Acorn Safety“Your Safety is Our Business”

Rev. Sept 2010a

A Member of Acorn Engineering's Family of Companies

Acorn Engineering• Emergency showers are plumbing fixtures • Acorn is a plumbing fixture manufacturer• Commercial showers• 55+ years of experience• Use to make safety showers –

Logan showers• Design, manufacture

are all underAcorn's control

Why Specify Acorn Safety?

What makes us different? Nothing, but…”

• We’re the new kids, able to use hindsight

• What did the competition do right or wrong?

• Incorporated all the best features, standard

• Little details that go unnoticed

Hi-Vis Yellow Powder Coat• Some competitors do,

some don’t• If it’s not stainless

steel, chrome plated or plastic

• Added corrosion and environmental protection

• Most importantly -Increased location recognition in time of need

Pre-Assembly

• Not all competitors do

• All Acorn eye and eye/face wash models 100%

• Combo shower has 40-50 pieces > 1-1/2 to 2 hours

• Loop assy complete

• Acorn shower < 1 hour

In-line Strainer

• Standard on all models• Some competition

doesn’t offer all or it’s an add$$

• Pipes never flushed enough

• Removes the slightest possibility of debris failure on startup

• Our models must work first time every time.

1/2" Ball Valve Construction

• Every competitor has had a failure

• Excessive force shearing brass stem

• Excessive torque • We use a stainless steel

stem and ball• Not every competitor has

done this• Our models must work

first time, every timeValve (closed) Valve (open)

Eyewash Push Flag

• 14 ga. stainless steel• Some competitors

use plastic, cast pot metal

• Excessive force failures

• First time, every time

Dust Covers

• Required by ANSI Z358.1• Protects from airborne

contaminants• Flush fit, won’t blow

open in wind• Easy release on

activation• Some competitors use

hard/soft plastic caps• Crack & break,

stick in heat

Barrier Free

• More building codes requiring all fixtures to be ADA or BF

• Recessed wall shower systems 4”

Barrier Free

• One of the largest offerings of BF models

Antimicrobial

• All eyewash, eye/face wash, and drench hose sprayheads and plastic showerheads are manufactured with antimicrobial ABS plastic.

• An antimicrobial agent is molded into the ABS material, providing integrated protection

Product Structure

S 1st I 2nd I 3rd I 4th I – Options

• 1st position – Showerhead

• 2nd position – Mounting

• 3rd position – Bowl (receptor configuration)

• 4th position – Drench hose

• Options

1st Position: Showerhead

• 0 – None

• 1 – Plastic

• 2 – Stainless steel

• 3 – Stainless steel, recessed

2nd Position: Mounting

• 0 – None• 1 – Vertical• 2 – Horizontal• 3 – Pedestal• 4 – Wall• 5 – Wall, recessed• 6 – Wall, swing down• 7 – Deck• 8 – Deck, swing down

• 9 – Deck, swivel• A – Deck, swivel

with 1/2" valve & push flag

• P – Portable plastic, gravity feed tank

3rd Position: Bowl/Receptor

• 0 – None• 1 – Plastic bowl,

eyewash• 2 – Plastic bowl,

eye/face wash• 3 – Stainless steel

bowl, eyewash• 4 – Stainless steel

bowl, eye/face wash

• 5 – No bowl, eyewash• 6 – No bowl,

eye/face wash• 7 – Stainless steel

shrouded bowl, eyewash

• 8 – Stainless steel shrouded bowl, eye/face wash

4th Position: Drench Hose• 0 – None• 1 – Single head with a self-closing valve• 2 – Single head with a stay-open valve • 3 – Single head with a self-closing valve & push handle • 4 – Single head with a stay-open 1/2" ball valve & push handle• 5 – Two heads with a self-closing valve• 6 – Two heads with a stay-open valve• 7 – Two heads with a self-closing valve & push handle• 8 – Two heads with a stay-open 1/2" ball valve & push handle• G – Auxiliary hand-held drench hose

(heat traced, combination shower units)• H – Auxiliary hand-held drench hose (gravity fed unit)

