ac voltage controller circuits (rms …kaliasgoldmedal.yolasite.com/resources/power_electronics/ac...
TRANSCRIPT
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
AC VOLTAGE CONTROLLER CIRCUITS
(RMS VOLTAGE CONTROLLERS)
AC voltage controllers (ac line voltage controllers) are employed to vary the RMS value
of the alternating voltage applied to a load circuit by introducing Thyristors between the load and
a constant voltage ac source. The RMS value of alternating voltage applied to a load circuit is
controlled by controlling the triggering angle of the Thyristors in the ac voltage controller
circuits.
In brief, an ac voltage controller is a type of thyristor power converter which is used to
convert a fixed voltage, fixed frequency ac input supply to obtain a variable voltage ac output.
The RMS value of the ac output voltage and the ac power flow to the load is controlled by
varying (adjusting) the trigger angle ‘’
ACVoltage
Controller
V0(RMS)
fS
Variable ACRMS O/P Voltage
ACInput
Voltagefs
Vs
fs
There are two different types of thyristor control used in practice to control the ac power flow
On-Off control
Phase control
These are the two ac output voltage control techniques.
In On-Off control technique Thyristors are used as switches to connect the load circuit to the
ac supply (source) for a few cycles of the input ac supply and then to disconnect it for few input
cycles. The Thyristors thus act as a high speed contactor (or high speed ac switch).
PHASE CONTROL
In phase control the Thyristors are used as switches to connect the load circuit to the
input ac supply, for a part of every input cycle. That is the ac supply voltage is chopped using
Thyristors during a part of each input cycle.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
The thyristor switch is turned on for a part of every half cycle, so that input supply
voltage appears across the load and then turned off during the remaining part of input half cycle
to disconnect the ac supply from the load.
By controlling the phase angle or the trigger angle ‘’ (delay angle), the output RMS
voltage across the load can be controlled.
The trigger delay angle ‘’ is defined as the phase angle (the value of t) at which the
thyristor turns on and the load current begins to flow.
Thyristor ac voltage controllers use ac line commutation or ac phase commutation.
Thyristors in ac voltage controllers are line commutated (phase commutated) since the input
supply is ac. When the input ac voltage reverses and becomes negative during the negative half
cycle the current flowing through the conducting thyristor decreases and falls to zero. Thus the
ON thyristor naturally turns off, when the device current falls to zero.
Phase control Thyristors which are relatively inexpensive, converter grade Thyristors
which are slower than fast switching inverter grade Thyristors are normally used.
For applications upto 400Hz, if Triacs are available to meet the voltage and current
ratings of a particular application, Triacs are more commonly used.
Due to ac line commutation or natural commutation, there is no need of extra
commutation circuitry or components and the circuits for ac voltage controllers are very simple.
Due to the nature of the output waveforms, the analysis, derivations of expressions for
performance parameters are not simple, especially for the phase controlled ac voltage controllers
with RL load. But however most of the practical loads are of the RL type and hence RL load
should be considered in the analysis and design of ac voltage controller circuits.
TYPE OF AC VOLTAGE CONTROLLERS
The ac voltage controllers are classified into two types based on the type of input ac
supply applied to the circuit.
Single Phase AC Controllers.
Three Phase AC Controllers.
Single phase ac controllers operate with single phase ac supply voltage of 230V RMS at
50Hz in our country. Three phase ac controllers operate with 3 phase ac supply of 400V RMS at
50Hz supply frequency.
Each type of controller may be sub divided into
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
Uni-directional or half wave ac controller.
Bi-directional or full wave ac controller.
In brief different types of ac voltage controllers are
Single phase half wave ac voltage controller (uni-directional controller).
Single phase full wave ac voltage controller (bi-directional controller).
Three phase half wave ac voltage controller (uni-directional controller).
Three phase full wave ac voltage controller (bi-directional controller).
APPLICATIONS OF AC VOLTAGE CONTROLLERS
Lighting / Illumination control in ac power circuits.
Induction heating.
Industrial heating & Domestic heating.
Transformer tap changing (on load transformer tap changing).
Speed control of induction motors (single phase and poly phase ac induction motor
control).
AC magnet controls.
