acoustical analysis report - lomita · 2016-05-16 · acoustical analysis report starbucks –...

57
ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California 90717 Prepared For GreenbergFarrow Attention: Catherine Otis 19000 MacArthur Boulevard, Suite 250 Irvine, California 92612 Phone: 949-296-0450 Prepared By Eilar Associates, Inc. Acoustical & Environmental Consulting 210 South Juniper Street, Suite 100 Escondido, California 92025 www.eilarassociates.com Phone: 760-738-5570 Fax: 760-738-5227 Job #B51104N2 December 9, 2015 Attachment B

Upload: others

Post on 16-Mar-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

ACOUSTICAL ANALYSIS REPORT

Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway

Lomita, California 90717

Prepared For

GreenbergFarrow Attention: Catherine Otis

19000 MacArthur Boulevard, Suite 250 Irvine, California 92612 Phone: 949-296-0450

Prepared By

Eilar Associates, Inc. Acoustical & Environmental Consulting

210 South Juniper Street, Suite 100 Escondido, California 92025

www.eilarassociates.com Phone: 760-738-5570

Fax: 760-738-5227

Job #B51104N2

December 9, 2015

Attachment B

Page 2: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

TABLE OF CONTENTS

Page 1.0 EXECUTIVE SUMMARY 1 2.0 INTRODUCTION 1 2.1 Project Description

2.2 Project Location 2.3 Applicable Noise Regulations

3.0 ENVIRONMENTAL SETTING 3 3.1 Noise Environment 3.2 Measured Noise Levels 3.3 Future Noise Environment 4.0 METHODOLOGY AND EQUIPMENT 5 4.1 Methodology 4.2 Measurement Equipment 5.0 IMPACTS AND MITIGATION 6 5.1 Exterior (Building Facades) 5.2 Interior 5.3 Noise Impacts on Surrounding Properties 6.0 CONCLUSION 9 7.0 CERTIFICATION 9 8.0 REFERENCES 10

Page 3: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

FIGURES 1. Vicinity Map 2. Assessor’s Parcel Map 3. Satellite Aerial Photograph 4. Topographic Map 5. Satellite Aerial Photograph Showing Noise Measurement Location 6. Satellite Aerial Photograph Showing Equipment Noise Contours and Receiver Locations APPENDICES A. Project Plans B. Pertinent Sections of CALGreen Code and the Cities of Lomita and Los Angeles Municipal

Codes C. Manufacturer Data Sheets D. Sound Insulation Prediction Results E. Exterior-to-Interior Noise Analysis F. Recommended Products G. Cadna Analysis Data and Results

Page 4: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________ Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 1

1.0 EXECUTIVE SUMMARY The proposed project, Starbucks – Pacific Coast Highway and Western Avenue, consists of the demolition of existing structures and the construction of a new walk-up and drive-through coffee shop. The project site is located at 1730-1734 Pacific Coast Highway in the Cities of Los Angeles and Lomita, California. The City of Los Angeles Department of Building and Safety, City of Lomita, and State of California require that commercial developments demonstrate compliance with the requirements of the California Green Building Standards Code (known as CALGreen). CALGreen states that, if noise level readings of 65 dBA LEQ or greater are documented at the proposed project site, the project must either (a) incorporate wall and roof/ceiling assemblies with a composite STC rating of at least 50 and exterior windows with an STC rating of at least 40, or (b) provide an acoustical analysis documenting interior noise levels do not exceed 50 dBA in occupied areas during any hour of operation. This report provides the performance method analysis described in Item (b). Calculations show that with the proposed exterior wall assembly and windows with a minimum rating of STC 25 in place, interior noise levels of 50 dBA or less can be achieved during the worst-case hour of operation (loudest ambient noise). With these project design features in place, all occupied rooms are expected to comply with CALGreen noise requirements. In addition, the Municipal Codes of the Cities of Los Angeles and Lomita require the assessment of noise impacts from the drive-through intercom system to determine if additional project design features are necessary and feasible to reduce project-related noise impacts to comply with applicable noise limits. Calculations show that, as currently designed, exterior noise levels from the proposed intercom are expected to meet the applicable nighttime noise limits defined by the Cities of Los Angeles and Lomita at all surrounding property lines. No mitigation is deemed necessary to attenuate project-generated noise impacts at neighboring receivers.

2.0 INTRODUCTION This acoustical analysis report is submitted to satisfy the noise requirements of the City of Los Angeles, the City of Lomita, and State of California. Its purpose is to assess interior noise impacts to the project site from transportation noise sources to determine if mitigation is necessary to reduce these noise impacts to comply with the applicable noise regulations of the City of Los Angeles and the California Green Building Standards Code (CALGreen). Additionally, this report assesses noise impacts from on-site project-related noise sources to determine if mitigation is necessary to reduce the noise impacts to be compliant with applicable limits. All noise level or sound level values presented herein are expressed in terms of decibels (dB), with A-weighting, abbreviated "dBA," to approximate the hearing sensitivity of humans. Time-averaged noise levels are expressed by the symbol “LEQ.” Unless a different time period is specified, “LEQ” is implied to mean a period of one hour. Some of the data may also be presented as octave-band-filtered and/or A-octave-band-filtered data, which are a series of sound spectra centered about each stated frequency, with half of the bandwidth above and half of the bandwidth below each stated frequency. This data is typically used for machinery noise analysis and barrier calculations.

Page 5: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 2

2.1 Project Description

The proposed project, Starbucks – Pacific Coast Highway and Western Avenue, consists of the demolition of existing structures and the construction of a new walk-up and drive-through coffee shop. The project will include interior workspaces, storage, and restrooms, but will not contain any indoor cafe space. The drive-through intercom system is located to the south of the proposed building. The proposed hours of operation for the store are 24 hours a day. For additional project details, please refer to the project plans provided in Appendix A.

2.2 Project Location

The subject property is located at 1730-1734 Pacific Coast Highway in the Cities of Los Angeles and Lomita, California. The Assessor’s Parcel Numbers is 7553-018-084 and 7553-018-032. The site is currently occupied by two existing buildings, both of which will be demolished. For a graphical representation of the site, please refer to the Vicinity Map, Assessor’s Parcel Map, Satellite Aerial Photograph, and Topographic Map, provided as Figures 1 through 4, respectively.

2.3 Applicable Noise Regulations

The City of Los Angeles Department of Building and Safety, City of Lomita, and State of California require that commercial developments demonstrate compliance with the requirements of the California Green Building Standards Code (known as CALGreen). CALGreen states that, if noise level readings of 65 dBA LEQ or greater are documented at the proposed project site, the project must either (a) incorporate wall and roof/ceiling assemblies with a composite STC rating of at least 50 and exterior windows with an STC rating of at least 40, or (b) provide an acoustical analysis documenting interior noise levels do not exceed 50 dBA in occupied areas during any hour of operation. This report provides the performance method analysis described in Item (b).

In addition to the acoustical requirements of CALGreen, noise levels from drive-through intercom equipment must be adequately controlled at surrounding noise-sensitive receivers. Residential receivers are located to the south of the project site, across 258th Place. As the adjacent receivers are located in either the City of Los Angeles or the City of Lomita, the municipal codes of both cities should be considered to ensure noise impacts will remain in compliance with applicable noise limits.

The City of Lomita requires that noise impacts are controlled to be 65 dBA or less during the daytime hours of 7 a.m. to 9 p.m. and 55 dBA or less during the nighttime hours of 9 p.m. to 7 a.m. at residential properties. Noise impacts at commercial properties must likewise be controlled to be 75 dBA during the daytime hours and 70 dBA during the nighttime hours. As the drive-through will be operational during nighttime hours, the most restrictive noise limits of 55 dBA would apply at residential receivers and 70 dBA at commercial receivers within the City of Lomita.

The City of Los Angeles Municipal Code contains “presumed ambient noise levels” for various zones and states that where the ambient noise level is less than the presumed ambient noise level, the presumed ambient shall be considered the minimum ambient noise level. Although ambient noise monitoring was conducted on the subject property, noise levels at adjacent residential properties will be less than those measured on site, due to additional distance from the roadways and shielding provided by intervening structures. For this reason, although ambient noise levels still likely exceed the presumed ambient noise levels shown herein, the presumed ambient noise levels have been considered in this analysis. The presumed ambient noise levels for residential properties are 50 dBA between the hours of 7 a.m. and 10 p.m. and 40 dBA between the hours of 10 p.m. and 7 a.m. Commercial presumed ambient noise levels are 60 dBA and 55 dBA for

Page 6: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 3

daytime and nighttime hours, respectively. The Municipal Code states that sound amplifying devices shall not cause the ambient noise level to be exceeded by more than five decibels. As the drive-through will be operational during nighttime hours, the most restrictive noise limits of 45 dBA at residential receivers and 60 dBA at commercial receivers would be applied to properties within the City of Los Angeles.

