The curves in this Application Data are to be used in conjunction with Application Data 29-160. Curves for standard and MARK 75 ® breakers have been combined on the same sheet. To locate curves for particular breakers, refer to the index at right. Breaker Description Curve No. Page Types EB, EHB; MARK 75 Type HFB; 15-40 Amperes, 1 Pole ................ SC-3506-77 3 Types EB, EHB; MARK 75 Type HFB; 50-70 Amperes, 1 Pole ................ SC-3507-77 4 Types EB, EHB; MARK 75 Type HFB; 90-100 Amperes, 1 Pole .............. SC-3508-77 5 Types EB, EHB, FB; MARK 75 Type HFB; 15-40 Amperes, 2, 3 Poles ... SC-3509-77 6 Types EB, EHB, FB; MARK 75 Type HFB; 50-70 Amperes, 2, 3 Poles ... SC-3510-77 7 Types EB, EHB; 90-100 Amperes, 2, 3 Poles ............................................ SC-3511-77 8 Type FB; MARK 75 Type HFB; 90-150 Amperes, 2, 3 Poles ................... SC-3511-77 8 Type FB Magnetic Only with Current Limiter; 3-150 Amperes, 3 Poles SC-3513-77 9 LFB Current Limiter for Type FB, 3 Pole, Thermal Magnetic Breakers . SC-3512-77A 10 Types JB, KB; MARK 75 Type HKB; 70-250 Amperes, 2, 3 Poles .......... SC-4009-77 11 Types JA, KA; MARK 75 Type HKA; 70-225 Amperes, 2, 3 Poles .......... SC-3514-77 12 Types CA, CAH, HCA; 125-225 Amperes, 2, 3 Poles ............................... SC-3504-77A 12.1 Type DA, 250-400 Amperes, 2, 3 Poles .................................................... SC-3505-77 13 Types LBB, LB; MARK 75 Type HLB; 70-400 Amperes, 2, 3 Poles ......... SC-3516-77 14 Types LAB, LA; MARK 75 Type HLA; 125-400 Amperes, 2, 3 Poles ...... SC-3515-77 15 Type LA, MARK 75 Type HLA; 250-600 Amperes, 2, 3 Poles ................. SC-3517-77 16 Type MA, MARK 75 Type HMA; 125-600 Amperes, 2, 3 Poles .............. SC-3521-77 17 Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles .............. SC-3522-77 18 Type NB, MARK 75 Type HNB; 800-1200 Amperes, 2, 3 Poles .............. SC-3524-77 19 Type PB, 600-1600 Amperes, 2, 3 Poles ................................................... SC-3527-77 20 Type PB, 1800-3000 Amperes, 2, 3 Poles ................................................. SC-3528-77 21 Types LC, LCG; MARK 75 Types HLC, HLCG; 75-150 Amperes, 2-3 Poles .................................................................................................... SC-3600-81A 22 Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 75-150 Amperes, 2-3 Poles .................................................................................................... SC-3612-81A 23 Types LC, LCG; MARK 75 Types HLC, HLCG; 150-300 Amperes, 2-3 Poles .................................................................................................... SC-3601-81A 24 Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 150-300 Amperes, 2-3 Poles .................................................................................................... SC-3613-81A 25 Types LC, LCG; MARK 75 Types HLC, HLCG; 200-400 Amperes, 2-3 Poles .................................................................................................... SC-3611-81A 26 Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 200-400 Amperes, 2-3 Poles .................................................................................................... SC-3623-81 27 Types LC, LCG; MARK 75 Types HLC, HLCG; 300-600 Amperes, 2-3 Poles .................................................................................................... SC-3602-81A 28 Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 300-600 Amperes, 2-3 Poles .................................................................................................... SC-3614-81A 29 Types LCG, LCGA, HLCG, HLCGA Ground Fault Pick-up Curves .......... SC-3603-81 30 Type LCLG 250 Ground Fault Pick-up Curves ......................................... SC-4122-87 31 Type LCLG 400 Ground Fault Pick-up Curves ......................................... SC-4123-87 32 Type LCG 150 Ground Fault Pick-up Curves ........................................... SC-4124-87 33 Type LCG 300 Ground Fault Pick-up Curves ........................................... SC-4125-87 34 Type LCG 400 Ground Fault Pick-up Curves ........................................... SC-4126-87 35 Type LCG 600 Ground Fault Pick-up Curves ........................................... SC-4127-87 36 Types MCA, MCGA; MARK 75 Types HMCA, HMCGA; 400-800 Amperes, 2-3 Poles ................................................................... SC-3616-81A 37 Types MC, MCG; MARK 75 Types HMC, HMCG; 400-800 Amperes, 2-3 Poles .................................................................................................... SC-3604-81A 38 Types MCG, MCGA, HMCG, HMCGA; NCG, NCGA, HNCG, HNCGA Ground Fault Pick-up Curves ................................................... SC-3606-81 39 Type MCG 800 Ground Fault Pick-up Curves .......................................... SC-4128-87 40 Types NCA, NCGA; MARK 75 Types HNCA, HNCGA; 800-1200 Amperes, 2-3 Poles ................................................................. SC-3617-81A 41 Types NC, NCG; MARK 75 Types HNC, HNCG; 800-1200 Amperes, 2-3 Poles .................................................................................................... SC-3605-81A 42 Type NCG 1200 Ground Fault Pick-up Curves ......................................... SC-4129-87 43 AB DE-ION ® Circuit Breakers April 1998 Application Data 29-168 Page 1

Upload: phamkhuong

Post on 29-May-2018

227 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

The curves in this Application Data are tobe used in conjunction with ApplicationData 29-160. Curves for standard andMARK 75® breakers have been combinedon the same sheet.

To locate curves for particular breakers,refer to the index at right.

Breaker Description Curve No. Page

Types EB, EHB; MARK 75 Type HFB; 15-40 Amperes, 1 Pole ................ SC-3506-77 3Types EB, EHB; MARK 75 Type HFB; 50-70 Amperes, 1 Pole ................ SC-3507-77 4Types EB, EHB; MARK 75 Type HFB; 90-100 Amperes, 1 Pole .............. SC-3508-77 5Types EB, EHB, FB; MARK 75 Type HFB; 15-40 Amperes, 2, 3 Poles ... SC-3509-77 6Types EB, EHB, FB; MARK 75 Type HFB; 50-70 Amperes, 2, 3 Poles ... SC-3510-77 7Types EB, EHB; 90-100 Amperes, 2, 3 Poles ............................................ SC-3511-77 8Type FB; MARK 75 Type HFB; 90-150 Amperes, 2, 3 Poles ................... SC-3511-77 8Type FB Magnetic Only with Current Limiter; 3-150 Amperes, 3 Poles SC-3513-77 9LFB Current Limiter for Type FB, 3 Pole, Thermal Magnetic Breakers . SC-3512-77A 10Types JB, KB; MARK 75 Type HKB; 70-250 Amperes, 2, 3 Poles .......... SC-4009-77 11Types JA, KA; MARK 75 Type HKA; 70-225 Amperes, 2, 3 Poles .......... SC-3514-77 12Types CA, CAH, HCA; 125-225 Amperes, 2, 3 Poles ............................... SC-3504-77A 12.1Type DA, 250-400 Amperes, 2, 3 Poles .................................................... SC-3505-77 13Types LBB, LB; MARK 75 Type HLB; 70-400 Amperes, 2, 3 Poles ......... SC-3516-77 14Types LAB, LA; MARK 75 Type HLA; 125-400 Amperes, 2, 3 Poles ...... SC-3515-77 15Type LA, MARK 75 Type HLA; 250-600 Amperes, 2, 3 Poles ................. SC-3517-77 16Type MA, MARK 75 Type HMA; 125-600 Amperes, 2, 3 Poles .............. SC-3521-77 17Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles .............. SC-3522-77 18Type NB, MARK 75 Type HNB; 800-1200 Amperes, 2, 3 Poles .............. SC-3524-77 19Type PB, 600-1600 Amperes, 2, 3 Poles ................................................... SC-3527-77 20Type PB, 1800-3000 Amperes, 2, 3 Poles ................................................. SC-3528-77 21Types LC, LCG; MARK 75 Types HLC, HLCG; 75-150 Amperes,