PRINCIPLE OF ON-OFF CONTROL TECHNIQUE (INTEGRAL CYCLE CONTROL)
The basic principle of on-off control technique is explained with reference to a single
phase full wave ac voltage controller circuit shown below. The thyristor switches 1T and 2T are
turned on by applying appropriate gate trigger pulses to connect the input ac supply to the load
for ‘n’ number of input cycles during the time interval ONt . The thyristor switches 1T and 2T are
turned off by blocking the gate trigger pulses for ‘m’ number of input cycles during the time
interval OFFt . The ac controller ON time ONt usually consists of an integral number of input
cycles.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
LR R = Load ResistanceFig.: Single phase full wave AC voltage controller circuit
Vs
Vo
io
ig1
ig2
wt
wt
wt
wt
Gate pulse of T1
Gate pulse of T2
n m
Fig.: WaveformsExample
Referring to the waveforms of ON-OFF control technique in the above diagram,
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
n Two input cycles. Thyristors are turned ON during ONt for two input cycles.
m One input cycle. Thyristors are turned OFF during OFFt for one input cycle
Fig.: Power Factor
Thyristors are turned ON precisely at the zero voltage crossings of the input supply. The
thyristor 1T is turned on at the beginning of each positive half cycle by applying the gate trigger
pulses to 1T as shown, during the ON time ONt . The load current flows in the positive direction,
which is the downward direction as shown in the circuit diagram when 1T conducts. The thyristor
2T is turned on at the beginning of each negative half cycle, by applying gating signal to the gate
of 2T , during ONt . The load current flows in the reverse direction, which is the upward direction
when 2T conducts. Thus we obtain a bi-directional load current flow (alternating load current
flow) in a ac voltage controller circuit, by triggering the thyristors alternately.
This type of control is used in applications which have high mechanical inertia and high
thermal time constant (Industrial heating and speed control of ac motors). Due to zero voltage
and zero current switching of Thyristors, the harmonics generated by switching actions are
reduced.
For a sine wave input supply voltage,
sin 2 sins m Sv V t V t
SV RMS value of input ac supply =2mV
= RMS phase supply voltage.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
If the input ac supply is connected to load for ‘n’ number of input cycles and
disconnected for ‘m’ number of input cycles, then
,ON OFFt n T t m T
Where1
Tf
= input cycle time (time period) and
f = input supply frequency.
ONt = controller on time = n T .
OFFt = controller off time = m T .
OT = Output time period = ON OFFt t nT mT .
We can show that,
Output RMS voltage ON ON
SO RMS i RMSO O
t tV V V
T T
Where i RMSV is the RMS input supply voltage = SV .
TO DERIVE AN EXPRESSION FOR THE RMS VALUE OF OUTPUT VOLTAGE, FOR
ON-OFF CONTROL METHOD.
Output RMS voltage 2 2
0
1.
ONt
mO RMSO t
V V Sin t d tT
2
2
0
.ONt
mO RMS
O
VV Sin t d t
T
Substituting for 2 1 2
2
CosSin
2
0
1 2
2
ONt
mO RMS
O
V Cos tV d t
T
2
0 0
2 .2
ON ONt t
mO RMS
O
VV d t Cos t d t
T
2
0 0
222
ON ONt tm
O RMSO
V Sin tV t
T
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
2 sin 2 sin 0
02 2
m ONONO RMS
O
V tV t
T
Now ONt = An integral number of input cycles; Hence
, 2 ,3 , 4 ,5 ,.....ONt T T T T T & 2 , 4 ,6 ,8 ,10 ,......ONt
Where T is the input supply time period (T = input cycle time period). Thus we note that
sin 2 0ONt
2
2 2m ON m ON
O RMSO O
V t V tV
T T
ON ON
SO RMS i RMSO O
t tV V V
T T
Where 2m
Si RMS
VV V = RMS value of input supply voltage;
ON ON
O ON OFF
t t nT nk
T t t nT mT n m
= duty cycle (d).
S SO RMS
nV V V k
m n
PERFORMANCE PARAMETERS OF AC VOLTAGE CONTROLLERS
RMS Output (Load) Voltage
1
222 2
0
sin .2 mO RMS
nV V t d t
n m
2m
SO RMS i RMS
V nV V k V k
m n
SO RMS i RMSV V k V k
Where S i RMSV V = RMS value of input supply voltage.
Duty Cycle
ON ON
O ON OFF
t t nTk
T t t m n T
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
Where,
nk
m n
= duty cycle (d).
RMS Load Current
O RMS O RMS
O RMSL
V VI
Z R ; for a resistive load LZ R .
Output AC (Load) Power
2
O LO RMSP I R
Input Power Factor
output load power
input supply volt amperesO O
S S
P PPF
VA V I
2LO RMS
i RMS in RMS
I RPF
V I
; S in RMSI I RMS input supply current.
The input supply current is same as the load current in O LI I I
Hence, RMS supply current = RMS load current; in RMS O RMSI I .