Pertinent sections of the CALGreen Code and the Municipal Codes of the Cities of Lomita and Los Angeles are provided as Appendix B.

3.0 ENVIRONMENTAL SETTING

3.1 Noise Environment

The primary noise source in the vicinity of the project site is automobile and truck traffic noise from Pacific Coast Highway and Western Avenue. No other noise sources are considered to be significant.

3.2 Measured Noise Levels

A long-term noise measurement was made beginning the morning of Thursday, November 5, 2015, and running through the morning of Friday, November 6, 2015. The purpose of this measurement was to obtain noise information for the site during the proposed hours of operation, currently expected to be 24 hours a day. The noise measurement was performed at four feet above the ground in a bush along the western property line with a direct line of sight to Pacific Coast Highway. Noise data obtained on site is shown in Table 1, and the measurement location is shown graphically in Figure 5.

Table 1. Long-Term Measured Noise Levels on Site

Date Time Hourly Average Noise Level (dBA LEQ)

November 5, 2015

6 a.m. – 7 a.m. 68.6 7 a.m. – 8 a.m. 66.9 8 a.m. – 9 a.m. 66.0

9 a.m. – 10 a.m. 66.8 10 a.m. – 11 a.m. 66.4 11 a.m. – 12 p.m. 65.5 12 p.m. – 1 p.m. 65.4 1 p.m. – 2 p.m. 66.0 2 p.m. – 3 p.m. 65.9 3 p.m. – 4 p.m. 65.1 4 p.m. – 5 p.m. 65.1 5 p.m. – 6 p.m. 65.1 6 p.m. – 7 p.m. 65.1 7 p.m. – 8 p.m. 64.8 8 p.m. – 9 p.m. 67.0

9 p.m. – 10 p.m. 66.2 10 p.m. – 11 p.m. 65.6 11 p.m. – 12 a.m. 63.9

Page 7: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 4

Table 1. Long-Term Measured Noise Levels on Site

Date Time Hourly Average Noise Level (dBA LEQ)

November 6, 2015

12 a.m. – 1 a.m. 62.8 1 a.m. – 2 a.m. 62.0 2 a.m. – 3 a.m. 60.7 3 a.m. – 4 a.m. 61.8 4 a.m. – 5 a.m. 64.0 5 a.m. – 6 a.m. 67.7 6 a.m. – 7 a.m. 69.2 7 a.m. – 8 a.m. 67.6

Measured noise levels were observed to range from 60.7 dBA between the hours of 2 a.m. and 3 a.m. on November 6 to 69.2 dBA between 6 a.m. and 7 a.m. on November 6. These noise levels are considered to be representative of noise impacts at the proposed building, as the measurement location was in-line with the northernmost wall of the proposed building, the closest wall to Pacific Coast Highway. For this reason, the highest measured hourly noise level of 69.2 dBA will be used to evaluate peak hour noise impacts at the building, as the business will be in operation during all hours of the day. Additional information is provided in Section 5.0.

3.2 Future Noise Environment

The future noise environment in the vicinity of the project site will be primarily a result of the same ambient noise sources, as well as the noise generated by activity on the project site. The primary source of noise associated with the coffee shop will be the proposed drive-through intercom equipment.

The proposed drive-through intercom is expected to be manufactured by HME. The proposed HME Intercom System is measured to have a maximum noise level of 84 dBA at one foot from the speaker post. The system will also be equipped with an automatic volume control (AVC) system that will automatically reduce the sound level produced by the intercom as the ambient noise level decreases. It is likely that the actual noise level produced by the intercom system during hours with lower levels of business would be less than the projected 84 dBA, as the ambient noise level may be lower during these hours due to lower traffic volumes; however, the higher noise level will be modeled for a worst-case analysis. For further details on the HME intercom system, please refer to Appendix C: Manufacturer Data Sheets.

Page 8: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 5

4.0 METHODOLOGY AND EQUIPMENT

4.1 Methodology

4.1.1 Exterior-to-Interior Noise Analysis

CALGreen requires nonresidential buildings to be designed in order to attenuate, control, and maintain average interior noise levels not greater than 50 dBA. Contemporary exterior building construction is expected to achieve at least 15 decibels of exterior-to-interior noise attenuation with windows opened. As a result, exterior noise levels of more than 65 dBA often result in interior conditions that fail to meet the 50 dBA requirements for occupied space.

Analysis for the interior noise levels requires consideration of:

• Number of unique assemblies in the wall (doors, window/wall mount air conditioners, slidingglass doors, and windows)

• Size, number of units, and sound transmission data for each assembly type• Length of sound impacted wall(s)• Depth of sound impacted room• Height of exterior wall of sound impacted room• Exterior noise level at wall assembly or assemblies of sound impacted room

The Composite Sound Transmission data is developed for the exterior wall(s) and the calculated noise exposure is converted to octave band sound pressure levels (SPL) for a typical traffic type noise. The reduction in room noise due to absorption is calculated and subtracted from the interior octave noise levels, and the octave band noise levels are logarithmically summed to yield the overall interior room noise level. When interior noise levels exceed 50 dBA, the noise reduction achieved by each element is reviewed to determine which changes will achieve the most cost-effective compliance. Windows are usually the first to be reviewed, followed by exterior doors, and then exterior walls.

Modeling of wall assemblies is accomplished using INSUL Version 6.4, which is a model-based computer program, developed by Marshall Day Acoustics for predicting the sound insulation of walls, floors, ceilings and windows. It is acoustically based on theoretical models that require only minimal material information that can make reasonable estimates of the sound transmission loss (TL) and STC for use in sound insulation calculations; such as the design of common party walls and multiple family floor-ceiling assemblies, etc. INSUL can be used to quickly evaluate new materials or systems or investigate the effects of changes to existing designs. It models individual materials using the simple mass law and coincidence frequency approach and can model more complex assembly partitions. It has evolved over several versions into an easy to use tool and has refined the theoretical models by continued comparison with laboratory tests to provide acceptable accuracy for a wide range of constructions. INSUL model performance comparisons with laboratory test data show that the model generally predicts the performance of a given assembly within 3 STC points.

4.1.2 Cadna Noise Modeling Software

Modeling of the outdoor noise environment is accomplished using Cadna Version 4.5, which is a model-based computer program developed by DataKustik for predicting noise impacts in a wide variety of conditions. Cadna (Computer Aided Noise Abatement) assists in the calculation,

Page 9: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 6

presentation, assessment, and mitigation of noise exposure. It allows for the input of project information such as noise source data, barriers, structures, and topography to create a detailed model and uses the most up-to-date calculation standards to predict outdoor noise impacts.

4.2 Measurement Equipment

Some or all of the following equipment was used at the site to measure existing noise levels:

• Larson Davis Model 720, Type 2 Sound Level Meter, Serial # 0462, with microphone &windscreen

• Larson Davis Model CA150, Type 2 Calibrator, Serial # 0203

The sound level meter was field-calibrated immediately prior to the noise measurement and checked afterward, to ensure accuracy. All sound level measurements conducted and presented in this report, in accordance with the regulations, were made with a sound level meter that conforms to the American National Standards Institute specifications for sound level meters (ANSI S1.4). All instruments are maintained with National Bureau of Standards traceable calibration, per the manufacturers’ standards.

5.0 IMPACTS AND MITIGATION

5.1 Exterior (Building Facades)

Per the Los Angeles Department of Building and Safety, noise monitoring should be performed for commercial sites in order to determine noise levels at all potential hours of operation for use in performance method interior noise calculations. Noise monitoring was performed at the project site and is detailed in Section 3.2. As shown above, peak traffic noise impacts along the western property line, in line with the northernmost wall of the proposed building, were measured to be approximately 69.2 dBA between 6 a.m. and 7 a.m. on November 6. All other hours were observed to have lesser noise impacts. For this reason, for a worst-case analysis, the maximum measured noise level of 69.2 dBA will be used to conduct peak hour interior noise calculations to determine what project design features are necessary to maintain interior noise levels of 50 dBA or less during all hours of operation, per CALGreen requirements. For a graphical representation of the noise measurement location, please refer to Figure 5.

