a systematic control approach to improve energy efficiency ... · • cooling tower outlet...

30
Dr. Pinakpani Biswas Principal Scientist R&D, SS TATA Steel Jamshedpur Sayani Adhikari, ME, BIT Mesra Arunima Giri, Mtech, VIT, Vellore A Systematic Control Approach to Improve Energy Efficiency of Industrial Cooling Towers

Upload: others

Post on 04-Nov-2019

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Dr. Pinakpani Biswas

Principal Scientist

R&D, SS

TATA Steel

Jamshedpur

Sayani Adhikari, ME, BIT Mesra

Arunima Giri, Mtech, VIT, Vellore

A Systematic Control Approach to

Improve Energy Efficiency of

Industrial Cooling Towers

Page 2: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

❖ Brief Introduction

❖ Key Challenges

❖ Solution Overview

❖ Objectives & Assumptions

❖ Approach

❖ Model Development

❖ Tools Used

❖ Optimization Flowchart

❖ Results and Discussion

❖ Conclusion

❖ Future Scope of work

Page 3: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

A device used to COOL hot water stream based on evaporative cooling

Hot stream(DM Water)

Cold stream(DM Water)

Warm Process Water

Cold Process Water

Page 4: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

➢Tuning cooling tower parameters for optimized

operation

➢Optimizing Energy Consumption

Cold Water

(Temperature

approach

ambient WBT)

Ambient Air

(Driving force:

Relative humidity)

Hot Air

Hot Water

Cooling

Tower

CT Objective

To decrease hot water temperature

by 4-8 degrees (TATA Steel

Jamshedpur)

Cooling tower is an energy

intensive process

Page 5: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Monitor Operation/

Collect data

Optimization:

E value

obtained

MATLAB Program

Validation

MATLAB/Simulink

Simulation

Implementation

Page 6: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

• Tune the model parameters to decrease energy consumption

❖ Stage efficiency was assumed to be equal for all stages for

basic simulation purpose which later on to be optimized with the

help of available data

❖ Vapor liquid equilibrium

Assumptions

Page 7: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Development of Equilibrium Model

for existing cooling tower

Mass Balance Energy Balance

Equilibrium Model

Optimized Model

Simulink Model Validation and

Implementation

MATLABCompiler , Optimization

toolbox & Simulink

Page 8: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Mass balance for 2 stages

8

Stage-1

𝑮 × 𝑪𝒑𝒂 × 𝑻𝟐 + 𝑳𝟎 × 𝑪𝒑𝒘 × 𝑻𝟎 + 𝑮 ×𝑯𝟐 × 𝑪𝒑𝒗 × 𝑻𝟐 + 𝑮 ×𝑯𝟐 × 𝝀

= 𝑮 × 𝑪𝒑𝒂 × 𝑻𝟏 + 𝑳𝟏 × 𝑪𝒑𝒘 × 𝑻𝟏 + 𝑮 ×𝑯𝟏 × 𝑪𝒑𝒗 × 𝑻𝟏 + 𝑮 ×𝑯𝟏 × 𝝀

𝐌𝐚𝐬𝐬 𝐨𝐟 𝐰𝐚𝐭𝐞𝐫 𝒊𝒏 = 𝐌𝐚𝐬𝐬 𝐨𝐟 𝐰𝐚𝐭𝐞𝐫 𝐨𝐮𝐭

𝐒𝐞𝐧𝐬𝐢𝐛𝐥𝐞 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐢𝐧𝐥𝐞𝐭 𝐚𝐢𝐫 + 𝐬𝐞𝐧𝐬𝐢𝐛𝐥𝐞 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐢𝐧𝐥𝐞𝐭 𝐰𝐚𝐭𝐞𝐫+ 𝐬𝐞𝐧𝐬𝐢𝐛𝐥𝐞 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐢𝐧𝐥𝐞𝐭 𝐰𝐚𝐭𝐞𝐫 𝐯𝐚𝐩𝐨𝐮𝐫 + 𝐥𝐚𝐭𝐞𝐧𝐭 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐢𝐧𝐥𝐞𝐭 𝐰𝐚𝐭𝐞𝐫 𝐯𝐚𝐩𝐨𝐮𝐫= 𝐬𝐞𝐧𝐬𝐢𝐛𝐥𝐞 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐞𝐱𝐢𝐭 𝐚𝐢𝐫 + 𝐬𝐞𝐧𝐬𝐢𝐛𝐥𝐞 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐞𝐱𝐢𝐭 𝐰𝐚𝐭𝐞𝐫+ 𝐬𝐞𝐧𝐬𝐢𝐛𝐥𝐞 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐞𝐱𝐢𝐭 𝐰𝐚𝐭𝐞𝐫 𝐯𝐚𝐩𝐨𝐮𝐫 + 𝐥𝐚𝐭𝐞𝐧𝐭 𝐡𝐞𝐚𝐭 𝐨𝐟 𝐞𝐱𝐢𝐭 𝐰𝐚𝐭𝐞𝐫 𝐯𝐚𝐩𝐨𝐮𝐫

Stage-1

𝑳𝒐 + 𝑮𝑯𝟐 = 𝑳𝟏 + 𝑮𝑯𝟏 => 𝑳𝟏 = 𝑳𝒐 + 𝑮(𝑯𝟐−𝑯𝟏)

Stage-2

𝑳𝟏 + 𝑮𝑯𝟑 = 𝑳𝟐 + 𝑮𝑯𝟐 => 𝑳𝟐 = 𝑳𝟏 + 𝑮(𝑯𝟑−𝑯𝟐)

