ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 1 Supercedes: New
PACKAGED ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
3, 4, 5, 6, 7.5, 8.5, 10, and 12.5 TONS
RGH units are high-efficiency, single-packaged electric cooling, gas heating units that are pre-wired and pre-charged with environmentally sound R-410A HFC refrigerant. The units are factory tested in both heating and cooling modes.
STANDARD FEATURES • R-410A HFC refrigerant • SEER up to 15.6 • EER up to 13.0 • IEERs up to 14.0 with single speed indoor fan motor • IEERs up to 16.0 with 2-speed/VFD indoor fan motor • DOE, ASHRAE 90.1 and IECC compliant, and Energy Star
qualified • Single-stage cooling capacity control on all 036-072 models • Two-stage cooling capacity control on 073 -150 models. • Rated in accordance with AHRI Standard 210/240 (036-060
sizes) and 340/360 (072-150 sizes) • Designed in accordance with U L Standard 1995 • Listed by UL and UL, Canada or ETL, ETL Canada • Non-corrosive composite condensate pan in accordance with
ASHRAE 62 Standard, sloping design; side or center drain
• Gas efficiencies up to 82% • Induced draft combustion • Redundant gas valve with 1 or 2 stages of heating • Pre-painted exterior panels and primer-coated interior panels
tested to 500 hours salt spray protection • TXV refrigerant metering device on each circuit • Exclusive IGC solid-state control for on-board diagnostics with
LED error code designation, burner control logic and energy saving indoor fan motor delay
• “Low NOx” models available that meet California Air Quality Management NOx requirements and include stainless steel heat exchangers
• Cooling operating range from 35°F up to 125°F. 110 size model standard cooling operation down to 0°F (–18°C)
• Large access panels with easy grip handles and no-strip screw feature
• Two-inch disposable return air filters • Tool-less filter access door • Belt drive evaporator fan motor and pulley combinations
available on all three phase models • Direct Drive x13 (5 speed/torque) motor on 036 to 060 models • Advanced terminal board for simple safety circuit
troubleshooting and control box arrangement • Field convertible from vertical to horizontal airflow on all
models. No special kit required on 036-120 models. Supply duct kit required for 150 size model only.
• Provisions for thru-the-bottom power entry capability • Single point gas and electric connections • Full perimeter base rail with built-in rigging adapters and fork
truck slots • Scroll compressors with internal line-break overload protection • Copper tube, aluminum fin coils • 24-volt control circuit protected with resettable circuit breaker • Permanently lubricated evaporator-fan motor • Permanently lubricated, totally enclosed, shaft down condenser
motors • Low pressure, freeze protection, and high pressure switches • Exclusive IGC anti-cycle protection for gas heat operation • Solid-state electronic direct spark ignition system • Liquid line filter drier STANDARD WARRANTY • 10-year heat exchanger parts – Aluminized
15-year Stainless Steel • 5-year compressor • 1-year parts FACTORY INSTALLED OPTIONS INCLUDE BUT NOT LIMITED TO: • Economizer and two position damper options • Disconnect and convenience outlet options • Multiple optional belt drive motor and pulley combinations • Supply air and return air smoke detectors • CO2 sensor options • Corrosion resistant options for evaporator and condenser coils • Optional Stainless Steel Heat Exchanger • Hot Gas Re-Heat dehumidification system. • 2-Speed indoor fan motor with VFD controller on 073 to 150
size models. Standard on 110 and 120 models. • Hinged Access Doors • Condensate Overflow Switch • Low and Ultra low leak economizers available. • Powered and non-powered convenience outlet
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 2 Supercedes: New
Position No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Example: R G H 0 7 2 L D A B 0 A A A
R = Rooftop
G = Gas Electric TYPE
H = High Efficiency ASHRAE 90.1 / Energy Star EFFICIENCY
036 = 36,000 BTUH = 3 tons 048 = 48,000 BTUH = 4 tons 060 = 60,000 BTUH = 5 tons 072 = 72,000 BTUH = 6 tons (1-Stage Cooling) 073 = 72,000 BTUH = 6 tons (2-Satge Cooling) 090 = 90,000 BTUH = 7.5 tons ( 2 Compressors) 102 = 102,000 BTUH = 8.5 tons (2 Compressors) 110 = 110,000 BTUH = 10 tons (2 Compressors) 12.0 EER 120 = 120,000 BTUH = 10 tons ( 2 Compressors) 11.5 EER 150 = 150,000 BTUH - 12.5 tons (2 compressors) NOMINAL COOLING CAPACITY
H = 208/230-3-60 K = 208/230-1-60 L = 460-3-60 S = 575-3-60 VOLTAGE
D = Low Gas Heat E = Medium Gas Heat F = High Gas Heat L = Low Gas Heat, Low NOx M = Medium Gas Heat, Low NOx N = High Gas Heat, Low NOx S = Low Gas Heat, Stainless Steel Heat Exchanger R = Medium Gas Heat, Stainless Steel Heat Exchanger T = High Gas Heat, Stainless Steel Heat Exchanger HEATING CAPACITY (See Spec Sheet for Actual Capacity)
X = Direct Drive - X13 A = Standard Motor / Drive - Belt Drive B = High Static Motor / Drive - Belt Drive E = High Static - Efficiency Motor / Drive - Belt Drive C = Medium Static Motor - Std or High Efficiency Motor G = High Static Motor / Drive with Hot Gas Re-Heat H = High Static Motor with Hot Gas Re-Heat MOTOR ( Indoor Fan ) See spec sheet for more details)
A = None B = Temp Economizer w/Baro-relief E = Temp Economizer w/Baro-relief + CO2 Sensor H = Enthalpy Economizer w/Baro-relief L = Enthalpy Economizer w/Baro-relief + CO2 Sensor U = Temp Ultra Low Leak Economizer w/Baro-relief W = Enthalpy Ultra Low Leak Economizer w/Baro-relief P = 2-Position damper OUTDOOR AIR OPTIONS / CONTROL (See Spec Sheet for Details)
0A = Standard 4B = Non Fused Disconnect Switch AA = Hinged Acess Panels AT = Un-Powered Convenience Outlet BB = Powered Convenience Outlet BP = Return Air Smoke Detector BR = Supply Air Smoke Detector CJ = Condensate Overflow Switch OTHER FACTORY INSTALLED OPTIONS
A = Aluminum / Copper Cond & Evap Coil B = Precoat Alum/Cu Cond & Alum / Cu Evap C = E-Coated Alum/Cu Cond & Alum / Cu Evap D = E-Coated Alum / Cu Cond & Evap E = Cu / Cu Cond & Alum/Cu Evap F = Copper/Copper Cond & Evap COIL FACTORY INSTALLED OPTIONS
A = Standard Single Speed Indoor Fan Motor. For W7212 controls B = Standard Single Speed Indoor Fan Motor. For W7220 controls T = 2-Speed Indoor Motor Controller (VFD) INDOOR FAN MOTOR
RGH - ROOFTOP PRODUCT MODEL NUMBER IDENTIFICATION GUIDE
Note: On single phase (K voltage code) models, the following are not available as factory installed options. - Coated or copper fin coils - Economizers or 2 position dampers - Hot Gas Re-Heat
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 3 Supercedes: New
FIELD INSTALLED ACCESSORIES
ECONOMI$ER IV (FOR 1-SPEED INDOOR FAN MOTOR ONLY) LOW LEAK CONTROLLER INCLUDED
VERTICAL
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRECOMZR020A02
LOW LEAK Vertical EconoMi$er IV with solid-state controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in non-DDC applications.
