acb mitsubishi catalog
TRANSCRIPT
-
7/25/2019 ACB Mitsubishi Catalog
1/52
Low Voltage
Switchgears
Air Circuit Breakers
Air CircuitDisconnectors
SUPER AE
AE 1000
AE6300
Technical Catalogue
MITSUBISHI ELECTRIC
2004
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
2/522 MITSUBISHI ELECTRICSUPER AE
New Items in this Catalogue
Current information on updates, alterations, new items, andtechnical support youwill find on MITSUBISHI ELECTRIC's web pages(www.mitsubishi-automation.com).
In the products section of the MITSUBISHI home site various documentationsof the whole product range by MITSUBISHI ELECTRIC as well as thecurrent version of this catalogue on hand are available as download. The content is updated daily and to date is provided in German andEnglish.
Due to the constantly growing product range, technical alteration, and new or changed characteristical features, this catalogue is updatedfrequently.
Texts, figures and diagrams shown in this product catalogue are intended exclusively for explanation and assistance in planning and ordering theelectronic air circuit breakers of the SUPER AE series and the associated accessories. Only the manuals supplied with the breakers are relevant forinstallation, commissioning andhandling of the air circuit breakers and the accessories. The information given in this documentation must beread before installation and commissioning of the modules.
Shouldquestions arise with regard to the planning of modules described in this product catalogue, do not hesitate to contact the german branchof the MITSUBISHI ELECTRIC EUROPE B.V. in Ratingen or one of its distributors (see cover page).
MITSUBISHI ELECTRIC EUROPE B.V. 01/2004 (4th edition)
Technical
Catalogues
01/2004
Further Publications within the LVS, PLC and inverter range
The air circuit breaker program from MITSUBISHI ELECTRIC:
Completebreaker program
Framesize from1000 A to6300 A
Wideperformancerange
Standard version "SS" from65 to130 kAHigh performance version"SH" with130 kA
High interrupting capacity
Growing power demands
Optimum overload trippingsystem
Safer and more selectivity
WSS, PSS & Super Series Technical Catalogue
Product catalogue for circuit breakers and disconnectors
from 3 A to 1600 A rated current (art no. 133207)
MS-N Technical Catalogue
Product catalogue for low voltage contactors and relaysfrom 20 A to 1000 A rated current (art no. 62306)
PLC and Inverter Technical Catalogues
Product catalogues for programmable logic controllers andfrequency inverters (more details on request)
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
3/523MITSUBISHI ELECTRIC SUPER AE
CONTENTS
SUPER AE SERIES
BASE UNITS
Program overview main unit features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Program overview ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ACCESSORIES
Overview of the main accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Standard equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Internal optional accessories for all breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Optional accessories for drawout breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
External optional accessories for all breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ELECTRONIC TRIP RELAY
Program overview Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Trip relay adjusting notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Special functions accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Operating characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SPECIFICATIONS
Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Dimensions breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Dimensions accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Environmental conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Specifications for marinal approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Calculation software MELSHORT2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
APPENDIX
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
4/524 MITSUBISHI ELECTRICSUPER AE
BASE UNITS
Program Overview Specifications
SUPER AESeries Standard series "SS"
Breaker type AE 1000 - SS AE 1250 - SS AE 1600 - SS AE 2000 - SS AE 2500 - SS AE 3200 - SS
Rated current (A) at 40 C IN max 1000 1250 1600 2000 2500 3200
Rated insulation voltage(V) 50/60 Hz Ui 1000 1000 1000 1000 1000 1000Rated operating voltage(V) 50/60 Hz Ue 690 690 690 690 690 690
Number of poles 3 4 3 4 3 4 3 4 3 4 3 4
Adjustment rangeRated current (A) Ir
General protection(currentrating adjustable)
500-600-700-800-900-1000
625-750-875-1000-1125-1250
800-960-1120-1280-1440-1600
1000-1200-1400-1600-1800-2000
1250-1500-1750-2000-2250-2500
1600-1920-2240-2560-2880-3200
315-378-441-504-567-630
800-960-1120-1280-1440-1600
157-189-220-252-284-315
625-750-875-1000-1125-1250
Generatorprotection(currentrating fixed)
500 In1000200In630 625 In1250 800 In1600
1000In2000625 In1000 1250In2500 1600In3200
Rated current for neutral pole N (A) 1000 1250 1600 2000 2500 3200
Rated serviceshort-circuitbreaking capacity
ICS(kA, eff, sym.)
Breaking duty:O-t-CO-t-COICS = ICU
IEC947-2,EN60947-2,VDE0660,
Withinstantaneoustrip
AC690V 50 50 50 50 50 50
AC600V 50 50 50 65 65 65
AC500V 65 65 65 85 85 85
Withoutinstantaneous trip(with MCR)
AC690V 42 42 42 50 50 50
AC600V 50 50 50 65 65 65
AC500V 65 65 65 65 65 65
Withoutinst. trip AC690V 25 25 25 45 45 45
Ratedshort-circuitmaking capacityICM(kA, peak value)
Withinstantaneoustrip
AC690V 105 105 105 105 105 105
AC600V 105 105 105 143 143 143
AC500V 143 143 143 187 187 187
Withoutinstantaneous trip(with MCR)
AC690V 88.2 88.2 88.2 105 105 105
AC600V 105 105 105 143 143 143
AC500V 143 143 143 143 143 143
Withoutinst. trip AC690V 52.5 52.5 52.5 94.5 94.5 94.5
Rated short time current (kA eff.) ICW
1s 65 65 65 65 65 65
2s 40 40 60 65 65 653s 30 30 50 65 65 65
Maximum total breaking time (sec) 0.04 0.04 0.04 0.04 0.04 0.04
Closing time (sec) 0.08 0.08 0.08 0.08 0.08 0.08
Number of operating cycles(ON/OFF)
With rated current 5000 5000 5000 1500 1500 1000
Without rated current 10000 10000 10000 10000 10000 10000
Fixedtype
a 340 425 340 425 340 425 475 605 475 605 475 605
b 410 410 410 410 410 410 410 410 410 410 410 410
c 290 290 290 290 290 290 290 290 290 290 290 290
d 40 40 40 40 40 40 40 40 40 40 40 40
Drawouttype
a 298 385 298 385 298 385 433 565 433 565 433 565
b 430 430 430 430 430 430 430 430 430 430 430 430
c 368 368 368 368 368 368 368 368 368 368 368 368
d 61 61 61 61 61 61 61 61 61 61 61 61
Weight(kg)
FixedtypeManual charging 41 51 41 51 42 52 60 72 61 73 63 75
Motor charging 44 54 44 54 45 55 63 75 64 76 66 78
Drawouttype(with cradle)
Manual charging 64 78 64 78 65 79 92 113 93 114 95 116
Motor charging 67 81 67 81 68 82 95 116 96 117 98 119
Cradle only 26 30 26 30 26 30 35 43 35 43 36 44
For further temperatures referto technicalinformation on page 48. The figures for "without instantaneous tripping" are the values when the bare main body and theexternalrelay are combined. The number of operating cycles with rated current also include the number of operating cycles without rated current. All specifications without peripheral accessories (e.g. UVT control unit). Further current ratingson request.
More details on request.
Dimensions(mm)
Chargingtype
a
b
a
b
c d
c d
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
5/525MITSUBISHI ELECTRIC SUPER AE
BASE UNITS
Standard series "SS" High performance series "SH"
AE 4 000 - S SA A E 4000 - S SC AE 4 000 - S S AE 5 000 - S S AE 6 300 - S S AE 1 000 - S H AE 1 250 - S H AE 1 600 - S H AE 2 000 - S H AE 2 500 - S H AE 3 200 - S H
4000 4000 4000 5000 6300 1000 1250 1600 2000 2500 3200
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000690 690 690 690 690 690 690 690 690 690 690
3 4 3 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4
3200-3600-4000 3200-3600-4000 2000-2400-2800-3200-3600-4000
2500-3000-3500-4000-4500-5000
3150-3780-4410-5040-5670-6300
500-600-700-800-900-1000
625-750-875-1000-1125-1250
800-960-1120-1280-1440-1600
1000-1200-1400-1600-1800-2000
1250-1500-1750-2000-2250-2500
1600-1920-2240-2560-2880-3200
315-378-441-504-567-630
3200In4000 3200 In4000 2000In4000 2500 In5000 3150In6 30 0 5 00 In1000 625In1250 800 In1600 1000 In2000 1250In2500 1600 In3200
4000 3200 3200 3200 1000 1250 1600 2000 2500 3200
50 50 50 50 50 65 65 65 65 65 65
65 65 85 85 85 85 85 85 85 85 85
85 85 130 130 130 130 130 130 130 130 130
50 50 50 50 50
65 65 85 85 85
75 75 85 85 85
45 45 50 50 50
105 105 105 105 105 65 65 65 65 65 65
143 143 187 187 187 85 85 85 85 85 85
187 187 286 286 286 130 130 130 130 130 130
105 105 105 105 105
143 143 187 187 187
165 165 187 187 187
94.5 94.5 105 105 105
75 75 85 85 85
65 65 70 70 70 65 65 70 70 70
0.04 0.04 0.05 0.05 0.05 0.04 0.04 0.04 0.04 0.04 0.04
0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08 0.08
500 500 500 500 500 3000 3000 2000 1500 1500 1000
5000 4000 5000 2000 2000 2000 10000 10000 10000 10000 10000 10000
475 605 605 475 605 475 605 475 605 475 605 475 605 475 605
410 410 414 410 410 410 410 410 410 410 410 410 410 410 410
290 290 290 290 290 290 290 290 290 290 290 290 290 290 290
117 117 136 70 70 70 70 70 70 70 70 70 70 70 70
439 569 565 875 1005 875 1005 875 1005 485 615 485 615 485 615 485 615 485 615 485 615
430 430 430 480 480 480 480 480 480 430 430 430 430 430 430 430 430 430 430 430 430
368 368 368 368 368 368 368 368 368 398 398 398 398 398 398 398 398 398 398 398 398
109 109 151 123 123 123 123 123 123 61 61 61 61 61 61 61 61 61 61 61 6181 99 109 66 79 66 79 66 79 66 79 66 79 68 81
85 103 112 69 82 69 82 69 82 69 82 69 82 71 84
107 136 145 240 263 240 263 240 263 105 127 105 127 105 127 105 127 105 127 107 129
111 140 148 244 267 244 267 244 267 108 130 108 130 108 130 108 130 108 130 110 132
49 61 75 125 140 125 140 125 140 42 50 42 50 42 50 42 50 42 50 43 51
Declaration of conformity:
Standards IEC947-2,EN60947-2,VDE0660
Certificates ASTA,SEV (types onrequest)
Marine approvals LRS,GL, BV, ABS,DNK,NK
(otherapprovals on request)
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
6/526 MITSUBISHI ELECTRICSUPER AE
BASE UNITS
Program Overview Order Information
Standard series AE-SS Fixed type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shippingcontents:
Baseunit Charginghandle (for manual operation) withoutelectronic trip relay 4 auxiliary contacts (2 NO,2 NC contacts)
Furtherelements thatmustbe ordered: Electronictrip relaye.g. ST1A Accessories as required
AE 1000 - SS AE1000-SS 3P Fix, Bare, CT, TC 129215 AE1000-SS 4P Fix, Bare, CT, TC 129216
AE 1250 - SS AE1250-SS 3P Fix, Bare, CT, TC 129217 AE1250-SS 4P Fix, Bare, CT, TC 129218
AE 1600 - SS AE1600-SS 3P Fix, Bare, CT, TC 129220 AE1600-SS 4P Fix, Bare, CT, TC 129222
AE 2000 - SS AE2000-SS 3P Fix, Bare, CT, TC 129224 AE2000-SS 4P Fix, Bare, CT, TC 129225
AE 2500 - SS AE2500-SS 3P Fix, Bare, CT, TC 129226 AE2500-SS 4P Fix, Bare, CT, TC 129227
AE 3200 - SS AE3200-SS 3P Fix, Bare, CT, TC 129246 AE3200-SS 4P Fix, Bare, CT, TC 129247
Standard series AE-SS Drawout type
Please refer to order information above.
