a12 apartments - pavilion construction apartments... · complex interlock (elec., pneumatic, etc.)...

26
# DRAWING CONSTRUCTION ("FLAG") NOTE EQUIPMENT IDENTIFIER X-XX MATCHLINE REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE PREVIOUS RELEASE) # REVISION REFERENCE EXISTING TO BE REMOVED (HATCH) HEAVY LINEWEIGHT INDICATES NEW WORK LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION POINT OF CONNECTION (POC) BETWEEN NEW AND EXISTING POINT OF CONNECTION N NORTH REFERENCE DETAIL REFERENCE X XX.XX DETAIL IDENTIFICATION NUMBER SHEET WHERE DETAIL IS DRAWN ELEVATION REFERENCE X XX.XX ELEVATION IDENTIFICATION NUMBER SHEET WHERE ELEVATION IS DRAWN SECTION REFERENCE X XX.XX SECTION IDENTIFICATION NUMBER SHEET WHERE SECTION IS DRAWN SYMBOL DESCRIPTION SYMBOLS LEGEND - GENERAL SYMBOL DESCRIPTION SYMBOLS LEGEND - HVAC SYMBOL DESCRIPTION SYMBOLS LEGEND - HVAC (CON'T) SYMBOL DESCRIPTION SYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMS ROOFTOP EXHAUST FAN , ROOFTOP SUPPLY FAN CEILING SUPPLY DIFFUSER CEILING RETURN DIFFUSER CEILING EXHAUST DIFFUSER LINEAR SLOT DIFFUSER SIDE WALL REGISTER BDD BACKDRAFT DAMPER DAMPER (OPPOSED BLADE / PARALLEL BLADE) MOTOR OPERATED DAMPER M M LOUVER UNIT HEATER AIRFLOW, SUPPLY AIRFLOW, RETURN THERMOSTAT, TEMPERATURE SENSOR T S HUMIDITY SENSOR H CARBON MONOXIDE SENSOR, CARBON DIOXIDE SENSOR CO SD SMOKE DETECTOR CONNECTION SIZE AIR FLOW (CFM) DIFFUSER TYPE MARK FSD FIRE SMOKE DAMPER (VERTICAL / HORIZONTAL) FSD SD SMOKE DAMPER (VERTICAL / HORIZONTAL) SD FIRE DAMPER (VERTICAL / HORIZONTAL) FD FD VOLUME DAMPER AP AD ACCESS DOOR (AD) OR ACCESS PANEL (AP) LINED DUCTWORK FLEXIBLE DUCT OR CONNECTION FLEXIBLE DUCT OR CONNECTION R INCLINE RISE (R) OR DROP (D) IN DIRECTION OF ARROW FLAT-OVAL DUCT - TURNING AWAY FLAT-OVAL DUCT - TURNING TOWARD ROUND DUCT - TURNING AWAY ROUND DUCT - TURNING TOWARD EXHAUST AIR DUCT - TURNING AWAY EXHAUST AIR DUCT - TURNING TOWARD RETURN AIR DUCT - TURNING AWAY RETURN AIR DUCT - TURNING TOWARD SUPPLY AIR DUCT - TURNING AWAY SUPPLY AIR DUCT - TURNING TOWARD RECTANGULAR TO ROUND TRANSITION TRANSITION OR REDUCER - NOTED FOT (FLAT ON TOP) OR FOB (FLAT ON BOTTOM) IF REQUIRED ROUND BRANCH TO RECTANGULAR DUCT CONNECTION ROUND BRANCH TO ROUND DUCT CONNECTION ROUND OR RECTANGULAR BRANCH TO ROUND OR RECTANGULAR DUCT CONNECTION RECTANGULAR BRANCH TO RECTANGULAR DUCT CONNECTION WITH 45° TAPER 45° BRANCH CONNECTION SQUARE CORNER ELBOW WITH TURNING VANES RECTANGULAR OR ROUND, 90° ELBOW, R/W OR R/D = 1.5 RECTANGULAR, 90° ELBOW, R/W OR R/D = 1.5 ROUND, 90° ELBOW, R/W OR R/D = 1.5 SD SMOKE DETECTOR PRESSURE GAGE THERMOMETER THERMOSTAT, TEMPERATURE SENSOR T S HUMIDITY SENSOR H CARBON MONOXIDE SENSOR, CARBON DIOXIDE SENSOR CO FLOW DIRECTION FLOOR DRAIN FLOOR SINK ELECTRIC MOTOR OPERATOR (VALVES AND DAMPERS) M ELECTRIC MOTOR/STARTER ASSEMBLY M CENTRIFUGAL FAN PUMP CONNECTION TO CENTRAL MONITORING AND CONTROL SYSTEM (CMCS) COMPLEX INTERLOCK (ELEC., PNEUMATIC, ETC.) FLOW CONTINUATION ARROW ELECTRICAL CONNECTION PIPING OR DUCTED AIRFLOW COND CONDENSATE RETURN DATE: JOB NO: SEPTEMBER 18, 2015 150150 REVISIONS: PERMIT REVIEW A12 APARTMENTS 1206 SE ANKENY ST PORTLAND, OR 97214 123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209 T: 971.888.5107 - E-MAIL: [email protected] architects A C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER, EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS. 111 SW Fifth Ave. Ste. 2120 Portland, Oregon 97204 Tel 503.416.2400 Fax 206.267.1701 SAZAN # 507-1501 M0.0 MECHANICAL SYMBOLS COND CONDENSATE RETURN

Upload: vobao

Post on 04-Apr-2018

220 views

Category:

Documents


3 download

TRANSCRIPT

# DRAWING CONSTRUCTION ("FLAG") NOTE

EQUIPMENT IDENTIFIERX-XX

MATCHLINE

REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE

THE PREVIOUS RELEASE)

# REVISION REFERENCE

EXISTING TO BE REMOVED (HATCH)

HEAVY LINEWEIGHT INDICATES NEW WORK

LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION

POINT OF CONNECTION (POC) BETWEEN NEW AND EXISTING

POINT OF CONNECTION

NNORTH REFERENCE

DETAIL REFERENCEX

XX.XX DETAIL IDENTIFICATION NUMBER

SHEET WHERE DETAIL IS DRAWN

ELEVATION REFERENCEX

XX.XXELEVATION IDENTIFICATION NUMBER

SHEET WHERE ELEVATION IS DRAWN

SECTION REFERENCEX

XX.XX SECTION IDENTIFICATION NUMBER

SHEET WHERE SECTION IS DRAWN

SYMBOL DESCRIPTION

SYMBOLS LEGEND - GENERAL

SYMBOL DESCRIPTION

SYMBOLS LEGEND - HVAC

SYMBOL DESCRIPTION

SYMBOLS LEGEND - HVAC (CON'T)SYMBOL DESCRIPTION

SYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMS

ROOFTOP EXHAUST FAN , ROOFTOP SUPPLY FAN

CEILING SUPPLY DIFFUSER

CEILING RETURN DIFFUSER

CEILING EXHAUST DIFFUSER

LINEAR SLOT DIFFUSER

SIDE WALL REGISTER

BDD

BACKDRAFT DAMPER

DAMPER (OPPOSED BLADE / PARALLEL BLADE)

MOTOR OPERATED DAMPER

M M

LOUVER

UNIT HEATER

AIRFLOW, SUPPLY

AIRFLOW, RETURN

THERMOSTAT, TEMPERATURE SENSORT S

HUMIDITY SENSORH

CARBON MONOXIDE SENSOR, CARBON DIOXIDE SENSORCO

SD SMOKE DETECTOR

CONNECTION SIZE

AIR FLOW (CFM)

DIFFUSER TYPE MARK

FSDFIRE SMOKE DAMPER (VERTICAL / HORIZONTAL)

FSD

SD

SMOKE DAMPER (VERTICAL / HORIZONTAL)SD

FIRE DAMPER (VERTICAL / HORIZONTAL)

FD

FD

VOLUME DAMPER

APAD

ACCESS DOOR (AD) OR ACCESS PANEL (AP)

LINED DUCTWORK

FLEXIBLE DUCT OR CONNECTION

FLEXIBLE DUCT OR CONNECTION

R INCLINE RISE (R) OR DROP (D) IN DIRECTION OF ARROW

FLAT-OVAL DUCT - TURNING AWAY

FLAT-OVAL DUCT - TURNING TOWARD

ROUND DUCT - TURNING AWAY

ROUND DUCT - TURNING TOWARD

EXHAUST AIR DUCT - TURNING AWAY

EXHAUST AIR DUCT - TURNING TOWARD

RETURN AIR DUCT - TURNING AWAY

RETURN AIR DUCT - TURNING TOWARD

SUPPLY AIR DUCT - TURNING AWAY

SUPPLY AIR DUCT - TURNING TOWARD

RECTANGULAR TO ROUND TRANSITION

TRANSITION OR REDUCER - NOTED FOT (FLAT ON TOP) OR

FOB (FLAT ON BOTTOM) IF REQUIRED

ROUND BRANCH TO RECTANGULAR DUCT CONNECTION

ROUND BRANCH TO ROUND DUCT CONNECTION

ROUND OR RECTANGULAR BRANCH TO ROUND OR

RECTANGULAR DUCT CONNECTION

RECTANGULAR BRANCH TO RECTANGULAR DUCT

CONNECTION WITH 45° TAPER

45° BRANCH CONNECTION

SQUARE CORNER ELBOW WITH TURNING VANES

RECTANGULAR OR ROUND, 90° ELBOW,

R/W OR R/D = 1.5

RECTANGULAR, 90° ELBOW, R/W OR R/D = 1.5

ROUND, 90° ELBOW, R/W OR R/D = 1.5

SD SMOKE DETECTOR

PRESSURE GAGE

THERMOMETER

THERMOSTAT, TEMPERATURE SENSORT S

HUMIDITY SENSORH

CARBON MONOXIDE SENSOR, CARBON DIOXIDE SENSORCO

FLOW DIRECTION

FLOOR DRAIN

FLOOR SINK

ELECTRIC MOTOR OPERATOR (VALVES AND DAMPERS)M

ELECTRIC MOTOR/STARTER ASSEMBLYM

CENTRIFUGAL FAN

PUMP

CONNECTION TO CENTRAL MONITORING AND CONTROL SYSTEM (CMCS)

COMPLEX INTERLOCK (ELEC., PNEUMATIC, ETC.)

FLOW CONTINUATION ARROW

ELECTRICAL CONNECTION

PIPING OR DUCTED AIRFLOW

COND CONDENSATE RETURN

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

M0.0

MECHANICAL SYMBOLS

COND CONDENSATE RETURN

ABBREVIATIONS

A AIR, AMPERE

ABS ABSOLUTE

ACU AIR CONDITIONING UNIT

AFF ABOVE FINISHED FLOOR

AG ABOVE GRADE

AHU AIR HANDLING UNIT

AL ALUMINUM, ACOUSTICAL LINING

AMB AMBIENT

ARRGT ARRANGEMENT

ATM ATMOSPHERE

BC BLOWER COIL

BDD BACKDRAFT DAMPER

BFF BELOW FINISHED FLOOR

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOB BOTTOM OF BEAM

BOD BOTTOM OF DUCT

BOS BOTTOM OF STEEL

BTUH BRITISH THERMAL UNITS PER

HOUR

C CELCIUS

CAP CAPACITY

CC COOLING COIL

CCW COUNTER-CLOCKWISE

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CLG CEILING, COOLING

COMP COMPRESSOR

CONC CONCRETE

COND CONDENSATE

CONT CONTINUE, CONTROL

COP COEFFICIENT OF PERFORMANCE

CP CIRCULATING PUMP

CRU CONDENSATE RETURN UNIT

CU CONDENSING UNIT

CU FT CUBIC FEET

CV CONSTANT VOLUME

CVTR CONVERTER

CW CLOCKWISE, COLD WATER

dB DECIBELS

DB DRY BULB

DCV DOUBLE CHECK VALVE

DEG DEGREE

DI DE-IONIZED

DIA DIAMETER

DMPR DAMPER

DN DOWN

E EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATING

EF EXHAUST FAN

EFF EFFICIENCY

EG EXHAUST GRILLE

EL ELEVATION

EQUIP EQUIPMENT

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR, EXTERNAL

F FAHRENHEIT, FIRE LINE

FD FIRE DAMPER

FDC FIRE DEPARTMENT CONNECTION

FE FIRE EXTINGUISHER

FLA FULL LOAD AMPS

FLR FLOOR

FLTR FILTER

FM FLOW METER

FOB FLAT ON BOTTOM

FO FLAT OVAL

FOT FLAT ON TOP

FPM FEET PER MINUTE

FPS FEET PER SECOND

FSD FIRE SMOKE DAMPER

FT FEET, FAN TERMINAL

FV FACE VELOCITY

GA GAGE

GAL GALLONS

GALV GALVANIZED

GPM GALLONS PER MINUTE

H HUMIDIFIER, HEIGHT

HC HEATING COIL

HD HEAD

HEX HEAT EXCHANGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER, HEAT PUMP

HTG HEATING

HWR HOT WATER HEATING RETURN

HWS HOT WATER HEATING SUPPLY

HZ HERTZ

ID INSIDE DIAMETER, INDIRECT DRAIN

IE INVERT ELEVATION

IH INTAKE HOOD

IN INCH

INIT INITIAL

INT INTERIOR

IPLV INTEGRATED PART LOAD VALUE

KW KILOWATT

KWH KILOWATT HOURS

L LENGTH

LAT LEAVING AIR TEMPERATURE

LB POUND, LINEAR BAR

LBS POUNDS

LD LINEAR DIFFUSER

LF LINEAR FEET

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

MCA MINIMUM CIRCUIT AMPACITY

MD MANUAL DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MOCP MAXIMUM OVER CURRENT

PROTECTION

MOD MOTOR OPERATED DAMPER

MTR MOTOR

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEG NEGATIVE

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NUMBER, NORMALLY OPEN

NTS NOT TO SCALE

OA OUTDOOR AIR

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

P PUMP, PLUMBING

PD PRESSURE DROP

PH PHASE

POC POINT OF CONNECTION

POS POSITIVE

PPM PARTS PER MILLION

PR PUMPED RETURN

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA PSI ABSOLUTE

PSIG PSI GAGE

P/T PRESSURE / TEMPERATURE

PVC POLYVINYL CHLORIDE

QTY QUANTITY

RA RETURN AIR

REF REFERENCE

REQD REQUIRED

RF RETURN FAN

RG RETURN GRILLE

RPBFP REDUCED PRESSURE BACKFLOW

PREVENTER

RH RELIEF HOOD, RELATIVE HUMIDITY

RPM REVOLUTIONS PER MINUTE

S SOIL

SA SUPPLY AIR

SC SHADING COEFFICIENT

SD SMOKE DAMPER

SENS SENSIBLE

SEER SEASONAL ENERGY EFFICIENCY

RATING

SF SUPPLY FAN, SQUARE FEET,

SAFETY FACTOR

SG SUPPLY GRILLE

SHG SENSIBLE HEAT GAIN

SHR SENSIBLE HEAT RATIO

SL SOUND LINING

SP STATIC PRESSURE

SS STAINLESS STEEL

T THERMOSTAT

TEMP TEMPERATURE

TG TRANSFER GRILLE

TOD TOP OF DUCT

TOT TOTAL

TP TRAP PRIMER, TOTAL PRESSURE

TRV TEMPERATURE RELIEF VALVE

TSP TOTAL STATIC PRESSURE

TU TERMINAL UNIT

TYP TYPICAL

UH UNIT HEATER

UON UNLESS OTHERWISE NOTED

V VENT, VOLT

VA VALVE

VAC VACUUM

VAV VARIABLE AIR VOLUME

VB VACUUM BREAKER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATER, WATT, WIDTH

WB WET BULB

WG WATER GAGE

WH WATER HEATER

WTR WATER

WWP WATER WORKING PRESSURE

GENERAL NOTES

1. THE FULL SCOPE OF THE MECHANICAL WORK IS THE TOTAL OF WORK SHOWN ON THE PLANS AND

CALLED FOR IN THE SPECIFICATIONS. IN CASE OF CONFLICT, THE SPECIFICATIONS SHALL GOVERN.

PROVIDE A COMPLETE & FUNCTIONAL SYSTEM.

2. PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES. OBTAIN AND PAY FOR

ALL REQUIRED PERMITS AND PAY FOR ALL FEES REQUIRED BY AUTHORITIES HAVING JURISDICTION.

PAY ALL ROYALTIES OR FEES REQUIRED IN CONNECTION WITH THE USE OF PATENTED DEVICES AND

SYSTEMS.

3. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION INCLUDING,

BUT NOT LIMITED TO, LOUVERS, CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC. REFER TO

ARCHITECTURAL DRAWINGS FOR ROOM ELEVATIONS, LOCATE MECHANICAL DEVICES SUCH AS

TEMPERATURE SENSORS, HUMIDISTATS, PANELS, ETC. SO THAT THEY DO NOT CONFLICT WITH

GENERAL CONSTRUCTION (WAINSCOT, DOOR HARDWARE, ETC.) NOR WITH ELECTRICAL SYSTEM (LIGHT

SWITCHES, SPEAKERS, OUTLETS, ETC.).

4. ARRANGE EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY DRAWINGS, REQUIRED BY CODES,

OR RECOMMENDED BY MANUFACTURER ARE PROVIDED; WHICH EVER ARE MOST STRINGENT.

5. THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT, DUCTWORK, AND PIPING WILL BE INSTALLED

AND REPORT ANY CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE MECHANICAL WORK.

6. COMPLY WITH OREGON ENERGY EFFICIENCY SPECIALTY CODE SECTION 503.2.9 HVAC SYSTEM

COMPLETION. INCLUDE THE DEVELOPMENT OF CONSTRUCTION AND AS-BUILT DRAWINGS, PROJECT

MANUALS, AND SYSTEM BALANCING REPORTS.