5.2 Interior

CALGreen requires that nonresidential structures that are exposed to greater than 65 dBA during any hour of operation must control interior noise levels to be 50 dBA or less. Contemporary exterior building construction is expected to achieve at least 15 decibels of exterior-to-interior noise attenuation with windows opened. As a result, exterior noise levels of more than 65 dBA may potentially result in interior conditions that fail to meet the 50 dBA requirements for commercial space.

An exterior-to-interior noise analysis was conducted for the building to evaluate the sound reduction properties of proposed exterior wall assembly, window, and door construction designs in the building. The roof assembly was not included in this evaluation as none of the surrounding roadway noise sources are elevated above the project site grade, and therefore, the roof will be shielded from high traffic noise levels. All occupied spaces were considered in this analysis.

Page 10: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 7

The proposed exterior wall will consist of stucco on the exterior over plywood sheathing with two-inch by six-inch wood framing, R19 insulation in the cavity, and 5/8-inch thick Type X gypsum board on the interior. The assembly was calculated to have a rating of STC 48. This wall assembly will be used in interior noise calculations in the building. Additionally, windows were evaluated as STC 25 insulated glazing units. Please refer to Appendix C for more details.

Calculations have been performed using the assemblies detailed above to determine whether interior noise levels of 50 dBA or less can be achieved during the worst-case hour of operation. Please refer to Table 2, showing interior noise levels with the acoustical mitigation recommendations made herein, and refer to Appendix D for additional information.

Table 2. Worst-Case Interior Traffic Noise Levels with Acoustical Recommendations

Room Maximum Assumed

Exterior Facade Impact (dBA)

Minimum STC Rating for Exterior Windows

Interior Noise Level (dBA)

Back Bar 69.2 25 48.7

Work Room 69.2 N/A 36.9

As shown above, with the proposed exterior wall assembly and windows with a minimum rating of STC 25, interior noise levels are expected to remain below 50 dBA during the worst-case hour of operation (highest ambient noise level). As this represents the maximum noise impact in any one hour period during the day, all other hours are expected to have interior noise impacts that are less than those shown above. The rating of STC 25 for windows is easily achievable with single or dual pane glass, and safety and thermal requirements will almost certainly require windows and doors that exceed this requirement; however, the STC rating of windows should be confirmed with the manufacturer to ensure this rating will be met.

Exterior door installation should include all-around weather-tight door stop seals and an improved threshold closure system. The additional hardware will improve the doors’ overall sound reduction properties. The transmission loss (TL) of an exterior door without weather-tight seals is largely a factor of sound leakage, particularly at the bottom of the door if excessive clearance is allowed for air transfer. By equipping exterior doors with all-around weather-tight seals and an airtight threshold closure at the bottom, a loss of up to 10 STC points can be prevented.

Additionally, it is imperative to seal and caulk between the rough opening and the finished door frame for all doors by applying an acoustically resilient, non-skinning butyl caulking compound. Sealant application should be as generous as needed to ensure effective sound barrier isolation. The same recommendation applies to any other penetrations, cracks, or gaps through the assembly. The OSI Green Series and the Pecora AC-20 FTR acoustic sound sealants are products specifically designed for this purpose. For additional information on these products, please refer to Appendix E: Recommended Products.

The proposed project was analyzed for worst-case exterior traffic noise impacts. With the proposed exterior wall assembly and windows meeting a minimum rating of STC 25, all occupied rooms are expected to comply with CALGreen noise requirements.

Page 11: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 8

5.3 Noise Impacts on Surrounding Properties

Noise levels of the proposed drive-through intercom were calculated using Cadna at surrounding property lines to the south (across 258th Place), east, and west. Commercial properties to the north are located at a considerable distance from drive-through equipment, and will also receive shielding from the on-site building. As the evaluated receivers represent the worst-case noise exposure, no noise receiver has been placed at commercial properties to the north. As per industry standard, the receivers were calculated at a height of five feet above grade to represent the height of an average individual’s ears above ground level. This calculation also makes conservative assumptions in that it was assumed that the intercom would be in constant operation, with no breaks between orders, while in actuality it will only operate for a fraction of an hour, thereby resulting in lower average hourly noise impacts than what have been calculated.

Results of the analysis are shown in Table 3. Noise contours showing intercom equipment noise levels and receiver locations are shown in Figure 6. Additional information can be found in Appendix G: Cadna Analysis Data and Results.

Table 3. Calculated Noise Impact Levels of Drive-Through Intercom Operation

Receiver Receiver Location Noise Limit (dBA) Drive-Through Intercom Noise Impact (dBA)

R-1 South Property Line (City of Los Angeles, Residential) 45 45.0

R-2 South Property Line (City of Lomita, Residential) 55 44.9

R-3 East Property Line (City of Los Angeles, Commercial) 60 58.9

R-4 West Property Line (City of Lomita, Commercial) 70 44.0

As shown above, as currently designed, noise levels from the proposed intercom are not expected to exceed the applicable nighttime noise limits of either the City of Lomita or the City of Los Angeles at surrounding property lines. Additionally, it should be noted that, as City of Los Angeles noise limits are dependent on the ambient noise environment, this assessment shows that even with the minimum possible noise limits in place for surrounding properties, noise levels are expected to remain in compliance with applicable regulations. For these reasons, no mitigation is deemed necessary to attenuate project-generated noise impacts at neighboring receivers.

Page 12: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________

Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 9

6.0 CONCLUSION

CALGreen Code requires interior noise levels of 50 dBA or less within occupied commercial space. Calculations show that with the proposed exterior wall assembly and windows with a minimum rating of STC 25 in place, interior noise levels of 50 dBA or less can be achieved during the worst-case hour of operation (loudest ambient noise). With these project design features in place, all occupied rooms are expected to comply with CALGreen noise requirements.

In addition, the Municipal Codes of the Cities of Los Angeles and Lomita require the assessment of noise impacts from the drive-through intercom system to determine if additional project design features are necessary and feasible to reduce project-related noise impacts to comply with applicable noise limits. Calculations show that, as currently designed, exterior noise levels from the proposed intercom are expected to meet the applicable nighttime noise limits defined by the Cities of Los Angeles and Lomita at all surrounding property lines. No mitigation is deemed necessary to attenuate project-generated noise impacts at neighboring receivers.

7.0 CERTIFICATION

All recommendations for noise control are based on the best information available at the time our consulting services are provided. However, as there are many factors involved in sound transmission, and Eilar Associates has no control over the construction, workmanship or materials, Eilar Associates is specifically not liable for final results of any recommendations or implementation of the recommendations.

This report is based on the related project information received and measured noise levels, and represents a true and factual analysis of the acoustical impact issues associated with Starbucks – Pacific Coast Highway and Western, to be located at 1730-1734 Pacific Coast Highway in the Cities of Los Angeles and Lomita, California. This report was prepared by Jonathan Brothers and Amy Hool.

___________________________________ ______________________________________ Amy Hool, Principal Acoustical Consultant Jonathan Brothers, Senior Acoustical Consultant

Page 13: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

_______________________________________________________________________________ Eilar Associates, Inc. Job #B51104N2 December 9, 2015 Page 10

8.0 REFERENCES 1. Beranek, Leo L., Acoustical Measurements, Published for the Acoustical Society of America

by the American Institute of Physics, Revised Edition, 1988. 2. California Green Building Code, Nonresidential Mandatory Measures. 3. City of Los Angeles Municipal Code 4. City of Lomita Municipal Code. 5. Harris, Cyril M., Handbook of Acoustical Measurements and Noise Control, Acoustical

Society of America, 3rd Edition, 1998. 6. Harris, Cyril M., Ph.D., Noise Control in Buildings, Original Edition, 1994. 7. Hirschorn, Martin, Noise Control Reference Handbook, Revised Edition, 1989. 8. Irvine, Leland K. and Richards, Roy L., Acoustics and Noise Control Handbook for

Architects and Builders, Original Edition, 1998. 9. Knudsen, Vern O. and Harris, Cyril M., Acoustical Designing In Architecture, American

Institute of Physics for the Acoustical Society of America, 2nd Edition, 1978. 10. Raichel, Daniel R., The Science and Applications of Acoustics, American Institute of Physics

Press for the Acoustical Society of America, 1st Edition, 2000.

