abb - lv catalog

1360
1 Across the line contactors Low Voltage Products & Systems 1.1 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Across the line contactors A9 - AF1650 A145 - AF1650 Maximum UL/CSA horsepower ratings according to UL508 and CSA22.2 No. 14 • Includes NEMA sizes 4 - 8 • CE mark • 1 NO & 1 NC auxiliary contacts are standard and up to 6 additional auxiliary contacts may be added to provide a total of 8 (4 NO & 4 NC) • Contactors ensure positive safety between their auxiliary contact blocks. • D.C. ratings and D.C. control operation available • Easy maintenance of main contacts and coil inspection • Can be mounted in any position • Terminal lugs sold separately. See page 1.25. • Operates over an extended voltage range of 85% to 110% of rated control voltage • NEMA, UL, IEC, CSA, VDE and most other international standards • UL File No: E36588 (A/AF145 - AF750) • UL File No: E73397 (AF1350 - AF1650) • CSA File No: LR19700 A9 - A110 • Maximum UL/CSA horsepower ratings according to UL508 and CSA22.2 No. 14 • Includes NEMA sizes 00 - 3 • CE mark • Compact space saving design • Standard auxiliary contact configurations: A9 - A40 1 NO or 1 NC A50 - A110 1 NO & 1 NC • Contactor sizes A50 - A110 can be supplied without auxiliaries Additional auxiliary contact blocks are available • D.C. ratings & D.C. control operation available • Fast, snap-on DIN rail mounting • Double break contact design • Snap-on front mounted accessories include mechanical latch, pneumatic timer, and 1 & 4 pole auxiliary contact blocks • Contactors ensure positive safety between their auxiliary contact blocks. • Easy coil change • Captive terminal screws • NEMA, UL, IEC, CSA, VDE and most other international standards • Touch safe design: All connection terminals are protected against accidental touch • Terminals supplied open for ease of wiring Operates over an extended voltage range of 85% to 110% of rated control voltage • Screwdriver guide holes • UL File No: E39231 (A9 - A75); (AE9 - AE75); (AL9 - AL40); (AF50 - AF75) • UL File No: E36588 (A95 - A110); (AE95 - AE110); (AF145 - AF750) • CSA File No: LR56745 (A9 - A75); (AE9 - AE75); (AF50 - AF75) • CSA File No: LR19700 (A95 - A110); (AE95 - AE110); (AF145 - AF750) • CSA approved for elevator service Across the line Contactors

Upload: hanssinekr9050

Post on 09-Aug-2015

1.045 views

Category:

Documents


22 download

DESCRIPTION

ABB's Low-Voltage Switchgears & Controls

TRANSCRIPT

Across the line contactors A9 - AF1650

Ac

ro co ss nt the ac to line 1 rs

Contactors

Across the line

Maximum UL/CSA horsepower ratings according to UL508 and CSA22.2 No. 14 Includes NEMA sizes 00 - 3 CE mark Compact space saving design Standard auxiliary contact configurations: A9 - A40 1 NO or 1 NC A50 - A110 1 NO & 1 NC Contactor sizes A50 - A110 can be supplied without auxiliaries Additional auxiliary contact blocks are available D.C. ratings & D.C. control operation available Fast, snap-on DIN rail mounting Double break contact design Snap-on front mounted accessories include mechanical latch, pneumatic timer, and 1 & 4 pole auxiliary contact blocks Contactors ensure positive safety between their auxiliary contact blocks. Easy coil change Captive terminal screws NEMA, UL, IEC, CSA, VDE and most other international standards Touch safe design: All connection terminals are protected against accidental touch Terminals supplied open for ease of wiring Operates over an extended voltage range of 85% to 110% of rated control voltage Screwdriver guide holes UL File No: E39231 (A9 - A75); (AE9 - AE75); (AL9 - AL40); (AF50 - AF75) UL File No: E36588 (A95 - A110); (AE95 - AE110); (AF145 - AF750) CSA File No: LR56745 (A9 - A75); (AE9 - AE75); (AF50 - AF75) CSA File No: LR19700 (A95 - A110); (AE95 - AE110); (AF145 - AF750) CSA approved for elevator service

A9 - A110

Maximum UL/CSA horsepower ratings according to UL508 and CSA22.2 No. 14 Includes NEMA sizes 4 - 8 CE mark 1 NO & 1 NC auxiliary contacts are standard and up to 6 additional auxiliary contacts may be added to provide a total of 8 (4 NO & 4 NC) Contactors ensure positive safety between their auxiliary contact blocks. D.C. ratings and D.C. control operation available Easy maintenance of main contacts and coil inspection Can be mounted in any position Terminal lugs sold separately. See page 1.25. Operates over an extended voltage range of 85% to 110% of rated control voltage NEMA, UL, IEC, CSA, VDE and most other international standards UL File No: E36588 (A/AF145 - AF750) UL File No: E73397 (AF1350 - AF1650) CSA File No: LR19700

A145 - AF1650

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

1.11SXU000023C0202

1

ine el s h s t tor os tac r Ac conApplication

A9 - A300 General information AC operated, UL rated, 3 phaseControl circuit types A-Line types: AC operated with laminated magnetic circuit.

A-Line contactors are mainly used for controlling 3-phase motors and for controlling power circuits corresponding to their operating characteristics up to 690 and even 1000 VAC. and 440 VDC.

Contactor types 3 pole contactors with NO or NC built in auxiliary contact for A9 - A40 contactors; factory assembled auxiliary contacts for A50 - A300 contactors 4 pole contactors: 4 NO or 2 NO & 2 NC without any auxiliary contacts. (A9 - A75)

Description of 3 pole and 4 pole contactors A9 - A300All A-Line contactors can be assembled side by side. The add-on or built-in auxiliary contacts are suitable for low level currents.

Quick mounting on DIN rail: EN 50022 and EN 50023 standards: 35 x 7.5mm for A9 - A40 35 x 15mm for A9 - A75 75mm for A45 - A110

Location of surge suppressors.

Clear marking of coil voltages and frequencies. Connecting point for control leads in top part of main terminals of A50 - A75 contactors. For A95 & A110 contactors these are additional power connections. Terminal marking according to IEC 947-4-1, EN 50005, EN 50012 and NEMA standards. Location of function marker. Stops for attaching front mounted accessories.

Location of side mounted accessories: on right or left hand side. Factory mounted on left hand side for CAL5 on A50 - A300 Holes for screw mounting (screws not supplied). Distance between holes according to EN 50003. Terminals in A9 - A110 contactors are delivered in open position with captive screws (screws of unused terminals must be tightened). Screwdriver guidance for all terminals makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106 - Part. 100. All A9 - A40 contactor terminals as well as A45 - A300 contactor auxiliary contact and coil terminals ensure IP20 degree of protection according to IEC 947-1.

A9 - A300

Terminal screws: Posidrive (+,-) No 2 for all A9 - A75 M8 hex threaded socket screw for A95 - A300 main terminals.

Catalog number explanationA9-30-10-84Frame size Power pole 30 = 3 NO 40 = 4 NO 22 = 2 NO & 2 NC Coil voltage (see coil voltage selection chart) Auxiliary contacts 10 01 11 00 22 = = = = = 1 NO & 0 NC 0 NO & 1 NC 1 NO & 1 NC No auxiliary provided 2 NO & 2 NC

Coil voltage selection chartCntr Hz type 12

24 81

Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 83 84 84 34 36 80 80 42 85 86 86 86 51 53 55 55

60

A

50 A 81 83 84 For other voltages, see page 1.24.

1.21SXU000023C0202

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

A9 - A300 Non-reversing, mechanically interlocked, reversing AC operated, UL rated, 3 phase

Ac

ro co ss nt the ac to line 1 rs

A26-30-10-84 UL general purpose current UL motor switching current Maximum motor horsepower ratings 208V 240V 480V 575/600V

A110M-30-11-84 Standard Aux. contacts NO NC Non-reversing Catalog number List price

A110R-30-11-84 Mechanically interlocked Catalog number List price Reversing Catalog number List price

AC1 21 25 30 40 50 60 80 90 105 125 140 230 250 300 350 400 550 650 750 900 1350 1650 9 11 17 28 34 42 54 65 80 95 110 130 156 192 248 302 414 480 602 810 960 1080 2 3 5 7.5 10 10 15 20 25 30 30 40 50 60 75 100 125 150 200 250 2 3 5 10 10 15 20 25 30 30 40 50 60 75 100 100 150 200 250 300 400 450 5 7.5 10 20 25 30 40 50 60 60 75 100 125 150 200 250 350 400 500 600 800 900 7.5 10 15 25 30 40 50 60 75 75 100 125 150 200 250 300 400 500 600 700 900 1000 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 A9-30-10-84 A9-30-01-84 A12-30-10-84 A12-30-01-84 A16-30-10-84 A16-30-01-84 A26-30-10-84 A26-30-01-84 A30-30-10-84 A30-30-01-84 A40-30-10-84 A40-30-01-84 A50-30-11-84 A63-30-11-84 A75-30-11-84 A95-30-11-84 A110-30-11-84 A145-30-11-84 A185-30-11-84 A210-30-11-84 A260-30-11-84 A300-30-11-84

UL rated $ 78 84 102 183 252 297 330 372 413 450 480 825 1,290 1,635 1,815 1,875 A9M-30-10-84 A9M-30-01-84 A12M-30-10-84 A12M-30-01-84 A16M-30-10-84 A16M-30-01-84 A26M-30-10-84 A26M-30-01-84 A30M-30-10-84 A30M-30-01-84 A40M-30-10-84 A40M-30-01-84 A50M-30-11-84 A63M-30-11-84 A75M-30-11-84 A95M-30-11-84 A110M-30-11-84 A145M-30-11-84 A185M-30-11-84 A210M-30-11-84 A260M-30-11-84 A300M-30-11-84 $ 255 315 345 405 548 639 713 870 1,155 1,230 1,365 2,235 3,360 4,035 4,485 5,460 A9R-30-10-84 A9R-30-01-84 A12R-30-10-84 A12R-30-01-84 A16R-30-10-84 A16R-30-01-84 A26R-30-10-84 A26R-30-01-84 A30R-30-10-84 A30R-30-01-84 A40R-30-10-84 A40R-30-01-84 A50R-30-11-84 A63R-30-11-84 A75R-30-11-84 A95R-30-11-84 A110R-30-11-84 A145R-30-11-84 A185R-30-11-84 A210R-30-11-84 A260R-30-11-84 A300R-30-11-84 $ 315 375 413 480 623 750 810 1,013 1,298 1,425 1,628 2,250 3,375 4,050 4,500 5,475

See Type AF contactors, page 1.9

Coil voltage selectionAll AC operated catalog numbers include a 120VAC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 240V coil is required for an A75 contactor: A75-30-11-80 Power wiring is not included. The NC electrical interlock is provided with the mechanical interlock for A9 - A110 contactors.

Coil voltage selection chartHz 60Cntr type 12

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.2. Add $ 20 to list price for each additional auxiliary, and see page 1.32 for available combinations. Only side-mounted blocks are allowed to be factory installed. If auxiliary contacts are not required for A50 - A300, subtract $ 40 from list price and change catalog number to 00 instead of 11.

Volts 24 81 48 110 120 125 208 220 240 277 380 415 440 480 500 600 83 84 84 34 36 80 80 42 85 86 86 86 51 53 55 55

A

50 A 81 83 84 For other voltages, see page 1.24.

ReversingReversing contactors are designed for reversing type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: A9 - A16 mounted on 35mm DIN rail A26 - A300 mounted on common baseplate The NC electrical interlock is provided with the mechanical interlock for A9 - A110 contactors.

Mechanical interlockMechanically interlocked contactors are designed for reversing, 2 speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: A9 - A16 mounted on 35mm DIN rail A26 - A300 mounted on common baseplate Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule AA [OA] - A9 - A110 Discount schedule AEA [OC] - A145 - A300

1.31SXU000023C0202

1

ine el s h s t tor os tac r Ac conApplication

AE9 - AE110 General information DC operated, UL rated, 3 phaseUc (DC) A1 A2 B2 - Holding NC contact in 4th contactor pole B1 - Pull-inA3

A-Line contactors are mainly used for controlling 3-phase motors and for controlling power circuits corresponding to their operating characteristics up to 690 and even 1000 VAC. and 440 VDC.

Uc (DC) A1 A2B2 - Holding

CDL5 (AE45 to AE75) CCL5 (AE95 to AE110)

Control circuit typesAE types: with laminated magnetic circuit and double-winding coil fed from DC supply via a CDL5 insertion contact mounted on the device. The CDL5 has an NC lagging contact for insertion of the second winding. (See schematic.)