7. ARRANGEMENT OF SYSTEMS INDICATED ON THE DRAWINGS IS DIAGRAMMATIC, AND INDICATES THE

MINIMUM REQUIREMENTS FOR PLUMBING AND MECHANICAL WORK. ADJUST BOX LOCATIONS, BASED

ON FIELD MEASUREMENTS, TO AVOID INSTALLATION ABOVE DESKS. SITE CONDITIONS SHALL

DETERMINE THE ACTUAL ARRANGEMENT OF THE WORK. TAKE FIELD MEASUREMENTS BEFORE

PREPARING SHOP DRAWINGS, OBTAIN APPROVAL OF SHOP DRAWINGS BEFORE BEGINNING

FABRICATION. BE RESPONSIBLE FOR ACCURACY OF DIMENSIONS AND LAYOUT. OVERHEAD PIPING AND

DUCTWORK SHALL BE ARRANGED TO OBTAIN MAXIMUM HEAD ROOM. SHOP DRAWINGS SHALL BE

STAMPED BY A LICENSED ENGINEER.

8. CLEAN AND PROTECT WORK FROM DAMAGE. RESTORE DAMAGED FINISHES. COVER ENDS OF PIPING

AND DUCTWORK NOT ACTIVELY BEING WORKED ON.

9. WHEN APPLICABLE, MODIFY AND EXTEND EXISTING SERVICE TO ACCOMMODATE NEW WORK.

RELOCATE EXISTING COMPONENTS AS REQUIRED FOR NEW SYSTEM. COORDINATE WITH BUILDING

MANAGEMENT.

10. CONCEAL PIPING AND DUCTWORK TO THE GREATEST EXTENT PRACTICAL.

11. DRAWINGS DO NOT SHOW ALL OFFSETS WHICH MAY BE REQUIRED. MAKE OFFSETS WITH FITTINGS

WITH AS SMALL ANGLE OF OFFSET AS POSSIBLE; DO NOT USE TURNING VANES UNLESS SPECIFICALLY

SHOWN. DUCTWORK & PIPING SHALL BE ROUTED TO AVOID ALL STRUCTURAL SUPPORTS. DO NOT CUT

STRUCTURAL ELEMENTS WITHOUT PRIOR WRITTEN APPROVAL.

12. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE LATEST

EDITION OF THE FOLLOWING CODES AS ADOPTED BY LOCAL JURISDICTION.

• OREGON STRUCTURAL SPECIALTY CODE (OSSC)

• OREGON MECHANICAL SPECIALTY CODE (OMSC)

• OREGON PLUMBING SPECIALTY CODE (OPSC)

• OREGON FIRE CODE (OFC)

• OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC)

SHEETMETAL NOTES

1. PERFORM ALL SHEETMETAL WORK IN ACCORDANCE WITH CURRENT SMACNA STANDARDS.

2. DUCT SEALING SHALL MEET REQUIREMENTS LISTED IN CHAPTER 6 OF (OMSC) AND (OEESC) STATE

ENERGY CODE. IN ADDITION, PROVIDE SEAL CLASS A FOR ALL DUCTWORK.

3. THOROUGHLY CLEAN ALL DEBRIS FROM THE INSIDE OF ALL DUCTWORK AND PLENUMS. BLOW FREE ALL

SMALL PARTICLES OF RUBBISH AND DUST.

4. MECHANICAL DRAWINGS SHOW APPROXIMATE LOCATIONS FOR GRILLES AND DIFFUSERS. REFER TO

ARCHITECTURAL REFLECTED CEILING PLANS AND ELEVATIONS FOR EXACT LOCATIONS. AFTER SHOP

DRAWINGS ARE COMPLETED VERIFY EXACT LOCATION OF GRILLES AND DIFFUSERS IN THE FIELD.

ENSURE THAT DIFFUSER AND GRILLE FRAMES MATCH CEILING TYPES AND FINISH PRIOR TO ORDERING.

FIRE PROTECTION NOTES

1. MAKE FIELD MEASUREMENTS, COORDINATE WITH ALL OTHER WORK AND SHOW THE MODIFICATIONS

REQUIRED ON SHOP DRAWINGS.

2. MODIFY FIRE PROTECTION SYSTEMS TO ALLOW INSTALLATION OF DUCTWORK, OTHER PIPING, AND

ELECTRICAL WORK AS SHOWN ON APPROVED SHOP DRAWINGS. NEW ARRANGEMENT SHALL LOCATE

PIPING AS HIGH AS POSSIBLE.

3. PROVIDE A COMPLETE FIRE SPRINKLER SYSTEM FOR THE ENTIRE PROJECT AREA.

4. FLOORS ARE CURRENTLY SERVED BY A COMPLETE AUTOMATIC SPRINKLER SYSTEM. PROVIDE NEW

SPRINKLER HEADS, BRANCH PIPING TO SUIT NEW PARTITIONS & REQUIREMENTS OF FIRE DEPARTMENT.

NEW HEADS SHALL BE LOCATED IN CENTER OF TILE.

ENERGY CODE MECHANICAL NOTES

1. THE TOTAL CAPACITY OF ALL COOLING EQUIPMENT WITHOUT ECONOMIZERS MUST BE LESS THAN 240 kBtu/h. THAT PORTION OF THE EQUIPMENT

SERVING DWELLING UNITS IS NOT INCLUDED IN DETERMINING THE TOTAL CAPACITY WITHOUT ECONOMIZER.

2. HEATING AND COOLING EQUIPMENT AND SYSTEMS CAPACITY DO NOT EXCEED THE LOADS CALCULATED IN ACCORDANCE WITH 2014 OEESC SECTION

(503.2.1).

3. THE SUPPLY OF HEATING AND COOLING ENERGY TO EACH ZONE IS TO BE CONTROLLED BY INDIVIDUAL THERMOSTATIC CONTROLS THAT RESPOND TO

TEMPERATURE WITHIN THE ZONE.

4. ZONE THERMOSTATIC CONTROLS TO PROVIDE A TEMPERATURE RANGE OR DEADBAND OF AT LEAST 5°F (2.8°C) WITHIN WHICH THE SUPPLY OF HEATING

AND COOLING ENERGY TO THE ZONE AND CAPABLE OF BEING SHUT OFF OR REDUCED TO A MINIMUM.

5. EACH ZONE TO BE PROVIDED WITH THERMOSTATIC SETBACK CONTROLS THAT ARE CONTROLLED BY PROGRAMMABLE CONTROL SYSTEM.

6. BOTH OUTDOOR AIR SUPPLY AND EXHAUST ARE EQUIPPED WITH NOT LESS THAN CLASS I MOTORIZED DAMPERS. GRAVITY DAMPERS SHALL BE

PERMITTED FOR OUTSIDE AIR INTAKE OR EXHAUST AIRFLOWS OF 300 CFM OR LESS.

7. ZONES WITH SPECIAL PROCESS TEMPERATURE REQUIREMENTS AND/OR HUMIDITY REQUIREMENTS ARE SERVED BY SEPARATE AIR DISTRIBUTION

SYSTEMS FROM THOSE SERVING ZONES REQUIRING ONLY COMFORT CONDITIONS.

8. MECHANICAL VENTILATION IS PROVIDED IN ACCORDANCE WITH 2014 OMSC. WHERE MECHANICAL VENTILATION IS PROVIDED, THE SYSTEM HAS THE

CAPABILITY TO REDUCE THE OUTDOOR AIR SUPPLY TO THE MINIMUM REQUIRED BY THE 2014 OMSC.

9. ALL LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND CONNECTIONS OF LOW-PRESSURE SUPPLY AND RETURN DUCTS ARE TO BE SECURELY

FASTENED AND SEALED WITH WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC - PLUS - EMBEDDED - FABRIC SYSTEMS OR TAPES INSTALLED IN

ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTIONS.

EXCEPTION(S):

A. CONTINUOUSLY WELDED AND LOCKING-TYPE LONGITUDINAL JOINTS AND SEAMS ON DUCTS OPERATING AT STATIC PRESSURES LESS THAN 2

INCHES W.G. PRESSURE CLASSIFICATION.

10. ALL DUCTS AND PLENUMS DESIGNED TO OPERATE MEDIUM-PRESSURE ARE TO BE INSULATED AND SEALED IN ACCORDANCE WITH SECTION 503.2.7.

PRESSURE CLASSIFICATIONS SPECIFIC TO THE DUCT SYSTEM ARE CLEARLY INDICATED ON THE CONSTRUCTION DOCUMENTS.

11. DUCTS DESIGNED TO OPERATE AT HIGH-PRESSURE ARE INSULATED AND SEALED IN ACCORDANCE WITH SECTION (503.2.7). IN ADDITION, DUCTS

AND PLENUMS ARE LEAK-TESTED IN ACCORDANCE WITH THE SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL.

12. EACH SUPPLY AIR OUTLET AND ZONE TERMINAL DEVICE TO BE EQUIPPED WITH MEANS FOR AIR BALANCING IN ACCORDANCE WITH THE REQUIREMENTS

OF 2014 OMSC.

13. OPERATING AND MAINTENANCE MANUAL TO BE PROVIDED TO THE BUILDING OWNER BY THE MECHANICAL CONTRACTOR. SEE LONG DESCRIPTION FOR

SPECIFICATIONS.

14. EACH HVAC SYSTEM, AT FAN SYSTEM DESIGN CONDITIONS, DOES NOT EXCEED THE ALLOWABLE FAN SYSTEM MOTOR NAMEPLATE HP (OPTION 1)

OR FAN SYSTEM BHP (OPTION 2) AS SHOWN AND CALCULATED IN REQUIREMENT DETAILS.

EXCEPTIONS

B. INDIVIDUAL EXHAUST FANS WITH MOTOR NAMEPLATE HORSEPOWER OF 1 HP OR LESS.

15. FOR EACH FAN, THE SELECTED FAN MOTOR IS TO BE NO LARGER THAN THE FIRST AVAILABLE MOTOR SIZE GREATER THAN THE BRAKE HORSEPOWER

(BHP).

EXCEPTION(S):

A. FOR FANS LESS THAN 6 BHP, WHERE THE FIRST AVAILABLE MOTOR LARGER THAN THE BRAKE HORSEPOWER HAS A NAMEPLATE RATING WITHIN

50% OF THE BHP, SELECTION OF THE NEXT LARGER NAMEPLATE MOTOR SIZE IS ALLOWED.

16. FAN MOTORS FOR SERIES FAN-POWERED TERMINAL UNITS ARE ELECTRONICALLY- COMMUTATED MOTORS AND HAVE A MINIMUM MOTOR EFFICIENCY

OF 70% WHEN RATED IN ACCORDANCE WITH NEMA STANDARD MG 1-2006 AT FULL LOAD RATING CONDITIONS.

17. COOLING SYSTEMS DO NOT USE HOT GAS BYPASS OR OTHER EVAPORATOR PRESSURE CONTROL UNLESS THE EQUIPMENT IS DESIGNED WITH

MULTIPLE STEPS (OR CONTINUOUS) CAPACITY MODULATION.

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

M0.1

MECHANICAL NOTES & ABBREVIATIONS

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

M1.0

MECHANICAL

SCHEDULES

N

SCALE:

BASEMENT PLAN - HVAC1/8" = 1'-0"

1

N

SCALE:

FIRST FLOOR PLAN - HVAC1/8" = 1'-0"

2

N

SCALE:

SECOND,THIRD & FOURTH FLOOR PLANS1/8" = 1'-0"

3

N

SCALE:

ROOF PLAN - HVAC1/8" = 1'-0"

4

FC-01

UH-01

16X

8

16x8

18x8

14X

8

2

9

EF-021

2

1

1

FC-02

FC-03

9

9

4

9

3FC-04

2

FC-05

4511

4

9

2

3

1

FC-06

EF-03

EF-04

EF-05

EF-06

EF-07

EF-08

EF-09

EF-10

1

1

FC-07

FC-08

13

32

2

11

5

4

FC-10

UH-02

10

2

1

FC-12

FC-09 3

415

2

26

1

17

1

18

27

4

29

3

10

2

31

11

54

3

7

25

320

4

2

30

HP-27 HP-06 HP-01

HP-20

HP-21

HP-13

HP-22 HP-15

HP-14 HP-28

HP-29

HP-08

HP-16 HP-23

HP-04 HP-09

HP-30

HP-02 HP-07

SF-01

HP-26

HP-31

HP-33

HP-10

HP-19

HP-24

HP-17

HP-11

HP-18

HP-05

EF-01

HP-32

HP-25

AC-12

(TYP.)33

(TYP.)34

1

M5.2

(TYP.)

5

M5.1

1

M5.1

2

M5.1

2

M5.2(TYP.)

(TYP.)35

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

TT

T

T

6

13

32

6

9

4

M5.1

2

2

2

HP-03

14

2

(TYP.)

18X8

24X6

7" Ø

7" Ø

6" Ø

8" Ø

COND COND COND COND COND

CO

ND

CO

ND

CO

ND

CO

ND

CO

ND

CO

ND

CO

ND

CO

ND

COND COND COND COND COND

COND COND

1-1/4" Ø

3/4" Ø

3/4" Ø

COND

CO

ND

CO

ND

CO

ND

COND COND

3/4" Ø

1-1/4" Ø

CO

ND

1-1/4" Ø

3/4" Ø

1-1/4" Ø RISER

1-1/4" Ø

RISER

CO

ND

1-1/4" Ø

1-1/4" Ø RISER

COND

1-1/4" Ø1-1/4" Ø RISER

COND

CO

ND

COND

1-1/4" Ø

1-1/4" Ø RISER

CO

ND

CO

ND

COND

COND COND

3/4" Ø

1-1/4" Ø RISER

1-1/4" Ø

1-1/4" Ø

1-1/4" Ø DROP

COND COND

COND

COND

1-1/4" Ø1-1/4" Ø RISER

2

3/4" Ø

1-1/4" Ø

RISER

COND

CO

ND

COND COND COND

COND

COND COND

CO

ND

CO

ND

CO

ND

1-1/4" Ø RISER

12

3/4" Ø

1-1/4" Ø

1-1/4" Ø

1-1/4" Ø

4" Ø

7" Ø

6" Ø

7" Ø

4" Ø6" Ø

7" Ø

4" Ø

6" Ø

7" Ø

4" Ø6" Ø

1-1/4" ØRISER

3/4" Ø

7" Ø

7" Ø

6" Ø4" Ø

4" Ø

6" Ø

4" Ø

7" Ø

18x8

14x6

6" Ø

1-1/4" Ø RISER1-1/4" Ø

12

9

7" Ø

6" Ø

10X6

7" Ø

4" Ø

6" Ø

7" Ø

4" Ø

6" Ø

4" Ø6" Ø 1-1/4" Ø

RISER

28

2

M5.0(TYP.)

3

M5.0(TYP.)

9

7" Ø

4" Ø6" Ø

7" Ø

6

M5.1

7

M5.1(TYP.)

16

8

4" Ø

7" Ø6" Ø

7" Ø

18X8

14X6

SD-1 14x6

155

3/4" Ø

RG-1 24x12

635

23

24

24 3-WAY THROW

22

8" Ø

RG-1 24x12

635

10X

6

4" Ø

10x4

4" Ø

3

(TYP.)

4

M5.0

(TYP.)

7

22

18X

12

321

4

14X6

24x6

3

10x6

2

19

4

2

14X6

COND

2

FULL WIDTH

DISCHARGE

PLENUM 8" HIGH

8x6

7

4" Ø

FC-11 3

12x8 (TYP 2)

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

6" Ø

6" Ø

6" Ø

FLAG NOTES

MOUNT FAN COIL HIGH ON WALL ABOVE BI-FOLD DOOR, MAINTAINING MANUFACTURER'S REQUIRED CLEARANCES.

ROUTE REFRIGERANT PIPING FROM FAN COIL IN CEILING SPACE, AS HIGH AS POSSIBLE AND UP IN WALL TO HEAT

PUMP ON ROOF. COORDINATE EXACT LOCATION WITH ARCHITECTURAL PLANS.

MOUNT FAN COIL IN CEILING SPACE, MAINTAINING MANUFACTURER'S REQUIRED CLEARANCES.

PROVIDE A MINIMUM 30"X18" CLEAR, ARCHITECTURAL ACCESS PANEL WITH CONCEALED HARDWARE AND GYPSUM

BOARD INLAY. COORDINATE EXACT LOCATION WITH THE EQUIPMENT MANUFACTURER'S REQUIREMENTS.

PROVIDE A MINIMUM 18"X18" CLEAR, ARCHITECTURAL ACCESS PANEL WITH CONCEALED HARDWARE AND GYPSUM

BOARD INLAY. LOCATE TO ALLOW ACCESS TO FIRE/SMOKE DAMPER ACTUATOR.

6"Ø BATHROOM EXHAUST FAN DUCT. TRANSITION TO WALL CAP AS REQUIRED.

PROVIDE FAN COIL MANUFACTURER'S FILTER BOX WITH 2" MERV 8 FILTERS AND BOTTOM DISCHARGE AND GRILLE.

TRANSITION OUTSIDE AIR DUCT TO END DISCHARGE CONNECTION OF FILTER BOX.

REFRIGERANT PIPING UP IN WALL FROM BASEMENT LEVEL. OFFSET AT HIGH LEVEL AND EXTEND UP TO ROOF.

4"Ø DRYER VENT DUCT, 6"Ø BATHROOM EXHAUST FAN DUCT, & 7"Ø KITCHEN EXHAUST HOOD DUCT. TRANSITION TO

WALL CAPS AS REQUIRED. COORDINATE EXACT LOCATION WITH ARCHITECTURAL DRAWINGS.

12"X4" EXHAUST DUCT UP TO EF-01 ON ROOF. DUCT TO BE LOCATED IN 2-HOUR RATED CHASE. SEE ARCHITECTURAL

PLANS.

PROVIDE 8"Ø COMBINATION FIRE/SMOKE DAMPER AT EACH FLOOR (TYP. 5). SEE EQUIPMENT SCHEDULES FOR MORE

INFORMATION.

DISCHARGE 1-1/4" CONDENSATE DRAIN OVER FLOOR SINK. SEE PLUMBING DRAWINGS.

(2) 4"Ø DRYER VENT DUCTS, 6"Ø BATHROOM EXHAUST FAN DUCT, & 7"Ø KITCHEN EXHAUST HOOD DUCT. TRANSITION

TO WALL CAPS AS REQUIRED. COORDINATE EXACT LOCATION WITH ARCHITECTURAL DRAWINGS.

