add: 233814 – kitchen range hoodbellconstruct.com/sites/default/files/add_1_specs_2.pdfforth by...

16
Page 1 of 9 Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U ADDENDUM NO. 1 Fire Station Renovation & Police Station Addition Building 7200 Camp Joseph T. Robinson North Little Rock, Arkansas ISSUED: July 25, 2016 BY: STOCKS-MANN ARCHITECTS, PLC 401 W. Capitol, Suite 402 Little Rock, Arkansas 72201 TO: All Prime Bidders and Plan Holders of Record (This Addendum forms a part of the Bidding Documents and modifies them as described herein.) I. REFER TO THE PROJECT MANUAL, dated July 1, 2016 A. Refer to Index, Division 23 1. Add: 233814 – Kitchen Range Hood B. Refer to Section 011000, para 1.3.A, Owner Occupancy 1. Add the following sentence: The existing ladder truck will remain on site and will be stored on the premises during construction. The ladder truck can be moved outside for construction purposes, weather permitting by contacting Camp Robinson. This storage area must be secured at the end of each day with the ladder truck inside. C. Refer to Section 033000 1. Add the following: 2.12 CRACK SEALANT: A. Concrete Crack Repair Less than 1/8” in Width: Rapid- setting, two-component polyurea polymer liquid of 100% solids content, complying with floor joint filler guidelines set forth by ACI 30 and 360. 1. Product: Rapid Refloor; Metzer/McGuire. B. Concrete Crack Repair Greater than 1/8” in Width and for Joint Spalling up to 1” Wide: Rapid-setting, two-component, heavy duty semi-rigid epoxy joint filler of 100% solids content, complying with floor joint filler guidelines set forth by ACI 30 and 360.

Upload: others

Post on 31-Jan-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Page 1 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    ADDENDUM NO. 1 Fire Station Renovation & Police Station Addition Building 7200 Camp Joseph T. Robinson North Little Rock, Arkansas ISSUED: July 25, 2016 BY: STOCKS-MANN ARCHITECTS, PLC 401 W. Capitol, Suite 402 Little Rock, Arkansas 72201 TO: All Prime Bidders and Plan Holders of Record

    (This Addendum forms a part of the Bidding Documents and modifies them as described herein.)

    I. REFER TO THE PROJECT MANUAL, dated July 1, 2016

    A. Refer to Index, Division 23 1. Add: 233814 – Kitchen Range Hood

    B. Refer to Section 011000, para 1.3.A, Owner Occupancy 1. Add the following sentence: The existing ladder truck will remain on site and will be stored on the premises during construction. The ladder truck can be moved outside for construction purposes, weather permitting by contacting Camp Robinson. This storage area must be secured at the end of each day with the ladder truck inside.

    C. Refer to Section 033000 1. Add the following: 2.12 CRACK SEALANT:

    A. Concrete Crack Repair Less than 1/8” in Width: Rapid- setting, two-component polyurea polymer liquid of 100% solids content, complying with floor joint filler guidelines set forth by ACI 30 and 360.

    1. Product: Rapid Refloor; Metzer/McGuire.

    B. Concrete Crack Repair Greater than 1/8” in Width and for Joint Spalling up to 1” Wide: Rapid-setting, two-component, heavy duty semi-rigid epoxy joint filler of 100% solids content, complying with floor joint filler guidelines set forth by ACI 30 and 360.

  • Page 2 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    1. Product: MM-80P; Metzer/McGuire. or

    Rapid-setting, two-component heavy duty semi-rigid polyurea polymer liquid of 100% solids content, complying with floor joint filler guidelines set forth by ACI 30 and 360.

