95-8533-16.1-eqp

Upload: angela-fasuyi

Post on 28-Feb-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 95-8533-16.1-EQP

    1/156

  • 7/25/2019 95-8533-16.1-EQP

    2/156

    2 95-853316.1

    Table of ContentsSection 1 - Safety

    ALERT MESSAGES ...................................................... 1-1

    Section 2 - IntroductionSYSTEM DESCRIPTION .............................................. 2-1 Communications Loop ...................................................2-1

    LON Communication Heartbeat .....................................2-2

    Theory of Operation .......................................................2-3

    Controller Logs ...............................................................2-4

    Controller User Logic .....................................................2-4

    Communication Network Fault Operation ...................... 2-5

    Multiple Wiring Faults .....................................................2-5

    MAJOR COMPONENT DESCRIPTIONS .....................2-6 System Controller ...........................................................2-6

    Controller Redundancy ............................................... 2-6

    Ethernet Interface Board .............................................2-7

    Serial Interface Board ................................................. 2-7

    ControlNet Board or Ethernet DLR Board ...................2-7

    Controller-to-Controller Communication ...................... 2-8

    EQP Supervising System.............................................2-8

    EQP Marine Application System .................................2-8

    Local Operating Network (LON).....................................2-8

    Network Extenders ......................................................2-8

    EQ21xxPS Series Power Supplies and

    EQ2100PSM Power Supply Monitor ............................ 2-9

    EQP21xxPS(X) Power Supplies andEQP2410PS(P) Converter ..........................................2-9

    EQ2220GFM Ground Fault Monitor .............................2-9

    Field Devices .................................................................. 2-9

    Flame Detectors ..........................................................2-9

    EQ3730EDIO Enhanced Discrete I/O Module ............2-9

    EQ3700 8 Channel DCIO Module ............................. 2-10

    EQ3720 8 Channel Relay Module ............................. 2-11

    EQ3710AIM Analog Input Module............................. 2-11

    EQ3750ASH Addressable Smoke & Heat Module .... 2-12 EQ25xxARM Agent Release Module......................... 2-13

    EQ25xxSAM Signal Audible Module ......................... 2-14

    EQ22xxIDC Series Initiating Device Circuit...............2-14

    EQ22xxDCU / EQ22xxDCUEX DigitalCommunication Units ................................................2-15

    PIRECL PointWatch Eclipse ......................................2-15

    OPECL Open Path Eclipse ........................................2-15

    UD10 DCU Emulator ................................................. 2-15

    Section 3 - InstallationSAFETY SYSTEM DESIGN REQUIREMENTS ............. 3-1 Identifying the Area of Protection ...................................3-1

    Identifying Wiring, Network (LON),and System Power Requirements ..................................3-1

    General Wiring Requirements .....................................3-1

    Power Wiring ...............................................................3-1

    System Wiring (ATEX and IECEx) ................................3-1

    Determining Power Requirements............................... 3-3

    EQ211xPS, EQ213xPS and EQ217xPSPower Supplies ...........................................................3-5

    Backup Battery ............................................................3-5

    Battery Charger ...........................................................3-5

    EQP21x0PS(X) Power Supplies .................................3-5

    EQP2410PS(P) Converter ..........................................3-6

    Determining Power Requirements............................... 3-6

    Shield Grounding ........................................................3-7

    Junction Box Grounding..............................................3-7

    Response Time vs. System Size .................................3-7

    Moisture Damage Protection .......................................3-7

    Electrostatic Discharge ............................................... 3-7

    GROUND FAULT MONITOR (GFM) INSTALLATION ......3-8 Mounting......................................................................... 3-8

    Wiring ............................................................................3-8

    NETWORK & NETWORK EXTENDER INSTALLATION...3-8 Mounting......................................................................... 3-8

    Wiring ............................................................................3-8

    INITIATING DEVICE CIRCUIT (IDC) INSTALLATION 3-11 EQ22xxIDC Series Initiating Device Circuit ..................3-11

    Mounting ................................................................... 3-11

    Wiring ........................................................................ 3-11

    EQ22xxIDCGF Series Initiating DeviceCircuit Ground Fault .....................................................3-12

    Mounting ................................................................... 3-12

    Wiring ........................................................................ 3-12 EQ22xxIDCSC Series Initiating Device

    Circuit Short Circuit ......................................................3-13

    Mounting ................................................................... 3-13

    Wiring ........................................................................ 3-13

  • 7/25/2019 95-8533-16.1-EQP

    3/156

    95-8533316.1

    Table of Contents ContinuedEQ3XXX CONTROLLER INSTALLATION ................. 3-13 Enclosure Requirements .............................................. 3-13

    Mounting....................................................................... 3-14

    Serial Interface Board...................................................3-14

    Ethernet Interface Board .............................................. 3-14 Wiring ..........................................................................3-14

    Power Wiring .............................................................3-14

    Electrical Connections .............................................. 3-14

    Controller to Controller Communication ....................... 3-19

    Configuration ................................................................3-23

    Software Defined Addresses .....................................3-23

    EQ3XXX REDUNDANT CONTROLLER

    INSTALLATION ..........................................................3-25 Enclosure Requirements .............................................. 3-25

    Mounting....................................................................... 3-25 Wiring ..........................................................................3-25

    LON Wiring ................................................................... 3-25

    High Speed Serial Link (HSSL) ....................................3-26

    Configuration ................................................................3-26

    SConfiguration .........................................................3-26

    Controller Addresses ................................................. 3-26

    RS485/RS232 ............................................................3-26

    ControlNet .................................................................3-26

    Ethernet DLR .............................................................3-26

    Ethernet ..................................................................... 3-26

    EQ21XXPS SERIES POWER SUPPLY AND

    POWER SUPPLY MONITOR INSTALLATION............3-26 Mounting....................................................................... 3-27

    Wiring ..........................................................................3-27

    Startup ..........................................................................3-27

    Measuring Battery Voltage and Charging Current ..........3-28

    EQP2XX0PS(X) POWER SUPPLIES AND

    REDUNDANCY MODULE INSTALLATION ...............3-29 Mounting....................................................................... 3-29

    Wiring ..........................................................................3-29 Startup ..........................................................................3-32

    EDIO MODULE INSTALLATION ................................3-32 Configuration ................................................................3-36

    8 CHANNEL DCIO INSTALLATION .......................3-37 Mounting....................................................................... 3-37

    Wiring ..........................................................................3-37

    Configuration ................................................................3-41

    8 CHANNEL RELAY MODULE INSTALLATION........3-41 Mounting....................................................................... 3-41

    Wiring ..........................................................................3-41

    Configuration ................................................................3-42

    ANALOG INPUT MODULE INSTALLATION .............3-43 Mounting....................................................................... 3-43

    Wiring ..........................................................................3-43

    Configuration ................................................................3-44

    GAS DETECTOR LOCATION AND INSTALLATION .3-45 Environments and Substances that Affect

    Gas Detector Performance ..........................................3-46

    EQ22xxDCU Digital Communication Unit used withDet-Tronics H2S/O2 Sensors or other Two-Wire4-20 mA Devices ..........................................................3-47

    Assembly and Wiring Procedure ...............................3-47

    Sensor Separation for DCU with H2S and O2Sensors.........................................................................3-47

    EQ22xxDCU Digital Communication Unit used withPointWatch/DuctWatch .................................................3-48

    Assembly and Wiring Procedure ...............................3-48

    Sensor Separation for DCU with PointWatch ...............3-49

    EQ22xxDCUEX Digital Communication Unit (used withDet-Tronics Combustible Gas Sensors) .......................3-49

    Mounting ................................................................... 3-49

    Wiring ........................................................................ 3-49

    Sensor Separation with DCUEX ...................................3-51 EQ25xxARM Series Agent Release Module.................3-52

    Mounting ................................................................... 3-52

    Wiring ........................................................................ 3-52

    Supervised Output for Deluge and Pre-action .............3-53

    Jumpers .................................................................... 3-54

    Address Setting .........................................................3-54

    EQ25xxSAM Series Signal Audible Module ................3-54

    Mounting ................................................................... 3-54

    Wiring ........................................................................ 3-54

    Jumpers .................................................................... 3-55 Address Setting .........................................................3-55

    SYSTEM CONFIGURATION ......................................3-56 Setting Device Network addresses ..............................3-56

    Overview of Network Addresses ...............................3-56

    Setting Field Device Addresses ................................3-56

    TYPICAL APPLICATIONS ..........................................3-56

  • 7/25/2019 95-8533-16.1-EQP

    4/156

  • 7/25/2019 95-8533-16.1-EQP

    5/156

    95-8533516.1

    Table of Contents ContinuedSection 5 - Maintenance

    ROUTINE MAINTENANCE ..........................................5-1 Batteries ......................................................................... 5-1

    Manual Check of Output Devices ..................................5-1

    O-Ring Maintenance ......................................................5-1

    GAS SENSOR MAINTENANCE ................................... 5-1

    CALIBRATION AND ADJUSTMENTS .........................5-2 Calibration Algorithm A For Manual Calibration

    of Universal DCU ............................................................5-2

    Normal Calibration ......................................................5-2

    Sensor Replacement ................................................... 5-3

    Calibration Algorithm C For Combustible Gas DCUsand Automatic Calibration of Universal DCUs ............... 5-3

    Routine Calibration ......................................................5-3

    Initial Installation and Sensor Replacement Combustible Gas ........................................................5-4

    Sensor Replacement Toxic Gas.............................. 5-5

    Calibration Algorithm D For Universal DCUswith O2 Sensor ............................................................... 5-5

    Normal Calibration ......................................................5-5

    Sensor Replacement ................................................... 5-5

    Calibration Algorithm G For DCUs with PointWatchor DuctWatch ..................................................................5-6

    Routine Calibration ......................................................5-6

    Sensor Replacement ................................................... 5-6

    DEVICE CALIBRATION LOGS AND RECORDS .........5-7

    TROUBLESHOOTING .................................................5-7

    REPLACEMENT PARTS ............................................... 5-7

    DEVICE REPAIR AND RETURN ..................................5-7

    ORDERING INFORMATION ........................................5-9

    Power Supplies .........................................................5-9

    LON Devices .............................................................5-9

    Redundancy ..............................................................5-9

    Controller Communication Cables ...........................5-9

    Section 6 - SpecificationsEQ3XXX Controller ............................................................6-1