036-060 Elect Mech
Controls
CRECOMZR021A03
LOW LEAK Vertical EconoMi$er IV with solid-state controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in non-DDC applications.
072-120 Elect Mech
Controls
CRECOMZR062A00
LOW LEAK Vertical EconoMi$er IV with solid-state controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in non-DDC applications.
150 Elect Mech
Controls
1 EconoMi$er IV cannot be installed with an EconoMi$er X, Manual Damper or Motorized Damper. 2 When installed on a unit with hinged panels, hinged panel access kit is also required.
ECONOMI$ER IV (FOR 1 - SPEED INDOOR FAN MOTOR ONLY) LOW LEAK CONTROLLER INCLUDED
HORIZONTAL
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRECOMZR024A02
LOW LEAK Horizontal EconoMi$er IV with solid-state controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in non-DDC applications.
036-060 Elect Mech
Controls
CRECOMZR025A02
LOW LEAK Horizontal EconoMi$er IV with solid-state controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in non-DDC applications.
072-120 Elect Mech
Controls
CRECOMZR064A00
LOW LEAK Horizontal EconoMi$er IV with solid-state controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in non-DDC applications.
150 Elect Mech
Controls
1 EconoMi$er IV cannot be installed with an EconoMi$er X, Manual Damper or Motorized Damper. 2 When installed on a unit with hinged panels, hinged panel access kit is also required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 4 Supercedes: New
ECONOMI$ER X (FOR 1 & 2-SPEED INDOOR FAN MOTOR) – LOW LEAK, CONTROLLER INCLUDED
VERTICAL
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRECOMZR076A00
LOW LEAK - Vertical EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in electro mechanical controls only. Controller meets California Title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.
036-060 Elect Mech
Controls
CRECOMZR078A00
LOW LEAK - Vertical EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in electro mechanical controls only. Controller meets California Title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.
072-120 Elect Mech
Controls
CRECOMZR080A00
LOW LEAK - Vertical EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in electro mechanical controls only. Controller meets California Title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.
150 Elect Mech
Controls
1 EconoMi$er X cannot be installed with an EconoMi$er IV, Manual Damper or Motorized Damper. 2 When installed on a unit with hinged panels, hinged panel access kit is also required.
HORIZONTAL ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRECOMZR077A00
LOW LEAK - Horizontal EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in electro mechanical controls only. Controller meets California title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.
036-060 Elect Mech
Controls
CRECOMZR079A00
LOW LEAK - Horizontal EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in electro mechanical controls only. Controller meets California Title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.
072-120 Elect Mech
Controls
CRECOMZR081A00
LOW LEAK - Horizontal EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible for use in electro mechanical controls only. Controller meets California Title 24 Section 120.2 Fault Detection and Diagnostic (FDD) requirements.
150 Elect Mech
Controls
1 EconoMi$er X cannot be installed with an EconoMi$er IV, Manual Damper or Motorized Damper. 2 When installed on a unit with hinged panels, hinged panel access kit is also required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 5 Supercedes: New
ECONOMI$ER X (FOR 1 & 2-SPEED INDOOR FAN MOTOR) ULTRA LOW LEAK CONTROLLER INCLUDED
VERTICAL
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRECOMZR067A01
Ultra LOW LEAK - Vertical EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible, for use in electro mechanical controls only. Also includes return, outside air, and relief air damper leakage that meets Title 24 section 140.4 and ASHRAE 90.1 requirements. Controller meets California Title 24 Fault Detection and Diagnostic (FDD) requirements. Also meets AMCA Class 1A economizer damper test standards and labeling.
036-060 Elect Mech
Controls
CRECOMZR069A01
Ultra LOW LEAK - Vertical EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible, for use in electro mechanical controls only. Also includes return, outside air, and relief air damper leakage that meets Title 24 section 140.4 and ASHRAE 90.1 requirements. Controller meets California Title 24 Fault Detection and Diagnostic (FDD) requirements. Also meets AMCA Class 1A economizer damper test standards and labeling.
072-120 Elect Mech
Controls
CRECOMZR071A01
Ultra LOW LEAK - Vertical EconoMi$er X with solid-state W7220 controller, gear-driven, modulating damper, spring return actuator, up to 100% barometric relief, supply and outdoor air temperature sensors, and CO2 sensor compatible, for use in electro mechanical controls only. Also includes return, outside air, and relief air damper leakage that meets Title 24 section 140.4 and ASHRAE 90.1 requirements. Controller meets California Title 24 Fault Detection and Diagnostic (FDD) requirements. Also meets AMCA Class 1A economizer damper test standards and labeling.
150 Elect Mech
Controls
NOTES: 1 EconoMi$er X cannot be installed with an EconoMi$er IV, Manual Damper or Motorized Damper. 2 Currently only available on vertical air flow configuration models. Contact your local MicroMetl account manager 1-800-884-4662 if horizontal model is required. 3 When installed on a unit with hinged panels, hinged panel access kit is also required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 6 Supercedes: New
ACCESSORY KITS FOR UNITS WITH HINGED ACCESS PANELS
VERTICAL ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRPECONV003A00 Vertical accessory kit is required when field installing a vertical economizer, 2-position damper or manual damper on a unit that has hinged access panels. Includes angle and seal strip.
