abb © ptmv - 1 abb medium voltage outdoor apparatus portfolio july 2004 brian johnson
TRANSCRIPT
AB
B© P
TM
V -
2
Typical Overhead Distribution System
B RB / R
B
B
S
Cutout OR1 Ph Sectionalizer
Switch - Manual- Automated
3PH
3PH
1PH
Line Recloser
CapacitorSwitch
Breaker /Recloser
3 Ph Sectionalizer
Switch - 1 Ph Manual OR Fuse OR Cutout
Switch - 1 Ph Manual
3PH
Reconfiguration Switch - Manual- Automated
AB
B© P
TM
V -
3
PTMV Outdoor Apparatus Portfolio
Outdoor Circuit Breakers
Reclosers
Automated Sectionalizers
Sealed Switches
Air Switches
Fused Cutouts
Not in portfolio, today: Voltage Regulators
Insulators, Cables, Hardware
AB
B© P
TM
V -
4
Outdoor Circuit Breakers
Dead Tank
Live Tank
Type R15-27 kV
ANSI
Type V38 kVANSI
Type SDB 1212 kVIEC
Type R-Mag15-27 kV
ANSI & IEC
Type OHB24-36 kV
IEC
AB
B© P
TM
V -
5
Type R Dead Tank Circuit Breaker
Vacuum Interruption
Spring Operated Mechanism
ANSI C37.06 – 1997
Dead tank design reduces cost of CTs and installation
Manufactured ABB, USA
VoltageRated
Continuous Current
Interrupting Current
15 – 27 kV 600 – 3,000 A 12 – 25 kA
AB
B© P
TM
V -
6
Type R-Magnetic Dead Tank Circuit Breaker
Vacuum Interruption
Magnetic Actuator Mechanism reduces maintenance costs and concerns
ANSI C37.06 – 1997 & IEC 56
Manufactured ABB, USA
VoltageRated
Continuous Current
Interrupting Current
15 – 27 kV 600 – 3,000 A 12 – 25 kA
AB
B© P
TM
V -
7
Type V Dead Tank Circuit Breaker Vacuum Interruption Spring Operated Mechanism 150 or 200 kV BIL High capacitor switching ratings to use
to protect and switch substation capacitor banks
Redundant vacuum bottle ANSI C37.06 – 1997 Manufactured ABB, USA
VoltageRated
Continuous Current
Interrupting Current
38 kV 1,200 – 2,000 A 25 – 40 kA
AB
B© P
TM
V -
8
Type SDB 12 Live Tank Circuit Breaker
Vacuum Interruption
Spring Operated Mechanism or Magnetic Actuator Drive
IEC
Manufactured ABB, India
VoltageRated
Continuous Current
Interrupting Current
12 kV 630 – 1,600 A 18.4 – 26.3 kA
AB
B© P
TM
V -
9
Type OHB Live Tank Circuit Breaker
SF6 Interruption
Spring Operated Mechanism
IEC
Manufactured ABB, India
VoltageRated
Continuous Current
Interrupting Current
24 – 36 kV 2,500 A 31.5 kA
AB
B© P
TM
V -
10
Automated Reclosers and Sectionalizers
OVR – 3 PhaseRecloser
15-38 kVANSI & IEC
OVS – 3 Phase
Sectionalizer15-38 kV
ANSI & IEC
Autolink –1 Phase
Sectionalizer12-38 kV
IEC
OVR –1 Phase Recloser
15-38 kVANSI & IEC
AB
B© P
TM
V -
11
OVR Three Phase Automated Recloser Embedded Vacuum Interrupters in
Solid Dielectric (no oil, nor SF6 to maintain)
Magnetic Actuators
Pole or Substation Mounting
Programmable PCD Control to automate system protection – loop schemes, automatic alternate settings
ANSI C37.60+90 – 1997
Manufactured ABB, USA
12 – 16 kA560 – 800 A15 – 38 kV
Interrupting Current
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
12
Ratings: 15 – 38 kV 630 / 800 Amp Up to 170 kV BIL 12.5 kA
Compact, lightweight HCEP Insulation Material Superior life – rated for 10,000 operations 2nd Generation Magnetic Actuators Environmentally friendly – no oil or gas ANSI C37.60+90 – 1997 Manufactured ABB, USA
OVR Single Phase Automated Recloser
AB
B© P
TM
V -
13
OVS Three Phase Automated Sectionalizer
Embedded Vacuum Interrupters in Solid Dielectric
Magnetic Actuators
Pole or Substation Mounting