Page 14: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

FIGURES

Page 15: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Vicinity MapJob # B51104N2

Eilar Associates, Inc.210 South Juniper Street, Suite 100

Escondido, California 92025760-738-5570

Figure 1

ProjectLocation

N

Page 16: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Los Angeles CountyAssessor’s

Parcel Number:#1 7553-018-032#2 7553-018-084

Assessor’s Parcel MapJob # B51104N2

Eilar Associates, Inc.210 South Juniper Street, Suite 100

Escondido, California 92025760-738-5570

Figure 2

N

ProjectLocation

# 1 # 2

Page 17: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Eilar Associates, Inc.210 South Juniper Street, Suite 100

Escondido, California 92025760-738-5570

Figure 3

ProjectLocation

Satellite Aerial PhotographJob # B51104N2

N

Page 18: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Topographic MapJob # B51104N2

Eilar Associates, Inc.210 South Juniper Street, Suite 100

Escondido, California 92025760-738-5570

Figure 4

N

ProjectLocation

Page 19: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Eilar Associates, Inc.210 South Juniper Street, Suite 100

Escondido, California 92025760-738-5570

Figure 5Satellite Aerial Photograph Showing

Noise Measurement LocationJob # B51104N2

N

Noise MeasurementLocation

Proposed BuildingFootprint

Page 20: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Figure 6Satellite Aerial Photograph Showing Equipment Noise Contours and Receiver Locations

Job # B51104N2

Eilar Associates, Inc.210 South Juniper Street, Suite 100

Escondido, California 92025760-738-5570

NIntercom Location

R1R2

R3R4

Page 21: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

APPENDIX A

Project Plans

Page 22: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

STARBUCKS±850 SF

CA

RL'

S J

R

JAC

K IN

TH

E B

OX

19000 MacArthur Blvd, Suite 250Irvine, CA 92612t: 949 296 0450 f: 949 296 0479

SITE PLANSTARBUCKSSWQ PACIFIC COAST HWY & WESTERN AVE

20150031.0

LOMITA, CA10.14.2015

40

SCALE: 1"=10'-0"

Page 23: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

19000 MacArthur Blvd, Suite 250Irvine, CA 92612t: 949 296 0450 f: 949 296 0479

STARBUCKSSWQ PACIFIC COAST HWY & WESTERN AVE

20150031.0

LOMITA, CA10.14.2015

40

SCALE: 1"=10'-0"

EXISTING CONDITIONS

Page 24: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

19000 MacArthur Blvd, Suite 250Irvine, CA 92612t: 949 296 0450 f: 949 296 0479

FLOOR PLANSTARBUCKSSWQ PACIFIC COAST HWY & WESTERN AVE

20150031.0

LOMITA, CA10.14.2015

SCALE: 3/8" = 1'-0"TRUE NORTH

Page 25: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

PARAPET18' - 6"

T.O.PARAPET

14' - 6 "

0'-0"0"

3'-6

"

2'-1

0"

5"

4'-0

"

11'-6"5"

11'-0

"

BEYOND

T.O.PARAPET14' - 6 "

T.O.PARAPETBEYOND18' - 6"

0'-0"0"

11'-0

"

3'-6

"

5"

18' - 6"

T.O.PARAPETBEYOND

0'-0"0"

3'-6

"

11'-0

"

T. O. PARAPET

14' - 6"BEYOND

T. O. PARAPET14' - 6"

T.O.PARAPETBEYOND

18' - 6"

0"0'-0"

11'-0

"

3'-6

"

6'-0

"

20150031.0

19000 MacArthur Blvd., Suite 250Irvine, CA 92612t: 949 296 0450 f: 949 296 0479

SCALE: 1/4" = 1'-0"1 NORTH ELEVATION

SCALE: 1/4" = 1'-0"2 SOUTH ELEVATION

SCALE: 1/4" = 1'-0"3 WEST ELEVATION

SCALE: 1/4" = 1'-0"4 EAST ELEVATION

10.15.2015

FINISH SCHEDULE1

3

2

FINISH MATERIAL

ALUMINUM STOREFRONT SYSTEM

SIGNAGE UNDER SEPARATE PERMIT

7

4

5

6

9

10

11

DRIVE-THRU WINDOW

8

EXTERIOR WALL SCONCE

CEMENT PLASTER W/ INTEGRAL COLOR FINISH COAT - MEDIUM SAND FLOAT

WALK-UP WINDOW

CEMENT PLASTER CONTROL JOINT

RECLAIMED WOOD CLADDING

PREFINISHED METAL COPING

Note:Colors shown on these elevations are for illustrationpurposes only. For actual colors, refer to manufacturer'ssamples.

A

FINISH COLOR

B WOOD STAIN TO MATCH COLOR A

SHERWIN WILLIAMS - SW7038 - TONY TAUPE

PAINT TO MATCH DARK BRONZEC

D POWDER COAT DARK BRONZE

METAL SCREEN PANEL WITH IMAGE

EXTERIOR METAL CLADDING

E PAINT STOREFRONT MULLION/FRAME TO MATCH DARK BRONZE

12 SOLID METAL DOOR

Page 26: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

APPENDIX B

Pertinent Sections of CALGreen Code and the Cities of Lomita and Los Angeles Municipal Codes

Page 27: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

3. Product labeled and invoiced as meeting the Com-posite Wood Products regulation (see CCR, Title17, Section 93120, et seq)

4. Exterior grade products marked as meeting thePS-1 or PS-2 standards of the Engineered WoodAssociation, the Australian AS/NZS 2269 orEuropean 636 3S standards

5. Other methods acceptable to the enforcing agency

5.504.4.6 Resilient flooring systems. For 50 percent offloor area receiving resilient flooring, install resilient floor-ing complying with the VOC-emission limits defined in the2009 Collaborative for High Performance Schools (CHPS)criteria and listed on its High Performance Products Data-base; products compliant with CHPS criteria certified underthe Greenguard Children & Schools program; certifiedunder the Resilient Floor Covering Institute (RFCI)FloorScore program; or meet California Department ofPublic Health 2010 Standard Method for the Testing andEvaluation of Volatile Organic Chemical Emissions fromIndoor Sources Using Environmental Chambers, Version1.1, February 2010 (also known as Specification 01350.)

5.504.4.6.1 Verification of compliance. Documenta-tion shall be provided verifying that resilient flooringmaterials meet the pollutant emission limits.

5.504.5.3 Filters. In mechanically ventilated buildings,provide regularly occupied areas of the building with air fil-tration media for outside and return air that provides at leasta Minimum Efficiency Reporting Value (MERV) of 8.MERV 8 filters shall be installed prior to occupancy, andrecommendations for maintenance with filters of the samevalue shall be included in the operation and maintenancemanual.

Exception: A MERV-1 filter shall be allowed for returnair only or return with prefiltered outside air, if the filteris of a reusable, nondisposable type, and the fan energyuse of that air delivery system is 0.4W/cfm or less atdesign airflow.

5.504.7 Environmental tobacco smoke (ETS) control.Where outdoor areas are provided for smoking, prohibit smok-ing within 25 feet of building entries, outdoor air intakes andoperable windows and within the building as already prohib-ited by other laws or regulations; or as enforced by ordinances,regulations or policies of any city, county, city and county, Cal-ifornia Community College, campus of the California State

University, or campus of the University of California,whichever are more stringent. When ordinances, regulations orpolicies are not in place, post signage to inform building occu-pants of the prohibitions.

SECTION 5.505INDOOR MOISTURE CONTROL

5.505.1 Indoor moisture control. Buildings shall meet orexceed the provisions of California Building Code, CCR, Title24, Part 2, Sections 1203 (Ventilation) and Chapter 14 (Exte-rior Walls). For additional measures not applicable to low-riseresidential occupancies, see Section 5.407.2 of this code.

SECTION 5.506INDOOR AIR QUALITY

5.506.1 Outside air delivery. For mechanically or naturallyventilated spaces in buildings, meet the minimum require-ments of Section 121 (Requirements For Ventilation) of the2010 California Energy Code, or the applicable local code,whichever is more stringent, and Division 1, Chapter 4 of CCR,Title 8.

5.506.2 Carbon dioxide (CO2) monitoring. For buildingsequipped with demand control ventilation, CO2 sensors andventilation controls shall be specified and installed in accor-dance with the requirements of the 2010 California EnergyCode, Section 121(c).

SECTION 5.507ENVIRONMENTAL COMFORT

5.507.4 Acoustical control. Employ building assemblies andcomponents with Sound Transmission Class (STC) valuesdetermined in accordance with ASTM E 90 and ASTM E 413or Outdoor-Indoor Sound Transmission Class (OITC) deter-mined in accordance with ASTM E 1332,using either the pre-scriptive or performance method in Section 5.507.4.1 or5.507.4.2.