036-060
DNPECONV004A00* (CRPECONV004A00)
Vertical accessory kit is required when field installing a vertical economizer, 2-position damper or manual damper on a unit that has hinged access panels. Includes angle and seal strip.
072-120
CRPECONV007A00 or CRPECONV007B00
Vertical accessory kit is required when field installing a vertical economizer, power exhaust, 2-position damper, or manual damper on a unit that has hinged access panels. Includes angle and seal strip.
150
HORIZONTAL
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRHNGPNL001A00 Horizontal accessory kit is required when field installing a horizontal economizer, 2-position damper or manual damper on a unit that has hinged access panels. Includes door panel, angle and seal strip.
036-060
CRHNGPNL002A00 Horizontal accessory kit is required when field installing a horizontal economizer, 2-position damper or manual damper on a unit that has hinged access panels. Includes door panel, angle and seal strip.
072-120
CRHNGPNL003A00
Currently in development - please contact application engineering ... Horizontal accessory kit is required when field installing a horizontal economizer, power exhaust, 2-position damper or manual damper on a unit that has hinged access panels. Includes door panel, angle and seal strip.
150
* DN accessory model numbers are available until inventory is depleted. Once inventory is depleted, use the CR accessory model
number for ordering.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 7 Supercedes: New
LOUVERED HAIL GUARDS – CONDENSER COIL ORDERING NUMBER DESCRIPTION APPLICATION
USAGE
CRLVHLGD012A00 Louvered Condenser Coil Hail Guard - Includes louvered panel(s) to protect condenser coil from damage and vandalism. 036
CRLVHLGD013A00 Louvered Condenser Coil Hail Guard - Includes louvered panel(s) to protect condenser coil from damage and vandalism. 048-060
CRLVHLGD014A00 Louvered Condenser Coil Hail Guard - Includes louvered panel(s) to protect condenser coil from damage and vandalism. 072/073
CRLVHLGD016A00 Louvered Condenser Coil Hail Guard - Includes louvered panel(s) to protect condenser coil from damage and vandalism. 090-120
CRLVHLGD032A00 Louvered Condenser Coil Hail Guard - Includes louvered panel(s) to protect condenser coil from damage and vandalism. 150
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 8 Supercedes: New
ECONOMIZER SENSOR USAGE CHART
DESIRED CONTROL METHOD
ECONOMI$ER IV 1 ECONOMI$ER X 1
REQUIRED FIELD-INSTALLED SENSOR(S)
REQUIRED FIELD-INSTALLED SENSOR(S)
Single Dry Bulb Control None. Outside Air dry bulb sensor is factory installed.
None. Outside Air dry bulb sensor is factory installed.
Single Enthalpy Control (1) AXB078ENT (1) FAST #1185124
Differential Enthalpy Control (1) AXB078ENT & (1) DNENTDIF004A00
(2) FAST #1185124
To Add CO2 DCV Control with above:
Duct Mount
(1) DNCBDIOX005A00
(1) DNCBDIOX005A00
NOTE: 1 OAT and SAT sensors included for EconoMi$er IV.or EconoMi$er X
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
DNTEMPSN002A00* (CRTEMPSN002A00)
Outdoor or Return Dry Bulb Temperature Sensor used with Electro- Mechanical control. EconoMi$er IV
DNCBDIOX005A00* (CRCBDIOX005A00)
CO2 Sensor for use in return airstream. Also includes Aspirator Box required for Duct Mounting. EconoMi$er IV, X
AXB078ENT (--HH--57AC-078)
Accu-sensor || Economizer differential Enthalpy Control Upgrade EconoMi$er IV
DNENTDIF004A00* (CRENTDIF004A00)
Return Air Enthalpy Sensor used with Electro-Mechanical controls, use with AXB078ENT for differential enthalpy control. EconoMi$er IV
FAST #1185124 (--HH57AC--081)
Enthalpy Control for W7220 Controller only, (One required for single enthalpy, two required for different enthalpy) Economi$er X
* DN accessory model numbers are available until inventory is depleted. Once inventory is depleted, use the
CR accessory model number for ordering.
NOTE: 1 Supply air temperature sensor (SAT and low ambient lockout switch) provided with EconoMi$er IV or EconoMi$er X
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 9 Supercedes: New
POWER EXHAUST OPTIONS
VERTICAL ORDERING NUMBER DESCRIPTION APPLICATION USAGE
CRPWREXH030A01 Power Exhaust System 036-060
208/230-1-60 208/230-3-60
CRPWREXH021A01 Power Exhaust System 036-060 460-3-60
CRPWREXH022A01 Power Exhaust System 072-120 208/230-3-60
CRPWREXH023A01 Power Exhaust System 072-120 460-3-60
CRPWREXH080A00 Power Exhaust System 150 208/230-3-60
CRPWREXH081A00 Power Exhaust System 150 460-3-60
NOTES: 1 Vertical Power Exhaust requires a vertical Economizer 2 Vertical Power Exhaust package includes exhaust hood, screens and propeller fan system
HORIZONTAL
ORDERING NUMBER DESCRIPTION APPLICATION USAGE
CRPWREXH028A01 Horizontal Power Exhaust - Mounted on Return Ductwork
036-120 208/230-1-60 208/230-3-60
575-3-60
CRPWREXH029A01 Horizontal Power Exhaust - Mounted on Return Ductwork
036-120 460-3-60
CRPWREXH082A00 Horizontal Power Exhaust –
Mounted on Return Ductwork 150
208/230-3-60 575-3-60
CRPWREXH083A00 Horizontal Power Exhaust – Mounted on Return Ductwork
150 460-3-60
NOTES: 1 Horizontal Power Exhaust should be duct-mounted in the return duct 2 Horizontal Power Exhaust package includes exhaust hood, screens, and propeller fan system
575V TRANSFORMER ORDERING
NUMBER / FAST # DESCRIPTION APPLICATION USAGE
--HT--01AH-859 / 1171494
Transformer for conversion from 575 volt to 208/230 volt power exhaust applications.
Convert from 575 Volt to 208-230 Volt Power Exhaust applications.
