abb_rcd_protection_press_geig_02122010.pdf
TRANSCRIPT
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
1/10
1
ABB GroupDecember 16, 2010 | Slide 1
Ian Richardson, Product Manager, December 2010
Goldfields Electrical Industry GroupRCDs and the Wiring Rules
ABB GroupDecember 16, 2010 | Slide 2
Examining RCDs and the Wiring Rules
AS/NZS3000:2007
RCD Arrangements as per AS/NZS3000:2007
Current danger curves
RCD Operation
Load types and the effect on RCD selection
RCD Classification
Nuisance Tripping
Some Applications
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
2/102
ABB GroupDecember 16, 2010 | Slide 3
AS/NZS3000:2007
Prepared by Joint Technical Committee EL-001
Joint Australian and New Zealand standard
Published on 12 November 2007
All new installations are currently bound by the newstandard
Examining RCDs and the Wiring Rules
ABB GroupDecember 16, 2010 | Slide 4
Some notes in AS/NZS3000:2007 with respect to RCDs
Clause 2.6 Additional protection by residual current devices
Selection Clause 2.6.2.1
Types of RCDs Clause 2.6.2.2
Arrangement Clause 2.6.2.4
Examining RCDs and the Wiring Rules
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
3/103
ABB GroupDecember 16, 2010 | Slide 5
RCD Arrangement requirements of AS/NZS3000:2007
Clause 2.6.2.4 Additional protection by residual current devices
Not more than three final sub circuits protected by any one RCD
If there is more than one RCD and more than one lighting circuit, thelighting circuits must be distributed between the RCDs
In domestic installations having more than one final sub-circuit, aminimum of two RCDs shall be installed.
Examining RCDs and the Wiring Rules
Additional requirements of EnergySafety, Department of Commerce WA
Since August 2009, people selling their home and all landlords must ensure
two RCDs are installed to protect power and lighting circuitsHome sellers are required to install prior to sale and landlords before a new
tenant moves in
Landlords must install in any case prior to 9 August 2011
ABB GroupDecember 16, 2010 | Slide 6
Effects on the body Current danger curvesIEC 60479-1
Examining RCDs and the Wiring Rules
Increasingrisk ofventricular
fibrilation
AC-1 Perception
possible but usuallyno startled reaction
AC-2 Involuntary
muscular
contraction-noharmful effects
AC-3 Strong
muscularcontractions,
reversibledisturbance toheart function
AC-4 Possible
cardiac arrest,breathing arrest,
ventricular fibrilation
30
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
4/104
ABB GroupDecember 16, 2010 | Slide 7
2. Tripping relay
6. Primary
conductor
8. Secondary circuit
Transformer-tripping device circuit without residual current
A0
2
8
6
Residual Current Devices (RCDs) RCDs: the electromagnetic relay as actuator
Examining RCDs and the Wiring Rules
ABB GroupDecember 16, 2010 | Slide 8
2. Tripping relay6. Primary
conductor
8. Secondary circuit
Transformer-tripping device circuit withresidual current
A0
2
8
6
Tripping of switchingmechanism
Residual Current Devices (RCDs)
RCDs: the electromagnetic relay as actuator
Examining RCDs and the Wiring Rules
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
5/105
ABB GroupDecember 16, 2010 | Slide 9
According to the load type,the waveforms of the earth faultcurrents can be different in terms of shape and frequency and canbe classified in four types:
Linear loads (resistance, impedance, capacitor) generate, in the case ofan earth fault, a sinusoidal alternating current, suddenly applied or slowlyrising, maintaining the frequency of the voltage supply.
Refer clause 2.6.2.2 Note 2 (a)
Line current Earth Fault current
Examining RCDs and the Wiring Rules
Protected by a Type AC RCD
ABB GroupDecember 16, 2010 | Slide 10
Non linear loads (diode, transistor, etc) generate, in the case of an earthfault, an alternating and/or pulsating current with a DC component,suddenly applied or slowly rising
Refer clause 2.6.2.2 Note 2 (b)
Line current Earth Fault current
Examining RCDs and the Wiring Rules
Protected by a Type A RCD
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
6/106
ABB GroupDecember 16, 2010 | Slide 11
Presence of a device that contains a rectifier section (like a half waverectifier, three-phase simple or double half-wave rectifier, single-phasedouble half-wave rectifier) can generate a smooth DC current.