    1. Product: Spal-Pro RS 88; Metzer/McGuire.

    D. Refer to Section 033000 1. Add the following: 3.6 CRACK SEALANT

    A. Install crack repair sealant in existing floor cracks. Comply with manufacturer’s recommendations and ACI guidelines.

    E. Refer to Section 088000, para 2.10.C.3

    1. Change to read: Outdoor Lite: Bronze tinted fully tempered float glass.

    F. Refer to Section 088000, para 2.10.C.5

    1. Change to read: Indoor Lite: Clear fully tempered float glass.

    G. Refer to Section 088000

    1. Add Para: 2.11 – LAMINATED GLASS

    A. Laminated Glass ASTM C 1172. Use materials that have a proven record of no tendency to bubble, discolor, or lose physical and mechanical properties after fabrication and installation. 1. Construction: Laminate glass with polyvinyl butyral interlayer, ionomeric polymer interlayer or cast-in-place an cured transparent-resin interlayer to comply with interlayer manufacturer’s written instructions. 2. Interlayer Thickness: Provide thickness not less than that indicated and as needed to comply with requirements. 3. Interlayer Color: White unless otherwise indicated.

    a. Light Transmittance: 80%

    H. Refer to Section 088000

  • Page 3 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    1. Add Para: 2.12 – LAMINATED GLASS TYPE

    A. Glass Type GL-4: Clear laminated glass with two plies of heat strengthened float glass.

    1. Minimum Thickness of Each Ply:As indicated. 2. Interlayer Thickness: 0.060 inch 3. Safety glazing required

    I. Refer to Section 096513, para. 2.1.D.

    1. Change to read: Height: 4 inches

    J. Refer to Section 211313 – WET PIPE SPRINKLER SYSTEMS, Part 1, Article 1.6 QUALITY ASSURANCE, Paragraphs C:

    1. Change paragraph to read as follows: “The Fire Protection Contractor shall be licensed as per the requirements of the Arkansas Fire Protection Licensing Board.”

    K. Refer to Section 211313 – DRY PIPE SPRINKLER SYSTEMS, Part 1, Article 1.6 QUALITY ASSURANCE, Paragraphs C:

    1. Change paragraph to read as follows: “The Fire Protection Contractor shall be licensed as per the requirements of the Arkansas Fire Protection Licensing Board.”

    L. Refer to Section 220000 – SUPPLEMENTARY PLUMBING GENERAL CONDITIONS, Part 1, Article 1.5 CODES AND STANDARDS, Paragraphs B:

    1. Change Item 1. as follows:

    Building Codes a. International Building Code b. Arkansas Fire Prevention Code c. National Electrical Code d. Arkansas Fuel Gas Code (International Fuel Gas Code) e. International Existing Building Code f. Arkansas Energy Code (based on ANSI/ASHRAE/IESNA Standard 90.1

    2007) g. Arkansas State Plumbing Code h. Arkansas Mechanical Code i. Accessibility Code ICC/ANSI A117.1 2003

  • Page 4 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    M. Refer to Section 230593 – TESTING, ADJUSTING, AND BALANCING, Part 1, Article 1.2 QUALITY ASSURANCE, Paragraph B:

    1. Delete paragraph.

    N. Refer to Section 230593 – TESTING, ADJUSTING, AND BALANCING, Part 1, Article 1.3 SUBMITTALS:

    1. Change title to read “SUBMITTALS: Comply with Sections 013300 and 230000.”

    O. Refer to Section 230713 – MECHANICAL SYSTEMS INSULATION, Part 1, Article 1.3 QUALITY ASSURANCE, Paragraph B:

    1. Delete paragraph.

    P. Refer to Section 233814 – KITCHEN RANGE HOOD: 1. Add attached section.

    Q. Refer to Section 238126 – HVAC EQUIPMENT, Part 1, Article 1.4 SUBMITTALS:

    1. Change Section numbers to be 013300 and 230000

    R. Refer to Section 260000 – SUPPLEMENTARY ELECTRICAL GENERAL CONDITIONS, Part 1, Article 1.4 CODES AND STANDARDS, Paragraph B:

    1. Change Item 1. as follows:

    Building Codes a. International Building Code b. Arkansas Fire Prevention Code c. National Electrical Code d. Arkansas Fuel Gas Code (International Fuel Gas Code) e. International Existing Building Code f. Arkansas Energy Code (based on ANSI/ASHRAE/IESNA Standard

    90.1- 2007) g. Arkansas State Plumbing Code h. Arkansas Mechanical Code i. Accessibility Code ICC/ANSI A117.1 2003

    2. Delete Item 2. 3. Delete Item 3.

    S. Refer to Section 265100 – INTERIOR LIGHTING, Part 1, Article 1.6 MAINTENANCE MATERIAL SUBMITTALS:

  • Page 5 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    1. Delete entire article.