OFFSET REFRIGERANT PIPING IN CEILING SPACE OF 4TH FLOOR TO MISS ROOF DECK WHEN PENETRATING ROOF.

2ND FLOOR: FC-13, 3RD FLOOR: FC-20, & 4TH FLOOR: FC-27.

TRANSITION TO 8"Ø DUCT DOWNSTREAM OF FSD-02.

2ND FLOOR: FC-14, 3RD FLOOR: FC-21, & 4TH FLOOR: FC-28.

2ND FLOOR: FC-15, 3RD FLOOR: FC-22, & 4TH FLOOR: FC-29.

2ND FLOOR: FC-16, 3RD FLOOR: FC-23, & 4TH FLOOR: FC-30.

2ND FLOOR: FC-17, 3RD FLOOR: FC-24, & 4TH FLOOR: FC-31.

2ND FLOOR: FC-18, 3RD FLOOR: FC-25, & 4TH FLOOR: FC-32.

PROVIDE 18"X12" DUCT FROM SF-01. TRANSITION TO 18"X10" DOWNSTREAM OF FSD-05. TRANSITION TO 14"X10"

DOWNSTREAM OF FSD-04.TRANSITION TO 10"X10" DOWNSTREAM OF FSD-03. DUCTWORK LOCATED EXTERIOR OF

BUILDING TO BE INTERNALLY LINED WITH 2" INSULATION, IN SHAFT TO BE INTERNALLY LINED WITH 1" INSULATION.

SD-1 24X6 NECK. BALANCE TO 385 CFM FOR 2ND FLOOR & 279 CFM FOR 3RD & 4TH FLOOR.

SD-2 FOR 2ND AND 3RD FLOOR, PROVIDE 10X10 NECK @ 318 CFM; FOR 4TH FLOOR, PROVIDE 8X8 NECK @ 265 CFM.

2ND FLOOR: FC-19, 3RD FLOOR: FC-26, & 4TH FLOOR: FC-33.

2ND FLOOR: EF-11, 3RD FLOOR: EF-17, & 4TH FLOOR: EF-23.

2ND FLOOR: EF-12, 3RD FLOOR: EF-18, & 4TH FLOOR: EF-24.

2ND FLOOR: EF-13, 3RD FLOOR: EF-19, & 4TH FLOOR: EF-25.

2ND FLOOR: EF-14, 3RD FLOOR: EF-20, & 4TH FLOOR: EF-26.

2ND FLOOR: EF-15, 3RD FLOOR: EF-21, & 4TH FLOOR: EF-27.

2ND FLOOR: EF-16, 3RD FLOOR: EF-22, & 4TH FLOOR: EF-28.

4"Ø DRYER VENT DUCTS, 6"Ø BATHROOM EXHAUST FAN DUCT, & (2)7"Ø KITCHEN EXHAUST HOOD DUCT. TRANSITION

TO WALL CAPS AS REQUIRED. COORDINATE EXACT LOCATION WITH ARCHITECTURAL DRAWINGS.

PROVIDE HEAT PUMP AS SCHEDULED IN THE LOCATION SHOWN.

PROVIDE ROOFTOP EQUIPMENT SUPPORT, MODEL: BIG FOOT EQUIPMENT MOUNTING FRAME BY RECTORSEAL, OR

APPROVAL EQUAL. SECURE HEAT PUMP TO SUPPORT FRAME. FRAMING SYSTEM TO BE SIZED BASED ON ACTUAL HEAT

PUMP OPERATING WEIGHTS AND REFRIGERANT LINES WEIGHTS.

PROVIDE LINESET DUCTING COVER, RD SERIES, BY RECTORSEAL, OR APPROVED EQUAL. SUPPORT FROM ROOF WITH

MODEL: BIG FOOT HD BEAMS BY RECTORSEAL, OR APPROVAL EQUAL. SECURE DUCTING COVER TO HD BEAMS.

1

GENERAL NOTES1. COORDINATE DUCT AND PIPING ROUTING WITH ALL OTHER TRADES. ALL DUCTWORK AND PIPING IS SHOWN

SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL

SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.

2. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL

EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.

3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC DUCT

CONSTRUCTION STANDARD. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF

DUCTWORK.

4. UTILIZE 1.5 X RADIUS ELBOWS WHERE EVER POSSIBLE; WHEN A 90 DEGREE ELBOW MUST BE USED PROVIDE AIR TURNING

VANES.

5. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND

EQUIPMENT OF ALL TRADES.

6. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48" ABOVE FINISHED

FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER EQUIPMENT, APPLIANCES, AND DOOR

SWINGS.

7. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL

SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.

8. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE PAINTED FLAT

BLACK.

9. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.

10. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR PROPER DRAINAGE TO

SUIT EQUIPMENT FURNISHED.

11. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING OR

MAINTENANCE OF ALL MECHANICAL EQUIPMENT.

12. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO SPECIFICATIONS FOR

DETAILED REQUIREMENTS.

13. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS, AND OTHER AIR

DISTRIBUTION DEVICES.

14. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR HANDLING UNITS, AND FAN

COIL UNITS. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE

CONNECTED.

15. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 10' CLEAR FROM ALL VENTS AND EXHAUST AIR DISCHARGE LOCATIONS.

16. SLOPE CONDENSATE DRAIN PIPING AT A MINIMUM 1% SLOPE TOWARD FLOOR SINK.

17. PENETRATION OF ALL RATED ASSEMBLIES TO BE PROPERLY SEALED.

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

M2.0

FLOOR PLANS - HVAC

SPIN-IN FITTING WITH

VOLUME DAMPER

SUPPLY

DUCT

FLEX DUCT

CLAMP (TYP.)

SCALE: NTS

CEILING DIFFUSER DETAIL1

NOTES:

1. SET DIFFUSER FOR HORIZONTAL THROW.

2. ADJUST THROW FOR POSITION IN SPACE FOR ONE, TWO, THREE, OR FOUR-WAY THROWS.

DIFFUSER NECK, SEE

PLANS FOR SIZE

LAY-IN T-BAR CEILING

SHOWN, VERIFY TYPE

OF CEILING

SECURE ELBOW TO

DIFFUSER WITH A

MINIMUM OF 4

SHEETMETAL

SCREWS

SHEETMETAL ELBOW, 5 GORE,

CENTERLINE RADIUS 1.5 X THE

DIAMETER OF THE DUCT.

NOTE: WHERE CENTERLINE

RADIUS (1.5 X THE DIAMETER

OF THE DUCT) CAN NOT BE

MAINTAINED SHORT RADIUS

SHORT RADIUS RIGID METAL

ELBOW MAY BE USED.

STRAP HANGER, 1" WIDE. BOLT

AROUND DUCT AND EXTEND A

SINGLE STRAP UP TO STRUCTURE

ADJUST SUPPORT TO RELIEVE

STRAIN FROM DIFFUSERS CLAMP (TYPICAL)

SCALE: NTS

FILTERED RETURN GRILLE DETAIL3

SCALE: NTS

DUCTED CONCEALED FAN COIL DETAIL2

PLAN VIEW

SIDE VIEW

MINIMUM ACCESS

REQUIREMENTS

SUPPLY AIR

SEE PLAN FOR

DUCT SIZE &

CONFIGURATION

RETURN AIR PLENUM,

FULL SIZE OF FAN COIL

BRACKET FOR

HANGER (TYP.)

CONTROL &

WIRING CABINET

FAN WITH MOTOR

HANGER SIZES FOR ROUND DUCT

HANGER SIZES FOR RECTANGULAR DUCTMAXIMUM

HALF OF

DUCTPERIMETER

P2

= 72"

P2

= 96"

P2

= 120"

P2

= 168"

P2

= 192"

P2

> 193"

PAIRING AT 10'-0"

SPACING

STRAP ROD

1" X 22 GA 1/4"

1" X 18 GA 3/8"

1" X 16 GA 3/8"

1 1/2" X 16 GA 1/2"

PAIRING AT 8'-0"

SPACING

1" X 22 GA 1/4"

1" X 20 GA 1/4"

1" X 18 GA 3/8"

1" X 16 GA 3/8"

1 1/2" X 16 GA 1/2"

STRAP ROD

PAIRING AT 5'-0"

SPACING

STRAP ROD

1" X 22 GA 1/4"

1" X 22 GA 1/4"

1" X 22 GA 1/4"

1" X 18 GA 3/8"

1" X 16 GA 3/8"

PAIRING AT 4'-0"

SPACING

STRAP ROD

1" X 22 GA 1/4"

1" X 22 GA 1/4"

1" X 22 GA 1/4"

1" X 18 GA 3/8"

1" X 16 GA 3/8"

WHEN STRAPS ARE LAP JOINED,USE THESE MINIMUM FASTENERS:

1"X 18,20,22 GA - TWO =10

1"X 16 GA - TWO 1/4" DIA

1 1/2"X 16 GA - TWO 3/8" DIA

1 1/2"X 16 GA - TWO 3/8" DIA

SINGLE HANGER MAXIMUM

ALLOWABLE LOAD:

1"X 22 GA - 260# 1/4" DIA 270#

1"X 20 GA - 320# 3/8" DIA 680#

1"X 18 GA - 420# 1/2" DIA 1250#

1"X 16 GA - 700# 5/8" DIA 2000#

1 1/2"X 16 GA - 1100# 3/4" DIA 3000#NOTES:

1. DIMENSIONS OTHER THAN GAGE ARE IN INCHES.

2. TABLES ALLOW FOR DUCT WEIGHT, 1/2 LB/SF INSULATION WEIGHT AND NORMAL REINFORCEMENT AND

TRAPEZE WEIGHT, BUT NO EXTERNAL LOADS!

3. CONSULT AISI LIGHT GAGE STEEL DESIGN MANUAL AND AISI STEEL CONSTRUCTION MANUAL FOR CRITERIA FOR

DESIGN OF OTHER HANGERS.

4. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL.

5. ALLOWABLE LOADS LISTED ASSUME THAT DUCTS ARE 16 GA MAXIMUM.

DUCT DIAMETER

UP THRU 26"

27" THRU 36"

37" THRU 50"

51" THRU 60"

61" THRU 84"

STRAP HANGERS

ONE 1" X 22 GA

ONE 1" X 18 GA

ONE 1" X 16 GA

TWO 1" X 18 GA

TWO 1" X 16 GA

MAXIMUM SPACING

12 FT

12 FT

12 FT

12 FT

12 FT

NOTES:

1. EXTERNAL LOADS ARE NOT ACCOUNTED FOR

FIXTURE

CLIPS

BAND PUSH NUTS

36" DIA. MAX. 24" DIA. MAX.

BAND OF SAME

SIZE AS HANGER

STRAP

1" MIN

HANGER STRAP

NOTES:

1. REINFORCEMENT MAY BE USED FOR

ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES.

2. DO NOT EXCEED ALLOWABLE LOAD LIMITS.

SCALE: NTS

DUCT SUPPORT / HANGING DETAIL8

>36" DIA.

LOAD RATED

FASTENERS

SLING TO AVOID

DISRUPTION OF

INSULATION

1" MIN.LOAD RATED

FASTENERS

3"

12"

12"

CONICAL CONNECTIONRECTANGULAR DUCT

VOLUME DAMPER - COORDINATE

FOR ACCESSIBLE LOCATIONFLEXIBLE OR SOLID DUCT BRANCH DUCT TAKE-OFF

PLAN VIEW

W

SCALE: NTS

SUPPLY DUCTWORK TAKE-OFFS DETAIL5

(1/4)'W' OR 4" MIN.

AIR

FLO

W

AIRFLOW

VOLUME DAMPER

MAIN

SUPPLY

DUCT

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

VOLUMEDAMPER

(TYP)SUPPLY REGISTER OR

BRANCH DUCT

AIRFLOW

MAIN SUPPLY

DUCT

TURNING VANES

SEE FLOOR PLAN FOR

SPLIT DIMENSION

AIRFLOW

AIR

FLO

W

SCALE: NTS

DUCTWORK DETAILEXHAUST OR RETURN BRANCH

9

W

AIR

FLO

W

BRANCH DUCT

PROVIDE VOLUME

DAMPER AT EACH BRANCH

(1/4)'W' OR 4" MIN.

MAIN EXHAUST OR

RETURN DUCT

AIRFLOWAIRFLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

SCALE: NTS

(WITH EQUIPMENT MOUNTED IN DUCT)DUCTWORK TRANSITIONS

6

NOTES:

AIRFLOW AIRFLOW

30° MAX.

30° MAX.

15° MAX.

15° MAX.

AIRFLOW

15° MAX.

15° MAX.

SCALE: NTS

TURNING VANE ELBOW DETAIL10

NOTES:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF 'W'

DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM SPACE BETWEEN VANES AND

A 3/4" TRAILING EDGE.

4. WHEN 'W' EQUALS 'W2' AND 'W1' IS GREATER THAN 20" VANES SHALL BE DOUBLE VANE TYPE.

W1

W2

SCALE: NTS

VOLUME DAMPER DETAIL7

NOTES:

1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE

DAMPERS & ROUND DAMPERS.

SIDE ELEVATION

HANDLE WITH

LOCKING QUADRANT

1/8" CLEARANCE

ALL AROUND SECTION

INSIDE END BEARING

DAMPER BLADE

INSULATION

STAND-OFF

DUCTWORK

INSULATION

(SEE SPECIFICATION)STIFFEN BLADE

AS REQUIREDOUTSIDE END BEARING

1/2" ROUND ROD PIN

ATTACH TO STRUCTURE

(TYP)

CEILING

RETURN AIR PLENUM

FILTERED RETURN GRILLE

FAN COIL

SCALE: NTS

WITH OUTSIDE AIR DETAILRETURN GRILLE (BOTTOM RETURN)

4

ATTACH TO STRUCTURE

(TYP)

CEILING

FILTER BOX

RETURN GRILLE

FAN COIL

TRANSITION AS REQUIRED

8"Ø OUTSIDE

AIR DUCT

RETURN AIRPLENUM, FULL

SIZE OF FAN

COIL

2" FILTER

HINGE 1/4 TURN FASTENER

MANUAL

BALANCING

DAMPER

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

M5.0

MECHANICALDETAILS

EXHAUST FAN

ROOF CURBROOF. SEE

ARCHITECTURAL AND

STRUCTURAL PLANS

FOR MORE

INFORMATION

DAMPER. SEE

FAN SCHEDULE

FOR TYPE

SEE PLANS FOR

DUCTWORK

CONTINUATION

NOTE:

1. PROVIDE WATERTIGHT SEAL AT ROOF PENETRATION.

2. USE ROOF CURB AS TEMPLATE FOR CUTTING ROOF OPENING.

3. ADJUST DUCT RISER AS REQUIRED TO MATCH ROOF CURB OPENING.

SCALE: NTS

UPBLAST EXHAUST FAN DETAIL1

SCALE: NTS

CONNECTION) DETAILFIRE / SMOKE DAMPER (ELECTRICAL

6

120V, 1Ø; REF ELEC.

TO FIRE ALARM PANEL, REF ELEC.

DAMPER

ACCESS

DOOR

M

JB

CEILING

SMOKE / FIRE DAMPER

AND SLEEVE, INSTALL

PER MANUFACTURER'S

INSTRUCTIONS & LISTING

ACCESS PANELS IN CEILINGS

AND/OR WALLS FOR ACCESS

TO DAMPERS AND DETECTORS

REF ARCH.

ACTUATOR DUCT

JUNCTION BOX

FIRE AND/OR SMOKE

SEPARATION, REF ARCH.

NOTE:

REFER TO ELECTRICAL DRAWINGS FOR POWER.

SCALE: NTS

FIRE DAMPER (WALL-MOUNTED) DETAIL7

NOTES:

32

4

1

6

ACCESS

PANEL

5

1"

1

1/2" 1/2" 1 1/2"

SCALE: NTS

FAN FLEXIBLE DUCT CONNECTION DETAIL3

ROUND FLEXIBLE CONNECTION

5/16" FLANGE

BOLTS ON 4" CENTERS

1"X1/8" BAND IRON

1"X1/8" DRAW BAND

FLEXIBLE

MATERIAL AS

SPECIFIED

SHEET METAL SCREWS ON 12" CENTERS

RIVETS ON 4" CENTERS

DUCT

FLANGED CONNECTION

ON FAN SIDE

WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED.

6" NOMINAL WITH MATERIAL TAUT.

FLANGED

CONNECTION

ON FAN SIDE

WASHER

SHEET METAL AS

SPECIFIED FOR

DUCTWORK

ALTERNATIVE

BOLT

LOCATION BOLTS ON 4" CENTERS

1"X1/8" BAND IRON

FLEXIBLE

MATERIAL AS SPECIFIED

1" FLANGE & HEM

DUCT

1-1/2" MIN. TO 3" MAX. INSTALLED.

6" NOMINAL WITH MATERIAL TAUT.

SHEET METAL AS SPECIFIED

FOR DUCTWORK

DUCT

1 1/2" POCKET

SLIP

NOTES:

1. CONSTRUCTION HOUSING AND TOP OF 22 GA SS. ALL JOINTS AND SEAMS

SHALL BE WELDED OR SOLDERED WATER TIGHT. CROSSBREAK OR SLOPE

TOP FOR DRAINAGE.

2. VERIFY DIMENSIONS REQUIRED TO CONFORM WITH ACTUAL PIPE AND/OR

INSULATION SIZES AND QUANTITIES.

3. VERIFY ROOF OPENING SIZE WITH ARCHITECTURAL AND/OR STRUCTURAL.

SCALE: NTS

ROOF PENETRATION DETAIL - PIPING5

REFER ARCHITECTURAL

FOR ROOF DECK, CURB,

INSULATION, VAPOR

BARRIER, ETC. MATERIALS

AND INSTALLATION

2 SCREWS ON EACH OF 3 SIDES (MIN)

LOCATE SCREWS 6" FROM END AND 12" O.C.

6"1/2" MAX.

SLOPE PIPES AWAY

FROM HOOD

STAINLESS

STEEL SCREWS

PROVIDE LOOSE

FIT JOINT

SCALE: NTS

SUPPLY FAN DETAIL2

10" MIN.

8" MIN.