2LO RMS O RMS i RMS
i RMS in RMS i RMS i RMS
I R V V kPF k
V I V V
nPF k
m n
The Average Current of Thyristor T AvgI
0 2 3 t
Im
nmiT
Waveform of Thyristor Current
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
0
sin .2 mT Avg
nI I t d t
m n
0
sin .2
mT Avg
nII t d t
m n
0
cos2
mT Avg
nII t
m n
cos cos 02
mT Avg
nII
m n
1 12
mT Avg
nII
m n
22 mT Avg
nI I
m n
.m m
T Avg
I n k II
m n
duty cycle ON
ON OFF
t nk
t t n m
.m m
T Avg
I n k II
m n
,
Where mm
L
VI
R = maximum or peak thyristor current.
RMS Current of Thyristor T RMSI
1
22 2
0
sin .2 mT RMS
nI I t d t
n m
1
222
0
sin .2
mT RMS
nII t d t
n m
122
0
1 cos 2
2 2m
T RMS
tnII d t
n m
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
1
22
0 0
cos 2 .4
mT RMS
nII d t t d t
n m
1
22
0 0
sin 224
mT RMS
nI tI t
n m
1
22 sin 2 sin 00
4 2m
T RMS
nII
n m
1
22
0 04
mT RMS
nII
n m
1 12 22 2
4 4m m
T RMS
nI nII
n m n m
2 2m m
T RMS
I InI k
m n
2m
T RMS
II k
PRINCIPLE OF AC PHASE CONTROL
The basic principle of ac phase control technique is explained with reference to a single
phase half wave ac voltage controller (unidirectional controller) circuit shown in the below
figure. The half wave ac controller uses one thyristor and one diode connected in parallel across
each other in opposite direction that is anode of thyristor 1T is connected to the cathode of diode
1D and the cathode of 1T is connected to the anode of 1D . The output voltage across the load
resistor ‘R’ and hence the ac power flow to the load is controlled by varying the trigger angle
‘’. The trigger angle or the delay angle ‘’ refers to the value of t or the instant at which the
thyristor 1T is triggered to turn it ON, by applying a suitable gate trigger pulse between the gate
and cathode lead.The thyristor 1T is forward biased during the positive half cycle of input ac
supply. It can be triggered and made to conduct by applying a suitable gate trigger pulse only
during the positive half cycle of input supply. When 1T is triggered it conducts and the load
current flows through the thyristor 1T , the load and through the transformer secondary winding.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
By assuming 1T as an ideal thyristor switch it can be considered as a closed switch when
it is ON during the period t to radians. The output voltage across the load follows the
input supply voltage when the thyristor 1T is turned-on and when it conducts from t to
radians. When the input supply voltage decreases to zero at t , for a resistive load the
load current also falls to zero at t and hence the thyristor 1T turns off at t . Between
the time period t to 2 , when the supply voltage reverses and becomes negative the diode
1D becomes forward biased and hence turns ON and conducts. The load current flows in the
opposite direction during t to 2 radians when 1D is ON and the output voltage follows
the negative half cycle of input supply.
Fig.: Halfwave AC phase controller (Unidirectional Controller)
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
Equations
Input AC Supply Voltage across the Transformer Secondary Winding.
sins mv V t
2m
S in RMS
VV V = RMS value of secondary supply voltage.
Output Load Voltage
0o Lv v ; for 0t to
sino L mv v V t ; for t to 2 .
Output Load Current
sino mo L
L L
v V ti i
R R
; for t to 2 .
0o Li i ; for 0t to .
TO DERIVE AN EXPRESSION FOR RMS OUTPUT VOLTAGE O RMSV
2
2 21sin .
2 mO RMSV V t d t
22 1 cos 2
.2 2
mO RMS
V tV d t
22
1 cos 2 .4
mO RMS
VV t d t
2 2
cos 2 .2
mO RMS
VV d t t d t
2 2sin 2
22m
O RMS
V tV t
2sin 2
222
mO RMS
V tV
sin 4 sin 22 ;sin 4 0
2 22m
O RMS
VV
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
sin 22
22m
O RMS
VV
sin 22
22 2m
O RMS
VV
1 sin 22
2 22m
O RMS
VV
1 sin 22
2 2O RMS i RMSV V
1 sin 22
2 2SO RMSV V
Where, 2m
Si RMS
VV V = RMS value of input supply voltage (across the transformer
secondary winding).