2-3 Poles .................................................................................................... SC-3600-81A 22Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 75-150 Amperes,

2-3 Poles .................................................................................................... SC-3612-81A 23Types LC, LCG; MARK 75 Types HLC, HLCG; 150-300 Amperes,

2-3 Poles .................................................................................................... SC-3601-81A 24Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 150-300 Amperes,

2-3 Poles .................................................................................................... SC-3613-81A 25Types LC, LCG; MARK 75 Types HLC, HLCG; 200-400 Amperes,

2-3 Poles .................................................................................................... SC-3611-81A 26Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 200-400 Amperes,

2-3 Poles .................................................................................................... SC-3623-81 27Types LC, LCG; MARK 75 Types HLC, HLCG; 300-600 Amperes,

2-3 Poles .................................................................................................... SC-3602-81A 28Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 300-600 Amperes,

2-3 Poles .................................................................................................... SC-3614-81A 29Types LCG, LCGA, HLCG, HLCGA Ground Fault Pick-up Curves .......... SC-3603-81 30Type LCLG 250 Ground Fault Pick-up Curves ......................................... SC-4122-87 31Type LCLG 400 Ground Fault Pick-up Curves ......................................... SC-4123-87 32Type LCG 150 Ground Fault Pick-up Curves ........................................... SC-4124-87 33Type LCG 300 Ground Fault Pick-up Curves ........................................... SC-4125-87 34Type LCG 400 Ground Fault Pick-up Curves ........................................... SC-4126-87 35Type LCG 600 Ground Fault Pick-up Curves ........................................... SC-4127-87 36Types MCA, MCGA; MARK 75 Types HMCA, HMCGA;

400-800 Amperes, 2-3 Poles ................................................................... SC-3616-81A 37Types MC, MCG; MARK 75 Types HMC, HMCG; 400-800 Amperes,

2-3 Poles .................................................................................................... SC-3604-81A 38Types MCG, MCGA, HMCG, HMCGA; NCG, NCGA, HNCG,

HNCGA Ground Fault Pick-up Curves ................................................... SC-3606-81 39Type MCG 800 Ground Fault Pick-up Curves .......................................... SC-4128-87 40Types NCA, NCGA; MARK 75 Types HNCA, HNCGA;

800-1200 Amperes, 2-3 Poles ................................................................. SC-3617-81A 41Types NC, NCG; MARK 75 Types HNC, HNCG; 800-1200 Amperes,

2-3 Poles .................................................................................................... SC-3605-81A 42Type NCG 1200 Ground Fault Pick-up Curves ......................................... SC-4129-87 43

AB DE-ION ®

Circuit BreakersApril 1998

Application Data29-168

Page 1

Page 2: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 2

Types PC, PCC, PCG, PCCG, PCF, PCCF, PCFG, PCCFG;1000-2000 Amperes, 2-3 Poles ............................................................... SC-3607-81A 44

Types PCA, PCCA, PCGA, PCCGA, PCFA, PCCFA, PCFGA, PCCFGA;1000-2000 Amperes, 2-3 Poles ............................................................... SC-3619-81A 45

Types PC, PCC, PCG, PCCG, PCF, PCCF, PCFG, PCCFG;1400-2500 Amperes, 2-3 Poles ............................................................... SC-3608-81A 46

Types PCA, PCCA, PCGA, PCCGA, PCFA, PCCFA, PCFGA, PCCFGA;1400-2500 Amperes, 2-3 Poles ............................................................... SC-3620-81A 47

Types PC, PCC, PCG, PCCG; 1600-3000 Amperes, 2-3 Poles ................. SC-3609-81A 48Types PCA, PCCA, PCGA, PCCGA; 1600-3000 Amperes, 2-3 Poles ....... SC-3621-81A 49Types PCG, PCGA, PCCG, PCCGA, PCFG, PCFGA, PCCFG, PCCFGA

Ground Fault Pick-up Curves .................................................................. SC-3610-81 50MCP Motor Circuit Protector, 3-150 Amperes, 600 Volts AC,

with Current Limiter Attachment ........................................................... SC-3505-76 51MCP Motor Circuit Protector, 250 and 400 Amperes, 600 Volts AC ..... SC-3637-76 52

Individual oversize copies of curves listed above printed on onion-skin paper are availablein limited quantity from:

Cutler-HammerCustomer Support CenterFive Parkway CenterPittsburgh, PA 15220

When ordering onion-skin curves, use number at bottom of page where curve appears,i.e., SC-3506-77. Requests for full sets of curves will not be honored.

Breaker Description Curve No. Page

Page 3: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 3

Curve No. SC-3506-77

Types EB, EHB; MARK 75 Type HFB; 15-40 Amperes, 1 Pole

MaximumMinimum

Maximum Single PoleTrip Times at 25°C➀

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Circuit Breaker Time/Current Curves

Types EB, EHB, HFB Breakers, One PoleWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C) per terminal. Tested in open air with current in all poles.

Maximum VoltsBreaker Ac Volts, Dc VoltsType 60 Hz

EB 120 125EHB 277 125HFB 277 125

Breaker RatingsContinuous InstantaneousAmperes Trip, Amperes

15-40 See Curve

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Dc AmpsType Amperes

120 Volts 277 Volts 125 Volts

EB 10,000 . . . . . 5,000EHB . . . . . 14,000 10,000HFB (15-30 Amps) . . . . . 65,000 10,000HFB (40 Amps) . . . . . 25,000 10,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECON

DS

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR

1 MIN

UTE

2 HO

URS

TIM

E IN

SEC

ON

DS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UTE

2 H

OU

RS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 4: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 4

Curve No. SC-3507-77

Types EB, EHB; MARK 75 Type HFB; 50-70 Amperes, 1 Pole

Minimum

Maximum Single PoleTrip Times at 25°C➀

Maximum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Circuit Breaker Time/Current Curves

Types EB, EHB, HFB Breakers, One PoleWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C) per terminal. Tested in open air with current in all poles.

Maximum VoltsBreaker Ac Volts, Dc VoltsType 60 Hz

EB 120 125EHB, HFB 277 125

Breaker RatingsContinuous InstantaneousAmperes Trip, Amperes

50-70 See Curve

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Dc AmpsType Amperes

120 Volts 277 Volts 125 Volts

EB 10,000 . . . . . 5,000EHB . . . . . 14,000 10,000HFB . . . . . 25,000 10,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECON

DS

1,000

500

300

200

5,000

3,000

2,0001 H

OU

R1 M

INU

TE2 H

OU

RS

TIM

E IN

SEC

ON

DS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UTE

2 H

OU

RS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 5: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 5

Curve No. SC-3508-77

Types EB, EHB; MARK 75 Type HFB; 90-100 Amperes, 1 Pole

Maximum

Maximum Single PoleTrip Times at 25°C➀

Minimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Circuit Breaker Time/Current Curves

Types EB, EHB, HFB Breakers, One PoleWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C) per terminal. Tested in open air with current in all poles.