    EQ3LTM LON Termination Module ....................................6-3

    EQ3730EDIO Enhanced Discrete I/O Module .................6-3

    EQ3700 DCIO Module.......................................................6-5EQ3720 Relay Module.......................................................6-7

    EQ3710AIM Analog Input Module.....................................6-7

    HART Interface Module .....................................................6-8

    EQ21xxPS Power Supplies................................................ 6-8

    EQP2xx0PS(x) Power Supplies .......................................6-9

    Redundancy Module Quint-Diode/40................................6-9

    EQ21xxPSM Power Supply Monitor ................................6-10

    EQ22xxIDC Series Initiating Device Circuit ..................... 6-10

    EQ2220GFM Ground Fault Monitor .................................6-11

    EQ22xxDCU Series Digital Communication Unit ............6-12EQ25xxARM Agent Release Module...............................6-13

    EQ25xxSAM Signal Audible Module ...............................6-14

    EQ24xxNE Network Extender..........................................6-15

    EQ3750ASH Addressable Smoke & Heat Module ..........6-16

    Combustible Gas Sensor ................................................6-16

    Electrochemical Sensors ................................................. 6-16

    EQ21xxPS Power Supply ................................................6-16

    AppendixAPPENDIX A FM APPROVAL DESCRIP. .................A-1

    APPENDIX B CSA CERTIFICATION DESCRIP..........B-1

    APPENDIX C ATEX AND IECEX CERTIFICATION ..C-1

    APPENDIX D EQP MARINE, USCG APPROVAL .....D-1

    APPENDIX E CE MARK ........................................... E-1

    APPENDIX F ROCKER SWITCH TABLE .................. F-1

    APPENDIX G DEVICE MODEL MATRICES ............ G-1

  • 7/25/2019 95-8533-16.1-EQP

    6/156

    1 95-853316.1

    Section 1

    Safety

    ALERT MESSAGES

    The following Alert Messages, DANGER,WARNING, CAUTION, and IMPORTANT areused throughout this manual and on the systemto alert the reader and operator to dangerousconditions and/or important operational or

    maintenance information.

    DANGER!

    Identifies immediate hazards that WILL

    result in severe personal injury or death.

    WARNING!

    Identifies hazards or unsafe practices

    that COULD result in severe personal

    injury or death.

    CAUTION!

    Identifies hazards or unsafe practices

    that COULD result in minor personal

    injury or damag e to equipment or

    property.

    IMPORTANT!

    A brief statement of fact, experience or

    importance that is given as an aid or

    explanation.

    WARNING!

    T h e h a za rd o u s a re a mu s t b e

    de-classified prior to removing a

    junction box cover or opening a detector

    assembly with power applied.

    CAUTION!

    1. Be sure to read and understand the entireinstruction manual before installing oroperating the Eagle Quantum Premier

    system. Only qualified personnel should

    install, maintain or operate the system.

    2. The wiring procedures in this manual areintended to ensure proper functioning of thedevices under normal conditions. However,because of the many variations in wiringcodes and regulations, total compliancewith these ordinances cannot beguaranteed. Be certain that all wiring and

    equipment installation meets or exceedsthe latest revisions of the appropriateNFPA Standards, National ElectricalCode (NEC), and all local ordinances. Ifin doubt, consult the Authority HavingJurisdiction (AHJ) before wiring the system.

    All wiring shall be installed in accordance withthe manufacturers recommendations.

    3. Some Eagle Quantum Premier devicescontain semiconductor devices that aresusceptible to damage by electrostaticdischarge. An electrostatic charge canbuild up on the skin and discharge whenan object is touched. Always observe thenormal precautions for handling electrostaticsensitive devices, i.e. use of a wrist strap (ifavailable) and proper grounding.

    4. To prevent unwanted actuation, alarms andextinguishing devices must be securedprior to performing system tests.

    Instructions

    Eagle Quantum Premier

    Fire and Gas Detection/Releasing System

    Detector Electronics Corporation 2014 Rev: 12/14

  • 7/25/2019 95-8533-16.1-EQP

    7/156

    95-85332-116.1

    Section 2

    Introduction

    SYSTEM DESCRIPTION

    The Eagle Quantum Premier (EQP) systemcombines "fire detection and extinguishing

    agent release" and "hazardous gas monitoring"in one complete package. The system isintended for use in hazardous locations and isdesigned to meet the requirements of approvalagencies from around the world.

    The system consists of a Controller and anumber of addressable microprocessor basedfield devices. The Controller coordinatessystem device configuration, monitoring,

    annunciation, and control, while the fielddevices communicate their status and alarmconditions to the Controller.

    The EQP controller can be arranged in aredundant configuration, thereby increasingthe availability of the system. The controllerswork in Master and Hot Standby mode.

    Various combinations of field devices can beconfigured as part of the system. The actual

    selection depends on the requirements of theapplication and the regulations that cover thetype of protection required. See Figure 2-1 fora block diagram of the Eagle Quantum Premiersystem.

    All field devices are tied into a communicationloop that starts and ends at the Controller.Each device connected to the communicationloop is assigned a unique identity by settingits address switches. All other device operation

    parameters are configured through Det-TronicsSafety System Software. These selectionsdefine the type of device and how it is tooperate. This system configuration data is thendownloaded into the Controller.

    A programmed Controller is configured toautomatically download the configurationdata into the individual devices when they firstcommunicate with the Controller.

    In addition to Det-Tronics advanced flameand gas detectors, Eagle Quantum Premieroffers the capability of incorporating third partyfire and gas protection equipment into thesystem. These can be either input or outputdevices. Typical input devices include manualfire alarm "call boxes", heat detectors, and

    analog combustible or toxic gas measurementinstruments. Typical output equipment includessolenoids, strobes, and horns. All equipment ismonitored for wiring fault conditions.

    For complete system integration, the Controllerhas the capability to communicate with other

    systems such as PLCs and DCSs. Differentcommunication protocols are supported,allowing the Controller to communicate withother systems either directly or throughcommunication gateways.

    NOTE

    For specific information relating to the

    SIL 2 rated EQP system, refer to manual

    number 95-8599.

    COMMUNICATIONS LOOP

    Eagle Quantum Premier utilizes a Det-TronicsSignaling Line Circuit (SLC), a version ofEchelons Local Operation Network (LON)customized specifically for Eagle QuantumPremier. This network provides several keyadvantages:

    ANSI/NFPA Class X performance of SLC

    Peer-to-peer communications

    Short message formats

    Expandability

    The Controller utilizes several mechanismsto continuously check the LON loop for faultconditions, thereby providing the highest levelof reliable communication.

    Every device on the LON loop has the ability

    to communicate with the Controller at any time.This is typically referred to as distributed peer-to-peer communications. This design allows forimmediate alarm messages to be sent from thefield devices to the Controller.

    All messages are kept short in order tomaximize network performance. This minimizesnetwork bottlenecks.

    The Eagle Quantum Premier system is easilymodified to accommodate design changesor plant expansions. This can involve addingLON sections, repositioning LON sections, orremoving LON sections from the loop. Thereare LON communication implementationdetails that affect and limit how the LON loopis changed.

  • 7/25/2019 95-8533-16.1-EQP

    8/156

    2-2 95-853316.1

    Only devices that have been approved for usewith Eagle Quantum Premier can be connectedup to the LON. All approved devices havebeen tested and certified to operate properlyon the LON.

    LON COMMUNICATION HEARTBEAT

    The Controller continuously broadcasts a

    heartbeat signal over the LON loop. Thisheartbeat is used for verifying the integrityof the LON loop and for keeping the fielddevices from going into a fault isolation mode.Once every second, the heartbeat containsthe current time and date, which are usedby the field devices to log status events andcalibrations.

    The Controller continuously tests LONcontinuity by sending out a heartbeat on oneLON port and then listening for it on the otherLON port. The Controller also broadcaststhe heartbeat signal in the opposite directionaround the loop. This ensures that all fielddevices, the LON Network Extenders (NE), andcommunication wiring are correctly passing

    the digital information around the loop.

    The field devices use the heartbeat asa mechanism to ensure that there is acommunication path back to the Controller. Ifthe field device does not receive a heartbeatfor a period of time, the device will go into aLON fault isolation. In this situation, the deviceopens one side of the LON and listens for aheartbeat on the other side. If the device

    doesnt receive a heartbeat, it listens on theother side of the LON and opens the oppositeLON connection.

    CONFIGURATION

    PC

    MODBUS

    INTERFACE

    NETWORK

    EXTENDER

    DIGITAL

    COMMUNICATION

    UNITS

    PIRECL

    GAS

    DETECTOR

    UD10-DCU

    OPECL

    GAS

    DETECTOR

    SIGNAL

    AUDIBLE

    MODULES

    HORNS

    &

    BEACONS

    GAS DETECTION

    COMBUSTIBLE, TOXIC,

    POINTWATCH OR

    OTHER 4-20 MA INPUT

    RS-232

    RS-485

    8 DRY CONTACT INPUTS8 RELAY

    OUTPUT POINTS

    UNSUPERVISED INPUTS AND OUTPUTS

    8 CHANNEL DCIO MODULE

    DRY CONTACT INPUTSCONFIGURABLE

    OUTPUT POINTS

    CONFIGURABLE INPUTS AND OUTPUTSFIRE DETECTION

    UV

    DETECTOR

    UVHT/C7050

    DETECTOR

    X3301

    DETECTOR

    X3302

    DETECTOR

    UVIR

    DETECTOR

    IR

    DETECTOR

    INITIATING

    DEVICE

    CIRCUIT

    CONTACT

    CLOSURE

    DEVICES

    SIGNALING LINE CIRCUIT (SLC)

    HARDWIRED I/O

    ETHERNET OR SERIAL INTERFACE BOARD

    EQP CONTROLLER

    CONTROLNET or

    ETHERNET DLR

    (OPTIONAL

    INTERFACE)

    ONBOARD

    SERIAL

    INTERFACE

    ETHERNET or SERIAL

    INTERFACE

    BOARD

    N2114

    ++

    AGENT

    RELEASE

    MODULES

    FIRE

    SUPPRESSION

    (SOL)

    POWER

    SUPPLY

    MONITOR

    ASH

    MODULE

    APOLLO

    DEVICES

    BATTERY

    CHARGER

    ACPOWERINPUT SYSTEM

    POWER

    NOTE: CHANNELS CAN BE CONFIGURED

    AS EITHER INPUTS OR OUTPUTS.