VaristorB1 - Pull-in A3 AE45 to AE110

AE9 to AE40

Location of surge suppressors. Quick mounting on DIN rail: EN 50022 and EN 50023 standards: 35 x 7.5mm for AE9 - AE40 35 x 15mm for AE9 - AE75 75mm for AE45 - AE110 Location of side mounted accessories: on right or left hand side. Factory mounted on left hand side for CAL5 on A50 - A300 right hand side for CDL5/CCL5 on AE45 - AE110 Connecting point for control leads in top part of main terminals of AE50 - AE75 contactors. For AE95 & AE110 contactors these are additional power connections. Terminal marking according to IEC 947-4-1, EN 50005, EN 50012 and NEMA standards. Location of function marker. Holes for screw mounting (screws not supplied). Distance between holes according to EN 50003. Stops for attaching front mounted accessories. Terminal screws: Terminals delivered in open position with captive screws (unused terminal screws must be tightened). Screwdriver guidance for all terminals makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106 - Part. 100. All AE9 - AE40 contactor terminals as well as AE45 - AE110 contactor auxiliary contact and coil terminals ensure IP20 degree of protection according to IEC 947-1.

Clear marking of coil voltages and frequencies.

AE9 - AE110

Posidrive (+,-) No 2 for all AE9 - AE75 M8 hex threaded socket screw for AE95 & AE110

Catalog number explanationAE9-30-00-81Frame size Power pole 30 = 3 NO 40 = 4 NO 22 = 2 NO & 2 NC Coil voltage (see coil voltage selection chart) Auxiliary contacts 00 = No auxiliary provided 11 = 1 NO & 1 NC

Coil voltage selection chartHz DC Contr. type AE Volts 12 80 24 81 48 83 110 86 125 87 220 88 240 89

For other voltages, see page 1.24.

1.41SXU000023C0202

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

U

AE9 - AE110 Non-reversing, mechanically interlocked, reversing DC operated, UL rated, 3 phase

Ac

ro co ss nt the ac to line 1 rs

AE26-30-11-81 General purpose current UL motor switching current Maximum motor horsepower ratings 208V 240V 480V 575/600V

AE110M-30-11-81 Standard Aux. contacts NO NC Non-reversing Catalog number List price

AE110R-30-11-81 Mechanically interlocked Catalog number List price Reversing Catalog number List price

AC1 21 25 30 40 50 60 80 90 105 125 140 230 250 300 350 400 550 650 750 900 1350 1650 9 11 17 28 34 42 54 65 80 95 110 130 156 192 248 302 414 480 602 810 960 1080 2 3 5 7.5 10 10 15 20 25 30 30 40 50 60 75 100 125 150 200 250 2 3 5 10 10 15 20 25 30 30 40 50 60 75 100 100 150 200 250 300 400 450 5 7.5 10 20 25 30 40 50 60 60 75 100 125 150 200 250 350 400 500 600 800 900 7.5 10 15 25 30 40 50 60 75 75 100 125 150 200 250 300 400 500 600 700 900 1000 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

UL rated AE9-30-11-81 AE12-30-11-81 AE16-30-11-81 AE26-30-11-81 AE30-30-11-81 AE40-30-11-81 AE50-30-11-81 AE63-30-11-81 AE75-30-11-81 AE95-30-11-81 AE110-30-11-81 $ 118 124 142 223 292 337 375 477 518 555 690 AE9M-30-11-81 AE12M-30-11-81 AE16M-30-11-81 AE26M-30-11-81 AE30M-30-11-81 AE40M-30-11-81 AE50M-30-11-81 AE63M-30-11-81 AE75M-30-11-81 AE95M-30-11-81 AE110M-30-11-81 $ 335 395 425 485 628 720 803 1,080 1,365 1,440 1,785 AE9R-30-11-81 AE12R-30-11-81 AE16R-30-11-81 AE26R-30-11-81 AE30R-30-11-81 AE40R-30-11-81 AE50R-30-11-81 AE63R-30-11-81 AE75R-30-11-81 AE95R-30-11-81 AE110R-30-11-81 $ 395 455 493 560 703 830 930 1,208 1,493 1,635 2,048

See AF contactors, page 1.9

Coil voltage selectionAll DC operated catalog numbers include a 24VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 110V coil is required for an AE75 contactor: AE75-30-11-86

Coil voltage selection chartHz DC Contr. type AE Volts 12 80 24 81 48 83 110 86 125 87 220 88 240 89

For other voltages, see page 1.24.

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.4. Add $ 20 to list price for each additional auxiliary, and see page 1.32 for available combinations.

ReversingReversing contactors are designed for reversing type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: AE9 - AE16 mounted on 35mm DIN rail AE26 - AE110 mounted on common baseplate The NC electrical interlock is provided with the mechanical interlock.

Mechanical interlockMechanically interlocked contactors are designed for reversing, 2 speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: AE9 - AE16 mounted on 35mm DIN rail AE26 - AE110 mounted on common baseplate Power wiring is not included. The NC electrical interlock is provided with the mechanical interlock.

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule AA [OA] - AE9 - AE110

1.51SXU000023C0202

1

ine el s h s t tor os tac r Ac conApplication

AL9 - AL40 General information DC operated, UL rated, 3 phase

AL and AL...Z contactors are mainly used for controlling 3-phase motors and for controlling power circuits corresponding to their operating characteristics up to 690 and even 1000 VAC. and 440 VDC.

Control circuit typesAL9 - AL40: DC coil with low power consumption of 3W to 3.5W AL9Z - AL16Z: DC coil with low power consumption of 2.4W. Designed to be directly controlled by PLC.

Location of surge suppressors. Quick mounting on DIN rail: EN 50022 and EN 50023 standards: 35 x 7.5mm for AL9 - AL40 35 x 15mm for AL9 - AL40

Clear marking of coil voltages and frequencies.

Location of side mounted accessories: on right or left hand side. Terminal marking according to IEC 60947-4-1, EN 50005, EN 50012 and NEMA standards. Location of function marker. Holes for screw mounting (screws not supplied). Distance between holes according to EN 50003. Stops for attaching front mounted accessories. Terminal screws: Terminals delivered in open position with captive screws (unused terminal screws must be tightened). Screwdriver guidance for all terminals makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106 - Part. 100. All AL9 - AL40 contactor terminals as well as contactor auxiliary contacts and coil terminals ensure IP20 degree of protection according to IEC 60947-1.

AL9 - AL40

Posidrive (+,-) No 2 for all AL contactors

Catalog number explanationAL9 - 30 - 10 - 81Frame size Power pole 30 = 3 NO Coil voltage (see coil voltage selection chart) Auxiliary contacts 10 = 1 NO & 0 NC 01 = 0 NO & 1 NC

Coil voltage selectionHz DC DC Contr. type AL AL...Z Volts 12 80 24 81 15 48 83 28 110 86 125 87 220 88 240 89

For other voltages, see page 1.24.

1.61SXU000023C0202

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

AL9 - AL40, AL9Z - AL16Z Non-reversing, mechanically interlocked, reversing DC operated, UL rated, 3 phase

Ac

ro co ss nt the ac to line 1 rs

AL9-30-10-81

AL26-30-10-81

AL40-30-10-81

AL Contactors 3W and 3.5W consumptionGeneral purpose current UL motor switching current Maximum motor horsepower ratings 240V 480V 208V 575/600V

Standard Aux. contacts NO NC

Non-reversing Catalog number List price

Mechanically interlocked Catalog number List price

Reversing Catalog number List price

AC1 21 25 30 40 50 60 9 11 17 28 34 42 2 3 5 7.5 10 10 2 3 5 10 10 15 5 7.5 10 20 20 30 7.5 10 15 25 30 40 1 0 1 0 1 0 1 0 1 0 1 0 0 1 0 1 0 1 0 1 0 1 0 1 AL9-30-10-81 AL9-30-01-81 AL12-30-10-81 AL12-30-01-81 AL16-30-10-81 AL16-30-01-81 AL26-30-10-81 AL26-30-01-81 AL30-30-10-81 AL30-30-01-81 AL40-30-10-81 AL40-30-01-81

UL rated $ 138 169 188 238 326 376 AL9M-30-10-81 AL9M-30-01-81 AL12M-30-10-81 AL12M-30-01-81 AL16M-30-10-81 AL16M-30-01-81 AL26M-30-10-81 AL26M-30-01-81 AL30M-30-10-81 AL30M-30-01-81 AL40M-30-10-81 AL40M-30-01-81 $ 411 490 526 606 781 892 AL9R-30-10-81 AL9R-30-01-81 AL12R-30-10-81 AL12R-30-01-81 AL16R-30-10-81 AL16R-30-01-81 AL26R-30-10-81 AL26R-30-01-81 AL30R-30-10-81 AL30R-30-01-81 AL40R-30-10-81 AL40R-30-01-81 $ 433 498 527 643 826 912

ALZ Contactors 2.4W consumptionGeneral purpose current UL motor switching current Maximum motor horsepower ratings 240V 480V 208V 575/600V

Standard Aux. contacts NO NC

Non-reversing Catalog number List price

Mechanically interlocked Catalog number List price

Reversing Catalog number List price

AC1 21 25 30 9 11 17 2 3 5 2 3 5 5 7.5 10 7.5 10 15 1 0 1 0 1 0 0 1 0 1 0 1 AL9Z-30-10-15 AL9Z-30-01-15 AL12Z-30-10-15 AL12Z-30-01-15 AL16Z-30-10-15 AL16Z-30-01-15

UL rated $ 141 173 188 AL9ZM-30-10-15 AL9ZM-30-01-15 AL12ZM-30-10-15 AL12ZM-30-01-15 AL16ZM-30-10-15 AL16ZM-30-01-15 $ 319 417 441 AL9ZR-30-10-15 AL9ZR-30-01-15 AL12ZR-30-10-15 AL12ZR-30-01-15 AL16ZR-30-10-15 AL16ZR-30-01-15 $ 429 477 501

Coil voltage selectionAll DC operated catalog numbers include a 24VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 48V coil is required for an AL30 contactor: AL30-30-10-83

Mechanical interlockMechanically interlocked contactors are designed for reversing, 2 speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: AL9 & AL16 mounted on 35mm DIN rail AL26 & AL40 mounted on common baseplate Power wiring is not included. The NC electrical interlock is provided

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.6. Add $ 20 to list price for each additional auxiliary, and see page 1.32 for available combinations.

Coil voltage selectionHz DC DC Contr. type AL AL...Z Volts 12 80 24 81 15 48 83 28 110 86 125 87 220 88 240 89

ReversingReversing contactors are designed for reversing type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted with line and load terminals.

For other voltages, see page 1.24.

1 Only coil voltages available for AL9Z AL16Z. Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule AA [OA] AL9 - AL40

1.71SXU000023C0202

1

ine el s h s t tor os tac r Ac conApplication

AF50 - AF1650 General information AC & DC operated, UL rated, 3 phaseControl circuit types AF types: AC/DC operated with laminated magnetic circuit.

A-Line contactors are mainly used for controlling 3-phase motors and for controlling power circuits corresponding to their operating characteristics up to 690 and even 1000 VAC. and 440 VDC.

Contact or types 3 pole contactors with 1 NO or 1 NC factory assembled auxiliary contacts for AF50 - AF1650 contactors

Description of 3 pole contactors AF50 - AF1650All AF contactors can be assembled side by side. The add-on auxiliary contacts are suitable for low level currents.

Quick mounting on DIN rail: EN 50022 and EN 50023 standards: 35 x 15mm for AF50 - AF75 75mm for AF50 - AF110

Surge suppressors built in as standard on the printed circuit board. Clear marking of coil voltages and frequencies. Connecting point for control leads in top part of main terminals of AF50 - AF75 contactors. For AF95 & AF110 contactors these are additional power connections. Terminal marking according to IEC 947-4-1, EN 50005, EN 50012 and NEMA standards. Location of function marker. Stops for attaching front mounted accessories.UL

Location of side mounted accessories: on right or left hand side. Factory mounted on left hand side for CAL5 on AF50 - AF1650 Holes for screw mounting (screws not supplied). Distance between holes according to EN 50003.

A2 A15L 3L 1L 1 2 3

Terminals delivered in open position with captive screws (screws of unused terminals must be tightened). Screwdriver guidance for all terminals makes it possible to use motorized screwdrivers. All terminals provide protection against accidental direct contact with live parts according to VDE0106 - Part. 100. All AF50- AF110 contactor terminals as well as AF50 - AF1650 contactor auxiliary contact and coil terminals ensure IP20 degree of protection according to IEC 947-1.