Maximum VoltsBreaker Ac Volts, Dc VoltsType 60 Hz

EB 120 125EHB, HFB 277 125

Breaker RatingsContinuous InstantaneousAmperes Trip, Amperes

90-100 See Curve

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Dc AmpsType Amperes

120 Volts 277 Volts 125 Volts

EB 10,000 . . . . . 5,000EHB . . . . . 14,000 10,000HFB . . . . . 25,000 10,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECON

DS

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR

1 MIN

UTE

2 HO

URS

TIM

E IN

SEC

ON

DS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UTE

2 H

OU

RS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 6: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 6

Types EB, EHB, FB; MARK 75 Type HFB; 15-40 Amperes, 2, 3 Poles

Curve No. SC-3509-77

Maximum Single PoleTrip Times at 25°C➀

MaximumMinimum

Type

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Circuit Breaker Time/Current Curves

Types EB, EHB, FB, HFB Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C) per terminal. Tested in open air with current in all poles.

Maximum VoltsBreaker Ac Volts, Dc VoltsType 60 Hz

EB 240 125/250EHB 480 250FB 600 250HFB 600 250

Breaker RatingsContinuous InstantaneousAmperes Trip, Amperes

15-40 See Curve

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

EB 10,000 . . . . . . . . . . 5,000 (125/250)EHB 18,000 14,000 . . . . . 10,000FB 18,000 14,000 14,000 10,000HFB 65,000 25,000 18,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 7: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 7

Types EB, EHB, FB; MARK 75 Type HFB; 50-70 Amperes, 2, 3 Poles

Curve No. SC-3510-77

Maximum Single PoleTrip Times at 25°C➀

MaximumMinimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Type

Circuit Breaker Time/Current Curves

Types EB, EHB, FB, HFB Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C) per terminal. Tested in open air with current in all poles.

Maximum VoltsBreaker Ac Volts, Dc VoltsType 60 Hz

EB 240 125/250EHB 480 250FB, HFB 600 250

Breaker RatingsContinuous InstantaneousAmperes Trip, Amperes

50-70 See Curve

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

EB 10,000 . . . . . . . . . . 5,000 (125/250)EHB 18,000 14,000 . . . . . 10,000FB 18,000 14,000 14,000 10,000HFB 65,000 25,000 18,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers. 100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 8: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 8

Curve No. SC-3511-77

Types EB, EHB; 90-100 Amperes, 2, 3 Poles Types FB; MARK 75 Type HFB; 90-150 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

Maximum

Minimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Circuit Breaker Time/Current Curves

Types EB, EHB, FB, HFB Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C up to 100 amps, 75°C above 100 amps) per terminal.Tested in open air with current in all poles.

Maximum VoltsBreaker Ac Volts, Dc VoltsType 60 Hz

EB 240 125/250EHB 480 250FB, HFB 600 250

Breaker RatingsBreaker Continuous InstantaneousType Amperes Trip, Amperes

EB, EHB 90-100 See CurveFB, HFB 90-150 See Curve

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

EB 10,000 . . . . . . . . . . 5,000 (125/250)EHB 18,000 14,000 . . . . . 10,000FB 18,000 14,000 14,000 10,000HFB 65,000 25,000 18,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 9: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 9

Curve No. SC-3513-77

100

8060 907050403020 1000

800

600

900

700

500

400

300

200

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

R.M.S. AMPERES

10,000

1086 9754321.8.6 .9.7.5

1000800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

20004321.8.6 .9.7.5 15 25 35 45 150

(7-22) FB3022MRL

(15-45) FB3045MRL

(35-110) FB3110MRL

(32-80) 2610D53G30

(66-190) FB3190MRL and 1268C14G02

(50-150) 1268C14G06

(90-270) FB3270MRL

(150-480) 1268C14G04

(160-480) FB3480MRL

(100-270) 2610D53G31

(450-1550) FB31550MRL

(575-1800) FB31800MRL

3 Pole Breaker Catalog Numbersare Shown but Curves also Applyto Saf-T-Vue Breakers ofCorresponding

FB Breaker Use LimiterRating Catalog(Amps) Number

3 LFB3003MR5 LFB3005MR

10 LFB3010MR25 LFB3025MR30 LFB3030MR50 LFB3050MR70 LFB3070MR

100 LFB3100MR150 LFB3150MR

Maximum BreakerInterrupting Time LFB3003MR

LFB3005MRLFB3010MR

LFB3025MRLFB3030MR

LFB3050MRLFB3070MR

LFB3100MRLFB3150MR

LFB3003MRLFB3005MR

LFB3010MRLFB3025MRLFB3030MR

LFB3050MRLFB3070MR

LFB3100MRLFB3150MR

Type FB Magnetic Only with Current Limiter; 3-150 Amperes, 3 Poles

Page 10: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 10

Curve No. SC-3512-77A

LFB Current Limiter for Type FB, 3 Pole, Thermal Magnetic Breakers

100

8060 907050403020 1000

800

600

900

700

500

400

300

200

LFB3150R

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1086 9754321.8.6 .9.7.5

1000800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

20004321.8.6 .9.7.5 15 25 35 45 150

Use This Curve in ConjunctionWith the Standard 3 Pole ThermalMagnetic FB Breaker Curves

Breaker Rating Use Limiter

Up to 70 LFB3070RAmps80-150 Amps LFB3150R

To Determine the Coordination of the Current Limiter andFB Breaker, Place the Specific Breaker Rating Belowon the 100% Line of the Appropriate 3 Pole FB Curve

LFB3070R

Page 11: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 11

Curve No. SC-4009-77

Types JB, KB; MARK 75 Type HKB; 70-250 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

High (±10%)Low (±25%)

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

MaximumMinimum

AdjustableMagnetic

Trip

Circuit Breaker Time/Current Curves

Types JB, KB, HKB Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C up to 100 amps, 75°C above 100 amps) per terminal.Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 HzMaximum Dc Volts: 250

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

70-250 500-1000% Trip Unit Rating

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

JB, KB 25,000 22,000 14,000 10,000HKB 65,000 25,000 18,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 12: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 12

Curve No. SC-3514-77

Types JA, KA; MARK 75 Type HKA; 70-225 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

MaximumMinimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Low (±25%) High (±10%)AdjustableMagnetic

Trip

Circuit Breaker Time/Current Curves

Types JA, KA, HKA Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60°C up to 100 amps, 70°C above 100 amps) per terminal.Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 HzMaximum Dc Volts: 250

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

70-225 500-1000% Trip Unit Rating

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

JA, KA 25,000 22,000 22,000 10,000HLB 65,000 35,000 25,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 13: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

Application Data

Effective: April 1998 Page

12.1

AD 29-168

Cutler-Hammer

AB DE-ION

T

Circuit Breakers

Types CA, CAH, HCA, 125-225 Amperes, 2 and 3 Poles

Curve No. SC-3504-77A

Maximum

Interrupting Rating (See Tabulation Above)

Circuit Breaker Time/Current Curves

Types CA, CAH and HCA Breakers, 2 and 3 Poles

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire (75°C)per terminal. Tested in open air with current in all poles.

Maximum Ac VoltsCA, CAH, HCA Breakers: 240 at 60 Hz

Breaker RatingContinuousAmperes

Minimum

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

➀ Single-pole test data at 25°C based on NEMA procedures for verifying performance of molded case circuit breakers.