    TROUBLE RELAY

    (NC CONTACT)

    RELAY

    MODULE

    8 UNSUPERVISED

    RELAY OUTPUT POINTS

    ANALOGINPUT

    MODULE8 4-20 MA INPUTS

    ETHERNET

    orRS-232

    ETHERNET

    orRS-232

    RS-485

    HSSL

    CHANNELS CAN BE CONFIGURED AS INPUTS,

    OUTPUTS, SMOKE/HEAT DETECTORS,

    CLASS A INPUTS, OR CLASS A OUTPUTS.

    8 CHANNEL EDIO MODULE

    Figure 2-1Block Diagram of Eagle Quantum Premier System

  • 7/25/2019 95-8533-16.1-EQP

    9/156

    95-85332-316.1

    THEORY OF OPERATION

    During normal operation, the Controllercontinuously checks the system for faultconditions and executes user definedprogrammed logic that coordinates the controlof the field devices. At the same time, the fielddevices are continuously monitoring for devicebased fault and alarm conditions.

    When a fault condition occurs, the Controllerdisplays the fault condition on the VacuumFluorescent Text Display, activates theappropriate fault LED(s), activates the Trouble

    signal using the Controllers internal enunciator,and de-energizes the Controllers Trouble relay.

    Controller based fault conditions include theController status and LON communicationssuch as the heartbeat being sent around

    the loop and the field device loss ofcommunications. Controller based faultconditions are listed in Table 2-1.

    Field device based fault conditions aretransmitted to the Controller, where they arethen annunciated. Refer to Table 2-2 for alisting of field device faults. Each field devicetransmits its status to the Controller on aregular basis.

    When an alarm condition occurs, the Controllerdisplays the alarm condition on the text display,activates the appropriate Alarm LED(s), andactivates the alarm signal using the Controllersinternal annunciator.

    Controller FaultsShown on TextDisplay

    TroubleLED

    LON FaultLED

    TroubleRelay

    Controller Fault x x

    Device Offline x x

    Extra LON Device x x

    Invalid Config x x

    Lon Fault x x x

    LON Ground Fault x x

    Power Fail 1 x x

    Power Fail 2 x x

    RTC Fault x x

    Redundancy Fault* x x

    Field Device Faults

    Shown on Text Display

    Trouble

    LED

    Trouble

    Relay

    290 Volt Fault X X

    AC Failed X X

    Battery Fault X XBeam Block X X

    Calibration Fault X X

    Channel Open X X

    Channel Short X X

    Dirty Optics X X

    Ground Fault Negative X X

    Ground Fault Positive X X

    IR Auto Oi Fault X X

    IR Fault X X

    IR Manual Oi Fault X X

    Low Aux Power Fault X X

    Missing IR Sensor Fault X X

    Missing UV Sensor Fault X X

    Power Supply Fault X X

    Sensor Fault X X

    Supply Voltage Fault X X

    Tx Lamp Fault X X

    UV Auto Oi Fault X X

    UV Fault X X

    UV Manual Oi Fault X X

    Table 2-1Controller Based Faults

    *Only for controller pair configured for redundancy.

    Table 2-2Field Device Based Faults

  • 7/25/2019 95-8533-16.1-EQP

    10/156

    2-4 95-853316.1

    Each field device must communicate alarmand fault conditions to the Controller. Thetiming for transmitting alarms and faults to theController is displayed in Table 2-3.

    NOTE

    All fault and alarm conditions are latched

    on the Controller. To reset the Controller,

    conditions indicated on the text display

    must currently be in the OFF state.

    Pushing the reset button then initiates a

    Controller reset. Active alarms will remain

    through a Controller reset.

    CONTROLLER LOGS

    The controller has an internal alarm andevent log. The logs can be accessed via theS software configuration ports (ConfigurationPort or Port 3) using a RS-232 serial cableand a Windows computer. The controllercan save up to 4,095 alarms and events in thecontroller memory.

    CONTROLLER USER LOGIC

    The Controller continuously executes theuser logic programs that are programmedusing S software. The user logic programsare set up in the same fashion as IEC 61131-3 programmable logic programmed intoProgrammable Logic Controllers (PLCs).Block diagram logic gates are tied together

    with inputs, outputs, and other logic gates toperform a specific task. A number of tasks canbe tied together to perform a system function.

    Typical programmed functions include flame/gas voting, timing delays, timing executions,latching conditions, alarm and troublenotification, suppression control, conditioncontrol, and process shutdown notification.

    The Controller executes program logicby starting with the first logic page of thefirst program and then progressing ontosubsequent pages of the same program. Inturn, subsequent programs are then executed.

    Every one hundred milliseconds, theController will start executing the user logicthat is programmed into the Controller. Withinthis logic execution cycle, the Controllerwill execute as many of the logic pages aspossible. If all programmed logic is executedin a cycle, the Controller will start executingprogram logic with the next cycle. Otherwise,subsequence logic execution cycles are used

    to finish executing the remaining logic gates.Only when all the logic gates have beenexecuted will the Controller start over. TheController will start executing the first logicpage of the first program at the beginning ofthe next logic cycle.

    Controller Type# of

    Devices

    Output

    Only

    Input

    No Exception

    Input

    With Exception

    Input

    With Exception

    ARM

    SAM

    IDC

    U-Series

    (UV & UVIR)

    DCU

    DCIO, EDIO, AIM

    Relay Module

    ASH Module

    X-Series

    OPECL

    PIRECL

    EQ3001

    1 to 100 1 Second 1 Second 1 Second 1 Second

    101 to 200 2 Seconds 2 Seconds 2 Seconds 1 Second

    201 to 246 5 Seconds 2 Seconds 3 Seconds 1 Second

    EQ3150*

    1 to 50 1 Second 1 Second 1 Second 1 Second

    51 to 100 2 Seconds 2 Seconds 2 Seconds 1 Second

    101 to 150 5 Seconds 2 Seconds 3 Seconds 1 Second

    EQ3016 1 to 16 1 Second 1 Second 1 Second 1 Second

    Table 2-3Eagle Quantum Premier Status Update Rates

  • 7/25/2019 95-8533-16.1-EQP

    11/156

    95-85332-516.1

    COMMUNICATION NETWORK

    FAULT OPERATION

    During normal operation, the Controller iscontinuously broadcasting a heartbeat aroundthe communication loop as shown in Figure2-2. The Controller broadcasts the heartbeatin both directions. At the same time, the fielddevices are transmitting status information tothe Controller over the communication loop.

    Every field device except the network extenderhas two LON fault isolation relays. Each relayis tied to a communication port on the device.When a field device fails to receive the heartbeatfrom the Controller, the device initiates a LON

    fault isolation routine. The isolation routinedisconnects one of the communication portsvia one of the LON fault isolation relays.The device listens for a heartbeat on thecommunication port that is connected. Ifa heartbeat is not found, the routine thendisconnects the other communication port andlistens for a heartbeat on the connected side.

    The process is repeated until either a heartbeatis located or a LON fault timeout period oftwo hours is reached. The LON fault isolationroutine is disabled and the LON fault isolationrelays are closed when the LON fault timeoutperiod has elapsed. The LON fault isolationroutine will be enabled when the device again

    receives a heartbeat.

    For a single wiring fault, the field devices withthe fault will isolate the fault by opening LONfault isolation relays. After the field devicesisolate the wiring fault, communications willbe resumed between the Controller and fielddevices. Refer to Figure 2-3.

    MULTIPLE WIRING FAULTS

    In the event of multiple wiring faults on the LON,the devices between the faults will continue tofunction, but the faults will prevent them fromcommunicating with the Controller. See Figure2-4. In this example, nodes 1 to 4 communicateusing one Controller port (path A) and nodes7 and 8 use the other Controller port (pathB). Nodes 5 and 6 are unable to report to theController because they are isolated by thetwo wiring faults. If a device is prevented from

    communicating with the Controller, the textdisplay on the Controller will show the messageDevice Offline.

    IMPORTANT!

    Since it is impossible to predict where

    a network fault might occur or exactly

    what effect it will have on actual system

    operation, it is important to diagnose

    and repair any fault as soon as possibleafter it is detected to ensure continuous,

    uninterrupted system operation.

    Figure 2-3Communication over the LON with a Single

    Wiring Fault

    Figure 2-4Communication over LON with Multiple Wiring

    Faults

    D1851

    NODE 1 NODE 8

    NODE 3 NODE 6

    NODE 2 NODE 7

    NODE 4 NODE 5

    EQPCONTROLLER

    EAGLEQUANTUM PREMIER

    Safety System Controller

    Fir e A la rm I nh ibit P ow er

    SuprHigh Gas

    Trouble

    CntrlF lt

    Lon FaultL ow Ga s A ck S il en ce

    Out Inhibit

    Eagle Quantum Premier

    Time &Date

    C a n c el En t e r N e x t Pre v i ou s R e s e t A c k n o w le d g e Si l e nc e

    DET-TRONICS

    D1852

    NODE 1 NODE 8

    NODE 3 NODE 6

    NODE 2 NODE 7

    NODE 4 NODE 5

    PATH A PATH B

    WIRING FAULT

    EQPCONTROLLER

    EAGLEQUANTUM PREMIER

    Safety System Controller

    FireA la rm I nh ib it P ow er

    SuprHigh Gas

    Trouble

    CntrlF lt

    Lon FaultL ow Ga s A ck S il en ce

    Out Inhibit

    Eagle Quantum Premier

    Time &Date

    C a n c el En t e r N e x t Pre v i ou s R e s e t A c k n o w l ed g e Si l e nc e

    DET-TRONICS

    D1853

    NODE 1 NODE 8

    NODE 3 NODE 6

    NODE 2 NODE 7

    NODE 4 NODE 5

    PATH A PATH B

    WIRING FAULTS

    EQPCONTROLLER

    EAGLEQUANTUM PREMIER

    Safety System Controller

    F ir e Al ar m I nh ib it P ow er

    SuprHigh Gas

    Trouble

    CntrlF lt

    Lon FaultLow Gas Ack Silence

    Out Inhibit

    Eagle Quantum Premier

    Time &Date

    C a n c el En t e r N e x t Pre v io u s R e s e t A c k n o w l ed g e Si l e nc e

    DET-TRONICS

    Figure 2-2Normal Communication over the LON

  • 7/25/2019 95-8533-16.1-EQP

    12/156

    2-6 95-853316.1

    MAJOR COMPONENT

    DESCRIPTIONS

    The system has three (3) main componentgroups the System Controller, LON (LocalOperating Network), and Intelligent FieldDevices.

