ac leakage current transformers - yuanxingint leakage current transformers.pdf · leakage c t ’ s...

3
AC Leakage current transformers PART NUMBERS www.yuanxing.net [email protected] . 7 - 1 FEATURES APPLICATIONS SPECIFICATIONS Center hole-through, easy installation,on the safe side. Metal casing,better capacity of resisting disturbance,be adequate for inside and outside surroundings. High-sensitivity/accuracy,good linearity. Two series for selection: passive and active Used in high voltage electric power equipment insulation monitoring plant, which is stalled in transformers station. Provide exact measurement for mA leakage current of high voltage power equipment, such as transformers sleeve, current transformers Frequency50Hz Rated current10mA20mA30mA Measuring range0.5700mA Output signalmVmA Amplitude error±0.1% Phase error±1' Environmental temperature:一30º C+75º C Influence on phase error by temperature change is1’ Diameter of primary center holeΦ13mm, 25mm, 40mm, 50mm TA Rated Output Current Rated Input Current Casing Number AC Leakage CT’s Phone: +86-533-381-8450 Fax: +86-533-381-8724 AC Leakage current transformers 25XL YUANXING TA25LXX Series of AC Leakage current transformers Base theory of zero flux, TA25LXX series is used for online insulation monitoring device of high-voltage electric equipment in electric substation, which can exactly transit mA AC leakage current. YUANXING can designe and manufacture to meet the spe- cific design challenges of the client’s specific application. The following models are only a small sampling of the many different products which have been and are currently being manufactured. TA25XL SHANDONG YUANXING Electronics Co.,Ltd. NO.39, QIXIN AVENUE, ZHANGDIAN, ZIBO, SHANDONG, CHINA 255095

Upload: others

Post on 19-Apr-2020

41 views

Category:

Documents


0 download

TRANSCRIPT

AC Leakage current transformers

PART NUMBERS

[email protected]

. 7 - 1

FEATURES

APPLICATIONS

SPECIFICATIONS

• Center hole-through, easy installation,on the safe side.   • Metal casing,better capacity of resisting disturbance,be adequate for inside and outside surroundings.    • High-sensitivity/accuracy,good linearity.    • Two series for selection: passive and active

• Used in high voltage electric power equipment insulation monitoring plant, which is stalled in transformers station. Provide exact measurement for mA leakage current of high voltage power equipment, such as transformers    sleeve, current transformers

• Frequency:50Hz • Rated current:10mA、20mA、30mA • Measuring range:0.5~700mA • Output signal:mV/mA • Amplitude error:±0.1% • Phase error:±1' • Environmental temperature:一30º C~+75º C   Influence on phase error by temperature   change is<1’ • Diameter of primary center hole:Φ13mm,   25mm, 40mm, 50mm 

TA

Rated Output Current

Rated Input Current

Casing Number

AC Leakage C

T’s

Phone: +86-533-381-8450 Fax: +86-533-381-8724

AC Leakage current transformers

25XL

YUANXING TA25LXX Series of AC Leakage current transformers Base theory of zero flux, TA25LXX series is used for online insulation monitoring device of high-voltage electric equipment in electric substation, which can exactly transit mA AC leakage current.

YUANXING can designe and manufacture to meet the spe-cific design challenges of the client’s specific application. The following models are only a small sampling of the manydifferent products which have been and are currently being manufactured.

TA25XL

SHANDONG YUANXING Electronics Co.,Ltd.NO.39, QIXIN AVENUE, ZHANGDIAN, ZIBO, SHANDONG, CHINA 255095

[email protected]

. 7 - 2

AC Leakage C

T’s

Phone: +86-533-381-8450 Fax: +86-533-381-8724

元星电子YUANXING

AC Leakage current transformers

PERFORMANCES

OUTLINE DRAWING

45.5 ±0.2

H

2-6.5X1.5

W

B

A

L

TA25L

H56

±0.2

34 ±0.2

A

B(L)4

4-5x2.5

46W

45

TA25CL

H

±0.2

4-

±0.2

6.5

2175

W

A

B(L)

TA25DL

TA25EL±0.295 6

8

76

±0.2W

7648±0.2

L

A

B(H)

2

L

H A

W

TA25BL

TA25BL 10~100

TA25CL

1000 :150/60

50/60

0 16.0-50-44-54.8

25.5-68-65.5-72

TA25DL

TA25EL

50/60

50/60 0.020.05

40.5-88-48-91

50-105-86-100

0.020.05

0.020.05

0.020.05

0

0

0

2000 :1

1000 :12000 :1

1000 :12000 :1

1000 :12000 :1

10~1000

10~1000

10~1000

TA25L 10~1001000 :1

50/60 0 12.4-58-43-560.020.052000 :1

Frequency Rated burdenNumber Outline dimension( Hz)

(mm)Accuracy class

Rated Input(mA)

Ratio ID-L-W-H (ohms)

SHANDONG YUANXING Electronics Co.,Ltd.NO.39, QIXIN AVENUE, ZHANGDIAN, ZIBO, SHANDONG, CHINA 255095

[email protected]

. 7 - 3

AC Leakage C

T’s

Phone: +86-533-381-8450 Fax: +86-533-381-8724

元星电子YUANXING

AC Leakage current transformers

OUTLINE DIMENTIONUnit:mm (inch)

TA25BL

TA25CL

50.0

(1.969)

44.0

(1.732)

54.8

(2.157)

12.4

(0.488)

53.0

(2.087)

68.0(2.677)

25.5(1.004)

68.0(2.677)

65.5(2.579)

72.0(2.835)

TA25DL

TA25EL

88.0

(3.465)

48.0

(1.890)

91.0

(3.583)

40.5

(1.594)

88.0

(3.465)

105.0(4.134)

50.0(1.969)

100.0(3.937)

86.0(3.386)

100.0(3.937)

L W H A B

TA25L58.0

(2.283)

43.0

(1.693)

56.0

(2.205)

12.4

(0.488)

53.0

(2.087)

Part number

SHANDONG YUANXING Electronics Co.,Ltd.NO.39, QIXIN AVENUE, ZHANGDIAN, ZIBO, SHANDONG, CHINA 255095