Note: Output RMS voltage across the load is controlled by changing ' ' as indicated by the
expression for O RMSV
PLOT OF O RMSV VERSUS TRIGGER ANGLE FOR A SINGLE PHASE HALF-WAVE
AC VOLTAGE CONTROLLER (UNIDIRECTIONAL CONTROLLER)
1 sin 22
2 22m
O RMS
VV
1 sin 22
2 2SO RMSV V
By using the expression for O RMSV we can obtain the control characteristics, which is the
plot of RMS output voltage O RMSV versus the trigger angle . A typical control characteristic
of single phase half-wave phase controlled ac voltage controller is as shown below
Trigger angle in degrees
Trigger angle in radians
O RMSV
0 02m
S
VV
030 6 1; 6
0.992765 SV
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
060 3 2; 6
0.949868 SV
090 2 3; 6
0.866025 SV
0120 23
4; 6 0.77314 SV
0150 56
5; 6 0.717228 SV
0180 6; 6 0.707106 SV
VO(RMS)
Trigger angle in degrees
0 60 120 180
100% VS
20% VS
60% VS
70.7% VS
Fig.: Control characteristics of single phase half-wave phase controlled ac voltage
controller
Note: We can observe from the control characteristics and the table given above that the range of
RMS output voltage control is from 100% of SV to 70.7% of SV when we vary the trigger angle
from zero to 180 degrees. Thus the half wave ac controller has the draw back of limited range
RMS output voltage control.
TO CALCULATE THE AVERAGE VALUE (DC VALUE) OF OUTPUT VOLTAGE
21
sin .2 mO dcV V t d t
2
sin .2
mO dc
VV t d t
2
cos2
mO dc
VV t
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
cos 2 cos2
mO dc
VV
; cos 2 1
cos 12
mdc
VV
; 2m SV V
Hence 2cos 1
2S
dc
VV
When ' ' is varied from 0 to . dcV varies from 0 to mV
DISADVANTAGES OF SINGLE PHASE HALF WAVE AC VOLTAGE CONTROLLER.
The output load voltage has a DC component because the two halves of the output
voltage waveform are not symmetrical with respect to ‘0’ level. The input supply current
waveform also has a DC component (average value) which can result in the problem of
core saturation of the input supply transformer.
The half wave ac voltage controller using a single thyristor and a single diode provides
control on the thyristor only in one half cycle of the input supply. Hence ac power flow to
the load can be controlled only in one half cycle.
Half wave ac voltage controller gives limited range of RMS output voltage control.
Because the RMS value of ac output voltage can be varied from a maximum of 100% of
SV at a trigger angle 0 to a low of 70.7% of SV at Radians .
These drawbacks of single phase half wave ac voltage controller can be over come by using a
single phase full wave ac voltage controller.
APPLICATIONS OF RMS VOLTAGE CONTROLLER
Speed control of induction motor (poly phase ac induction motor).
Heater control circuits (industrial heating).
Welding power control.
Induction heating.
On load transformer tap changing.
Lighting control in ac circuits.
Ac magnet controls.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
SINGLE PHASE FULL WAVE AC VOLTAGE CONTROLLER (AC REGULATOR) ORRMS VOLTAGE CONTROLLER WITH RESISTIVE LOAD
Single phase full wave ac voltage controller circuit using two SCRs or a single triac is
generally used in most of the ac control applications. The ac power flow to the load can be
controlled in both the half cycles by varying the trigger angle ' ' .
The RMS value of load voltage can be varied by varying the trigger angle ' ' . The input
supply current is alternating in the case of a full wave ac voltage controller and due to the
symmetrical nature of the input supply current waveform there is no dc component of input
supply current i.e., the average value of the input supply current is zero.
A single phase full wave ac voltage controller with a resistive load is shown in the figure
below. It is possible to control the ac power flow to the load in both the half cycles by adjusting
the trigger angle ' ' . Hence the full wave ac voltage controller is also referred to as to a bi-
directional controller.
Fig.: Single phase full wave ac voltage controller (Bi-directional Controller) using SCRs
The thyristor 1T is forward biased during the positive half cycle of the input supply
voltage. The thyristor 1T is triggered at a delay angle of ' ' 0 radians . Considering
the ON thyristor 1T as an ideal closed switch the input supply voltage appears across the load
resistor LR and the output voltage O Sv v during t to radians. The load current flows
through the ON thyristor 1T and through the load resistor LR in the downward direction during
the conduction time of 1T from t to radians.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
At t , when the input voltage falls to zero the thyristor current (which is flowing
through the load resistor LR ) falls to zero and hence 1T naturally turns off . No current flows in
the circuit during t to . The thyristor 2T is forward biased during the negative
cycle of input supply and when thyristor 2T is triggered at a delay angle , the output
voltage follows the negative halfcycle of input from t to 2 . When 2T is ON, the
load current flows in the reverse direction (upward direction) through 2T during t to
2 radians. The time interval (spacing) between the gate trigger pulses of 1T and 2T is kept at
radians or 1800. At 2t the input supply voltage falls to zero and hence the load current
also falls to zero and thyristor 2T turn off naturally.
Instead of using two SCR’s in parallel, a Triac can be used for full wave ac voltage control.