Instantaneous Trip,Amperes

Maximum Interrupting Time

Maximum Single-PoleTrip Times at 25°C➀

See Curve125-225

Interrupting Rating (UL Listed)

Symmetrical RMS AmperesBreakerType 240 Volts

10,00022,00042,000

CACAHHCA

Page 14: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 13

Curve No. SC-3505-77

Type DA: 250-400 Amperes, 2 and 3 Poles

MaximumMinimum

Maximum Single PoleTrip Times at 25°C➀

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Magnetic Trip (±10%)

Circuit Breaker Time/Current Curves

Type DA Breaker, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(75°C) per terminal. Tested in open air with current in all poles.

Maximum Ac Volts: 240 at 60 HzMaximum Dc Volts: 250

Breaker RatingsContinuous InstantaneousAmperes Trip, Amperes

250-400 1000%

Interrupting Rating (UL Listed)Symmetrical RMS Amperes Dc Amps

240 Volts 250 Volts

22,000 10,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 15: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 14

Curve No. SC-3516-77

Types LBB, LB; MARK 75 Type HLB; 70-400 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

MaximumMinimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Low (±25%) High (±10%)AdjustableMagnetic

Trip

Circuit Breaker Time/Current Curves

Types LB, LBB, HLB Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C up to 100 amps, 75°C above 100 amps) per terminal.Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 HzMaximum Dc Volts: 250

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

70-400 500-1000% Trip Unit Rating

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

LB, LBB 42,000 30,000 22,000 20,000HLB 65,000 35,000 25,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 16: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 15

Curve No. SC-3515-77

Types LAB, LA; MARK 75 Type HLA; 70-400 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

MaximumMinimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Low (±25%) High (±10%)AdjustableMagnetic

Trip

Circuit Breaker Time/Current Curves

Types LAB-400, LA-400, HLA-400 Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(60°C up to 100 amps, 75°C above 100 amps) per terminal.Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 HzMaximum Dc Volts: 250

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

70-400 500-1000% Trip Unit Rating

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

LAB-400, LA-400 42,000 30,000 22,000 20,000HLA-400 65,000 35,000 25,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 17: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 16

Curve No. SC-3517-77

Type LA, MARK 75 Type HLA; 250-600 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

MaximumMinimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Low (±25%) High (±10%)AdjustableMagnetic

Trip

Circuit Breaker Time/Current Curves

Types LA-600, HLA-600 Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(75°C) per terminal. Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 HzMaximum Dc Volts: 250

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

250-600 500-1000% Trip Unit Rating

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

LA-600 42,000 30,000 22,000 20,000HLA-600 65,000 35,000 25,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 18: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 17

Curve No. SC-3521-77

Type MA, MARK 75 Type HMA; 125-600 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

MaximumMinimum

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

Low (±25%) High (±10%)AdjustableMagnetic

Trip

Circuit Breaker Time/Current Curves

Types MA, HMA Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(75°C) per terminal. Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 HzMaximum Dc Volts: 250

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

125-600 500-1000% Trip Unit Rating

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes Dc Amps

240 Volts 480 Volts 600 Volts 250 Volts

MA 42,000 30,000 22,000 20,000HMA 65,000 35,000 25,000 20,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 19: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 18

Curve No. SC-3522-77

Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

700 Amps

800 Amps

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

AdjustableMagnetic

Trip

Maximum

Minimum

Low (±25%) High (±10%)

Circuit Breaker Time/Current Curves

Types MA, HMA Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(75°C) per terminal. Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 Hz

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

700-800 3000-6000

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes

240 Volts 480 Volts 600 Volts

MA 42,000 30,000 22,000HMA 65,000 35,000 25,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 20: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 19

Curve No. SC-3524-77

Type NB, MARK 75 Type HNB; 800-1200 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

700, 900 Amps

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

High SettingRMS Amps (±10%)

Maximum

Minimum

1000 Amps

800, 1100 Amps

1200 Amps

700, 900 Amps

Low SettingRMS Amps (±25%)

1000 Amps

800, 1100 Amps

1200 Amps

Circuit Breaker Time/Current Curves

Types NB, HNB Breakers, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(75°C) per terminal. Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 Hz

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

700-1200 3000-6000 (700-800 Amps)4000-8000 (900-1200 Amps)

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes

240 Volts 480 Volts 600 Volts

NB 42,000 30,000 22,000HNB 65,000 35,000 25,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 21: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 20

Curve No. SC-3527-77

Type PB, 600-1600 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀(For 600-900 Amp Ratings)

1000 Amps

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

AdjustableMagnetic TripLow (±25%)

Maximum

Minimum

1200 Amps800, 1400, 1600 Amps

600 Amps

1000, 1200, 1400, 1600 Amps

High (±10%)

800 Amps

600 Amps

Maximum Short Time Delay

Minimum Short Time Delay

Maximum Single PoleTrip Times at 25°C➀(For 1000-1600 Amp Ratings)

Circuit Breaker Time/Current Curves

Type PB Breaker, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(75°C) per terminal. Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 Hz

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

600-1600 1500-5000 (600-1000 Amps)2000-6000 (1200 Amps)2500-7000 (1400 Amps)3000-8000 (1600 Amps)

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes

240 Volts 480 Volts 600 Volts

PB 125,000 100,000 100,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 22: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 21

Curve No. SC-3528-77

Type PB, 1800-3000 Amperes, 2, 3 Poles

Maximum Single PoleTrip Times at 25°C➀

1800 Amps

Maximum Interrupting Time

Interrupting Rating (See Tabulation Above)

AdjustableMagnetic TripLow (±25%)

Maximum

Minimum

2000 Amps2500 Amps

3000 Amps

1800 Amps

High (±10%)

2000 Amps and 3000 Amps

2500 Amps

Maximum Short Time Delay

Minimum Short Time Delay

Circuit Breaker Time/Current Curves

Type PB Breaker, Two and Three PolesWestinghouse Electric Corporation

For application and coordination purposes only. Based on 40°Cambient, cold start. Connected with four (4) feet of rated wire(75°C) per terminal. Tested in open air with current in all poles.

Maximum Ac Volts: 600 at 60 Hz

Breaker RatingsContinuous Amperes Instantaneous Trip, Amperes

1800-3000 3000-8000 (1800-2500 Amps)4000-12,000 (3000 Amps)

Interrupting Rating (UL Listed)Breaker Symmetrical RMS Amperes

240 Volts 480 Volts 600 Volts

PB 125,000 100,000 100,000

➀ Single pole test data at 25°C based on NEMA Procedures forverifying performance of Molded Case Circuit Breakers.

Type

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

100

8060 907050 1000

800

600

900

700

500

400

300

200

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Page 23: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 22

Curve No. SC-3600-81A

Types LC, LCG; MARK 75 Types HLC, HLCG; 75-150 Amperes, 2-3 Poles

Maximum TotalClearing Time0.20 Seconds

(2) FixedOveride

CURRENT IN MULTIPLES OF RATING PLUG➀

➂➂

➁ FixedOverride

➁ FixedOverride

➁ FixedOverride

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 5 6 8 10 20 30 40 50 60 80 1010 20 30 40 50 60

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

75 A

90 A

125

A15

0 A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

Circuit Breaker Time/Current Curves

Types LC, LCG, HLC, HLCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings75-150 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLC, LCG 42,000 30,000 22,000HLC, HLCG 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment150 Amps Fixed 100%150 Amps 50 - 100% ➀125 Amps Fixed 100%125 Amps 70 - 100% ➀100 Amps Fixed 100%100 Amps 75 - 100% ➀ 90 Amps Fixed 100% 75 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 150 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is150 x 50% x 4 = 300 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCG and HLCG,see curve No. SC-3603-81.3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