NOTES: 1. Vertical power exhaust package includes exhaust hood, screens and propeller fan system. 2. 24” Roof curbs are NOT required with vertical power exhaust. 3. Horizontal power exhaust should be duct-mounted in the return ductwork and is supplied with a single fan and wiring harness. 4. Both vertical and horizontal power exhaust packages can be used with either EconoMi$er IV or EconoMi$er X. In either case, the power exhaust is
controlled by the EconoMi$er IV, X controller. 5. Order --HT--01AH-859, FAST# 1171494, for 575V applications.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 10 Supercedes: New
OUTDOOR AIR DAMPER OPTIONS
MANUAL OUTDOOR AIR DAMPERS ORDERING NUMBER DESCRIPTION APPLICATION USAGE 1
CRMANDPR001A03 25% Open Manual Outdoor Air Damper 036-060 CRMANDPR002A03 25% Open Manual Outdoor Air Damper 072-120 CRMANDPR001A02 50% Open Manual Outdoor Air Damper 036-060 CRMANDPR002A02 50% Open Manual Outdoor Air Damper 072-120 CRMANDPR011A00 50% Open Manual Outdoor Air Damper 150
NOTE: 1 EconoMi$er IV, EconoMi$er X, Manual Damper and 2-Pos Motorized Damper are all mutually exclusive and cannot be installed together.
MOTORIZED OUTDOOR AIR DAMPERS
ORDERING NUMBER DESCRIPTION APPLICATION USAGE 1
CRTWOPOS010A00 Motorized 2-position outdoor air damper (25-100% Outdoor Air) 036-060
CRTWOPOS011A00 Motorized 2-position outdoor air damper (25-100% Outdoor Air) 072-120
CRTWOPOS014A00 Motorized 2-position outdoor air damper (25-100% Outdoor Air) 150
NOTE: 1 EconoMi$er IV, EconoMi$er X, Manual Damper and 2-Position Motorized Damper are all mutually exclusive and cannot be installed together. ADDITIONAL NOTES:
• Manual dampers include hood assembly, bird screen, adjustable damper blade (to allow up to the rated outdoor air %), and bottom panel with opening.
• Motorized dampers include bottom panel with opening (100% 2-position damper includes 30% barometric relief capability), and adjustable damper (to allow up to the rated outdoor air %).
• Motorized dampers will close on loss of power to the rooftop unit. • Manual and Motorized dampers are not compatible with a vertical power exhaust module
SPECIAL – 150 SIZE SPECIFIC ACCESSORIES ORDERING NUMBER DESCRIPTION APPLICATION
USAGE
CRDISBKT001A00
Disconnect Switch Bracket - Provides a pre-engineered and sized mounting bracket for applications requiring a unit mounted fused and non-fused disconnect of greater than 100 amps. Bracket assures that no damage will occur to coils when mounting with screws and other fasteners.
150
CRDUCTCV002A00 Supply Duct Cover - This supply duct cover is required when field converting the factory standard vertical duct supply to horizontal duct supply configuration. One required per unit.
150
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 11 Supercedes: New
ROOF CURB OPTIONS
STANDARD ROOF CURBS
ORDERING NUMBER DESCRIPTION APPLICATION USAGE
CRRFCURB001A01 14-inch Tall Roof Curb. Complies with NRCA standards. Ductwork attaches to the roof curb. Includes thru-the-bottom capability. 036-060
CRRFCURB003A01 14-inch Tall Roof Curb. Complies with NRCA standards. Ductwork attaches to the roof curb. Includes thru-the-bottom capability. 072-120
CRRFCURB002A01 24-inch Tall Roof Curb. Complies with NRCA standards. Ductwork attaches to the roof curb. Includes thru-the-bottom capability. 036-060
CRRFCURB004A01 24-inch Tall Roof Curb. Complies with NRCA standards. Ductwork attaches to the roof curb. Includes thru-the-bottom capability. 072-120
CRRFCURB074A00 14-inch Tall Roof Curb. Complies with NRCA standards. Ductwork attaches to the roof curb. Includes thru-the-bottom capability. 150
CRRFCURB075A00 24-inch Tall Roof Curb. Complies with NRCA standards. Ductwork attaches to the roof curb. Includes thru-the-bottom capability. 150
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 12 Supercedes: New
THRU-THE-BOTTOM CONNECTION KITS
ORDERING NUMBER DESCRIPTION APPLICATION USAGE
CRBTMPWR008A00
Thru-the-bottom electrical connections and thru-the-curb (not thru the bottom) gas connections. Includes a 3/4-inch diameter liquid tight conduit fitting for high voltage power wires and (2) 1/2-inch diameter liquid tight conduit fittings for thermostat wires and convenience outlet wires. Includes a 3/4-inch inside pipe coupling and gas plate assembly for thru-the-curb connections. Provides for watertight seals.
036-060
CRBTMPWR009A00
Thru-the bottom power, control and gas connections. Includes a 3/4-inch diameter liquid tight conduit fitting for high voltage power wires, (2) 1/2-inch diameter liquid tight conduits for thermostat wires and convenience outlet wires and 1/2-inch gas adapter fitting for gas piping. Provides for watertight seal.
036-060
CRBTMPWR002A01
Thru-the-bottom electrical connections and thru-the-curb (not thru the bottom) gas connections. Includes a 1-1/4-inch diameter liquid tight conduit fitting for high voltage power wires and (2) 1/2-inch diameter liquid tight conduit fittings for thermostat wires and convenience outlet wires. Includes a 3/4-inch inside pipe coupling and gas plate assembly for thru-the-curb connections. Provides for watertight seals.
072-120
CRBTMPWR004A01
Thru-the bottom power, control and gas connections. Includes a 1-1/4-inch diameter liquid tight conduit fitting for high voltage power wires, (2) 1/2-inch diameter liquid tight conduits for thermostat wires and convenience outlet wires and 3/4-inch gas adapter fitting for gas piping. Provides for watertight seal.
072-120
CRBTMPWR005A00
Thru-the bottom power, control and gas connections. Includes a 1-1/4-inch diameter liquid tight conduit fitting for high voltage power wires, (2) 1/2-inch diameter liquid tight conduits for thermostat wires and convenience outlet wires and 3/4-inch gas adapter fitting for gas piping, 4 cover plates, and gaskets for watertight seal.
150
CRBTMPWR006A00
Thru-the bottom power, control and gas connections. Includes a 1-1/2-inch diameter liquid tight conduit fitting for high voltage power wires, (2) 1/2-inch diameter liquid tight conduits for thermostat wires and convenience outlet wires and 3/4-inch gas adapter fitting for gas piping, 4 cover plates, and gaskets for watertight seal.