    T. Refer to Section 265100 – INTERIOR LIGHTING, Part 1, Article 1.9 WARRANTY, Paragraph A:

    1. Change Item 1. to read:

    “Warranty Period for Emergency Lighting Unit Batteries: 3 years from date of Substantial Completion. Full warranty shall apply for first year, and prorated warranty for the remaining two years.”

    2, Change Item 2. to read:

    “Warranty Period for Emergency Fluorescent Ballast, Emergency LED battery packs and Self-Powered Exit Sign Batteries: 3 years from date of Substantial Completion. Full warranty shall apply for first year, and prorated warranty for the remaining two years.”

    U. Refer to Section 265600 – EXTERIOR LIGHTING, Part 1, Article 1.7 MAINTENANCE MATERIAL SUBMITTALS:

    1. Delete entire article.

    V. Refer to Section 331100, para 1.02, A. & B.

    1. Delete para: A. and B.

    W. Refer to Section 331100, para 2.01.B

    1. Delete para: B.

    X. Refer to Section 331210, para 1.2, A. & C.

    1. Delete para: A. and C.

    II. REFER TO THE PROJECT DRAWINGS, dated July 1, 2016

    A. Refer to Sheet D1.0, Site Demolition General Notes

  • Page 6 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    1. Add Note #9, to read: Sheet Metal and Cardboard Recycling Dumpsters will be provided by Camp Robinson for use by the General Contractor for sheet metal debris and cardboard debris. Concrete demolition debris will need to be disposed of by the General Contractor, concrete debris can be disposed of on Post where designated by Camp Robinson. All other debris will be the responsibility of the General Contractor.

    B. Refer to Sheet D2.0,

    1. Delete this sheet and add the attached: D2.0, Add#1, revision dated 7-19-16:

    C. Refer to Sheet D2.1, Demolition General Notes

    1. Add Note #11, to read: Sheet Metal and Cardboard Recycling Dumpsters will be provided by Camp Robinson for use by the General Contractor for sheet metal debris and cardboard debris. Concrete demolition debris will need to be disposed of by the General Contractor, concrete debris can be disposed of on Post where designated by Camp Robinson. All other debris will be the responsibility of the General Contractor.

    D. Refer to Sheet D2.2, Demolition General Notes

    1. Add Note #12, to read: Sheet Metal and Cardboard Recycling Dumpsters will be provided by Camp Robinson for use by the General Contractor for sheet metal debris and cardboard debris. Concrete demolition debris will need to be disposed of by the General Contractor, concrete debris can be disposed of on Post where designated by Camp Robinson. All other debris will be the responsibility of the General Contractor.

    E. Refer to Sheet D2.3, Demolition General Notes

    1. Add Note #13, to read: Sheet Metal and Cardboard Recycling Dumpsters will be provided by Camp Robinson for use by the General Contractor for sheet metal debris and cardboard debris. Concrete demolition debris will need to be disposed of by the General Contractor, concrete debris can be disposed of on Post where designated by Camp Robinson. All other debris will be the responsibility of the General Contractor.

    F. Refer to Sheet A8.1, Detai #1

    1. Delete Note: “1x2 P.T. wood batten strip – continuous along front, back, and all seams of plywood soffits”

  • Page 7 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    G. Refer to Sheet A9.1, Detail #4 & #5