Terminal screws: Posidrive (+,-) No 2 for all AF50 AF75

AF50 - AF1650

M8 hex threaded socket screw for AF95 AF1650 main terminals.

Catalog number explanationAF50 - 30 - 11 - 70Frame size Power pole 30 = 3 NO 40 = 4 NO 22 = 2 NO & 2 NC Coil voltage (see coil voltage selection chart) Auxiliary contacts 11 = 1 NO & 1 NC 00 = No auxiliary provided 22 = 2 NO & 2 NC

Coil voltage selection AF50 to AF165024 - 60 DC 68 1 20 - 60 DC 72 2 AC/DC VOLTS, 40 - 60 Hz 48 - 130 AC/DC 100 - 250 AC/DC 69 70 3 250 - 500 AC//DC 71 4

1 AF400 AF750, DC only. 2 AF50 AF300, DC only. 3 Only option for AF1350 / AF1650. 4 AF400 - AF750 only.

1.81SXU000023C0202

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

AF50 - AF1650 Non-reversing, mechanically interlocked, reversing AC & DC operated, UL rated, 3 phase

Ac

ro co ss nt the ac to line 1 rs

AF63-30-11-70

AF95-30-11-70

AF400-30-11-70

AF750-30-11-70

3 PoleGeneral purpose current AC1 UL motor switching current 208V Maximum UL Listed motor horsepower ratings 240V 480V 575/600V Standard auxiliary contacts NO NC Non-reversing Catalog number List price Mechanically interlocked Catalog number List price Reversing Catalog number List price

80 90 105 125 140 230 250 300 350 400 550 650 750 900 1260 1350 1650 2050

54 65 80 95 110 130 156 192 248 302 414 480 602 810 960 1080

15 20 25 30 30 40 50 60 75 100 125 150 200 250

20 25 30 30 40 50 60 75 100 100 150 200 250 300 400 450

40 50 60 60 75 100 125 150 200 250 350 400 500 600 800 900

50 60 75 75 100 125 150 200 250 300 400 500 600 700 900 1000

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

AF50-30-11-70 AF63-30-11-70 AF75-30-11-70 AF95-30-11-70 AF110-30-11-70 AF145-30-11-70 AF185-30-11-70 AF210-30-11-70 AF260-30-11-70 AF300-30-11-70 AF400-30-11-70 AF460-30-11-70 AF580-30-11-70 AF750-30-11-70 AF1250-30-11-70 AF1350-30-11-70 AF1650-30-11-70 AF2050-30-11-70

$ 450 495 535 570 600 1,110 1,635 1,980 2,235 2,385 3,120 4,425 6,900 7,200 8,120 8,490 10,230 12,820

AF50M-30-11-70 AF63M-30-11-70 AF75M-30-11-70 AF95M-30-11-70 AF110M-30-11-70 AF145M-30-11-70 AF185M-30-11-70 AF210M-30-11-70 AF260M-30-11-70 AF300M-30-11-70 AF400M-30-11-70 AF460M-30-11-70 AF580M-30-11-70 AF750M-30-11-70

$ 953 1,116 1,399 1,470 1,605 2,655 3,870 4,545 5,055 6,030 6,705 13,275 18,375 19,725

AF50R-30-11-70 AF63R-30-11-70 AF75R-30-11-70 AF95R-30-11-70 AF110R-30-11-70 AF145R-30-11-70 AF185R-30-11-70 AF210R-30-11-70 AF260R-30-11-70 AF300R-30-11-70 AF400R-30-11-70 AF460R-30-11-70 AF580R-30-11-70 AF750R-30-11-70

$ 1,050 1,259 1,542 1,665 1,868 2,670 3,375 4,560 5,070 6,045 6,720 13,290 18,390 19,740

Coil voltage selection wide range AC/DC coilsAll catalog numbers include a 100-250V AC/DC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 24V coil is required for a AF110 contactor: AF110-30-11-72

Coil voltage selection AF50 to AF165024 - 60 DC 68 1 20 - 60 DC 72 2 AC/DC VOLTS, 40 - 60 Hz 48 - 130 AC/DC 100 - 250 AC/DC 69 70 3 250 - 500 AC//DC 71 4

1 AF400 AF1250, DC only. 2 AF50 AF300, DC only. 3 Only option for AF1350 - AF2050. 4 AF400 - AF750 only.

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule AA [OA] - AF50 AF110 Discount schedule AEA [OC] - AF145 - AF2050

1.91SXU000023C0202

1

ine el s h s t tor os tac r Ac conUL general purpose current AC1 UL Motor switching current

A/AF/AL9 - A/AF/AL110 Contactors for ring tongue termination AC & DC operated, UL rated, 3 phaseUL/CSA horsepower ratings 240V 480V 575/600V Auxiliary contacts NO NC AC operated Catalog number List price DC operated Catalog number List price

21 25 30 40 80 90 105 125 140

9 11 17 28 54 65 80 95 110

2 3 5 10 20 25 30 30 40

5 7.5 10 20 40 50 60 60 75

7.5 10 15 25 50 60 75 75 100

1 0 1 0 1 0 1 0 0 0 0 0 0

0 1 0 1 0 1 0 1 0 0 0 0 0

A93010RT-84 A93001RT-84 A123010RT-84 A123001RT-84 A163010RT-84 A163001RT-84 A263010RT-84 A263001RT-84 A503000RT-84 A633000RT-84 A753000RT-84 AF95B3011RT-70 AF110B3011RT-70

$ 83 90 122 172 363 417 475 927 986

AL93010RT-81 AL93001RT-81 AL123010RT-81 AL123001RT-81 AL163010RT-81 AL163001RT-81 AL263010RT-81 AL263001RT-81 AF503000RT-70 AF633000RT-70 AF753000RT-70 AF95B3011RT-70 AF110B3011RT-70

$ 152 186 207 211 262 582 647 687 927 986

Coil voltage selection AC coilsAll AC operated catalog numbers include a 120VAC coil. To select other coil voltages, substitute the code from the AC coils Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 240V coil is required for an A75 contactor: A753000RT-80

Coil voltage selection chart AC coilsCntr Hz type 12 60 A 50 A

24 81 81

Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 83 84 84 34 36 80 42 86 86 51 53 55 83 84 80 85 86 55

Coil voltage selection DC coilsAll DC operated catalog numbers include a 24VDC coil. To select other coil voltages, substitute the code from the DC coils Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 110V coil is required for an AE75 contactor: AE753000RT-86

For other voltages, see page 1.24.

Coil voltage selection chart DC coilsHz DC Contr. type AE 24 81 48 83 Volts 110 86 125 87 220 88 240 89

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.2. Add $ 20 to list price for each additional auxiliary, and see page 1.32 for available combinations. Only side-mounted blocks are allowed to be factory installed.

For other voltages, see page 1.24.

Auxiliary contact block with ring tongue terminationPositioning Maximum number of contact blocks Contact description Catalog number List price

Front mounting (C4-pole)

1 block A/AE9 A/AE110

2 NO & 2 NC 3 NO & 1 NC 4 NO

CA5-22ERT CA5-31ERT CA5-40ERT

$ 35

1.101SXU000023C0202

Discount schedule AA [OA] A9 - A110 Discount schedule ABA [OF] Auxiliary contact blocks

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

A9 AF1650 Non-reversing, mechanically interlocked, reversing NEMA rated, AC operated, 3 phase

Ac

ro co ss nt the ac to line 1 rs

A26N1-30-10-84

A145N4-30-11-84

AF400N6-30-11-70

NEMA size

Continuous current

Maximum motor horsepower ratings 200V 230V 460/575V

Standard Aux. contacts NO NC

Non-reversing Catalog number List price

Mechanically interlocked Catalog number List price

Reversing Catalog number List price

NEMA rated 00 0 1 2 3 4 5 6 7 8 9 18 27 45 90 135 270 540 810 1215 1.5 3 7.5 10 25 40 75 150 1.5 3 7.5 15 30 50 100 200 300 450 2 5 10 25 50 100 200 400 600 900 1 1 1 1 1 1 1 1 1 1 0 0 0 1 1 1 1 1 1 1 A9N00-30-10-84 $ 78 A16N0-30-10-84 102 A26N1-30-10-84 183 A50N2-30-11-84 330 A75N3-30-11-84 413 A145N4-30-11-84 825 A260N5-30-11-84 1,815 4,425 AF460N6-3011-70 AF750N7-3011-70 7,200 AF1650N83011-70 10,230 A9N00M-10-84 A16N0M-10-84 A26N1M-10-84 A50N2M-11-84 A75N3M-11-84 A145N4M-11-84 A260N5M-11-84 AF460N6M-11-70 AF750N7M-11-70 $ 255 345 405 713 1,155 2,235 4,485 13,275 19,725 A9N00R-10-84 A16N0R-10-84 A26N1R-10-84 A50N2R-11-84 A75N3R-11-84 A145N4R-11-84 A260N5R-11-84 AF460N6R-11-70 AF750N7R-11-70 $ 315 413 480 810 1,298 2,250 4,500 13,290 19,740

Coil voltage selection A contactorsAll AC operated catalog numbers include a 120VAC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 240V coil is required for an A75 contactor: A75N3-30-11-80

ReversingReversing contactors are designed for reversing type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: A9 - A16 mounted on 35mm DIN rail A26 - A750 mounted on common baseplate For A9 - A750 contactors the NC electrical interlock is provided with the mechanical interlock.

Coil voltage selection wide range AC/DC coilsThe NEMA size 6,7 and 8 contactors are provided with a wide range coil voltage. They are shown with the standard 100-250V AC/DC coil. To select other ranges substitute the code from the coil voltage selection chart for the two digits after the last dash in the catalog number. Ex.: A 24V coil is required for the AF460N6 contactor: AF460N6-3011-68

Coil voltage selection A contactorsHz Cntr type 12 60 A 50 A Volts 24 81 81 48 110 120 125 208 220 240 277 380 415 440 480 500 600 83 84 84 34 36 80 42 86 86 51 53 55 83 84 80 85 86 55

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.2. Add $ 20 to list price for each additional auxiliary, and see page 1.32 for available combinations.

For other voltages, see page 1.24.

Mechanical interlockMechanically interlocked contactors are designed for reversing, 2 speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: A9 - A16 mounted on 35mm DIN rail A26 - A750 mounted on common baseplate Power wiring is not included. For A9 - A110 contactors the NC electrical interlock is provided with the mechanical interlock.

Coil voltage selection AF460N6 to AF1650N8AC/DC VOLTS, 40 - 60 HZ24 - 60 DC 48 - 130 AC/DC 100 - 250 AC/DC 250-500 AC/DC

68 1

69

70 3

71 2

1 AF400 AF750, DC only. 2 AF400 - AF750 only. 3 Only option for AF1650.

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule AA [OA] - A9 - A110 Discount schedule AEA [OC] - A145 - AF750

1.111SXU000023C0202

1

ine el s h s t tor os tac r Ac con

AE9 AF1650, AL9 AL26 Non-reversing, mechanically interlocked, reversing NEMA rated, DC operated, 3 phase

AE26N1-30-11-81

AF145N4-30-11-68

AF460N6R-11-68

AE & AF ContactorsNEMA size Continuous current

Maximum motor horsepower ratings 230V 460/575V

Standard Aux. contacts NO NC

Non-reversing Catalog number List price

Mechanically interlocked Catalog number List price

Reversing Catalog number List price

200V

NEMA rated 00 0 1 2 3 4 5 6 7 8 9 18 27 45 90 135 270 540 810 1215 1.5 3 7.5 10 25 40 75 150 1.5 3 7.5 15 30 50 100 200 300 450 2 5 10 25 50 100 200 400 600 900 1 1 1 1 1 1 1 1 1 1 0 0 0 1 1 1 1 1 1 1 AE9N00-30-11-81 $ 118 AE16N0-30-11-81 142 AE26N1-30-11-81 223 AE50N2-30-11-81 375 AE75N3-30-11-81 518 AF145N4-3011-70 1,110 AF260N5-3011-70 2,235 AF460N6-3011-70 4,425 AF750N7-3011-70 7,200 AF1650N83011-70 10,230 AE9N00M-11-81 AE16N0M-11-81 AE26N1M-11-81 AE50N2M-11-81 AE75N3M-11-81 AF145N4M-11-70 AF260N5M-11-70 AF460N6M-11-70 AF750N7M-11-70 $ 325 425 485 803 1,365 2,655 5,055 13,275 19,725 AE9N00R-11-81 AE16N0R-11-81 AE26N1R-11-81 AE50N2R-11-81 AE75N3R-11-81 AF145N4R-11-70 AF260N5R-11-70 AF460N6R-11-70 AF750N7R-11-70 $ 395 493 560 930 1,493 2,670 5,070 13,290 19,740

AL ContactorsMaximum motor horsepower ratings NEMA size Continuous current 208V 240V 460/575V Standard Aux. contacts NO NC Non-reversing Catalog number List price Mechanically interlocked Catalog number List price Reversing Catalog number List price

NEMA rated 00 0 1 9 18 27 1.5 3 7.5 1.5 3 7.5 2 5 10 1 1 1 0 0 0 AL9N00-30-10-81 AL16N0-30-10-81 AL26N1-30-10-81 $ 155 205 253 AL9N00M-10-81 AL16N0M-10-81 AL26N1M-10-81 $ 319 441 473 AL9N00R-10-81 AL16N0R-10-81 AL26N1R-10-81 $ 379 501 533

Coil voltage selection AE contactorsAll DC operated catalog numbers include a 24VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 125V coil is required for an AE75 contactor: AE75N3-30-11-87

ReversingReversing contactors are designed for reversing type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: AE9 - AE16 mounted on 35mm DIN rail AE26 - AE75 mounted on common baseplate For AE9 - AE75 contactors the NC electrical interlock is provided with the mechanical interlock.