Exception: Buildings with few or no occupants or whereoccupants are not likely to be affected by exterior noise, asdetermined by the enforcement authority, such as factories,stadiums, storage, enclosed parking structures and utilitybuildings.

2010 CALIFORNIA GREEN BUILDING STANDARDS CODE JULY 1, 2012 SUPPLEMENT 41

NONRESIDENTIAL MANDATORY MEASURES

>

>

>

>

Page 28: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

5.507.4.1 Exterior noise transmission, prescriptivemethod. Wall and roof-ceiling assemblies exposed to thenoise source making up the building envelope shall meet acomposite STC rating of at least 50 or a composite OITCrating of no less than 40, with exterior windows of a mini-mum STC of 40 or OITC of 30 in the following locations:

1. Within the 65 CNEL noise contour of an airport.

Exceptions:

1. Ldn or CNEL for military airports shall bedetermined by the facility Air InstallationCompatible Land Use Zone (AICUZ) plan.

2. Ldn or CNEL for other airports and heliportsfor which a land use plan has not been devel-oped shall be determined by the local gen-eral plan noise element.

2. Within the 65 CNEL or Ldn noise contour of a freewayor expressway, railroad, industrial source orfixed-guideway source as determined by the NoiseElement of the General Plan.

5.507.4.1.1 Noise exposure where noise contours arenot readily available. Buildings exposed to a noise levelof 65 dB Leq-1-hr during any hour of operation shall haveexterior wall and roof-ceiling assemblies exposed to thenoise source meeting a composite STC rating of at least45 (or OITC 35), with exterior windows of a minimumSTC of 40 (or OITC 30).

5.507.4.2 Performance method. For buildings located asdefined in Section A5.507.4.1 or A5.507.4.1.1, wall androof-ceiling assemblies exposed to the noise source makingup the building envelope shall be constructed to provide aninterior noise environment attributable to exterior sourcesthat does not exceed an hourly equivalent noise level(Leq-1Hr) of 50 dBA in occupied areas during any hour ofoperation.

5.507.4.2.1 Site features. Exterior features such as soundwalls or earth berms may be utilized as appropriate to theproject to mitigate sound migration to the interior.

5.507.4.2.2 Documentation of compliance. An acousti-cal analysis documenting complying interior sound lev-els shall be prepared by personnel approved by thearchitect or engineer of record.

5.507.4.3 Interior sound transmission. Wall and floor-ceiling assemblies separating tenant spaces and tenantspaces and public places shall have an STC of at least 40.

Note: Examples of assemblies and their various STCratings may be found at the California Office of NoiseControl: http://www.toolbase.org/PDF/CaseStudies/stc_icc_ratings.pdf.

SECTION 5.508OUTDOOR AIR QUALITY

5.508.1 Ozone depletion and greenhouse gas reductions.Installations of HVAC, refrigeration and fire suppressionequipment shall comply with Sections 5.508.1.1 and 5.508.1.2.

5.508.1.1 Chlorofluorocarbons (CFCs). Install HVAC,refrigeration and fire suppression equipment that do notcontain CFCs.

5.508.1.2 Halons. Install HVAC, refrigeration and fire sup-pression equipment that do not contain Halons.

42 JULY 1, 2012 SUPPLEMENT 2010 CALIFORNIA GREEN BUILDING STANDARDS CODE

NONRESIDENTIAL MANDATORY MEASURES

>

Page 29: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California
Page 30: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California
Page 31: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California
Page 32: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California
Page 33: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California
Page 34: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California
Page 35: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California
Page 36: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

APPENDIX C

Manufacturer Data Sheets

Page 37: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Memo Re: Drive-Thru Sound Pressure Levels From the Menu Board or Speaker Post The sound pressure levels from the menu board or speaker post are as follows:

1. Sound pressure level (SPL) contours (A weighted) were measured on a typical HME SPP2 speaker post. The test condition was for pink noise set to 84 dBA at 1 foot in front of the speaker. All measurements were conducted outside with the speaker post placed 8 feet from a non-absorbing building wall and at an oblique angle to the wall. These measurements should not be construed to guarantee performance with any particular speaker post in any particular environment. They are typical results obtained under the conditions described above.

2. The SPL levels are presented for different distances from the speaker post:

Distance from the Speaker (Feet) SPL (dBA)

1 foot 84 dBA 2 feet 78 dBA 4 feet 72 dBA 8 feet 66 dBA

16 feet 60 dBA 32 feet 54 dBA

3. The above levels are based on factory recommended operating levels, which are preset for

HME components and represent the optimum level for drive-thru operations in the majority of the installations.

Also, HME incorporates automatic volume control (AVC) into many of our Systems. AVC will adjust the outbound volume based on the outdoor, ambient noise level. When ambient noise levels naturally decrease at night, AVC will reduce the outbound volume on the system. See below for example:

Distance from Outside Speaker Decibel Level of standard

system with 45 dB of outside noise without AVC

Decibel level of standard system with 45 dB of outside noise with

AVC active 1 foot 84 dBA 60 dBA 2 feet 78 dBA 54 dBA 4 feet 72 dBA 48 dBA 8 feet 66 dBA 42 dBA

16 feet 60 dBA 36 dBA If there are any further questions regarding this issue please contact HME customer service at 1-800-848-4468. Thank you for your interest in HME’s products.

Page 38: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

APPENDIX D

Sound Insulation Prediction Results

Page 39: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

Sound Insulation Prediction (v6.4)Program copyright Marshall Day Acoustics 2010

- Key No. 1866Margin of error is generally within STC +/- 3 dBJob Name:SBUX WesternJob No.: B51002 Page No.:Date: 14 Oct 15 Initials:AH

Notes:

File Name: WC Exterior Wall.ins

Exterior Wall

System descriptionPanel 1 Outer layer: 1 x 0.88 in -Coat Plaster (sand:gypsum =3:1)- (m=10.01 lb/ft2, fc=716 Hz, damping=0.04) Panel 1 Inner layer: 1 x 0.50 in Plywood (m=1.46 lb/ft2, fc=1828 Hz,damping=0.01)

Panel 2 Inner layer: 1 x 0.63 in Type X Gypsum Board- (m=2.24 lb/ft2, fc=2511 Hz, damping=0.01) Cavity: Timber stud @ 16 in , Infill 4" fiberglass (1.4 lb/ft3) Thickness 6 in

Mass-air-mass resonant frequency =51 Hz Panel Size 8.9x13 ft

6.00 in

8.00 in

STC 48OITC 43

frequency (Hz) TL(dB) TL(dB)

50 2163 2880 33

100 35125 37160 39200 41250 42315 43400 44500 45630 46800 42

1000 441250 471600 502000 532500 553150 584000 615000 64

25

37

42

45

44

52

60

Page 40: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

APPENDIX E

Exterior-to-Interior Noise Analysis

Page 41: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EXTERIOR TO INTERIOR NOISE REDUCTION ANALYSIS

Project Name: SBUX PCH & Western Wall 1 of 4Project # : B51104N1Room Name: Back Bar Room Type :

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzReverberation Time (sec) : 1.2 1.2 1.2 1.2 1.0 1.0 : Moderately Reflective Room

Room Absorption (Sabins) : 141 141 141 141 176 176

Noise Level 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSource 1: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Traffic Spectrum

Source 2: 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 3: 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 4: 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Overall: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Effective Noise Spectrum

Assembly Type Open Width Height Qty Total Area 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSTC 48 Typical Exterior Wall N 32 11 1 194.5 37 42 45 44 52 60

Window, Insulated Dual-Glazed (STC 25) N 4.5 7 5 157.5 14 21 24 22 30 29<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0

Room Depth: 10 ft Overall Area: 352 ft²Volume: 3520 ft³

Number of Impacted Walls: 4

Windows Open 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz Interior Noise Level: 48.7 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure

17.5 24.5 27.5 25.5 33.5 32.5 : Transmission Loss Windows Closed 25.5 25.5 25.5 25.5 25.5 25.5 : Wall Surface Area Factor Interior Noise Level: 48.7 dBA 21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

39.0 37.5 37.0 43.0 34.1 29.0 : Noise Level

46.2 dBA WINDOWS OPEN

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure17.5 24.5 27.5 25.5 33.5 32.5 : Transmission Loss25.5 25.5 25.5 25.5 25.5 25.5 : Wall Surface Area Factor21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

39.0 37.5 37.0 43.0 34.1 29.0 : Noise Level

46.2 dBA WINDOWS CLOSED

<N/A>

Traffic

Medium Hard

<N/A><N/A>

Page 42: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EXTERIOR TO INTERIOR NOISE REDUCTION ANALYSIS