Stage-2

𝑮 × 𝑪𝒑𝒂 × 𝑻𝒂 + 𝑳𝟏 × 𝑪𝒑𝒘 × 𝑻𝟏 + 𝑮 ×𝑯𝟑 × 𝑪𝒑𝒗 × 𝑻𝒂 + 𝑮 ×𝑯𝟑 × 𝝀

= 𝑮 × 𝑪𝒑𝒂 × 𝑻𝟐 + 𝑳𝟐 × 𝑪𝒑𝒘 × 𝑻𝟐 + 𝑮 ×𝑯𝟐 × 𝑪𝒑𝒗 × 𝑻𝟐 + 𝑮 ×𝑯𝟐 × 𝝀

Energy balance for 2 stages

Page 9: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

➢ Unknowns: L2, L1, T2, T1, H2, H1 (No of unknowns is 6)

➢ No of equations: 4

➢ Degrees of freedom=2

➢ To eliminate one set of unknowns in order to make the number of unknowns and number of equations equal murphy

efficiency equation is used

𝑬𝒏= 𝒀𝒏−𝒀 𝒏+𝟏

𝒀𝑺𝒏−𝒀(𝒏+𝟏)

➢ Equations obtained for ‘2’ stages are

𝒀𝟏 = 𝑬𝟏 𝒀𝑺𝟏 − 𝒀𝟐 + 𝒀𝟐

𝒀𝟐 = 𝑬𝟐 𝒀𝑺𝟐 − 𝒀𝟑 + 𝒀𝟑

➢ H1 and H2 can be calculated from Y1 and Y2

𝑯𝟏 =𝒀𝟏

𝟏 − 𝒀𝟏∗𝑴𝑯𝟐𝑶

𝑴𝑨𝒊𝒓

𝑯𝟐 =𝒀𝟐

𝟏 − 𝒀𝟐∗𝑴𝑯𝟐𝑶

𝑴𝑨𝒊𝒓

➢ Degrees of freedom after variable substitution: No. of variables 4 and No. of equations 4. This implies D.O.F=0

Page 10: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

MATLAB R2016b

Simulink

MATLAB Compiler

Optimization toolbox

Page 11: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized
Page 12: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Variable initialization

Calculation of primary unknowns from initial parameters

(vapor pressure, inlet humidity, mole fraction etc.)

Calculation of partial pressure, humidity, mole

fraction and liquid flow rate for each individual

stages (in terms of temperature)

Calculation of temperature by substitution

Outlet temperature value for all stages

Providing the final

temperature value to the

respective calculations

Final values

i

ii

Page 13: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized
Page 14: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Main function

Data set

Function solver

Temperature value

Error<0.1

Optimized efficiency

and number of stages

Page 15: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized
Page 16: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized
Page 17: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

A: Comparison of initial MATLAB model with optimized model validated with

experimental data. B: Error Comparison before optimization and after

optimization

A B

Page 18: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized
Page 19: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

S-Function block

Used to solve differential equations with initial conditions

Conditions: flag=0 initialization, flag=1 derivatives

Flag=3 output, flag=2 discrete, flag=9 termination

Heater

Input: water temperature, flowrate, constant heat supply

Output: heat gain (increase in temperature due to heat supply)

Temperature calculation module

Input to the module: gas and liquid flow rate, relative humidity, partial

pressure, ambient air temperature, inlet liquid temperature

Output of the module: stage temperatures, liquid flow rate at each stage

Page 20: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

-Controllers were tuned by auto tuning method and by adjusting time and robustness

Page 21: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized
Page 22: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized
Page 23: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

10% reduction in liquid flowrate

567.586553.071

30.86

446.72

498.324

32.6476

0

100

200

300

400

500

600

CT Fan (KW) PumpPower (KW) CT in Temp(oC)

Power (in KW)

Original Final

Page 24: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

20% reduction in liquid flowrate

567.586553.071

30.86

430.254442.947

33.41907

0

100

200

300

400

500

600

CT Fan (KW) PumpPower (KW) CT in Temp(oC)

Power (in KW)

Original Final

Page 25: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

30% reduction in liquid flow rate

567.586553.071

30.86

411.753387.567

34.4027

0

100

200

300

400

500

600

CT Fan(KW) PumpPower (KW) CT in Temp(oC)

Power (in KW)

Original Final

Page 26: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

40% reduction in liquid flow rate

567.586553.071

30.86

338.184 332.478

34.4193

0

100

200

300

400

500

600

CT Fan(KW) PumpPower(KW) CT in Temp(oC)

Power (in KW)

Original Final

Page 27: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

• Cooling tower outlet temperature was predicted by mathematical model created

• Created model was optimized dynamically

• Improved efficiency and optimized number of stages were obtained

• Three stages with 60 % efficiency

• Cooling tower can be operated by decreasing the water flowrate up to 30 % without

affecting the overall performance

Page 28: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Data collection

Development of mathematical

model

Model creation in Matlab

Validation of Matlab result

using collected data

Matlab model optimization

Optimized number of stages=3,

efficiency= 60%

Performance evaluation at

reduced flowrate

Page 29: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized

Control Application based on MIMO system

Model predictive control, robust control

Page 30: A Systematic Control Approach to Improve Energy Efficiency ... · • Cooling tower outlet temperature was predicted by mathematical model created • Created model was optimized