    SYSTEM CONTROLLER

    The Controller (see Figure 2-5) performsall communication, command, and controlfunctions for the system. The Controllersupports both Static and Programmablelogic. Other features include:

    Redundant controller capability

    User pushbutton controls (reset,

    acknowledge, etc.) Real time system clock

    Internal alarm sounder

    Vacuum fluorescent text based display thatshows current system status

    8 programmable unsupervised inputs

    8 programmable unsupervised relayoutputs

    RS-485 Modbus RTU communication

    interface that supports coils, discreteinputs, and holding registers

    Optional ControlNet communication boardsupports redundant communicationchannels.

    Optional Ethernet DLR communicationboard supports Ethernet Device Level Ringcommunications.

    Ethernet Interface Board supports

    configuration, MODBUS TCP/IP, controllerredundancy, and RS-485 MODBUS.

    Serial Interface Board supportsconfiguration, RS-232 MODBUS, controllerredundancy, and RS-485 MODBUS.

    Controller Redundancy

    The EQP controllers can be configured

    as a redundant pair. See Figure 2-6. Theredundancy scheme is a hot standby systemthat offers the following primary features:

    Automatic configuration of the standbycontroller

    Bumpless transfer

    Forced and automatic switchover

    No downtime on controller replacement

    Automatic synchronization betweencontrollers

    Increased system availability

    During normal operation one controller acts asthe Master while the other acts as the HotStandby.

    Terminology used for redundancy:

    Master controller This is the normal mode

    for non-redundant andmaster controllers. Userlogic is executed, outputsare being controlled andall serial and/or Ethernetports are active.

    Standby controller This controller is receivingall inputs but does nothave any control over theoutputs and user logic is

    not executed. The standbycontroller receivesupdate information fromthe master controllerto ensure a bumplesstransfer should a controllerswitchover occur.

    LON

    S3

    CONFIGURATION

    SOFTWARE

    ONE PROJECT FILE

    LOADED TO

    CONTROLLER A

    CONTROLLER A

    LON ADDRESS 1

    CONTROLLER B

    LON ADDRESS 2

    DCS/PLC/HMI

    HIGH SPEED

    RS-232

    SERIAL LINK

    ETHERNET OR

    RS-232

    SERIAL LINK

    ETHERNET

    OR MODBUS

    RS-485

    B2275

    Figure 2-6 Block Diagram of EQP System

    with Redundant Controllers

    Figure 2-5System Controller

  • 7/25/2019 95-8533-16.1-EQP

    13/156

    95-85332-716.1

    Primary controller The controller assignedaddress 1.

    Secondary controller The controller assignedaddress 2.

    Bumpless transfer During a controllerswitchover no change inoutput will occur due tothe switchover.

    Ethernet Interface Board

    The Ethernet Interface Board supports twoadditional serial ports and two Ethernet ports.See Table 2-4. Ethernet supports 10/100 Mbscommunication. Figure 2-7 shows the EthernetTCP/IP Server/Client and Modbus RTU Master/Slave relationship. For a redundant controllerconfiguration, the board is required in bothcontrollers.

    Serial Interface Board

    The Serial Interface Board supports up to fouradditional serial ports. See Table 2-5. For aredundant controller configuration, the boardis required in both controllers.

    ControlNet Board or Ethernet DLR Board

    (Optional)

    An optional ControlNet Board or EthernetDevice Level Ring (DLR) Board can beinstalled to allow ControlNet or Ethernet DLRcommunication to a compatible PLC. Bothinterfaces operate in a non-interfering manner.The functionality of the ControlNet and EthernetDLR boards is not covered by any approval.Both options offer two ports. See Tables2-6 and Table 2-7. The interfaces must beconfigured through S3 prior to use. Consultthe factory for details. For redundant controllerconfigurations, identical option boards arerequired in both controllers.

    Table 2-6Ports on ControlNet Interface Board

    Port Name Comm Function

    Port A ControlNet ControlNet

    Communication

    Port B ControlNet ControlNet

    Communication

    Table 2-7Ports on Ethernet DLR Interface Board

    Port Name Comm Function

    Port 1 Ethernet

    DLR

    Ethernet DLR

    Communication

    Port 2 Ethernet

    DLR

    Ethernet DLR

    Communication

    Table 2-4Ports on Ethernet Interface Board

    Port Name Comm Function

    Serial Port 2 RS-485

    ModBus (Master/Slave) GroundFault Monitored,Isolated

    Ethernet Port 3 EthernetMODBUS TCP/IP(Master/Slave)SConfiguration

    Ethernet Port 4 EthernetMODBUS TCP/IP(Master/Slave)

    HSSL RedundancyPort

    RS-232RedundantController toController Only

    Table 2-5Ports on Serial Interface Board

    Port Name Comm Function

    Serial Port 2 RS-485ModBus (Master/Slave) Ground FaultMonitored, Isolated

    Serial Port 3 RS-232ModBus (Master/Slave) SConfiguration

    Serial Port 4 RS-232ModBus (Master/Slave)

    HSSLRedundancy Port

    RS-232Redundant Controllerto Controller Only

  • 7/25/2019 95-8533-16.1-EQP

    14/156

    2-8 95-853316.1

    Controller-to-Controller Communication(SLC485)

    The EQP controllers can be configured tocommunicate with up to 12 controllers viaRS-485 communication. The controller-to-controller scheme provides the ability to meetNFPA 72 SLC requirements with the followingprimary features:

    Modular trouble and alarm configuration

    Multiple zone application with controller-to-controller communication

    Multiple media options.

    EQP Supervising System (EQPSS)

    The Det-Tronics EQP controllers can besupervised via the EQPSS using PCs and HMI.Each EQPSS PC can communicate with up to

    12 EQP controllers over Ethernet. This is a Det-Tronics solution. Please consult the factory formore information.

    EQP Marine Application System

    For information regarding EQP MarineApplication Systems, refer to Appendix D.

    LOCAL OPERATING NETWORK (LON)

    The LON is a fault tolerant, two wire, digitalcommunication network. The circuit is arrangedin a loop starting and ending at the Controller.The circuit supports up to 246 intelligent fielddevices spread over a distance of up to 10,000meters (32,500 feet).

    NOTE

    Al l LON devices support ANSI/NFPA

    72 Class X communication with the

    Controller.

    Network Extenders

    Transmitted signals can travel a maximumdistance of 2,000 meters through LONcommunication wire. At the end of thisdistance, a network extender (see Figure2-8) must be installed to rebroadcast thecommunications into the next wire segment.For every network extender added, the lengthof the communications loop extends up to2,000 meters. Due to propagation delaysaround the loop, the maximum loop length islimited to 10,000 meters.

    NOTES

    A network extender is requi red for

    communication loops greater than 60

    nodes.

    Communication wire segment lengths

    are dependant upon physical and

    electrical characteristics of the cable.

    Refer to the installation section for LON

    cable wire information.

    No more than six network extenders may

    be used on the communication loop.

    When a network extender is installed in

    the communication loop, up to 40 field

    devices can be installed per network

    segment. The network segment is the

    wiring segment between two network

    extenders or between a network

    extender and a controller.

    Modbus Slave

    TCP/IP Server

    Modbus Slave

    TCP/IP Server

    TCP/IP Client

    Modbus Master

    10/100M Et hernet LAN

    EQP Controller EQP Controller

    HMI/DCS

    Figure 2-7Ethernet TCP/IP Server/Client Relationship &

    Modbus RTU Master/Slave Relationship

    Figure 2-8Eagle Quantum Premier Network Extender

  • 7/25/2019 95-8533-16.1-EQP

    15/156

    95-85332-916.1

    EQ21xxPS Series Power Supplies and

    EQ2100PSM Power Supply Monitor

    The Power Supply, Power Supply Monitor, andbackup batteries are used to provide powerto the system. The power supply monitorcommunicates trouble conditions to theController. Monitored status conditions include:power supply failure, loss of AC power, lossof battery power, power ground fault, AC andDC voltage (hi/low level), and backup batterycurrent charge levels.

    The Power Supply provides main and backuppower to the EQP System. The device includesmany features such as voltage regulation, highefficiency, and high power factor.

    An equalize switch is located on the frontpanel of the charger for manual activation,or a multi-mode electronic timer can be usedfor automatic activation. Steady state outputvoltage remains within +/ 1/2% of the settingfrom no load to full load for AC input voltageswithin +/ 10% of the nominal input voltage.

    EQP21XXPS(X) Power Supplies and

    EQP2410PS(P) Converter

    The Power Supplies and Converter providemain and backup power to the EQP Systemin ordinary and marine applications. Referto Section 3 of this manual for completeinformation.

    EQ2220GFM Ground Fault Monitor

    The EQ2220GFM Ground Fault Monitor (see

    Figure 2-9) provides ground fault monitoringin a system that includes a floating 24 Vdcpower source. The device detects ground faultconditions on +/ power and all secondaryI/O circuits. A positive or negative groundfault condition is indicated immediately bylocal LEDs, and by a relay contact after a 10second time delay. The ground fault monitor isintended to be mounted in the same enclosureas the controller.

    FIELD DEVICES

    Flame Detectors

    For flame detector installation, operation,maintenance, specifications and orderinginformation, refer to Table 2-8.

    For information regarding USCG Approval ofthe X3301 Flame Detector, refer to Appendix D.