Fig.: Single phase full wave ac voltage controller (Bi-directional Controller) using TRIAC
Fig: Waveforms of single phase full wave ac voltage controller
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
EQUATIONSInput supply voltage
sin 2 sinS m Sv V t V t ;
Output voltage across the load resistor LR ;
sinO L mv v V t ;
for tot and to 2t
Output load currentsin
sinO mO m
L L
v V ti I t
R R
;
for tot and to 2t
TO DERIVE AN EXPRESSION FOR THE RMS VALUE OF OUTPUT (LOAD)VOLTAGE
The RMS value of output voltage (load voltage) can be found using the expression
2
2 2 2
0
1
2 LO RMS L RMSV V v d t
;
For a full wave ac voltage controller, we can see that the two half cycles of output voltage
waveforms are symmetrical and the output pulse time period (or output pulse repetition time) is
radians. Hence we can also calculate the RMS output voltage by using the expression given
below.
2 2 2
0
1sin .mL RMSV V t d t
2
2 2
0
1.
2 LL RMSV v d t
;
sinL O mv v V t ; For tot and to 2t
Hence,
2
2 22 1sin sin
2 m mL RMSV V t d t V t d t
2
2 2 2 21sin . sin .
2 m mV t d t V t d t
22 1 cos 2 1 cos 2
2 2 2mV t t
d t d t
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
2 22
cos 2 . cos 2 .2 2
mVd t t d t d t t d t
2 22 sin 2 sin 2
4 2 2mV t t
t t
2 1 1
sin 2 sin 2 sin 4 sin 24 2 2
mV
2 1 1
2 0 sin 2 0 sin 24 2 2
mV
2 sin 2sin 22
4 2 2mV
2 sin 2 2sin 22
4 2 2mV
2 sin 2 1
2 sin 2 .cos 2 cos 2 .sin 24 2 2
mV
sin 2 0 & cos 2 1
Therefore,
2
2 sin 2 sin 22
4 2 2m
L RMS
VV
2
2 sin 24
mV
2
2 2 2 sin 24
mL RMS
VV
Taking the square root, we get
2 2 sin 22
mL RMS
VV
2 2 sin 22 2
mL RMS
VV
12 2 sin 2
22m
L RMS
VV
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
1 sin 22
2 22m
L RMS
VV
1 sin 2
22m
L RMS
VV
1 sin 2
2L RMS i RMSV V
1 sin 2
2SL RMSV V
Maximum RMS voltage will be applied to the load when 0 , in that case the full sine
wave appears across the load. RMS load voltage will be the same as the RMS supply
voltage2mV
. When is increased the RMS load voltage decreases.
0
1 sin 2 00
22m
L RMS
VV
0
1 0
22m
L RMS
VV
0 2
mSL RMS i RMS
VV V V
The output control characteristic for a single phase full wave ac voltage controller with
resistive load can be obtained by plotting the equation for O RMSV
CONTROL CHARACTERISTIC OF SINGLE PHASE FULL-WAVE AC VOLTAGE
CONTROLLER WITH RESISTIVE LOAD
The control characteristic is the plot of RMS output voltage O RMSV versus the trigger angle ;
which can be obtained by using the expression for the RMS output voltage of a full-wave ac
controller with resistive load.
1 sin 2
2SO RMSV V
;
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
Where2m
S
VV RMS value of input supply voltage
Trigger angle in degrees
Trigger angle in radians O RMSV %
0 0 SV 100% SV
030 6 1; 6
0.985477 SV 98.54% SV
060 3 2; 6
0.896938 SV 89.69% SV
090 2 3; 6
0.7071 SV 70.7% SV
0120 23
4; 6 0.44215 SV 44.21% SV
0150 56
5; 6 0.1698 SV 16.98% SV
0180 6; 6 0 SV 0 SV
VO(RMS)
Trigger angle in degrees
0 60 120 180
VS
0.2 VS
0.6VS
We can notice from the figure, that we obtain a much better output control characteristic
by using a single phase full wave ac voltage controller. The RMS output voltage can be varied
from a maximum of 100% SV at 0 to a minimum of ‘0’ at 0180 . Thus we get a full
range output voltage control by using a single phase full wave ac voltage controller.
Need For Isolation
In the single phase full wave ac voltage controller circuit using two SCRs or Thyristors
1T and 2T in parallel, the gating circuits (gate trigger pulse generating circuits) of Thyristors 1T
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
and 2T must be isolated. Figure shows a pulse transformer with two separate windings to provide
isolation between the gating signals of 1T and 2T .