CONNECT DUCT TO CURB

ROOF STRUCTURE

SEE ARCHITECTURAL

AND STRUCTURAL PLANS

FOR DETAILS

CURB (SEE SPECIFICATIONS)

THERMAL INSULATION

FASTEN INTO WOODEN

OR SIMILAR BASE

ACOUSTICAL LINING

SECURE EQUIPMENT TO CURB

WITH SCREWS 12" OC ALL AROUND

NOTES:

1. SPUD BACK GRAVEL A MIN. OF 30" IN ALL DIRECTIONS. FLASH WITH 90# MINERAL FACED BASE

FLASHING. STRIP WITH 3 LAYERS OF ROOFING FELT EMBEDDED ASPHALT. GRAVEL TO MATCH.

2. INSTALL LOUVER DAMPERS WHEN REQUIRED WITHOUT DEFORMATION TO LOUVER FRAME; INSURE

LOUVER'S MOVEMENT IS FREE AND UNRESTRICTED AFTER FAN IS INSTALLED.

INSULATION

WELD OR SOLDER

WATERTIGHT ALL DUCT

ABOVE ROOF

CURB CAP

ROOF DECK W/ BUILT-UP

ROOFING; EXTEND TO TOP

OF CURB

CURB FASTENING

FLANGE

SECURE CURB TO ROOF WITH

METHOD CONSISTENT WITH

ROOF CONSTRUCTION

ROOF OPENING AND SIZE PER CURB

MFG'S APPROVED SHOP DWGS

SCALE: NTS

DUCT PENETRATION OF CURB DETAIL4

PLAN VIEW SECTION VIEW DISCHARGE END VIEW

SUPPLY FAN, SEE

SCHEDULE

PROVIDE WEATHER

SHROUD OVER

MOTOR AND DRIVE

ASSEMBLY.

CONTRACTOR

FABRICATED INTAKE

HOOD, WITH BIRD

SCREEN ON INTAKE

BIG FOOT EQUIPMENT MOUNTING

FRAME BY RECTORSEAL, OR

APPROVAL EQUAL

SEE DETAIL 4, THIS

SHEET

DUCTWORK TO BE

SEALED WEATHER

TIGHT

SEE DETAIL 4, THIS

SHEET

DUCTWORK TO BE

SEALED WEATHER

TIGHT

BIG FOOT EQUIPMENT MOUNTING

FRAME BY RECTORSEAL, OR

APPROVAL EQUAL

ROOF

SUPPLY FAN, SEE

SCHEDULE

SEE DETAIL 3, THIS

SHEET

SEE DETAIL 3, THIS

SHEET

PROVIDE WEATHER

SHROUD OVER

MOTOR AND DRIVE

ASSEMBLY.

SUPPORT RAILS SUPPLIED BY FAN

MANUFACTURER. SECURE TO ROOF

AND FAN PER MANUFACTURER'S

RECOMMENDATIONS.

ROOF

CONTRACTOR

FABRICATED INTAKE

HOOD, WITH BIRD

SCREEN ON INTAKE

DUCTWORK TO

INTERNALLY LINED

WITH 2" INSULATION

3'-0"

1'-6"

DUCTWORK TOINTERNALLY LINED

WITH 2" INSULATION

DUCTWORK TOINTERNALLY LINED

WITH 1" INSULATION

IN SHAFT

3'-0"

14" Wx24" H

OPENINGMINIMUM

MOTORIZED DAMPERMOTORIZEDDAMPER

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

M5.1

MECHANICALDETAILS

4'4'

SCALE: NTS

HOOD DETAILELEVATOR SHAFT RELIEF

3

COUNTER-BALANCED

BACKDRAFT DAMPER

INSECT SCREEN

ROOF CURB, FLASHING

AND COUNTERFLASHING

RELIEF HOOD

1" #16F FLATTENED

EXPANDED STEEL W/78%

FREE AREA

STEEL ANGLE FRAME

SCALE: NTS

HEAT PUMP SUPPORT DETAIL1

SCALE: NTS

REFRIGERANT PIPING SUPPORT2

SIDE VIEW FRONT VIEW

SECTION VIEW FRONT VIEW

E

BIG FOOT EQUIPMENT MOUNTING

FRAME BY RECTORSEAL, OR

APPROVAL EQUAL

LINESET DUCTING COVER, RD

SERIES, BY RECTORSEAL, OR

APPROVED EQUAL.

MAXIMUM LINE SET CAPACITYDUCT SERIES WIDTH (IN) HEIGHT (IN) QTY OF TUBING COMMENTS

RD300 11 7/8" 0'-5 1/8" 8 1

RD450 1'-5 3/4" 0'-5 1/8" 12 1

RD600 1'-11 5/8" 0'-5 1/8" 19 1

RD900 2'-11 3/8" 0'-5 1/8" 25 1

1. THESE VALUES ARE BASED ON 3/8" & 5/8" LIQUID / GAS LINE SETS WITH 1/2" THICK INSULATION. SEE MANUFACTURER'S DATA FOR OTHER SIZES.

SPACING TO BE DETERMINED BASED ON

MANUFACTURER'S RECOMMENDATIONS.

MAXIMUM 6'-0" SPACE

BIG FOOT EQUIPMENT MOUNTING

FRAME BY RECTORSEAL, OR

APPROVAL EQUAL

HEAT PUMP OR AC (TYP)

SEE SCHEDULE

SECURE TO FRAME

AND ROOF PER

MANUFACTURER'S

RECOMMENDATIONS

H

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

M5.2

MECHANICALDETAILS

ABBREVIATIONS

A AIR, AMPERE

ABS ABSOLUTE

ACU AIR CONDITIONING UNIT

AFF ABOVE FINISHED FLOOR

AG ABOVE GRADE

AHU AIR HANDLING UNIT

AL ALUMINUM

AMB AMBIENT

ARRGT ARRANGEMENT

ATM ATMOSPHERE

BFF BELOW FINISHED FLOOR

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOB BOTTOM OF BEAM

BOD BOTTOM OF DUCT

BOS BOTTOM OF STEEL

BT BATHTUB

BTUH BRITISH THERMAL UNITS PER

HOUR

C CELCIUS

CAP CAPACITY

CCW COUNTER-CLOCKWISE

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CI CAST IRON

CLG CEILING

CO CLEANOUT

CONC CONCRETE

COND CONDENSATE

CONT CONTINUE, CONTROL

COTG CLEANOUT TO GRADE

CP CIRCULATING PUMP

CRU CONDENSATE RETURN UNIT

CU FT CUBIC FEET

CV CONSTANT VOLUME

CVTR CONVERTER

CW COLD WATER, CLOCKWISE

DCVA DOUBLE CHECK VALVE ASSEMBLY

DEG DEGREE

DF DRINKING FOUNTAIN

DFU DRAINAGE FIXTURE UNITS

DI DE-IONIZED

DIA DIAMETER

DL DEVELOPMENTAL LENGTH

DN DOWN

DS DOWNSPOUT

E EXISTING

EFF EFFICIENCY

EL ELEVATION

EQUIP EQUIPMENT

EWT ENTERING WATER TEMPERATURE

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR, EXTERNAL

F FAHRENHEIT, FIRE LINE

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FE FIRE EXTINGUISHER

FLA FULL LOAD AMPS

FLR FLOOR

FLTR FILTER

FM FLOW METER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FT FEET, FAN TERMINAL

FU FIXTURE UNITS

GA GAGE

GAL GALLONS

GALV GALVANIZED

GPM GALLONS PER MINUTE

H HEIGHT

HB HOSE BIBB

HD HEAD

HEX HEAT EXCHANGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER, HEAT PUMP

HTG HEATING

HW HOT WATER

HWC HOT WATER CIRCULATING

HWP HOT WATER PUMP

HWR HOT WATER HEATING RETURN

HWS HOT WATER HEATING SUPPLY

ID INSIDE DIAMETER, INDIRECT DRAIN

IE INVERT ELEVATION

IN INCH

INIT INITIAL

INT INTERIOR

L LENGTH, LAVATORY

LB POUND

LBS POUNDS

LF LINEAR FEET

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

MCA MINIMUM CIRCUIT AMPACITY

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MOCP MAXIMUM OVER CURRENT

PROTECTION

MTR MOTOR

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEG NEGATIVE

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NUMBER, NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

ORD OVERFLOW ROOF DRAIN

P PUMP, PLUMBING

PD PRESSURE DROP

PH PHASE

POC POINT OF CONNECTION

POS POSITIVE

PPM PARTS PER MILLION

PR PUMPED RETURN

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA PSI ABSOLUTE

PSIG PSI GAGE

P/T PRESSURE/TEMPERATURE

PVC POLYVINYL CHLORIDE

QTY QUANTITY

RD ROOF DRAIN

REF REFERENCE

REQD REQUIRED

RH RELATIVE HUMIDITY

RPBFP REDUCED PRESSURE BACKFLOW

PREVENTER

RPM REVOLUTIONS PER MINUTE

S SOIL, SINK

SD STORM DRAIN

SENS SENSIBLE

SF SQUARE FEET, SAFETY FACTOR

SG SPECIFIC GRAVITY

SH SHOWER

SL SOUND LINING

SP STATIC PRESSURE

SS STAINLESS STEEL, SANITARY

SEWER, SERVICE SINK

T THERMOSTAT

TEMP TEMPERATURE

TOT TOTAL

TP TRAP PRIMER, TOTAL PRESSURE

TRV TEMPERATURE RELIEF VALVE

TSP TOTAL STATIC PRESSURE

TW TEMPERED WATER

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

UR URINAL

V VENT, VOLT

VA VALVE

VAC VACUUM

VB VACUUM BREAKER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

VTR VENT THROUGH ROOF

W WASTE, WATER, WATT, WIDTH

WB WET BULB

WCO WALL CLEANOUT

WG WATER GAGE

WH WATER HEATER, WALL HYDRANT

WOG WATER, OIL, & GAS

WSFU WATER SUPPLY FIXTURE UNITS

WTR WATER

WWP WATER WORKING PRESSURE

YH YARD HYDRANT

SYMBOL DESCRIPTION

SYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMS

SYMBOL DESCRIPTION

SYMBOLS LEGEND - PLUMBING

FLOW DIRECTION

FLOOR DRAIN

FLOOR SINK

ELECTRIC MOTOR OPERATOR (VALVES AND DAMPERS)M

ELECTRIC MOTOR/STARTER ASSEMBLYM

CENTRIFUGAL FAN

PUMP

CONNECTION TO CENTRAL MONITORING AND CONTROL SYSTEM (CMCS)

COMPLEX INTERLOCK (ELEC., PNEUMATIC, ETC.)

FLOW CONTINUATION ARROW

ELECTRICAL CONNECTION

PIPING OR DUCTED AIRFLOW

HUMIDITY SENSORH

SD SMOKE DETECTOR

PRESSURE GAGE

THERMOMETER

THERMOSTATT

TEMPERATURE SENSORS

CARBON MONOXIDE SENSORCO

CARBON DIOXIDE SENSOR

FIREF

BELOW GRADE SOIL OR WASTE

VENT

RAIN LEADERRL

OVERFLOW RAIN LEADERORL

INDIRECT DRAINID

COLD WATER

HOT WATER

HOT WATER CIRCULATING

140° POTABLE HOT WATER140°HW

120° POTABLE HOT WATER120°HW

NON-POTABLE WATERNP

FLEXIBLE CONNECTION IN PIPING

EXPANSION JOINT IN PIPING

PIPE SUPPORTPS

PIPE ALIGNMENT GUIDE

PIPE ANCHORA

REDUCER, CONCENTRIC

CLEANOUT TO GRADECOTG

WALL CLEANOUTwco

co FLOOR CLEANOUT

HOSE BIBB

AAV MAV AUTOMATIC AIR VENT, MANUAL AIR VENT

FLOOR DRAIN

FLOOR SINK

UNION

PLUG

CAP

PIPE UP TEE / TOWARDS

PIPE DOWN TEE, PIPE DOWN TEE / AWAY

PIPE TURNING UP / TOWARDS

PIPE TURNING DOWN / AWAY

CHECK VALVE

RELIEF VALVE

BALANCING/MEASURING VALVE

PRESSURE REDUCING VALVE

NEEDLE VALVE

BALANCING OR PLUG VALVE

BUTTERFLY VALVE

BALL VALVE

GLOBE VALVE

GATE VALVE

WYE STRAINER, WYE STRAINER WITH CAPPED HOSE END BLOWDOWN VALVE

VALVE IN RISER

ANGLE VALVE

PRESSURE REDUCING REGULATOR

PRESSURE REGULATOR

AUTOMATIC CONTROL VALVE - THREE WAY (ELECTRIC OPERATOR SHOWN)M

AUTOMATIC CONTROL VALVE - TWO WAY (PNEUMATIC OPERATOR SHOWN)

THERMOWELL

PRESSURE/TEMPERATURE TEST PORTP/T

PRESSURE GAGE

THERMOMETER

CONTROL VALVE STATION

SOIL OR WASTE ABOVE GRADE

NATURAL GAS

# DRAWING CONSTRUCTION ("FLAG") NOTE

EQUIPMENT IDENTIFIERX-XX

MATCHLINE

REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE

THE PREVIOUS RELEASE)

# REVISION REFERENCE

EXISTING TO BE REMOVED (HATCH)

HEAVY LINEWEIGHT INDICATES NEW WORK

LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION

POINT OF CONNECTION (POC) BETWEEN NEW AND EXISTING

POINT OF CONNECTION

NNORTH REFERENCE

DETAIL REFERENCEX

XX.XXDETAIL IDENTIFICATION NUMBER

SHEET WHERE DETAIL IS DRAWN

ELEVATION REFERENCEX

XX.XXELEVATION IDENTIFICATION NUMBER

SHEET WHERE ELEVATION IS DRAWN

SECTION REFERENCEX

XX.XX SECTION IDENTIFICATION NUMBER

SHEET WHERE SECTION IS DRAWN

SYMBOL DESCRIPTION

SYMBOLS LEGEND - GENERAL

ENERGY CODE WATER HEATING NOTES

1. SERVICE WATER HEATING EQUIPMENT TO HAVE TEMPERATURE CONTROLS TO ALLOW A SET POINT OF 110°F FOR EQUIPMENT SERVING DWELLING

UNITS AND 90°F FOR EQUIPMENT SERVING OTHER OCCUPANCIES. THE OUTLET TEMPERATURE OF LAVATORIES IN PUBLIC FACILITY REST ROOMS IS

LIMITED TO 110°F.

2. WATER HEATING EQUIPMENT NOT SUPPLIED WITH INTEGRAL HEAT TRAPS AND SERVING NON-CIRCULATING SYSTEMS; TO HAVE HEAT TRAPS ON THE

SUPPLY AND DISCHARGE PIPING ASSOCIATED WITH THE EQUIPMENT.

3. HOT WATER SYSTEM CONTROLS DESIGNED TO MAINTAIN USAGE TEMPERATURES IN HOT WATER PIPES IS TURNED OFF AUTOMATICALLY WHEN THE

HOT WATER SYSTEM IS NOT IN OPERATION AND HAS DEMAND SENSING CONTROLS THAT TURN OFF THE SYSTEM WHEN THERE IS NO DEMAND WHEN

THE SYSTEM IS OPERATIONAL. A CHECK VALVE OR SIMILAR DEVICE IS INSTALLED PER REQUIREMENT DETAILS.

GENERAL NOTES

1. THE FULL SCOPE OF THE MECHANICAL WORK IS THE TOTAL OF WORK SHOWN ON THE PLANS

AND CALLED FOR IN THE SPECIFICATIONS. IN CASE OF CONFLICT, THE SPECIFICATIONS SHALL

GOVERN. PROVIDE A COMPLETE & FUNCTIONAL SYSTEM.

2. PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES. OBTAIN AND

PAY FOR ALL REQUIRED PERMITS AND PAY FOR ALL FEES REQUIRED BY AUTHORITIES HAVING

JURISDICTION. PAY ALL ROYALTIES OR FEES REQUIRED IN CONNECTION WITH THE USE OF

PATENTED DEVICES AND SYSTEMS.

3. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION

INCLUDING, BUT NOT LIMITED TO, LOUVERS, CONCRETE EQUIPMENT PADS, FLASHING DETAILS,

ETC. REFER TO ARCHITECTURAL DRAWINGS FOR ROOM ELEVATIONS, LOCATE MECHANICAL

DEVICES SUCH AS TEMPERATURE SENSORS, HUMIDISTATS, PANELS, ETC. SO THAT THEY DO

NOT CONFLICT WITH GENERAL CONSTRUCTION (WAINSCOT, DOOR HARDWARE, ETC.) NOR

WITH ELECTRICAL SYSTEM (LIGHT SWITCHES, SPEAKERS, OUTLETS, ETC.).

4. ARRANGE EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY DRAWINGS, REQUIRED

BY CODES, OR RECOMMENDED BY MANUFACTURER ARE PROVIDED; WHICH EVER ARE MOST

STRINGENT.

5. THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT, DUCTWORK, AND PIPING WILL BE

INSTALLED AND REPORT ANY CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE

MECHANICAL WORK.

6. COMPLY WITH OREGON ENERGY EFFICIENCY SPECIALTY CODE SECTION 503.2.9 HVAC

SYSTEM COMPLETION. INCLUDE THE DEVELOPMENT OF CONSTRUCTION AND AS-BUILT

DRAWINGS, PROJECT MANUALS, AND SYSTEM BALANCING REPORTS.

7. ARRANGEMENT OF SYSTEMS INDICATED ON THE DRAWINGS IS DIAGRAMMATIC, AND

INDICATES THE MINIMUM REQUIREMENTS FOR PLUMBING AND MECHANICAL WORK. ADJUST

BOX LOCATIONS, BASED ON FIELD MEASUREMENTS, TO AVOID INSTALLATION ABOVE DESKS.

SITE CONDITIONS SHALL DETERMINE THE ACTUAL ARRANGEMENT OF THE WORK. TAKE FIELD

MEASUREMENTS BEFORE PREPARING SHOP DRAWINGS, OBTAIN APPROVAL OF SHOP

DRAWINGS BEFORE BEGINNING FABRICATION. BE RESPONSIBLE FOR ACCURACY OF

DIMENSIONS AND LAYOUT. OVERHEAD PIPING AND DUCTWORK SHALL BE ARRANGED TO

OBTAIN MAXIMUM HEAD ROOM. SHOP DRAWINGS SHALL BE STAMPED BY A LICENSED

ENGINEER.

