a or b existing cylinder see note 5 on sht 5...drawing number coordinator r.c.e. 56523 date revision...
TRANSCRIPT
20" TO 54" DIAMETER PIPE
BETW EEN SCRW AND W SP
BUTT STRAP CONNECTION
DRAWING
NUMBER
COORDINATOR R.C.E. 56523 DATE
BY APPROVED DATEREVISION
CITY OF SAN DIEGO - STANDARD DRAWING OF SAN DIEGO STANDARDS COMMITTEERECOMMENDED BY THE CITY
9/7/18
SDW -175
ORIGINAL EH J. NAGELVOORT 09/18
A or B
4" MIN (TYP)SEE NOTE 7 ON SHT 5
SEE NOTE 3 ON SHT 5
(TYP)
SHEET 2
A or B
(TYP)
FOR PREPARING SCRW PIPE (C303) FOR BUTT STRAP INSTALLATION, SEE SHEET 4.4.
FOR FINAL BUTT STRAP CONNECTION AND M ORTAR COATING DETAILS, SEE DETAILS ON SHEET 3.3.
FOR BUTT STRAP THICKNESS AND W IDTH, SEE TABLE 1, SHEETS 6 & 7.2.
FOR INSTALLATION INSTRUCTIONS AND NOTES, SEE SHEET 5.1.
NOTES:
1"
6"(TYP)butt W
4" MIN 4" MIN
PLAN VIEW
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
SHT 5
& 5 ON
NOTES 4
SEE
SEE NOTE 5 ON SHT 5
EXISTING CYLINDER
AW W A C303
PRETENSIONED PIPE
EXISTING SCRW PIPE,
NOTE 3 ON SHT 3
FILLER BAR, SEE
SHOW N FOR CLARITY
AW W A C200, COATING NOT
W ELDED STEEL PIPE (W SP)
SHT 4
W ELD SEE
INITIAL
SHT 4
PRETENSIONED ROD, SEE
EXISTING PIPE W /
REGARDING CUTTING OF
INSTRUCTION AND DETAILS
EDGE OF CUT, FOR
SHEET 3
CONNECTION SEE
BUTT STRAP
ON SHT 5
SEE SHT 3 AND NOTE 12
BUTT STRAP HAND HOLE
SHEET 1 OF 7
20" TO 54" DIAMETER PIPE
BETW EEN SCRW AND W SP
BUTT STRAP CONNECTION
DRAWING
NUMBER
COORDINATOR R.C.E. 56523 DATE
BY APPROVED DATEREVISION
CITY OF SAN DIEGO - STANDARD DRAWING OF SAN DIEGO STANDARDS COMMITTEERECOMMENDED BY THE CITY
9/7/18
ORIGINAL EH J. NAGELVOORT 09/18
SDW -175
NOTES:
t rqd
t rqd
45° (T
YP)
90°0'0" (TYP)
120°0'0" (TYP)
30°0'0" (T
YP)
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C CC
C
BUTT STRAP
CEMENT M ORTAR LINING
FIELD APPLIED
BUTT STRAP
DETAILS, SEE SHEET 3.FOR FINAL M ORTAR COATING 3.
TW O HAND HOLES ON TOP HALF CONTRACTOR M AY ALSO USE 4.
AND W IDTH, SEE TABLE 1.
FOR INSTALLATION INSTRUCTIONS 1.
FOR BUTT STRAP THICKNESS 2.
AND NOTES, SEE SHEET 5.