Refer clause 2.6.2.2 Note 2 (c)
PE
Three-phase star
N
L1L2L3 I
IB IB
t
I
t
I
t
IB
tPEN
L1
L2L3
I
IB
Six-pulse bridge
Line current Earth Fault current
Examining RCDs and the Wiring Rules
Protected by a Type B RCD
ABB GroupDecember 16, 2010 | Slide 12
Some situations may require a time delay on the residual currentprotection specifically designed to attain a predetermined operating timedelay, corresponding to a given value of residual current.
Refer clause 2.6.2.2 Note 2 (d)
Often used upstream in conjunction with other rapid residual currentoperated circuit breakers to guarantee selectivity and limit the poweroutage to the portion of the system affected by the fault.
Examining RCDs and the Wiring Rules
Protected by a Type S RCD
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
7/107
ABB GroupDecember 16, 2010 | Slide 16
AS/NZS3000:2007 Wiring Rules clause 2.6.2.1RCDs shall be so selected, and the electrical circuits so sub-divided,that any leakage current that may be expected to occur during normaloperation of the connected load or loads will be unlikely to causeunnecessary tripping of the device
Notes:
RCDs may operate at any value of residual current in excess of 50% ofthe rated residual current.
To avoid unwanted tripping because of leakage currents and transientdisturbances.it is recommended that the loading of a circuit does not
exceed one third of the rated residual current.
Nuisance tripping
ABB GroupDecember 16, 2010 | Slide 17
Why splitting circuits is a general recommendation?
The increased in use of electronic devices that contain EMC filters in an installation provide an accumulationof earth leakage currents.
Typical values of earth leakage current of electronic devices are shown in the table below.
To
1,5 mA
1 mA
0,75 mA
1 mA
2 mA
Earth leakage current
around 1 mAFilters
0,5 mAPhotocopiers
0,5 mAFax machines
0,5 mASmall portable appliances
0,5 mAPrinters
1 mAComputers
From
Appliances
Nuisance tripping
For example: A typical office final sub-circuit may trip with as few as eightcomputers on a 30mA RCD protected circuit.
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
8/108
ABB GroupDecember 16, 2010 | Slide 18
An Alternate Solution
Consider three different samples of RCDs*:
Instantaneous RCD 30mA
Selective RCD 300mA
Hi Immunity Type RCD 30mA
The different behaviour has been illustrated in the nextslides.
* these values result from tests on single devices therefore valuesare representative only of this phenomenon.
ABB GroupDecember 16, 2010 | Slide 19
The instantaneous 30 mA intervenes around 22mA with a tripping time 35mswhich decreases with the increase of the I nup to 10mA.
Instantaneous tripping characteristic
Instantaneous 30 mA
An Alternate Solution
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
9/109
ABB GroupDecember 16, 2010 | Slide 20
The selective 300mA intervenes at around 200mA with a tripping time of180ms, which reduces with the increase of the Inremaining however higher
than that of the 30mA instantaneous.
Selective 300mA
Selectivetripping characteristic
Instantaneous 30 mA
An Alternate Solution
ABB GroupDecember 16, 2010 | Slide 21
Selective 300mA
Instantaneous 30 mA
High immunity30mA
The 30mA high immunity intervenes at around 25mA with a tripping time of 100..120ms whichdecreases with the increase of the I
nup to 20 ms remaining always however in the same trippingzone of a 30mA instantaneous.
High immunity RCD tripping characteristic
An Alternate Solution
-
8/13/2019 ABB_RCD_Protection_Press_GEIG_02122010.pdf
10/10
ABB GroupDecember 16, 2010 | Slide 22
Application notes: when does a high immunity RCD solve specificsituations
1. Presence of an overvoltage due to lightning
2. Simultaneous switching of fluorescent lamps withelectronic ballasts
3. Simultaneous connection of computer or electronicdevices
4. Devices with capacitors which connect phases to the
earth installed in a long length circuit
5. Installation of Soft starter/Variable Speed Drive motor controllers
ABB GroupDecember 16, 2010 | Slide 23