    1. Change Note “Clothes Locker” to “Plastic Lockers for Sleeping Quarters”

    H. Refer to Sheet A9.2, Detail #10

    1. Change Note “Food Locker” to “Plastic Lockers for Food Storage”

    I. Refer to Sheet A10.1, Detail #3

    1. Delete Note: ”Mirror mounted on solid surface countertop material”

    J. Refer to Sheet S1.1 1. Remove note: Provide self-leveling topping slab to hatched existing flooring floor area.

    K. Refer to Revised Sheet M0.0 – GENERAL NOTES AND LEGENDS – HVAC – revision dated 7-19-2016:

    1. Removed “PRELIMINARY NOT FOR CONSTRUCTION” stamp.

    L. Refer to Revised Sheet M0.1 – SCHEDULES – HVAC – revision dated 7-19-2016:

    1. Removed “PRELIMINARY NOT FOR CONSTRUCTION” stamp.

    M. Refer to Revised Sheet M1.0 – DEMOLITION FLOOR PLAN - HVAC – revision dated 7-19-2016:

    1. Added keyed note 3 to indicate thermostat to be relocated. 2. Removed “PRELIMINARY NOT FOR CONSTRUCTION” stamp.

    N. Refer to Revised Sheet M2.0 – FLOOR PLAN - HVAC– revision dated 7-19-2016:

    1. Revised location of existing thermostat.

    2. Removed “PRELIMINARY NOT FOR CONSTRUCTION” stamp.

    O. Refer to Revised Sheet M3.0 – DETAILS - HVAC – revision dated 7-19-2016:

    1. Revised detail 4. 2. Detail 5 removed from sheet. 3. Detail 6 removed from sheet. 4. Detail 9 removed from sheet. 5. Detail 10 removed from sheet. 6. Removed “PRELIMINARY NOT FOR CONSTRUCTION” stamp.

  • Page 8 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    P. Refer to Revised Sheet M3.1 – DETAILS - HVAC – revision dated 7-19-2016:

    1. Removed “PRELIMINARY NOT FOR CONSTRUCTION” stamp”.

    Q. Refer to Revised Sheet E1.0 – DEMOLITION FLOOR PLAN – ELECTRICAL – revision dated 7/19/2016:

    1. Added keyed note 12 to indicate receptacles which are existing to remain.

    2. Added keyed note 13 indicating demolition of wall switch in room EXIST APPARATUS ROOM.

    R. Refer to Revised Sheet E2.0 – FLOOR PLAN – LIGHTING – revision dated

    7/19/2016:

    1. Added keyed note 6 indicating installation of wall switch for Mezzanine lights. Verify switching of circuit.

    2. Removed battery pack from type A fixture and type I fixture. Changed circuiting to accommodate.

    3. Added battery pack to type A fixture in room WAITING 100.

    S. Refer to Revised Sheet E3.0 – FLOOR PLAN – POWER – revision dated 7/19/2016:

    1. Added keyed note 9 indicating connection of existing receptacles to new circuit in room EXIST OFFICE 139.

    2. Removed receptacle installed on CMU wall in room WASHER/DRYER 131.

    3. Clarified keyed note 1 to mean the video monitor and television outlets are two-gang back-boxes with combination duplex receptacle and outlet connector).

    4. Removed dead-front GFCIs for refrigerators in room FOOD STR. 128.

    T. Refer to Revised Sheet E6.0 – PANEL SCHEDULES – ELECTRICAL – revision dated 7/19/2016:

    1. Refer to branch panel E1. Changed circuits 3, 9, and 10 from AFCI breakers to dual function AFCI/GFCI breakers for refrigerators.

  • Page 9 of 9

    Fire Station Renovation & Addendum No. 1 Police Station Addition SMA #0901U

    Attachments:

    A. Spec Section 233814 – KITCHEN RANGE HOOD B. AD1.0 C. AD1.1 D. AD1.2 E. D2.0, - ADD#1, revision dated 7-19-16 F. M0.0 – ADD#1, revision dated 7-19-16 G. M0.1 – ADD#1, revision dated 7-19-16 H. M1.0 – ADD#1, revision dated 7-19-16 I. M2.0 – ADD#1, revision dated 7-19-16 J. M3.0 – ADD#1, revision dated 7-19-16 K. M3.1 – ADD#1, revision dated 7-19-16 L. E1.0 – ADD#1, revision dated 7-19-16 M. E2.0 – ADD#1, revision dated 7-19-16 N. E3.0 – ADD#1, revision dated 7-19-16 O. E6.0 – ADD#1, revision dated 7-19-166

    END OF ADDENDUM NO. 1

  • 233814 Page 1

    Fire Station Renovation & KITCHEN HOOD EXHAUST FANS Police Station Addition ADDENDUM #1 SMA #0901U

    SECTION 233814 - KITCHEN RANGE HOOD

    PART 1 - GENERAL

    1.1 SUMMARY: This section specifies fully integrated, pre-engineered fire suppression range hood systems.

    1.2 DEFINITIONS

    A. Range hood, unit, kitchen hood and hood system; for purposes of this specification section, these terms all have the same definition.