Coil voltage selection AF wide range AC/DC coilsAll catalog numbers include a 100-250V AC/DC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 24V coil is required for a AF145 contactor: AF145N4-30-11-72

Coil voltage selection AF50 to AF165024 - 60 DC 68 1 20 - 60 DC 72 2 AC/DC VOLTS, 40 - 60 Hz 48 - 130 AC/DC 100 - 250 AC/DC 250 - 500 AC/DC 69 70 4 71 3

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.2. Add $ 20 to list price for each additional auxiliary, and see page 1.32 for available combinations.

Coil voltage selection AE & AL contactorsHz DC Contactor type AE, AL Volts 12 24 81 48 83 110 86 125 87 220 88 240 89

Mechanical interlockMechanically interlocked contactors are designed for reversing, 2 speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: AE9 - AE16 mounted on 35mm DIN rail AE26 - AE75 mounted on common baseplate Power wiring is not included. For AE9 - AE75 contactors the NC electrical interlock is provided with the mechanical interlock.1 AF400 AF750, DC only. 2 AF50 AF300, DC only. 3 AF400 - AF750 only. 4 Only option for AF1650.

1.121SXU000023C0202

Discount schedule AA [OA] - A9 - A110 Discount schedule AEA [OC] - A145 - AF750

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

A9 A/AE75 , EK110 EK1000, AL9 AL26 AC & DC operated, UL rated, 4 pole

Ac

ro co ss nt the ac to line 1 rs

A9-40-00

A75-40-00

EK175C4P-PL

4 Pole 4 NO power polesUL general purpose current AC operated DC operated AC operated Catalog number List price DC operated Catalog number List price

21 30 40 65 80 105 150 200 250 300 400 600 1000 1

21 30 40 65 80 105 150 200 250 300 400 600 1000 1

A9-40-00-84 A16-40-00-84 A26-40-00-84 A45-40-00-84 A50-40-00-84 A75-40-00-84 EK110C4P-1L EK150C4P-1L EK175C4P-1L EK210C4P-1L EK370C4P-1L EK550C4P-1L EK1000C4P-1L

$ 120 165 228 360 413 525 743 1,013 1,763 2,025 4,650 6,510 9,000

AL9-40-00-81 AL16-40-00-81 AL26-40-00-81 AE45-40-00-86 AE50-40-00-86 AE75-40-00-86 EK110C4P-PL EK150C4P-PL EK175C4P-PL EK210C4P-PL EK370C4P-PL EK550C4P-PL EK1000C4P-PL

$ 141 192 246 420 473 570 953 1,238 1,988 2,280 5,010 7,005 9,700

4 Pole 4 NC power polesUL general purpose current AC operated AC operated Catalog number List price

30

A16-04-00-84

$ 165

4 Pole 2 NO & 2 NC power polesUL general purpose current AC operated DC operated AC operated Catalog number List price DC operated Catalog number List price

21 30 40 65 105

21 21 30 65 105

A9-22-00-84 A16-22-00-84 A26-22-00-84 A45-22-00-84 A75-22-00-84

$ 120 165 228 360 525

AL9-22-00-81 AL16-22-00-81 AL26-22-00-81 AE45-22-00-86 AE75-22-00-86

$ 141 215 278 420 570

Coil voltage selectionAll AC operated catalog numbers include a 120VAC coil. All DC operated catalog numbers include a 110VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 240V coil is required for an A75 contactor: A75-30-00-80

Coil voltage selection A contactorsHz Cntr type 12 60 50 A A 24 81 81 83 83 84 84 84 34 Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 36 80 80 42 85 86 86 86 51 53 55 55

For other voltages, see page 1.24.

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.2. Add $ 20 to list price for each additional auxiliary, and see page 1.32 for available combinations.

Coil voltage selection EK contactorsHz 60 50 DC Contr. type EK EK EK 24 F N Y W G 1 P Q 1 B J R Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 2 C Z 3 M T 3 4 5 6

Accessories for EKPlease consult factory.

For other voltages, consult factory. 24 & 48VAC coils are not available for sizes EK550. For these applications, use an interposing control relay.

Coil voltage selection AE & AL contactorsHz DC Contr. type AE, AL 12 24 81 Volts 48 83 110 86 125 87 220 88 240 89

For other voltages, see page 1.24. 1 Not UL Listed. IEC value AC1 for 40C.

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule AA [OA] - A9 - A75 Discount schedule AEA [OC] - EK110 - EK550

1.131SXU000023C0202

1

ine el s h s t tor os tac r Ac con

AF45 - AF75 AC & DC operated, UL rated, 4 pole

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.8. Add $ 20 to the list price for each additional auxiliary and see page 1.32 for available combinations. If auxiliary contacts are required for AF50 AF750 contactors, add $ 40 to the list price and change the 8th & 9th digits in the catalog number from "00" to "11".

4 Pole 4 NO power polesGeneral purpose AC1 Auxiliary contacts NO NC Catalog number List price

65 80 105

0 0 0

0 0 0

AF45-40-00-70 AF50-40-00-70 AF75-40-00-70

$ 385 435 645

4 Pole 2 NO - 2 NC power polesGeneral purpose AC1 Auxiliary contacts NO NC Catalog number List price

65 105

0 0

0 0

AF45-22-00-70 AF75-22-00-70

$ 385 645

These contactors (2 NO & 2 NC power poles) can be used for controlling either 2 separate circuits, i.e. 2 loads with 2 separate supplies, or 1 circuit comprising 2 separate loads with 1 single supply (see diagrams below). When the contactor operates, there is no mechanical overlapping between the NO main poles and NC main poles: Break before Make. These contactors (2 NO & 2 NC power poles) are not suitable for a reversing starter or a wye-delta starter or for controlling a single load from 2 separate supplies.

1 single supply and 2 separate loadsSupply

2 separate supplies and 2 separate loads"Main" supply "Back-up" supply

A1

1

R3

R5

7

A1

1

R3

R5

7

A2

2

R4

R6 Load Load

8

A2

2

R4

R6 Load Load

8

Coil voltage selection wide range AC/DC coilsAll catalog numbers include a 100-250V AC/DC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number. Ex.: A 24V coil is required for a AF45 contactor: AF45-22-00-72

Coil voltage selection AF50 to AF75AC/DC VOLTS, 40 - 60 HZ24 - 60 DC 20 - 60 DC 48 - 130 AC/DC 100 - 250 AC/DC

68 1

72 2

69

70

1 AF400 AF750, DC only. 2 AF50 AF300, DC only.

1.141SXU000023C0202

Discount schedule AA [OA] - AF45 - AF75

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

UA26 UA110 for 3 phase capacitor switching, 3 phase AC operated

Ac

ro co ss nt the ac to line 1 rs

UA75-30-00-84 Max kvar switching capacity 240V 480V 575/600V NO

UA95-30-00-84 Standard auxiliary contacts NC Catalog number List price

12.5 16 20 27.5 35 40

25 32 40 55 70 80

30 40 50 70 75 85

1 1 0 1 0 1 0 1 0 1

0 0 0 1 0 1 0 1 0 1

UA26-30-10-84 UA30-30-10-84 UA50-30-00-84 UA50-30-11-84 UA75-30-00-84 UA75-30-11-84 UA95-30-00-84 UA95-30-11-84 UA110-30-00-84 UA110-30-11-84

$ 225 338 345 375 450 480 465 495 525 570

For 3 phase capacitors carrying out single bank or stepped bank compensation. Max. peak current : 100 times the capacitor nominal r.m.s. current at Ue 500V or 90 times for Ue>500V Electrical durability: 100,000 operating cycles.

Power in kvarContactor 208V 240V 480V 600V Max amps

UA26 UA30 UA50 UA75 UA95 UA110 A145 A185 A210 A260 A300 AF400 AF460 AF580 AF750

3.5 7.0 10.5 21.5 25.0 28.5 43 57 66 75 88 119 142 178 214

4.0 8.0 12.5 25.0 29.0 33.0 50 66 77 87 101 137 164 205 247

8.0 16.5 25.0 50.0 58.0 66.0 100 133 153 174 203 274 329 411 495

10.0 20.5 31.0 62.0 72.0 83.0 125 166 192 218 254 343 410 514 618

10 20 30 60 70 80 120 160 185 210 245 330 396 495 595

Coil voltage selectionAll AC operated catalog numbers include a 120VAC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection Chart for the two digits after the last dash in the catalog number.

Coil voltage selection chartCntr Hz type 12 60 A 50 A

Auxiliary contact blocksFor additional auxiliary contact blocks, see catalog number explanation on page 1.2. Add $20 to list price for each additional auxiliary, and see page 1.32 for available combinations.

24 81 81

Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 83 84 84 34 36 80 42 86 86 51 53 55 83 84 80 85 86 55

For other voltages, see page 1.24.

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Discount schedule AA [OA] - UA26 - UA110

1.151SXU000023C0202

ine el s h s t tor os tac 1 cr n A co

Accessories forA/AF/AL&AEcontactorsAuxiliary contact blocks Standard Positioning Maximumnumber ofcontactblocks Contact Description Catalog number List price

F rontmounting (singlepole) CAL5-11 CA5-10

4blocks:A9A26 AE9AE26 AL9AL26 5blocks:A30,A40,AE30,AE40,AL30,AL40 6blocks:A45A110 AE45-AE110 AF45-AF110

1N.O. 1N.C. 1N.O.Earlymake 1N.C.Latebreak 4N.O. 3N.O.&1N.C. 2N.O.&2N.C. 4N.C. 2N.O./2N.C.1 3N.O.&1N.C. 2N.O.&2N.C. 1N.O.&3N.C. 4N.C. 4N.O. 2N.O./2N.C.1 1N.O.&1N.C. 1N.O.&1N.C.

CA5-10 CA5-01 CC5-10 CC5-01 CA5-40E CA5-31E CA5-22E CA5-04E CA5-11/11E CA5-31M CA5-22M CA5-13M CA5-04M CA5-40N CA5-11/11M CAL5-11 CAL18-11 $ 15

A9A26-40-00 A30 A110 F rontmounting 1block: AE9AE110 (4pole) 1block:

A9A40-30-10 AL9AL40-30-10

30

2blocks:A9A75,AE9-AE45 1block: AE50AE75,AL9AL40

idemounting 1block: A/AE/AF95-A/AE/AF110 S (2pole) 2blocks:A145A300,AF145-AF2050 2blocks:A145A300,AF145-AF2050

1N.O.&1N.C.(insideLorR) CAL18-11 1N.O.&1N.C.(outside,LorR) CAL18-11B

Auxiliary contact blocksFrontmounting,switchinglowvoltageandlowcurrent Positioning Maximumnumber ofcontactblocks Contact Description Degreeof protection Catalog number List price

4blocks:A9A26 rontmounting F AE9AE26 (singlepole) AL9AL26 5blocks:A30,A40,AE30,AE40,AL30,AL40 6blocks:A45A110 AE45-AE110 AF45-AF110

1N.O. 1N.C. 1N.O. 1N.C. 1N.O. 1N.C. 1N.O. 1N.C.

