UPS A3 & A5 Quick Guide User’s Manual
UPS A3&A5 QUICK GUIDE
Copyright AST 2010 www.ast-global.com
1. Table 1 Safety Symbols and Means
Safety Symbols Means
Secure alarm
Risk of electric shock
2. Table 2 UPS Main Performance Index
Model
Index A5 A3
Rating voltage (V) In range 120V~290V, 50% load,in range 160V~290V, full load
Rating frequency (Hz) 50/60 ±10%
Input mode Single-phase three-line Inpu
t
char
acte
ristic
Battery voltage (V) 192
Capacity (VA/W) 5000/3500 3000/2100
Voltage (V) 230±1%
Frequency (Hz) 50/60Hz (Battery mode) Out
put
Cha
ract
eris
tic
Waveform Sine wave
Overload capacity 105%~129% Load, lasting 60 seconds , or 130%~150% Load, lasting 30
seconds turn to BYPASS
Out
put
Cha
ract
eris
tic
Output mode Line bar
Panel display LED
Warning function Battery low voltage, abnormal power supply, UPS malfunction, overload
Protection function Battery low voltage protection, overload protection, short-circuit protection and
over temperature protection, over voltage protection
Working temperature -20 ~ 40℃
Relative humidity 0 ~ 95%,No condensation
A3/A5: 440×700×130 Size (mm) (W×D× H)
External Battery Cabinet: : 440×460×176
A3/A5: 17.5
Oth
er C
hara
cter
istic
s
Weight (kg) External Battery Cabinet: : 55.5(including BAT. 7Ah,16 PCS)
3. Panel Indicator
Illuminate:
①、BYPASS Indicator light
②、Mains supply Indicator light
③、INVERTER Indicator light
④、Capacity indicator of load (contain four lights, each
Standing for 25% of total capacity.)
LINE INV. LOAD
BYPASS
100%100%
BAT.FAULT
①
② ③ ④
⑤ ⑥
⑦ ⑧POWER
OFFON/TEST
UPS A3&A5 QUICK GUIDE
Copyright AST 2010 www.ast-global.com
⑤、Capacity indicator of Battery Indicator light (contain four
lights,each standing for 25% of total capacity.)
⑥、FAULT Indicator light
⑦、“ON/TEST” Key
START UPS (Please press the “ON” key for 0.5 seconds to run the UPS.)
⑧、“OFF” Key (Please press the “OFF” key for 0.5 second to turn off the
UPS.)
Press “ON/TEST” for 3 seconds to make the buzzer quiet on battery mode, while power on.
4. Rear Panel
AC OUTPUT 16A MAX.AC OUTPUT 10A MAX.
USB RS232 EPO DRY CONTACTDIP SWITCH
DC INPUT192V/12.4A
1
3 245689 7 AC INPUT 230V/20.6AL N PE
AC INPUT 230V/20.6AL N PE
Fuse 250V/15A
Fuse 250V/15A
Fuse 250V/10A
Fig .1 A5 Rear Panel
1. Output Socket 2. Terminal for DC Input 3. Output fuse 4. Terminal for AC Input 5. Dry contact
6. Dip switch 7. EPO 8. RS232 9. USB
AC OUTPUT 16A MAX.AC OUTPUT 10A MAX.
USB RS232 EPO DRY CONTACTDIP SWITCH
DC INPUT192V/12.4A
1
3 24AC INPUT 230V/12A
5689 7
Fuse 250V/15A
Fuse 250V/15A
Fuse 250V/10A
Fig.2 A3 Rear Panel
1. Output Socket 2. Terminal for DC Input 3. Output fuse 4. Socket for AC Input 5. Dry Contact 6. Dip switch 7. EPO 8. RS232 9. USB
UPS A3&A5 QUICK GUIDE
Copyright AST 2010 www.ast-global.com
Fig. 3 A5 Connection Schematic
AC OUTPUT 16A MAX.AC OUTPUT 10A MAX.
USB RS232 EPO DRY CONTACTDIP SWICH
DC INPUT192V/12.4A
AC INPUT 230V/13.8A
Share alike!
Socketsoutput to load
Commercialpower input
DC Input192V
Fuse 250V/15A
Fuse 250V/10A
Fig. 4 A3 Connection Schematic
UPS A3&A5 QUICK GUIDE
Copyright AST 2010 www.ast-global.com
5. Preparations before First Start-up
To ensure normal operation of UPS, please confirm the following before use:
A. Correct installation of input and output.
B. If supply terminals connect to the rated power. .
C. Confirm that UPS output does not short circuit and the load capacity does not exceed UPS capacity.
D. Confirm if computer or other instrument is turned off.
E. Confirm if battery voltage is normal.
F. It is not recommended to connect reactive load to the UPS output. Loads are normally powered by electric network directly.
6. UPS Start-up Sequence
After confirming all the above, please start the machine by following means:
A. Press the "ON/TEST" button on the UPS panel to start UPS, the "INV." indicator light will light up. After retardation time, the
"BYPASS" light goes out and the UPS is changed inverter power supply. By this time, the start-up is completed and the
equipment starts operation. Wait for about 20 seconds after normal no-load operation to turn on the computer or other
instrument. Start the load in the sequence of high-power to low power, first start the high-power equipment then in turns start
equipment with lower power.
B. Start computer or other equipment.
7. Daily Start-up and Shutdown
During daily operation, operate as per the following for start-up or shut down:
A. Press the "ON/TEST" button on the UPS panel to start UPS, after 10 seconds, turn on the computer or other instrument.
B. Normally, only when the UPS has been started and is working stably, can the loading equipment power switch be turned on. First
turn on high-power equipment, then the equipment with lower power. Some equipment has large start current (such as monitors of
some brands). When starting such equipment, overload protection (such as bypass operation) may occur. In this case, it's
recommended to start this type of equipment before other equipment.
Before shutdown, turn off the computer and other instrument first and perform no-load operation of UPS for 10 minutes. After the heat
in the equipment has been discharged, press the "OFF" button on the panel.
8. Maintenance Guide
Proper maintenance includes preventive maintenance and remedial maintenance, which is crucial to optimum operation of UPS and
can ensure relatively long service life of the equipment. Preventive maintenance includes some procedures that are frequently
performed. These procedures are used to prevent system failure as well as to obtain best operating efficiency. Remedial
maintenance includes searching for system malfunction to facilitate effective repair.
9. Safety Precaution In order to securely and successfully conduct system maintenance, relevant safety precautions must be observed and necessary
tools and testing equipment must be used, with the participation of qualified maintenance personnel. Pay attention to the following
safety operation rules:
A. Bear in mind that the equipment contains lethal voltage even if the system is not in operation.
B. Servicing should be performed by qualified service personnel with knowledge of the UPS and required precautions. Keep
unauthorized personnel away from the equipment.
10. When operating UPS, do not wear gold or silver jewelry such as ring or watch, etc.
11. Do not take the safety operation procedure for granted. If there is any doubt, consult personnel who are familiar with
the equipment. Be cautious that there is dangerous voltage in UPS. Before maintenance and adjustment, use voltmeter to check and ensure that the power is turned off and the equipment is under safe condition.