150
CRBTMPWR007A00
Thru-the bottom power, control and gas connections. Includes a 2-inch diameter liquid tight conduit fitting for high voltage power wires, (2) 1/2-inch diameter liquid tight conduits for thermostat wires and convenience outlet wires and 3/4-inch gas adapter fitting for gas piping, 4 cover plates, and gaskets for watertight seal
150
NOTE: Access to the bottom of the RTU is required to install a THRU-THE-BOTTOM Connection Kit. Recommend installing kit prior to installing RTU on roof curb.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 13 Supercedes: New
FIELD INSTALLED ACCESSORIES
Table 1. NATURAL GAS & NATURAL GAS LOW NOX HIGH ALTITUDE KITS 036-060
Unit Size - Natural Gas Unit Size - Natural Gas - LOW NOX
ELEVATION UNIT SIZE (VOLTAGE) 036 - 060 (Three Phase) 036 - 060 (Single Phase) ELEVATION UNIT SIZE
(VOLTAGE) 036 - 060 (Single and Three Phase)
Ft (m) Heat Size CRLPELEV****** Required Ft (m) Heat Size / Input CRLPELEV****** Required Input Kit Input Kit
0 – 2000 (610)
Low 72,000 As shipped 65,000 As shipped 0 – 2000
(610)
Low / 60,000 Std Std Std Med 115,000 As shipped 90,000 As shipped Med / 90,000 Std Std Std High 150,000 As shipped 130,000 As shipped High / 120,000 NA Std Std
2000 (610)
Low 72,000 001A00 65,000 002A00 2000 (610)
Low / 60,000 002A00 Med 115,000 90,000 008A00 Med / 90,000 High 150,000 t30 130,000 001A00 High / 120,000 001A00
3000 (914)
Low 72,000 001A00
65,000 002A00 3000 (914)
Low / 60,000 t40 Med 115,000 90,000 008A00 Med / 90,000 High 150,000 130,000 001A00 High / 120,000 001A00
4000 (1219)
Low 72,000 001A00
65,000 008A00 4000
(1219)
Low / 60,000 t41 Med 115,000 90,000 Med / 90,000 High 150,000 130,000 001A00 High / 120,000 001A00
5000 (1524)
Low 72,000 001A00
65,000 008A00 5000
(1524)
Low / 60,000 t41 Med 115,000 90,000 Med / 90,000 High 150,000 130,000 001A00 High / 120,000 001A00
6000 (1829)
Low 72,000 002A00 65,000 008A00 6000
(1829)
Low / 60,000 t42 Med 115,000 90,000 002A00 Med / 90,000 High 150,000 001A00 130,000 High / 120,000 001A00
7000 (2134)
Low 72,000 002A00 65,000 008A00 7000
(2134)
Low / 60,000 t42 Med 115,000 90,000 002A00 Med / 90,000 High 150,000 001A00 130,000 High / 120,000 001A00
8000 (2438)
Low 72,000 002A00 65,000 002A00
8000
(2438)
Low / 60,000 t43 Med 115,000 90,000 Med / 90,000 High 150,000 001A00 130,000 High / 120,000 002A00
9000 (2743)
Low 72,000 t40 65,000 002A00 9000
(2743)
Low / 60,000 t43 Med 115,000 90,000 003A00 Med / 90,000 High 150,000 001A00 130,000 008A00 High / 120,000 002A00
10000 (3048)
Low 72,000 t41 65,000 003A00 10000 (3048)
Low / 60,000 002A00 Med 115,000 90,000 Med / 90,000 High 150,000 001A00 130,000 008A00 High / 120,000 t40
11000 (3353)
Low 72,000 t42 65,000 003A00 11000 (3353)
Low / 60,000 002A00 Med 115,000 90,000 Med / 90,000 High 150,000 001A00 130,000 008A00 High / 120,000 t41
12000 (3658)
Low 72,000 t43 65,000 003A00 12000 (3658)
Low / 60,000 002A00 Med 115,000 90,000 Med / 90,000 High 150,000 002A00 130,000 002A00 High / 120,000 t42
13000 (3962)
Low 72,000 t43 65,000 003A00 13000 (3962)
Low / 60,000 003A00 Med 115,000 90,000 Med / 90,000 High 150,000 002A00 130,000 002A00 High / 120,000 t43
14000 (4267)
Low 72,000 002A00 65,000 003A00 14000 (4267)
Low / 60,000 003A00 Med 115,000 90,000 004A00 Med / 90,000 High 150,000 t 40 130,000 003A00 High / 120,000 t43
t Orifice size listed - not a kit - must be purchased separately from RCD/Fast Parts. See product data for number required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 14 Supercedes: New
Table 2. NATURAL GAS HIGH ALTITUDE KITS 072 - 120
ELEVATION UNIT SIZE 072 / 073 UNIT SIZE 090 102 UNIT SIZE 110 & 120
Ft (m) Heat Size / Input CRLPELEV******
Required Heat Size / Input CRLPELEV******
Required Heat Size / Input CRLPELEV******
Required
0 - 2000 (610)
Low / 72,000 Std Low / 125,000 Std Std Low / 180,000 Std Std Med / 125,000 Std Med / 180,000 Std Std Med / 224,000 Std Std High / 150,000 Std High / 224,000 Std Std High / 250,000 Std Std
2000 (610)
Low / 72,000 Low / 125,000 001A00
Low / 180,000 001A00 Med / 125,000 001A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000 t 30
3000 (914)
Low / 72,000 Low / 125,000 001A00
Low / 180,000 001A00 Med / 125,000 001A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
4000 (1219)
Low / 72,000 Low / 125,000 001A00
Low / 180,000 001A00 Med / 125,000 001A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
5000 (1524)
Low / 72,000 Low / 125,000 001A00
Low / 180,000 001A00 Med / 125,000 001A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
6000 (1829)
Low / 72,000 002A00 Low / 125,000 001A00
Low / 180,000 001A00 Med / 125,000 001A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
7000 (2134)
Low / 72,000 002A00 Low / 125,000 001A00
Low / 180,000 001A00 Med / 125,000 001A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
8000 (2438)
Low / 72,000 002A00 Low / 125,000 001A00
Low / 180,000 001A00 Med / 125,000 001A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
9000 (2743)
Low / 72,000 t 40 Low / 125,000 002A00
Low / 180,000 002A00 Med / 125,000 002A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000 001A00
10000 (3048)
Low / 72,000 t 41 Low / 125,000 002A00
Low / 180,000 002A00 Med / 125,000 002A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000 001A00
11000 (3353)
Low / 72,000 t 42 Low / 125,000 002A00
Low / 180,000 002A00 Med / 125,000 002A00 Med / 180,000 Med / 224,000
High / 150,000 t 40 High / 224,000 High / 250,000 001A00
12000 (3658)
Low / 72,000 t 42 Low / 125,000 t 41
Low / 180,000 t 41 Med / 125,000 t 41 Med / 180,000 Med / 224,000
High / 150,000 t 40 High / 224,000 High / 250,000 002A00
13000 (3962)
Low / 72,000 t 43 Low / 125,000 t 42