-Options• -AL1 = Electric alarm with light and horn• -AL2 = Electric alarm with flashing light and horn• -AL3 = Electric alarm for recessed laboratory

applications• -AS = All stainless steel• -BF = Barrier free• -BFP = Back flow preventor, double

check valve with vent to atmosphere• -BS1 = Bottom supply inlet• -C1D1 = Class 1, Division 1• -C1D2 = Class 1, Division 2

-Options• -CH12 = 12 foot coiled hose• -CS1 = SS clam shell cover• -DB1= Double pole (for flow switches)• -FLW1 = Flow switch, single pole (showers)• -FLW2 = Flow switch, single pole (eyewashes)• -FPB = Frost proof bury • -FPV = Freeze protection valve (1/2")• -FRV = Freeze resistant valve (thru wall models)• -HFC = Hand foot control• -HG = Hose guide (under counter)• -HT = Heat traced• -IWH1= Instantaneous water heater – 208V• -IWH2= Instantaneous water heater – 240V• -LGT1 = Area light (blue globe)• -LH = Left hand operation

-Options• -LWB = Less mounting bracket• -MC1 = Modesty curtain (for horizontal arms) • -MC2 = Modesty curtain (for vertical arms)• -MC3 = Modesty curtain (for wall installation)• -PAN = Waste water drain pan• -PCP = Polished chrome plated• -PDV = Push down valve (desk mounted units)• -PE_ _ = Pipe extension (in inches)• -PR_ _ = Pull rod length (in inches)• -PT1 = 1-1/4" P-trap• -RA = Recessed wall activation

-Options

• -RH = Right hand operation• -SDC = Stainless steel dust cover• -SGN1 = Sign for eyewash or eye/face wash• -SGN2 = Sign for shower• -SGN3 = Sign for shower & eyewash

or eye/face wash combination• -SGN4 = Sign for drench hose• -SPV = Scald protection valve (1/2")• -SSE = Stainless steel eyewash head• -SSH = Stainless steel hose• -STK = Shower test kit• -SV1 = 1" stainless steel ball valve• -SV2 = 1/2" stainless steel ball valve

-Options• -TMV8, TMV33, TMV83, TMV119=

Thermostatic Mixing Valves– ASSE Listed per the ASSE 1071 standard.– Available in 8, 33, 83 and 119 gpm – Exclusive "dual internal by-pass" insures

cold water flow in the event of a valve failure or loss of hot water

• -TS1 = Top supply inlet• -WS1 = Wall supply inlet• -240V = 240 volt, 50 hertz

Acorn AdvantageEye & Eye/Face Washes

• Integral in-line strainer standard

• Flip top dust covers

• Durable ABS plastic or Stainless Steel bowl

• Stainless Steel push handle (14 ga)

• Protective, hi-vis yellow powder coating

Eyewash – Wall MountedS0410

• S – Acorn Safety prefix• 1st position 0, Showerhead – none• 2nd position 4, Mounting – wall• 3rd position 1, Bowl/Receptor – plastic, eyewash• 4th position 0, Drench hose – none• Typical options – BF, PT1, TMV1

The most commonly sold plumbed Eyewash unit in the market place. Cost effective. Used anywhere.

S0410

S0430

S0470

Eye/Face Wash – Wall MountedS0420

• S – Acorn Safety prefix• 1st position 0, Showerhead – none• 2nd position 4, Mounting – wall• 3rd position 2, Bowl/Receptor – plastic, eye/face wash• 4th position 0, Drench hose – none• Typical options – BF, PT1, TMV1

Most basic eye/face wash unit sold. “Up sell” for improved employee safety.

S0420

S0440

S0440-BF

S0480

Eyewash & Eye/face – PedestalS0310, S0320 - Plastic Bowl

S0330, S0340 – Stainless Steel Bowl• S – Acorn Safety prefix• 1st position 0, Showerhead – none• 2nd position 3, Mounting – pedestal• 3rd position 1, 3, Bowl/Receptor –

plastic or stainless steel bowl, eyewash• 4th position 0, Drench hose – none• Typical options – AS, CS1, HFC, SDC, SSE, drench hose• Delivered fully assembled SS bowl is popular. Not many spec’s.