    NOTE

    Existing Eagle Quantum field devices

    such as EQ22xxUV and EQ22xxUVIR

    are supported by the Eagle Quantum

    Premier system (not FM Approved).

    EQ3730EDIO Enhanced Discrete Input/

    Output Module

    The 8 Channel EDIO Module (see Figure 2-10)expands the Input and Output capability of theEagle Quantum Premier System.

    The unit is designed to provide continuousand automated fire/gas protection, whileensuring system operation through continuoussupervision of System Inputs/Outputs.

    Figure 2-9Ground Fault Monitor

    Table 2-8Flame Detector Manuals

    Detector Manual Number

    X3301 95-8527

    X3301A 95-8527 & 95-8534

    X3302 95-8576

    X5200 95-8546

    X2200 95-8549

    X9800 95-8554

    UVHT 95-8570

  • 7/25/2019 95-8533-16.1-EQP

    16/156

    2-10 95-853316.1

    The EDIO module provides eight channels ofconfigurable input or output points that can beprogrammed for supervised or unsupervisedoperation. Each input point can accept firedetection devices such as heat, smoke, orunitized flame detectors. Each output pointcan be configured for signaling or releasing

    output operation. Each channel on the moduleis provided with individual indicators for activeand fault conditions.

    IMPORTANT

    For Class A wiring, two input/output

    channels are combined, thereby

    supporting up to four input/output

    circuits.

    NOTE

    An input must be active for at least 750

    milliseconds in order to be recognized.

    The EDIO module can be mounted directly toa panel, or it can be DIN rail mounted. Systemstatus can be determined using the trouble-shooting procedures, Eagle Quantum SafetySystem Software (S) and the status indicators

    on the module.

    Refer to the Enhanced Discrete Input/OutputModule Specification Data sheet (form number90-1189) for additional information.

    EQ3700 8 Channel DCIO Module

    The 8 Channel Discrete Input/Output (DCIO)Module (see Figure 2-11) consists of eightindividually configured channels. Each channelis configured as either an input or output withthe appropriate wiring supervision. Wiringsupervision includes none, open circuits, and

    "open and short" circuits. In addition to definingthe type of supervision, an input channel is alsoconfigured to generate the appropriate staticlogic alarm message to the controller.

    NOTE

    NFPA 72 requires wire supervision

    select ion for f i re detect ion and

    not i f icat ion devi ces ( ID C, NAC,

    supervisory and releasing devices).

    Heat, smoke, or unitized flame detectors canbe wired into channels defined as inputs.Horns, strobes/beacons, and solenoids can bewired into channels defined as outputs.

    NOTE

    The DCIO outputs only support

    equipment that operates on 24 vdc (notto exceed 2 amperes per channel).

    The DCIO has two device status LEDs, as wellas two LEDs for each channel. On the devicelevel, one green LED indicates power, while theother amber LED indicates a LON CPU fault. Foreach channel, one red LED indicates channelactivation and the other amber LED indicatesa fault condition when wiring supervision isdefined for the channel.

    Refer to the DCIO Specification Data sheet(form number 90-1149) for additionalinformation.

    Figure 2-11DCIO ModuleFigure 2-10Enhanced Discrete

    Input/Output Module

  • 7/25/2019 95-8533-16.1-EQP

    17/156

    95-85332-1116.1

    EQ3720 8 Channel Relay Module

    The 8 Channel Relay Module (see Figure 2-12)consists of eight individually configured outputchannels.

    NOTE

    The relay module only supportsequipment that operates on 24 vdc (not

    to exceed 2 amperes) at each output

    channel.

    The relay module has two LEDs for the deviceand two LEDs for each channel. On the devicelevel, one green LED indicates power, whilethe other amber LED indicates a LON CPUfault. For each channel, one red LED indicates

    channel activation and the other amber LEDindicates that the module operating voltage islow or that the module has not been configured(all eight channel LEDs blink).

    Refer to the Relay Module Specification Datasheet (form number 90-1181) for additionalinformation.

    EQ3710AIM Analog Input Module

    The 8 Channel Analog Input Module (seeFigure 2-13) provides a means of connectingdevices with a calibrated 4-20 mA outputsignal to the Eagle Quantum Premier System.

    The Analog Input Module (AIM) provides 8

    configurable channels that can be set for eithercombustible gas mode or universal mode. Thecombustible gas mode provides a numberof automatically programmed settings, andalarm thresholds that are limited to approvalbody requirements. The universal mode isused for generic devices where control overall configuration parameters is required. Alldevices must provided their own calibrationfacilities.

    For fire detector 4-20 mA inputs, the AnalogInput Module (AIM) is certified for use as anNFPA 72 Class B Approved input.

    Refer to the Analog Input Module SpecificationData sheet (form number 90-1183) foradditional information.

    Figure 2-12Eight Channel Relay Module Figure 2-13Eight Channel Analog Input Module

  • 7/25/2019 95-8533-16.1-EQP

    18/156

  • 7/25/2019 95-8533-16.1-EQP

    19/156

    95-85332-1316.1

    EQ25xxARM Agent Release Module

    The EQ25xxARM Series Agent Release Module(ARM) (see Figure 2-15) provides agentrelease or deluge pre-action capability. Thedevice is controlled by programmable logic inthe Controller. Time delay, abort and manualrelease sequences allow the device output to

    be programmed for use in unique applications.

    The device is field programmed to operate inone of the following modes:Timed Output is activated for a field

    selectable duration from 1 to65,000 seconds.

    Continuous Output latches until reset.Non-latching Output follows the input.

    The device can monitor and control two outputdevices (24 vdc rated) that are programmedand energized together. The release circuitsare compatible with a variety of solenoid orinitiator based suppression systems.

    The release circuit is supervised for open circuit

    conditions. If a trouble condition occurs (opencircuit or solenoid supply voltage less than 19volts), it will be indicated at the Controller. Eachoutput is rated at 2 amperes and auxiliary inputterminals are provided for additional 24 vdcoutput power where needed.

    NOTE

    For deluge and pre-action applications,

    the input voltage to the ARM or

    DCIO must be 21 VDC minimum with

    connection to any solenoid listed in

    Table 2-9 or 2-10. Wiring must be in

    accordance with the listed maximum

    wiring lengths.

    Refer to the EQ25xxARM Specification Datasheet (form number 90-1128) for additionalinformation

    Figure 2-15Agent Release Module

    Table 2-10Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications

    Table 2-9Solenoid Compatibility with Agent

    Release Module for Deluge and Pre-Action Applications

    FM Group Device

    B ASCO T8210A107

    D ASCO 8210G207

    E Skinner 73218BN4UNLVNOC111C2

    F Skinner 73212BN4TNLVNOC322C2

    G Skinner 71395SN2ENJ1NOH111C2

    H Viking 11601

    Solenoids Maximum Wire Length in Feet (Meters)

    FM Solenoid Group Manufacturer Model 12 AWG 14 AWG 16 AWG 18 AWG

    B ASCO T8210A107 183 (56) 115 (35) 72 (22) 46 (14)

    D ASCO 8210G207 314 (96) 198 (60) 124 (38) 78 (24)

    E Skinner 73218BN4UNLVNOC111C2 331(101) 208 (63) 131 (40) 82 (25)

    F Skinner 73212BN4TNLVNOC322C2 130 (40) 82 (25) 51 (16) 32 (10)

    G Skinner 71395SN2ENJ1NOH111C2 331 (101) 208 (63) 131 (40) 82 (25)

    H Viking 11601 180 (55) 110 (34) 70 (21) 45 (14)

  • 7/25/2019 95-8533-16.1-EQP

    20/156

  • 7/25/2019 95-8533-16.1-EQP

    21/156

    95-85332-1516.1

    EQ22xxDCU and EQ22xxDCUEX

    Digital Communication Units

    The EQ22xxDCU Digital Communication Unit(DCU) is an analog signal input device thataccepts a 4 to 20 milliampere signal. Thedevice is typically connected to gas detectors,where the analog signal represents the gas

    concentration.

    Calibration of the DCU involves a non-intrusiveprocedure that can be performed by oneperson at the device without declassifying thearea.

    The device supports two alarm setpoints thatare defined as part of the devices configurationsetup. When detecting combustible gases,

    the alarm setpoints represent low and highgas alarm levels. When detecting oxygen, thealarms represent the range for the acceptableoxygen level. If oxygen drops below the alarmrange, a low alarm is generated by the device.

    PointWatch/DuctWatch IR gas detector as wellas electrochemical sensors (hydrogen sulfide,carbon monoxide, chlorine, sulfur dioxide, andnitrogen dioxide) are examples of devices that

    can be connected to the DCU.

    NOTE

    A catalytic sensor can be connected

    to a DCU through a transmitter, which

    converts the millivolt signal to a 4 to 20

    milliampere signal.

    The EQ22xxDCUEX is a specialized versionof the DCU that contains a transmitter forconnection to a Det-Tronics Model CGScatalytic combustible gas sensor.

    Refer to the EQ22xxDCU Specification Datasheet (form number 90-1118) for additionalinformation.

    PIRECL PointWatch Eclipse

    The Pointwatch Eclipse Model PIRECL isa diffusion-based, point-type infrared gasdetector that provides continuous monitoring ofcombustible hydrocarbon gas concentrationsin the range of 0 to 100% LFL.

    The LON supervision meets Signaling LineCircuit (Class X) requirements per NFPA72:2010 for the Model PIRECL.

    For PIRECL installation, operation,maintenance, specifications and orderinginformation, refer to form number 95-8526.

    NOTE

    The low alarm range for the EQP PIRECL

    is 5-40% LFL (the standard PIRECL is

    5-60% LFL).

    For information regarding USCG Approval ofthe PIRECL Detector, refer to Appendix D.

    OPECL Open Path Eclipse

    The Open Path Eclipse Model OPECL is anopen path infrared gas detection system thatprovides continuous monitoring of combustiblehydrocarbon gas concentrations in the rangeof 0 to 5 LFL-meters, over a distance of 5 to120 meters.

    The LON supervision meets Signaling LineCircuit (Class X) requirements per NFPA72:2010 for the Model OPECL.

    For OPECL installation, operation,maintenance, specifications and orderinginformation, refer to form number 95-8556.