G1
K1G2
K2
GateTriggerPulse
Generator
Fig.: Pulse Transformer
SINGLE PHASE FULL-WAVE AC VOLTAGE CONTROLLER WITH COMMON
CATHODE
It is possible to design a single phase full wave ac controller with a common cathode
configuration by having a common cathode point for 1T and 2T & by adding two diodes in a full
wave ac controller circuit as shown in the figure below
Fig.: Single phase full wave ac controller with common cathode(Bidirectional controller in common cathode configuration)
Thyristor 1T and diode 1D are forward biased during the positive half cycle of input
supply. When thyristor 1T is triggered at a delay angle , Thyristor 1T and diode 1D conduct
together from t to during the positive half cycle.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
The thyristor 2T and diode 2D are forward biased during the negative half cycle of input
supply, when trigged at a delay angle , thyristor 2T and diode 2D conduct together during the
negative half cycle from t to 2 .
In this circuit as there is one single common cathode point, routing of the gate trigger
pulses to the thyristor gates of 1T and 2T is simpler and only one isolation circuit is required.
But due to the need of two power diodes the costs of the devices increase. As there are
two power devices conducting at the same time the voltage drop across the ON devices increases
and the ON state conducting losses of devices increase and hence the efficiency decreases.
SINGLE PHASE FULL WAVE AC VOLTAGE CONTROLLER USING A SINGLE
THYRISTOR
RL
T1
ACSupply
-
D1
D4
D3
D2
+
A single phase full wave ac controller can also be implemented with one thyristor and
four diodes connected in a full wave bridge configuration as shown in the above figure. The four
diodes act as a bridge full wave rectifier. The voltage across the thyristor 1T and current through
thyristor 1T are always unidirectional. When 1T is triggered at t , during the positive half
cycle 0 , the load current flows through 1D , 1T , diode 2D and through the load. With a
resistive load, the thyristor current (flowing through the ON thyristor 1T ) , the load current falls
to zero at t , when the input supply voltage decreases to zero at t , the thyristor
naturally turns OFF.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
In the negative half cycle, diodes 3 4&D D are forward biased during
to 2t radians. When 1T is triggered at t , the load current flows in the
opposite direction (upward direction) through the load, through 3D , 1T and 4D . Thus 3D , 4D and
1T conduct together during the negative half cycle to supply the load power. When the input
supply voltage becomes zero at 2t , the thyristor current (load current) falls to zero at
2t and the thyristor 1T naturally turns OFF. The waveforms and the expression for the
RMS output voltage are the same as discussed earlier for the single phase full wave ac controller.
But however if there is a large inductance in the load circuit, thyristor 1T may not be
turned OFF at the zero crossing points, in every half cycle of input voltage and this may result in
a loss of output control. This would require detection of the zero crossing of the load current
waveform in order to ensure guaranteed turn off of the conducting thyristor before triggering the
thyristor in the next half cycle, so that we gain control on the output voltage.
In this full wave ac controller circuit using a single thyristor, as there are three power
devices conducting together at the same time there is more conduction voltage drop and an
increase in the ON state conduction losses and hence efficiency is also reduced.
The diode bridge rectifier and thyristor (or a power transistor) act together as a
bidirectional switch which is commercially available as a single device module and it has
relatively low ON state conduction loss. It can be used for bidirectional load current control and
for controlling the RMS output voltage.
SINGLE PHASE FULL WAVE AC VOLTAGE CONTROLLER (BIDIRECTIONAL
CONTROLLER) WITH RL LOAD
In this section we will discuss the operation and performance of a single phase full wave
ac voltage controller with RL load. In practice most of the loads are of RL type. For example if
we consider a single phase full wave ac voltage controller controlling the speed of a single phase
ac induction motor, the load which is the induction motor winding is an RL type of load, where
R represents the motor winding resistance and L represents the motor winding inductance.
A single phase full wave ac voltage controller circuit (bidirectional controller) with an
RL load using two thyristors 1T and 2T ( 1T and 2T are two SCRs) connected in parallel is shown
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
in the figure below. In place of two thyristors a single Triac can be used to implement a full wave
ac controller, if a suitable Traic is available for the desired RMS load current and the RMS
output voltage ratings.
Fig: Single phase full wave ac voltage controller with RL load
The thyristor 1T is forward biased during the positive half cycle of input supply. Let us
assume that 1T is triggered at t , by applying a suitable gate trigger pulse to 1T during the
positive half cycle of input supply. The output voltage across the load follows the input supply
voltage when 1T is ON. The load current Oi flows through the thyristor 1T and through the load in
the downward direction. This load current pulse flowing through 1T can be considered as the
positive current pulse. Due to the inductance in the load, the load current Oi flowing through 1T
would not fall to zero at t , when the input supply voltage starts to become negative.
The thyristor 1T will continue to conduct the load current until all the inductive energy
stored in the load inductor L is completely utilized and the load current through 1T falls to zero at
t , where is referred to as the Extinction angle, (the value of t ) at which the load
current falls to zero. The extinction angle is measured from the point of the beginning of the
positive half cycle of input supply to the point where the load current falls to zero.