SUPER AE Air Circuit Breaker Order Information
The circuit breakers of the frame sizes AE1000-SS to AE3200-SS areoffered withouttrip relay and auxiliary switch included as stan-dard equipment. The circuitbreakers of the frame sizes
AE4000-SSA/SSC/SS to AE6300-SS are available including the triprelay ST1A and auxiliary relay. The circuitbreakers of the framesizes AE4000-SS,AE5000-SS,and AE6300-SS forhandling andweight reasons areavailable as drawout types.The circuit breakersof the high-performance series AE-SH as well areavailable includ-ing the triprelay ST1Aand auxiliary relay. They areavailable asfixed and drawout types.
To purchase a fully functional 3-pole or 4-pole fixed typecircuitbreaker please select the following:
base unit: fixed type, 3 or 4 pole with 3 current sensors (CT),
electronic trip relay,
auxiliary switches,
and the required accessory.
Please refer to order example 1.To purchase a fully functional 3-pole or 4-pole drawout typecircuitbreaker please select the following:
the corresponding circuit breaker fixed type,
the corresponding cradle
and the drawout mechanism.
Please refer to order example 2.
To purchase a fully functional 3-pole or 4-pole drawout typedisconnector please select the following:
the corresponding disconnector fixed type,
the corresponding cradle
and the drawout mechanism.
Please refer to order example 3.
Order example 1:
Base unit fixed type, 3 pole with 3 current sensors:AE1000-SS 3P Fix, Bare, CT, TC (art. no. 129215)
Electronic trip relay (for general use - S type): ST1A-SAE
(art. no. 135976)
Auxiliary switches: AX-SAE2A2BA (art. no. 28786)
Order example 2:
Base unit fixed type, 3 pole with 3 current sensors:AE1000-SS 3P Fix, Bare, CT, TC (art. no. 129215)
Electronic trip relay (for general use - S type): ST1A-SAE(art. no. 135976)
Auxiliary switches: AX-SAE2A2BA (art. no. 28786)
Cradle with horizontal terminals:CRADLE-02SEA3 (art. no. 25897)
Drawout mechanism: REC-SAEFD (art. no. 34666)
Base unitAE-SSwithouttrip relay,auxiliaryswitches or
other accessories
separateto order:triprelay,e.g. ST1A-SAE
separateto order:furtheraccessories ,e.g. auxiliary switches
TRIP
INDICA
TOR
LOAD
CURR
ENT
LARG
ESTP
HASE
RATE
DCU
RREN
TMAX RA
TED
CURR
ENT
%lu
SPGT
-CIACT
ELECTRON
ICTRIPRE
LAY
MITSUB
ISHI
MODEL
Order example 3:
Base unit (Disconnector *) fixed type, 3 pole: AE1000-SS 3PFix, Bare (art. no. 129228)
Cradle with horizontal terminals:CRADLE-02SEA3 (art. no. 25897)
Drawout mechanism: REC-SAEFD (art. no. 34666)
* Air circuit breaker without overcurrent short-circuit release andwithout current transformer
For specification and orderinformation about electronic trip relays refer to page 20 ff. For breaker accessories refer to page 8 ff. Further breaker typeswith other rated current on request.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
7/527MITSUBISHI ELECTRIC SUPER AE
BASE UNITS
Switch-disconnector* AE-SS Fixed type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shippingcontents:
Baseunit Charginghandle (for manual operation) withoutauxiliary contacts
Furtherelements thatmustbe ordered: Electronictrip relaytypeB ifyoudo notwant
without triprelay Accessories as required
AE 1000 - SS AE1000-SS 3P SS Fix, Bare 129228 AE1000-SS 4P SS Fix, Bare 129229
AE 1250 - SS AE1250-SS 3P SS Fix, Bare 129232 AE1250-SS 4P SS Fix, Bare 129234
AE 1600 - SS AE1600-SS 3P SS Fix, Bare 129236 AE1600-SS 4P SS Fix, Bare 129238
AE 2000 - SS AE2000-SS 3P SS Fix, Bare 129240 AE2000-SS 4P SS Fix, Bare 129241
AE 2500 - SS AE2500-SS 3P SS Fix, Bare 129242 AE2500-SS 4P SS Fix, Bare 129244
AE 3200 - SS AE3200-SS 3P SS Fix, Bare 129248 AE3200-SS 4P SS Fix, Bare 129249
Switch-disconnector* AE-SS Draw-out type
Please refer to order information on the top left side.
Air circuit breaker series AE-SS 40006300 A Draw-out type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shippingcontents:
Baseunit Charginghandle (for manual operation) Electronictrip relayST1A 4 auxiliary contacts (2 NO,2 NC contacts) Safety shutters
Furtherelements thatmustbe ordered: Differenttrip relayif youdo notwant ST1A
Accessories as required
AE 4000 - SS AE4000-SS 3P D/O, ST1A, AX2A2B, SST 56977 AE4000-SS 4P D/O, ST1A, AX2A2B, SST 56978
AE 5000 - SS AE5000-SS 3P D/O, ST1A, AX2A2B, SST 56976 AE5000-SS 4P D/O, ST1A, AX2A2B, SST 56975
AE 6300 - SS AE6300-SS 3P D/O, ST1A, AX2A2B, SST 56974 AE6300-SS 4P D/O, ST1A, AX2A2B, SST 56973
High performance series AE-SH Draw-out type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shippingcontents:
Baseunit Drawoutmechanism Cradle Charginghandle (for manual operation) Electronictrip relayST1A 4 auxiliary contacts (2 NO,2 NC contactsr)
Furtherelements thatmustbe ordered:
Differenttrip relayif youdo notwant ST1A
Accessories as required
AE 1000 - S H AE1000-SH 3P D /O , ST1A, AX 2A2B 43701 AE1000-S H 4P D/ O, S T1A, AX 2A2B 43695
A E 1 25 0 - SH A E1 25 0-SH 3 P D/O , ST1 A, A X2 A2 B 1 39 90 5 A E1 25 0-SH 4 P D/O , ST1 A, A X2 A2 B 1 39 90 8
A E 1 60 0 - SH A E1 60 0-SH 3 P D/O , ST1 A, A X2 A2 B 1 39 90 6 A E1 60 0-SH 4 P D/O , ST1 A, A X2 A2 B 1 39 90 9
AE 2000 - SH AE2000-SH 3P D /O , ST1A, AX2A2B 43698 AE2000-S H 4P D/ O, ST1A, AX2A2B 139910
A E 2 50 0 - SH A E2 50 0-SH 3 P D/O , ST1 A, A X2 A2 B 1 39 90 7 A E2 50 0-SH 4 P D/O , ST1 A, A X2 A2 B 1 39 91 1
AE 3200 - SH AE3200-SH 3P D /O , ST1A, AX2A2B 43696 AE3200-S H 4P D/ O, ST1A, AX2A2B 43690
For specification and orderinformation about electronic trip relays refer to page 20 ff. For breaker accessories refer to page 8 ff. Further breaker types with otherrated current on request. * Air circuit breakerwithout overcurrent short-circuit release and without current transformer
High performance series AE-SH Fixed type
Base unit equipment Breaker 3-pole type Art. no. 4-pole type Art. no.
Shippingcontents:
Baseunit Charginghandle (for manual operation) Electronictrip relayST1A 4 auxiliary contacts (2 NO,2 NC contacts)
Furtherelements thatmustbe ordered: Differenttrip relayif youdo notwant ST1A Accessories as required
AE 1000 - S H A E1000- SH 3P FI X, ST1A, AX2A2B 43713 AE1000- SH 4P FI X, S T1A, AX 2A2B 139891
AE 1250 - S H A E1250- SH 3P FI X, ST1A, AX2A2B 139887 AE1250- SH 4P F IX, ST1A, AX2A2B 139902
AE 1600 - S H A E1600- SH 3P FI X, ST1A, AX2A2B 43711 AE1600- SH 4P FI X, ST1A, AX2A2B 139903
AE 2000 - S H A E2000- SH 3P FI X, ST1A, AX2A2B 139888 AE2000- SH 4P F IX, ST1A, AX2A2B 139904
AE 2500 - S H A E2500- SH 3P FI X, ST1A, AX2A2B 139889 AE2500- SH 4P F IX, ST1A, AX2A2B 43703
AE 3200 - S H A E3200- SH 3P FI X, ST1A, AX2A2B 139890 AE3200- SH 4P F IX, ST1A, AX2A2B 43702
Air circuit breaker series AE-SSA/SSC 4000 A
Base unit equipment Breaker Fixed type Art. no. Draw-out type Art. no.