    UD10 DCU Emulator

    The FlexVu Model UD10 DCU Emulator(UD10-DCU) is designed for applications thatrequire a gas detector with digital readout ofdetected gas levels. Its LON interface board

    makes the UD10-DCU compatible with EagleQuantum Premier systems by digitizing the4-20 mA analog signal from the attachedsensor/transmitter and transmitting the valueas a process variable over the LON to the EQPcontroller. The UD10-DCU is designed for usewith most currently available Det-Tronics gasdetectors.

    For a list of compatible gas detectors, as wellas information regarding installation, operation,maintenance, specifications and orderinginformation, refer to form number 95-8656.

  • 7/25/2019 95-8533-16.1-EQP

    22/156

    3-1 95-853316.1

    Section 3

    Installation

    NOTE

    For specific information regarding

    systems meeting EN54 standards, refer

    to the EQ5400 Series operation manual95-8642.

    SAFETY SYSTEM DESIGN

    REQUIREMENTS

    Many factors need to be considered whendetermining proper EQP System design. Thefollowing paragraphs will discuss these factorsand other issues useful in designing, installing

    and configuring the Eagle Quantum PremierSystem.

    IDENTIFYING THE AREA OF PROTECTION

    In order for the system to provide optimumcoverage and protection, it is critical toproperly define the required Area ofProtection (total area being monitored by thesystem). The area of protection should includeall hazard sources requiring monitoring, as wellas suitable locations for mounting detection,extinguishing, notification, and manualdevices. In order to accurately define the areaof protection and provide maximum protection,all potential Real and False hazard sourcesmust be identified. The number and locationof Real Hazards determines the extent of thearea of protection, and impacts all subsequentdesign decisions.

    WARNING!

    When drilling through surfaces in the

    process of mounting equipment, verify

    that the location is free of electrical

    wiring and electrical components.

    IDENTIFYING WIRING, NETWORK (LON),

    AND SYSTEM POWER REQUIREMENTS

    General Wiring Requirements

    WARNING!

    DO NOT open any junction box or device

    enclosure when power is applied without

    first de-classifying the hazardous area.

    CAUTION!

    Any deviation from the manufacturers

    recommended wiring practices can

    compromise system operation and

    effectiveness. ALWAYS consult the factory

    if different wire types or methods arebeing considered.

    NOTE

    All field wiring must be marked per NFPA

    70 Article 760.

    NOTE

    Specific installation requirements may

    differ depending on local installation

    practices and compliance wi th th ird

    party certifications. For local installation

    practices, consult the local authorit y

    having jurisdiction. For compliance with

    third party certifications, consult the

    appropriate appendix in this manual for

    additional installation requirements.

    Power Wiring

    IMPORTANT!

    For deluge and pre-action applications,

    input voltage to the DCIO or ARM must

    be 21 vdc minimum to ensure proper

    operation of the connected output

    device.

    IMPORTANT

    To ensure proper operation of fielddevices, the voltage input to the device

    (measured at the device) must be within

    the range indicated for that device in the

    Specifications section of this manual

    (18 Vdc minimum).

    System Wiring (ATEX and IECEx)

    For the interconnection of the modules withinthe EQP system, use fixed installed wiring.

    (For correct wiring size and type for a specificdevice, refer to the appropriate section in thismanual.)

    For ambient temperatures below 10C andabove +60C, use field wiring suitable for bothminimum and maximum ambient temperatures.

  • 7/25/2019 95-8533-16.1-EQP

    23/156

    95-85333-216.1

    The EQP Ex n modules may only be installed,connected or removed when the area is knownto be non-hazardous. The screw terminals areto be tightened with a minimum torque of 0.5Nm. Equipotential bonding connection facilitieson the outside of electrical equipment shallprovide effective connection of a conductor

    with a cross-sectional area of at least 4 mm2

    .

    The Eagle Quantum Premier system utilizes apower supply that provides an isolated 24 vdcbattery backed-up power to the fire protectiondevices as described in NFPA 72. More thanone power supply may be used in a system toprovide power to different sets of equipment aspart of the system.

    The power supply wiring may consist of one ormore daisy-chained wire segments providingpower to the devices. For each of the daisy-chained wire segments, the installer mustcalculate the voltage drops that occur acrossthe devices in order to determine the gauge ofthe wire that will be installed.

    A power supply wiring diagram should containinformation describing wire distances andcurrent draws associated with all devices

    connected to the wire segment. A typicalpower supply wiring recommendation is thatthe voltage drop from the power source to theend device should not exceed ten percent.Using 24 vdc as a reference, the maximumvoltage drop should not exceed 2.4 vdc. A wiregauge must be selected to ensure that the end

    device has at least 21.6 vdc or higher.

    In order to calculate the power supply voltagefor the end device, calculate the voltage dropsthat occur due to each wire segment betweenthe devices. This involves determining thetotal current draw and the two conductor wireresistance per each wire segment.

    Example:Can 18 AWG wire be used to powerthree devices from the 24 vdc power supply?Refer to the figure below for wiring and devicecurrent draw information along with voltagedrop calculations.

    Answer: If the Authority Having Jurisdiction(AHJ) requires a voltage loss of 10% or less,only 16 AWG wire could be used, since the enddevice would require 21.4 vdc. If there is nolocal requirement, then 18 AWG wire could beused to provide power to the devices.

    Device 1

    65 mACurrent Draw

    Device 2

    65 mACurrent Draw

    Device 3

    565 mACurrent Draw

    24 vdc PowerSupply

    18 AWG Single Wire Resistance: R = 0.6385 Ohms per 100 ft2 Conductor Resistance: CR = 2 R

    Device 1 Voltage = Supply Voltage (Voltage Drop)= 24 (I CR)

    = 24 (0.695 0.6385)= 23.55 vdc

    Device 2 Voltage = Device 1 Voltage (Voltage Drop)= 23.55 (I CR)

    = 23.55 (0.630 1.9155)= 22.35 vdc

    Device 3 Voltage = Device 2 Voltage (Voltage Drop)= 22.35 (I CR)

    = 22.35 (0.565 1.9155)= 21.27 vdc

    50 ft0.6385 Ohms

    150 ft1.9155 Ohms

    150 ft1.9155 Ohms

    Total Current695 mA

    Total Current630 mA

    =Device 2

    +Device 3

    Total Current565 mA

    =Device 3

  • 7/25/2019 95-8533-16.1-EQP

    24/156

    3-3 95-853316.1

    Determining Power Requirements

    Tables 3-1 and 3-2 are provided for calculatingthe total current requirements for those parts ofthe system requiring battery backup.

    Table 31StandbyCurrent Requirements at 24 vdc

    Note: Standby current is the average current draw for the device in normal mode.

    This table is for battery calculations only.

    Device TypeNumber of

    DevicesStandbyCurrent

    Total Current for Device Type

    EQP Controller X 0.360 =

    EQ3LTM Module X 0.001 =

    EDIO Module X 0.075 =

    DCIO Module X 0.075 =

    Power Supply. Monitor X 0.060 =

    IDC/IDCGF/IDCSC X 0.055 =

    X3301/X3301A - w/o heater X 0.160 =

    X3301/X3301A - with heater X 0.565 =

    X3302 - without heater X 0.160 =

    X3302 - with heater X 0.565 =

    X2200 X 0.135 =

    X9800 - without heater X 0.085 =

    X9800 - with heater X 0.420 =

    X5200 - without heater X 0.155 =

    X5200 - with heater X 0.490 =

    DCUEX X 0.145 =

    DCU with EC Sensor X 0.060 =

    DCU with PointWatch X 0.300 =

    DCU with DuctWatch X 0.300 =

    Relay Module X 0.120 =

    Analog Input Module X 0.160 =

    EQ2220GFM X 0.018 =

    PIRECL X 0.270 =

    OPECL Transmitter X 0.220 =

    OPECL Receiver X 0.220 =

    ARM X 0.075 =

    SAM X 0.060 =

    Network Extender X 0.090 =

    ASH Module X 0.560 =EQ21xxPS Power Supply X 0.350 =

    Other X =

    Total StandbyCurrent for System (in amperes) =

  • 7/25/2019 95-8533-16.1-EQP

    25/156

    95-85333-416.1

    Table 3-2AlarmCurrent Requirements at 24 Vdc

    Device TypeNumber of

    DevicesAlarm Current Total Current for Device Type

    EQP Controller X 0.430 =

    EQ3LTM Module X 0.001 =

    EDIO 8 Inputs X 0.130 =EDIO 8 Outputs X 0.075 =

    DCIO 8 Inputs X 0.130 =

    DCIO 8 Outputs X 0.075 =

    Relay Module X 0.120 =

    Power Supply Monitor X 0.060 =

    IDC/IDCGF/IDCSC X 0.090 =

    X3301/X3301A - w/o heater X 0.160 =

    X3301/X3301A - with heater X 0.565 =

    X3302 - without heater X 0.160 =

    X3302 - with heater X 0.565 =

    X2200 X 0.135 =

    X9800 - without heater X 0.085 =

    X9800 - with heater X 0.420 =

    X5200 - without heater X 0.155 =

    X5200 - with heater X 0.490 =

    DCUEX X 0.160 =

    DCU with EC Sensor X 0.075 =

    DCU with PointWatch X 0.320 =

    DCU with DuctWatch X 0.320 =

    Analog Input Module X 0.300 =

    EQ2220GFM X 0.018 =

    PIRECL X 0.275 =

    OPECL Transmitter X 0.220 =

    OPECL Receiver X 0.220 =

    ARM X 0.120 =

    SAM X 0.120 =

    Network Extender X 0.090 =

    ASH Module X 0.560 =

    EQ21xxPS Power Supply X 0.350 =Other X =

    Total Solenoid Load +

    Total Signaling Load +

    Total AlarmCurrent for System (in amperes) =

    Note: This table is for battery calculations only.

  • 7/25/2019 95-8533-16.1-EQP

    26/156

    3-5 95-853316.1

    EQ211xPS, EQ213xPS and EQ217xPS

    Power Supplies

    Refer to Table 3-3A for Power Supply ratings.