The thyristor 1T conducts from t to . The conduction angle of 1T is ,
which depends on the delay angle and the load impedance angle . The waveforms of the
input supply voltage, the gate trigger pulses of 1T and 2T , the thyristor current, the load current
and the load voltage waveforms appear as shown in the figure below.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
Fig.: Input supply voltage & Thyristor current waveforms
is the extinction angle which depends upon the load inductance value.
Fig.: Gating Signals
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
Waveforms of single phase full wave ac voltage controller with RL load for .
Discontinuous load current operation occurs for and ;
i.e., , conduction angle .
Fig.: Waveforms of Input supply voltage, Load Current, Load Voltage and ThyristorVoltage across 1T
Note
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
The RMS value of the output voltage and the load current may be varied by varying the
trigger angle .
This circuit, AC RMS voltage controller can be used to regulate the RMS voltage across
the terminals of an ac motor (induction motor). It can be used to control the temperature
of a furnace by varying the RMS output voltage.
For very large load inductance ‘L’ the SCR may fail to commutate, after it is triggered
and the load voltage will be a full sine wave (similar to the applied input supply voltage
and the output control will be lost) as long as the gating signals are applied to the
thyristors 1T and 2T . The load current waveform will appear as a full continuous sine
wave and the load current waveform lags behind the output sine wave by the load power
factor angle .
TO DERIVE AN EXPRESSION FOR THE OUTPUT (INDUCTIVE LOAD) CURRENT,
DURING tot WHEN THYRISTOR 1T CONDUCTS
Considering sinusoidal input supply voltage we can write the expression for the
supply voltage as
sinS mv V t = instantaneous value of the input supply voltage.
Let us assume that the thyristor 1T is triggered by applying the gating signal to 1T at
t . The load current which flows through the thyristor 1T during t to can be found
from the equation
sinOO m
diL Ri V t
dt
;
The solution of the above differential equation gives the general expression for the output
load current which is of the form
1sint
mO
Vi t A e
Z
;
Where 2m SV V = maximum or peak value of input supply voltage.
22Z R L = Load impedance.
1tanL
R
= Load impedance angle (power factor angle of load).
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
L
R = Load circuit time constant.
Therefore the general expression for the output load current is given by the equation
1sinR
tm L
O
Vi t A e
Z
;
The value of the constant 1A can be determined from the initial condition. i.e. initial
value of load current 0Oi , at t . Hence from the equation for Oi equating Oi to zero and
substituting t , we get
10 sinR
tm L
O
Vi A e
Z
Therefore 1 sinR
tmL
VA e
Z
1
1sinm
Rt
L
VA
Ze
1 sinR
tmL
VA e
Z
1 sinR t
mLV
A eZ
By substituting t , we get the value of constant 1A as
1 sinR
mLV
A eZ
Substituting the value of constant 1A from the above equation into the expression for Oi , we
obtain
sin sinRR
tm mLL
O
V Vi t e e
Z Z
;
sin sinR t R
m mL LO
V Vi t e e
Z Z
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
sin sinR
tm mL
O
V Vi t e
Z Z
Therefore we obtain the final expression for the inductive load current of a single phase
full wave ac voltage controller with RL load as
sin sin
Rt
m LO
Vi t e
Z
; Where t .
The above expression also represents the thyristor current 1Ti , during the conduction time
interval of thyristor 1T from tot .
To Calculate Extinction Angle
The extinction angle , which is the value of t at which the load current Oi falls
to zero and 1T is turned off can be estimated by using the condition that 0Oi , at t
By using the above expression for the output load current, we can write
0 sin sin
Rm L
O
Vi e
Z
As 0mV
Z we can write
sin sin 0
R
Le
Therefore we obtain the expression
sin sin
R
Le
The extinction angle can be determined from this transcendental equation by using the
iterative method of solution (trial and error method). After is calculated, we can determine the
thyristor conduction angle .
is the extinction angle which depends upon the load inductance value. Conduction
angle increases as is decreased for a known value of .
For radians, i.e., for radians, for the load current
waveform appears as a discontinuous current waveform as shown in the figure. The output load
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
current remains at zero during t to . This is referred to as discontinuous load
current operation which occurs for .
When the trigger angle is decreased and made equal to the load impedance angle
i.e., when we obtain from the expression for sin ,
sin 0 ; Therefore radians.