Shippingcontents: Baseunit Charginghandle (for manual operation) Electronictrip relayST1A 4 auxiliary contacts (2 NO,2 NC contacts) Safety shuttersFurtherelements thatmustbe ordered: Differenttrip relayif youdo notwant ST1A Accessories as required
AE 4000 - SSA AE4000-SSA 3P Fix, ST1A, AX2A2B 142593 AE4000-SSA 3P D/O, ST1A, AX2A2B, SST 142596
AE 4000 - SSA AE4000-SSA 4P Fix, ST1A, AX2A2B 142594 AE4000-SSA 4P D/O, ST1A, AX2A2B, SST 142599
A E 40 00 - SSC A E4 000 -SSC 3 P F ix , ST1A , A X2 A2 B 69 98 4 A E4 00 0-SSC 3P D/O , ST1 A, A X2 A2 B, SST 6 99 85
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
8/528 MITSUBISHI ELECTRICSUPER AE
ACCESSORIES
Overview and mounting positions of the main accessories
TRIPI
NDICA
TOR
LOAD
CURR
ENT
LARG
ESTP
HASE
RATE
DCUR
RENT
MAX RA
TEDC
URRE
NT
%lu
SPGT
- CIAC
T
ELECTR
ONICT
RIPRELAY
MITSUB
ISHI
MODEL
External power supply unit PS Page 19
Lifting hooks HP Page 15
Motor charging device MD Page 10
Cylinder lock CYL Page 13
Castell lock CAL Page 13
Electronic trip relay Page 20
Drawout mechanismwith drawout handle
Page 6
Counter CNT Page 13
Auxiliary switch AX Page 12
Under voltage trip device UVT Page 11
Closing coil CC Page 12
Shunt trip device SHT Page 12
Mis insertion preventer MIP Page 15
Safety shutters SST Page 14
Cell switch CL Page 14
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
9/529MITSUBISHI ELECTRIC SUPER AE
ACCESSORIES
Overview and description of the standard equipment
Manual charging
OFF
OFF
ON
GESPAN
NT
The spring is charged by the manual
charging handle. The breakeris closedwhen theON button is pressed,andopened when the OFF button is pressed.
When the closingspring charging is com-pleted,the charging indicator displaysCHARGED.
The indicator displays ON or OFF state of
the main contacts.
The breaker cannot be closed while theOFF button is being pressed (safety fea-ture).
The manual charging process is one of thestandard features of the breakerand part
of the standard equipment.
Drawout interlock
Position lock
Interphase barrier
A safety device prevents the circuitbreakerfrom being pushed in or drawnout while thebreaker is on.
The drawout handle cannot be insertedunless the OFF button is pressed.
The device is for locking the drawoutmechanism at the TEST position.This then
indicates the TEST position.The lock can be used during either thedrawing out or pushing-in operation.
The lock is released when the lock plate ispushed in,and the nextoperationbecomes possible.
Padlocking is possible at the CONNECTED,TEST,and DISCONNECTED positions. Use
thislock to prevent unauthorised chang-ing of positions.
(Thepadlock should be supplied by thecustomer)
The interphase barrier of the circuitbreakerprevent the short-circuit due to
conductivematters or dust.
The interphase barrier are simple to add
and have been designed as fixed typesand drawout types,to suityour require-ments.Thetable on theright shows youwhich circuitbreakers are supplied withpre-mounted barriers.
Breaker Fixed type Drawout type
AE1000-SSAE1600-SS
AE2000-SSAE3200-SS
AE4000-SSA/SSCAE4000-SSAE6300-SS
AE1000-SHAE3200-SH
=Standard equipment by horizontalconnection
6
5
5
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
10/5210 MITSUBISHI ELECTRICSUPER AE
ACCESSORIES
Overview and description on the optional accessories
Motor charging device (MD)
In additionto manual operation, the clos-ing spring can be charged automaticallyby an electric motor every timethebreakeris closed (ON charging method).
If the closing springis to be charged auto-matically whenever the breakeris opened,then this can be done through an addi-tional auxiliary contact (AXb) (OFF charg-ingmethod).As soon as charging is com-pleted, a visual display on the front says"CHARGED".
The "CHARGED" signal is also availablevia
the413 (TS+) and414 (TS-) terminals(included in the standardMD configura-tion).
There is always the option of manual
operation in an emergency. A closing coil(CC) is required for closingthe breakerbyremotecontrol,and a shunt trip device(SHT) is required for openingit in this way.
This warrants the prevention of pumping,both electronically and mechanically. Thecircuitof themotor is separate fromtheON/OFF circuit (CC,SHT).
Specifications MD-SAED24 MD-SAED48 MD-SAED60 MD-SAEAD013 MD-SAWAD013 MD-SAEAD025C MD-SAWAD025C
Application
AE1000-SS/-SH AE3200-SS/-SH,AE4000-SSA
AE4000-SSC
AE1000-SS/-SH AE3200-SS/-SH,AE4000-SSA
AE4000-SSC
AE1000-SS/-SH AE3200-SS/-SH,AE4000-SSA
AE4000-SSC
AE1000-SS/-SH AE3200-SS/-SH,AE4000-SSA
AE4000-SSC
AE4000-SSA,AE4000-SSAE6300-SS
AE1000-SS/-SH AE3200-SS/-SH,AE4000-SSA
AE4000-SSC
AE4000-SSA,AE4000-SSAE6300-SS
Rated voltage * (V) 24 (DC) 48 ( DC) 60 ( DC) 100125 (AC/DC) 100125 (AC/DC) 200250 ( AC/DC) 2 00250 ( AC/DC)
Applicable voltage range (V) 20.426.4 40.852.8 5160 85137.5 85137.5 170275 170275
Applied voltage (V) 24 48 60 100 / 125 100 / 125 200 / 250 200 / 250
Inrush current (peak value) (A) 22 14 9 10 / 12 10 / 12 5 / 6 7 / 8
Steady current (A) 6 3 3 3 4 1 2
Charging time (sec) 5 5 5 5 5 5 5
Order information Art. no. 29453 34352 34368 32843 58320 25830 58321
* Rated frequencyat AC = 50/60 Hz Not available for AE4000-SS AE6300-SS. for 3-pole type for 4-pole type
U1
(M+)
U2
(M-)
U1
(M+)
U2
(M-)
AXb
Charging completion switch (TS)
413
(TS+)
414
(TS-)
As soon as charging has been completed,this status is reported by the413 (TS+) and414 (TS-) terminals (signal display ofcharged status). This function is available
during the charging process both manu-ally and automatically.
Specifications TS-SAE1A
Contact c apacity refer t o auxiliary s witch
Order information Art. no. 30439
Controlsupply
Controlsupply
ON chargingmethod
OFFchargingmethod
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
11/5211MITSUBISHI ELECTRIC SUPER AE
ACCESSORIES
Undervoltage trip device (UVT)
Two trip types are available:
instantaneous (for immediate tripping)
with a time delay of 0.5 or 3 seconds
All UVT controllers are fitted withadditionalterminalsfor the connection of an emer-gency OFF switch.The UVT controllercan
be mounted to theleft of thethe unit.
If tworated voltages areused,the lowestvalue is applied.
If an emergencyOFF trip function isrequired, remove the shorting wire across
terminals DT1 (UO+)and DT2 (UO-)andreplace with an emergency OFF switch.
This device is used for tripping the breaker
when the supply voltage drops below theratedvalue.
The undervoltage trip device consists of a
UVT coil and a UVT controller. Bothpartsmust be orderedseparately.
D4(UL3)
D3(UL2)
D2(UL1)
D1(UL0)
DT1(U
0+
)
DT2(U
0
)
J1
(U+)
J2 J2
(U)
J1
Specifications UCON-
SAED24-BUCON-SAED011-B
UCON-SAEA123T-B
UCON-SAED24-05B
UCON-SAED011-05B
UCON-SAEA123T-05B
UCON-SAED24-30B
UCON-SAED011-30B
UCON-SAEA123T-30B
UVT-SAEUC
Ratedvoltage(+10%/-15%)* (V) 24(DC) 100125(DC) 100460(AC) 24(DC) 100110(DC) 100460(AC) 24(DC) 100110(DC) 100460(AC) UVTcoil
Operation Instantaneous With time delay
Tripcoilforthe besidementionedcontrollers
Operating time (sec) 0.1 or less 0.1 or less 0.1 or less 0.5 or more 0.5 or more 0.5 or more 3 or more 3 or more 3 or more
Closing d elay ** (sec) Approx. 1 .5 Approx. 1 .5 Approx. 1 .5 Approx. 1 .5 Approx. 1 .5 Approx. 1 .5 Approx. 3 Approx. 3 Approx. 3
Pick-up/drop-outvoltage (V) Pick-upvoltage 6585 %,drop-out voltage 4570 %
Trip f unct ion With o pen circuit (terminals DT1 ( UO +), DT2 ( UO ); rated 0.5 A at DC 2 50 V )
Power consumption (VA) 20
Order information Art. no. 30440 30441 30209 30442 30443 30206 30444 30445 30208 25912
* Ratedfrequency at AC= 50/60 Hz
** Delay which must be taken into account between the charging of the UVT controllerand the closing of the breaker.
Notes on the circuit diagram:
The UVT,as delivered,has a shorting wire between the DT1 (U0+) and DT2 (U0-) terminals.If an emergency OFF switch is used,this contact bridge must be removed.The emergency
OFF switch is not included in the package.The maximumlength of thewire between DT1(U0+)and DT2 (U0-)and thetripbutton should be 5 m.If longer distances are requiredplease contactyour nearest Mitsubishi distributor.