    Backup Battery

    Refer to Table 3-4 or 3-5 to calculate theminimum size of the backup battery (in amphours). Select a sealed lead-acid battery withan adequate amp hour rating.

    NOTE

    Connect two batteries in series for 24

    volts. Batteries must be protected from

    physical damage. The battery installation

    shall be adequately ventilated.

    Battery Charger

    Use the following formula to calculate theminimum battery charger size:

    MinimumCharge Rate

    =Alarm

    Current+

    Total Amp Hours48

    CAUTION!Care should be taken when considering

    the final voltage at the device during AC

    power loss. With loss of AC power, the

    device voltage will drop over time as the

    batteries lose their charge. If extended

    periods of AC power loss are to be

    expected, either consider a heavier wire

    gauge or specify batteries with higher

    amp-hour ratings.

    EQP21X0PS(X) Power Supplies

    The EQP2110PS(P) and EQP2120PS(B)Power Supplies are used in pairs where theprimary source of input supply is connected toone and the secondary source is connected tothe other. Each power supply may be backedup by another power supply of the samemodel or by a DC-DC converter (see Figures3-23A, B and C for available configurations).A maximum of eight power supplies operatedin parallel can be connected to each input

    supply. Both the primary and secondary setsmust be individually capable of operating thesystem without the other supply. The secondarysource is required to be continuously powered.

    The use of these supplies is based uponacceptance of the local AHJ of the securesupply system that provides the secondarysupply. These supplies must be used in aredundant configuration, where one bank of

    supplies is fed from the primary source andthe other bank from the secondary source.Both primary and secondary supplies shallbe continuously available and both rated for aminimum 100% of load.

    Refer to Table 3-3B for power supply ratings.

    Characteristic

    Power Supply

    EQ2110PS/EQ2111PS EQ2130PS/EQ2131PS EQ2175PS/EQ2176PS

    Input Voltage 120 vac 120/208/240 vac 120/208/240 vac

    Input Current 4 Amps 11/6/6 Amps 24/15/12 Amps

    Input Frequency 60 Hz EQ2110PS 60 Hz EQ2130PS 60 Hz EQ2175PS

    Input Frequency 50 Hz EQ2111PS 50 Hz EQ2131PS 50 Hz EQ2176PS

    Supply Rating 10 Amps 30 Amps 75 Amps

    Maximum Alarm Current 10 Amps 30 Amps 75 Amps

    Maximum Standby Current 3.33 Amps 10 Amps 25 Amps

    Recharge Current 6.67 Amps 20 Amps 50 Amps

    Minimum Battery Capacity** 40 AmpHours 120 AmpHours 300 AmpHours

    Maximum Battery Capacity 100 AmpHours 300 AmpHours 750 AmpHours

    Maximum Deluge Standby Current* 1 Amp 3 Amps 7.5 Amps

    *Only applies to 90 hour back-up applications.

    **Use a battery with a maximum charge rate that exceeds 25% of the rating of the power supply.

    Table 3-3AEQ21xxPS Power Supply Specifications

  • 7/25/2019 95-8533-16.1-EQP

    27/156

    95-85333-616.1

    IMPORTANT

    The EQP21X0PS(X) Power Supplies

    provide EQP System devices with power

    from input supply 120 to 220 V ac. Use

    of this power supply does not provide

    the source of the secondary supply such

    as secondary source batteries, their

    supervision or charging, or UPS. PerNFPA 72-2010 requirements, such power

    supply related requirements must be

    separately provided for and be accepted

    by the local Authority Having Jurisdiction

    (AHJ).

    EQP2410PS(P) Converter

    The EQP2410PS(P) Converter converts theDC input voltage to an adjustable, controlled

    and galvanically separated 24 Vdc outputvoltage. The converter is always connected tothe secondary source.

    Determining Power Requirements

    Use of the EQP2110PS(P) andEQP2120PS(B) Power Supplies provides theprimary and secondary supplies.

    The EQP2410PS(P) Converter provides thesecondary supply only. It is used in conjunctionwith the EQP2110PS(P) or EQP2120PS(B)Power Supplies, which serve as the primarysupply (see Figures 3-23A, B and C foravailable configurations). The customer isresponsible for providing adequate secondarypower supply source needs. The ac inputcurrent requirements for EQP2XX0PS(X)in relation to EQP system dc current load(power supply output) are calculated using thefollowing formula:

    Input Current = [Output Current x OutputVoltage Input Voltage Efficiency] + 0.43 A

    Example:

    [20 Adc x 28 Vdc 120 Vac 0.91] + 0.43 =

    5.56 Aac

    For Standby Current (amperes ac)requirements, use Total Standby Current(amperes dc) for the systems applicable fielddevices from Table 3-1.

    For Alarm Current (amperes ac) requirements,

    Standby Current Standby Time* Standby Amp HoursX =

    24 Hours

    Alarm Current 5 Minute Alarm Time* Alarm Amp HoursX =

    0.083 Hours

    Sum of Standby and Alarm Amp Hours =

    Multiply by 1.2 (20% Safety Factor) X

    Total Battery Amp Hour Requirement

    T0014B

    * FM MINIMUM REQUIREMENT FOR EXTINGUISHING SYSTEMS

    IS 24 HOURS STANDBY TIME AND 5 MINUTES ALARM TIME.

    Table 3-4Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge

    Standby Current Standby Time* Standby Amp HoursX =

    90 Hours

    Alarm Current 10 Minute Alarm Time* Alarm Amp HoursX =

    0.166 Hours

    Sum of Standby and Alarm Amp Hours =

    Multiply by 1.2 (20% Safety Factor) X

    Total Battery Amp Hour Requirement

    T0040B

    * FM MINIMUM REQUIREMENT FOR DELUGE SYSTEMS IS

    90 HOURS STANDBY TIME AND 10 MINUTES ALARM TIME.

    Table 3-5Backup Battery Requirements for Deluge and Pre-Action Applications

  • 7/25/2019 95-8533-16.1-EQP

    28/156

  • 7/25/2019 95-8533-16.1-EQP

    29/156

    95-85333-816.1

    CAUTION!

    ALWAYS discharge static charges

    from hands before handling electronic

    devices or touching device terminals.

    Many devices contain semiconductors

    that are susceptible to damage by

    electrostatic discharge.

    NOTE

    For more information on proper handling,

    refer to Det-Tronics Service Memo form

    75-1005.

    GROUND FAULT MONITOR

    (GFM) INSTALLATIONMounting

    The GFM is a DIN rail mountable devicedesigned to be mounted in the same enclosureas the EQP controller.

    Wiring

    1. Connect power wiring from the EQPcontroller power terminals 1 and 2 to the

    GFM terminals 1 and 2.2. Connect power wiring from the GFM

    terminals 3 and 4 to the EQP controllerpower terminals 3 and 4.

    3. Connect earth ground to terminal 5 or 10.

    4. Connect the relay contacts as required.

    Refer to Figure 3-1 for terminal blockidentification.

    NETWORK AND NETWORK

    EXTENDER INSTALLATIONMounting

    The device should be securely mounted to avibration free surface. (See the Specificationssection in this manual for device dimensions.)

    Wiring

    All devices on the LON are wired in a loop thatstarts and ends at the System Controller. To

    ensure proper operation, the LON should bewired using high speed communication gradecable.

    NOTE

    Cable meeting the specifications listed in

    Table 3-6 is suitable for distances up to

    2000 meters.

    Any of the cable types listed in Table 3-7 canbe used for wiring the LON for the distances

    indicated.

    6 7 8 9 10

    COMMON NO NC N/C

    RELAY

    SPARE

    1 2 3 4 5

    + +

    EARTHGROUND

    + + EARTH

    GROUND

    24 VDCINPUT VOLTAGE

    NOTE: RELAY CONTACTS ARE SHOWN IN THE REST STATE,NO POWER APPLIED. RELAY IS ENERGIZED WITH

    POWER APPLIED AND NO GROUND FAULT(TERMINALS 6 & 7 CLOSE, TERMINALS 6 & 8 OPEN).

    Figure 3-1Terminal Configuration for Ground Fault Monitor

  • 7/25/2019 95-8533-16.1-EQP

    30/156

    3-9 95-853316.1

    NOTE

    If no network extenders are used, the

    distances listed are for the entire loop.

    If network extenders are used, the

    distances listed are for the wiring length

    between network extenders or between

    a network extender and the System

    Controller.

    IMPORTANT!

    Det-Tronics recommends the use of

    shielded cable (required by ATEX)

    to prevent external electromagnetic

    interference from affecting field devices.

    WARNING!

    Be sure that the selected cable meets

    all job specifications and is rated for the

    installation per local and national codes

    and practices. The use of other cable

    types can degrade system operation.

    If necessary, consult factory for further

    suggested cable types.

    Table 3-7LON Maximum Cable Lengths

    Note: *Use the same type of cable in each wiring

    segment between network extenders.

    **Maximum wire lengths represent

    the linear wire distance of LON

    communications wiring between network

    extenders. Be sure that selected cable meets all job

    specifications.

    If necessary, consult factory for further

    suggested cable types.

    ***Cables designed to ISA SP50 Type A

    or IEC 61158-2 Type A are suitable for use

    in LON/SLC wiring. For armored version,

    contact cable manufacturer.

    Table 3-6Typical Specification for 16 AWG (1.5 mm2) LON Wiring Cable per Echelon

    Minimum Typical Maximum Units Condition

    DC Resistance, each conductor 14 14.7 15.5 ohm/km 20 C per ASTM D 4566

    DC Resistance Unbalanced 5% 20 C per ASTM D 4566

    Mutual Capacitance 55.9 nF/km per ASTM D 4566

    Characteristic Impedance 92 100 108 ohm 64 kHz to 1 MHz, per ASTM D 4566

    Attenuation 20 kHz 1.3 dB/km 20 C per ASTM D 4566

    64 kHz 1.9

    78 kHz 2.2

    156 kHz 3

    256 kHz 4.8

    512 kHz 8.1

    772 kHz 11.3

    1000 kHz 13.7

    Propagation Delay 5.6 nsec/m 78 kHz

    T0049B

    Length: 6,500 feet/2000 meters maximum (basic loop or between Network Extenders).

    Type: Single twisted pair.

    Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield.