8. CLEAN AND PROTECT WORK FROM DAMAGE. RESTORE DAMAGED FINISHES. COVER ENDS OF

PIPING AND DUCTWORK NOT ACTIVELY BEING WORKED ON.

9. WHEN APPLICABLE, MODIFY AND EXTEND EXISTING SERVICE TO ACCOMMODATE NEW WORK.

RELOCATE EXISTING COMPONENTS AS REQUIRED FOR NEW SYSTEM. COORDINATE WITH

BUILDING MANAGEMENT.

10. CONCEAL PIPING AND DUCTWORK TO THE GREATEST EXTENT PRACTICAL.

11. DRAWINGS DO NOT SHOW ALL OFFSETS WHICH MAY BE REQUIRED. MAKE OFFSETS WITH

FITTINGS WITH AS SMALL ANGLE OF OFFSET AS POSSIBLE; DO NOT USE TURNING VANES

UNLESS SPECIFICALLY SHOWN. DUCTWORK & PIPING SHALL BE ROUTED TO AVOID ALL

STRUCTURAL SUPPORTS. DO NOT CUT STRUCTURAL ELEMENTS WITHOUT PRIOR WRITTEN

APPROVAL.

12. MATERIALS, METHODS, AND INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE

LATEST EDITION OF THE FOLLOWING CODES AS ADOPTED BY LOCAL JURISDICTION.

• OREGON STRUCTURAL SPECIALTY CODE (OSSC)

• OREGON MECHANICAL SPECIALTY CODE (OMSC)

• OREGON PLUMBING SPECIALTY CODE (OPSC)

• OREGON FIRE CODE (OFC)

• OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC)

PIPING NOTES

1. PROVIDE ALL REQUIRED ACCESSORIES INCLUDING SHUT-OFFS AND CLEAN-OUTS. PROVIDE

COMPONENTS WHICH PREVENT BACK-SIPHONAGE OR CROSS-CONNECTIONS. PROVIDE

ISOLATION DEVICES TO REDUCE SOUND TRANSMISSION.

2. PROVIDE STOPS FOR EACH WATER CONNECTION TO EACH FIXTURE OR ITEM OF EQUIPMENT.

3. DISINFECT WATER DISTRIBUTION SYSTEM. FLUSH AND TEST ALL SYSTEMS FOR PROPER

OPERATION. ADJUST SYSTEM TO PREVENT WATER HAMMER.

4. REFER TO PIPING DIAGRAMS AND DETAILS FOR REQUIRED FITTINGS, VALVES, ETC. FLOOR

PLANS AND SECTIONS INDICATE EQUIPMENT LOCATIONS AND GENERAL PIPE ROUTING ONLY.

FIRE PROTECTION NOTES

1. MAKE FIELD MEASUREMENTS, COORDINATE WITH ALL OTHER WORK AND SHOW THE

MODIFICATIONS REQUIRED ON SHOP DRAWINGS.

2. MODIFY FIRE PROTECTION SYSTEMS TO ALLOW INSTALLATION OF DUCTWORK, OTHER PIPING,

AND ELECTRICAL WORK AS SHOWN ON APPROVED SHOP DRAWINGS. NEW ARRANGEMENT

SHALL LOCATE PIPING AS HIGH AS POSSIBLE.

3. PROVIDE A COMPLETE FIRE SPRINKLER SYSTEM FOR THE ENTIRE PROJECT AREA.

4. FLOORS ARE CURRENTLY SERVED BY A COMPLETE AUTOMATIC SPRINKLER SYSTEM.

PROVIDE NEW SPRINKLER HEADS, BRANCH PIPING TO SUIT NEW PARTITIONS &

REQUIREMENTS OF FIRE DEPARTMENT. NEW HEADS SHALL BE LOCATED IN CENTER OF TILE.

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

P0.0

PLUMBING NOTES, SYMBOLS &ABBREVIATIONS

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

P1.0

PLUMBING

SCHEDULES

SCALE:

BASEMENT PLAN - PLUMBING1/8" = 1'-0"

1SCALE:

FIRST FLOOR PLAN - PLUMBING1/8" = 1'-0"

2

SCALE:

SECOND,THIRD & FOURTH FLOOR PLANS - PLUMBING1/8" = 1'-0"

3SCALE:

ROOF PLAN - PLUMBING1/8" = 1'-0"

4

COTG

FS-1

FS-1

6" SAN

360 DFU

SEE CIVIL FOR

INVERT ELEVATION

HB-1

RD-1/ORD-1

1-1/2" NG

799.8 MBH

SEE CIVIL FOR INVERT

ELEVATION

2-1/2"CW

1/2" CW UP FROM

4TH FLOOR TO

HOSE BIBB ON

ROOF

1

2

WCO

WCO

WCO

WCO

3" ORD OFFSET IN WALL SEE 2/P2.0

3" RD OFFSET IN WALL SEE 2/P2.0

3" ORD

3" RD

WCO

WCO

WCO

WCO

3

4

2-1/2" DCW

397 WSFU

SEE CIVIL FOR INVERT

ELEVATION

3

P6.0

WCO

WCO

WCO

WCO

WCO

6

6

6

6

12

12

12

7

7

7

8

13

10

10

13

9

9

2-1/2" VTR

2-1/2" VTR

2-1/2" VTR

3" VTR

3" V

3" SAN

3" SAN

4" SAN

4" SAN

6" SAN

4" SAN

4" SAN

1-1/2"CW

1-1/2"HW

3/4 HWC

1-1/2"CW

1-1/2"HW

3/4 HWC

1-1/2"CW

1-1/2"HW

3/4 HWC

1-1/2"CW

1-1/2"HW

3/4 HWC

1-1/2"CW

1-1/2"HW

3/4 HWC

3" SAN

3" SAN

3" SAN

2-1/2" SAN

4" SAN

3" SAN

3" SAN

3" SAN

3" SAN

3" SAN

2-1/2" SAN

6

1-1/2"CW

1-1/2"HW

3/4 HWC

11

11

3" SAN

3" SAN

3" SAN

NATURAL GAS

METER FOOTPRINT

2-1/2"HW

3/4 HWC

3"

3" RD EXIT BUILDING

AT HIGH LEVEL

DN-1

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

2" VENT

HB-2

(2) 4" PVC BOILER VENT &

(2) 4" PVC BOILER AIR

INTAKE IN CHASE

(2) 4" PVC BOILER VENT &

(2) 4" PVC BOILER AIR

INTAKE IN CHASE (2) CONCENTRIC VTR4

P6.1

141/2" CW

1/2" CW UP FROM 4TH

FLOOR TO HOSE BIBB

ON ROOF

FLAG NOTES

CW, HW & HWC ROUTED IN CEILING. TYPICAL THIS VIEW.

SAN ROUTED IN SLAB. TYPICAL THIS VIEW

1-1/4"CW, 1-1/4" HW, 3/4" HWC & 4" SAN ROUTED IN FLOOR OF APARTMENT

ABOVE.

3" SAN DOWN FROM FIRST FLOOR TRASH ROOM FD-1, ROUTE TO WALL

AND DOWN TO CONNECT WITH SAN BELOW SLAB.

EXTEND COTG CAP TO TOP OF LANDSCAPING.

1-1/2" CW, 1-1/2" HW, 3/4" HWC & 4" SAN IN CHASE.

1-1/2" CW, 1-1/2" HW, 3/4" HWC & 4" SAN IN CHASE.

1-1/2" CW, 1-1/4" HW, 3/4" HWC & 4" SAN FROM FLOOR ABOVE, ROUTE IN

FLOOR OF APARTMENT ABOVE ON WARM SIDE OF INSULATION.

AT SECOND FLOOR:

1-1/2"CW, 1-1/2" HW, 3/4" HWC & 4" SAN IN CHASE.

AT THIRD FLOOR:

1-1/4" CW, 1-1/4" HW, 3/4" HWC & 4" SAN IN CHASE.

AT FOURTH FLOOR:

1" CW, 1" HW, 3/4" HWC & 4" SAN IN CHASE.

AT SECOND FLOOR:

1-1/2"CW, 1-1/2" HW, 3/4" HWC & 4" SAN IN WALL.

AT THIRD FLOOR:

1-1/4" CW, 1-1/4" HW, 3/4" HWC & 3" SAN IN WALL.

AT FOURTH FLOOR:

1" CW, 1" HW, 3/4" HWC & 3" SAN IN WALL.

AT SECOND FLOOR:

3" SAN IN WALL.

AT THIRD FLOOR & FOURTH FLOORS:

2" SAN IN WALL.

1-1/2" CW, 1-1/2" HW, 3/4" HWC & 4" SAN IN CHASE.

AT SECOND FLOOR:

1-1/2"CW, 1-1/2" HW, 3/4" HWC & 4" SAN IN WALL.

AT THIRD FLOOR:

1-1/4" CW, 1-1/4" HW, 3/4" HWC & 4" SAN IN WALL.

AT FOURTH FLOOR:

1" CW, 1" HW, 3/4" HWC & 4" SAN IN WALL.

1/2"CW UP TO HB-2 ABOVE.

1

2

GENERAL NOTES

1. SEE PIPING RISER DIAGRAM SHEETS P5.0 AND P5.1 FOR ADDITIONAL PIPE

SIZES.

2. SEE SHEETS P2.0 AND P2.1 FOR UNIT PIPING, SIZES AND LAYOUT TO EACH

FIXTURE.

3. CW, HW AND HWC RISERS TO TO SERVE EACH UNIT FROM CEILING SPACE

ABOVE.

4. PLUMBING PLANS ARE DIAGRAMMATIC IN NATURE AND REPRESENT

CONCEPTUAL ROUTING ONLY. CONTRACTOR IS RESPONSIBLE FOR FIELD

VERIFICATION OF ALL ACTUAL CONDITIONS.

5. ALL PIPING LOCATED IN EXTERIOR WALLS TO BE FULLY INSULATED AND

PROTECTED AGAINST FREEZING.

6. CONTRACTOR TO COORDINATE UNIT SHUTOFF VALVES, BUILDING SHUT

OFF VALVE AND CLEAN OUT LOCATIONS WITH ALL TRADES AND BUILDING

OWNER.

3

4

5

6

7

8

9

10

11

12

13

14

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

P2.0

FLOOR PLANS - PLUMBING

1

GENERAL SHEET NOTES

1. CONTRACTOR TO CONNECT DISHWASHER DRAIN HOSE TO SINK

DRAIN ON S-1.

2. IN ADA UNITS, REPLACE BT-1 WITH BT-2, L-1 WITH L-2 AND WC-1

WITH WC-2.

3. CW AND HW PIPING TO DROP DOWN TO EACH FIXTURE FROM

ABOVE.

4. PLUMBING PLANS ARE DIAGRAMMATIC IN NATURE AND REPRESENT

CONCEPTUAL ROUTING ONLY. CONTRACTOR IS RESPONSIBLE FOR

FIELD VERIFICATION OF ALL ACTUAL CONDITIONS. COORDINATE

WITH ALL OTHER TRADES.

5. ALL PIPING LOCATED IN EXTERIOR WALL TO BE FULLY INSULATED

AND PROTECTED AGAINST FREEZING.

6. CONTRACTOR TO COORDINATE UNIT SHUTOFF VALVES, BUILDING

SHUT OFF VALVE AND CLEAN OUT LOCATIONS WITH ALL TRADES

AND BUILDING OWNER.

FLAG NOTES

FOR SAN AND VENT PIPE SIZING IN CHASE, SEE RISER DIAGRAM

SHEET P5.0 .

FOR CW, HW & HWC PIPE SIZING IN CHASE, SEE RISER DIAGRAM

SHEET P5.1.

2

SCALE:

UNIT PLAN - STUDIO A - BASEMENT - PLUMBING1/4" = 1'=0"

1 SCALE:

TYPICAL UNIT PLAN - STUDIO B - PLUMBING1/4" = 1'=0"

2

SCALE:

TYPICAL UNIT PLAN - STUDIO C - PLUMBING1/4" = 1'=0"

3

SCALE:

TYPICAL UNIT PLAN - STUDIO D - PLUMBING1/4" = 1'=0"

4

WMOB-1

S-2

WC-2L-2

BT-2

WMOB-1

BT-1

WC-1 L-1

S-1

WMOB-1

WMOB-1

BT-1

BT-1

S-1 S-1

WC-1

WC-1

L-1

L-1

WASTE RISER

SAN, CW, HW &

HWC

WASTE RISER

DW-1

DW-1

DW-1

DW-1

SAN, CW, HW &

HWC

SAN, CW, HW & HWC

SAN, CW, HW &

HWC

WASTE RISER

2" SAN

2" SAN

3" SAN

2" SAN

2" SAN

3" SAN

2" SAN

3" SAN

21

21

21

21

1

1

1

11"

6" SAN

4" SAN

6" SAN

4" SAN

3/4" CW & HW

1"

3/4" CW & HW

1" CW & HW

1" CW & HW

3/4" CW & HW

WCO

4" SAN

3/4" HW

3/4"

CW &

HW

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

P3.0

ENLARGED PLANS-PLUMBING

SCALE:

TYPICAL UNIT PLAN - 1 BED A - PLUMBING1/4" = 1'=0"

1SCALE:

TYPICAL UNIT PLAN - 1 BED B - PLUMBING1/4" = 1'=0"

2

SCALE:

TYPICAL UNIT PLAN - 1 BED C - PLUMBING1/4" = 1'=0"

3SCALE:

TYPICAL UNIT PLAN - 1 BED D - PLUMBING1/4" = 1'=0"

4

WMOB-1

WMOB-1

WMOB-1

BT-1

BT-1

BT-1

S-1

S-1

S-1

WC-1

WC-1

WC-1

L-1

L-1

L-1

S-2

WMOB-1

WASTE RISER

WASTE RISER

DW-1

DW-1

DW-1DW-1

WASTE RISER

WASTE RISER

SAN, CW, HW &

HWC

SAN, CW, HW &

HWC

SAN, CW, HW &

HWC

2" SAN

3" SAN

2" SAN

2" SAN

3" SAN

2" SAN2" SAN

2" SAN

3" SAN

3/4" CW & HW

21

21

21

1

1

1

1

1" CW & HW

1" CW & HW

3/4" CW & HW

3/4" CW & HW

1" CW & HW

3/4" CW & HW

3/4" CW & HW

(2) 4" BOILER VENT &

(2) 4" BOILER AIR INTAKE

BT-1

WC-1L-1

SAN, CW, HW &

HWC

2" SAN

3" SAN

21

1" CW & HW

FLAG NOTES

FOR SAN AND VENT PIPE SIZING IN WALL, SEE RISER DIAGRAM

SHEET P5.0 .

FOR CW, HW & HWC PIPE SIZING IN WALL, SEE RISER DIAGRAM

SHEET P5.1.

1

2

GENERAL SHEET NOTES

1. CONTRACTOR TO CONNECT DISHWASHER DRAIN HOSE TO SINK

DRAIN ON S-1.

2. IN ADA UNITS, REPLACE BT-1 WITH BT-2, L-1 WITH L-2 AND WC-1

WITH WC-2.

3. CW AND HW PIPING TO DROP DOWN TO EACH FIXTURE FROM

ABOVE.

4. PLUMBING PLANS ARE DIAGRAMMATIC IN NATURE AND REPRESENT

CONCEPTUAL ROUTING ONLY. CONTRACTOR IS RESPONSIBLE FOR

FIELD VERIFICATION OF ALL ACTUAL CONDITIONS. COORDINATE

WITH ALL OTHER TRADES.

5. ALL PIPING LOCATED IN EXTERIOR WALL TO BE FULLY INSULATED

AND PROTECTED AGAINST FREEZING.

6. CONTRACTOR TO COORDINATE UNIT SHUTOFF VALVES, BUILDING

SHUT OFF VALVE AND CLEAN OUT LOCATIONS WITH ALL TRADES

AND BUILDING OWNER.