Project Name: SBUX PCH & Western Wall 2 of 4Project # : B51104N1Room Name: Back Bar

Noise Level 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSource 1: Traffic 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Traffic Spectrum

Source 2: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 3: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 4: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Overall: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Effective Noise Spectrum

Assembly Type Open Width Height Qty Total Area 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSTC 48 Typical Exterior Wall N 10 11 1 65.0 37 42 45 44 52 60

Window, Insulated Dual-Glazed (STC 25) N 7.5 6 1 45.0 14 21 24 22 30 29<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0

Overall Area: 110 ft²

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure17.9 24.8 27.8 25.8 33.8 32.9 : Transmission Loss20.4 20.4 20.4 20.4 20.4 20.4 : Wall Surface Area Factor21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

33.6 32.1 31.6 37.6 28.6 23.6 : Noise Level

40.8 dBA WINDOWS OPEN

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure17.9 24.8 27.8 25.8 33.8 32.9 : Transmission Loss20.4 20.4 20.4 20.4 20.4 20.4 : Wall Surface Area Factor21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

33.6 32.1 31.6 37.6 28.6 23.6 : Noise Level

40.8 dBA WINDOWS CLOSED

Page 43: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EXTERIOR TO INTERIOR NOISE REDUCTION ANALYSIS

Project Name: SBUX PCH & Western Wall 3 of 4Project # : B51104N1Room Name: Back Bar

Noise Level 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSource 1: Traffic 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Traffic Spectrum

Source 2: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 3: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 4: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Overall: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Effective Noise Spectrum

Assembly Type Open Width Height Qty Total Area 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSTC 48 Typical Exterior Wall N 14 11 1 122.5 37 42 45 44 52 60

Window, Insulated Dual-Glazed (STC 25) N 4.5 7 1 31.5 14 21 24 22 30 29<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0

Overall Area: 154 ft²

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure20.8 27.8 30.8 28.8 36.8 35.9 : Transmission Loss21.9 21.9 21.9 21.9 21.9 21.9 : Wall Surface Area Factor21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

32.1 30.6 30.1 36.1 27.1 22.0 : Noise Level

39.3 dBA WINDOWS OPEN

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure20.8 27.8 30.8 28.8 36.8 35.9 : Transmission Loss21.9 21.9 21.9 21.9 21.9 21.9 : Wall Surface Area Factor21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

32.1 30.6 30.1 36.1 27.1 22.0 : Noise Level

39.3 dBA WINDOWS CLOSED

Page 44: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EXTERIOR TO INTERIOR NOISE REDUCTION ANALYSIS

Project Name: SBUX PCH & Western Wall 4 of 4Project # : B51104N1Room Name: Back Bar

Noise Level 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSource 1: Traffic 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Traffic Spectrum

Source 2: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 3: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 4: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Overall: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Effective Noise Spectrum

Assembly Type Open Width Height Qty Total Area 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSTC 48 Typical Exterior Wall N 10 11 1 68.8 37 42 45 44 52 60

Window, Insulated Dual-Glazed (STC 25) N 7.5 5.5 1 41.3 14 21 24 22 30 29<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0

Overall Area: 110 ft²

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure18.2 25.2 28.2 26.2 34.2 33.3 : Transmission Loss20.4 20.4 20.4 20.4 20.4 20.4 : Wall Surface Area Factor21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

33.2 31.7 31.2 37.2 28.3 23.2 : Noise Level

40.4 dBA WINDOWS OPEN

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure18.2 25.2 28.2 26.2 34.2 33.3 : Transmission Loss20.4 20.4 20.4 20.4 20.4 20.4 : Wall Surface Area Factor21.5 21.5 21.5 21.5 22.5 22.5 : Absorption

33.2 31.7 31.2 37.2 28.3 23.2 : Noise Level

40.4 dBA WINDOWS CLOSED

Page 45: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EXTERIOR TO INTERIOR NOISE REDUCTION ANALYSIS

Project Name: SBUX PCH & Western Wall 1 of 3Project # : B51104N1Room Name: Work Room Room Type :

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzReverberation Time (sec) : 1.2 1.2 1.2 1.2 1.0 1.0 : Moderately Reflective Room

Room Absorption (Sabins) : 190 190 190 190 238 238

Noise Level 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSource 1: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Traffic Spectrum

Source 2: 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 3: 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 4: 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Overall: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Effective Noise Spectrum

Assembly Type Open Width Height Qty Total Area 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSTC 48 Typical Exterior Wall N 24 11 1 264.0 37 42 45 44 52 60

<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0

Room Depth: 18 ft Overall Area: 264 ft²Volume: 4752 ft³

Number of Impacted Walls: 3

Windows Open 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz Interior Noise Level: 36.9 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure

37.0 42.0 45.0 44.0 52.0 60.0 : Transmission Loss Windows Closed 24.2 24.2 24.2 24.2 24.2 24.2 : Wall Surface Area Factor Interior Noise Level: 36.9 dBA 22.8 22.8 22.8 22.8 23.8 23.8 : Absorption

16.9 17.4 16.9 21.9 13.0 -1.0 : Noise Level

25.2 dBA WINDOWS OPEN

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure37.0 42.0 45.0 44.0 52.0 60.0 : Transmission Loss24.2 24.2 24.2 24.2 24.2 24.2 : Wall Surface Area Factor22.8 22.8 22.8 22.8 23.8 23.8 : Absorption

16.9 17.4 16.9 21.9 13.0 -1.0 : Noise Level

25.2 dBA WINDOWS CLOSED

<N/A>

Traffic

Medium Hard

<N/A><N/A>

Page 46: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EXTERIOR TO INTERIOR NOISE REDUCTION ANALYSIS

Project Name: SBUX PCH & Western Wall 2 of 3Project # : B51104N1Room Name: Work Room

Noise Level 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSource 1: Traffic 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Traffic Spectrum

Source 2: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 3: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 4: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Overall: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Effective Noise Spectrum

Assembly Type Open Width Height Qty Total Area 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSTC 48 Typical Exterior Wall N 11 11 1 100.0 37 42 45 44 52 601 3/4" Thick Solid Core Door N 3 7 1 21.0 18 22 26 24 23 20

<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0

Overall Area: 121 ft²

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure25.4 29.4 33.4 31.4 30.6 27.6 : Transmission Loss20.8 20.8 20.8 20.8 20.8 20.8 : Wall Surface Area Factor22.8 22.8 22.8 22.8 23.8 23.8 : Absorption

25.2 26.6 25.2 31.1 31.0 28.0 : Noise Level

36.3 dBA WINDOWS OPEN

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure25.4 29.4 33.4 31.4 30.6 27.6 : Transmission Loss20.8 20.8 20.8 20.8 20.8 20.8 : Wall Surface Area Factor22.8 22.8 22.8 22.8 23.8 23.8 : Absorption

25.2 26.6 25.2 31.1 31.0 28.0 : Noise Level

36.3 dBA WINDOWS CLOSED

Page 47: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EXTERIOR TO INTERIOR NOISE REDUCTION ANALYSIS

Project Name: SBUX PCH & Western Wall 3 of 3Project # : B51104N1Room Name: Work Room

Noise Level 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSource 1: Traffic 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Traffic Spectrum

Source 2: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 3: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Source 4: <N/A> 0.0 dBA 0.0 0.0 0.0 0.0 0.0 0.0

Overall: 69.2 dBA 52.5 58.0 60.5 64.5 64.5 58.5 : Effective Noise Spectrum

Assembly Type Open Width Height Qty Total Area 125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHzSTC 48 Typical Exterior Wall N 18 11 1 198.0 37 42 45 44 52 60

<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0<N/A> N 0 0 0 0.0 0 0 0 0 0 0

Overall Area: 198 ft²

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure37.0 42.0 45.0 44.0 52.0 60.0 : Transmission Loss23.0 23.0 23.0 23.0 23.0 23.0 : Wall Surface Area Factor22.8 22.8 22.8 22.8 23.8 23.8 : Absorption

15.7 16.2 15.7 20.7 11.7 -2.3 : Noise Level

23.9 dBA WINDOWS OPEN

125 Hz 250 Hz 500 Hz 1KHz 2KHz 4KHz52.5 58.0 60.5 64.5 64.5 58.5 : Exterior Wall Noise Exposure37.0 42.0 45.0 44.0 52.0 60.0 : Transmission Loss23.0 23.0 23.0 23.0 23.0 23.0 : Wall Surface Area Factor22.8 22.8 22.8 22.8 23.8 23.8 : Absorption

15.7 16.2 15.7 20.7 11.7 -2.3 : Noise Level

23.9 dBA WINDOWS CLOSED

Page 48: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

APPENDIX F

Recommended Products

Page 49: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

TECHNICAL DATA

The sealant is used for exposed and unexposed applications at perimeter joints, floor and ceiling runners, cut outs in gypsum board, veneer plaster systems and other areas where a sound rated assembly is required. The sealant can also be applied or buttered around all electrical boxes and outlets, cold air returns, heating and air conditioning ducts, and other utility equipment penetrating wall surfaces for increased acoustical performance. Also works well for sealing sill and and base plates in residential construction.