SEE NOTE 4 20" TO 33" DIAMETER PIPE
SEE NOTE 12 ON SHEET 5
SECTION B-B
SECTION A-A
DIAMETERS 24 INCHES AND LESS.OF PIPE, PER SECTION A, FOR PIPE
SEE NOTE 12 ON SHEET 536" TO 54" DIAMETER PIPE
SHEET 3
SPLICE SEE
BUTT STRAP
HOLE SEE SHEET 3
BUTT STRAP HAND
HOLE SEE SHEET 3
BUTT STRAP HAND
SHEET 3
SPLICE SEE
BUTT STRAP
M ORTAR LINING
FIELD APPLIED CEMENT
SHEET 2 OF 7
20" TO 54" DIAMETER PIPE
BETW EEN SCRW AND W SP
BUTT STRAP CONNECTION
DRAWING
NUMBER
COORDINATOR R.C.E. 56523 DATE
BY APPROVED DATEREVISION
CITY OF SAN DIEGO - STANDARD DRAWING OF SAN DIEGO STANDARDS COMMITTEERECOMMENDED BY THE CITY
9/7/18
ORIGINAL EH J. NAGELVOORT 09/18
SDW -175
BUTT STRAP SPLICE
t y
t y
t y
t y
SEE NOTE 16ON SHT 5
SEE NOTE 3 ON SHT 5
SEE NOTES 14 & 15 ON SHT 5
1/4
t rqd /2
t rqd /2
t rqd
NOTES
FOR INSTALLATION INSTRUCTIONS AND NOTES SEE, SHEET 5.
FOR BUTT STRAP THICKNESS AND W IDTH, SEE TABLE 1, SHEETS 6 & 7.
OUTSIDE DIAMETER OF STEEL CYLINDER (C200) W ITH FILLER BAR SHALL BE
OUTSIDE DIAMETER OF SCRW PIPE STEEL CYLINDER (C303) +0" -1/8".
2"
MIN
1"1"
3"
t rq
d
t rqd
t pip
e
2"
MIN
t rq
d
t pip
e
t y
t y
t fill
er
3"
(TYP)
4" MIN 8" MIN 4" MIN
SEAL
SEE NOTE 10ON SHT 5
SEE NOTE 10 ON SHT 5
BUTT STRAP HAND HOLE
BUTT STRAP CONNECTION
SEE NOTES 10 & 13 ON SHT 5
1/4" MIN W ELD TYP
C
C
C
C
CC
C
C
C
C
C
C
C
C
CC
C
C
C
C
C
C
C C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
CC
C
CC
C
C
CC
CC
C
C
C
C
C
C
C
C
C
C
CC
CC
C
2" x 4" W 0.9 x W 0.9
CEMENT-M ORTAR LINING
BOTTOM HALF OF BUTT STRAP
OF JOINT
IN GAP FOR FULL W IDTH
1/4" x 1" BACKING PLATE
2" x 4" W 0.9 x W 0.9
OVER BUTT STRAP
M ORTAR COATING
5", 3000# STEEL THD HALF COUPLING
CEMENT-M ORTAR LINING
CEMENT-M ORTAR COATING
OVER BUTT STRAP
M ORTAR COATING
AW W A C200 W SP
AW W A C200 W SP
SEE NOTE 10 ON SHT 5
1.
2.
3.
CONCRETE LINING
TO M ATCH EXISTING
HAND APPLY CEMENT-M ORTAR
HOLES SEE NOTE 10 ON SHT 5
CONCRETE LINING
TO M ATCH EXISTING
HAND APPLY CEMENT-M ORTAR
HOLES SEE NOTE 10 ON SHT 5
ON SHT 5
PRETENSION BARS, SEE NOTE 9
CONCRETE LINING
TO M ATCH EXISTING
HAND APPLY CEMENT-M ORTAR
AFTER INSTALLATION.
SEAL-W ELD STEEL PLUGS
5" STEEL, NTP, THD PLUG.