    B. Residential grade fire suppression: a hood suppression system that fulfills the 300A standard, being designed to protect a residential-grade cooking appliance that is used within a commercial space.

    C. Eyebrow, compensating, short circuit hood types are not allowed.

    1.3 QUALITY CONTROL

    A. Installer Qualifications: Experienced in mechanical equipment installation or supervised by an experienced mechanical equipment installer.

    1. Where required to complete equipment installation, electrician and plumber shall be licensed in jurisdiction where project is located.

    B. NSF Compliance: Equipment bears NSF Certification Mark (when required)

    C. UL Listing: Equipment has been evaluated according to UL or ETL 300A and is labeled for intended use.

    D. Fire-Protection Systems: to be pre-engineered and factory integrated into the design of the hood

    E. Vibration Restraint:

    1. Comply with requirements in Section 230548, Noise, Vibration, and Expansion Control.

    F. In-Use Service: The manufacturer maintains that the system can be operated or maintained by any qualified maintenance technician. However, the manufacturer will offer web-based certification training by request. The manufacturer does not provide field service.

    1.4 SUBMITTALS

    A. Manufacturer’s Literature and Data:

    1. Include catalog or model numbers, and illustrations and descriptions of ventilators and accessories.

  • 233814 Page 2

    Fire Station Renovation & KITCHEN HOOD EXHAUST FANS Police Station Addition ADDENDUM #1 SMA #0901U

    B. Shop Drawings:

    1. Include plans, elevations, sections, and attachment details. 2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required

    clearances, method of field assembly, components, and location and size of each field connection.

    3. Include diagrams for power, signal, and control wiring. 4. Design Calculations: Calculate requirements for selecting vibration isolators and for

    designing vibration isolation bases. 5. Vibration Isolation Base Details: Detail fabrication, including anchorages and attachments

    to structure and to supported equipment. Include auxiliary motor slides, rails, and base weights.

    C. Field Test Reports: Indicate whether demonstration will be necessary, dates and times of tests and certify test results.

    D. Operating Instructions: Include operating instructions covering operation of all components and maintenance procedures covering proper cleaning and necessary lubrication or adjustments to controls.

    1.5 APPLICABLE PUBLICATIONS

    A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

    B. ICC Evaluation Service Listing Criteria #1031 (LC1031)

    C. ICC Evaluation Services PMG Listing #1293 (PMG1293)

    D. UL or ETL Standard 300A

    PART 2 – PRODUCTS

    2.1 EXHAUST HOODS

    A. The hood shall be constructed of 18 & 20 gauge (type 304) polished stainless steel. Hood shall have fire suppression system factory installed into the hood system. Activation of the mechanical fire suppression system shall be by 212 or 280-degree fusible link (30” vs. 36” sizes). Fire suppression agent will be Amerex 660 Low PH wet chemical suppressant. Unit shall include centrifugal fan with air delivery of 380 to 610 cfm depending of calibration of unit. Unit shallinclude fuel shutdown option for Gas, Electric or Dual Element Devices. The hood system will also have multiple alarm and monitoring contacts factory installed into the hood.

    Greenheck Model Width Fan Type Venting CFM (at hood) Duct Length (max) GRRS-36-R-G-N 36 Internal Rear 500 N/A GRRS-36-T-G-W-N 36 Wall Mount Fan Top 550 20 Feet

  • 233814 Page 3

    Fire Station Renovation & KITCHEN HOOD EXHAUST FANS Police Station Addition ADDENDUM #1 SMA #0901U

    C. Hood system include commercial-grade grease extractor type, high efficiency cartridge style baffle filters of adequate number and sizes to ensure optimum performance in accordance with manufacturer’s published information. The filter housing shall terminate in a pitched, full-length grease trough, which shall drain into a removable grease container.

    D. Shatter proof light fixtures shall be included in the hood system. Wiring shall conform to the requirements of the National Electrical Code (NEC #70).

    1. Pre-Installed Fire protection system to provide duct entry, plenum, and surface protection for hood system and equipment located below ventilator.

    2. System interconnected with included shunt trip breaker and/or gas solenoid valve of equipment located below ventilator for power and fuel shutoff during system actuation.