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

P3.1

ENLARGED PLANS-PLUMBING

SCALE:

WASTE & VENT PLUMBING RISER DIAGRAMNTS

1

BASEMENT

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

FOURTH FLOOR

ROOF

FS-1

S-1DW-1

3" VTR

WC-1 BT-1 WMOB-1

L-1 S-1 DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1 BT-1 WMOB-1

L-1 S-1 DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1 BT-1 WMOB-1

L-1 S-1 DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1 BT-1 WMOB-1

L-1 S-1 DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1 BT-1 WMOB-1

L-1 S-1 DW-1

WC-1BT-1WMOB-1

L-1

FD-1

WMOB-1 WC-1BT-1

L-1 S-1DW-1 L-1

WC-1 BT-1 WMOB-1

S-1DW-1 L-1

WC-1 BT-1 WMOB-1

S-1DW-1 L-1

WC-1 BT-1 WMOB-1

S-1DW-1

L-1

WC-1 BT-1 WMOB-1

S-1DW-1 L-1

WC-1 BT-1 WMOB-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1L-1

WC-1

S-2DW-1 L-2

WC-2 BT-2WMOB-1

BT-1WMOB-1

S-2DW-1 L-2

WC-2 BT-2WMOB-1

S-2DW-1 L-2

WC-2 BT-2WMOB-1

2-1/2" VTR 2-1/2" VTR 2-1/2" VTR 2-1/2" VTR

4" SAN

2-1/2" SAN

3" SAN

2" SAN

3" SAN

4" SAN

2" SAN

4" SAN

2" SAN

2-1/2" SAN

3" SAN

4" SAN

3" SAN

4" SAN

2" SAN

2-1/2" SAN

4" SAN2-1/2" SAN

2" SAN

2-1/2" SAN

3" SAN3" SAN

4" SAN

2" SAN

2-1/2" SAN

3" SAN

2-1/2" SAN

4" SAN4" SAN

2-1/2" SAN

4" SAN

3" SAN

4" SAN

4" SAN

4" SAN

6" SAN

362 DFU

SEE CIVIL FOR

INVERT ELEVATION

WCO WCO

WCO WCO

WCO

WCO WCO

WCO

WCOWCO

WCOWCO

4" SAN

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

2" V

2" V

2" V

2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

3" V

2" V

1-1/2" V

1-1/2" V

1-1/2" V

1-1/2" V

1-1/2" V

2" V

2-1/2" V2-1/2" V2-1/2" V3" V 2-1/2" V

2" V

2" V

2" V

2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

2" V

2" V

2" V2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

2" V

1-1/2" V

4" SAN

4" SAN

6" SAN

3" SAN

2-1/2"

SAN

4" SAN

2" V

S-1 DW-1

WCO

2" V

2" V

4" SAN

1-1/2" V

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

P5.0

WASTE & VENT

PLUMBING

RISER DIAGRAM

SCALE:

DOMESTIC WATER PLUMBING RISER DIAGRAMNTS

1

BASEMENT

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

FOURTH FLOOR

ROOF

DCBP-1B-01

S-1 DW-1

WMOB-1 WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

SEE DETAIL 3/P6.0

FOR PIPING AT

BOILER PLANT

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1 DW-1

WMOB-1WC-1BT-1

L-1

S-1DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1BT-1WMOB-1

L-1

S-1DW-1

WC-1BT-1WMOB-1

L-1

S-1 DW-1

WC-1 BT-1 WMOB-1

L-1

S-1 DW-1

WC-1 BT-1 WMOB-1

L-1

S-1 DW-1

WC-1 BT-1 WMOB-1

L-1

S-1 DW-1

WC-1 BT-1 WMOB-1

L-1

S-1 DW-1

WC-1 BT-1 WMOB-1

L-1

S-1 DW-1L-1

WC-1

S-2DW-1 L-2

WC-2 BT-2WMOB-1

BT-1WMOB-1

S-2DW-1 L-2

WC-2 BT-2WMOB-1

S-2DW-1 L-2

WC-2 BT-2WMOB-1

WC-1 BT-1 WMOB-1

L-1S-1DW-1

WC-1 BT-1 WMOB-1

L-1S-1DW-1

WC-1 BT-1 WMOB-1

L-1S-1DW-1

WC-1 BT-1 WMOB-1

L-1S-1DW-1

WC-1 BT-1 WMOB-1

L-1S-1DW-1

HB-1

2-1/2" CW

2-1/2" HW

2-1/2" CW

2-1/2" HW

2-1/2" CW

2" HW

2" CW

2" HW

2" CW

2" HW

1-1/2" CW

1-1/2" HW

1-1/2" CW

1-1/2" HW

1" CW

1" HW & 3/4" HWC

1-1/4" CW

1-1/4" HW

& 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1" CW

1" HW & 3/4" HWC

1-1/4" CW

1-1/4" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1" CW

1" HW & 3/4" HWC

1-1/4" CW

1-1/4" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1" CW

1" HW & 3/4" HWC

1-1/4" CW

1-1/4" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1" CW

1" HW & 3/4" HWC

1-1/4" CW

1-1/4" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1" CW

1" HW & 3/4" HWC

1-1/4" CW

1-1/4" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1/2" CW 3/4" CW

3/4" HW

1-1/2" CW

1-1/2" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

1-1/2" CW

1-1/2" HW & 3/4" HWC

3/4" HW 3/4" HW 3/4" HW3/4" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

3/4" CW

3/4" HW

1" CW

1" HW

1" CW

1" HW

1" CW

1" HW

B-02

3/4" CW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

HB-2

1" CW

1" HW

1" CW

1" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

2-1/2" CW

397 WSFU

SEE CIVIL FOR

INVERT ELEVATION

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

P5.1

DOMESTIC WATER

PLUMBING

RISER DIAGRAM

SCALE:

ENLARGED BOILER ROOM PLAN1/2" = 1'-0"

3

FLAG NOTES THIS DETAIL

MINIMUM 32" THERMAL TRAP.1

B-01

B-02

ET-01

ST-01

DC

BP

-1

1

2"

2

P6.0

4

P6.0

5

P6.0

5

P6.0

5

P6.0

1

P6.0

(2) 4" PVC BOILER VENT &

(2) 4" PVC BOILER AIR INTAKE

UP THROUGH ROOF

TV-1

1 -1/4 CW"

1" HWC

P-03

P-01

P-02

2 -1/2 CW"

SCALE: NTS

CONDENSING GAS FIRED BOILER DETAIL5

HWR

FLOW METER

HWS

PIPE TO NEAREST FLOORDRAIN AND TERMINATE

WITH AN AIR GAP.

PRESSURE

RELIEFVALVE

4" Ø BOILER

VENT, SEE PLANS

FOR ROUTINGGATE VALVE (TYP)

MANUAL AIR VENT

CHECK VALVE

UNION (TYP)

TEMPERATURE

GAUGE (TYP)

PRESSURE

GAUGE (TYP)

PRESSURE

REGULATORVALVE

BALL VALVE (TYP)

DIRT LEG

UP TO ROOF

SCALE: NTS

GAUGE PIPING DETAIL7

LEVER HANDLE GAUGE

COCK W/ PIPE THREADS

INSTALL GAUGE COCK ON

EITHER SIDE OF PIPE

INSTALLATION SHOWN ON TOP

OF PIPE FOR ILLUSTRATION

PURPOSES ONLY

3000# FULL STRENGTH COUPLING

WELDED TO PIPE; 1/4" MIN. SIZE

3" LONG SCHEDULE

80 BLACK NIPPLE

SCALE: NTS

THERMOMETER PIPING DETAIL6

2-1/2" MIN.

BULB MUST BE AT

BOTTOM OF WELL

3000# FULL STRENGTH

COUPLING WELDED TO

PIPE; 3/4"Ø MIN. SIZE

THERMOMETER SHOWN AT TOP

OF PIPE FOR ILLUSTRATION

PURPOSES ONLY; PREFERRED

LOCATION ON SIDE OF PIPE

SEE NOTE 3

45°45°

NOTES:

1. MOUNT 5'-6" AFF. OR AT EYE LEVEL, 7'-0" MAX HEIGHT.

2. THERMOMETER ILLUSTRATED TEST WELL TYP. TO BOLTON

TYPE 600 SERIES OR H.O. TERICE SERIES 5550 OR 5590

COMPLETE W/ CAP AND CHAIN.

3. ALLOW CLEARANCE FOR THERMOMETER REMOVAL.

4. SELECT COUPLING DIAMETER TO ACCOMMODATE TEST WELL

OR THERMOMETER AS REQUIRED.

SCALE: NTS

EXPANSION TANK AND AIR ELIMINATION SYSTEM DETAIL4

AUTOMATIC AIR ELIMINATOR

PIPED TO NEAREST FLOOR DRAIN

PRESSURE RELIEF VALVE (PIPED TO NEAREST FLOOR DRAIN)

ASME PRECHARGED

BLADDER TYPE

EXPANSION TANK

PROVIDE 4" THICK

CONC. PAD FOR TANK

GLOBE BY-PASS VALVE

FLOW

DCW

PRESSURE GAUGE

2-1/2" DCW

AIR REMOVAL TRAP

PRESSURE REDUCING VALVEGATE VALVE (TYP)

SCALE: NTS

INLINE PUMP DETAIL1

BALL VALVE (TYP) STRAINER WITH

BLOWDOWN

FLEXIBLE

CONNECTION (TYP)

CHECK VALVE

BALANCING DEVICE

1/2" LINES

PRESSURE

GAUGE

SUPPORT PUMP AND PIPING

FROM BUILDING

STRUCTURE AS REQUIRED.

BOILERDCW

GATE VALVE (TYP)

DOUBLE CHECK VALVE

STRAINER WITH BLOWDOWN

SCALE: NTS

PREVENTER DETAIL (>2"Ø)DOUBLE CHECK VALVE BACKFLOW

2

NOTES:

DCW

2-1/2"

2-1/2"

ET-01ST-01

PROVIDE 4" THICK

CONC. PAD FOR TANK

2"

1"

BOILER

BOILER

3"

HWS

2"

TEMPERATURE AND PRESSURE RELIEF

VALVE PIPE TO NEAREST DRAIN

ASME GLASS-LINED AND

JACKETED STORAGE TANK

1"

PIPE TO NEAREST

FLOOR DRAIN

2-1/2"

3/4"

4" Ø BOILER

OUTSIDE AIR, SEE

PLANS FOR ROUTING

1-1/2"

STRAINER

WITH BLOW

DOWN

P-2P-1

HWR

P-3

3/4"

1-1/4"

TO TEMPERINGVALVE

ST-01

1"

H

WC

P-3

TO TV-1

SEE DETAIL #1, THIS

SHEET FOR PUMP

VALVING

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

P6.0

PLUMBINGDETAILS

SCALE: NTS

ROOF DRAIN WITH OVERFLOW DETAIL #31

SAME SIZE

OVERFLOW ROOF DRAIN,

INLET 2" ABOVE ROOF DRAIN

ROOF DRAIN

DAYLIGHT 3' ABOVE

FINISHED GRADE

TO STORM

SEWER

SCALE: NTS

FLOOR DRAIN DETAIL2

1'SEE ARCHITECTURAL FOR

FLOOR FINISH AND

FLASHING REQUIREMENTS

CORE DRILL, VERIFY

LOCATION WITH ARCHITECT

FLOOR DRAIN OR SINK

CONCRETE

STRUCTURE

TWO WAY CLEANOUTONE WAY CLEANOUT

SCALE: NTS

CLEANOUT TO GRADE DETAIL6

NOTES:

1. TWO WAY CLEANOUT IS REQUIRED WHERE SEWER LINE EXITS THE BUILDING

AND AT ANY OTHER LOCATIONS NOTED ON PLANS.

FINISH GRADE

CAST IRON

EXTENSION

SAME SIZE AS

SEWER PIPING

(TYP)

6" CONCRETE PAD

(TYP)SEE PLANSCAST IRON LONG

SWEEP 1/4 BEND OR

CAST IRON COMB. Y &

1/8 BEND (USE

REDUCING TYPE

WHERE REQUIRED

SANITARY SEWER

(TYP)

CAST IRON

TWO WAY

CLEANOUT

TEE

CAST IRON CLEANOUT

WITH COVER FOR

DUTY REQUIRED.

COVER TO BE

INSCRIBED "SANITARY

SEWER CLEANOUT"

GAS EQUIPMENT

SCALE: NTS

GAS LINE CONNECTION DETAIL7

DRIP LEG

6" VERTICAL

FLEXIBLE GAS

CONNECTOR, 18"MAXIMUM

TRANSITION TO

EQUIPMENT AS

REQUIRED

GROUND JOINT UNION

MANUAL MAIN

SHOT-OFF VALVE

DROP FROM MAIN. SEE

PLANS FOR SIZE AND

ROUTING

SCALE: NTS

WASHING MACHINE OUTLET BOX DETAIL5

TO

VT

RW

AS

TE

2" P-TRAP

6" MINIMUM &18" MAXIMUM AFF.

CROSS MEMBER ATTACHED TO STUDS

SCREW TO CROSS MEMBERS (TYP 4)

1/2" CW & HW

SUPPLY AND WASTE HOSE BOX.

SIMILAR TO ACORN #8186

8-5/8" SQ.

3'-0" +/-

FINISHED FLOOR

TAIL PIECE

18" MINIMUM &

30" MAXIMUM

HANGER RODS

W / OR W / OUT TYPE 48 SPRING

ISOLATOR AS REQUIRED PER

SPECIFICATIONS

W / OR W / OUT PROTECTIVE

SADDLE OR SHIELD AS REQUIRED

ANGLE IRON OR UNISTRUT

TYPE SUPPORT

INSULATE PIPE AS REQUIRED

BY SPECIFICATIONS

NON-INSULATED

PIPE

HYDRONIC PIPING

INSULATION AND

VAPOR BARRIER

AS REQUIRED BY

SPECIFICATIONS

ATTACH TO STRUCTURETYPE 1

CLEVIS

HANGER

INSULATE AS

REQUIRED

BY CODE

W / OR W / OUT PROTECTIVE

SADDLE OR SHIELD AS REQUIRED

W / OR W / OUT TYPE 48 SPRING ISOLATOR AS

REQUIRED PER SPECIFICATIONS

ATTACH TO STRUCTURE

NOT TO ROOF DECK (TYP)

NOTES:

1. SIZE RODS, SPRING CUSHION, AND HORIZONTAL

MEMBER APPROVED TO SATISFY LOAD

REQUIREMENT W / SAFETY FACTOR OF 5.

2. DO NOT EXCEED ALLOWABLE LOAD LIMITS.ROOF

SHEET METAL SHOE

FOR PIPE >= 2-/2"Ø

4" X 4" PRESSURE TREATED

TIMBER LAID FLAT ON ROOF

W/OUT ANCHORS

1" MIN.

THICKNESS

SCALE: NTS

PIPING SUPPORT DETAIL11

INTERIOR STUD WALL

16 GA GALV STEEL

SLEEVE. SECURE TO

PARTITION - GROUT TIGHT

PIPE WITH OR

WITHOUT INSULATION

SEAL AND SECURE

SLEEVE AND COLLAR

TO CONCRETETYPE 8 RISER

CLAMP

ESCUTCHEON PLATE

WHERE EXPOSED

FILL ANNULAR SPACE COMPLETELY

BETWEEN PIPE AND SLEEVE WITH

FIRECAULK (3M FIRE SAFING)

NEOPRENE PAD,

ONE PER SIDE

PIPE WITH OR

WITHOUT INSULATION

TYPE 8 RISER

CLAMP

NEOPRENE PAD,

ONE PER SIDE

FILL ANNULAR SPACE COMPLETELY

AROUND PIPE W / FIRE CAULK, USE

FILLER ROD PER MANUFACTURER AND

FILL FLUSH TO TOP OF PIPE SLEEVE

1" IN UNFINISHED SPACES, FLUSH

WITH FLOOR AND ESCUTCHEON

IN FINISHED AREAS

CORE DRILL

CAST IN PLACE

SCALE: NTS

PIPING PENETRATIONS DETAIL10

WALL

5 FT

7

6 8 10

9 1110 12-1312 14 -16 -

1614 17 2219 23

-- - -

2725 28 3230

20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/47 7

7 98

SIDE VIEW TRAPEZE HANGER FOR UP TO 1000 LB.

UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE

1 - SEE SPECIFICATIONSADJUSTABLE CLEVIS HANGER TYPE

43 - SEE SPECIFICATIONS

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING (8"MIN.)

BAND (TYP)1-5/8" 12 GAUGE CHANNEL

OR 2"x2"x1/4" ANGLE

1/2" [15mm] DIA. HANGER RODS WITH

36" MAX. SPACING ON EACH CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

INSULATION PER

SPECIFICATIONS (TYP)

HANGER ROD (TYP)

MAXIMUM SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

FT.

FT.

1" M

AX

.

NOTES:

SEE SPECIFER FOR DETAILED

HANGER REQUIREMENTS

SCALE: NTS

PIPE HANGER DETAIL12

SCALE: NTS

PIPE IDENTIFICATION DETAIL9

PIPE INSULATION

PIPE

TYPICAL 2" WIDE COLOR CODED

TAPE (WRAP A MINIMUM OF 1-1/2

TIMES AROUND PIPE)

TYPICAL CONTINUOUS PIPE

IDENTIFICATION MARKER AND

DIRECTION OF FLOW ARROW

TO EXTEND 1" IN TO TAPE

NOTE:

1. APPLY A CONTINUOUS COATING OF CONTACT CEMENT TO THE LABEL TO

ENSURE PERMANENT ADHESION.

2. REFER TO SPECIFICATION FOR COLOR CODING OF SERVICES.

3. REFER TO SPECIFICATION FOR LOCATION REQUIREMENTS AND MAXIMUM

INTERVAL SPACING.

SCALE: NTS

TRAP PRIMER (SINGLE OUTLET) DETAIL8

SUPPLY TUBING, SEE

SPECIFICATIONS FORMATERIAL.

TRAP PRIMER VALVE

P-1000 UNISTRUT 4"LG W/(2)

1/4x2" TOGGLE BOLTS

1/2"1/2"

TRAP PRIMER VALVE

WALL

SCALE: NTS

VENT THROUGH ROOF DETAIL3

VENT PIPE

2" MIN.

AROUND

ALL AROUND

MIN CLEAR ALL

BLOCKING

COUNTER FLASHING RIMSTALL CONE FITTING WITH

COUNTER FLASHING RIMSRUN ROOF UP UNDER

SCALE: NTS

CONCENTRIC VENT THRU ROOF4

24" MIN.