75 Amp Rating Plug 150 Amp Rating Plug

100

A

Page 24: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 23

Curve No. SC-3612-81A

Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 75-150 Amperes, 2-3 Poles

Maximum TotalClearing Time0.13 Secondswith Short DelayTime Adjust Setto Minimum

Maximum TotalClearing Time0.34 Secondswith Short DelayTime Adjust Setto Maximum

(2) FixedOveride

CURRENT IN MULTIPLES OF RATING PLUG➀

➂➂

➁ FixedOverride

➁ FixedOverride

➁ FixedOverride

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 5 6 8 10 20 30 40 50 60 80 1010 20 30 40 50 60

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

75 A

90 A

125

A15

0 A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

Circuit Breaker Time/Current Curves

Types LCA, LCGA, HLCA, HLCGA Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings75-150 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLCA 42,000 30,000 22,000HLCA 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment150 Amps Fixed 100%150 Amps 50 - 100% ➀125 Amps Fixed 100%125 Amps 70 - 100% ➀100 Amps Fixed 100%100 Amps 75 - 100% ➀ 90 Amps Fixed 100% 75 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 150 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is150 x 50% x 4 = 300 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCGA and HLCGA,see curve No. SC-3603-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

75 Amp Rating Plug 150 Amp Rating Plug

100

A

Page 25: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 24

Curve No. SC-3601-81A

Types LC, LCG; MARK 75 Types HLC, HLCG; 150-300 Amperes, 2-3 Poles

Maximum TotalClearing Time0.20 Seconds

➁ FixedOverride

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 5 6 8 10 20 30 40 50 60 80 15 20 30 40 50 60

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

175

A275

A

200

A

300

A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

250

A

150

A

80 100

Circuit Breaker Time/Current Curves

Types LC, LCG, HLC, HLCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings150-300 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLC, LCG 42,000 30,000 22,000HLC, HLCG 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment300 Amps Fixed 100%300 Amps 50 - 100% ➀275 Amps Fixed 100%275 Amps 70 - 100% ➀250 Amps Fixed 100%250 Amps 70 - 100% ➀225 Amps Fixed 100%225 Amps 70 - 100% ➀200 Amps Fixed 100%175 Amps Fixed 100%150 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 300 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is300 x 50% x 4 = 600 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCG and HLCG,see curve No. SC-3603-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

150 Amp Rating Plug 300 Amp Rating Plug

225

A

Page 26: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 25

Curve No. SC-3613-81A

Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 150-300 Amperes, 2-3 Poles

Maximum TotalClearing Time0.13 Secondswith Short DelayTime Adjust Setto Minimum

Maximum TotalClearing Time0.34 Secondswith Short DelayTime Adjust Setto Maximum

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

➁ FixedOverride

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 5 6 8 10 20 30 40 50 60 80 15 20 30 40 50 60

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

150

A17

5 A

275

A30

0 A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

80 100

250

A

200

A

Circuit Breaker Time/Current Curves

Types LCA, LCGA, HLCA, HLCGA Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings150-300 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLCA 42,000 30,000 22,000HLCA 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment300 Amps Fixed 100%300 Amps 50 - 100% ➀275 Amps Fixed 100%275 Amps 70 - 100% ➀250 Amps Fixed 100%250 Amps 70 - 100% ➀225 Amps Fixed 100%225 Amps 70 - 100% ➀200 Amps Fixed 100%175 Amps Fixed 100%150 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 300 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is300 x 50% x 4 = 600 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCGA and HLCGA,see curve No. SC-3603-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

150 Amp Rating Plug 300 Amp Rating Plug

225

A

Page 27: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 26

Curve No. SC-3611-81A

Types LC, LCG; MARK 75 Types HLC, HLCG; 200-400 Amperes, 2-3 Poles

Maximum TotalClearing Time0.20 Seconds

(2) FixedOveride

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 10 30 5020 40 60 80 100 15 20 4030 50 80 100

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

200

A

350

A

225

A

400

A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

250

A

15060

Circuit Breaker Time/Current Curves

Types LC, LCG, HLC, HLCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings200-400 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLC, LCG 42,000 30,000 22,000HLC, HLCG 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment400 Amps Fixed 100%400 Amps 50 - 100% ➀350 Amps Fixed 100%350 Amps 70 - 100% ➀300 Amps Fixed 100%300 Amps 70 - 100% ➀250 Amps Fixed 100%225 Amps Fixed 100%200 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 400 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is400 x 50% x 4 = 800 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCG and HLCG,see curve No. SC-3603-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

200 Amp Rating Plug 400 Amp Rating Plug

300

A

➁ FixedOverride

Page 28: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 27

Curve No. SC-3623-81

Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 200-400 Amperes, 2-3 Poles

Maximum TotalClearing Time0.13 Secondswith Short DelayTime Adjust Setto Minimum

Maximum TotalClearing Time0.34 Secondswith Short DelayTime Adjust Setto Maximum

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

➁ FixedOverride

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 20 30 40 50 60 80 15 20 30 40 50 60

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

250

A

200

A

350

A40

0 A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

80 100

225

A

10 100

150

Circuit Breaker Time/Current Curves

Types LCA, LCGA, HLCA, HLCGA Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings200-400 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLCA, LCGA 42,000 30,000 22,000HLCA, HLCGA 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment400 Amps Fixed 100%400 Amps 50 - 100% ➀350 Amps Fixed 100%350 Amps 70 - 100% ➀300 Amps Fixed 100%300 Amps 70 - 100% ➀250 Amps Fixed 100%225 Amps Fixed 100%200 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 400 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is400 x 50% x 4 = 800 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCGA and HLCGA,see curve No. SC-3603-81.3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

200 Amp Rating Plug 400 Amp Rating Plug

300

A

Page 29: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 28

Curve No. SC-3602-81A

Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 300-600 Amperes, 2-3 Poles

Maximum TotalClearing Time0.20 Seconds

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 30 5020 40 60 80 100 20 4030 50 80 100

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

400

A50

0 A

600

A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

300

A

20060

Circuit Breaker Time/Current Curves

Types LC, LCG, HLC, HLCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings300-600 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLC, LCG 42,000 30,000 22,000HLC, HLCG 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment600 Amps Fixed 100%600 Amps 50 - 100% ➀500 Amps Fixed 100%500 Amps 70 - 100% ➀450 Amps Fixed 100%450 Amps 70 - 100% ➀400 Amps Fixed 100%400 Amps 75 - 100% ➀350 Amps Fixed 100%300 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 600 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is600 x 50% x 4 = 1200 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCG and HLCG,see curve No. SC-3603-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

300 Amp Rating Plug 600 Amp Rating Plug

450

A

➁ FixedOverride

Page 30: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 29

Curve No. SC-3614-81A

Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 300-600 Amperes, 2-3 Poles

Maximum TotalClearing Time0.34 Secondswith Short DelayTime Adjust Setto Maximum

Maximum TotalClearing Time0.13 Secondswith Short DelayTime Adjust Setto Minimum

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 30 5020 40 60 80 100 20 4030 50 80 100

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

400

A50

0 A

600

A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

300

A

20060200

Circuit Breaker Time/Current Curves

Types LCA, LCGA, HLCA, HLCGA Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings300-600 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsLCA 42,000 30,000 22,000HLCA 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment600 Amps Fixed 100%600 Amps 50 - 100% ➀500 Amps Fixed 100%500 Amps 70 - 100% ➀450 Amps Fixed 100%450 Amps 70 - 100% ➀400 Amps Fixed 100%400 Amps 75 - 100% ➀350 Amps Fixed 100%300 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 600 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is600 x 50% x 4 = 1200 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of LCGA and HLCGA,see curve No. SC-3603-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

