ac supply system.pdf

Upload: rajeevagrawal

Post on 05-Nov-2015

7 views

Category:

Documents


0 download

TRANSCRIPT

  • 1

    AC Supply

    System

  • 2

    Importance of Elect System for Auxiliary

    Classification of Auxiliaries

    Choice of Voltage for Aux

    Aux. Power supply system

    Emergency AC Supply

    Presentation outline

  • 3

    Auxiliary Power Supply System

    The purpose of an Electrical system is to generate and supply electrical energy .

    The system should be designed and managed to deliver power with Reliability and Economy.

    As these two requirements are quite opposed a balance is required to have an optimum design of Auxiliary power

    supply system

    The auxiliaries have Ratings range from a few watts to few Mega Watts & Located over a large area

    Work under varied Operating Conditions

  • 4

    Auxiliary Power Supply System

    Failure of Auxiliaries can cause Outage of Power Plant

    Auxiliaries need Reliable Power Supply

    System designed to cater to this need

    Loads segregated on the basis of

    Rating (to decide Voltage)

    Location (to decide the

    Feeding Point)

    Change-over schemes & Alternate Power Supply arrangement

    to ensure Reliability

  • 5

    Elements of Aux. Power System

    More than 95% of the auxiliaries are driven by Motors

    Different Voltage levels are interconnected through

    Transformers

    Miscellaneous Elements

    Incomers

    Ties

    Diesel Generators

  • 6

    Auxiliary Power Supply

    Voltage Rating of Motors Decided based on kW Rating Rating 160kW 415V (LV), Contactor > 160kW & 200kW 415V (LV), Breaker > 200kW & 1500kW 3.3kV (MV), Breaker > 1500kW 11kV (MV), Breaker Frequent Start / Stop Operations (Coal Conveyor Motors)

    MV Vacuum Contactor

    List of Boards / Feeding Points arrived at based on Location of Load Centers / Systems

    Quantity & Rating of Transformers calculated based on Load & Operational Requirements

    Rating of Board Calculated based on the Operating Load & Transformer Rating

  • 7

    MV Switchgears System Parameters

    Nominal System voltage 6.6kV 11kV 3.3kV

    Highest System voltage 7.2 kV 12kV 3.6kV

    Rated Frequency 50Hz 50Hz 50Hz

    Number of phases/ poles Three Three Three

    System Neutral Earthing Earthed through Resistance of 6.35 to Limit E/F Current to 300A

    One minute power frequency

    withstand voltage 20kV 28kV 10kV

    Impulse withstand voltage 60kV (peak) 75kV (peak) 40kV (peak)

    Maximum System Fault Level 40kA (rms)

    Short time rating of Eqpt. 40kA (rms) for 1 second

    Dynamic withstand rating 100kA (peak)

  • 8

    LV Switchgears System Parameters

    Nominal System voltage 415V, 10%

    Rated Frequency 50Hz

    Number of phases Three

    System Neutral Earthing Solidly Earthed

    Maximum System Fault Level 45kA (rms)

    Short time rating of Eqpt. 45kA (rms) for 1 second

    Dynamic withstand rating 105kA (peak)

  • 9

    Auxiliary Power Supply System

    Sizing of Unit & Station transformer

    Start up source short circuit power

    Feeding offsite areas loads

    Rating of the Switchgear

    Loads

    Power Supply arrangement

    6.6& 0.415kV System

    11 & 3.3 & 0.415kV System

  • 10

    Auxiliary Power Supply

    INTRODUCTION

    Commonly used voltage level up to 200 MW unit size- 6.6kV, 415V

    Initially same voltage level (6.6 kv, 415v) were adopted

    for 500 MW unit size as well.

    With 500 MW unit, quantitative and qualitative change

    in auxiliaries took place.

    However no significant change in SWGR available in

    market.