Simple Sectionalizing Control
ANSI & IEC
Manufactured ABB, USA
16 – 20 kA630 A15 – 38 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous Current
Voltage
AB
B© P
TM
V -
14
Autolink Single Phase Sectionalizer
Single Phase Automatic Sectionalizer
Specialty device to reduce nuisance tripping problems
Magnetic Actuation to eliminate fuse replacement costs
IEC
Manufactured ABB T&D Ltd, Australia
VoltageRated
Continuous Current
Interrupting Current
Actuating Current
12 – 36 kV 250 A 6 kA 5 – 224 A
AB
B© P
TM
V -
15
Sealed Contact, Loadbreak Switches
OVS15-38 kV
ANSI & IEC
Sectos NXA38 kV
ANSI & IEC
Sectos NXBD12-24 kV
IEC
Sectos NXB12-24 kV
IEC
AB
B© P
TM
V -
16
OVS Automated Switch Embedded Vacuum Interrupters in Solid
Dielectric Magnetic Actuators ISD or PCD Control for simple applications or
sophisticated automation schemes ANSI & IEC Manufactured ABB Inc., USA Development project to add visible break 10,000 loadbreak operations SCADA Ready – integrated current sensing,
voltage sensing on frame, control cabinet space and power for customer communications
16 – 20 kA630 A15 – 38 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous Current
Voltage
AB
B© P
TM
V -
17
Sectos NXA Switch Disconnector
Two-position Load Break-Fault Make Switch Disconnector
Single or Double Spring Mechanism Manual (Hook stick) or Integrated Motor
Operated Shipped complete, Simple to install SF6 insulation IEC (General Purpose Type) & ANSI Manufactured ABB, China
12.5 kA
Short Time Withstand Current 3 Sec. Sym
630 A36 kV (38 kV ANSI)
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
18
Sectos NXB Switch Disconnector
Two or Three-position Load Break-Fault Make Switch Disconnector
Single or Double Spring Mechanism
Manual (Hook stick) or Integrated Motor Operated
Shipped complete, Simple to install
Available in single phase for special applications
SF6 insulation
IEC (General Purpose Type)
Manufactured ABB, China
20 kA
Short Time Withstand Current
3 Sec. Sym
630 A12 – 24 kV
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
19
Sectos NXBD Switch Disconnector Two Switches in Same Housing
Two Switched Ways and One Tapped Way
Two or Three-Position Load Break-Fault Make Switches Disconnector
Single or Double Spring Mechanism
Manual Operation by Hook Stick
Shipped complete, Simple to install
SF6 Insulation
IEC (General Purpose Type)
Manufactured ABB, China
20 kA
Short Time Withstand Current
3 Sec. Sym
630 A12 – 24 kV
Rated Continuous Current
Voltage
AB
B© P
TM
V -
20
Three Phase Air Switch Disconnects
Series ‘R’12-36 kV
IEC
Series ‘U’12-36 kV
IEC
NPS12-36 kV
IEC
AB
B© P
TM
V -
21
NPS Switch Disconnector Vertical and Horizontal Break Vertical and Horizontal Pole-
Mounted Optional Load Break and Load
Make Control Units (DTU) available IEC (Limited Purpose Type) Manufactured ABB, Finland Easy to localize, if desired
Up to 16 kA630 A12 – 24 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
22
Series ‘R’ Disconnect Switch
Vertical Break
Horizontal & Vertical Pole Mounted
Optional Load Break
IEC
Manufactured ABB, Australia
Up to 31.5 kA800 – 2000 A12 – 36 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
23
Series ‘U’ Disconnect Switch
Side Break
Horizontal & Vertical Pole Mounted
Optional Load Break
IEC
Manufactured ABB, Australia