300 Amp Rating Plug 600 Amp Rating Plug

450

A

➁ FixedOverride

Page 31: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 30

Curve No. SC-3603-81

Types LCG, LCGA, HLCG, HLCGA Ground Fault Pick-up Curves

* Minimum Setting on 150 Amp Frames is 50 Amps

Minimum Time (±20%)

Maximum Time (±20%)

Minimum Pick-Up*(±20%)

Maximum Pick-Up

( %)

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

1086 975 100

8060 907050403020 1000

800

600

900

700

500

400

300

200

1000

0

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

+0-20

Page 32: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 31

Curve No. SC-4122-87

Type LCLG 250 Ground Fault Pick-up Curves

AMPERES

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 HO

UR2

HOUR

S

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.09

0.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INUT

E

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE1 HOUR

2 HOURS

Minimum Pickup(±20%) ( %)

Minimum Time(±20%)

Maximum Time(±20%)

Maximum Pickup+0–20

Page 33: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 32

Curve No. SC-4123-87

Type LCLG 400 Ground Fault Pick-up Curves

AMPERES

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 H

OU

R2

HO

URS

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.09

0.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INU

TE

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE

1 HO

UR

2 HO

URS

Minimum Pickup(±20%)

( %)

Minimum Time(±20%)

Maximum Time(±20%)

Maximum Pickup+0–20

Page 34: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 33

Curve No. SC-4124-87

Type LCG 150 Ground Fault Pick-up Curves

AMPERES

Minimum Time(±20%)

Maximum Time(±20%)

Maximum Pickup+0–20

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 HO

UR2

HOUR

S

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.09

0.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INUT

E

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE1 HOUR

2 HOURS

( %)

Minimum Pickup(±20%)

Page 35: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 34

Curve No. SC-4125-87

Type LCG 300 Ground Fault Pick-up Curves

AMPERES

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 H

OU

R2

HO

URS

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.009

0.01

0.02

0.03

0.04

0.050.060.070.080.09

0.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INU

TE

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE

1 HO

UR

2 HO

URS

Maximum Pickup+0–20

Minimum Pickup(±20%)

Minimum Time(±20%)

Maximum Time(±20%)

( %)

Page 36: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 35

Curve No. SC-4126-87

Type LCG 400 Ground Fault Pick-up Curves

AMPERES

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 HO

UR2

HOUR

S

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INUT

E

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE1 HOUR

2 HOURS

Maximum Pickup+0–20

Minimum Pickup(±20%)

Minimum Time(±20%)

Maximum Time(±20%)

( %)

Page 37: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 36

Curve No. SC-4127-87

Type LCG 600 Ground Fault Pick-up Curves

AMPERES

Maximum Pickup+0–20

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 H

OU

R2

HO

URS

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INU

TE

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE

1 HO

UR

2 HO

URS

Minimum Pickup(±20%)

Minimum Time(±20%)

Maximum Time(±20%)

( %)

Page 38: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 37

Curve No. SC-3616-81A

Types MCA, MCGA; MARK 75 Types HMCA, HMCGA; 400-800 Amperes, 2-3 Poles

Maximum TotalClearing Time0.42 Secondswith Short DelayTime Adjust Setto Maximum

Maximum TotalClearing Time0.14 Secondswith Short DelayTime Adjust Setto Minimum

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 30 5020 40 60 80 100 20 4030 50 80 100

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

500

A

700

A80

0 A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

400

A

20060200

Circuit Breaker Time/Current Curves

Types MCA, MCGA, HMCA, HMCGA Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings400-800 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsMCA 42,000 30,000 22,000HMCA 65,000 35,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment800 Amps Fixed 100%800 Amps 50 - 100% ➀700 Amps Fixed 100%700 Amps 70 - 100% ➀600 Amps Fixed 100%600 Amps 70 - 100% ➀500 Amps Fixed 100%500 Amps 80 - 100% ➀400 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 800 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is800 x 50% x 4 = 1600 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of MCGA and HMCGA,see curve No. SC-3606-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

400 Amp Rating Plug 800 Amp Rating Plug

600

A

➁ FixedOverride

Page 39: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 38

Curve No. SC-3604-81A

Types MC, MCG; MARK 75 Types HMC, HMCG; 400-800 Amperes, 2-3 Poles

Maximum TotalClearing Time0.222 Seconds

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 30 5020 40 60 80 100 20 4030 50 80 100

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

500

A

700

A80

0 A

9X8X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

400

A

20060200

Circuit Breaker Time/Current Curves

Types MC, MCG, HMC, HMCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings400-800 3x to 10x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsMC, MCG 42,000 30,000 22,000HMC, HMCG 65,000 50,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment800 Amps Fixed 100%800 Amps 50 - 100% ➀700 Amps Fixed 100%700 Amps 70 - 100% ➀600 Amps Fixed 100%600 Amps 70 - 100% ➀500 Amps Fixed 100%500 Amps 80 - 100% ➀400 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 800 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is800 x 50% x 4 = 1600 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of MCG and HMCG,see curve No. SC-3606-81.

3X

10X

Expanded view in short circuit area with short time adjustment set at minimum

400 Amp Rating Plug 800 Amp Rating Plug

600

A

➁ FixedOverride

Page 40: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 39

Curve No. SC-3606-81

Types MCG, MCGA, HMCG, HMCGA; NCG, NCGA, HNCG, HNCGA Ground Fault Pick-up Curves

Minimum Time (±20%)

Minimum Pick-Up(±20%)

Maximum Time (±20%)

Maximum Pick-Up

( %)

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

1086 975 100

8060 907050403020 1000

800

600

900

700

500

400

300

200

1000

0

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

+0-20

Page 41: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 40

Curve No. SC-4128-87

Type MCG 800 Ground Fault Pick-up Curves

AMPERES

Minimum Time(±20%)

Maximum Time(±20%)

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 HO

UR2

HOUR

S

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INUT

E

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE1 HOUR

2 HOURS

Maximum Pickup+0–20

Minimum Pickup(±20%) ( %)

Page 42: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 41

Curve No. SC-3617-81A

Types NCA, NCGA; MARK 75 Types HNCA, HNCGA; 800-1200 Amperes, 2-3 Poles

Maximum TotalClearing Time0.42 Secondswith Short DelayTime Adjust Setto Maximum

Maximum TotalClearing Time0.14 Secondswith Short DelayTime Adjust Setto Minimum

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 30 5020 40 60 80 100 20 4030 50 80 100

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

900

A

1100

A12

00 A

3X

7X6X

5X

4X

Short DelayPickup Settings

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

800

A

20060200

Circuit Breaker Time/Current Curves

Types NCA, NCGA, HNCA, HNCGA Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings800-1200 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsNCA 42,000 30,000 22,000HNCA 65,000 50,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment1200 Amps Fixed 100%1200 Amps 50 - 100% ➀1100 Amps Fixed 100%1100 Amps 70 - 100% ➀1000 Amps Fixed 100%1000 Amps 70 - 100% ➀ 900 Amps Fixed 100% 900 Amps 70 - 100% ➀ 800 Amps Fixed 100% 800 Amps 75 - 100% ➀

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 1200 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is1200 x 50% x 4 = 2400 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of NCA and HNCA,see curve No. SC-3606-81.