IP40 IP40 IP40 IP40 IP67 IP67 IP67 IP67

CE5-10D0.1 CE5-01D0.1 CE5-10D2 CE5-01D2 CE5-10W0.1 CE5-01W0.1 CE5-10W2 CE5-01W2

$ 38

42

1Includes1N.O.&1N.C.overlapping

1.161SXU000023C0202

Discount schedule ABA [OF]

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Accessories Auxiliarycontactblock technicaldata CA5/CAL5-11/CAL18-11/CC5TypesStandards Rated insulation voltage Ui accordingtoIEC 947-5-1 accordingtoUL/CSA Rated operational voltage Ue Conventional thermal current Ith Rated operational current Ie inAC-15acc.toIEC 947-5-1 inDC-13acc.toIEC947-5-1 Connecting terminals Connecting capacity Rigid solid Flexible with cable end Mechanical durability Max. switching frequency Electrical durability Max. switching frequency Rated making capacity Rated breaking capacity Rated short-time withstand current Icw q = 40C Min. switching capacity Short-circuit protection-gG(gl)fuses Power loss per pole at 6 A Degree of protection accordingtoIEC529, IEC144,DIN40050andNFC20-010 1s 0.1 s A W A A 17V/1mA 10 0.15 IP20 24to127V 220 to 240 V 380to440V 500to690V 24V 48V 72V 125V 250V V V ~ V A A A A A A A A A A 690 600 24to690 16 6 4 3 2 6 2.8 1 0.55 0.3 M3.5(+,-)pozidriv2screw withcableclamp 1 to 4 cycles 10million,A9-A75; 3600 Seecurvebelow 1200 10 x IeAC-15 10 x IeAC-15 100 140 24V/50mA 0.75to2.5 0.75to2.5

Ac

ro co ss nt the ac to line rs

1

1-pole CA5, 4-pole CA5 2-pole CAL5-11 and 1-pole CC5IEC 947-5-1andEN60947-5-1

CAL18-11 CAL18-11B

690 690

(deliveredinopenposition.Screwsofunusedterminalsshouldbetightened).

1 or 2 x mm2 1 x mm2 2 x mm2

5million,A/AF95-A/AF185; 3million,A/AF210-AF750; 0.5million,AF1350&AF1650

cycles/h cycles/h

CAL18Million ops.

CA5, CAL530

30 20 10

20 10 5 CA 5, CAL 5 3 2 1 0.5 0.3 0.2

A/AF210...AF750

3 2 1

AF1350/AF1650

0.5 0.3 0.2 0.1 0.02 0.05 0.1 0.2 0.3 0.5 1 2 3 4 5 6 10

Million ops

A/AF95...A/AF185 5

Breaking current (A)

0.1 0.02

0.05

0.1

0.2 0.3

0.5

1

2

3

4 5 6

10

Electrical durability AC-15accordingtoIEC947-5-1 makingcurrent:10x Iewherecos=0.7andUe breakingcurrent: Iewherecos = 0.4 and Ue Thecurvesoppositeshowtheelectricaldurabilityoftheauxiliarycontactblocks accordingtobreakingcurrentIc. Thesecurveshavebeenplottedforresistiveandinductiveloadsupto690 V,40to60Hz. Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Breaking current (A)

1.171SXU000023C0202

ine el s h s t tor os tac 1 cr n A co

Accessories Auxiliarycontactblock technicaldata CE5

Auxiliary contact blocks for switching low level voltage and currentTypesCE5-10D0.1 CE5-01D0.1 CE5-10W0.1 CE5-01W0.1 Version 100 mA CE5-10DZ CE5-01DZ CE5-10WZ CE5-01WZ Version 2 A

Standards Approvals Rated insulation voltage Ui accordingtoIEC 947-5-1 accordingtoUL/CSA Rated operational voltage Ue Rated operational current Ie inAC-15orAC-14acc.toIEC947-5-1 inDC-12acc.toIEC947-5-1

IEC 947-5-1andEN60947-5-1 UL/CSA

V V V 24V 60 V 110 V 220 V A A A A A

250 125 125 0.1 0.1 0.1 0.1 0.1 3V/1mA 10 -8 M3.5(+,-)posidriv2screwwithcableclamp

250 250 250 2 2 0.5 0.2 0.1 17V/1mA

Minimal switching Reliability for the minimal switching Connecting terminals Connecting capacity Rigidsolid Flexiblewithcableend Short circuit protection Degree of protection accordingtoIEC529,IEC144,DIN40050,NFC20-010 Mounting Dimensions

100 mA

1ou2(1...4)mm2 1ou2(0.75...2.5)mm2 10 A

IP20 Frontmountingoncontactors:A,AE,TAE9...110,AL,AF,GA,N,NE IdenticaltothoseofCA5singlepole

1.181SXU000023C0202

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Accessories forA/AF/AL&AEcontactorsPneumatic timers Mounting on Timing range Contacts N.O.N.C.

Ac

ro co ss nt the ac to line rs

1

Catalog number

List price

A9A75 AE9AE75 AL9AL40

Ondelay0.140s Ondelay10180s Offdelay0.140s Offdelay10180s

1 1 1 1

1 1 1 1

TP40DA TP180DA TP40IA TP180IA

$ 108

TP40DA

Interlocks for two horizontally mounted contactors A9-A110 Feature Mounting on Contacts N.O.N.C. Catalog number List price

Mechanical/electrical Mechanical/electrical Mechanical

A/AE/AL9A/AE/AL40 A45A110 A/AE/AL9A/AE/AL40

2 2

VE5-1 VE5-2 1 VM5-1

$ 45 45 21

Interlocks for two horizontally mounted contactorsA95-AF1250contactors VE5-1 Feature Left contactors Right contactors Catalog number List price

Mechanical Mechanical Mechanical

A95 A300 A210 A300 AF400 AF1250

A145 A300 AF400 AF460 AF400 AF1250

VM300H VM300/460H VM750H

$ 110 130 150

Interlocks for two vertically mounted contactorsA95-AF1250contactors Feature Top contactor Bottom Contactor Catalog number List price

Mechanical Mechanical Mechanical

A95 A300 A210 A300 AF400 AF1250

A145 A300 AF400 AF460 AF400 AF1250

VM300V VM300/460V VM750V

$ 205 250 270

VM300H

Interlocks for two horizontally mounted contactorsAF1350-AF2050contactors Feature Left contactor Right Contactor Catalog number List price

Mechanical

AF1350 AF2050

AF1350 AF2050

VM1650H

$ 655

LK75-L

LK75-F

LK110

Auxiliary lead terminals Connections Mounting on Catalog number List price

Connectsfromside Connectsfromtop Connectsfromside

A50 A75 A50 A75 A95 A110

LK75-L LK75-F LK110

$ 15 15 23

1UsetypeVE5-2formechanicalandelectricalinterlockingbetweenA30/A40andA50-A75contactors.

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Discount schedule ABA [OF]

1.191SXU000023C0202

ine el s h s t tor os tac 1 cr n A co

Accessories forA/AE/AL/AFcontactorsTerminal lug kits(Setof3) Wire range 6300MCM 4 400 MCM (2)4-500MCM (2)2/0500MCM (3)2/0500MCM (4)4/0500MCM (4)1/0750MCM (6)1/0750MCM For contactor A145 A185 A210 A300 A210 A300 AF400 AF580 AF580 AF1250 A F1350 AF1350 AF2050 AF1350 AF2050 Catalog number ATK185 ATK300 ATK300/2 ATK580/2 ATK750/3 ATK1350/4 ATK1650/4 ATK1650/6 List price $ 45 68 110 150 225 235 335 560

ATK185

Contact kits 3 Pole For contactors A/AE/AF50 A/AE/AF63 A/AE/AF75 A/AE/AF95 A/AE/AF110 A/AF145 A/AF185 A/AF210 A/AF260 A/AF300 AF400 AF460 AF580 AF750 AF1250 AF1350 AF1650 AF2050 A/AE45 A/AE50 A/AE75 UA50 UA75 UA95 UA110

Catalog number ZL50 ZL63 ZL75 ZL95 ZL110 ZL145 ZL185 ZL210 ZL260 ZL300 ZL400 ZL460 ZL580 ZL750 ZL1250 ZL1350 ZL1650 ZL2050 ZLT45 ZLT50 ZLT75 ZLU50 ZLU75 ZLU95 ZLU110

List price $ 113 135 158 225 255 300 420 525 855 1,020 1,716 2,434 3,795 3,960 5,280 4,255 4,890 6,290 150 150 210 150 215 306 347

ATK750/3

ZL75

4 Pole 3 Pole

Mechanical latchesZL145 For contactors Catalog number List price

A9-A75,AE45-AE75,&AL9-AL40

WB75A-

$ 84

-Coilvoltagesuffix.RefertoCoilVoltageSelectionchartandsubstitutethedesiredcoilvoltagesuffixforthe.

Coil voltage selection chart mechanicallatchesforA,AE&ALcontactors50Hz(AC/DC) 60Hz(AC) Voltage code 50Hz(DC) 60Hz(AC) Voltage code

WB75A-04

24 42 48 1 10

24 28 42 48 48 55 110 127

01 02 03 04

220 230 230 240 380 415 415 440

220 255 230 277 380 440 440 480

06 05 07 08

Range: WB75AforcontactorsA9A75,AL9AL40,AE45AE75andcontrolrelaysNandNL. Description:WB75Ablock:containsamechanicallatchingdevicewithelectromagneticimpulseunlatching(ACorDC) ormanualunlatching.Captivescrewtypeconnectingterminals,built-incableclamps,M3.5(=,-)posidrive1screwwith screwdriverguidance,delivereduntightenedandprotectedagainstaccidentaldirectcontact. Operation: Afterclosing,thecontactorcontinuestobeheldintheclosedpositionbythelatchingmechanismshouldthe supplyvoltagefailatthecontactcoilterminals. Contactoropeningcanbecontrolled: Electricallybyanimpulse*(ACorDC)ontheWB75Ablockcoil.Thecoilisnotdesignedtopermanentlyenergized. ManuallybypressingthepushbuttononthefrontfaceoftheWB75Ablock. Mounting: WB75Aisclippedontothefrontfaceofthecontactor.

Identification markers BA5-50 Mounting on Coil voltage Catalog number List price

A/AE/AL/AF9A/AE/AL/AF110 Discount schedule ABA [OF]

Packof50

BA5-50

$ 15

1.201SXU000023C0202

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Accessories forA/AE/AL/AFcontactorsConnection kits for reversing Mountingon3polecontactors

Ac

ro co ss nt the ac to line rs

1

Catalog number

List price

A/AE/AL9A/AE/AL16 A/AE/AL26A/AE/AL40 A/AE/AF50A/AE/AF75 A/AE/AF95,A/AE/AF110 A/AF145A/AF185 A/AF210A/AF300 AF400 AF460 AF580AF750

BER16V BER40V BEM75-30 BEM110-30 BEM185-30 BEMA300-30 BEM460-30 BEM750-30

$ 35 49 165 180 260 470 850 1,200

BER...

Application Connectionsbetweenthemainpolesoftwo 3 pole contactorsmountedsidebysidesothattheyoperateasreversing contactors.BEM...

A1

1 2

3 4

5 6

1 2

3 4

5 6

A1

Description Theconnectionkitsforreversingcontactorsaremadeupofthreereversingconnectionsandthreephasetophase connections. BER16V Moldedplastic,solidcopperbars BER40V Moldedplastic,solidcopperbars BEM75and110-30 Insulated,solidcopperbars

A2

A2

Connection kits for phase to phase Mountingon3polecontactors Catalog number List price

BEM circuit diagram

A/AE/AF50, A/AE/AF75 A/AE/AF95, A/AE/AF110 A/AF145 A/AF185 A/AF210 A/AF300 AF400 AF460 AF580 AF750

BES75-30 BES110-30 BES185-30 BESA300-30 BES460-30 BES750-30

$ 75 90 130 200 425 650

BES...A1 1 2 3 4 5 6 1 2 3 4 5 6A1

Theconnectionkitforphasetophasecontactorsismadeupofthreephasetophasebusbars.

Connection kits for wye-delta startersMounting on contactors Line and delta contactor Wyecontactor Catalog number List price

A2

A2

BES110 connection diagram

BED...