Used in open locations with drench hose.

S0310

S0330

S0340S0320

Eyewash – Laboratory S0650 – Wall mount, swing down

S0850 – Swing downS0950 – SwivelS0A50 – Swivel with 1/2" valve & push handle

• S – Acorn Safety prefix• 1st position 0, Showerhead – none• 2nd position 7, 8, 9, A, Mounting – deck• 3rd position 3, 5, Bowl/Receptor –

stainless steel or no bowl, eyewash• 4th position 0, Drench hose – none• Typical options – AS, LH, PCP, PDV, RH, SSE, TMV

Swivel with 1/2” valve doesn’t meet Z358.1 (activation).

Up sell to Eye/Face Wash.

S0850-RH

S0950-RH

S0650-RH

Faucet Mounted Eyewash

• Mounts behind the faucet spout

• Remains out of the way for everyday faucet use

• Permanent eyewash stationwhen needed.

• No plumbing required.• Installs easily onto any

faucet, in any sink, or basin.• 2 common adapters

are supplied

Eye/Face Wash – Laboratory

S0660 – Wall mount, swing downS0740-PDV – deck mount, push down valveS0860 – Swing downS0960 – SwivelS0A60 – Swivel with 1/2” valve & push handle

• S – Acorn Safety prefix• 1st position 0, Showerhead – none• 2nd position 7,8,9,A, Mounting – deck• 3rd position 4, 6, Bowl/Receptor –

stainless steel or no bowl, eye/face wash• 4th position 0, Drench hose – none• Typical options – AS, BF, LH, PCP, PDV, RH, TMV1

S0860-RH

S0960-LH

S660-LH

Eye/Face Wash – Wall Mounted, Recessed

S0560• S – Acorn Safety prefix• 1st position 0, Showerhead – none• 2nd position 5, Mounting – wall, recessed• 3rd position 6, Bowl/Receptor – no bowl, eye/face wash• 4th position 0, Drench hose – none• Typical options - AS, PAN, PCP, SDC, TMV1• Fits in four (4) inch wall

Single motion, pull down activation. Many lab specs.

S0560

Acorn Advantage - Showers

• Full sheeting "wall of water" shower head spray pattern, common on all Acorn showers

• Yellow protective powder coating

• Standard 20 gpm flow control

• Stainless steel actuator arm and pull rod

Drench Showers - VerticalS1100 – Plastic Head

S2100 – Stainless Steel Head• S – Acorn Safety prefix• 1st position 1, 2, Showerhead – plastic or stainless steel• 2nd position 1, Mounting – vertical• 3rd position 0, Bowl/Receptor – none• 4th position 0, Drench hose – none• Typical options - MC2, PR_ _, RA, TMV2

RA option is a space saver. Labs, industrial, institutional. Flush or ceiling.

S1100 S2100

Drench Showers – HorizontalS1200 – Plastic Head

S2200 – Stainless Steel Head• S – Acorn Safety prefix• 1st position 1, 2, Showerhead – plastic or stainless steel • 2nd position 2, Mounting – horizontal• 3rd position 0, Bowl/Receptor – none• 4th position 0, Drench hose – none• Typical options – MC1, RA, TMV2

RA for space saver. Labs, industrial, institutional. Flush or ceiling.

S1200 S2200

Combination Shower & EyewashS1310 & S1330

• S – Acorn Safety prefix• 1st position 1, Showerhead – plastic • 2nd position 3, Mounting – pedestal• 3rd position 1 or 3, Bowl/Receptor –

plastic or stainless steel eyewash• 4th position 0, Drench hose – none• Typical options – BF, FPB, HFC, MC1, TMV2, • Eyewash section fully assembled

Frequently specified. Used everywhere. Best bang for the buck.

