INTEGRITY EXCELLENCE TRUST Addendum No. 1 Issue Date: October 6, 2020 Project: Interior Renovations The Betty Hardwick Center The following are additions, deletions, clarifications, or corrections to the Specifications and Drawings and shall become a part of the Contract Documents. Drawings Item #D1 Sheet M0.1 - General Notes – Updates made to General Notes J, K, Q, R, and CC. Item #D2 Sheet M1.0 - Mechanical Plan Duct and takeoff size changes due to updated air flows to each room Return air ducts added to RTU-13 and 14 Changed the corner office return air silencers to a model U device due to clearance issues above the door frame Item #D3 Sheet M2.0 - Keyed Notes – Updates made to Keyed Notes 1 and 2. Item #D4 Sheet M3.0 - Mechanical Schedules and Details Updated air device schedule due to duct and takeoffs size changes Added a new model U return air silencer device for office that didn’t allow for the standard model Z Updated Rooftop Unit Return Detail to show that the bottom of the return air duct shall be installed flush with the bar joists, and the grilles will be duct mounted on the side of the duct. Updated model of EF-2 to account for higher static pressure drop within the duct work END OF ADDENDUM NO. 1 A T T S X E T E F O S A W I L L A M R . D U N C A 9 R E G I S T E R E D A R C H I T E C T I N I I 6 8 4 2

Upload: others

Post on 08-Feb-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

INTEGRITY

EXCELLENCE

TRUST

Addendum No. 1

Issue Date: October 6, 2020

Project: Interior Renovations

The Betty Hardwick Center

The following are additions, deletions, clarifications, or corrections to the Specifications and Drawings

and shall become a part of the Contract Documents.

Drawings

Item #D1 Sheet M0.1 - General Notes – Updates made to General Notes J, K, Q, R, and CC.

Item #D2 Sheet M1.0 - Mechanical Plan

• Duct and takeoff size changes due to updated air flows to each room

• Return air ducts added to RTU-13 and 14

• Changed the corner office return air silencers to a model U device due to

clearance issues above the door frame

Item #D3 Sheet M2.0 - Keyed Notes – Updates made to Keyed Notes 1 and 2.

Item #D4 Sheet M3.0 - Mechanical Schedules and Details

• Updated air device schedule due to duct and takeoffs size changes

• Added a new model U return air silencer device for office that didn’t allow for

the standard model Z

• Updated Rooftop Unit Return Detail to show that the bottom of the return air

duct shall be installed flush with the bar joists, and the grilles will be duct

mounted on the side of the duct.

• Updated model of EF-2 to account for higher static pressure drop within the

duct work

END OF ADDENDUM NO. 1

AT

TS

XETE FO

SA

WILL

AMR.DUN

CA

9

REGIS

TERED ARCH

ITECT

I

NII

6 842

72"x6"

1,000 CFM

S-2 /

T

2X2 LAY-IN DIFFUSER.

1X2 SUPPLY DIFFUSER

THERMOSTAT LOCATION.

RIGID ROUND DUCT

INSULATED FLEX SUPPLY DUCT. R-4.2 INSULATION LOCATED

ABOVE CEILING

ROOF MOUNTED EXHAUST FAN

ROOF TOP UNIT (RTU)

CUBIC FEET PER MINUTE.

DUCT SIZE

DIFFUSER/ LOUVER/GRILL/

MARK FROM SCHEDULE.

GALVANIZED STEEL PLENUM FOR SUPPLY AND RETURN

CEILING MOUNTED EXHAUST FAN

1X2 LAY-IN RETURN AIR GRILL.

WALL MOUNTED SUPPLY DIFFUSER

WALL MOUNTED RETURN GRILL

INSULATED FLEX RETURN DUCT. LOCATED ABOVE CEILING

RECTANGULAR GALVANIZED STEEL SUPPLY DUCT

RECTANGULAR GALVANIZED STEEL RETURN DUCT

EXISTING SPIRAL DUCT TO BE REUSED

NEW SPIRAL DUCT

SIDE WALL DUCT MOUNTED RETURN/SUPPLY GRILL

2X2 LAY-IN RETURN AIR GRILL.

EXHAUST LAY-IN GRILLE

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

SCAL

E

PROJ

ECT #

DESIG

NED

DRAW

N

CHEC

KED

DATE

NO.

SHEET

SEQ. OF

BAR

IS ON

E INC

H IN

LENG

TH O

N OR

IGINA

L DRA

WING

.CH

ECK S

CALE

AND

ADJU

ST AC

CORD

INGL

Y.