COATING
CEMENT-M ORTAR
:
PRETENSIONED PIPE
EXISTING C303 (SCRW )
PRETENSIONED PIPE
EXISTING C303 (SCRW )
SHEET 3 OF 7
20" TO 54" DIAMETER PIPE
BETW EEN SCRW AND W SP
BUTT STRAP CONNECTION
DRAWING
NUMBER
COORDINATOR R.C.E. 56523 DATE
BY APPROVED DATEREVISION
CITY OF SAN DIEGO - STANDARD DRAWING OF SAN DIEGO STANDARDS COMMITTEERECOMMENDED BY THE CITY
9/7/18
ORIGINAL EH J. NAGELVOORT 09/18
SDW -175
SCRW PIPETO REM AIN
SCRW PIPETO REM OVE
SCRW PIPETO REM AIN
SCRW PIPETO REM OVE
SCRW PIPETO REM AIN NEW PIPE SCRW PIPE
TO REM AIN
NOTE 4 ON SHT 5
L
16" M AX
NOTES:
SEE SHEET 5 FOR DETAILED INSTALLATION INSTRUCTIONS.
SEE SHEETS 1, 2 & 3 FOR BUTT STRAP INSTALLATION.
SEE SHEETS 6 & 7 FOR BUTT STRAP DIMENSIONS.
C OF BUTT STRAP
10" MIN4" MIN
"L"
6" M AX
C
C
C
CC
C
C
C
C
C
C
C
C
C
C
EDGE OF CUT
EDGE OF CUT
UNDAM AGED ROD W RAP
COIL BACK REM AINING BUTT STRAP
M ORTAR COATING
REINFORCED CEMENT-
CUT PROCEDURE
1.
2.
3.
NOTE 7. SHEET 5
SHEET 1 AND
CYLINDER, SEE
STEEL
W RAP TO
W ELD ROD
STRAP, SEE SHEET 1
W RAP TO BUTT
PULL TAUT W ELD ROD
STRAP BY 1" MIN,
OVERLAPPING BUTT
UNCOIL ROD W RAP
SHEET 4 OF 7
20" TO 54" DIAMETER PIPE
BETW EEN SCRW AND W SP
BUTT STRAP CONNECTION
DRAWING
NUMBER
COORDINATOR R.C.E. 56523 DATE
BY APPROVED DATEREVISION
CITY OF SAN DIEGO - STANDARD DRAWING OF SAN DIEGO STANDARDS COMMITTEERECOMMENDED BY THE CITY
9/7/18
ORIGINAL EH J. NAGELVOORT 09/18
SDW -175
PENETRANT TESTING SHALL BE PERFORMED ON THE GROOVE W ELD ROOT PASS.16.
.y
SHALL NOT BE LESS THAN tfiller t15.
rqd
, ELSE W ELD SIZE SHALL BE tfiller
THEN W ELD SIZE SHALL BE ty
IS LESS THAN tfiller
IF t14.
rqd , ELSE W ELD SIZE SHALL BE t
filler , THEN W ELD SIZE SHALL BE t
rqd IS LESS THAN t
filler IF t13.
OR SIMILAR ACCESS POINT.
HAND-HOLES CAN BE OMITTED IF INTERIOR OF PIPE IS ACCESSIBLE THROUGH NEARBY ACCESS M ANW AY 12.
FABRIC HELD 3/8" FROM THE STEEL.
COATING TO EXTERIOR OF PIPE IN ACCORDANCE W ITH AW W A C205/C303 REINFORCED W ITH W ELDED W IRE
USING HAND HOLES. THEN INSTALL HAND HOLE PLUG AND SEAL W ELD. APPLY PORTLAND CEMENT M ORTAR
AFTER W ELDING AND TESTING OF BUTT STRAP IS COMPLETE, APPLY PORTLAND CEMENT M ORTAR LINING 11.
OF ACCESS, AIR TEST HOLES CAN BE OMITTED AND FILLET W ELDS SHALL BE TESTED USING PENETRANT TEST.
HOLES ON COMPLETION OF SOAP AND AIR TEST. IF INSIDE W ELD CANNOT BE PERFORMED DUE TO THE LACK
DRILL AND TAP HOLES FOR AIR TESTING PRIOR TO W ELDING, CONTRACTOR SHALL PLUG W ELD TAPPED 10.
