Aberystwyth Town Football Club
Floodlighting Analysis Report
11 February 2015
Waterman Building Services Limited
South Central, Peter Street, Manchester M2 5QR
Aberystwyth Town Football Club
Floodlighting Analysis Report
Client Name: Aberystwyth Town Football Club
Document Reference: 29.1
Project Number: BSD40000-100
Our Markets
Property & Buildings Transport & Infrastructure Energy & Utilities Environment
Quality Assurance – Approval Status
This document has been prepared and checked in accordance with Waterman Group’s IMS (BS EN ISO 9001: 2009 and BS EN ISO 14001: 2004)
Issue Date Prepared by Checked by Approved by
0 11-02-2015 C. Lumor T. Davies T. Davies
A 11-02-2015 C. Lumor T. Davies T. Davies
B 12-02-2015 C. Lumor T. Davies T. Davies
C 13-02-2015 C. Lumor T. Davies T. Davies
Comments
0
For Comment
A Executive Summary Tables Updated
B Introduction, Result Table 2 and Conclusion Updated
C Final Report
Disclaimer
This report has been prepared by Waterman Building Services, with all reasonable skill, care and diligence within the terms of the Contract with the client, incorporation of our General Terms and Condition of Business and taking account of the resources devoted to us by the agreement with the client.
We disclaim any responsibility to the client and others of any matters outside the scope above.
This report is confidential to the client and we accept no responsibility of whatsoever nature to third parties to whom this report, or any part thereof, is made known. Any such party relies on the report at its own risk.
Aberystwyth Town Football Club
C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
Content
1. Executive Summary ................................................................................................................... 1
2. Introduction ................................................................................................................................. 3
3. Modelling Input Data .................................................................................................................. 4
4. Results ......................................................................................................................................... 5
5. Conclusion .................................................................................................................................. 6
6. Recommendations ..................................................................................................................... 7
7. Abbreviations .............................................................................................................................. 8
Appendices
A. Floodlighting Design Analysis Output – At 500 Lux
B. Floodlighting Design Analysis Output – 100 Lux
C. Proposed Luminaire Datasheet
D. Full Summary of Report on A1 Sheet
Aberystwyth Town Football Club
1 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
1. Executive Summary
Waterman Building Services (WBS) has been appointed by Tai Ceredigion, to provide a floodlighting
assessment in support of planning application for the use of the football pitch and for the impact on
the proposed residential development.
The original design carried out by the Football Club’s floodlighting specialist could not address the
potential of light intrusion (into windows) to be experienced by the residents of the proposed
residential flats hence the appointment of WBS to carry out floodlighting design to minimise the
spilling of light beyond the football field and also to offer improved the energy efficiency.
The current design proposals reflect comments exchanged between Ainsley Gommon Architects and
Waterman Building Services (WBS) over the past few weeks. The target modelled lighting levels for
the pitch are 500lux for exceptional use for matches in Winter seasons and reduced 100 lux level for
training and other outdoor events.
The design carried out by Waterman Building Services were modelled using the existing high
columns positions and good LED light source output of 1700W (at 100%) and dims down to 200W
(at 10%) was used. The luminaire proposed is specifically designed to minimise the upward spread
of light near to and above the horizontal and correctly aimed to minimised obtrusive light into the
flats.
The results of the floodlighting calculation are summarised in the table below and the full results in
Section 4 and Appendix A.
1.0 Scenario 1: Results at 500l ux
Area Ave
Max Min Min/Avg Min/Max
Pitch 505 839 400 0.70 0.48
Flat Side_24 99.94 170 44 0.44 0.26
Flat Side_30 55.86 100 22 0.39 0.22
Flat Side_38 27.21 62 9 0.33 0.15
Flat Side_44 52.27 91 26 0.49 0.29
Aberystwyth Town Football Club
2 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
2.0 Scenario 2: Results at 100 lux
Area Ave
Max Min Min/Avg Min/Max
Pitch 112 168 80 0.7 0.48
Flat Side_24 19.99 34 9 0.45 0.26
Flat Side_30 11.17 20 4 0.36 0.20
Flat Side_38 5.40 12 2 0.37 0.17
Flat Side_44 10.45 18 5 0.48 0.28
The results in the tables above shows the pitch lux values with their corresponding values on the
flats. Some of these values on the flats at 500 lux are higher than the recommended ILP values of
25 lux for pre-curfew and 5 lux for post curfew for an urban classification.
However, at the 100 lux setting the majority of the lighting levels on the flats is within the ILP guidance
values, albeit some areas are still higher which are not covered by windows.
Aberystwyth Town Football Club
3 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
2. Introduction
This report has been produced at the request of Tai Ceredigion in support of the planning application
for the proposed residential development and also to alleviate concerns raised by the planning
authority of potential for nuisance from floodlighting at the football ground to the proposed residential
units.
