz b bOperating threshold (V) 255 (-0, +5 %) 275 (-0, +5 %)Holding current (A) 0,002 0,002Inrush power (VA) 128 128Power consumption (VA) 0,046 0,046Breaking time (ms) according to the curve

    OF, SD, OF + SD/OF, OF.S, OFsp auxiliary contactsConform to EN 62019 for C60, C120 and i DPN (DPN).Degree of protection: IP20.Rating of auxiliary contact short-circuit protection device:circuit breaker: C60 / i DPN - 2P - C curve - 6 A - limitation class 3

    fuse: 6 A, 500 V, type Gg, 10.3 x 38 mm.

    Contact rated operational current le (A) to CEI 60947-5 :Contacts auxiliary OF, SD,

    OF + SD/OF, OF.SOFsp

    Cat.no. 26924/26927/26929/26923 16940Rated operational cat. AC12 380...415 V AC 3 -Voltage Ue (V) 220...240 V AC 6 -

    cat. AC15 220...240 V AC - 6cat. DC12 24 V DC 6 -

    48 V DC 2 -60 V DC 1,5 -130 V DC 1 -

    cat. DC13 230 V DC - 1

    Common technical data of auxiliary contacts andreleasesCommon technical dataOperating temperature when live (C) -25 C +50 CStorage temperature -40 C +85 C

    b

    b

    b

    v

    v

    Additional informationSee MSU releases catalogue module: page 92519