S1310 S1330

Combination Shower & Eye/Face Wash

S1320 & 1340

• S – Acorn Safety prefix• 1st position 1, Showerhead – plastic • 2nd position 3, Mounting – pedestal• 3rd position 2 or 4, Bowl/Receptor –

plastic or stainless steel eye/face wash• 4th position 0, Drench hose – none• Typical options - BF, CS1, FPB, HFC, MC1, PR_ _,

TMV2, drench hose• Eye/face wash section full assembled

S1320 S1340

Stainless Steel Combination Shower & Eye/Face Wash

S2340-AS• S – Acorn Safety prefix• 1st position 2, Showerhead – stainless steel • 2nd position 3, Mounting – pedestal• 3rd position 4, Bowl/Receptor – stainless steel, eye/face wash• 4th position 0, Drench hose – none• Suffix -AS, All Stainless Steel• Typical options – BF, CS1, FPB, HFC, MC1, TMV2 • Eye/face wash section fully assembled

Specified for labs, clean room, medical.

S2340-AS-BFS2340-AS

Combination Shower & Eye/Face WashS1360 (no bowl)

• S – Acorn Safety prefix• 1st position 1, Showerhead – plastic • 2nd position 3, Mounting – pedestal• 3rd position 6, Bowl/Receptor – no bowl, eye/face

wash• 4th position 0, Drench hose – none• Typical options – BF, FPB, HFC, MC1, TMV2,

Mainly used in industrial settings, no drain.

S1360

S1360-HT

Acorn Advantage-Heat Traced Combination Shower & Eye/Face Wash

S1360-HT

• Extensive insulation provides increased freeze protection

• Over 200 inches of heat tape used• Tested to -50° F, lowest in industry• Impact and corrosion resistant• High-vis yellow covers• Class 1, Division 2 is standard

Combination Shower & Eye/Face Wash Recessed Activation

S2260-RA• S – Acorn Safety prefix• 1st position 2, Showerhead – stainless steel• 2nd position 2, Mounting – vertical• 3rd position 6, Bowl/Receptor – no bowl, eye/face wash• 4th position 0, Drench hose – none• Suffix -RA, recessed shower activation• Fully recessed in on & off positions• Fits in a four (4) inch wall• Typical options – PAN, TMV2

Very popular in lab specs.

S2260-PAN-RA

Drench Hoses

• S0402 – single head, wall, stay-open• S0402-CH12 – single head, wall,

stay-open, 12 foot coiled hose• S0702 – single head, deck mounted,

stay-open• S0406 – two heads, wall, stay-open• S0406-CH12 – two heads, wall, stay-open,

12 foot coiled hose• S0706 – two heads, deck mounted, stay-open

S0402 S0406

S0406-CH12

S0P50

Acorn Advantage –Portable Gravity Fed Eyewash

S0P50

• 15 minutes of use when tank is full

• Low cost

• Wall and counter mount

• Hi-vis yellow polyproylene tank

Tempered Water Mixing Valves

• All Acorn Safety valves are ASSE Listed per the ASSE 1071 standard.

• TMV8 (14 gpm) – eye wash, eye/face wash and drench hoses

• TMV33 (33 gpm) – drench showers and combination units

• TMV83 (83 gpm) and TMV119 (119 gpm) – multiple units needing higher flow rates

• Exclusive "dual internal by-pass" insures cold water flow in the event of a valve failure or loss of hot water

S0000-TMV8

S0000-TMV33

Codes & Compliance

• ANSI Z358.1- 2009, Emergency Eyewash and Shower Equipment– Voluntary Standard, not enforceable– OSHA uses as a guideline, cites through the general

duty clause 29 CFR 1910.151, which requires that...“...where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.”

ANSI Z358.1 - 2009• The standard which governs the configuration,

performance, installation, testing and maintenance of all emergency drench equipment.

• Owner, Engineer and Manufacturer must work together to determine proper equipment selection.

• Acorn Safety products are compliant and will be third party certified (IAPMO)

• “The Owner has to know his work place environment”

• “Can’t be a little bit pregnant, can’t be a little bit compliant”