UPS A3&A5 QUICK GUIDE

Copyright AST 2010 www.ast-global.com

 

UPS A3 & A5 Quick Guide User’s Manual

Page 2: A3 A5 Quick Guide

UPS A3&A5 QUICK GUIDE

Copyright AST 2010 www.ast-global.com

1. Table 1 Safety Symbols and Means

Safety Symbols Means

Secure alarm

Risk of electric shock

2. Table 2 UPS Main Performance Index

Model

Index A5 A3

Rating voltage (V) In range 120V~290V, 50% load,in range 160V~290V, full load

Rating frequency (Hz) 50/60 ±10%

Input mode Single-phase three-line Inpu

t

char

acte

ristic

Battery voltage (V) 192

Capacity (VA/W) 5000/3500 3000/2100

Voltage (V) 230±1%

Frequency (Hz) 50/60Hz (Battery mode) Out

put

Cha

ract

eris

tic

Waveform Sine wave

Overload capacity 105%~129% Load, lasting 60 seconds , or 130%~150% Load, lasting 30

seconds turn to BYPASS

Out

put

Cha

ract

eris

tic

Output mode Line bar

Panel display LED

Warning function Battery low voltage, abnormal power supply, UPS malfunction, overload

Protection function Battery low voltage protection, overload protection, short-circuit protection and

over temperature protection, over voltage protection

Working temperature -20 ~ 40℃

Relative humidity 0 ~ 95%,No condensation

A3/A5: 440×700×130 Size (mm) (W×D× H)

External Battery Cabinet: : 440×460×176

A3/A5: 17.5

Oth

er C

hara

cter

istic

s

Weight (kg) External Battery Cabinet: : 55.5(including BAT. 7Ah,16 PCS)

3. Panel Indicator

Illuminate:

①、BYPASS Indicator light

②、Mains supply Indicator light

③、INVERTER Indicator light

④、Capacity indicator of load (contain four lights, each

Standing for 25% of total capacity.)

LINE INV. LOAD

BYPASS

100%100%

BAT.FAULT

② ③ ④

⑤ ⑥

⑦ ⑧POWER

OFFON/TEST

Page 3: A3 A5 Quick Guide

UPS A3&A5 QUICK GUIDE

Copyright AST 2010 www.ast-global.com

⑤、Capacity indicator of Battery Indicator light (contain four

lights,each standing for 25% of total capacity.)

⑥、FAULT Indicator light

⑦、“ON/TEST” Key

START UPS (Please press the “ON” key for 0.5 seconds to run the UPS.)

⑧、“OFF” Key (Please press the “OFF” key for 0.5 second to turn off the

UPS.)

Press “ON/TEST” for 3 seconds to make the buzzer quiet on battery mode, while power on.

4. Rear Panel

AC OUTPUT 16A MAX.AC OUTPUT 10A MAX.

USB RS232 EPO DRY CONTACTDIP SWITCH

DC INPUT192V/12.4A

1

3 245689 7 AC INPUT 230V/20.6AL N PE

AC INPUT 230V/20.6AL N PE

Fuse 250V/15A

Fuse 250V/15A

Fuse 250V/10A

Fig .1 A5 Rear Panel

1. Output Socket 2. Terminal for DC Input 3. Output fuse 4. Terminal for AC Input 5. Dry contact

6. Dip switch 7. EPO 8. RS232 9. USB

AC OUTPUT 16A MAX.AC OUTPUT 10A MAX.

USB RS232 EPO DRY CONTACTDIP SWITCH

DC INPUT192V/12.4A

1

3 24AC INPUT 230V/12A

5689 7

Fuse 250V/15A

Fuse 250V/15A

Fuse 250V/10A

Fig.2 A3 Rear Panel

1. Output Socket 2. Terminal for DC Input 3. Output fuse 4. Socket for AC Input 5. Dry Contact 6. Dip switch 7. EPO 8. RS232 9. USB

Page 4: A3 A5 Quick Guide

UPS A3&A5 QUICK GUIDE

Copyright AST 2010 www.ast-global.com

Fig. 3 A5 Connection Schematic

AC OUTPUT 16A MAX.AC OUTPUT 10A MAX.

USB RS232 EPO DRY CONTACTDIP SWICH

DC INPUT192V/12.4A

AC INPUT 230V/13.8A

Share alike!

Socketsoutput to load

Commercialpower input

DC Input192V

Fuse 250V/15A

Fuse 250V/10A

Fig. 4 A3 Connection Schematic

Page 5: A3 A5 Quick Guide

UPS A3&A5 QUICK GUIDE

Copyright AST 2010 www.ast-global.com

5. Preparations before First Start-up

To ensure normal operation of UPS, please confirm the following before use:

A. Correct installation of input and output.

B. If supply terminals connect to the rated power. .

C. Confirm that UPS output does not short circuit and the load capacity does not exceed UPS capacity.

D. Confirm if computer or other instrument is turned off.

E. Confirm if battery voltage is normal.

F. It is not recommended to connect reactive load to the UPS output. Loads are normally powered by electric network directly.

6. UPS Start-up Sequence

After confirming all the above, please start the machine by following means:

A. Press the "ON/TEST" button on the UPS panel to start UPS, the "INV." indicator light will light up. After retardation time, the

"BYPASS" light goes out and the UPS is changed inverter power supply. By this time, the start-up is completed and the

equipment starts operation. Wait for about 20 seconds after normal no-load operation to turn on the computer or other

instrument. Start the load in the sequence of high-power to low power, first start the high-power equipment then in turns start

equipment with lower power.

B. Start computer or other equipment.

7. Daily Start-up and Shutdown

During daily operation, operate as per the following for start-up or shut down:

A. Press the "ON/TEST" button on the UPS panel to start UPS, after 10 seconds, turn on the computer or other instrument.

B. Normally, only when the UPS has been started and is working stably, can the loading equipment power switch be turned on. First

turn on high-power equipment, then the equipment with lower power. Some equipment has large start current (such as monitors of

some brands). When starting such equipment, overload protection (such as bypass operation) may occur. In this case, it's

recommended to start this type of equipment before other equipment.

Before shutdown, turn off the computer and other instrument first and perform no-load operation of UPS for 10 minutes. After the heat

in the equipment has been discharged, press the "OFF" button on the panel.

8. Maintenance Guide

Proper maintenance includes preventive maintenance and remedial maintenance, which is crucial to optimum operation of UPS and

can ensure relatively long service life of the equipment. Preventive maintenance includes some procedures that are frequently

performed. These procedures are used to prevent system failure as well as to obtain best operating efficiency. Remedial

maintenance includes searching for system malfunction to facilitate effective repair.

9. Safety Precaution In order to securely and successfully conduct system maintenance, relevant safety precautions must be observed and necessary

tools and testing equipment must be used, with the participation of qualified maintenance personnel. Pay attention to the following

safety operation rules:

A. Bear in mind that the equipment contains lethal voltage even if the system is not in operation.

B. Servicing should be performed by qualified service personnel with knowledge of the UPS and required precautions. Keep

unauthorized personnel away from the equipment.

10. When operating UPS, do not wear gold or silver jewelry such as ring or watch, etc.

11. Do not take the safety operation procedure for granted. If there is any doubt, consult personnel who are familiar with

the equipment. Be cautious that there is dangerous voltage in UPS. Before maintenance and adjustment, use voltmeter to check and ensure that the power is turned off and the equipment is under safe condition.