The floodlighting assessment carried out by the Football Club’s Specialist in 2009 reveals that the
required illumination on the pitch do not meet UEFA/FAW standard. There were concerns raised in
the report of lack of flexibility in the operation of the floodlights and the high cost of running the highly
inefficient metal halide lamps.
It is understood that a total of 20 home games per year, with 10 under floodlights are played, mainly
in winter seasons under UEFA/FAW guidelines. Also, the total use of floodlighting for First Team
games will not exceed 30 hours per year, which equates to approximately 10 matches of 3 hours
duration under floodlighting.
This floodlighting analysis aims to assess the impact of using the floodlights under UEFA illumination
level of 500lux on the proposed residential development and also for reduced lighting levels at 100lux
on training and other outdoor events.
The proposed wide beam luminaire and the high output LED lamp source are selected to address
the light spillage problems and improve energy efficiency. This luminaire offers easy replacement as
no complicated bracketry is required and the existing electrical cabling can be used.
Aberystwyth Town Football Club
4 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
3. Modelling Input Data
The calculation comprises 4 x 1700W LED lamps mounted on the 4No. 16m columns and 13 x 1700W LED lamps mounted on the 2No. 18m columns. These columns were modelled to reflect the exact positions onsite.
All the luminaires were aimed at the correct angle to achieve the 500 lux levels in order to meet the UEFA requirement and also to achieve a uniformity of 0.7.
In order to achieve the required 100 lux illumination level the designed floodlights at 500 lux were dimmed down.
Aberystwyth Town Football Club
5 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
4. Results
Results at 500 Lux
The vertical illuminance light spills on the flats recorded at full switched at 500 lux shows readings
varying from 0 lux to 135 lux (max).
The tabulated results below indicate that the design at 500 lux will have a significant light spillage on
the proposed block of flats.
The full recorded readings are in Appendix A and D.
Area Ave
Max Min Min/Avg Min/Max
Pitch 505 839 400 0.70 0.48
Flat Side_20 98.71 164 43 0.44 0.26
Flat Side_22 72.21 154 23 0.32 0.15
Flat Side_24 99.94 170 44 0.44 0.26
Flat Side_26 74.71 150 25 0.33 0.17
Flat Side_28 92.57 161 40 0.43 0.25
Flat Side_30 55.86 100 22 0.39 0.22
Flat Side_32 84.14 145 36 0.43 0.25
Flat Side_34 58.29 115 21 0.36 0.18
Flat Side_36 65.86 116 29 0.44 0.25
Flat Side_38 27.21 62 9 0.33 0.15
Flat Side_42 64.66 112 30 0.46 0.27
Flat Side_44 52.27 91 26 0.49 0.29
Results at 100 Lux Switched Down
The results at 100 lux (ave) show reduced light spillage on the proposed block of flats. These values
range from 0 lux to 19 lux (max).
The full recorded readings are in Appendix B and Appendix D
Aberystwyth Town Football Club
6 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
5. Conclusion
The design at 500 Lux average with 0.71 uniformity ratio shows a vertical overspill on the flats as
high as 170 lux (Max) and as low as 9 lux (Min). These values are higher than the ILP allowance of
25 Lux for pre-curfew and 5lux for post-curfew.
However, with the 500 lux switch-down to 100 lux, we are at 80 percent reduction of power (for 100
lux switch down). The maximum vertical readings recorded 0 lux to 19 lux thereby falling within the
recommended ILP requirement of 25 lux.
The values at 500lux might be acceptable if the EHO relaxes the requirement from the ILP Guidance.
Aberystwyth Town Football Club
7 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
6. Recommendations
Undertake the following in relation to the design:
1. Check and confirm if the existing 18m columns can carry the 13 x AAA Lux luminaires and 16m columns can carry the 4 x AAA Lux proposed luminaires.
Aberystwyth Town Football Club
8 C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
7. Abbreviations
Ave Average
FAW Football Association of Wales
FLA Floodlighting Analysis
ILP Institution of Lighting Professionals
LED Light Emitting Diode
Lux Unit of light measurement
Max Maximum
Min Minimum
Ave Average
UEFA Union of European Football Association
WBS Waterman Building Services
Aberystwyth Town Football Club
C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
APPENDICES
A Floodlighting Design Analysis Output – Results on Pitch and Flats at 500 Lux
B Floodlighting Design Analysis Output – Results on Pitch and Flats at 100 Lux
C Proposed Luminaire Datasheet
D Full Summary of Design Output on A1 Sheet.
Aberystwyth Town Football Club
C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
A. Floodlighting Design Analysis Output – At 500 Lux
Aberystwyth Town Football Club
C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
B. Floodlighting Design Analysis Output – At 100 lux
Aberystwyth Town Football Club
C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx
Aberystwyth Town Football Club
C:\Users\MRCL\Desktop\New folder\40000 -100 Floodlighting Analysis Rev C.docx