Coil
Controller
Circuitvoltage
Controlcircuit
UVT controller
Trip button
UVTcoil
AircircuitbreakerUVTcircuit diagram
seenote below
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
12/5212 MITSUBISHI ELECTRICSUPER AE
ACCESSORIES
Closing coil (CC)
A1
(CC+)
A2
(CC-)
The closing coil is seperate from themotor charging power supply.
Steady current is the value at maximumratedvoltage.
An interlock to prevent pumpingis pro-vided electrically. The pumpingpreven-tion is not performed, when the supply
voltageis 50 % or less the minimum ratedvoltage.
Closingtime is from the initial energiza-tion of the closing coil to thecompletionof the closing of the main contacts.
No pumpingprevention takes place if an
integrated auxiliary switch (AXb) is used asa cut-off switch.
An auxiliary contact with high switching
capacity shouldbe used with DC supplyvoltage (HAX).
The closing coil is a device to close thebreakerby remote control.Only one
closingsignal (about 100 msec.) is senteven when theclosingcoil supply is main-tained ON.
Specifications CC-SAED004A CC-SAED60 CC-SAEAD025A
Rated voltage * (V) 2448 (DC) 60 (DC) 100250 (AC/DC)
Applicable voltage range (V) 1852,8 4560 75275
Operating voltage (V) 24 / 48 60 100 / 250
Inrushcurrent
DC (A) 3.5/ 7.0 (DC24V 100 W,(DC48V200W)
1.1 0.6 / 1.3 (DC100V 100W,DC250V200W)
AC (A)
0.5 / 1.0 (AC 100V 100VA,
AC250V200VA)Closing time (sec) max. 0.08 max. 0.08 max. 0.08
Order information Art. no. 30399 40310 25909
* Rated frequency at AC = 50/60 Hz
Shunt trip device (SHT)
Auxiliary switch (AX, HAX)
Controlsupply
Controlsupply
C1(S+)
C2(S-)
The shunt trip device is used to open thebreakerby remote control.
A cut-off switch is included.
Specifications SHT-SAED004A SHT-SAED60 SHT-SAED025A SHT-SAEA046A
Rated voltage * (V) 2448 (DC) 60 (DC) 100250 (AC/DC) 380500 (AC)
Applicable voltage range (V) 16.852.8 4266 70275 266550
Operating voltage (V) 24 / 48 60 100 / 250 460
Inrushcurrent(peakvalue)
DC (A)3.5/7.0(DC24V 100 W,(DC48V200W)
10.8/2.0(DC100 V 100 W,(DC250V200W)
AC (A) 0.6/1.7(AC100V100VA,(AC250V150VA)
0.6(AC460V200VA)
Closing t ime (sec) max. 0 .04 (AE 4 000-SS A E 6300-SS = m ax. 0 .05)
Order information Art. no. 27215 40309 25831 27614
* Rated frequency at AC = 50/60 Hz
13
(AX+)
14
(AX-)
11
(BX+)
12
(BX-)
These auxiliary contacts are used toremotely indicate the ON or OFF statusof the breaker.
Specifications AX-SAE2A2BA AX-SAE5A5BA AX-SAE5A5BAD
Type Standard capacity (AX) High capacity (HAX)
Contactcapacity
Resistanceload
Inductiveload
Resistanceload
Inductiveload
Resistanceload
Inductiveload
460 V 5 2 5 2 5 2.5
(A) AC 250 V 10 10 10 10 10 10
125 V 10 10 10 10 10 10
250 V 0.3 0.3 0.3 0.3 3 1.5
DC 125 V 0.6 0.6 0.6 0.6 10 6
30 V 10 6 10 6 10 10
Maximum number of contacts 2 NO, 2NC 5 NO, 5NC 5 NO, 5NC
Order information Art. no. 28786 25835 38468
Note: The chattering time at the time of contact ON - OFF is below0.025 sec.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
13/5213MITSUBISHI ELECTRIC SUPER AE
ACCESSORIES
Condensor trip device (COT)
Counter (CNT)
Interlock device (CYL, CAL)
C2
AC1
S1
R2
R1
R3
N6
DC
DC+
C2(S)
SHT
C1(S+)
C
0000
0258
CYL
CAL
This device allows the electrically actuatedopening of the breakerby remote controlwithin a given period of time,despite a
power cut. The COT is used in conjunction
with theshunt trip device (SHT).For dimensionsreferto page 41.
Furtherdetailson request.
This is a mechanical counter which regis-ters the total number of operating cycles(with 1 ON/OFF switching operation =1 operating cycle).
The numberof operating cycles is displayedon thefront of theunit.
The interlock device locks the circuitbreakerinto the OFF position.
The relevant key can only be taken out inthe OFF positionof the circuit breaker,so that it canalsobe used for unlockingother breakers.
There are two locking options available:
Cylinder lock (CYL)
Castell lock (CAL) *
Specifications KF-100 KF-200
Rated in put voltage* V A C 1 00/110 200/220
Rated charging voltage V 140/155 280/310
Power supply capacity VA 1 1
Capacitor capacity F 660 150
Voltage range % 60125 60125
Chargingtime(capacitor) s max.0.5 max.0.5
Trip limit time s min. 900 min. 300
Order information Art. no. Onrequest Onrequest
* Rated frequencyat AC = 50/60 Hz
Specifications CNT-SAE
Counter type Mechanical
Display 5 digits
Order information Art. no. 25914
Specifications CYL-
SAEWKCYL-SAEWK1
CYL-SAEWK2
CYL-SAEWK3
CYL-SAEWK4
CAL-SAEWK
Interlock Cylinder Cylinder Cylinder Cylinder Cylinder Castell
Closing Basic 1 2 3 4 Basic
Order information Art. no. 25838 39485 39486 39488 39489 On request
* The closing basisfor the Castell lock can be designed individually. Further details on request.
Circuit diagram
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
14/5214 MITSUBISHI ELECTRICSUPER AE
ACCESSORIES
Cell switch (CL)
Safety shutters (SST)
In addition to the mechanical positionindicator on thefront panel,it is also possi-ble to mount these cell switches onto thecradle.
The cell switches can be set for all therelevant positions,i.e. connected,testand disconnected.
Each cell switch consists of 4 individual
switches.
Specifications CL-SAE211 CL-SAH211
Load Resistive Inductive Resistive Inductive
Contactcapacity (A)
AC 460AC 250AC 125
51010
2.51010
51010
2.51010
DC 250DC 125DC 30
31010
1.5610
31010
1.5610
Number a nd t ype o f switches 4 i nterchange s witches 4 i nterchange s witches
Application (breaker) AE1000-SS A E6300-SS AE1000-SH A E3200-SH
Order information Art. no. 25840 45578
The safety shutters cover the main con-ductors of thecradleside(supply andload
side) automatically when the circuitbreakeris drawn out.
When checkingthe main circuit,the safetyshutters on the supply andloadsides canbe opened independently of one another.
The safety shutters can also be locked witha mechanical locking device (SST LOCK).
The padlocks have to be supplied by cus-tomer.
Specifications SST-
02SAE3SST-02SAE4
SST-05SAE3
SST-05SAE4
SST-SAELOCK
Application (breaker) * AE10001600-SS AE20003200-SS /AE10003200-SH Safety
shutterlock
Breaker type Drawout
Number of poles 3 4 3 4
Order information Art. no. 25836 25837 25907 25908 30458
* Onbreakertypes AE 4000-SSA/SSCSS to AE 6300-SSthe safety shutters arealready part ofthestandardversion.
Switchf unction
CONNECTED
CLCTESTCL-T
DISCONNECTEDCL-D
discon.
Disconnected Connected
test operation
Disconnected Connected
Disc. Test Operation
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
15/5215MITSUBISHI ELECTRIC SUPER AE
ACCESSORIES
Vertical terminal adapter (VTA)
Lifting hooks (HP)
Vertical terminal adapters allow youto turnpower connection by 90.
Other forms of terminal adapters onrequest.Dimensions see page 37 ff.
Specifications VTA-02SAE VTA-03SAE VTA-32SAE
Application ( breaker) AE1000AE1600-SS AE20002500-SS/
AE10002500-SH AE3200-SS/SH
Shipping contents pieces 1 1 1
Order information Art. no. 34193 34192 34191
These hooks are used to remove thedrawout breakerfrom thecradle.
The option is not necessary,when a speciallifter (bucket type) forAE-SS is used.
The fixed type breaker is equipped withthe lifting hooks as standard.
The lifting hooks can not be used for
AE4000-SSto AE6300-SS.
Specifications HP-SAE
Material Metal
Order information Art. no. 30485
Mis-insertion preventor (MIP)
To obtain the right drawout configuration,it is extremely important that the breakerunit specifications (type, current rating,
optional accessories,etc.) should matchthe cradle.
Mis-insertion is prevented by a combi-nation of matching components (on thebreaker and the cradle).
Specifications MIP-SAE
Application (breaker) AE1000AE3200-SS/SH
AE4000-SSA/SSC
Material Metal
Order information Art. no. 30455
Shorting b-contact (SBC)
When movingthe breaker from the con-nected to thetest positions,this contactisused to short circuitauxiliary switch (Axb)
thusmaintaining the correct sequence of
operation of the externalcontrol circuit.
When ordering, the same number ofshorting b-contactsas auxiliary switches(AXb) willbe provided.
Specifications SBC-SAE
Application ( breaker) All b reaker
Order information Art. no. 30456
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
16/5216 MITSUBISHI ELECTRICSUPER AE
ACCESSORIES
Mechanical interlock (MI)
Door interlock (DI)
1000 (Max.)
134
144
0
12
1000(Max
.)
47
The mechanical interlock is a secure inter-lock prohibiting the parallel closingof twoor three breakers.
Any combination between AE1000-SS/SH
up to AE3200-SS/SHand AE4000-SSA/SSCis possible.
The interlock can be simply installed on
either fixed or drawout type breakers.