COUNTER FLASHING RIMSTALL CONE FITTING WITH

COUNTER FLASHING RIMSRUN ROOF UP UNDER

COMBUSTION AIRFLUE VENT

MIN CLEAR ALL AROUND

BLOCKING ALL AROUND

FLUE VENT

COMBUSTION AIR

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

P6.1

PLUMBINGDETAILS

ABBREVIATIONS

@ AT

A/C AIR CONDITIONING(ER)

A (AMP) AMPERE

AC ABOVE COUNTER, ALTERNATING CURRENT

AFF ABOVE FINISHED FLOOR

AHJ LOCAL AUTHORITY HAVING JURISDICTION

AIC AMPERES INTERRUPTINGAL or ALUM ALUMINUMALT ALTERNATE

ANN ANNUNCIATOR

ARCH ARCHITECT; ARCHITECTURAL

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

BKR BREAKER

BLDG BUILDING

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

COM COMMUNICATION

CT CURRENT TRANSFORMER

CU COPPER

DWG DRAWING

(E) EXISTING TO REMAIN

E EAST

EF EXHAUST FAN

EGC EQUIPMENT GROUNDING CONDUCTOR

EL ELEVATION

ELEC ELECTRIC(AL)

ELEV ELEVATOR

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EQUIP/EQP EQUIPMENT

EWH ELECTRIC WATER HEATER

EXH EXHAUST

EXT EXTERIOR

FA FIRE ALARM

FC FOOTCANDLE

FCP FIRE ALARM SYSTEM CONTROL PANEL

FCU FAN COIL UNIT

FD FIRE DAMPERFDR FEEDER

FLA FULL LOAD AMPS

FSA FIRE SYSTEM ANNUNCIATOR

FSD FIRE/SMOKE DAMPER

GEC GROUNDING ELECTRODE CONDUCTOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

H HEIGHT

HP HORSEPOWERHZ HERTZ

IBC INTERNATIONAL BUILDING CODE

IC INTERCOM

IESNA ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

JB or J-BOX JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LBS POUNDS

LF LINEAR FEET (FEET)

LRA LOCKED ROTOR AMPS

LS LIFE SAFETY

LV LOW VOLTAGE

MAN MANUALMAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MECH MECHANICAL

MH MANHOLEMIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

(N) NEW

N NORTH; NEUTRAL

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION

NESC NATIONAL ELECTRICAL SAFETY CODE

NFPA NATIONAL FIRE PROTECTION AGENCY

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OL OVERLOAD

P POLE; PHASE; PRIMARY

PA PUBLIC ADDRESS

PAR PARALLEL

PB PULL BOX

PE PHOTO ELECTRIC

PF POWER FACTOR

PH PHASE

PIV POST INDICATOR VALVE

PNL PANEL

POC POINT OF CONNECTION

PSE PUGET SOUND ENERGY

PWR POWER

QTY QUANTITY

(R1) RELOCATE

(R2) RELOCATED (NEW LOCATION)

RECPT RECEPTACLE

REF REFRIGERATOR

RLA RUNNING LOAD AMPS

RPM REVOLUTIONS PER MINUTE

S SOUTH

SEC SECURITY; SECOND (ARY)

SD SMOKE DETECTOR

SF SUPPLY FAN

SHT SHEET

SPEC SPECIFICATION

SPD SURGE PROTECTIVE DEVICE

SQ SQUARE

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

T THERMOSTAT

TB TERMINAL BOX

TC TIME CLOCK

TEL TELEPHONE

TV TELEVISION

TYP TYPICAL

UG UNDERGROUNDUH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UV UNIT VENTILATOR

V VOLT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VM VOLTMETER

VOL VOLUME

W WATT, WEST

W/ WITH

W/O WITHOUT

WHM WATTHOUR METER

WP WEATHERPROOF

(X) DEMOLISH

X REACTANCE

XFMR TRANSFORMER

Z IMPEDANCE

& AND

I.E.: THAT IS

I.G.: FOR EXAMPLE

# NUMBER

1. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE

OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.

2. COORDINATE ALL ELECTRICAL DEVICE LOCATIONS (SWITCHES, RECEPTACLES,

ETC.) WITH ARCHITECTURAL.

3. COORDINATE CONNECTION REQUIREMENTS FOR MECHANICAL EQUIPMENT

WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN. THIS INCLUDES, BUT IS

NOT LIMITED TO, OVER CURRENT PROTECTION, CONDUCTORS, RACEWAYS,

AND OTHER CIRCUITING EQUIPMENT REQUIRED FOR COMPLETE INSTALLATION.

MODIFY ELECTRICAL AS REQUIRED TO ACCOMMODATE, CONNECT AND

COMPLETE ALL MECHANICAL EQUIPMENT.

4. SEE MECHANICAL DRAWINGS AND SPECIFICATIONS FOR ALL INTERLOCK

WIRING REQUIREMENTS BETWEEN MOTORS, MINIMUM CONTROL WIRING SHALL

BE #14 AND MAY BE RUN IN SAME CONDUIT AS MOTOR FEEDERS.

5. PROVIDE EQUIPMENT GROUNDING CONDUCTOR (GREEN WIRE) IN ALL

RACEWAYS.

6. PROVIDE A SEPARATE NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR.

DO NOT SHARE NEUTRALS.

7. MINIMUM CONDUCTOR SIZE IS #12 AWG AND MINIMUM CONDUIT SIZE IS 1/2"C

UNLESS NOTED OTHERWISE.

8. IN GENERAL, WIRE COUNTS ARE NOT INDICATED ON PLANS. FOR EACH 20 AMP

120 VOLT OR 277 VOLT CIRCUIT, PROVIDE 1 #12 CONDUCTOR, 1 #12 NEUTRAL

CONDUCTOR, AND 1 #12 GROUNDING CONDUCTOR. ALL WORK SHALL COMPLY

WITH NEC 300-17. GROUND WIRE SHALL BE GREEN SHEATHED. WHERE WIRE

SIZES/COUNTS ARE INDICATED ON THE DRAWINGS, PROVIDE THESE CIRCUIT

CONDUCTORS (INCLUDING NEUTRAL AND GROUNDING CONDUCTORS FOR THE

PORTION OF THE CIRCUIT IN WHICH THEY SHARE A COMMON CONDUIT).

9. DO NOT COMBINE MORE THAN THREE SINGLE-PHASE CIRCUITS INTO A SINGLE

CONDUIT. IN ALL CASES OF TWO OR THREE CIRCUITS IN A SINGLE HOME RUN

CONDUIT, COMBINE CIRCUITS OF THREE DIFFERENT PHASES, CONSISTENT

WITH GENERAL NOTE 9 ABOVE. IN ALL CASES OF TWO OR THREE CIRCUITS IN A

SINGLE HOME RUN CONDUIT, THE CIRCUITS MAY SHARE A SINGLE GROUNDING

CONDUCTOR FOR THE PORTION OF THE CIRCUIT IN WHICH THEY SHARE A

COMMON CONDUIT.

10. DO NOT INSTALL ELECTRICAL BOXES IN RATED WALLS CLOSER TO EACH OTHER

THAN 2'-0". PROVIDE "PADDY" PADS OR EQUIVALENT ON EACH BOX INSTALLED.

11. SEAL ALL PENETRATIONS OF FIRE WALLS IN ACCORDANCE WITH DIVISION 1.

SEAL EXISTING PENETRATIONS OF EXISTING WALLS. SEAL PENETRATIONS OF

EXISTING WALLS MADE UNDER THIS CONTRACT. SEAL PENETRATIONS OF NEW

WALLS BY CONDUITS PROVIDED UNDER THIS CONTRACT. SEAL PENETRATIONS

OF NEW WALLS BY EXISTING CONDUITS.

12. ELECTRICAL EQUIPMENT ARRANGEMENT IN ELECTRICAL ROOM IS BASE ON ONE

MANUFACTURER. COORDINATE SPACE REQUIREMENTS WITH EQUIPMENT

SUPPLIER. MAINTAIN CLEARANCE REQUIREMENTS, AS PER NEC AND PER

EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.

13. ELECTRICAL LAYOUT DRAWINGS ARE PARTIALLY DIAGRAMMATIC. REFER TO

ARCHITECTURAL, STRUCTURAL, MECHANICAL AND HVAC DRAWINGS FOR

GUIDANCE ON DIMENSIONS, CEILING HEIGHTS, DOOR SWINGS, ROOM FINISHES,

STRUCTURAL AND ARCHITECTURAL DETAILS, LOCATIONS OF DUCTS, PIPES AND

STRUCTURAL STEEL. INSTALL THE ELECTRICAL SYSTEMS WITHOUT

INTERFERING WITH DUCTS, PIPES, STRUCTURAL STEEL OR OTHER SYSTEMS.

LOCATE LIGHTING SYMMETRICALLY IN PROPER RELATION TO FINISHED AREAS

EXCEPT WHERE DIMENSIONED ON THE DRAWINGS OR LOCATED ON

REFLECTED CEILING PLANS.

14. PROVIDE ADDITIONAL SUPPORTS FOR SWITCHES, STARTERS, RACEWAYS AND

OTHER ELECTRICAL EQUIPMENT WHERE THE BUILDING STRUCTURE IS NOT

SUITABLE FOR DIRECT MOUNTING.

15. A NUMERAL BESIDE A BRANCH CIRCUIT OUTLET ON WIRING PLANS INDICATES

PANELBOARD BRANCH CIRCUIT CONNECTION.

16. SYMBOLS IN THE LEGENDS ARE APPLICABLE GENERALLY. FOR EXACT

REQUIREMENTS REFER TO THE SCHEDULES, LAYOUTS, DETAILS AND

SPECIFICATIONS.

17. GENERATOR IS A NEC 700 EMERGENCY SYSTEM.

GENERAL NOTES SYMBOL DESCRIPTION

SYMBOLS LEGEND - POWER

SYMBOL DESCRIPTION

SYMBOLS LEGEND - RACEWAY

SYMBOL DESCRIPTION

SYMBOLS LEGEND - LIGHTING

DESCRIPTION

SYMBOLS LEGEND - SWITCHESSYMBOL

SYMBOL DESCRIPTION

SYMBOLS LEGEND - GENERAL

HEAVY LINEWEIGHT INDICATES NEW WORK

LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION

POINT OF CONNECTION (POC) BETWEEN NEW AND EXISTING

EQUIPMENT IDENTIFIER

XX = ABBREVIATION

Y = EQUIPMENT SCHEDULE NUMBER

XXXDN

DRAWING CONSTRUCTION ("FLAG") NOTE1

EQUIPMENT IDENTIFIERX-XX

MATCHLINE

REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE

THE PREVIOUS RELEASE)

REVISION REFERENCE1

DETAIL REFERENCEX

XX.XXDETAIL IDENTIFICATION NUMBER

SHEET WHERE DETAIL IS DRAWN

ELEVATION REFERENCEX

XX.XXELEVATION IDENTIFICATION NUMBER

SHEET WHERE ELEVATION IS DRAWN

NORTH REFERENCE

N

208Y/120V, 3Ø, 4W PANELBOARD

GROUND BAR

SINGLE RECEPTACLE NEMA 5-20R, +18" AFF UON

DUPLEX RECEPTACLE NEMA 5-20R, +18" AFF UON

DOUBLE DUPLEX RECEPTACLE NEMA 5-20R, +18" AFF UON

TAMPER RESISTANT RECEPTACLE NEMA 5-20R, +18" AFF UONTT

RECEPTACLE NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER, +18"

AFF UON

SPLIT WIRED DUPLEX RECEPTACLE NEMA 5-20R, +18" AFF UON

DUPLEX RECEPTACLE NEMA 5-20R, ISOLATED GROUND, +18" AFF UON

RECEPTACLE NEMA 5-20R, ABOVE COUNTER.

RECEPTACLE NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER,

ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND

ARCHITECTURAL DRAWINGS.

TAMPER RESISTANT RECEPTACLE NEMA 5-20R WITH GROUND FAULT CIRCUIT

INTERRUPTER, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP

DRAWINGS AND ARCHITECTURAL DRAWINGS.

T T

RECEPTACLE NEMA 5-20R, CONNECTED TO EMERGENCY CIRCUIT, +18" AFF UON

RECEPTACLE NEMA 5-20R MOUNTED ABOVE COUNTER. COORDINATE WITH

CASEWORK SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS.

SPECIAL PURPOSE RECEPTACLE TYPE AS SHOWN ON PLANS

SINGLE SERVICE OR COMBINATION FLUSH FLOOR POKE THRU. REFER TO

FLOOR PLANS FOR DEVICES.1

SINGLE SERVICE OR COMBINATION FLUSH MOUNTED FLOOR BOX. REFER TO

FLOOR PLANS FOR DEVICES.1

CEILING-MOUNTED DUPLEX RECEPTACLE, NEMA 5-20R

A-1,3,5

PANEL DESIGNATION

BRANCH CIRCUIT NUMBERS

INDICATES GROUNDING CONDUCTOR

INDICATES HOT CONDUCTOR

INDICATES NEUTRAL CONDUCTOR

HOMERUN

MINIMUM 3/4" CONDUIT CONCEALED IN CEILING SPACE OR IN WALL MINIMUM

3/4" WITH #12 AWG CONDUCTORS WITH DEDICATED NEUTRAL EACH

CIRCUIT, UNLESS OTHERWISE NOTED ON PLAN.

PROVIDE EQUIPMENT GROUNDING CONDUCTORS SIZED PER NFPA 70.

FLEXIBLE METAL CONDUIT

CONDUIT - CONCEALED IN OR UNDER FLOOR

CONDUIT - ROUTED UNDERGROUNDUG

LOW-VOLTAGE WIRING (CLASS B)LV

CONDUIT OR CABLE VERTICAL DOWN

CONDUIT OR CABLE VERTICAL UP

CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND

JUNCTION BOXJ

A1

a

FIXTURE TYPE DESIGNATION

SWITCH LEG DESIGNTION

NL

SHADING INDICATES LIGHT FIXTURE ON EMERGENCY CIRCUIT

OR WITH BATTERY BACKUP BALLAST

NL = NIGHT LIGHT

2x4 LIGHT FIXTURE

1x4 LIGHT FIXTURE

2x2 LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE

UNDER-CABINET LIGHT FIXTURE

LINEAR WALL WASH LIGHT FIXTURE

STRIP LIGHT FIXTURE

DOWNLIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE

WALL WASH LIGHT FIXTURE

WALL MOUNTED DIRECTIONAL LIGHT FIXTURE

DECORATIVE PENDENT LIGHT FIXTURE

NUMBER OF LIGHT FIXTURES AS SHOWN

TRACK LIGHT - LENGTH AS INDICATED ON PLANS

POLE-MOUNTED LIGHT FIXTURE

NUMBER OF FIXTURES AS SHOWN ON PLANS

IN-GROUND LANDSCAPE LIGHT FIXTURE

ILLUMINATED EXIT SIGN - SINGLE FACE

ARROW INDICATES DIRECTION OF EGRESS, UNIVERSAL MOUNT

ILLUMINATED EXIT SIGN - DOUBLE FACE

ARROW INDICATES DIRECTION OF EGRESS, UNIVERSAL MOUNT

SINGLE-POLE WALL SWITCH - MOUNT SWITCHES AT 48" AFF. TO CL, UON.

XXWALL SWITCH - MOUNT SWITCHES AT +48" AFF. TO CL, UON.

2 = 2-POLE

3 = 3-WAY4 = 4-WAY

K = KEYED

LV = LOW-VOLTAGE

OS = OCCUPANCY SENSOR TYPE

OP = OCCUPANCY/PHOTOELECTRIC TYPE

WP = WEATHERPROOF

x = LOWER CASE LETTER INDICATES SWITCHING GROUP

ANY COMBINATION OF SWITCH TYPES CAN BE USED

(IE. 3K = 3-WAY KEYED SWITCH)

DAYLIGHTING SENSORDL

OS CEILING MOUNTED OCCUPANCY SENSOR WITH POWER PACK -

PASSIVE INFRARED TYPE UNLESS NOTED

U = ULTRASONIC

DT = DUAL TECHNOLOGY

OCCUPANCY SENSOR WALL MOUNTEDOS

PHOTOELECTRIC CONTROL CEILING MOUNTEDPC

PHOTOELECTRIC CONTROL WALL MOUNTEDPC

TC TIME CLOCK - TYPE AS NOTED

RELAYR

SECTION REFERENCEX

XX.XX SECTION IDENTIFICATION NUMBER

SHEET WHERE SECTION IS DRAWN

JUNCTION BOXJ

SYMBOL DESCRIPTION

SYMBOLS LEGEND - GROUNDING

SYMBOL DESCRIPTION

SYMBOLS LEGEND - ONE-LINE DIAGRAM

GROUND CONNECTION

GROUND ROD

GROUND WELL

CB CIRCUIT BREAKER

CIRCUIT BREAKER WITH SHUNT TRIPST

CIRCUIT BREAKER WITH GROUND FAULT PROTECTIONG

FUSE

MOTOR THERMAL OVERLOADS - (3) UNLESS OTHERWISE NOTED

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

SV SOLENOID VALVE

M MOTOR-OPERATED VALVE

THERMOSTATT

TERMINAL BLOCK

BINDICATING LIGHT

A = AMBER

B = BLUE

G = GREEN

R = REDW = WHITE

TRANSFORMER

TRANSFORMER WITH GROUND

DELTA

WYE

METERM

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

POLE-MOUNTED TRANSFORMER

SYMBOL DESCRIPTION

SYMBOLS LEGEND - LIGHTING (CONT.)

208Y/120V, 1Ø, 3W LOAD CENTER

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E0.0

ELECTRICALNOTES, SYMBOLS &ABBREVIATIONS

"LCP" LIGHTING CONTROL PANEL SCHEDULE

RELAY PANEL / CIRCUIT LOAD (VA) LUMINARIE TYPE DESCRIPTION / LOCATION NOTES

R1 H1-1 140 'L-1', 'C-2' COMMON SPACES 1

R2 H1-1 65 'C-1' EXTERIOR SOFFIT 1,4

R3 H1-1 155 'L-1', 'C-2' COMMON SPACES 1

R4 H1-1 111 'C-1','C-4' EXTERIOR LIGHTING 1,4

R5 H1-1 420 'L-1', 'C-2' COMMON SPACES 1

R6 SPARE

R7 SPARE

R8 SPARE 3

R9 INV-1 142 'L-1', 'C-2' COMMON SPACES 1,2,3

R10 INV-2 201 'L-1', 'C-2' COMMON SPACES 1,2

R11 INV-2 26 'C-1' EXTERIOR LIGHTING 1,2,4

R12 INV-3 426 'L-1', 'C-2' COMMON SPACES 1,2

R13 INV-4 167 'L-4', 'C-1', 'C-5', 'C-6' ROOF TOP 1,2,4

R14 INV-5 440 'C-3' STAIRWELL 2

R15 INV-5 360 'C-3' STAIRWELL 2

R16 SPARE 2

NOTES:

1. CONFIRM SCHEDULING WITH TENANT.

2. PROVIDE UL924 RELAY TO ENERGIZE FIXTURES UPON LOSS OF NORMAL POWER.

3. PROVIDE SEPARATION BARRIER BETWEEN R8 AND R9.

4. DUSK TO DAWN OPERATIONS BY ASTRONOMICAL TIME CLOCK IN LCP. TIE INTO PHOTOCELL. REFER TO DRAWING E2.0.

INVERTOR "INV" SCHEDULE

# LOAD (VA) DESCRIPTION / LOCATION NOTES

INV-1 250 BASEMENT LEVEL EGRESS

INV-2 281 FIRST FLOOR EGRESS

INV-3 444SECOND, THIRD, FOURTH FLOOR

EGRESS

INV-4 170 ROOF EGRESS

INV-5 800 STAIRWELL EGRESS

INV-6 SPARE

TOTAL 1,945

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E0.1

LUMINIAIRE SCHEDULE

1

MDP

2

FLAG NOTES

PROVIDE (4)4" CONDUIT FROM PULL SECTION TO PGE UTILITY POLE.