SPECIFICATIONS� UL Classified – 48S9 (R9732).

Tested in accordance with and conforms to UL 723: U.B.C. Standard No. 42-1 Class I.

� ASTM E84: Surface Burning Characteristics of Building Materials.

� ASTM E90-85: Laboratory Measurement of Airborne-Sound Transmission Loss of Building Materials.

� ASTM D217: Testing Standard for Consistency.

PHYSICAL PROPERTIES Type Synthetic Latex Rubber Color White Solids by weight 75% Toxicity Toxic only if swallowed. Refer to MSDS. Flammability Nonflammable Flash Point 200°F. TCC (minimum amount of solvent present) Tooling/Open Time 15 minutes Tack Free Time 30 minutes Cure Time 2-7 days Application Temperature 40°F minimum Service Temperature -5°F - 170°F Freeze-Thaw Stability 3 cycles. Unaffected by freezing after curing Shelf Life 1 year from date made at 75°F Sag or Slump Nil (ASTM D2202) VOC Level 22g/l or <1% by wt. Shore “A” Hardness 45 +/-5 (Cured 30 days @ room temp.) Clean-up Water and soap before curing Accelerated Weathering No cracks, discoloration or chalking: 1000

hrs. in Xenon Arc Weatherometer _____________________________________________________

� ASTM C919-79: Standard Practice for Use of Sealants in Acoustical Applications.

� SCAQMD Rule 1168 V.O.C.; CARB; and BAAQMD compliant

� GREENGUARD Certified � Meets LEEDS requirements

LIMITATIONS� Keep from freezing � Do not use below 40°F. (5°C.). � Not recommended for use on mirrors or underwater

applications. � Not recommended for exterior

use. PACKAGING28 oz. cartridges – 12 per case (Item No. GS79928) STORAGEStore at 70°F. +/- 5° (21°C) for long shelf life and easy application. Do not store below 40°F. (5°C.). COVERAGE3/8” round bead size: approx. 40 lin. ft. per 28 oz. cartridge. ¼” round bead size: Approx. 89 lin. ft. / 28oz cartridge.

DRAFT &ACOUSTICALSOUND SEALANT

OSI® Greenseries™ Draft &Acoustical Sound Sealant is a non-flammable, latex-based sealant specially designed to reduce sound transmissions and drafts in all types of wall systems where a sound-rated assembly is required. Its primary function is to achieve and maintain the specific STC (Sound Transmission Class) value of the system designed. The paintable sealant remains flexible and adheres firmly to wood, metal studs, concrete, gypsum board and most other building materials. The easy-to-use sealant cleans up easily with soap and water. FEATURES

� Permanently flexible � Easy application and cleanup � UL Classification – R9732; UL 723 � Easy water cleanup � Low VOC, compliant formula � Will not harden, crack or

separate � Non-staining & non-migrating � High degree of adhesive and

cohesive strength.

USESGreenseries™ Draft & Acoustical was developed primarily for commercial construction utilizing light weight cavity walls and floor systems. Draft & Acoustical Sealant is used successfully in office buildings, hotels, apartment complexes, and other types of commercial & residential construction.

Page 50: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

A. Bottom & Top Runners: Apply a continuous 3/8” round bead of sealant on runners before setting gypsum board. Gypsum board shall be set into sealant to form complete contact with adjacent materials. Fill joint on top runners to complete seal. Repeat procedure for double layer applications. B. Cut-Outs and Perimeter Joints.Backs of electrical boxes, pipes, duct systems and other types of utility equipment penetrating wall surfaces shall be buttered with sealant. Seal all joints at perimeter edges including abutting surfaces and corner joints. 3. Maximum joint size should not exceed �” x ½”. 4. Clean tools and excess sealant immediately after application with soap and water. 5. If necessary, sealant can be painted as applicable to meet project requirements after 24 hours.

CAUTION! CONTAINS ETHYLENE GLYCOL , MINERAL SPIRITS and crystalline silica. Avoid eye contact. Do not take internally. If swallowed, may cause abdominal discomfort. Use with adequate ventilation. Refer to MSDS. WARNING: This product contains a chemical known to the State of California to cause cancer.

KEEP OUT OF REACH OF CHILDREN

FIRST AIDEye Contact: In case of eye contact, flush with clean water for at least 15 minutes. Skin Contact: Wash skin thoroughly with soap and water. Ingestion: DO NOT induce vomiting. Seek medical attention. If dizziness occurs, remove to fresh air.

NOTICE TO PURCHASER Henkel Corporation warrants this product when used according to directions. If not satisfied with the product’s performance when used as directed, return sales receipt and used container to Henkel Corporation, 32150 Just Imagine Drive, Avon OH, 44011 for product replacement or refund. User shall determine suitability of product for use and assumes all risk. QUESTIONS?For commercial use or other questions pertaining to this product, call Henkel Technical Service at 800-321-0253 M-F, 9am – 4pm. or visit our website at www.greenseries.com.

PERFORMANCECHARACTERISTICS1. Underwriters Laboratories

Inc. Classified 48S9 (R9732) UL 723: Sealant tested for surface burning characteristics

Applied to organic Reinforced Cement Board*

Flame Spread 5 Smoke Development 5 *Tested as applied in two 1/2in. beads, 8in. on center. The sealant covered 5.6 percent of theexposed sample area. 2. ASTM E90-85: STC Value – Effect of sealing the opening on a test wall partition. APPLICATIONPROCEEDURESAll surfaces must be clean and free of dust, dirt, oil, moisture and other foreign substances which could interfere with the bond of the sealant. DIRECTIONS1. Cut spout on tube to desired

bead size (3/8” round bead recommended) and puncture seal inside spout.

2. Sealant should be applied as specified in the sound-rated system being installed (either wood or metal studs)

OSI® GreenSeries™ Draft & Acoustical Sound Sealant is currently under going tested by GREENGUARD. The GREENGUARD INDOOR AIR QUALITY CERTIFIED Mark is a registered certification mark used under license through the GREENGUARD Environmental Institute.

Test partition consisted of metal studs 24” O.C. with double layer gypsum board, Fire code “C” and attached with screws on both sides. Inside of partition was filled with sound insulation. Partition system was erected and shimmed out 4.75 mm (0.1875in.) at top, bottom and edges. Results: Sound Transmission Class Value

1. Un-sealed partition – Arrows show sound travel around or through partitions.

a. STC=15 2. Single bead of sealant used at top and bottom runners only – both

sides of partition system. a. STC=24

Metal Stud Partition Door/Window frame in a hollow partition

3. Single bead of sealant used at top, bottom and perimeter joints – both sides of system.

a. STC=45 4. Double bead of sealant used at top, bottom and perimeter joints – both

sides of system. a. STC=55

Henkel Consumer AdhesivesProfessional Adhesives & Sealants 32150 Just Imagine Drive Avon, OH 44011 U.S.A. Phone: (440) 937-7000 Fax: (440) 937-7092 sG11102

Page 51: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

BASIC USES• AC-20 FTR® fire-rated systems aresuitable for applications in schools,hospitals, churches, high-rise officebuildings and hotels, prisons, sportsarenas, and other public-use buildings toensure a safe and orderly evacuation inthe event of a fire.

PACKAGING• 30 fl. oz. (.887 liter) fiber cartridges• 5-gallon (18.9 liter) pails

COLOR• White, Beige-GraySpecial colors available in 250-gallon(946 liter) batches.

Test Property Value Procedure

Modulus @ 100% (psi) 15-20 ASTM D412Ultimate Tensile (psi) 30-40 ASTM D412Ultimate Elongation (%) 400-500 ASTM D412Movement Capability (%) ±7 1/2 ASTM D412VOC Content 31 g/L

Since Pecora architectural sealants are applied to varied substrates under diverse environmental conditions and construction situations it is recommended that substrate testing be conducted prior to application.