Withthe drawout type, the interlock oper-ates at the connecting point andcan bereleased at other positions,providingsecuremaintenance and inspection of thebreaker.
For AE4000-SS up to AE6300-SS a combi-nation is possible only between twobreak-ers.
Note:When using the mechanical interlock,theapplicationof the door interlock (DI) is notpossible.
G
Specifications MI-SAE163F
MI-SAE164F
MI-SAE323F
MI-SAE324F
MI-SAE163D
MI-SAE164D
MI-SAE323D
MI-SAE324D
MI-SAW633D
MI-SAW634D
MI-SAEIW
Application (breaker) AE10001600SS
AE20003200SS
AE10003200SHAE4000-SSA AE10001600SS
AE20003200SS
AE10003200SHAE4000-SSA AE40006300SS Bowdencable setBreaker type Fixed Drawout
Number of poles 3 4 3 4 3 4 3 4 3 4
Order information Art. no. 30450 30451 30452 30453 30446 30447 30448 30449 62327 62326 30454
Interlocking requires a separate unit for eachbreaker. If you have 3 breakers,you need a separate set of bowden cables MI-SAEIW.
This mechanical interlock device makes itimpossible to open the panel door unlessthe circuitbreaker is not switched off.
The device has been designed for paneldoors with thegroove on the left (stan-dard).Locks for grooves on the right areavailable on request.
A wire-type mechanical interlock is usedto
allow flexibility in positioning breakers inthe panel.
Note:
When using the door interlock (DI)theapplication of the mechanical interlock(MI)is not possible.
Specifications DI-SAEF DI-SAED
Application (breaker) For all breakers For all breakers
Breaker type Fixed Drawout
Order information Art. no. 31538 31537
Horizotal mounting
Verticalmounting
[mm]
Change overof2 power supplies
Change overof2 supplysystems
ON OFF
Cabinetdoor
ONOFF
ON
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
17/5217MITSUBISHI ELECTRIC SUPER AE
ACCESSORIES
Push button cover (BC-L)
This mechanical device can be locked witha padlock or a seal (not included in thepackage) to protect the pushbuttons of
the breaker unitagainst inadvertent
ON/OFF operation.The padlockhas to be suppliedby the
customer.
Specifications BCL-SAE
Material Acrylic plate
Order information Art. no. 27727
Specifications DUC-SAE
Protection IP 54
Order information Art. no. 42618
The transparent dust cover is hinged ontothe panel door.It has a screwlock andprevents dustand water entering into the
circuitbreaker.
Dust cover (DUC)
Specifications TTC-SAEF TTC-SAED
Appl ication ( breaker) F ix ed t ype Draw-out
Protection IP 20 IP 20
Order information Art . no. 62482 62481
The terminal cover is a transparent coverforsafety finger protection of control ter-minals.
The terminal cover prevents from careless
touching to the live control terminals.
Terminal cover (TTC)
Specifications DF-SAE
Appl icat ion ( breaker) Forallb reak ers
Material Plastic
Protection IP 20
Order information Art. no. 28319
The door frame improves the appearance,
aftercuttingout the panel door to installthe breaker.
Refer to the overall dimension drawingson page 36 ff for the installation method.
Door frame (DF)
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
18/5218 MITSUBISHI ELECTRICSUPER AE
ACCESSORIES
Current transformer (CT)
Neutral current transformer (NCT)
External current transformer (ZCT)
These currenttransformers (CT and sensorcoil) aresuitablefor the mainconductorand the N conductor.
Current transformers of type CT-06servethe reduction of Inmax .onanAE 1000.
Specifications CT-06SAE031
CT-06SAE050
CT-06SAE063
CT-10SAE100
CT-12SAE125
CT-16SAE160
CT-20SAE125
CT-20SAE160
CT-20SAE200
CT-25SAE250
CT-32SAE320
Application (breaker)* AE1000
-SSAE1000-SS
AE1000-SS
AE1000-SS
AE1250-SS
AE1600-SS
AE2000-SSAE1250-SH
AE2000-SS/-SHAE1600-SH
AE2000-SS/-SH
AE2500-SS/-SH
AE3200-SS/-SH
Rated currentInmax** (A) 315 500 630 1000 1250 1600 1250 1600 2000 2500 3200
Order information Art. no. 30476 30477 30478 33437 30479 30480 43387 62748 39539 39540 39541
More CTs on request.* Shipping contents includs CT andsensor coil for1 pole. Other transformerson request.** At 40C and50/60Hz (othertemperatures see Technical Informationon page 48)
N2
N1
Schalter
Elektr.Auslserelaismit Erdschlussschutz
Stromwandler
Widerstand
Stromwandler fr Neutralpol (NCT)
The neutral CT is used for ground fault pro-tection when a 3 pole breakeris used on a3 phase4 wiresystem.It should be used
together with a electronic trip relay thathas the ground fault protection (GFR)option.
Specifications NCT-
06SAENCT-10SAE
NCT-12SAE
NCT-16SAE
NCT-20SAE
NCT-25SAE
NCT-32SAE
NCT-40SAW
NCT-50SAW
NCT-63SAW
Application(breaker)* AE1000 AE1000 AE1250 AE1600 AE2000 AE2500 AE3200 AE4000 AE5000 AE6300
Current range (A) 630 1000 1250 1600 2000 2500 3200 4000 5000 6300
Order information Art . no. 39038 39026 33853 37323 39037 39036 39035 62330 62329 62328
* A suitable resistor (0.1 / 10 W) is attached to the product. Further technical details on request.For AE4000-SSC on request.
ETR
N2C2 C1
L2
N1
L1
SHT
713
714
ETR
N2
L2
C2 C1
N1
L1
SHT
713
714
This option is used to detect severalamperes of earthleakage when used incombinationwith an electronictrip relaythat has the earth leakagetripping (ER)option.
Two methods are available:
ZCT:three-load phase conductors (andthe neutral conductor in a 4-wire sys-tem) are passed through the ZCT
ZT:The supply transformers groundwire passes through to earth.
Specifications ZCT-163 ZCT-323 ZCT-324 ZT-15A ZT-30A ZT-40A ZT-60A ZT-80A ZT-100A
Application Load circuits Transformer ground wire
Holediameterforwire* (mm) 230x60(oval) 370x108(oval) 500x108(oval) 15 30 40 60 80 100
Order information Art. no. Onrequest
* For detailed dimensions referto page 46. Further specificationson request.
Diagram
Loadcircuitmethod(ZCT) External currenttransformer
Electronictriprelay
Transformer ground wiremethod(ZT)
Externalcurrenttransformer
Electronictriprelay
Power supply Powersupply
Breaker Currenttransformer
Electronic triprelaywithground fault prot.
Resistor
Currenttransformerfor neutralpole
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
19/5219MITSUBISHI ELECTRIC SUPER AE
ACCESSORIES
External power supply unit (PS)
Field test devices
Test jumper (TJ)
This unit is used when a DC 24 V controlsupplyis needed for thetripindicator onthe electronic triprelay.
The unit can be installed from the front tothe leftside of the breaker (for dimensionsplease refer to page 46).
Specifications PS-A200 PS-D200 PS-A400
Rated voltage * (V) 100110 / 200220 (AC) 200 (DC) 380415 (AC)
Input voltage range (%) +10 / -15 % +10 / -15 % +10 / -15 %
Input capacity 30 VA or less 30 W or less 30 VA or less
Output voltage (V) 24 (DC) 10 % 24 (DC) 10 % 24 (DC) 10 %
Output current (A) 0.42 or less 0.42 or less 0.3 or less
Order information Art. no. On request On request On request
* Rated frequency at AC = 50/60 Hz
The test devices are for testing thefunctioningof the electronictrip relay.
It allows you totest the trip relay withoutthe breaker being connected to themainsupply.The breakerwill tripwhen tested.
Specifications Y-160 Y-2000
Test functions LTD, S TD, I NST, Groundfault LTD, I NST, STD, Groundfault, pre-alarm
Power supply * 100120 V, 200240 V ( AC) or battery 100240 V ( AC)
Testcurrent signalsetting 6-point settingpossible
(20,40,125,200, 500 and2000 %)Continuously variable(102000%)
Others Time counter Ammeter, time counter
Order information Art. no. 27497 27496
* Rated frequency at AC = 50/60 Hz
888.8
88
888.8
8.8
STOP
a?/OC
R
VT
50/60
50Hz
60Hz
OCR
VT
TESTING
7
4
1
0
9
6
3
SET
SIGNA
LSET
SIGNA
LADJUS
T
STOP
SIGNA
L
STOP
FREQ
UENC
Y
SIGNA
L
BREA
KERT
ESTER
UP
OPER
ATING
TIME
DOWN
8
5
2
?
C
OUTPUT
OUTPUT
S1S2S3
S3
S2
TC
S1
STOP
TRIP
CHEC
K
STAR
T
RESET
TRIP
MITS
UBISH
I
Y-20
00
The test jumper cableis for testingthefunctioning of the circuit breakerwhen
the unitis removed from its cradle.
Take the breaker outofitscradle andusethiscableto switch thebreaker on andoffelectrically, so that you cancheck allitsfunctions.
Specifications TJ-SAE
Cable length (m) 3 *
Order information Art. no. 30457* Otherlengths on request
(Y2000)
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
20/5220 MITSUBISHI ELECTRICSUPER AE
ELECTRONIC TRIP RELAY
Introduction and selection
Applicable types B type General useStype
GeneratorprotectionMtype Power
supply Remarks Reference
Functions Code ST SPT SPGT SPET MT MPT MPGT
Long-time-delay L
ThebasicL, S andI protectionfunctionsarealso available whenthe controlpowersupplyfails.
Page 23, 25+ Short-time-delay S
+ Instantaneuous I
Trip indicator TRIP required *) Both LEDdisplayand relayoutputterminalsare available.
Page 22, 24
Load currentindicator LCI Theload state is indicateby thecolor
oftheLED. Page 22, 24
STD lock button Convenientfor checking instantaneous
operation Page 23, 25
OCRalarm AL Since theoutput signal is a short pulse,an
externalself-holding circuitis required. Page 29
4-pole
Neutralpoleovercurrent protection
100% Neutralpole protectionis providedforall4-polebreakers,if theN-poleis equippedwithCT.