    E. Environmental Monitoring / Internal Monitoring / Pre-Suppression

    1. Two temperature sensors are located on the inner face of the hood; one at a medium set point, the other at high. Under cooking conditions, when the medium set point is reached, the fan is turned on high. This feature dissipates the heat from the area but also draws it into the unit, past the fusible links in the system. If temperatures continue to rise and the high temperature set point is reached, the system reacts by shutting down power to the range prior to suppression system release. When this occurs, the unit’s internal alarm is activated so that occupants are notified that the system is working to prevent further escalation of a potential fire. This is considered two stages of pre-suppression, where the unit is interacting with the cooking environment - working to minimize the risk of a fire event

    Should temperatures continue to rise, fire is present. The fusible links will melt, mechanically actuating the suppression system and releasing a low PH wet chemical agent across the cook-top. At actuation, the system will also make a second attempt to shut down power to the range; in the event of a flash-fire, or something that happens too quickly to register with the temperature sensors. The system will continue to sound its internal alarm while also communicating a “fire code” back to a monitored alarm panel.

    The PLC Self-Monitoring-System also monitors the entire suppression assembly for completeness and continuity. If the suppression system is ever compromised through a loss of pressure or broken connection, or tampering of any kind, the unit reacts by shutting down power to the range. In this case the suppression system is compromised therefor the range shouldn't be in use. Under this condition, the system communicates a separate "maintenance code" saying that the unit is down and needs service. When preemptive shutdown occurs, the system and the cooking equipment will not come back on-line until the GRRS is reset.

    F. Accessories

    1. Manual Pull Station (MPK) – Mechanical assembly allowing the fire suppression system to be actuated manually normally located at the point of egress.

    2. The CLOCKBOX (CLBX) – Cooking Element Time-Out System allowing for separate control functionality over when the appliance is used.

    3. NSF (NSF) – The hood system can be upgraded to the NSF Standard 4. Handicapped Accessible Controls (ADA) – Separate control system designed to mirror the

    front-end controls of the hood, to be installed at under counter-top height. 5. Powder Coating (PC) – The hood system can be powder coated in a variety of standard

    colors, the manufacturer can also color match. 6. NFPA101 Upgrade (NFPA101) – Combines MPK, CLBX and an upgraded fan to deliver

    >500cfm in order to comply with the requirements of the NFPA Life Safety Code.

  • 233814 Page 4

    Fire Station Renovation & KITCHEN HOOD EXHAUST FANS Police Station Addition ADDENDUM #1 SMA #0901U

    PART 3 – EXECUTION

    3.1 INSTALLATION

    A. Install hood system level and plumb with access clearances required for operation, maintenance and cleaning and in accordance with the manufacturer's published documentation. Show on drawings overhead or rear support for equipment specified in this section. Specify requirements for support in Section 230529.

    B. Interconnect ventilators to service utilities.

    3.2 FIELD TESTING

    A. Functional Test: using manufacturer-supplied procedure, short internal sensors to demonstrate shutdown and communication features.

    B. Puff Test: using manufacturer supplied test cylinder, replace suppressant cylinder in system with test (nitrogen only) cylinder. Replace fusible links in line with a “test link”. Cut the test link and allow the system to actuate, performing all of its standard functions.

    3.3 CLEAN-UP

    A. At completion of the installation, clean and adjust equipment as required to produce ready-for-use condition.

    B. Where stainless-steel surfaces are damaged during installation procedures, repair finishes in order to match adjoining undamaged surfaces.

    3.4 INSTRUCTIONS

    A. Instruct personnel and transmit operating instructions in accordance with requirements.

    END OF SECTION 233814

  • Addendum #1, #0901U for reviewKitchen Range Hood Spec 233814ADD01 071916233814 Kitchen Range Hood-ADD01M0-0M0-1M1-0M2-0M3-0M3-1E1-0E2-0E3-0E6-0

    Joint Spalling, Minor, Up to 1 inch wideRandom Cracks less than an eighth inchRandom Cracks greater than an eighth inch wideD2.0 Add#1, 7-19-16Addendum # 1 DrawingsADD01 071916233814 Kitchen Range Hood-ADD01M0-0M0-1M1-0M2-0M3-0M3-1E1-0E2-0E3-0E6-0