TYPICAL PHYSICAL PROPERTIES

Specification Data SheetAC-20 FTR®

(Fire & Temperature Rated) Acoustical & Insulation Sealant

2. MANUFACTURERPecora Corporation165 Wambold Road Harleysville, PA 19438

Phone: 215-723-6051800-523-6688

Fax: 215-721-0286Website: www.pecora.com

3. PRODUCT DESCRIPTIONAC-20 FTR® is a unique acrylic latexsealant that is UL® Classified infirestopping systems for expansion jointsand through penetrations.When properlyinstalled, these systems effectively containfire, smoke, toxic fumes, and water within agiven area surrounded by firewalls for atwo, three, or four hour period, dependingon the design specifications.

Other Uses: Excellent adhesive, flexibilityand durability qualities make AC-20 FTR®

ideal for insulating and weatherproofingaround windows, doors, panels, siding, ductwork, base plates, etc. It is compatible withall common building materials includingspecialties such as polystyrene,polyurethane, cork, vinyl, foamed andfibrous glass.

Used as an acoustical sealant,AC-20 FTR®

reduces sound transmission in partitionsystems to achieve specific STC values bysealing spaces around cut-outs and atperimeters of partitions.The sealant curesto a tough rubber to form a long-lastingacoustical seal.

4.TECHNICAL DATAApplicable Standards: ASTM C-834-86specification for latex sealing compounds.

Fire Rated System: Two-hour Fire andTemperature Rated wall and floor jointsystems up to 7" (178mm) wide andfour-hour systems up to 4" wide can bedesigned with AC-20 FTR® in conjunctionwith Ultra Block fire blocking material infire-rated walls and floors. Reference:ANSI/UL 263,ASTM E-119, NFPA No. 251.

UNDERWRITERSLABORATORIES INC.®

CLASSIFIEDJOINT TREATMENT MATERIALS

FIRE RESISTANCE CLASSIFICATION

DESIGNS J900H (FFS 0006) &U900 "O"(WWS 0010), J900Z (FFS 2002), U900Z-009 (WWS 2008), J900Z-007 (FFS 1010),

U900Z-015 (WWS 1012)

AC-20 FTR® in conjunction with UltraBlock® achieves a 2-hour fire rating whensealing around steel or copper pipe andelectrical metallic tubing or steel conduit inthrough penetration systems. Reference:ANSI/UL 1479,ASTM E-814.

FILL,VOID OR CAVITY MATERIALSCLASSIFIED BY

UNDERWRITERS LABORATORIES INC.

FOR USE INTHROUGH-PENETRATION

FIRESTOP SYSTEM NO. CAJ 1093

In addition to its fire-blocking value, UltraBlock® is very efficient acoustically, having anoise reduction coefficient of .75 andsound transmission coefficient of .5 (UltraBlock® is a registered trademark of BackerRod Mfg. and Supply Co., Denver, CO, USA.)

5. INSTALLATIONSurface Preparation: Surfaces must befree of all contamination. Sealant may beapplied to damp, porous surfaces. Nopriming is required.

Application: Refer to PecoraFirestopping Manual 07270 and UL FireResistance Directory for installation detailson fire-rated joint and through penetrationsystems. For insulating and weatherproof-ing purposes, fill all window, door, andpanel perimeter joints using a resilientbacker rod to control sealant depth to1/2" (13mm) maximum. For best results,protect sealant from excessive lowtemperatures and apply above 40°F (4°C).For acoustical purposes, apply continuous

UL®

CLASSIFIED

Page 52: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

P E O P L E • P R O D U C T S • P E R F O R M A N C E

HARLEYSVILLE, PA165 Wambold Road, Harleysville, PA 19438Phone: 800-523-6688 • 215-723-6051 • FAX: 215-721-0286

DALLAS,TX11501 Hillguard Road, Dallas,TX 75243Phone: 800-233-9754 • 214-348-5313 • FAX: 214-348-5421

www.pecora.com

Specification Data Sheet

beads of sealant to seal perimeters of allsound-rated partitions.Apply sealant in theangles formed by metal components orbase-layer panels and abutting surfaces.Apply sealant around all openings formedfor outlets; electrical, telephone, lightfixtures, etc.

Tooling: Tool material flush with surfacesto allow for expected shrinkage and insuregood contact and adhesion to thesubstrate.

Cleaning: Remove excess material withwater or a damp cloth before it cures.Sealant may be painted within 30 minutesafter application with a good grade of latexpaint.

Shelf Life: AC-20 FTR® has a shelf lifewell in excess of one year when stored inunopened containers below 80° F (27°C).

Precautions: AC-20 FTR® isnon-flammable, non-toxic, non-irritatingand environmentally safe. However, do nottake internally. Refer to Material SafetyData Sheet for additional information.

Ultra Block® is a non-carcinogenicprocessed continuous filament textile glassfiber that may cause skin, eye andrespiratory irritation.When applying, wearlong sleeves, gloves, cap, goggles or safetyglasses and NIOSH/MSHA-approved dustrespirator.After use bathe with soap andwarm water.Wash clothes separately andrinse after use. Refer to Material SafetyData Sheet for additional information.

FOR PROFESSIONAL USE ONLY.KEEP OUT OF THE REACH

OF CHILDREN.

6.AVAILABILITY AND COSTPecora products are available from ourstocking distributors in all major cities.For the name and telephone number ofyour nearest representative call one of our locations listed below or visit our websiteat www.pecora.com.

7.WARRANTYPecora Corporation warrants its productsto be free of defects. Under this warranty,we will provide, at no charge, replacementmaterials for, or refund the purchase priceof, any product proven to be defectivewhen installed in accordance with ourpublished recommendations and inapplications considered by us as suitablefrom this product.This warranty in lieu ofany and all other warranties expressed orimplied, and in no case will Pecora be liablefor incidental or consequential damages.

8. MAINTENANCEIf the sealant is damaged and the bond isintact, cut out the damaged area andrecaulk. No primer is required. If the bondhas been affected, remove the sealant,clean and prepare the joint in accordancewith instructions under "Installation".

9.TECHNICAL SERVICESPecora representatives are available toassist you in selecting an appropriate product and to provide on-site applicationinstructions or to conduct jobsite inspections. For further assistance call ourTechnical Service Department at 800-523-6688.

3K0704

Page 53: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

APPENDIX G

Cadna Analysis Data and Results

Page 54: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EILAR ASSOCIATES, INC.Acoustical and Environmental Consulting

Name ID Type SourceWeight 63 125 250 500 1000 2000 4000 8000 A lin

DT Intercom L1 Lw (c) A 84.5 84.5 87.7 Manufacturer

Oktave Spectrum (dB)Cadna Noise Model - Sound Levels

Page 1 of 4

Page 55: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EILAR ASSOCIATES, INC.Acoustical and Environmental Consulting

Name ID Result. PWL HeightDay Type Value X Y Z

(dBA) (m) (m) (m) (m)DT Intercom S_1 84.5 Lw L1 1.22 106.76 81.84 1.22

Lw / Li CoordinatesCadna Noise Model - Point Sources

Page 2 of 4

Page 56: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EILAR ASSOCIATES, INC.Acoustical and Environmental Consulting

Name IDX Y Z

(m) (m) (m)96 105.34 3.66

96.2 95.51 3.6699.63 95.51 3.6699.57 93.47 3.66

105.24 93.34 3.66105.3 100.85 3.6699.43 100.85 3.6699.57 105.34 3.66

Cadna Noise Model - BuildingsAbsorptionCoordinates

0.37Proposed Bldg BL_1

Page 3 of 4

Page 57: ACOUSTICAL ANALYSIS REPORT - Lomita · 2016-05-16 · ACOUSTICAL ANALYSIS REPORT Starbucks – Pacific Coast Highway & Western Avenue 1730-1734 Pacific Coast Highway Lomita, California

EILAR ASSOCIATES, INC.Acoustical and Environmental Consulting

Name ID Level Lr HeightDay X Y Z

(dBA) (m) (m) (m) (m)South (LA) R_1 45.0 1.52 107.97 59.15 1.52

South (Lomita) R_2 44.9 1.52 99.01 59.17 1.52East (LA) R_3 58.9 1.52 112.40 81.83 1.52

West (Lomita) R_4 44.0 1.52 81.96 82.17 1.52

Cadna Noise Model - Noise Levels at ReceiversCoordinates

Page 4 of 4