Page 29
Test terminal TEST For characteristics check
Page 23, 25
Specialfunctions
Pre-alarm PAL required *) Both LEDdisplayand relayoutputterminalsare available.
Page 22, 24
Groundfault GFR
1. With ground fault alarmswitch2. If a 3-polebreakeris usedin a 4-wire
circuit,a neutral-poleCT (NCT) hasto beordered.
3. The groundfaultprotection(GFR)is notavailablewhenthe maximumratedcur-rentislessthan315/500Aor630AforAE1000-SH.
Page28
Earth leakage ER requiredAn externalZCT anda shunt tripdevice(SHT)are required(not availablefor AE 40006300)
Page 28
Accessory
Load currentmeasurement LM required *)
Themaximum phase currentflowingthroughthebrakercan be measured. Page 29
Unusualtemperatureindicator TAL required *) Thesensoris integratedinthebreaker. Page 29
Instantaneous/ MCR
1. Thelong-timeand short-timedelayfunction (L)is notavailable.
2. A changeover betweeninstantaneousand MCR characteristicsis possible.
3-and4-pole
Short-time delay+instantaneous/ MCR(I)
MCR(I)
1. Thelong-timedelayfunction (L)isnotavailable.
2. A change-overbetweeninstantaneousandMCR characteristicsis notpossible.
Long-time delay+short-time delay+instantaneous/ MCR(C)
MCR(C)
A change-over betweeninstantaneousandMCR characteristicsis possible(not available forAE 40006300).
Page 22, 23
Relaypowersupply
Applicablevoltage range **AC 100120/200240VDC 100125 VDC 2460V
124
An externalpowersupply fortrip indication (TRIP)andrelaycontrolis requiredfor alltype of relays.Therelay types areavailable in the3 shownvoltageranges(standard = AC100120/200240V).Please remark whenordering.
Whenthe controlpowersupply failsthe func-tionof theLED displaysand outputterminalsare disabled.Allstandard protectionfunctionsare stillavailable.
Equipped with functionas standard. Function available as an option. Function not available. Only one of thespecialversions (MCR-I,or MCR-C) is available as an option.
* No additional power supply is required as longas control power is available.** Other voltages on request.Rated frequency at AC = 50/60 Hz.
Special notes:
The circuit breakers are equipped with the S type relay in ST1A version (applicable voltage range AC 100120/200240 V)
asstandard (referto page 6).
All other model types and accessories can be configuredand ordered individually.
In the table on page 30 and 31 the most common configurations arelisted with order informations.
The trip relay type B is suitable for switch disconnectors with instantaneous MCR characteristics only.
Standardfunctions
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
21/5221MITSUBISHI ELECTRIC SUPER AE
ELECTRONIC TRIP RELAY
FunctionAppli-cabletype
Application
Standard protectionStype
GeneratorprotectionMtype
ST SPT SPGT SPET MT MPT MPGT
Max. ratedcurrent
(Inmax)
All
types
Maximum rated current
(In max.)
Conforms to CT ratings
(see table below)
Rated current(In) All
typesMaximum rated current
(In max) setting
0.50.60.70.80.91.0AE4000 SSA/SSC: 0.80.91.0
(adjustable in steps)
0.5 1.0 (continuously adjustable)AE4000-SSA/SSC: 0.8 1.0
(Setting only by authorizide persons)
Uninterruptedcurrent(IU)
S type Rated current (I n)
setting0.800.820.840.860.880.900.920.940.960.981.0
(adjustable in steps)
Long-timedelay(L)
Current(IL)
S type Uninterrupted current (IU) setting 1.15 10 %
(fixed)11.051.11.151.2 5 %
(adjustable in steps)M type
Rated current (I n) setting
Time (TL)S type
At uninterrupted current (IU ) 2 122550100150 sec 20 %
(adjustable in steps)122025304060 s20 %
(adjustable in steps)M type At current (IL)
1.2
Timefine ad-
justment
M type Long-time delay
time (TL) setting Details on request
Short-timedelay(S)
Current(Isd)
Alltypes
Rated current (I n) setting
234681015 %(adjustable in steps)
22.533.544.5 15 %(adjustable in steps)
Time(Tsd)
At short-time delaycurrent (I sd) 1.5
00.10.20.30.40.5s 20 %(adjustable in steps)
Remark: the operating time for "0" is 0.05 sec. (only for M type)
Instanta-neous (I)
Current(I i)
Alltypes
Rated current (I n) setting
46810121615 %AE5000-SS: 46810 12 15 %, AE6300-SS: 468 1015 % (adjustable in steps each)
Pre-alarm(PAL)
Current(Ip)
S type Uninterrupted current (IU )
setting 0.70.80.91.0OVER 10 %
(adjustable in steps) 0.840.880.920.961.0 5 %
(adjustable in steps)M type
Long-time delay current (IL) setting
Time (Tp)All
types
At long-time delay time (TL) setting
0.5 times 20 % 0.5 times 20 %
Resetsystem
Self holding Automatic reset
Ground fault(GFR)
Current(Ig) All
types
Maximum rated current(In max) setting
0.10.20.30.5 20%AE4000-SSA/SSC,
AE4000 AE6300-SS:0.20.30.5 20 %
(adjustable in steps each)
0.10.20.30.520%AE4000-SSA/SSC,
AE4000 AE6300-SS:0.20.30.520 %
(adjustable in steps each)
Time (Tg) At ground fault current (I g)
1.5 0.30.81.53s 20 %
(adjustable in steps) 0.30.81.53 s 20 %
(adjustable in steps)
Earthleakage(ER)
Current(Ie)
S type
Earth leakage current (I e)= setting
1235A 20 %(adjustable in steps)
Time (Te) At earth leakage current (Ie)
1.5 0.30.81.53s 20 %
(adjustable in steps)
Not available at In max 315 A,500 A and AE 1000-SH, 630 A. At 105 % non trip, at 125% pick up.
Note:The electronic trip relay will be delivered set to the values shown in bold type.
"SS" t ype AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SSA/SSC AE4000-SS AE5000-SS AE6300-SS
Rated current(Inmax)
315, 500630,1000
1250 1600125016002000
2500 3200 4000 4000 5000 6300
"SH" t ype AE1000-SH AE1250-SH AE16000-SH AE2000-SH AE2500-SH AE3200-SH
Rated current(Inmax)
6301000 1250 1600 2000 2500 3200
Overview of rated currents (In max) CT ratings
Characteristics setting table
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
22/5222 MITSUBISHI ELECTRICSUPER AE
Trip Indicator
Display of trippingcondition:
L for Long-time delay
S/I for short-time delay (S) /instantaneous (I)
G for ground fault (GFR)
E for earth leakage (ER)
Both an LED display (red) and a relay out-put are provided.
Remarks: , ,
Pre-AlarmDisplay
Pre-alarm display when a pre-determinedload current is reached.
Display method: Bothan LED display(yellow) and a relay output areavailable.
The "PAL" LED lights up when the pre-set value is exceeded (the relay is notactivated when this happens).
The relay output is activated when the
"PAL OUT" LED lights up.
The "PAL OUT" is self-holding and keeps
lightning, even if the load value is againsmaller than the set value.
Remarks: , ,
Temperature Alarm
An alarm signal is generatedwhen the
temperatureof themaincontacts rises abovethethresholdlevel (approx.170 C ormore).
Display methods:Both an LED indicator(red) and a relay output areprovided.
Remarks: , ,
Load CurrentIndicator
Indicates the percentage of uninterruptedcurrent (Iu ) in the following steps60-70-80-90-100-OVER.
LEDindication in different colours:
60 80 % = green
90 100 % = yellow OVER = red
The LEDs goes out when the breaker trips.
OCRAlarmContact
An alarmsignal is output tothe contact
when thebreaker is tripped by one of thefollowing causes:
L Long-time delay
S Short-time delay
I Instananeous trip (I) or MCR G Ground fault or
E Earth leakage
Remarks: ,
IndicatorReset Button
Pressing thisbutton resets the displays
and the relay output.
Trip indicator (TRIP)
Unusual temperature indicator (TAL)
Pre-alarm (PAL)
X Iu
INST P.U.li
46
810 12 16
0.50.6
0.70.8 0.91.0
X Iu
STD P.U.lsd
STD LOCK
23
46 8 10
TRIP INDICATOR L S/I G
PAL P.U.
60 80 100 OVER
RESET
TALALARM
RATED CURRENT MAX.(CT RATING) RATED CURRENT
LOAD CURRENT % lu
SPGT - C1AT
ELECTRONICTRIP RELAYMODEL
X IN MAX
AIN MAX
UNINTERRUPTEDCURRENT Iu
X I N
.80
.84.88
.92
.96
1.0X Iu
PAL P.U. Ip
I NS T M CR
0.70.8
0.91.0 OVER
X In max.
GFR P.U.lg
0.1
0.20.3
0.5
GFR TIME
SEC.SEC.
0.30.30.80.8
1.51.53.03.0
LTD TIME
TEST
SEC.
lu X 2 lsd X 1.5
1225
50100150
STD TIME
SEC.
MADE IN JAPAN
00.10.2
0.30.4 0.5
PAL OUT
T RI P A LA RM
S Types General Protection
ELECTRONIC TRIP RELAY
Remarks:
All functions marked in gray areincludedas standard equipment (standard relayST1A).
This overview lists the maximum possiblefunctionality of the units.
Triprelayswith special functions (functionswich are notmarked in gray)have to beordered seperately (please referto order
information on page 30 and31).
Page 28 and following contain a detailleddescription of all special functions.
An external power supply for trip indi-cation and relay control is required forall type of relays.Thevoltage range for
the power supply must be within one ofthe following ranges:- 1: AC 100120 / 200240 V (standard)- 2: DC 100125 V
- 4: DC 2460 V(other voltages on request)
The LED will go out when the controlpower supply is interrupted or whenthe RESET button is pushed.