Extinction angle ; for the case when
Conduction angle 0 radians 180 ; for the case when
Each thyristor conducts for 1800 ( radians ) . 1T conducts from t to and
provides a positive load current. 2T conducts from to 2 and provides a negative
load current. Hence we obtain a continuous load current and the output voltage waveform
appears as a continuous sine wave identical to the input supply voltage waveform for trigger
angle and the control on the output is lost.
vO
2
3
t
Vm
0
Im
t
v =vO S
iO
Fig.: Output voltage and output current waveforms for a single phase full wave ac voltagecontroller with RL load for
Thus we observe that for trigger angle , the load current tends to flow continuously
and we have continuous load current operation, without any break in the load current waveform
and we obtain output voltage waveform which is a continuous sinusoidal waveform identical to
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
the input supply voltage waveform. We loose the control on the output voltage for as the
output voltage becomes equal to the input supply voltage and thus we obtain
2m
SO RMS
VV V ; for
Hence,
RMS output voltage = RMS input supply voltage for
TO DERIVE AN EXPRESSION FOR RMS OUTPUT VOLTAGE O RMSV OF A SINGLE
PHASE FULL-WAVE AC VOLTAGE CONTROLLER WITH RL LOAD.
When O , the load current and load voltage waveforms become discontinuous asshown in the figure above.
1
22 21sin .mO RMSV V t d t
Output sino mv V t , for tot , when 1T is ON.
122 1 cos 2
2m
O RMS
tVV d t
1
22
cos 2 .2
mO RMS
VV d t t d t
1
22 sin 222
mO RMS
V tV t
1
2 2sin 2 sin 2
2 2 2m
O RMS
VV
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
1
21 sin 2 sin 2
2 2 2mO RMSV V
1
21 sin 2 sin 2
2 22m
O RMS
VV
The RMS output voltage across the load can be varied by changing the trigger angle .
For a purely resistive load 0L , therefore load power factor angle 0 .
1tan 0L
R
;
Extinction angle 0 radians 180
PERFORMANCE PARAMETERS OF A SINGLE PHASE FULL WAVE AC VOLTAGE
CONTROLLER WITH RESISTIVE LOAD
RMS Output Voltage 1 sin 2
22m
O RMS
VV
;2m
S
VV = RMS input
supply voltage.
O RMS
O RMSL
VI
R = RMS value of load current.
S O RMSI I = RMS value of input supply current.
Output load power
2
O LO RMSP I R
Input Power Factor
2
L LO RMS O RMSO
S S S SO RMS
I R I RPPF
V I V I V
1 sin 2
2O RMS
S
VPF
V
Average Thyristor Current,
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
Im
iT1
2 (2 + )
3
t
Fig.: Thyristor Current Waveform
1 1sin .
2 2T mT AvgI i d t I t d t
sin . cos2 2
m mT Avg
I II t d t t
cos cos 1 cos2 2
m mT Avg
I II
Maximum Average Thyristor Current, for 0 ,
m
T Avg
II
RMS Thyristor Current
2 21sin .
2 mT RMSI I t d t
1 sin 2
2 22m
T RMS
II
Maximum RMS Thyristor Current, for 0 ,
2m
T RMS
II
In the case of a single phase full wave ac voltage controller circuit using a Triac with
resistive load, the average thyristor current 0T AvgI . Because the Triac conducts in both the
half cycles and the thyristor current is alternating and we obtain a symmetrical thyristor current
waveform which gives an average value of zero on integration.
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
PERFORMANCE PARAMETERS OF A SINGLE PHASE FULL WAVE AC VOLTAGE
CONTROLLER WITH R-L LOAD
The Expression for the Output (Load) CurrentThe expression for the output (load) current which flows through the thyristor, during tot is given by
1
sin sinR
tm L
O T
Vi i t e
Z
; for t
Where,
2m SV V = Maximum or peak value of input ac supply voltage.
22Z R L = Load impedance.
1tanL
R
= Load impedance angle (load power factor angle).
= Thyristor trigger angle = Delay angle.
= Extinction angle of thyristor, (value of t ) at which the thyristor (load) current fallsto zero.
is calculated by solving the equation
sin sin
R
Le
Thyristor Conduction Angle
Maximum thyristor conduction angle radians = 1800 for .
RMS Output Voltage
1 sin 2 sin 2
2 22m
O RMS
VV
The Average Thyristor Current
1
1
2 TT AvgI i d t
1sin sin
2
Rt
m LT Avg
VI t e d t
Z
AC-VOLTAGE REGULATORS M.Kaliamoorthy PSNACET
sin . sin2
Rt
m LT Avg
VI t d t e d t
Z
Maximum value of T AvgI occur at 0 . The thyristors should be rated for maximum
m
T Avg
II
, where mm
VI
Z .
RMS Thyristor Current T RMSI
1
21
2 TT RMSI i d t
Maximum value of T RMSI occurs at 0 . Thyristors should be rated for maximum
2m
T RMS
II
When a Triac is used in a single phase full wave ac voltage controller with RL type of
load, then 0T AvgI and maximum 2m
T RMS
II