POLE LOCATION TO BE DETERMINED.

COORDINATE ROUTING AND STUB LOCATION WITH STRUCTURAL.

1

2

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E1.0

SITE PLANELECTRICAL

SCALE:

N

SITE PLAN - ELECTRICAL1/4" - 1'-0"

SCALE:

BASEMENT PLAN - LIGHTING1/8" = 1'-0"

1SCALE:

FIRST FLOOR PLAN - LIGHTING1/8" = 1'-0"

2

SCALE:

SECOND,THIRD & FOURTH FLOOR PLANS - LIGHTING1/8" = 1'-0"

3SCALE:

ROOF PLAN - LIGHTING1/8" = 1'-0"

4

'C-3'

'C-3''L-1'

'L-1'

'L-1'

'L-1'

'C-2'

'C-2'

'C-2''C-2'

'C-2'

'C-3'

'C-3''L-1'

'L-1'

'L-1'

'L-1'

'C-2'

'C-2'

'C-2''C-2'

'C-2'

'C-3'

'C-3'

4

E4.0

2

E4.0

1

E4.0

2

E4.1

2

E4.0

2

E4.0

1

E4.1

3

E4.0

2

E4.1

2

E4.0

2

E4.0

1

E4.1

3

E4.1

4

E4.1

2

E4.0

'C-3'

'C-3''L-1'

'L-1'

'L-1'

'L-1'

'C-2'

'C-2'

'C-2'

'C-2'

'C-3'

'C-3'

'C-2' 'C-2'

'C-2' 'C-2' 'C-2'

'C-1'

'C-1'

'C-1'

'C-1'

'C-1'

'C-1'

'C-1'

'C-1'

'C-5'

'C-4'

'C-4'

'C-4'

'C-5'

'C-1'

'C-5'

'C-6'

'C-1'

'C-1'

'C-1'

'C-1'

'C-1'

PC

J

JJ

J

J

J

J J

J

JJ

J

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

1 TYP.

1 TYP.

1TYP.

J

J

J J

J

LCP-R9LCP-R1

H1-1

1

TYP.

X1

X1

X1

X1

J

X1

X1

X1

X1

1 TYP.

R1

R1

R1

R1

R9

R9

R9

R9

R9

LCP-R13

'L-4'

'L-4'

'L-4'

'L-4'

'L-4'

'L-4'

'L-4'

'L-4'

'L-4'

'L-4'

'L-4'

'L-4''L-4'

'L-4'

LCP-R10,R14,R15

LCP-R12

LCP-R11

1

1

1

1

1

a

b a

a

a

a

a

b

b

R14

R10

R10

R10

R10

R10

R10

R10

LCP-R3

INV-2

R3R3

R3R3

R3

R3

INV-1

R15

INV-1

INV-1

INV-1

INV-1

R14

R14

R15

R15

INV-2

INV-2

R11

R11

R4

R4

R4

R4

R4

R4

LCP-R4

LCP-R2

R2

R2

R2

R2

R2

R4

R4

R4

R14R14

R15

R15

R12

R12

R12

R12

R12

LCP-R5

R5

R5

R5

R5

2

2

'C-3'OS

R14

J 3

3

J 3

J

3

J3

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

H1-1

X1

'C-3'

R14

LCP PNL 'H1' FLAG NOTES

TIE EXTERIOR FIXTURES ON THIS FLOOR TO PHOTOCELL CONTROLS

LOCATED ON THE ROOF VIA THE LCP.

THE CIRCUIT NOTED WILL SERVE FLOORS 2 THRU 4.

EACH STAIRWELL WILL BE ON AN INDEPENDENT RELAY. REFER TO

DETAIL 2/E2.0 FOR HOMERUN AND WIRE CONFIGURATION.

1

GENERAL SHEET NOTES

1. PROVIDE UNSWITCHED HOT LEG TO ALL EXIT SIGNS.

2

3

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E2.0

FLOOR PLANS - LIGHTING

SCALE:

BASEMENT PLAN - POWER1/8" = 1'-0"

1SCALE:

FIRST FLOOR PLAN - POWER1/8" = 1'-0"

2

SCALE:

SECOND,THIRD & FOURTH FLOOR PLANS - POWER1/8" = 1'-0"

3SCALE:

ROOF PLAN - POWER1/8" = 1'-0"

4

4

E4.0

2

E4.0

1

E4.0

2

E4.1

2

E4.0

2

E4.0

1

E4.1

3

E4.0

2

E4.1

2

E4.0

2

E4.0

1

E4.1

3

E4.1

4

E4.1

LCP

MDP

PNL 'H1'

2

E4.0

WP

WP

WP

WP

WP

PNL 'H2'

HP-27 HP-06 HP-01

HP-20 HP-13

HP-21 HP-22 HP-15

HP-29 HP-08 HP-03

HP-14 HP-28

HP-02 HP-07HP-16 HP-23

HP-04 HP-09 HP-30

HP-26 HP-19

HP-31 HP-24

HP-33 HP-17

HP-10 HP-11

HP-32

HP-18 HP-25

HP-05 AC-12

EF-01

SF-01

1,3 5,7 9,11

13,15 17,19

21,23 25,27 29,3133,35 37,39 2,4 6,8 10,12

14,16 18,20

22,24 26,2830,32 34,36 38,40

43,45 47,49

51,53 55,57

59,61 63,65

67,69 71,7341

41

44,46

48,50 52,54

56,58 60,62

H2-68,70,72

H2-42

1

2"C, (4)#1/0,#6G

42

42

42

42

42

H1-2

H1-4

H1-6

H1-8

2

2

2

2

2

4

4

4

4

4

8

8

8

INVERTER 'INV'

H1-10

MH1-12,14

MM

12

14 M

H1-16

M

M

H1-18

H1-20

H2-64

2

P-3

P-2

P-1

B-02

B-01

4

H1-3

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

E

F

D

C

B

A

654321

(2)#10,#10G

M

M

FACR

ELEVATORELEVATOR CAB

LTC

3

4

FLAG NOTES

PROVIDE 6'-0" TALL UNISTRUT RACK MOUNTED TO ROOF

STRUCTURE. MOUNT PANELS TO UNISTRUT RACK.

THE CIRCUIT NOTED WILL SERVE FLOORS 2 THRU 4.

PROVIDE BUSMAN ELEVATOR MODULE. PS SERIES OR APPROVED.

ROUTING PATH FOR CONDUIT TO UNIT PLAN LOAD CENTERS FROM

THE MAIN DISTRIBUTION PANEL.

1

GENERAL SHEET NOTES

1. MINIMUM CONDUCTOR SIZE IS #12 AWG, U.O.N.

2. MINIMUM CONDUIT SIZE IS 1/2", U.O.N.

3. ALL CIRCUITS SHOWN ON ROOF TO BE CONNECTED TO PANEL 'H2', U.O.N.

MININUM CONDUCTORS SIZE ON ROOF IS #10 AWG, U.O.N.

4. PROVIDE 1/2" EMT CONDUIT FROM EACH HEAT PUMP TO ITS RESPECTIVE

FAN COIL UNIT. REFER TO MECHANICAL DRAWINGS FOR FURTHER

INFORMATION.

2

3

4

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E3.0

FLOOR PLANS - POWER

FLAG NOTES

REFER TO MANUFACTURERS INSTALLATION INSTRUCTION AND

ARCHITECTURAL ELEVATIONS FOR HOOD AND POWER MOUNTING

HEIGHTS.

1

GENERAL SHEET NOTES

1. CIRCUITS #2 AND #4 FOR EACH UNIT PANEL ARE DEDICATED TO

SMALL KITCHEN APPLIANCES PER NEC 210.52(B)(1). REFER TO E7.0

FOR UNIT PANEL SCHEDULES.

SCALE:

UNIT PLAN - STUDIO A - ELECTRICAL1/4" = 1'=0"

1 SCALE:

UNIT PLAN - STUDIO B - ELECTRICAL1/4" = 1'=0"

2

SCALE:

UNIT PLAN - STUDIO C - ELECTRICAL1/4" = 1'=0"

3

SCALE:

UNIT PLAN - STUDIO D - ELECTRICAL1/4" = 1'=0"

4

DW OVHD RF

WS

DR

DW

OV

HD

RF

WS

DR

APPLIANCE\EQUIPMENT LEGEND

DISHWASHER

OVEN

HOOD

REFRIGERATOR

CLOTHES WASHER

CLOTHES DRYER

MOUNTING HEIGHT

+18" AFF

+18" AFF

DW

OV HD

RF

WS DR

OV HD

WS

DR

DW

RF

+48" AFF

+18" AFF

+18" AFF

PNL

PNL

PNL

PNL

DWOV HD

RF

WS

DR

'L-1'

'L-2''L-2'

'L-1''L-1'

'L-1' 'L-1'

'L-1'

EF'L-1'

'L-5'

'L-3' 'L-3'

'L-1''L-2''L-2'

ab

a

bb

b b

ccc

c c

d

d e

e

e

'L-1''L-1'

'L-1' 'L-1'

EF'L-1'

'L-5'

'L-3''L-3'

a

ab

bb

cc

c c

c

bb

d ed

d

e

'L-3'b

'L-3'

'L-3'

b

b'L-2'

b

'L-2'

b

'L-1'

a

'L-1'

a

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

d

EF

a

bc

dd

e

e

'L-1'

c

'L-1'

a

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

a

'L-2'

b

'L-2'

b

a

bc

EF

e

'L-1'

d

'L-3'

b

'L-3'

b

'L-5'

'L-5'd

d e

1

EF EXHAUST FAN

'L-4'

'L-2'

f

f

g

'L-4'

f

f

'L-4'

g

g

'L-4'

gg

CEILING

UH-01

UH-02

e

g

g

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E4.0

ENLARGED PLANS-POWER

SCALE:

UNIT PLAN - 1 BED A - ELECTRICAL1/4" = 1'=0"

1SCALE:

UNIT PLAN - 1 BED B - ELECTRICAL1/4" = 1'=0"

2

SCALE:

UNIT PLAN - 1 BED C - ELECTRICAL1/4" = 1'=0"

3SCALE:

UNIT PLAN - 1 BED D - ELECTRICAL1/4" = 1'=0"

4

DW

OV

HD

RF

WS

DR

DISHWASHER

OVEN

HOOD

REFRIGERATOR

CLOTHES WASHER

CLOTHES DRYER

MOUNTING HEIGHT

+18" AFF

+18" AFF

DW

OV HDRFWS DR

DW

OVHDRF

WS DR

DW

OV

HD

RF

WS

DR

DW

OV

HD

RF

WS

DR

+48" AFF

+18" AFF

+18" AFF

PNL

PNL

PNL

PNL

'L-1'

a

a

'L-2'

b

'L-2'

b

'L-2'

b

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

d

'L-1'

d

b

'L-1'

e

e

e

EF

f

'L-3''L-3'

bb

f

dc

'L-1'

a

'L-1'

a

'L-1'

a

'L-2'

b

'L-2'

b

'L-2'

b

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

c

'L-1'

d

a

b c

dde

EF

e

'L-3''L-3'

b

'L-3'

b b

'L-1'

a

'L-1'

a

'L-2'

b

'L-2'

b

'L-1'

c

'L-1'

c

'L-3'

b

'L-3'

b

'L-1'

d

EF

e

a

d

de

1

'L-1'

a

'L-1'

a

'L-1'

a'L-1'

d

EF

e

'L-2'

b

'L-2'

b

'L-1'

c

'L-1'

c

a

b c

d

d

e

EF EXHAUST FAN

'L-3'

b

'L-3'

b

'L-1'

a

'L-2'

f

f

APPLIANCE\EQUIPMENT LEGEND

'L-2'

g

g

'L-2'

f

f

'L-4'

gg

'L-2'

f

CEILING

'L-5'

'L-5'

'L-5''L-5'

'L-2'

h

h

FLAG NOTES

REFER TO MANUFACTURERS INSTALLATION INSTRUCTION AND

ARCHITECTURAL ELEVATIONS FOR HOOD AND POWER MOUNTING

HEIGHTS.

1

GENERAL SHEET NOTES

1. CIRCUITS #2 AND #4 FOR EACH UNIT PANEL ARE DEDICATED TO

SMALL KITCHEN APPLIANCES PER NEC 210.52(B)(1). REFER TO E7.0

FOR UNIT PANEL SCHEDULES.

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E4.1

ENLARGED PLANS-POWER

FEEDER SCHEDULE - LOW VOLTAGE

(600V)

FDR WIRE AND CONDUIT SIZE

(3) #2, (1) #8 GND, 1-1/4"C1003

(4) #2, (1) #8 GND, 1-1/2" C1004

FLAG NOTES#4 AWG CU CONDUCTOR TO CONCRETE ENCASED ELECTRODE PER

NEC 250-52 (A)(3). SEE DETAIL 1/E7.0.

#1/0 AWG CU CONDUCTOR TO INTERIOR METAL PIPING SYSTEM PER

NEC 250-104.

#6 AWG CU CONDUCTOR TO GROUNDING ELECTRODE SYSTEM

(GROUND ROD) PER NEC 250-52 (A)(5).

#1/0 AWG CU EQUIPMENT BONDING JUMPER PER NEC 250-102.

#1/0 AWG CU MAIN BONDING JUMPER PER NEC 250.28.

1

2

3

4

5

M

PANEL H1

1003

L.C.

STUDIOA

100/3

100/2

NG

1-1/4" EC

BASEMENT

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

FOURTH FLOOR

1003 1003 1003

1003 1003 1003 1003 1003

1003 1003 1003 1003 1003 1003

1003 1003 1003 1003 1003 1003

1003 1003 1003 1003 1003 1003

100/2 100/2 100/2

100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2 100/2

MDP

1200A, 208/120V, 3Ø, 4W

ROOF

400/31200/3

4004

PANEL H2 SECT. 2

(4) #500 KCM, (1) #3 GND, 3-1/2"C4004

12004

L.C.

STUDIOB

L.C.

STUDIOB

L.C.

STUDIOD

L.C.

1 BDRMA

L.C.

1 BDRMB

L.C.

STUDIOB

L.C.

STUDIOB

L.C.

STUDIOC

L.C.

1 BDRMA

L.C.

1 BDRMB

L.C.

1 BDRMC

L.C.

1 BDRMD

L.C.

STUDIOB

L.C.

STUDIOB

L.C.

1 BDRMA

L.C.

1 BDRMB

L.C.

1 BDRMC

L.C.

1 BDRMD

L.C.

STUDIOB

L.C.

STUDIOB

L.C.

1 BDRMA

L.C.

1 BDRMB

L.C.

1 BDRMC

L.C.

1 BDRMD

L.C.

STUDIOB

L.C.

STUDIOB

4

5

32

1

GENERAL SHEET NOTES1. LOAD CENTERS WILL BE INSTALLED IN STUDIO AND ONE

BEDROOM UNITS.

1004

4 SETS, (4) #350 KCM, (1) #3/0 GND, 3"C12004

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E5.0

ONE-LINEDIAGRAM

SCALE:

ONE-LINE DIAGRAMNTS

1

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E6.0

PANEL SCHEDULE

FLAG NOTES

UNIT HEATERS ONLY INSTALLED ON SELECT STUDIO UNITS. REFER TO

DRAWING E4.0 FOR UNIT TYPES.

1

1

STEEL REINFORCING BAR (REBAR) .

LESS THAN \'' IN DIAMETER .

WITH A MINIMUM OF 2'' CONCRETE .

ELECTRODE/REBAR SHALL BE

ELECTRODE/REBAR TO BE NOT

INSTALL PER NEC 250.

CONCRETE FOUNDATION IN CONTACT DIRECTLY WITH

CONCRETE FOUNDATION AND ENCASEDLOCATED NEAR THE BOTTOM OF THE

THE EARTH .

AREA MIN.12'' TIE

TO MAIN SERVICE GROUND BAR.

ELECTRODE OR TIE TO 40' OF

CONDUCTOR. EXOTHERMIC WELD AT ALL SPLICES.#4 AWG , BARE , CU GROUNDING ELECTRODE

NON-METALIC PROTECTIVE SLEEVE.

40' OF BARE OR ZINC GALVANIZED

ELECTRICALLY CONDUCTIVE COATED

EXTEND 1/2-INCH (MIN) REINFORCING BAR OR ROD UPAT 12-INCHES ABOVE FLOOR LEVEL, PER OREGONAMENDENTS TO NATIONAL ELECTRIC CODE.

EXOTHERMIC WELD (TYP.)

SCALE:

CONCRETE ENCASED ELECTRODENTS

1

NOTE: COORDINATE PROGRAMING OF LIGHTING CONTROL PANEL WITH OWNER,

DRAWINGS AND SCHEDULE (TYP.)LOW VOLTAGE SWITCHES AS INDICATED ON

PHOTO - ELECTRIC SWITCH TO BE USED AS INPUT TO THE LIGHTING CONTROL PANEL

LV INPUTS

PANEL'SCPU/CLOCK

LIGHTING CONTROL PANEL'LCPA'

R1

R3

R5

R4

R2

R8

R7

R6

P

R10

R12

R11

R9

R15

R14

R13

R16

SCALE:

LIGHTING CONTROL PANELNTS

2

DATE:

JOB NO:

SEPTEMBER 18, 2015

150150

REVISIONS:

PERMIT

REVIEW

A12

AP

AR

TM

EN

TS

120

6 S

E A

NK

EN

Y S

T

PO

RTLA

ND

, O

R 9

7214

123 NW 2ND AVE SUITE 204 - PORTLAND, OR 97209

T: 971.888.5107 - E-MAIL: [email protected]

architects

A

C YBA ARCHITECTS - THESE DRAWINGS ARE THE PROPERTY OF YBA

ARCHITECTS AND ARE NOT TO BE REPRODUCED IN ANY MANNER,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF YBA ARCHITECTS.

111 SW Fifth Ave. Ste. 2120

Portland, Oregon 97204

Tel 503.416.2400

Fax 206.267.1701SAZAN # 507-1501

E7.0

ELECTRICALDETAILS