20 kA630 A12 – 36 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
24
Series ‘SLD’ & DCD
12-36 kVIEC & ANSI SID, LSID &
SLS12-38 kV
NEMA, ANSI & IEC
Single Phase Air Switch Disconnects
RBD & SLDT – Recloser
Bypass Switch15-36 kV
ANSI & IEC
ITD – Inline Disconnect
15-36 kVANSI
Series ‘SLSB’12-24 kV
IEC
AB
B© P
TM
V -
25
Series ‘SLD’ & ‘DCD’ Disconnect Switches
SLD/DCD: Single Phase Double Insulator
SLD/DCD: Horizontal & Vertical Pole Mounted
SLD – IEC; DCD - ANSI
SLD - Manufactured ABB, Australia
DCD - Manufactured ABB, USA
16 – 25 kA630 – 900 A12 – 36 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
26
ITD Disconnect Switches
ITD: Inline Tension Single Phase Disconnect
Installs directly into the distribution line
ANSI Standards
ITD - Manufactured ABB, USA
200kV BIL insulation to limit flashovers
16 – 25 kA600 – 900 A12 – 36 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
27
SID, LSID, SLS Disconnect Switches
SID & SLS: Single Phase
LSID: Single Phase Load Break
SID & LSID: NEMA & ANSI
SLS: IEC
SID & LSID: Manufactured ABB, USA
SLS: Manufactured ABB, Australia
Good design for narrow installations and riser pole installations
16 – 40 kA600 – 900 A12 – 38 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
28
Series RBD & ‘SLDT’ Bypass Switches
RBD/SLDT: Single Phase Bypass Switch
RBD/SLDT: Horizontal & Vertical Pole Mounted
Main application – bypassing reclosers and voltage regulators to perform maintenance
SLDT – IEC; RBD - ANSI
SLDT - Manufactured ABB, Australia
RBD - Manufactured ABB, USA
16 – 25 kA630 – 900 A12 – 36 kV
Short Time Withstand Current
3 Sec. Sym
Rated Continuous
CurrentVoltage
AB
B© P
TM
V -
29
Series ‘SLSB’
Single Phase By-Pass Disconnector
Integrated Fused Cutout for fault protection
IEC
Manufactured ABB, Australia
VoltageRated
Continuous Current
Interrupting Current
12 – 24 kV 630 A 25 kA
AB
B© P
TM
V -
30
Fused Cutouts
Type NCX7.8-38 kV
NEMA & ANSI
Type ICX7.8-38 kV
NEMA & ANSI
Series ‘V’12-36 kV
IEC
Type LBU-II7.8-34.5 kV
NEMA & ANSI
Type EU & EUH2.6-7.8 kV
NEMA & ANSI
Most complete portfolio in the world!
AB
B© P
TM
V -
31
Type NCX Fused Cutout
VoltageRated
Continuous Current
Interrupting Current
7.8 – 38 kV 100 – 300 A 2 – 20 kA
NEMA & ANSI
Manufactured ABB, USA
Dual-venting to reach higher interrupting ratings
AB
B© P
TM
V -
32
Type ICX Fused Cutout
VoltageRated
Continuous Current
Interrupting Current
7.8 – 38 kV 100 – 300 A 8 – 16 kA
Interchangeable Fuse Tube (with S & C, Chance, Cooper)
Moisture Proof Fuse Tube reduces swelling over time
NEMA & ANSI
Manufactured ABB, USA
AB
B© P
TM
V -
33
Type LBU-II Fused Cutout
VoltageRated
Continuous Current
Interrupting Current
7.8 – 34.5 kV 100 – 300 A 6 – 20 kA
Integrated Load Break Device to loadbreak safer, simpler and without special tools
NEMA & ANSI
Manufactured ABB, USA
AB
B© P
TM
V -
34
Series ‘V’ Fused Cutout
Single & Three Phase
IEC
Manufactured ABB, Australia
VoltageRated
Continuous Current
Interrupting Current
12 – 36 kV 100 A 2 – 8 kA
AB
B© P
TM
V -
35
Type EU and EUH
VoltageRated
Continuous Current
Interrupting Current
2.6 – 7.8 kV 100 – 200 A 4 – 20 kA
Enclosed Cutouts
Specialty cutout normally used in indoor and grid applications
Dropout or Non-dropout
NEMA & ANSI
Manufactured ABB, USA
Only major producer in the world