OVERLAP THE BUTT STRAP BY 1" AND W ELD ROD AS SHOW N ON SHEET 1.
W ELD THE BUTT STRAP TO THE CYLINDER, AS SHOW N. PULL TAUT THE REM AINING ROD W RAP AND 9.
OF UNTENSIONED ROD W RAP SO THE BUTT STRAP CAN BE INSTALLED (DO NOT BEND THE RODS).
M ARK AND REM OVE PIPE AND ANY ROD NOT STILL CONNECTED TO THE REM AINING PIPE. COIL BACK PORTION
AFTER W ELDING THE ROD W RAP TO THE STEEL CYLINDER, CUT THE CYLINDER AND ROD W RAP ALONG CUT 8.
RODS AND THE W ELDERS SHALL BE CERTIFIED W ELDERS PER ASME BPVC, SECTION IX.
. ALL W ELDING SHALL BE PERFORMED USING E60XX W ELDING IS PROPERLY W ELDED TO THE STEEL CYLINDER
NOTE THE ROD W RAP HAS TENSION AND CANNOT BE CUT UNTIL IT REM AIN; 6" M AX FROM THE CUT M ARK.
M AKE A 4" LONG W ELD ON ONE CIRCUMFERENTIAL ROD W RAP TO THE STEEL CYLINDER OF THE PIPE TO 7.
M ARK THE CUT LOCATION ON THE EXPOSED ROD W RAPPED CYLINDER.6.
CUT M ARK FOR THE PIPE THAT W ILL BE REM OVED.
FOR THE PIPE THAT W ILL REM AIN. THEN CHIP OFF THE M ORTAR COATING 4” FROM THE CENTERLINE OF THE
CAUTIOUSLY CHIP OFF 10" TO 16" OF THE M ORTAR COATING FROM THE CENTERLINE OF THE CUT M ARK 5.
DETERMINE LENGTH "L" OF PIPE TO BE REM OVED AND M ARK ON PIPE.4.
CONDITIONS.
STRAP W IDTH SHOW N ON TABLE 1 IS THE MINIM UM W IDTH. THE W IDTH M AY BE INCREASED TO MEET FIELD
FABRICATE THE BUTT STRAP USING THE DIMENSIONS SHOW N ON TABLE 1, SHEETS 6 AND 7. THE BUTT 3.
DO NOT W ELD REINFORCING TO CYLINDER OR CUT REINFORCING W HILE PIPE HAS INTERNAL PRESSURE.2.
ENTIRE PIPE SECTION (TO THE NEAREST JOINT) SHOULD BE REM OVED AND REPLACED.
PIPELINE. IF THE CYLINDER THICKNESS IS LESS THAN 10 GAGE (0.135”), DO NOT USE THIS DETAIL. THE
DETERMINE THE PIPE DIAMETER, CYLINDER THICKNESS AND PRESSURE RATING OF THE EXISTING 1.
:NOTES
SHEET 5 OF 7
20" TO 54" DIAMETER PIPE
BETW EEN SCRW AND W SP
BUTT STRAP CONNECTION
DRAWING
NUMBER
COORDINATOR R.C.E. 56523 DATE
BY APPROVED DATEREVISION
CITY OF SAN DIEGO - STANDARD DRAWING OF SAN DIEGO STANDARDS COMMITTEERECOMMENDED BY THE CITY
9/7/18
ORIGINAL EH J. NAGELVOORT 09/18
SDW -175
SHEET 6 OF 7
20" TO 54" DIAMETER PIPE
BETW EEN SCRW AND W SP
BUTT STRAP CONNECTION
DRAWING
NUMBER
COORDINATOR R.C.E. 56523 DATE
BY APPROVED DATEREVISION
CITY OF SAN DIEGO - STANDARD DRAWING OF SAN DIEGO STANDARDS COMMITTEERECOMMENDED BY THE CITY
9/7/18
ORIGINAL EH J. NAGELVOORT 09/18
SDW -175
SHEET 7 OF 7