An external self-hold circuitis required,as the alarmsignal pulsehas a durationof only 0.03 sec.
The contact rating (A) for the signalrelays arelisted in the table below.
Voltage(V) Resistiveload Inductiveload*
AC 1202 2250
DC30
125 0.2 0.1
*cos =0,4, L/R= 7 msec
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
23/5223MITSUBISHI ELECTRIC SUPER AE
ELECTRONIC TRIP RELAY
BasicSetting
RatedCurrent
RATEDCURRENT
The maximum rated current can beselected as follows:
Max.rated current (Inmax) x setting(A)
0.5-0.6-0.7-0.8-0.9-1.0
AE4000-SSA/SSC:0.80.91.0
Changing this settingchanges thefollowing values proportionally:
Uninterrupted current (I u)
Short-time delay current (Isd)
Instantaneous current (Ii)
Pre-alarm (Ip)
OverloadProtection
UninterruptedCurrent (Iu)
UNINTERRUPTEDCURRENT
Rated current (In) x setting(A)
0.80-0.84-0.88-0.92-0.96-1.0
Used forsetting the continuous uninter-rupted current value. Theactual trippingrangeisIux 1.05 1.25.
The load current is displayed as a percent-age of the uninterrupted current and thuschanges proportionally when the uninter-rupted current settingis changed.
Long-Time Delay Time(TL)
LTDTIME
Time setting (in seconds)
12-25-50-100-150
This value specifies the operating time
when the current flowing is the uninter-rupted current set value 2.
The pre-alarm operating time is half of thelong-time-delay time setting.
INST/MCRSwitch
INST/MCR
This switch makes it possible to selectbetween instantaneous operation charac-teristic (INST) and MCR characteristic.
The MCR characteristicsthe abbreviation for
Making Current Release.With thischarac-teristic,instantaneous trippingis only possi-ble if a shortcircuit occurs during switch-ON.Afterthe initial switch-ON,the timedelay trippingcharacteristic is active but
the instantaneous tripping is not possible.
Pre-AlarmCurrent(I p)
PALP.U.
Rated current (Iu) x setting(A)
0.7-0.8-0.9-1.0-OVER
Currentsetting forpre-alarmactivation.
Short-CircuitProtection(STD)
Short-TimeDelay P.U.Current (Isd)
STD P.U.
Rated current (In) x setting(A)
2-3-4-6-8-10
Current threshold value settingforshort-time delay tripping.
Short-Time Delay Time(T sd)
STDTIME
Time-delay setting (in seconds)
0-0.1-0.2-0.3-0.4-0.5
The setting value is the operating timewhen the current flowing is the short-time
delay current setting(I sd)1,5.If thedialis set to 0 seconds the breakerwilltripin 0.05 seconds.
Short-TimeDelayLockButton
STDLOCK
When measuring the instantaneous trip-pingcurrent,press the short time delayoperation inhibit button (STDLOCK) inorder to disable the short-time-delay trip-ping function.
Short-CircuitProtection(instantaneous)
InstantaneousP.U.Current (Ii)
Rated current (In) x setting(A)
4-6-8-10-12-16
AE5000:4-6-8-10-12AE6300:4-6-8-10
Setsthe threshold current value forinstantaneous tripping.
EarthLeakage Protection(I e)
ER P.U.
Current setting 1235Bothexternal ZCT and SHT are required (seepage 18 and 26 for further details).
EarthLeakage Protection( Te)
(TE)ER TIME
Time setting (in seconds)
0.30.81.53
The setting represents the operating timewhen thecurrent flowing is theearth leak-age current value setting 1,5.
The earth leakage protection facility is not
illustrated because it is only possibletohave either earth leakageor ground faultprotection.
Ground FaultProtection (GFR)
GroundFaultP.U.Current(Ig)
GFR P.U.
Max.rated current (In max.)x setting (A)
0.1-0.2-0.3-0.5
AE4000-SSA/SSC;AE40006300:0.2-0.3-0.5
The function is not available whenIn max. isless than630 A and forAE1000-SH Inmax 630 A.
GroundFaultTime(Tg)
GFRTIME
GFR time setting(in seconds)0.3-0.8-1.5-3
The setting specifies the operating timewhen the current flowing is the ground
fault current value setting(Ig) x 1.5.
GroundFault Trip Switch
GFRTRIP/ ALARM
The breaker will trip when the switch isset to the "TRIP" position.
When the switch is set to the "ALARM"positiona red trip indicator LED willlight up andthe relay output will be acti
-vated when a ground fault occurs; thebreaker will not trip,however.
The switch must be set to the "TRIP"position when the overcurrent trippingcharacteristic is activated (referto p.28).
Others
Test Terminal
Test functions:
Tripping characteristics
Long-time-delay (L)
Short-time-delay (S) Instantaneous (I)
Pre-alarm (P)
Ground fault (GFR)
A specialtesting deviceis required(see page 19).
The boldmarked values show the set-tingat time of shipment.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
24/5224 MITSUBISHI ELECTRICSUPER AE
ELECTRONIC TRIP RELAY
M Types General Protection
Trip Indicator
Display of trippingcondition:
L for Long-time delay
S/I for short-time delay (S) /instantaneous (I)
G for ground fault (GFR)
Both an LED display (red) and a relay out-put are provided.
Remarks: , ,
Pre-AlarmDisplay
Pre-alarm display when a pre-determinedload current is reached.
Display method: Bothan LED display(yellow) and a relay output areavailable.
The "PAL" LED lights up when the pre-
set value is exceeded (the relay is notactivated when this happens).
The relay output is activated when the
"PAL OUT" LED lights up.
The "PAL OUT" is self-holding and keepslightning, even if the load value is again
smaller than the set value.
Remarks: , ,
Temperature Alarm
An alarm signal is generatedwhen the
temperature of the main contacts risesabove the threshold level (approx.170 Cor more).
Display methods:Both an LED indicator(red) and a relay output areprovided.
Remarks: , ,
Load CurrentIndicator
Indicates the percentage of uninterrup-tedcurrent (IL) in thefollowing steps50-60-70-80-90-100-OVER.
LEDindication in different colours:
50 70 % = green
80 90 % = yellow
100 % = red
The LEDs goes out when the breaker trips.
OCRAlarmContact
An alarmsignal is output tothe contactwhen thebreaker is tripped by one of the
following causes:
L Long-time delay
S Short-time delay
I Instananeous trip (I)
G Ground fault
Remarks: ,
IndicatorReset Button
Pressing thisbutton resets the displaysand the relay output.
Trip indicator (TRIP)
Unusual temperature indicator (TAL)
Pre-alarm (PAL)
X Iu
INST P.U.li
46
810 12 16
X In
STD P.U.lsd
STD LOCK
22.5
33.5 4 4.5
TRIP INDICATOR L S/I
PAL P.U.
50 70 90 100
RESET
PAL OUTALARM
RATED CURRENT MAX.(CT RATING) RATED CURRENT In
LOAD CURRENT % lL
MPGT - 1AT
ELECTRONICTRIP RELAYMODEL
AA
IN MAX
LTD P.U. IL
X In
1.01.05
1.11.21.15
X IL
PAL P.U. Ip
.84.88.92
.961.0
LTD TIME
FINE
TEST
s s
l X 2L lsd X 1.5
1520
25304060
STD TIME
MADE IN JAPAN
00.10.2
0.30.4 0.5
X In max.
GFR P.U.lg
0.1
0.20.3
0.5
GFR TIME
SEC.SEC.
0.30.3
0.80.81.51.5
3.03.0
T RIP A LA RM
G
TAL
Remarks:
All functions marked in gray areincluded
asstandardequipment(standardrelay MT1A).
This overview lists the maximum possible
functionality of the units.
Triprelayswith special functions (functions
wich are notmarked in gray)have to be
ordered seperately (please refer to orderinformation on page 30 and31).
Page 28 and following contain a detailleddescription of all special functions.
An external power supply for trip indi-cation and relay control is required forall type of relays.The voltagerangeforthe power supply must be within one ofthe following ranges:
- 1: AC 100120 / 200240 V (standard)- 4: DC2460V
(other voltages on request)The LED will go out when the controlpower supply is interrupted or whenthe RESET button is pushed.
An external self-hold circuitis required,as the alarmsignal pulsehas a durationof only 0.03 sec.
The contact rating (A) for the signalrelays arelisted in the table below.
Voltage(V) Resistiveload Inductiveload*
AC
120
2 2250
DC30
125 0.2 0.1
* cos =0,4, L/R= 7 msec
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
25/5225MITSUBISHI ELECTRIC SUPER AE
ELECTRONIC TRIP RELAY
Basic Setting
RatedCurrent
RATEDCURRENT
The rated current will be preset to a fixedvalueat timeof shipment (select a valuebetween 0.5 and 10 (AE4000-SSA/SSC:0.8and 1.0)of the maximum rated current).
The value is stamped on the relay.
Note:Specify the preset rated current in writtenform when ordering.
Overload Protection
Long-TimeDelayCurrent(IL)
LTDP.U.
Rated current (In) x setting(A)
1-1.05-1.1-1.15-1.2
The breaker trips within a range from(IL) x 0.95to 1.05.
The load current is displayed as a percent-ageof the long-time delay current (IL).
The pre-alarm set value varies proportion-ally to the long-time delay current setting.
Long-Time Delay Time(TL)
LTD TIME
Time setting (in seconds)
15-20-25-30-40-60
This value specifies the operating timewhen the current flowingis the long-timedelay current set value (IL)x 1.2.
The pre-alarm operating time is half of thelong-time delay setting.
Long-TimeDelayTimeFINE(T L)
FINE
Fine adjustment of long-time delay time.
Detailled information on request.
This setting has no influence on thepre-alarm time.
Pre-Alarm (Ip)
PALP.U.
Long-time-delay current value (IL) x setting
0.84-0.88-0.92-0.96-1.0
Threshold value for pre-alarm operation.
Short-Circuit Protection (STD)
Short-TimeDelay P.U.Current (Isd)
STD P.U.