Low / 180,000 t 42 Med / 125,000 t 42 Med / 180,000 Med / 224,000
High / 150,000 t 41 High / 224,000 High / 250,000 002A00
14000 (4267)
Low / 72,000 t 43 Low / 125,000 t 43
Low / 180,000 t 43 Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 t 41 High / 224,000 High / 250,000 t 40
t Orifice size listed - not a kit - must be purchased separately from RCD/Fast Parts. See product data for number required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 15 Supercedes: New
Table 3. PROPANE GAS, PROPANE GAS LOW NOX, AND PROPANE GAS HIGH ALTITUDE KITS 036-060
Unit Size – LP Gas
ELEVATION UNIT SIZE (VOLTAGE) 036- 060 (Three Phase) 036 - 060 (Single Phase)
Ft (m) Heat Size CRLPELEV****** Required Input Kit Input Kit
0 – 2000 (610)
Low 72,000 004A00 65,000 004A00 Med 115,000 003A00 90,000 High 150,000 003A00 130,000 003A00
2000 (610)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
3000 (914)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
4000 (1219)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
5000 (1524)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
6000 (1829)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
7000 (2134)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
8000 (2438)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
9000 (2743)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
10000 (3048)
Low 72,000 004A00 65,000 004A00 Med 115,000 90,000
High 150,000 003A00 130,000
11000 (3353)
Low 72,000 004A00
65,000 004A00 Med 115,000 90,000
High 150,000 130,000
12000 (3658)
Low 72,000 004A00
65,000 t 56 Med 115,000 90,000 High 150,000 130,000 004A00
13000 (3962)
Low 72,000 004A00
65,000 t 56 Med 115,000 90,000 High 150,000 130,000 004A00
14000 (4267)
Low 72,000 t 56 65,000 t 56 Med 115,000 004A00 90,000 High 150,000 130,000 004A00
Note: Units converted to LP may have a slightly lower firing rate than the Natural Gas base unit t Orifice size listed - not a kit - must be purchased separately from RCD/Fast Parts. See product data for number required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 16 Supercedes: New
Table 4. PROPANE GAS AND PROPANE GAS HIGH ALTITUDE KITS 072-120
ELEVATION UNIT SIZE 072/073 UNIT SIZE 090 102 UNIT SIZE 110 & 120
Ft (m) Heat Size / Input CRLPELEV****** Required Heat Size / Input CRLPELEV******
Required Heat Size / Input CRLPELEV****** Required
0 - 2000 (610) Low / 72,000 004A00 Low / 125,000
003A00 Low / 180,000
003A00 Med / 125,000 003A00 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
2000 (610) Low / 72,000 004A00 Low / 125,000
003A00 Low / 180,000
003A00 Med / 125,000 003A00 Med / 180,000 Med / 224,000
High / 150,000 004A00 High / 224,000 High / 250,000
3000 (914) Low / 72,000 004A00 Low / 125,000
003A00 Low / 180,000
003A00 Med / 125,000 003A00 Med / 180,000 Med / 224,000
High / 150,000 004A00 High / 224,000 High / 250,000
4000 (1219) Low / 72,000 004A00 Low / 125,000
003A00 Low / 180,000
003A00 Med / 125,000 003A00 Med / 180,000 Med / 224,000
High / 150,000 004A00 High / 224,000 High / 250,000
5000 (1524) Low / 72,000
004A00 Low / 125,000 004A00 Low / 180,000
003A00 Med / 125,000 Med / 180,000 003A00 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
6000 (1829) Low / 72,000
004A00 Low / 125,000 004A00 Low / 180,000
003A00 Med / 125,000 Med / 180,000 003A00 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
7000 (2134) Low / 72,000
004A00 Low / 125,000 004A00 Low / 180,000
003A00 Med / 125,000 Med / 180,000 003A00 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
8000 (2438) Low / 72,000
004A00 Low / 125,000
004A00 Low / 180,000 004A00
Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000 003A00
9000 (2743) Low / 72,000
004A00 Low / 125,000
004A00 Low / 180,000 004A00
Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000 003A00
10000 (3048) Low / 72,000
004A00 Low / 125,000
004A00 Low / 180,000 004A00
Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000 003A00
11000 (3353) Low / 72,000
004A00 Low / 125,000
004A00 Low / 180,000
004A00 Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
12000 (3658) Low / 72,000
004A00 Low / 125,000
004A00 Low / 180,000
004A00 Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
13000 (3962) Low / 72,000
004A00 Low / 125,000
004A00 Low / 180,000
004A00 Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
14000 (4267) Low / 72,000
004A00 Low / 125,000
004A00 Low / 180,000
004A00 Med / 125,000 Med / 180,000 Med / 224,000
High / 150,000 High / 224,000 High / 250,000
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 17 Supercedes: New
Table 5. NATURAL GAS HIGH ALTITUDE KITS 150 SIZE
ELEVATION UNIT SIZE 150
Ft (m) Heat Size / Input CRLPELEV****** Required
0 - 2000 (610) Low / 150,000 Std Std Med / 180,000 Std Std High / 240,000 Std Std
2000 (610) Low / 150,000
007A00 Med / 180,000 High / 240,000
3000 (914) Low / 150,000
007A00 Med / 180,000 High / 240,000
4000 (1219) Low / 150,000
007A00 Med / 180,000 High / 240,000
5000 (1524) Low / 150,000
008A00 Med / 180,000 High / 240,000
6000 (1829) Low / 150,000
008A00 Med / 180,000 High / 240,000
7000 (2134) Low / 150,000
008A00 Med / 180,000 High / 240,000
8000 (2438) Low / 150,000
008A00 Med / 180,000 High / 240,000
9000 (2743) Low / 150,000
008A00 Med / 180,000 High / 240,000
10000 (3048) Low / 150,000
008A00 Med / 180,000 High / 240,000
11000 (3353) Low / 150,000
t 44 Med / 180,000 High / 240,000
12000 (3658) Low / 150,000
t 45 Med / 180,000 High / 240,000
13000 (3962) Low / 150,000
t 46 Med / 180,000 High / 240,000
14000 (4267) Low / 150,000
t 47 Med / 180,000 High / 240,000