A9 A12 A16 A26 A30 A40 A50 A63 A75 A95 A110 A145 A185 A210 A260/A300 AF400/AF460 AF460 AF580 AF750

A9 A9 A12 A16 A26 A26 A30 A40 A50 A75 A95 A110 A145 A185 A210 A260/A300 AF400 AF400/AF460 AF580

BEY16V-2 BEY26-2 BEY40-2 BED50U BED75U BED95U BED110U BED145U BED185U BED210U BED300U BED400U BED460U BED580U BED750U

$ 46 76 76 165 180 195 225 250 290 375 500 850 900 1,250 1,450

Application Connectionsbetweenthemainpolesofawye-deltastarter.BEY...

Description Theconnectionkitsforwye-deltastartersaremadeupof: Threelinecontactor/wyecontactorconnectionslineside. Threewyecontactor/deltacontactorconnectionsload side. TheshortingconnectionfortheScontactor. BEY16V-2,BEY26-2,BEY40-2Moldedplastic,solid copperbars BED50UthruBED750UInsulated,solidcopperbars. Theaboveconnectionsetsallowamechanicalinterlockunitto bemountedbetweenthewyeanddeltacontactorsifrequired.

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Discount schedule ABA [OF]

1.211SXU000023C0202

ine el s h s t tor os tac 1 cr n A co

Accessories forA/AE/AL/AFcontactorsAdditional terminal blocks

Mountingon3polecontactors

Wire range

Catalog number

List price

A/AE/AL9 A/AE/AL16(setof2) A/AE/AL26(setof2) A/AE/AL30 A/AE/AL40 A/AE/AF50 A/AE/AF75 A/AE/AF95 A/AE/AF110

166 146 124 102 81

LD-16 LD-26 LD-40 LD-75 LD-110

$ 20 22 26 28 30

UtilizationTheLDseriesterminalblockisdesignedtoincreasetheconnectioncapacityofthecontactoronwhichitis mounted.TheLD75andLD110terminalblocksaremountedinthethreeindependentapertureslocatedabovethebuilt-in connectors.

Terminal extensions Mounting oncontactors Catalog number List price

LD110

A/AE/AF50A/AE/AF75 A/AE/AF95,A/AE/AF110 A/AF145A/AF185 A/AF210A/AF300 AF400 AF460 AF580AF750

BEXT-75 LW110 LX185 LX300 LX460 LX750

$ 15 95 90 140 195 225

Application Theyaredesignedtoincreasethewidthofthecontactorterminalpadstoallowlargerconnectorstobemounted. Description Terminal extension setscontain3bars.

Terminal shrouds twopiecesBEXT-75 For contactor Catalog number List price

LX...

A/AF145 A/AF185forflushmount A/AF145 A/AF185forextendedmount A/AF145 A/AF185forshortingbarLY...betweenA(F)145/A(F)185&TA200DU A/AF210 A/AF300forflushmount A/AF210 A/AF300forextendedmount A/AF210 A/AF300forshortingbarLY300 AF400 AF460forflushmount AF400 AF460 for extended mount AF580 AF1250forflushmount AF580 AF1250forextendedmount

LT185-AC LT185-AL LT185-AY LT300-AC LT300-AL LT300-AY LT460-AC LT460-AL LT750-AC LT750-AL

$ 10

20

Terminal enlargements For contactor Catalog number List price

LT185-AC

A/AF95 A/AF110 A/AF145 A/AF185 A/AF210 A/AF300 AF400 AF460 AF580 AF750 AF1250

LW110 LW185 LW300 LW460 LW750 LW1250

$ 95 120 130 295 355 375

Arc chutes For contactor Catalog number List price

A/AF145 A/AF185 A/AF210 A/AF300 A/AF400 A/AF460 A/AF580 A/AF750 AF1350 AF1650

ZW185 ZW300 ZW460 ZW750 ZW1650

$ 130 180 190 230 215

LT185-AL

LW...

1.221SXU000023C0202

Discount schedule ABA [OF]

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Accessories forA/AE/AFcontactorsVertical connection bars between contactor and MCCB threebars MCCB For contactor

Ac

ro co ss nt the ac to line rs

1

Catalog number

List price

BEA185/S3/S4

T1 T3 T3 S3,S4 T4 T4 T5 T5 S5 S51 S6

A/AE/AF50 A/AE/AF75 A/AE/AF95 A/AE/AF110 A/AF145 A/AF185 A/AF145 A/AF185 A/AF145 - A/AF185 A/AF210 - A/AF300 A/AF210 A/AF300 A/AF400 - A/AF750 A/AF210 A/AF300 AF400 AF460 AF400 AF750

BEA75/T1 BEA110/T3 BEA185/T3 BEA185/S3/S4 BEA185/T4 BEA210/T4 BEA300/T5 BEA750/T5 BEA300/S5 BEA400/S5 BEA750/S6

$ 85 95 60 60 70 70 75 115 75 95 115

Vertical connection bars between contactor and MCCB threebars BEAD185D/S3/S4 MCCB For contactor Catalog number List price

S3,S4 S4 S5 S5 S6

A/AF145 A/AF185 A/AF210 A/AF300 A/AF210 A/AF300 AF400 AF460 AF400 AF750

BEA185D/S3/S4 BEA210D/S4 BEA300D/S5 BEA400D/S5 BEA750D/S6

$ 70 80 85 105 125

Tobeusedwhenpowertakeoffisneeded(IP00)orwithotherbusbars.(EX:Reversing,IP20)

Horizontal connection busbars between contactor and MCCB threebars BEA185H/S4 MCCB For contactor Catalog number List price

S3,S4 S4 S5 S5 S6 S6

A/AF145 A/AF185 A/AF210 A/AF300 A/AF210 A/AF300 AF400 AF460 AF400 AF460 AF580 AF750

BEA185H/S4 BEA210H/S4 BEA300H/S5 BEA400H/S5 BEA460H/S6 BEA750H/S6

$ 150 220 220 435 660 670

Shorting bars, 2 poleLP185 For contactor Catalog number List price

A/AF145A/AF185 A/AF210A/AF300 AF400 AF460 AF580AF750

LP185 LP300 LP460 LP750

$ 35 50 50 50

Shorting bars, 3 pole LY... For contactor Catalog number List price

A/AE45A/AE/AF75 A/AE/AF95A/AE/AF110 A/AE/AF145A/AE/AF185 A/AE/AF210A/AE/AF300 AF400 AF460 AF580AF750

LF75 LY110 LY185 LYA300 LY460 LY750

$ 40 40 40 60 60 60

1 Notforusewithflangehandles.

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Discount schedule ABA [OF]

1.231SXU000023C0202

ine el s h s t tor os tac 1 cr n A co

Accessories forA/AE/AL/AFcontactors Coils&coilvoltagecodesCoils ACoperated For contactors Catalog number List price

ZA16-81

A9 A16 A26 A40 A45 A75 A95 A110 A145 A185 A210 A300

ZA16- ZA40- ZA75- ZA110- ZA185- ZA300-

$ 24 30 57 60 150 180

Coils DCoperated AE9 AE16 AE26 AE40 AE45 AE75 AE95 AE110 AE95 AE110 AF45 AF75 AF95,AF110 AF145AF185 AF210 AF300 AF400,AF460 AF580,AF750,AF1250 AF1350,AF2050(Setof2coilsonly) AF1350 AF2050 ZAE16- ZAE40- ZAE75- ZAE110- CCL18-01 ZAF75- ZAF110- ZAF185- ZAF300- ZAF460- ZAF750- ZAF1650- ZP1650 24 30 57 90 45 120 165 200 240 450 525 920 1,620

AuxiliaryincludinganinsertioncontactandavaristorforDCoperatedcontactors

Coils AC/DCoperated(coilandprintedcircuitboardexceptZAF1650)ZAF1650

Printed circuit boardAC/DCoperated Coilvoltagesuffix.RefertoCoilVoltageSelectionchartsbelowandsubstitutethedesiredcoilvoltagecodeforthe.ZP1650

Coil voltage selectionACoperated forA9A300;UA26UA110 VAC(50Hz) VAC(60Hz) Voltage Code

Coil voltage selectionDCoperated for AE contactors VDC Voltage code AE contactors

24 26 28 42 48 60 100 110 110115 120 125127 175 190 200 220 230 230 240 230240 230/400 380400 400415 440 500 550 660690

24 28 32 42 48 60 100 110 110 120 115127 140 150 208 220 200 220 230 240 240 260 277 230/400 400415 415440 480 500 600

81 16 17 82 83 73 74 2 84 89 3 29 30 34 36 75 2 80 88 42 62 1 63 1 85 86 51 53 55 56 58

12 24 42 48 50 60 75 110 125 220 240 250

80 81 82 83 21 84 85 86 87 88 89 38

Coil voltage selection AC/DCoperatedforAF50AF2050 VAC&VDC 40-60Hz Suffix Code

2460VDC 2060VDC 48130VAC/VDC 100250VAC/VDC 250500VAC/DC

68 72 69 70 71

4 5 7 6

1 OnlyforA9A16. 2 NotforA145A300 3 A145A300at60Hz,115Vonly 4 AF400AF1250,DConly 5 AF45AF300 6 AF400-AF750only 7 OnlyoptionforAF2050-AF1650

1.241SXU000023C0202

Discount schedule ABA [OF]

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Accessories for EK contactors Coils&coilvoltagecodes

Ac

ro co ss nt the ac to line rs

1

CoilsAC&DCoperatedContactor size

ACCoils Catalog number List price

DCCoils Catalog number List price

EK110,EK150 EK175,EK210 EK370,EK550

KH210- KH300- KH800-

$ 200 240 580

KH210- KH300- KH800-

$ 200 240 580

Coilvoltagesuffix.RefertotheCoilVoltageSelectionchartandsubstitutethedesiredcoilvoltagesuffixforthe.ACandDCoperatedcontactorsDONOThavethe samemagnetstructure.Therefore,DCcoilswillnotfitonanACmagnetstructureandviceversa.

Coil voltage selection AC operated forEK110EK550VAC(50Hz) VAC(60Hz) Voltage Code

Coil voltage selection DC operated forEK110EK550VDC Voltage Code

24 110 220 230 380400 400415 500

24 48 120 208 240 380 440 480 600

F N G 1 B 2 J Z 3 M 4 5 6

24 48 110 125 220 440

Y W P Q R T

Consultfactoryifothervoltagesarerequired.

Consultfactoryifothervoltagesarerequired.

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Discount schedule AB

1.251SXU000023C0202

ine el s h s t tor os tac 1 cr n A co

Accessories SurgesuppressorsforA/AE/AL/EKcontactorsSurge suppression device Mounting on Voltage range Catalog number List price

AE9toAE110 AL9toAL40 A9toA110;AE9toAE110 AL9toAL40 A9toA40 A45toA300 EK110toEK210 EK370toEK550 EK110toEK550 EK370toEK550

12 32VDC 25 65VDC 50 90VDC 77 150VDC 150 264VDC 24 50VAC/VDC 50 133VAC/VDC 110 250VAC/VDC 250 440VAC/VDC 24 50VAC 50 133VAC 110 250VAC 250 440VAC 24 50VAC 50 133VAC 110 250VAC 250 440VAC 24 48VAC 110 415VAC 48 110VAC 24 125VDC 220 600VAC

RT5/32 RT5/65 RT5/90 RT5/150 RT5/264 RV5/50 RV5/133 RV5/250 RV5/440 RC5-1/50 RC5-1/133 RC5-1/250 RC5-1/440 RC5-2/50 RC5-2/133 RC5-2/250 RC5-2/440 RC-EH250/48 RC-EH250/415 RC-EH800/110 RC-EH800/110 RC-EH800/600 52

RV5/50

$ 30

RC5-1/150

Technical dataType Control circuit Openingtime growthfactor Residualovervoltage orclippingvoltage Remarks

RT 5 /... transil diode

32 65 90 150 264

DC DC DC DC DC AC/DC AC/DC AC/DC AC/DC AC

2.5to3 1.1to1.5 1.2 to 3 1.1to1.5

50V 100V 150V 210V 390V 132V 270V 480V 825V 2 to 3 x Uc 205V 1100V

Advantages Drawback Advantages Drawback Advantages Advantages

Goodenergyabsorption Unpolarizedsystem Simple,reliablesystem Acertaindelayondropoutwhichdoesnot howeverreducecontactorbreakingcapacity.

Varistor

RV 5/... 50 133 250 440 seetable above

Highenergyabsorption;gooddamping Unpolarizedsystem ClippingasfromUvdr,thusvoltagefrontupto thispoint Veryfastclipping Attenuationofsteepfrontsandthusof highfrequencies Nooperatingdelays Highenergyabsorption:gooddamping Unpolarizedsystem TheRCsystemdampsthevoltage frontundertheUvdr*threshold.