    Need for optimizing and cost effective solution

  • 11

    Aux. Supply system(500MW)

    Grid Voltage- Normally 400kV for most of the200, 500MW units in India except few deviations

    Any Intermediate Voltage Available-to provide reliable start-up power source and to meet initial

    commissioning activities as well as to supply bulk

    loads(CW system, make-up water etc.) away from

    the main plants.Generally used Intermediate voltage

    levels are 220kV, 132kV, 33kV

    Nature of Auxiliaries i.e. ratings, basic characteristics and location

  • 12

    Auxiliary Power Supply-

    500MW

    Selection of voltage levels to be adopted for 500MW and above unit size.

    a) 6.6 KV and 415 V system

    b) 11& 3.3 kV system

  • 13

    HT/LT Supply System- Without

    GCB

    G

    UAT-A Dyn1

    UAT-B 16.5 KV

    6.6 KV Ynd11

    GT

    Ynyn0

    Station TRF-1

    UNIT SWGR--A UNIT SWGR--B

    Stn. SWGR-SA SB

    UST

    A

    ESP TRF-A

    S/Serv.

    Trf.-B

    UST-B ESP TRF-B

    USS-A USS-B 415 V Unit EMG SWGR

    X

    From DG SWGR

    X Blr MCC

    Turb MCC

    BFP ID Fan

    Air Compr

    Trf

    X X

    X

    Stn Serv

    Trf-A DMP Serv

    Trf

    1)SWYD

    Serv

    Trf-1

    2)Ash

    Handl T/F

    1600KVA

    6.6 KV

    B.C.

    N.O.

    TMCC

    Fdr to

    Clarif

    Water

    SWGR

  • 14

    220 KV TRANSFER BUS

    220 KV BUS I

    220 KV BUS II

    C.B.

    G.T.

    UAT-A

    GENERATOR

    UAT-B

    1A 1B

    ST

    SA SB

    Elect. Layout With GCB (220 KV BUS

    SYSTEM)

    ISOLATOR

    GCB

  • 15

    Transformer feeder Details

    To PMCC

    MCC/PCCMedium Voltage

    Magnetic Contactor

    SFU CB

    To ACDB

    Motor Feeder

    Unit Service Transformer

    To PMCC

    Magnetic Contactor

    SFU

    To ACDB

    Motor Feeder

    Dyn11

    C.B.

    415 V

    6.6 KV

  • 16

    X X

    X X

    X X X X

    DG-1 DG-3

    DG-2

    DG SWGR-1 DG SWGR-2

    UNIT EMER

    SWGR-1 UNIT EMER

    SWGR-2

    UNIT EMER

    SWGR-3

    UNIT EMER

    SWGR-4

  • 17

    1A 1B 2A 2B 3A 3B 4A 4B

    USS-1 USS-2 USS-3 USS-4

    UES-1 UES-2 UES-3 UES-4

    DG SWGR-1 DG SWGR-2

    DG-3 DG-1 DG-2

    EMERGENCY SWGR. SYSTEM

  • 18

    EMCC

    (1) AOP-1 (2) Em. Lighting Trf.

    (3) TVDC Reserve Supply (4) UPS Ch.

    (5) Scanner Air Fan (6) BVDC Reserve Supply

    (7) AC Seal Oil Pump (8) Air Heater Lub Oil Panel

    (9) Jacking Oil Pump (10) Stator Water Pump-B

    (11) Barring Gear (12) +26 v DC ATRS Ch. B

    (13) -26V DC ATRS Ch.B (14) 26V DC FSSS Ch. B

    (15) 26V DC DDC Ch. A

  • 19

    From Unit SWGR A Normally

    (1) BFP-1C (2) BFP-1A

    (3) PA Fan-1A (4) ID Fan -1A

    (5) UST-1A (6) ESP T/F -1A

    (7) FD Fan -1A (8) Coal Mill- 1A, C, E

    (9) CEP-1A,C (10) ACW Booster Pump-1A

    (11) Bus V.T.

  • 20

    USS A

    (1) Unit Em. SWGR (2) Boiler MCC

    (3) BVDC A (4) Turb. MCC A

    (5) 220V Dc Ch. A (6) +24 DC ATRS Ch. A

    (7) -24V DC ATRS Ch.A (8) Turb ACDB A

    (9) +24 V DDCMIS Ch. B (10) Gen Control Panel

    (11) Boiler ACDB A a) Grav. Feeder A,B, C,D,E,F

    b) S/B MCC Feeder-1

    c) INC From USS B

    (12) MOT Centrifuge

  • 21

    USS B

    (1) UPS Ch. (2) +24V FSSS Ch.

    (3) TVDC (4) Boiler MCC B

    (5) Turb MCC B (6) Turb ACDS B

    (7) Boiler ACDB B

  • 22

    THANK YOU