t Orifice size listed - not a kit - must be purchased separately from RCD/Fast Parts. See product data for number required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 18 Supercedes: New
Table 6. PROPANE GAS AND PROPANE GAS HIGH ALTITUDE KITS 150 SIZE
ELEVATION UNIT SIZE 150
Ft (m) Heat Size / Input CRLPELEV****** Required
0 - 2000 (610) Low / 150,000
009A00 Med / 180,000 High / 240,000
2000 (610) Low / 150,000
009A00 Med / 180,000 High / 240,000
3000 (914) Low / 150,000
009A00 Med / 180,000 High / 240,000
4000 (1219) Low / 150,000
009A00 Med / 180,000 High / 240,000
5000 (1524) Low / 150,000
009A00 Med / 180,000 High / 240,000
6000 (1829) Low / 150,000
009A00 Med / 180,000 High / 240,000
7000 (2134) Low / 150,000
009A00 Med / 180,000 High / 240,000
8000 (2438) Low / 150,000
009A00 Med / 180,000 High / 240,000
9000 (2743) Low / 150,000
009A00 Med / 180,000 High / 240,000
10000 (3048) Low / 150,000
009A00 Med / 180,000 High / 240,000
11000 (3353) Low / 150,000
009A00 Med / 180,000 High / 240,000
12000 (3658) Low / 150,000
009A00 Med / 180,000 High / 240,000
13000 (3962) Low / 150,000
009A00 Med / 180,000 High / 240,000
14000 (4267) Low / 150,000
t 56 Med / 180,000 High / 240,000
t Orifice size listed - not a kit - must be purchased separately from RCD/Fast Parts. See product data for number required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 19 Supercedes: New
NG/LIQUID PROPANE (LP) / HIGH ALTITUDE GAS KITS ORDERING NUMBER DESCRIPTION APPLICATION
USAGE
CRLPELEV001A00 Hi Altitude conversion kit. Contains spuds sizes 31, 32, 33, 35, and 36 (5 spuds/ size) and other necessary conversion parts. Use this kit for Natural Gas high altitude applications only.
See Table Above
CRLPELEV002A00 Hi Altitude conversion kit. Contains spuds sizes 37, 38, 39, 44, and 45 (5 spuds/size) and other necessary conversion parts. Use this kit for Natural Gas high altitude applications only
See Table Above
CRLPELEV003A00
Propane and Hi Altitude conversion kit. Contains spuds sizes 46, 47, 48, 49, and 50 (5 spuds/size) and other necessary conversion parts. Use this kit to convert Natural Gas rooftops to Propane and propane high altitude applications.
See Table Above
CRLPELEV004A00
Propane and Hi Altitude conversion kit. Contains spuds sizes 51, 52, 53, 54, and 55 (5 spuds/size) and other necessary conversion parts. Use this kit to convert Natural Gas rooftops to Propane and propane high altitude applications.
See Table Above
CRLPELEV007A00 Hi Altitude conversion kit. Contains spuds sizes 36, 37, 38, and 39 (10 spuds/size) and other necessary conversion parts. Use this kit for Natural Gas high altitude applications only.
See Table Above
CRLPELEV008A00 Hi Altitude conversion kit. Contains spuds sizes 40, 41, 42, and 43 (10 spuds/size) and other necessary conversion parts. Use this kit for Natural Gas high altitude applications only.
See Table Above
CRLPELEV009A00
Propane and Hi Altitude conversion kit. Contains spuds sizes 51, 52, 53, 54, and 55 (10 spuds/size) and other necessary conversion parts. Use this kit to convert Natural Gas rooftops to Propane and propane high altitude applications.
See Table Above
HEATING UPGRADE KITS ORDERING NUMBER DESCRIPTION APPLICATION
USAGE
CRFLUEDS001A00 Flue Discharge Deflector -- Directs flue gas exhaust 90 degrees upward from current discharge. Designed to allow tighter distances between unit and combustible surfaces. 24 inch Height. AGA certified. 1
036-120 Only
CRFLUEHD001A01 Flue Exhaust Heat Shield -- Provides a sheet metal guard around the flue gas hood which prevents service personnel or small children from coming into contact with the flue hood. 1
036-120 Only
CRFLUEDS007A00 Flue Discharge Deflector – Defects flue gas exhaust 90 degrees upward from current discharge. Designed to allow tighter distances between units and combustible surfaces.
150 Only
1 CRFLUEDS001A00 and CRFLUEHD001A01 are mutually exclusive. Cannot install both on the same unit.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 20 Supercedes: New
CONTROL ACCESSORY KITS
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRDISKIT001A00 2 Speed VFD display kit – Provides the field capability to set up points and troubleshooting codes on the VFD controller. Kit includes display, and cable. If preferred, kit can be used for any associated unit with VFD.
All 2 Speed VFD Controllers
CRTIMEGD001A00
Time Guard II -- Automatically prevents the compressor from restarting for at least 4 minutes and 45 seconds after shutdown of the compressor. Not required when a commercial thermostat has a minimum 5 min time delay between cooling cycles available (One required per unit)
All Sizes
CRPHASE3001A02 Phase Monitor Control - Provides phase loss/phase reversal protection All 3-Ph 208-230 & 460v
CRPHASE3002A00 Phase Monitor Control - Provides phase loss/phase reversal protection All 575v Only
CRWINSTR001A00 Winter Start Package - Contains time delay relay for timed bypass of low pressure switch on startup. (One required per refrigerant circuit) 1 All
CRSDTEST001A00 Remote keyed attenuator / test / reset station for use with factory installed smoke detectors. Includes power, alarm & trouble indicator lights.
All
CRCONVOUT01A00 20 Amp non (unit) powered convenience outlet kit is to provide a flexible installation method that will allow code compliance for height requirements of the GFCI outlet from finished roof surface on the range of rooftop and split system products as well as the capability to relocate the outlet into a more convenient location if necessary.
All
CRCNDOVR003A00 Condensate Overflow Switch - Includes electronic controller and sensor. Compressor(s) turn off if the drain trap becomes plugged. It can be used in down flow or side discharge units.
