abb_rcd_protection_press_geig_02122010.pdf

Upload: bilgipaylasim

Post on 04-Jun-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    1/10

    1

    ABB GroupDecember 16, 2010 | Slide 1

    Ian Richardson, Product Manager, December 2010

    Goldfields Electrical Industry GroupRCDs and the Wiring Rules

    ABB GroupDecember 16, 2010 | Slide 2

    Examining RCDs and the Wiring Rules

    AS/NZS3000:2007

    RCD Arrangements as per AS/NZS3000:2007

    Current danger curves

    RCD Operation

    Load types and the effect on RCD selection

    RCD Classification

    Nuisance Tripping

    Some Applications

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    2/102

    ABB GroupDecember 16, 2010 | Slide 3

    AS/NZS3000:2007

    Prepared by Joint Technical Committee EL-001

    Joint Australian and New Zealand standard

    Published on 12 November 2007

    All new installations are currently bound by the newstandard

    Examining RCDs and the Wiring Rules

    ABB GroupDecember 16, 2010 | Slide 4

    Some notes in AS/NZS3000:2007 with respect to RCDs

    Clause 2.6 Additional protection by residual current devices

    Selection Clause 2.6.2.1

    Types of RCDs Clause 2.6.2.2

    Arrangement Clause 2.6.2.4

    Examining RCDs and the Wiring Rules

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    3/103

    ABB GroupDecember 16, 2010 | Slide 5

    RCD Arrangement requirements of AS/NZS3000:2007

    Clause 2.6.2.4 Additional protection by residual current devices

    Not more than three final sub circuits protected by any one RCD

    If there is more than one RCD and more than one lighting circuit, thelighting circuits must be distributed between the RCDs

    In domestic installations having more than one final sub-circuit, aminimum of two RCDs shall be installed.

    Examining RCDs and the Wiring Rules

    Additional requirements of EnergySafety, Department of Commerce WA

    Since August 2009, people selling their home and all landlords must ensure

    two RCDs are installed to protect power and lighting circuitsHome sellers are required to install prior to sale and landlords before a new

    tenant moves in

    Landlords must install in any case prior to 9 August 2011

    ABB GroupDecember 16, 2010 | Slide 6

    Effects on the body Current danger curvesIEC 60479-1

    Examining RCDs and the Wiring Rules

    Increasingrisk ofventricular

    fibrilation

    AC-1 Perception

    possible but usuallyno startled reaction

    AC-2 Involuntary

    muscular

    contraction-noharmful effects

    AC-3 Strong

    muscularcontractions,

    reversibledisturbance toheart function

    AC-4 Possible

    cardiac arrest,breathing arrest,

    ventricular fibrilation

    30

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    4/104

    ABB GroupDecember 16, 2010 | Slide 7

    2. Tripping relay

    6. Primary

    conductor

    8. Secondary circuit

    Transformer-tripping device circuit without residual current

    A0

    2

    8

    6

    Residual Current Devices (RCDs) RCDs: the electromagnetic relay as actuator

    Examining RCDs and the Wiring Rules

    ABB GroupDecember 16, 2010 | Slide 8

    2. Tripping relay6. Primary

    conductor

    8. Secondary circuit

    Transformer-tripping device circuit withresidual current

    A0

    2

    8

    6

    Tripping of switchingmechanism

    Residual Current Devices (RCDs)

    RCDs: the electromagnetic relay as actuator

    Examining RCDs and the Wiring Rules

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    5/105

    ABB GroupDecember 16, 2010 | Slide 9

    According to the load type,the waveforms of the earth faultcurrents can be different in terms of shape and frequency and canbe classified in four types:

    Linear loads (resistance, impedance, capacitor) generate, in the case ofan earth fault, a sinusoidal alternating current, suddenly applied or slowlyrising, maintaining the frequency of the voltage supply.

    Refer clause 2.6.2.2 Note 2 (a)

    Line current Earth Fault current

    Examining RCDs and the Wiring Rules

    Protected by a Type AC RCD

    ABB GroupDecember 16, 2010 | Slide 10

    Non linear loads (diode, transistor, etc) generate, in the case of an earthfault, an alternating and/or pulsating current with a DC component,suddenly applied or slowly rising

    Refer clause 2.6.2.2 Note 2 (b)

    Line current Earth Fault current

    Examining RCDs and the Wiring Rules

    Protected by a Type A RCD

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    6/106

    ABB GroupDecember 16, 2010 | Slide 11

    Presence of a device that contains a rectifier section (like a half waverectifier, three-phase simple or double half-wave rectifier, single-phasedouble half-wave rectifier) can generate a smooth DC current.