2X

8X

Expanded view in short circuit area with short time adjustment set at minimum

800 Amp Rating Plug 1200 Amp Rating Plug

1000

A

➁ FixedOverride

Page 43: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 42

Curve No. SC-3605-81A

Types NC, NCG; MARK 75 Types HNC, HNCG; 800-1200 Amperes, 2-3 Poles

Maximum TotalClearing Time0.222 Seconds

Short DelayPickup Settings

CURRENT IN MULTIPLES OF RATING PLUG➀

➁ FixedOverride

➁ FixedOverride

➂➂

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0 30 5020 40 60 80 100 20 4030 50 80 100

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

900

A

1100

A12

00 A

3X

7X6X

5X

4X

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

800

A

20060200

Circuit Breaker Time/Current Curves

Types NC, NCG, HNC, HNCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings800-1200 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsNC, NCG 42,000 30,000 22,000HNC, HNCG 65,000 50,000 25,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment1200 Amps Fixed 100%1200 Amps 50 - 100% ➀1100 Amps Fixed 100%1100 Amps 70 - 100% ➀1000 Amps Fixed 100%1000 Amps 70 - 100% ➀ 900 Amps Fixed 100% 900 Amps 70 - 100% ➀ 800 Amps Fixed 100% 800 Amps 75 - 100% ➀

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 1200 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is1200 x 50% x 4 = 2400 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of NCG and HNCG,see curve No. SC-3606-81.

2X

8X

Expanded view in short circuit area with short time adjustment set at minimum

800 Amp Rating Plug 1200 Amp Rating Plug

1000

A

➁ FixedOverride

Page 44: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 43

Curve No. SC-4129-87

Type NCG 1200 Ground Fault Pick-up Curves

AMPERES

Minimum Time(±20%)

Maximum Time(±20%)

7,000

4,000

10

TIM

E IN

SEC

ONDS

0.002

0.001

1 HO

UR2

HOUR

S

10 20 30 40 50

20 30 40 50 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

AMPERES

60

TIME IN

SECONDS

70

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.09

0.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

56789

10

20

30

40

5060708090

100

1 M

INUT

E

200

300

400

500600700800900

1,000

2,000

3,000

5,0006,000

8,0009,000

10,000

60 70 80 90 100

200

300

400

500

600

700

800

900

1,00

0

2,00

0

7,000

4,000

0.002

0.001

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2

3

4

5678910

20

30

40

5060708090100

200

300

400

5006007008009001,000

2,000

3,000

5,0006,000

8,0009,00010,000

1 MIN

UTE1 HOUR

2 HOURS

Maximum Pickup+0–20

Minimum Pickup(±20%)

( %)

Page 45: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 44

Curve No. SC-3607-81A

Types PC, PCC, PCG, PCCG, PCF, PCCF, PCFG, PCCFG; 1000-2000 Amperes, 2-3 PolesCURRENT IN MULTIPLES OF RATING PLUG➀

➂➂➂

Circuit Breaker Time/Current Curves

Types PC, PCC, PCG, PCCG, PCF, PCCF, PCFG, PCCFG Breakers,Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings1000-2000 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsAll above 125,000 100,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment2000 Amps Fixed 100%2000 Amps 50 - 100% ➀1800 Amps Fixed 100%1800 Amps 70 - 100% ➀1600 Amps Fixed 100%1600 Amps 70 - 100% ➀1400 Amps Fixed 100%1200 Amps Fixed 100%1000 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 2000 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is2000 x 50% x 4 = 4000 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of PCG, PCCG, PCFG,and PCCFG, see curve No. SC-3610-81.

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

60 80 100

200

300

400

500

600 60 80 100

200

300

400

500

600

Expanded view in short circuit area with short time adjustment set at minimum

1000 Amp Rating Plug 2000 Amp Rating Plug

Short DelayPickup Settings

➁ Fixed Override

➁ Fixed Override

➁ Fixed Override

Maximum TotalClearing Time0.222 Seconds

1400

A

1000

A1800

A20

00A

7X6X

5X

4X

3X

1200

A

8X

1600

A

2X

Page 46: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 45

Curve No. SC-3619-81A

Types PCA, PCCA, PCGA, PCCGA, PCFA, PCCFA, PCFGA, PCCFGA; 1000-2000 Amperes, 2-3 PolesCURRENT IN MULTIPLES OF RATING PLUG➀

➂➂➂

Circuit Breaker Time/Current Curves

Type PCA, PCCA, PCGA, PCCGA, PCFA, PCCFA, PCFGA, PCCFGABreakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings1000-2000 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsAll above 125,000 100,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment2000 Amps Fixed 100%2000 Amps 50 - 100% ➀1800 Amps Fixed 100%1800 Amps 70 - 100% ➀1600 Amps Fixed 100%1600 Amps 70 - 100% ➀1400 Amps Fixed 100%1200 Amps Fixed 100%1000 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 2000 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is2000 x 50% x 4 = 4000 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of PCGA, PCCGA, PCFGA,and PCCFGA, see curve No. SC-3610-81.

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

60 80 100

200

300

400

500

600 60 80 100

200

300

400

500

600

Expanded view in short circuit area with short time adjustment set at minimum

1000 Amp Rating Plug 2000 Amp Rating Plug

Short DelayPickup Settings

➁ Fixed Override

➁ Fixed Override

➁ Fixed Override

Maximum TotalClearing Time0.42 Secondswith Short DelayTime Adjust Setto Maximum

Maximum TotalClearing Time0.14 Secondswith Short DelayTime Adjust Setto Minimum

1400

A

1000

A1800

A20

00A

7X6X

5X

4X

3X

1200

A

8X

1600

A

2X

Page 47: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 46

Curve No. SC-3608-81A

Types PC, PCC, PCG, PCCG, PCF, PCCF, PCFG, PCCFG; 1400-2500 Amperes, 2-3 PolesCURRENT IN MULTIPLES OF RATING PLUG➀

➂➂➂

Circuit Breaker Time/Current Curves

Types PC, PCC, PCG, PCCG, PCF, PCCF, PCFG, PCCFG Breakers,Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings1400-2500 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsAll above 125,000 100,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment2500 Amps Fixed 100%2500 Amps 50 - 100% ➀2000 Amps Fixed 100%2000 Amps 70 - 100% ➀1800 Amps Fixed 100%1800 Amps 70 - 100% ➀1600 Amps Fixed 100%1400 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 2500 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is2500 x 50% x 4 = 5000 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of PCG, PCCG, PCFG,and PCCFG, see curve No. SC-3610-81.

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

TIME IN

SECONDS

60 80 100

200

300

400

500

600 60 80 100

200

300

400

500

600

Expanded view in short circuit area with short time adjustment set at minimum

1400 Amp Rating Plug 2500 Amp Rating Plug

Short DelayPickup Settings

➁ Fixed Override

➁ Fixed Override

➁ Fixed Override

Maximum TotalClearing Time0.222 Seconds

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

1400

A16

00A

2000

A

2500

A

7X6X

5X

4X

3X

8X

2X

1800

A

Page 48: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 47

Curve No. SC-3620-81A

Types PCA, PCCA, PCGA, PCCGA, PCFA, PCCFA, PCFGA, PCCFGA; 1400-2500 Amperes, 2-3 PolesCURRENT IN MULTIPLES OF RATING PLUG➀

➂➂➂

Circuit Breaker Time/Current Curves

Types PCA, PCCA, PCGA, PCCGA, PCFA, PCCFA, PCFGA, PCCFGABreakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings1400-2500 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsAll above 125,000 100,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment2500 Amps Fixed 100%2500 Amps 50 - 100% ➀2000 Amps Fixed 100%2000 Amps 70 - 100% ➀1800 Amps Fixed 100%1800 Amps 70 - 100% ➀1600 Amps Fixed 100%1400 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 2500 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is2500 x 50% x 4 = 5000 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of PCGA, PCCGA, PCFGA,and PCCFGA, see curve No. SC-3610-81.