    Cables meeting these specifications are good for up to 2000 meters.

    LON Cable Maximum Length**

    (Manufacturer and Part No.)* Feet Meters

    Belden 3073F (Tray Rated) 6,500 2,000

    Det-Tronics NPLFP 6,500 2,000

    Technor BFOU 4,900 1,500

    Rockbestos Gardex Fieldbus***1 Shielded Pair, 16 AWG,Type TC, p/n FB02016-001 6,500 2,000

    1 Shielded Pair, 18 AWG,Type TC, p/n FB02018-001 6,500 2,000

  • 7/25/2019 95-8533-16.1-EQP

    31/156

  • 7/25/2019 95-8533-16.1-EQP

    32/156

    3-11 95-853316.1

    INITIATING DEVICE CIRCUIT

    (IDC) INSTALLATION

    EQ22XXIDC SERIES INITIATING DEVICE

    CIRCUIT (IDC)

    The following paragraphs describe how to

    properly install the EQ22xxIDC InitiatingDevice Circuit.

    Mounting

    The device should be securely mounted to avibration free surface. (See Specifications inthis manual for device dimensions.)

    WARNING!

    T h e h a za rd o u s a re a mu s t b ede-classified prior to removing a junction

    box cover with power applied.

    Wiring

    1. Remove cover from device junction box.

    2. Connect external system wiring to the

    appropriate terminals on the terminal block.(See Figure 3-4 for terminal block locationand Figure 3-5 for terminal identification).The input to the IDC consists of one ormore normally open switches (momentarypushbuttons are not recommended), with a10K ohm, 1/4 watt EOL resistor in parallelacross the furthest switch from the input.

    IMPORTANT!

    An EOL resistor must be installed on

    both IDC inputs (including unused

    inputs) . Wiring impedance must not

    exceed 500 ohms.

    3. Check wiring to ensure that ALL connectionshave been properly made.

    IMPORTANT!

    Be sure that the keyed ribbon cable is

    properly connected to the terminal board.

    4. Inspect the junction box O-ring to be sure

    that it is in good condition.5. Lubricate the O-ring and the threads of the

    junction box cover with a thin coat of greaseto ease installation and ensure a watertightenclosure.

    NOTE

    The recommended lubricant is a silicone

    free grease, available from Det-Tronics.

    6. Set the node address for the device. (SeeSetting Device Network Addresses in thissection.)

    7. Place the cover on the junction box andtighten only until snug. DO NOT overtighten.

    GND

    910

    78

    56

    34

    12

    13

    14

    1112

    A1870

    Figure 3-4IDC Terminal Wiring Board Mounted in Six-Port

    Junction Box

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    IDC MANUAL PULL STATIONOR OTHER CONTACT DEVICE

    14

    13

    12

    11

    +

    +

    24 VDC

    +

    +

    A

    B

    A

    B

    CIRCUIT 1

    CIRCUIT 2

    COM 2

    COM SHIELD

    COM 1

    EOL (10K)

    EOL (10K)

    A1871

    Figure 3-5Terminal Configuration for IDC

  • 7/25/2019 95-8533-16.1-EQP

    33/156

    95-85333-1216.1

    EQ22XXIDCGF SERIES INITIATING

    DEVICE CIRCUIT GROUND FAULT

    The following paragraphs describe howto properly install and configure theEQ22xxIDCGF Initiating Device Circuit GroundFault.

    Mounting

    The device should be securely mounted to avibration free surface. (See Specifications inthis manual for device dimensions.)

    Wiring

    WARNING!

    The enclosure must be electricallyconnected to earth ground.

    1. Remove the enclosure cover from thedevice.

    2. Remove the communication module fromthe junction box. Connect external wiringto the appropriate points on the deviceterminal block. (See Figure 3-4 for terminalblock location and Figure 3-6 for terminal

    identification)

    3. Check wiring to ensure that ALL connectionshave been properly made.

    4. Inspect the enclosure O-ring to be sure thatit is in good condition. Lubricate the O-ringand the threads of the enclosure cover toease both installation and future removal ofthe cover.

    NOTE

    The recommended lubricant is a silicone

    free grease available from Detector

    Electronics.

    WARNING!

    If the installation uses catalytic type

    combustible gas sensors, it is imperative

    that lubricants containing silicone not beused, since they will cause irreversible

    damage to the sensor.

    5. Install the communication module in thedevice enclosure.

    NOTE

    Be sure the ribbon cable is properly

    connected.

    6. Set the node address for thedevice. (See Setting DeviceNetwork Addresses in this section)

    When configuring the EQ22xxIDCGF,its device type should be configuredas an initiating device circuit (IDC).

    Both inputs must be configured for a trouble

    condition.

    Circuit 1 Open indicates a 24 VDC groundfault condition. Active indicates a+24 VDC ground fault condition.

    Circuit 2 Active indicates aloss of AC input power.Open indicates a loss of batterypower.

    7. Place the cover on the enclosure andtighten until snug. DO NOT over tighten.

    Figure 3-6Terminal Configuration for IDCGF

    3

    4

    5

    6

    7

    8

    9

    10

    14

    13

    12

    11

    +

    +

    24 VDC

    +

    A

    B

    A

    B

    INPUT

    COM 2

    COM SHIELD

    COM 1

    68K OHM

    RESISTOR

    RELAY CONTACT

    FOR MONITORING

    BATTERY.

    CONTACT OPENS

    WITH BATTERY

    TROUBLE CONDITION.

    RELAY CONTACT

    FOR MONITORING

    AC POWER.

    CONTACT CLOSES

    ON LOSS OF

    AC POWER.

    B1922

    NOTE: ENCLOSURE AND/OR MOUNTING BRACKET

    MUST BE CONNECTED TO EARTH GROUND.

  • 7/25/2019 95-8533-16.1-EQP

    34/156

    3-13 95-853316.1

    EQ22xxIDCSC series initiating Device

    Circuit Short Circuit (Not FM Approved)

    The following paragraphs describe howto properly install and configure theEQ22xxIDCSC Initiating Device Circuit ShortCircuit.

    Mounting

    The device should be securely mounted to avibration free surface. (See Specifications inthis manual for device dimensions.

    Wiring

    CAUTION!

    The enclosure should be electrically

    connected to earth ground.

    1. Remove the cover from the deviceenclosure.

    2. Remove the communication module fromthe junction box. Connect external wiringto the appropriate terminals on deviceterminal block. (See Figure 3-4 for terminalblock location and Figure 3-7 for terminalidentification.) The input to the IDCSCconsists of a normally open switch with a3.3k ohm series resistor, and a 10K ohm,1/4 watt EOL resistor in parallel across theswitch.

    NOTE

    An EOL resistor must be installed on

    both IDCSC inputs (including unused

    inputs) . Wiring impedance must not

    exceed 500 ohms. A 3.3K ohm resistor

    must be instal led in series wi th the

    switch. For correct operation, only one

    switch per input can be connected.

    3. Check wiring to ensure that ALL connectionshave been properly made.

    4. Install the communication module in thedevice enclosure.

    5. Inspect the enclosure O-ring to be sure thatit is in good condition. Lubricate the O-ringand the threads of the enclosure cover toease both installation and future removal ofthe cover.

    NOTE

    The recommended lubricant is a silicone

    free grease available from Detector

    Electronics.

    NOTE

    Be sure the ribbon cable is properly

    connected.

    6. Set the node address for the device. (SeeSetting Device Network Addresses in thissection.)

    7. Place the cover on the enclosure andtighten until snug. Do not over tighten.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    IDCSC

    MANUAL PULL STATION

    OR OTHER CONTACT DEVICE

    14

    13

    12

    11

    +

    +

    24 VDC

    +

    +

    A

    B

    A

    B

    CIRCUIT 1

    CIRCUIT 2

    COM 2

    COM SHIELDS

    COM 1

    C2076

    EOL (10K)

    3.3 K

    EOL (10K)

    3.3 K

    Figure 3-7IDCSC Terminal Identification

    EQ3XXX CONTROLLERINSTALLATION

    The following paragraphs describe how toproperly install and configure the EQ3XXXController.

    ENCLOSURE REQUIREMENTS

    The Controller must be properly installed in asuitable enclosure that is rated for the location.

    The enclosure must provide space to installand wire the Controller and must also providefor ground wire termination. The enclosuremust contain either a keyed lock or a specialtool to gain access into the enclosure. Theenclosure should be rated for the temperaturerange of the location plus the temperature riseof all equipment installed inside the enclosure.

  • 7/25/2019 95-8533-16.1-EQP

    35/156

    95-85333-1416.1

    The enclosure must be rated for electricalequipment that is going to be installed.

    NOTE

    The Controller and enclosure must be

    connected to earth ground.

    For ordinary locations when entry is required tooperate the equipment, the cabinet should bea dead-front construction and 16-gauge cold-rolled steel. The door lock system shall acceptdifferent keys for entry. An Authorized Personskey and a Person-in-charge key will allow entryinto the cabinet. The cabinet should contain awindow to view the Controllers text display andLED indicators.

    NOTE

    For any selected enclosure, theenclosure must conform to all applicable

    regulations and requirements.

    NOTE

    The Trouble signal must be located in an

    area where it is likely to be heard.

    Classified locations require the appropriatehazardous rated enclosure. It is recommended

    that operators/switches be installed in theenclosure. This avoids the need to declassifythe area in order to operate the Controller.Regulations require that key switches beinstalled for certain operations. An appropriatewindow should be part of the enclosure in orderto allow an operator to view the text display andLED indicators.

    NOTE

    If an enclosure does not have a keyed

    entry, a special tool is required to gain

    entry into an enclosure.

    Det-Tronics offers several approved (FM/CSA/ATEX/CE) hazardous area enclosures that haveEagle Quantum Premier equipment installed inthe enclosure. Contact Det-Tronics for furtherinformation.

    MOUNTING

    The Controller is designed for direct panelmounting or DIN rail (optional) mounting. SeeSpecifications section of this manual formounting dimensions.

    NOTE

    Clips for DIN rail mounting are available,

    but must be specified at the time of

    ordering.

    NOTE

    A minimum clearance of 4 inches

    between the Controller and nearby

    equipment is re