    Refer clause 2.6.2.2 Note 2 (c)

    PE

    Three-phase star

    N

    L1L2L3 I

    IB IB

    t

    I

    t

    I

    t

    IB

    tPEN

    L1

    L2L3

    I

    IB

    Six-pulse bridge

    Line current Earth Fault current

    Examining RCDs and the Wiring Rules

    Protected by a Type B RCD

    ABB GroupDecember 16, 2010 | Slide 12

    Some situations may require a time delay on the residual currentprotection specifically designed to attain a predetermined operating timedelay, corresponding to a given value of residual current.

    Refer clause 2.6.2.2 Note 2 (d)

    Often used upstream in conjunction with other rapid residual currentoperated circuit breakers to guarantee selectivity and limit the poweroutage to the portion of the system affected by the fault.

    Examining RCDs and the Wiring Rules

    Protected by a Type S RCD

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    7/107

    ABB GroupDecember 16, 2010 | Slide 16

    AS/NZS3000:2007 Wiring Rules clause 2.6.2.1RCDs shall be so selected, and the electrical circuits so sub-divided,that any leakage current that may be expected to occur during normaloperation of the connected load or loads will be unlikely to causeunnecessary tripping of the device

    Notes:

    RCDs may operate at any value of residual current in excess of 50% ofthe rated residual current.

    To avoid unwanted tripping because of leakage currents and transientdisturbances.it is recommended that the loading of a circuit does not

    exceed one third of the rated residual current.

    Nuisance tripping

    ABB GroupDecember 16, 2010 | Slide 17

    Why splitting circuits is a general recommendation?

    The increased in use of electronic devices that contain EMC filters in an installation provide an accumulationof earth leakage currents.

    Typical values of earth leakage current of electronic devices are shown in the table below.

    To

    1,5 mA

    1 mA

    0,75 mA

    1 mA

    2 mA

    Earth leakage current

    around 1 mAFilters

    0,5 mAPhotocopiers

    0,5 mAFax machines

    0,5 mASmall portable appliances

    0,5 mAPrinters

    1 mAComputers

    From

    Appliances

    Nuisance tripping

    For example: A typical office final sub-circuit may trip with as few as eightcomputers on a 30mA RCD protected circuit.

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    8/108

    ABB GroupDecember 16, 2010 | Slide 18

    An Alternate Solution

    Consider three different samples of RCDs*:

    Instantaneous RCD 30mA

    Selective RCD 300mA

    Hi Immunity Type RCD 30mA

    The different behaviour has been illustrated in the nextslides.

    * these values result from tests on single devices therefore valuesare representative only of this phenomenon.

    ABB GroupDecember 16, 2010 | Slide 19

    The instantaneous 30 mA intervenes around 22mA with a tripping time 35mswhich decreases with the increase of the I nup to 10mA.

    Instantaneous tripping characteristic

    Instantaneous 30 mA

    An Alternate Solution

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    9/109

    ABB GroupDecember 16, 2010 | Slide 20

    The selective 300mA intervenes at around 200mA with a tripping time of180ms, which reduces with the increase of the Inremaining however higher

    than that of the 30mA instantaneous.

    Selective 300mA

    Selectivetripping characteristic

    Instantaneous 30 mA

    An Alternate Solution

    ABB GroupDecember 16, 2010 | Slide 21

    Selective 300mA

    Instantaneous 30 mA

    High immunity30mA

    The 30mA high immunity intervenes at around 25mA with a tripping time of 100..120ms whichdecreases with the increase of the I

    nup to 20 ms remaining always however in the same trippingzone of a 30mA instantaneous.

    High immunity RCD tripping characteristic

    An Alternate Solution

  • 8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf

    10/10

    ABB GroupDecember 16, 2010 | Slide 22

    Application notes: when does a high immunity RCD solve specificsituations

    1. Presence of an overvoltage due to lightning

    2. Simultaneous switching of fluorescent lamps withelectronic ballasts

    3. Simultaneous connection of computer or electronicdevices

    4. Devices with capacitors which connect phases to the

    earth installed in a long length circuit

    5. Installation of Soft starter/Variable Speed Drive motor controllers

    ABB GroupDecember 16, 2010 | Slide 23