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

TIME IN

SECONDS

60 80 100

200

300

400

500

600 60 80 100

200

300

400

500

600

Expanded view in short circuit area with short time adjustment set at minimum

1400 Amp Rating Plug 2500 Amp Rating Plug

Short DelayPickup Settings

➁ Fixed Override

➁ Fixed Override

➁ Fixed Override

1400

A16

00A

2000

A

2500

A

7X6X

5X

4X

3X

Maximum TotalClearing Time0.14 Secondswith Short DelayTime Adjust Setto Minimum

Maximum TotalClearing Time0.42 Secondswith Short DelayTime Adjust Setto Maximum

Minimum TotalClearing Time

Maximum TotalClearing Time

1800

A

2X

8X

Page 49: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 48

Curve No. SC-3609-81A

Types PC, PCC, PCG, PCCG; 1600-3000 Amperes, 2-3 PolesCURRENT IN MULTIPLES OF RATING PLUG➀

➂➂➂

Circuit Breaker Time/Current Curves

Types PC, PCC, PCG, PCCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings1600-3000 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsAll above 125,000 100,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment3000 Amps Fixed 100%3000 Amps 50 - 100% ➀2500 Amps Fixed 100%2500 Amps 70 - 100% ➀2000 Amps Fixed 100%1800 Amps Fixed 100%1600 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 3000 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is3000 x 50% x 4 = 6000 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of PCG and PCCG,see curve No. SC-3610-81.

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

TIME IN

SECONDS

60 80 100

200

300

400

500

600 60 80 100

200

300

400

500

600

Expanded view in short circuit area with short time adjustment set at minimum

1600 Amp Rating Plug 3000 Amp Rating Plug

Short DelayPickup Settings

➁ Fixed Override

➁ Fixed Override

➁ Fixed Override

Maximum TotalClearing Time0.222 Seconds

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

1600

A18

00A

2500

A30

00A

7X6X

5X

4X

3X

8X

2X

2000

A

Page 50: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 49

Curve No. SC-3621-81A

Types PCA, PCCA, PCGA, PCCGA; 1600-3000 Amperes, 2-3 PolesCURRENT IN MULTIPLES OF RATING PLUG➀

➂➂➂

Circuit Breaker Time/Current Curves

Types PC, PCC, PCG, PCCG Breakers, Two and Three PolesWestinghouse Electric Corporation

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toWestinghouse.

Breaker RatingsMaximum Ac Volts 600, 50/60 Hz

Continuous Amperes Short Delay Pickup Settings1600-3000 2x to 8x rating plug value with

calibration settings as shown oncurve (Tolerance ±10%)

Interrupting Rating (UL/CSA Listed)Breaker Symmetrical AMS AmperesFrame 240 Volts 480 Volts 600 VoltsAll above 125,000 100,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment3000 Amps Fixed 100%3000 Amps 50 - 100% ➀2500 Amps Fixed 100%2500 Amps 70 - 100% ➀2000 Amps Fixed 100%1800 Amps Fixed 100%1600 Amps Fixed 100%

➀ When adjustable rating plugs are used, short delay pickupsettings track the selected position of the adjustable rating plug.For example, with an adjustable 3000 Amp rating plug set at 50%,and the short delay pickup set at 4x, the short delay pickup is3000 x 50% x 4 = 6000 Amps.

➁ For high fault current levels, a fixed instantaneous overrideis provided. The trip level for each rating plug is shown.(Tolerance ±15%)

➂ The end of the curve is determined by the interrupting ratingand/or the specific application.

➃ For ground fault time-current characteristics of PCGA, PCCGA,PCFGA, and PCCFGA, see curve No. SC-3610-81.

0.5

0.5

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN MULTIPLES OF RATING PLUG➀

0.5

0.5

0.6

0.8

1.0

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

0.6

0.8

1.0

2.0

3.0

4.0

5.0

8.0

10.0

20.0

30.0

40.0

50.0

60.0

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

AMPERES X 100

6.0

TIME IN

SECONDS

60 80 100

200

300

400

500

600 60 80 100

200

300

400

500

600

Expanded view in short circuit area with short time adjustment set at minimum

1600 Amp Rating Plug 3000 Amp Rating Plug

Short DelayPickup Settings

➁ Fixed Override

➁ Fixed Override

➁ Fixed Override

Maximum TotalClearing Time0.42 Secondswith Short DelayTime Adjust Setto Maximum

Minimum TotalClearing Time

Maximum TotalClearing Time

Standard Fixed Rating Plug

Optional Adjustable Rating Plug➀

Maximum TotalClearing Time0.14 Secondswith Short DelayTime Adjust Setto Minimum

1600

A18

00A

2500

A30

00A

7X6X

5X

4X

3X

8X

2X

2000

A

Page 51: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 50

Curve No. SC-3610-81

Types PCG, PCGA, PCCG, PCCGA, PCFG, PCFGA, PCCFG, PCCFGA Ground Fault Pick-up Curves

Minimum Time (±20%)

Minimum Pick-UpEach Rating

(±20%)

Maximum Time (±20%)

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

1086 975 100

8060 907050403020 1000

800

600

900

700

500

400

300

200

1000

0

8000

6000

9000

7000

5000

4000

3000

2000

1000800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

Maximum Pick-Up ( %)+0-20

PC

G/P

CC

G20

00 P

CG

/PC

CG

2500

PC

G/P

CC

G30

00

PC

G/P

CC

G20

00

PC

G/P

CC

G30

00 P

CG

/PC

CG

2500

Page 52: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data

29-168Page 51

Curve No. SC-3505-76

MCP Motor Circuit Protector, 3-150 Amperes, 600 Volts AC with Current Limiter Attachment

100

8060 907050403020 1000

800

600

900

700

500

400

300

200

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1086 9754321.8.6 .9.7.5

1000800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

20004321.8.6 .9.7.5

Maximum MCPInterrupting Time

EL3003R and EL3007R

EL3015R

EL3030REL3050R

EL3100R

EL3150R

MCP Use LimiterCatalog Number Catalog No.( 7- 22A) MCP0322R EL3003R( 18- 58A) MCP0358R EL3007R( 50- 150A) MCP03150R EL3015R(100- 300A) MCP13300R EL3030R(160- 480A) MCP23480R EL3050R(275-1000A) MCP331000R EL3100R(450-1550A) MCP431550R EL3150R(575-1800A) MCP431800R EL3150R

(Tolerance ±10% on High or Low Setting)

MCP0358R

MCP03150R

MCP13300R

MCP23480R

MCP331000R

MCP431550R

MCP431800R

MCP0322R

Page 53: AB DE-ION Circuit Breakers - Eatonpub/@electrical/... · Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles.....SC-3522-77 18 Type NB, ... SC-4129-87 43 AB DE-ION® Circuit Breakers

October 1997

AB DE-ION Circuit Breakers

Application Data29-168

Page 52

Curve No. SC-3637-76

MCP Motor Circuit Protector, 250 and 400 Amperes, 600 Volts AC

100

8060 907050403020 1000

800

600

900

700

500

400

300

200

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,0001 HOUR

1 MIN

UTE2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1086 9754321.8.6 .9.7.5

1000800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

20004321.8.6 .9.7.5

MCP532500 andMCP532500C(1250-2500)

MCP534000 andMCP534000C(2000-4000)

Maximum MCPInterrupting Time