RC 5-1/... or RC 5-2/... RC-EH 300/... Varistor + RC

RC-EH ... 800/110 AC/DC 800/600 AC

*Uvdr=Varistoroperatingvoltage(voltagedependentresistor),tolerance10%

1.261SXU000023C0202

Discount schedule ABA [OF]

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Accessories SurgesuppressorsforA/AE/AL/EKcontactors GeneralinformationGeneralU (V)1000

Ac

ro co ss nt the ac to line rs

1

Theoperationofinductivecircuitscausesovervoltages,inparticularonopeningofthecontactorcoil.T (s)100

0 1000

Theelectromagneticenergystoredbythecoilduringcontactorclosingisrestoredonopeningintheformofsurges,the slopeandamplitudeofwhichmayrisetoseveralkilovolts.Anumberofdrawbacksareobservedrangingfrominterference ontheelectronicdevicestobreakdownofinsulatorsandevendestructionofcertainsensitivecomponents. Thegraphoppositereproducestheoscillogramshowingvoltagedischargesattheterminalsofa42V/50Hzcoilwithout peakclipping.Thecoilwasswitchedby8series-connectedpolesofacontactorrelay. Followingaburstofdischargeswithaverysteepslopeadampedoscillationemergeswithapeakvalueof3500V.

0

100

Overvoltage factorTheovervoltagefactorkisdefinedastheratioofthemaximumovervoltagepeakvalues tothepeakvaluec ofthecoil ratedcontrolvoltageUc: smax. k=_______ c inDC: smax. k=_______ Uc orinAC: s max. k=_______ Uc2

3500 Forexamplethefollowingisobtainedfortheabovegraph:k=_____ 60 42 2

Surge suppressorsToguardagainsttheharmfuleffectsoftheseovervoltages,ABBhasdevelopedarangeofsurgesuppressorsdesignedto reducethekfactordefinedaboveandtolimitorevencompletelyeliminatethehighpre-dampingvoltagefrequencies. Eachcaseisdifferent,butthetechnicaldatatolerancesandthegeneroussizingofpartshaveenabledustoreducethe numberofvariants. Wehavechosenthefollowingsolutions:transildiodes,varistorsandRCblocks. Note:Avaristorisaresistorwhosevalueincreasestoaverylargeextentwhenacertainvoltageisappliedatits terminals.

Wiring diagramsTransil diode A1

Varistor (only) A1

RC type A1A1

Varistor + RC

A2

A2

A2

A2

General technical dataThehousingsandimpregnationresinsofthesurgesuppressorsaremadeofflame-resistantmaterialsinaccordancewith theUL94standard. Thesesystemsarenotpolarized,i.e.d.c.operateddevicesdonothavetobeconnectedinaspecificdirection. Operatingtemperature:-20to+70C Connectiontothecoilterminals(parallelmounting) For RT 5,RV 5,RC 5-1 and RC 5-2:clip-onforbothfixingandconnection. Mounting: RT 5,RV 5 and RC 5:clippedontothetoppartofthecontactorbase.Thismountingmethodpreventsany projectionsandchangeincontactordimensions. RC-EH:gluedtothetoppartofthecontactorbase.

U

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

1.271SXU000023C0202

ine el s h s t tor os tac 1 cr n A co

Accessories Interface relays for A contactorsInterface relays Mounting on contactortypes Control voltageUc Coil voltages Catalog number List price

N,A9A110

24VDC

24250V,50,60Hz

RA5-1

$ 75

NOTE:TheinterfacerelaysprovidedfortheAcontactorscanalsobeusedforUA,UA...,RAandGAtypes.

ApplicationRA5-1interfacerelaysaredesignedtoreceive24VDCsignalsdelivered byPLC'sorothersourceswithalowoutputpowerandrestorethem withsufficientpowertooperatethecoilsoftherelevantA9-A110 contactorsortheNcontrolrelays. IEConly

RA 5-1 interface relay for the A 9 A 110 contactors and N control relaysPLC Output Uc 250 VAC A0 RA 5 A2 24 VDC E2 E1 + +

DescriptionA30-30-10+RA5

RA5interfacerelaysaremadeupofaminiatureelectromechanicalrelay equippedwithaN.O.contactandwithalowconsumption24VDCcoil. TheinterfacerelaycoiliscontrolledbythePLCwhiletheN.O.contact ensuresswitchingofthepowercontactor. Coilswitchinggivesrisetoovervoltageswhichhaveadverseeffectson theelectronicdevices,insulatorsand,moregenerally,oncomponent lifetime.TheRA5-1isequippedwithsurgesuppressors: onthe24VDCrelaycoilviaadiode onthepowercontactorcoilviaavaristor.

A1 KM1 A2

RA5

Furthermore,theRA5-1areprotectedagainstrelaypolereversalbya diodeinsertedbetweentheE1andE2inputterminals.

ConnectionTheE1+andE2 inputterminalsmustbeconnected,accordingto theirpolarity,tothePLCoutput. TheRA5isequippedwithtwoterminalpadsforconnectiontotheA1 andA2terminalsofthecontactorcoil.Thiscoilissuppliedbetweenthe A0andA2terminalsoftheRA5.

MountingRA5:terminalpadsclampedinsidethecontactorcoilterminals.

1.281SXU000023C0202

Discount schedule ABA [OF]

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

Accessories InterfacerelaytechnicaldataGeneral technical dataCompliance with standards Rated insulation voltage Ui according to IEC 60947-4-1 Permissible ambient temperature: for free air operation: at Uc = 24 V d.c. (between E1 and E2) from 0.85 to 1.1 Uc for storage Climatic withstand Operating altitude Mounting position Fixing Connecting terminals (delivered in open position) Connecting capacity (min. ... max.) rigid solid exible with cable end Tightening torque recommended max. Degree of protection according to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529 2 x mm2 2 x mm2 Nm Nm m V a.c. IEC 60255-5 250

Ac

ro co ss nt the ac to line rs

1

C C C

-25 ... +70 -25 ... +55 -40 ... +70 Complies with that of associated contactors 3000 No limitation Using the contactor A1 and A2 terminal connecting parts M3.5 (+,-) pozidriv 2 screws with cable clamp 1 ... 4 0.75 ... 2.5 1.00 1.20 Protection against direct contact in acc. with EN 50274 RA5-1 wired and mounted on the associated contactor

Working dataSurge suppression: for contactor coil for interface relay coil Protection against polarity reversal between terminals E1 and E2 Interface relay operating time Total operating time, interface relay + contactor: between energization and: N.O. contact closing N.C. contact opening between de-energization and: N.O. contact opening N.C. contact closing ms Varistor Diode Diode Closing and drop-out 10

ms ms ms ms

20 ... 37 17 ... 32 17 ... 25 20 ... 28

Electrical input dataControl voltage (E1and E2 terminals) Uc rated value max. range at ambient temperature 20 C Max. consumption for Uc = 24 V d.c., = 20 C "0" status (relay open) for Uc or I c V d.c. V d.c. W V d.c. mA V d.c. ms 24 19 ... 30 0.3 2.4 3.7forcoilterminal-L4.2forbuilt-inauxiliaryterminals. 2WithLW110enlargementpiece.Seepage1.31.

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

1.551SXU000023C0202

1

ine el s h s t tor os tac r Ac conConnecting CharacteristicsContactor types: Main terminals Flattype A... AF...

IEC Technical data A/AF145AF750

145 145

185 18517.5 5

210 210

260 26020 5

300 300

400

46025 6 22.5

580

75040

6 22.5

6.5

8.5

10.2

10.5

6.5 12.5

Connectingcapacity(min....max.) Mainconductors(poles) Rigid: Rigid with connector singleforCucable singleforAl/Cucable doubleforAl/Cucable Flexible Barsorlugs Auxiliaryconductors (coilterminals) Rigidsolid Flexiblewithcableend Lugs l L L

1xmm2 2xmm2 mm2 mm2 mm2 1xmm2 2xmm2 Lmm mm> 1xmm2 2xmm2 1xmm2 2xmm2 Lmm lmm> 6...185 25...150 24 8 1...4 1...4 0.75...2.5 0.75...2.5 8 3.7 Protectionagainstdirectcontactacc.toVDE0106-part100 IP00 IP20 240 240 2x240 47/45 10 300 300 3x185 52/50 12

16...240 120...240 2x95...120 32 10

Degreeofprotectionacc.toIEC60947-1/ EN60947-1andIEC60529/EN60529 Mainterminals Coilterminals Built-inauxiliaryterminals Screw terminals Mainterminals Built-inauxiliaryterminals Tightening torque Mainpoleterminals recommended max. Coil terminals recommended max. Built-inauxiliaryterminals recommended Terminalmarkingandpositioning

Screwsandbolts M 8

M10

M10

M12

Coilterminals(deliveredinopenposition)

M3.5(+,-)pozidriv2screwswithcableclamp

Nm/lb.in Nm Nm/lb.in Nm Nm/lb.in max.

18/160 20 1.00/9 1.20 Nm

28/240 30

40/354 44

45/443 49

seepages1.36&1.37

1.561SXU000023C0202

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

IEC Technical data AF1350AF1650Connecting CharacteristicsContactor types: Main terminals Flattype Connectingcapacity(min....max.) Mainconductors(poles) Rigid: Rigid with connector singleforCucable singleforAl/Cucable doubleforAl/Cucable Flexible Bars or lugs Auxiliaryconductors (coilterminals) Rigidsolid Flexiblewithcableend Lugs L

Ac

ro co ss nt the ac to line rs

1

AF... 1xmm2 2xmm2 mm2 mm2 mm2 1xmm2 2xmm2 L mm mm > 1xmm2 2xmm2 1xmm2 2xmm2l L

1350

1650

100 12 1...4 1...4 0.75...2.5 0.75...2.5 8 3.7

100 12

1...4 1...4 0.75...2.5 0.75...2.5 8 3.7

Lmm lmm>

Degreeofprotectionacc.toIEC60947-1/ EN60947-1andIEC60529/EN60529 Mainterminals Coilterminals Built-inauxiliaryterminals Screwterminals Main terminals

IP00 IP20

IP00 IP20

Screwandbolts M12 M3.5(+,-)pozidriv2screwswithcableclamp

Coilterminals(deliveredinopenposition) Built-inauxiliaryterminals Tightening torque Mainpoleterminals recommended max. Coil terminals recommended max. Built-inauxiliaryterminals recommended max.

Nm/lb.in Nm Nm/lb.in Nm Nm/lb.in Nm

45/443 49 1.00/9 1.20

45/443 49 1.00/9 1.20

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

1.571SXU000023C0202

1

ine el s h s t tor os tac r Ac conContactor types: RatedinsulationvoltageUi accordingtoIEC60947-4-1 accordingtoUL/CSA RatedimpulsewithstandvoltageUimp. Standards Airtemperatureclosetocontactor fittedwiththermalO/Lrelay withoutthermalO/Lrelay forstorage Climaticwithstand Operatingaltitude

UL/CSA & IEC Technical data AL9AL40AL V V kV C C C m AL9 AL12 AL16 AL26 1000 600 8 DevicescomplyingwithinternationalstandardsIEC60947-1/60947-4-1 andEuropeanstandardsEN60947-1/60947-4-1 see"Conditionsforuse"page1.50,forcontrolvoltagelimitsandauthorizedmountingpositions -25to+55 -40to+70(55max.forTAE...contactors) -60to+80 < 3000 1/2sinusoidalshockfor11ms:nochangeincontactposition Shockdirection Makingposition Breakingposition A 20 g 20 g B1 10 g 5g B2 15 g 15 g C1 20 g 20 g C2 20 g 20 g AL30 AL40

acc.toIEC60068-2-30and60068-2-11-UTEC63-100specificationII

Shock withstand acc.IEC60068-2-27andEN60068-2-27 Mountingposition1(seepage1.50) C1A A B1 B2

C2

1.581SXU000023C0202

Low Voltage Products & SystemsABBInc.888-385-1221www.abb.us/lowvoltage

IEC Technical data AL9AL40Main Pole - Utilization CharacteristicsContactor types: AL RatedoperationalvoltageUemax. Ratedfrequencylimits Conventionalfree-airthermalcurrentIth acc.toIEC60947-4-1, opencontactors40C withconductorcross-sectionalareamm2 V Hz

Ac

ro co ss nt the ac to line rs

1

AL9

AL12

AL16 690 25-400

AL26

AL30

AL40

A 4

26 4

28 4

30 6

45 16

65 16

65 35

RatedoperationalcurrentIe/AC-1 forairtemperatureclosetocontactor 40C A Uemax.690V 55C A 70C 3 A 2 withconductorcross-sectionalareamm

{

25 22 18 2.5

27 25 20 4

30 27 23 4

45 40 32 6

55 55 39 10

60 60 42 16

UtilizationcategorieAC-3 forairtemperatureclosetocontactor 15 cycles/hour 5 Locked rotor 6 Overloads due to phase failure 7 Network undervoltage or overvoltage 8 Fluctuation of network frequency 9 Ambient temperature too high 10 Overheating due to external cause (i.e. overheating of bearings) 11 Motor cooling disturbed 12 13 for motors with special rotor Undercurrent protection on drop in load Protection of asymmetry: wrong phase direction rotation or asymmetrical load Earth fault protection Automatic disconnection for auxiliary load fault

14 15

Protectionefficiency: unsuitable very average efficiency perfectly efficient

Note:Fuses

Fuses do not protect motors against overloads. They are only used to protect installations and lines against short circuits. To ensure efficient protection of a motor against short circuits, it is advisable to use aM type fuses in association with thermal OLR relays. For the selection of fuses or circuit-breakers, refer to the indications given in this catalogue concerning contactors on the one hand and thermal O/L relays on the other. In general, fuse protection for direct-on-line starting must be sized as follows: aM fuses: choose the fuse rating immediately above the full load value of the motor current. gG (gI) fuses: determine the fuse rating immediately above the motor current value and choose the next highest fuse rating.