All
1 If mechanical cooling below 25 degrees ambient is necessary, consider additional low-ambient control measures (for
example, economizer or Motormaster)
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 21 Supercedes: New
LOW AMBIENT CONTROLS
Motormaster I Usage and Parts Table (036 - 102 Models)
RGH UNITS VOLTAGE MOTOR OTHER CONTROL
NEEDED CAPACITOR MOTORMASTER I
CONTROLLER
036
208/230-1-60 HC38GE231
Fast # 1178185
CRWINSTR001A00 Keep Factory Installed 32LT900301
208/230-3-60 575-3-60*
HC38GE231
Fast # 1178185
CRWINSTR001A00 Keep Factory Installed 32LT900301
460-3-60
HC36GE461
Fast # 1178186
CRWINSTR001A00 Keep Factory Installed 32LT900611
048,060
208/230-1-60 HC40GE233
Fast # 1171974
CRWINSTR001A00 Keep Factory Installed 32LT900301
208/230-3-60 HC40GE233
Fast# 1171974
CRWINSTR001A00 Keep Factory Installed 32LT900301
460-3-60 HC40GE463
Fast # 1171975
CRWINSTR001A00
048 Size – Replace with HC91CL010Fast # 1171809
060 size – Keep Factory
Installed
32LT900611
575-3-60* HC40GE233
Fast # 1171974
CRWINSTR001A00
Replace with HC91CL010
Fast # 1171809
32LT900301
072 -102
208/230-3-60
(2) HC40GE233
Fast # 1171974
Qty (1) = 072 1-stage clg., Qty. (2) = 073 2-
stage clg, 90, 102 Sizes
CRWINSTR001A00
Keep Factory Installed 32LT900301
460-3-60
(2) HC40GE463
Fast # 1171975
Qty (1) = 072 1-stage clg. Qty. (2) = 073 2-stage clg., 090, 102
Sizes CRWINSTR001A00
Replace with HC93CA013
Fast # 1175708
32LT900611
575-3-60**
(2) HC40GE233
Fast # 1171974
Qty (1) = 072 1-stage clg, Qty. (2) = 073 2-stage clg.,090, 102
Sizes CRWINSTR001A00
Replace with HC93CA013
Fast # 1175708
32LT900301
The Capacitor Straps in the unit can be reused. If needed part numbers are as follows: HC91CL010 / Fast # 1171809 use HC98ZY071 / Fast # 1171552, and HC93CA013 / Fast # 1175708 uses 50DK507522 / Fast # 1171537. *Transformer HT01AH856 / Fast # 1178302 (0.75kva, 575v to 230v) and transformer bracket 50DK502263 / Fast # 1171069 is required. **Transformer HT01AH859 / Fast # 1171494 (1kva, 575v to 230v) and transformer bracket 50DK502263 / Fast # 1171069 is required.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 22 Supercedes: New
LOW AMBIENT CONTROLS (SIZE 036-102)
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CPLOWAMB001A00
Motormaster® II Low Ambient Control - Enables cooling system to operate down to 0° F by cycling condenser fan on and off. The control is activated by a temperature sensor. No motor change-out required.
208/230-1 208/230-3 460-3-60 All Sizes
Winter Start package CRWINSTR001A00 Also required (1 per Refrigerant Circuit)
32LT-900---301 Motormaster I Single-Phase Solid-State Variable Speed Motor Controller enables cooling down to –20°F by varying the speed on the condenser fan. Refer to Motormaster I
Usage Table 32LT-900---611
Motormaster I Single-Phase Solid-State Variable Speed Motor Controller enables cooling down to –20°F by varying the speed on the condenser fan.
HC38GE231 Fast #
1178185 Motormaster I Compatible Condenser Fan Motor
Refer to Motormaster I Usage Table
HC40GE233 Fast #
1171974 Motormaster I Compatible Condenser Fan Motor
HC40GE463 Fast #
1171975 Motormaster I Compatible Condenser Fan Motor
HC91CL010 Fast #
117107 MFD 10
HC93CA013 Fast #
1175708 Dual MFD 10 + 10
NOTES: • Sizes 036-060 require one (1) Low Ambient Controller and one (1) compatible condenser fan motor for change-out. • Sizes 072-102 require one (1) Low Ambient Controller and one (2) compatible condenser fan motor for change-out.
ACCESSORY USAGE GUIDE FOR RGH 3 to 12.5 TONS
Form No. RGH.1 Accy (1/20) Specifications subject to change without notice. 23 Supercedes: New
LOW AMBIENT CONTROLS (SIZE 120 ONLY) 1-3
ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRLOWAMB030A00 Motormaster V Low Ambient Kit. Mechanical cooling operation down to -20°F (–29°C)
120 Size 208/230-3-60
One required per unit
CRLOWAMB031A00 Motormaster V Low Ambient Kit. Mechanical cooling operation down to -20°F (–29°C)
120 Size 460-3-60
One required per unit
CRLOWAMB032A00 Motormaster V Low Ambient Kit. Mechanical cooling operation down to -20°F (–29°C).
120 Size 575-3-60
One required per unit 1 Also requires two CRWINSTR001A00 Start Packages (One per refrigerant circuit)
No motor changed is required on these specific models. 2 Size 110 has standard cooling operation down to 0°F. No accessory kit is available. 3 Units equipped with hot gas reheat include Motormaster controls. For a hot gas reheat unit to achieve low ambient
operation down to –20°F, only one CRWINSTR001A00 per circuit is required.
LOW AMBIENT CONTROLS (SIZE 150 ONLY) ORDERING NUMBER
DESCRIPTION APPLICATION USAGE
CRLOWAMB039A00
Motormaster I Low Ambient Kit. Mechanical cooling operation down to -20°F (- 29°C). Kit includes 3 motors, Motormaster controller, wiring label, and required wire ties and connectors, CRWINSTR001A00 also required (one per refrigerant circuit)
150 Size 208/230-3-60
CRLOWAMB040A00
Motormaster I Low Ambient Kit. Mechanical cooling operation down to -20°F (- 29°C). Kit includes 3 motors, Motormaster controller, wiring label, and required wire ties and connectors ) 575 Volt models also require CRTRXKIT002A00 plus CRWINSTR001A00 also required (one per refrigerant circuit)
150 Size 460-3-60 575-3-60
CRTRXKIT002A00 Motormaster® I Low Ambient Control - Transformer Kit. Must be used in conjunction with Low Ambient Controller if used on 575-3-60 volt models.
150 Size 575-3-60