Rated current (In) x setting(A)
2-2.5-3-3.5-4-4.5
Current threshold value settingforshort-time delay tripping.
Short-Time Delay Time(T sd)
STDTIME
Time delay setting (in seconds)
0-0.1-0.2-0.3-0.4-0.5
The setting value is the operating timewhen the current flowing is the short-time
delay current setting(I sd)x1.5.If thedialis set to 0 seconds the breakerwill
tripin 0.05 seconds.
Short-TimeDelayLockButton
STDLOCK
When measuring the instantaneous trip-pingcurrent,press the short time delay
operation inhibit button (STDLOCK) inorder to disable the short-time-delay trip-ping function.
Short-Circuit Protection (instantaneous)
Instantaneous P.U.Current (Ii)
INSTP.U.
Rated current (In) x setting(A)
4-6-8-10-12-16
AE5000:4-6-8-10-12AE6300:4-6-8-10
Setsthe threshold current value forinstantaneous tripping.
Ground Fault Protection
GroundFaultP.U.Current(Ig)
GFR P.U.
Max.rated current (In max.) x setting(A)
0.1-0.2-0.3-0.5
AE4000-SSA/SSC,AE40006300:0.2-0.3-0.5
This function is not available if max.rated current values Inmax is less than
630A andfor AE1000-SH,Inmax630A.
GroundFaultTime(Tg)
GFRTIME
Time setting (in seconds)
0.3-0.8-1.5-3The setting specifies the operating timewhen the current flowing is the groundfault current value setting(Ig) x 1.5.
Ground Fault Trip Switch
GFRTRIP / ALARM
The breaker will trip when the switch is
set to the "TRIP" position.
When the switch is set to the "ALARM"
positiona red trip indicator LED willlight up andthe relay output will be acti-
vated when a ground fault occurs; thebreaker will not trip,however.
The switch must be set to the "TRIP"position when the overcurrent trippingcharacteristic is activated (referto p.28).
Others
Test Terminal
Test functions:
Tripping characteristics
Long-time-delay (L)
Short-time-delay (S)
Instantaneous (I)
Pre-alarm (P)
Ground fault (GFR)
A specialtesting deviceis required(see page 19).
The bold marked values show the set-tingat time of shipment.
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
26/5226 MITSUBISHI ELECTRICSUPER AE
ELECTRONIC TRIP RELAY
How to Adjust the Electronic Trip Relay
S type setting dial operation schematic General use
Max. rated current In max
Rated Current In
GFR Ground Fault P.U. Current Ig orER Earth Leackage Fault Current In
INST Instantaneous P.U. Current Ii
STD Short-Time Delay P.U. Current Isd
UninterruptedCurrent Iu
Pre-Alarm Current Ip
Load Current Indicator LEDs
Load Current Indicator LEDs
Pre-Alarm Current IpLTD Long-TimeDelay Current IL
STD Short-Time Delay P.U. Current Isd
INST Instantaneous P.U. Current Ii
GFR Ground Fault P.U. Current Ig
Rated Current In
Max. rated current In max
M type setting dial operation schematic Generator protector use
Characteristic curve for the example next page
1000
500400
300
200
100
605040
30
20
10
54
3
2
1
0,50,4
0,3
0,2
0,1
0,050,04
0,03
0,02
0,01
Groundfault current(Ig) settingrange
Short-time delay operation time(Tsd ) settingrange
Ground fault operation time(T g) settingrange
Pre-alarmcurrent (Ip) settingrange
Long-time delay operation time(TL) settingrange
Short-timedelay current(Isd) settingrange
Op
eratingtime[sec]
Current (%)
Instantaneous current(I i) settingrange
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
27/5227MITSUBISHI ELECTRIC SUPER AE
ELECTRONIC TRIP RELAY
Setting example for S Type Generaluse
The following example shows in a simpleway how you canset your required valueson the S type trip relay.
Additional all current settings and opera-tion times arecalculated and shown.
Functions Description Setting value
Max. Rated Current Inmax 1600A
Set rated value In 1280AUniterrupted Current Iu 1152A
Long-Time Delay Time LTD TIME 100 s 20 % (at 2304 A)
Short-TimeDelayP.U.Current Isd 3840A15%
Short-Time Delay Time STD TIME 0.3 s 20 % (at 5760 A)
Functions Description Setting value
Ins tan taneous P .U. C urren t Ii 15360A15%
Pre-Alarm Current Ip 921,6A10%Pre-alarmp ick-up t ime PALp ick-up t ime 50 s 2 0 % ( at2304 A )
Ground Fault P.U. Current Ig 160A20%
Ground Fault Time GFR TIME 0.8 s 20 % (at 240 A)
Actual settings areas in the following table
In =0.8 InmaxIn =0.81600AIn =1280A
Iu =0.9 InIn =0.81280A
In =1152A
Ip =0.8 IuIn =0.81152AIn =921,6A
Ig =0.1 InmaxIn =0.11600A
In =160A
GFR TIME= 0.8 s(at Ig 1.5=1601.5=240A)
In,max= 1600A
Isd =3 InIsd=3 1280AIsd=3840 A
Ii= 12 InIi =121280A
Ii =15360A
LTD TIME TL =100 s
(at Iu 2 =11522=2304A)
STD TIMETsd =0.3 s(at Isd 1.5=38401.5=5760A)
Pre-alarm pick-up time= 0.5 TL = 5 0 s(at Iu 2 = 1 1 5 2 2=2304A)
X Iu
INST P.U. li
4
68
1012 16
0.5
0.60.7
0.8 0.9 1.0
X Iu
STD P.U. lsd
STD LOCK
2
34
6 8 1 0
TRIP INDICATORL S/I G
PAL P.U.
60 80 100 OVER
RESET
TALALARM
RATED CURRENT MAX.(CT RATING) RATED CURRENT
LOAD CURRENT % lu
SPGT - C1AT
ELECTRONICTRIP RELAYMODEL
X IN MAX
IN MAX
UNINTERRUPTEDCURRENT Iu
X IN
.80
.84.88
.92
.96
1.0X Iu
PAL P.U.I p
I NS T M CR
0.7
0.80.9
1.0 OVER
X In max.
GFR P.U.lg
0.1
0.2
0.30.5
GFR TIME
SEC.SEC.
0.30.3
0.80.81.51.5
3.03.0
LTD TIME
TEST
SEC.
lu X 2 lsd X 1.5
12
2550
100150
STD TIME
SEC.
MADE IN JAPAN
0
0.10.2
0.3 0.4 0.5
PAL OUT
T RI P A LA RM
1600 A
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
28/52MITSUBISHI ELECTRICSUPER AE28
ELECTRONIC TRIP RELAY
Special Functions Accessories
Earth leakage protection (ER)
The earth leakage alarm facility is realised
with an electronictrip relay with earthleakage protection (ER characteristics) andan externalZCT (referto page 18 and 20).
When earth leakage current flows analarm is activated but the breakerdoes nottrip (see the earth leakage alarm systemwiring diagram).
If you require the breaker to trip uponearthleakageyou must also install an SHT
device(see the earth leakagetripping sys-temwiring diagram).Observe the voltagerange specificationsforthevoltage trippingdevice SHT;the voltage tripping device (SHT)issuitable for250 V AC/DCor less.
The earth leakage protection is not avail-ablefor AE4000 to AE6300-SS breakers.
ETR
N2
L2
N1
L1
SHT
713
C1C2 714
ETR
BZ
N2 N1
L1
513
544
L2
If the load current flowing through thebreakerexceeds the preset value the "PAL"LED lights up anda relay output is acti-vated.This is a useful option for ensuring a
continuous power supply to an
important circuit.The operating characteristic shown in the
graph is proportional to half of thelong-time-delay tripping characteristic. Ithas been designed to prevent unneces-sary alarms from inrush currents to the
load.
TLrepresents the long-time delay time.
The general use relay output is of aself-hold type; the relay typefor generatorprotection features auto reset.(The con-trol power supply and reset button
required for theLED display is also used
internally for the pre-alarm).
1 h
10 min.
2 min.
1 min.30 sec
10 sec
4 sec
1 sec
0.4 sec
0.1 sec
0.04 sec
2010 40 60100
200 400600
10002000
40006000
70% Pre-alarm
current setting range
Overcurrent
characteristics
T =50 secLPre-alarm
characteristics
Pre-alarm
operating time
for T =150 secL
Pre-alarm
operating time
for T =50 secL
OVER
T =150 secL
Pre-alarm (PAL)
Ground fault protection (GFR)
ExternalZCT forGroundwire
Earth leakagetrippingsystem
Controlpower supply
Electronictriprelay
(withearthleakageprotection)
Earth leakagetrippingsystem
ExternalZCT forGroundwire
Controlpower supply
Electronictriprelay
(withearthleakageprotection)
Earth leakagealarmbuzzer
Characteristics (type S)
Current (%)
Time(t)
When ground fault currents of severalhundred amperes flow,it is possible thatthe long-time-delay or short-time-delayfunctions may not be able to protectthe
circuit.The ground fault function (GFR) canprovide the necessary protection in thesesituations. Response sensitivity can be setin the range 0.10.20.30.5,multiplied by
the maximum rated current (IN max. );oper-ating time can be set in the range
0.30.81.53 seconds.No control power supply is requiredforthis function.
Similary with a 3 pole breaker, groundfault protection is also possible for a3-phase, 3-wire circuit.
In a 3-phase, 4-wire circuit ground faultprotection is also possible if the3-pole breaker is combined with a neu-tral pole CT (NCT). See page 18 fordetails.
The ground fault protection is not avail-able if the max. rated current
(IN max.) is less than 315 A or 500 A andless than 630 A for AE1000SH.
GFR
4 pole breaker Current sensor coil
Electronictrip relay(with groundfault protectionGFR)
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
-
7/25/2019 ACB Mitsubishi Catalog
29/5229MITSUBISHI ELECTRIC SUPER AE
ELECTRONIC TRIP RELAY
The OCR alarm is a short-timeoperating
contact (NO contact)that indicates whenthebreaker hastrippedas a result of anovercurrent situation.The AL unit