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

2.131SXU000023C0202

al m er load Th er s Ov elay r

Technical data Resistance and Joule losses per phase Short circuit protection

2

Resistance and Joule losses per phase, short circuit protectionSetting range current from to A A Resistance per phase m Joule losses per phase at max. setting W Setting range current from to A A Resistance per phase m Joule losses per phase at max. setting W

TA25DU 0.1 0.16 0.25 0.4 0.63 1.0 1.3 1.7 2.2 2.8 3.5 4.5 6.0 7.5 10 13 18 24

0.16 0.25 0.4 0.63 1.0 1.4 1.8 2.4 3.1 4.0 5.0 6.5 8.5 11 14 19 25 32

85850 85150 13750 5370 2190 1120 670 383 229 137 87.5 61 30.4 18.2 11.2 6.3 4.7 3.2 5.5 2.89 1.84 5.5 2.89 1.84 1.3 0.936 0.615 1.84 1.3 0.936 0.615

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.9 3.3 3.43 2.91 3.24 3.43 2.91 3.24 3.51 3.72 3.94 3.24 3.51 3.72 3.94

TA110DU 80 TA200DU 100 110 130 150

110 135 150 175 200

0.378 0.318 0.255 0.214 0.182

3.78 5.79 5.74 6.55 7.28 2.5 2.5 2.5

TA450DU 130 185 165 235 220 310

TA42DU 18 25 22 32 29 42 TA75DU 18 22 29 36 45 60 TA80DU 29 36 45 60 25 32 42 52 63 80 42 52 63 80

2.141SXU000023C0202

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Technical data Tripping curves

Th Ov erm e a re rloa l lay d s

2

TA25DU

TA75DU

TA110DU/SU

TA450DU

TA-DU thermal O/L relays are 3-pole with manual or automatic resetting mode selection. The resetting button can also be used for stopping. Built-in auxiliary contacts are physically separate and, consequently, can be used in different circuits (control circuit/indication circuit). Each relay is temperature compensated and ensures phase failure protection. Protective relays up to size TA75DU are protected against direct contact via the front face. Terminal shrouds are available for TA200DU to TA450DU size relays. The connecting terminals are delivered in open position with (+,-) pozidriv screws and screwdriver guidance. It is advisable to tighten unused terminal screws.

Thermal O/L relay tripping curvesTA25DU(tripping class 10A)120 100 80 60 40 20 10 8 6

TA42DU, TA75DU and TA80DU(tripping class 10A)120 100 80 60 40 20 10 8 6

TA110DU120 100 80 60 40 20 10 8 6

(tripping class 10A)

from cold state

Minutes

Minutes

Minutes

4 2 1 40 20

4 2 1 40 20

4 2 1 40 20

Tripping time

Tripping time

2 Phases 3 Phases 2 Phases

Tripping time

from cold state

from cold state 2 Phases 3 Phases

2 Phases

3 Phases

Seconds

Seconds

Seconds

10 8 6 4 2 1 0.8

2 Phases 3 Phases from warm state1 1.2 1.5 2 3 4 5 6 7 8 9 10

10 8 6 4 2 1 0.8 1 1.2

3 Phases

10 8 6 4 2

3 Phases 2 Phases

from warm state

from warm state1 1.5 2 3 4 5 6 7 8 9 10 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10

Tripping current in multiples of the setting current

Tripping current in multiples of the setting current

Tripping current in multiples of the setting current

TA200DU120 100 80 60 40 20 10 8 6

(tripping class 10A)

TA450DU120 100 80 60 40 20 10 8 6 4from cold state

(tripping class 10A)

Minutes

minutes

4 2 1 40 20Seconds

from cold state2 Phase 3 Phase

2 1 40 20

2 Phases 3 Phases

Triping time

Tripping time

10 8 6 4 2 1 0.8

2 Phases

seconds

10 8 6 4 2 1

2 Phase 3 Phase from warm state 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10

3 Phases

from warm state

1 1.2 1.5

2

3

4

5

6 7 8 9 10

Tripping current in multiples of the setting current

Tripping current as multiple of setting current

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

2.151SXU000023C0202

al m er load Th er s Ov elay r

Technical data, Class 20 OLR Resistance and Joule losses per phase Short circuit protectionShort-circuit protection (fuses) Type "2" co-ordination Type "1" co-ordination gL/gG A Fuse/600V K5 A 600V CB A mOhm at upper current setting W UL UL Resistance per phase Power Loss per phase

2Setting Range

from ... to A A

gL/gG A

Thermal overload relay TA25DU trip class 20 1.3 1.8 10 1.7 2.4 16 2.2 3.1 16 2.8 4.0 20 3.5 5.0 25 4.5 6.5 25 6.0 8.5 32 7.5 11 40 10 14 50 13 19 63 18 25 80 24 32 100 Thermal overload relay TA42DU trip class 20 18 25 100 22 32 125 29 42 160 Thermal overload relay TA75DU trip class 20 18 25 100 22 32 125 29 42 160 36 52 200 45 63 200 60 80 250 Thermal overload relay TA80DU trip class 20 29 42 160 36 52 200 45 63 200 60 80 250

25 25 25 25 25 25 32 40 50 63 80 100

6 10 10 15 20 25 35 45 60 60 70 100

-

670.3 381 235.3 140.7 91.2 54.5 32.1 15.5 12 6.3 4.7 3.2

2.2 2.2 2.3 2.3 2.3 2.3 2.3 1.9 2.4 2.3 3.0 3.3

160 160 160

80 100 150

80 80 80

5.5 2.89 1.84

3.43 2.91 3.24

160 160 160 200 250 250

80 100 150 175 200 250

80 80 80 125 125 125

5.5 2.89 1.84 1.3 0.936 0.615

3.43 2.91 3.24 3.51 3.72 3.94

160 200 250 250

150 175 200 250

80 125 125 150

1.84 1.3 0.936 0.615

3.24 3.51 3.72 3.94

Type 1 co-ordination according to IEC 60947-4-1: Under short-circuit conditions, the starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement of parts. Type 2 co-ordination according to IEC 60947-4-1: Under short-circuit conditions, the contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment. Standardtechnicaldata,operatingdataanddimensionsseeTA...RelayMainCatalog

2.161SXU000023C0202

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

Technical data, Class 20 OLR Short-circuit ratings

Th Ov erm e a re rloa l lay d s

2Setting Range A ... A Catalog number Voltage 480V Fuse K5 5 kA CB Fuse K5 10 kA CB Fuse K5 18 kA CB

1.3 1.8 1.7 2.4 2.2 3.1 2.8 4.0 3.5 5.0 4.5 6.5 6.0 8.5 7.5 11 10 14 13 19 18 25 24 32 18 25 22 32 29 42 18 25 22 32 29 42 36 52 45 63 60 80 29 42 36 52 45 63 60 80

TA25DU-1.8-20 TA25DU-2.4-20 TA25DU-3.1-20 TA25DU-4.0-20 TA25DU-5.0-20 TA25DU-6.5-20 TA25DU-8.5-20 TA25DU-11-20 TA25DU-14-20 TA25DU-19-20 TA25DU-25-20 TA25DU-32-20 TA42DU-25-20 TA42DU-32-20 TA42DU-42-20 TA75DU-25-20 TA75DU-32-20 TA75DU-42-20 TA75DU-52-20 TA75DU-63-20 TA75DU-80-20 TA80DU-42-20 TA80DU-52-20 TA80DU-63-20 TA80DU-80-20

TA25DU

TA42DU

TA75DU

TA80DU

6 10 10 15 20 25 35 45 60 60 70 100 80 100 150 80 100 150 175 200 250 150 175 200 250

80 80 80 80 80 80 125 125 125 80 125 125 150

6 10 10 15 20 25 35 45 60 60 70 100 80 100 150 80 100 150 175 200 250 150 175 200 250

-

6 10 10 15 20 25 35 45 60 60 70 100 150 150 200 150 150 200 250 250 250 150 175 250 250

-

Setting Range A ... A

Catalog number

Voltage 600V Fuse K5

5 kA CB Fuse K5

10 kA CB Fuse K5

18 kA CB

1.3 1.8 1.7 2.4 2.2 3.1 2.8 4.0 3.5 5.0 4.5 6.5 6.0 8.5 7.5 11 10 14 13 19 18 25 24 32 18 25 22 32 29 42 18 25 22 32 29 42 36 52 45 63 60 80 29 42 36 52 45 63 60 80

TA25DU-1.8-20 TA25DU-2.4-20 TA25DU-3.1-20 TA25DU-4.0-20 TA25DU-5.0-20 TA25DU-6.5-20 TA25DU-8.5-20 TA25DU-11-20 TA25DU-14-20 TA25DU-19-20 TA25DU-25-20 TA25DU-32-20 TA42DU-25-20 TA42DU-32-20 TA42DU-42-20 TA75DU-25-20 TA75DU-32-20 TA75DU-42-20 TA75DU-52-20 TA75DU-63-20 TA75DU-80-20 TA80DU-42-20 TA80DU-52-20 TA80DU-63-20 TA80DU-80-20

TA25DU

TA42DU

TA75DU

TA80DU

6 10 10 15 20 25 35 45 60 60 70 100 80 100 150 80 100 150 175 200 250 150 175 200 250

80 80 80 80 80 80 125 125 125 80 125 125 150

6 10 10 15 20 25 35 45 60 60 70 100 80 100 150 80 100 150 175 200 250 150 175 200 250

-

6 10 10 15 20 25 35 45 60 60 70 100 150 150 200 150 150 150 175 250 250 150 175 250 250

-

Low Voltage Products & SystemsABB Inc. 888-385-1221 www.abb.us/lowvoltage

2.171SXU000023C0202

al m er load Th er s Ov elay r

Technical data, Class 20 OLR Table for tripping time

2

Tripping times of thermal overload relays as a function of a multiple of the setting current from cold state (tolerance +/- 20% of the tripping time).Tripping times of thermal overload relays: at multiple of setting current 3 from ... to A A 4 5 6 7.2 8

Setting Range

Tripping times in seconds

Thermal overload relays TA25DU trip class 20 1.3 1.8 1.7 2.4 2.2 3.1 2.8 4.0 3.5 5.0 4.5 6.5 6.0 8.5 7.5 11 10 14 13 19 18 25 24 32 47.1 43.3 47.5 45.6 47.8 47.4 46.1 42.3 39.4 38.1 44.4 44.4 27 25 28 27 29 28 27 25 25 21 25 27 20.3 18.9 20.8 19.8 21.2 20.3 20 17.8 16.8 13.6 16.1 17.7 15.8 14.4 16 15.3 16 15.5 15 14.1 13 10 11 13 12.7 11.9 13.1 12.5 13.2 12.5 11.7 10.9 9.9 7.4 9 9.8 11.5 10.4 11.8 11 11.8 11 10 10.5 8.5 6.2 8 8.5

Thermal overload relays TA42DU, TA75DU, TA80DU trip class 20 18 25 51.6 29 22 32 67.9 38 29 42 58.8 33 36 ... 52 59.9