---

---

---

---

---

---

---

---

---

REVIS

ION

ISSUED FOR BID

ABILE

NE,

TXWE

ATHE

RFOR

D, TX

LUBB

OCK,

TX

TBPE

FIRM

# 2

448

TBAE

FIRM

# BR

226

1TB

PELS

FIRM

# 10

1944

93 -A

BILEN

ETB

PELS

FIRM

# 10

1945

90 -W

EATH

ERFO

RD

1/8" =

1'-0

"

1852

4

M0.1

BETT

Y HA

RDW

ICK

INTE

RIOR

REN

OVAT

ION

MEC

HANI

CAL

-ABB

REVI

ATIO

NS A

ND G

ENER

AL N

OTES

1A

DD

EN

DU

M #

110

-06-

2020

JSD

JSD

JSD

A - AIR (COMPRESSED)ABV - ABOVEA/C - AIR CONDITIONINGAC - ALTERNATING CURRENT,

AIR COMPRESSORACCH - AIR COOLED CHILLERACCU - AIR COOLED CONDENSING UNITAD - ACCESS DROP, AREA DRAINADJ - ADJUSTABLEAF - AIR FILTERAFC - ABOVE FINISHED CEILINGAFF - ABOVE FINISHED FLOORAFG - ABOVE FINISHED GRADEAHU - AIR HANDLING UNITAL - ALUMINIUMALT - ALTERNATEAMB - AMBIENTAP - ACCESS PANELAPD - AIR PRESSURE DROPAPPROX. - APPROXIMATEARI - AMERICAN REFRIGERATION INSTITUTEARCH - ACHITECT, ARCHITECTURALAS - AIR SEPARATORASHRAE - AMERICAN SOCIETY OF HEATING,

REFRIGERATING, AND AIR-CONDITIONINGENGINEERS

ASME - AMERICAN SOCIETY OF MECHANICALENGINEERS

ASTM - AMERICAN SOCIETY OF TESTING ANDMATERIALS

AV - ACID VENT, AIR VENTAVG - AVERAGEAW - ACID WASTEAWS - AMERICAN WELDING SOCIETYAUX - AUXILIARY

B - BOILERBC - BELOW COUNTERB/C - BACK OF CURBBFF - BELOW FINISHED FLOORBFV - BUTTERFLY VALVEBH - BOX HYDRANTBLDG - BUILDINGBM - BENCHMARKBOF - BOTTOM OF FOOTINGBOP - BOTTOM OF PIPEBOS - BOTTOM OF STRUCTUREBOT - BOTTOMBP - BACKFLOW PREVENTERBT - BATH TUB, BREAK TANKBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNITS PER HOURBV - BALL VALVE, BALANCING VALVEBWV - BACK WATER VALVE

C - CELCIUSCAB - CABINETCAV - CONSTANT AIR VOLUMECB - CATCH BASIN]CC - CAPPED CONNECTIONCD - CONDENSATE DRAINCFM - CUBIC FEET PER MINUTECFS - CUBIC FEET PER SECONDCH - CHILLERCHW - CHILLED WATERCHWP - CHILLED WATER PUMPCHWR - CHILLED WATER RETURNCHWS - CHILLED WATER SUPPLYCI - CAST IRONCIRC - CIRCULATINGCL - CENTERLINECLG - CEILINGCLR - CLEARCMP - CORRUGATED METAL PIPECMU - CONCRETE MASONRY UNITCPI - CAST IRON PIPE INSTITUTECPVC - CHLORINATED POLYVINYL CHLORIDECO - CLEAN OUTCOL - COLUMNCOMB - COMBINATIONCOMP - COMPRESSORCON - CONVERTERCONC - CONCRETE, CONCENTRICCOND - CONDENSER, CONDENSATECONN - CONNECTIONCONT - CONTINUOUS, CONTINUATIONCONTR - CONTROLLER, CONTRACTORCOP - COEFFICIENT OF PERFORMANCECRAC - COMPUTER ROOM AIR-CONDITIONING UNITCT - COOLING TOWERCTR - CENTERCU - COPPERCV - CHECK VALVECW - COLD WATERCWP - CONDENSER WATER PUMPCWR - CONDENSER WATER RETURNCWS - CONDENSER WATER SUPPLY

D - DEPTH, DRAIN, DRYERDB - DRY BULBDC - DOUBLE DUCT CONSTANT AIR VOLUME,

DIRECT CURRENTDDC - DIRECT DIGITAL CONTROLDESIG - DESIGNATIONDTL - DETAILDF - DRINKING FOUNTAINDFU - DRAINAGE FIXTURE UNITSDIA - DIAMETERDIFF - DIFFUSERDIM - DIMENSIONDISC - DISCONNECTDN - DOWNDPR - DAMPERDS - DOWNSPOUT, DOUBLE SUCTIONDV - DOUBLE DUCT VAVDW - DISHWASHERDWG - DRAWINGDWH - DOMESTIC WATER HEATERDWP - DOMESTIC WATER PUMPDX - DIRECT EXPANSION

EA - EACHEAT - ENTERING AIR TEMPERATUREEC - ELECTRICAL CONTRACTORECC - ECCENTRICEDB - ENTERING DRY BULBEDF - ELECTRIC DRINKING FOUNTAINEDH - ELECTRIC DUCT HEATEREF - EXHAUST FANEFF - EFFICIENCYEJ - EXPANSION JOINTEL - ELEVATIONELEC - ELECTRICALELEV - ELEVATOREMERG - EMERGENCYENCL - ENCLOSUREENGR - ENGINEEREQ - EQUALEQUIP - EQUIPMENTES - END SUCTION, EMERGENCY SHOWERESP - EXTERNAL STATIC PRESSUREET - EXPANSION TANKETR - EXISTING TO REMAINEVAP - EVAPORATOREWB - ENTERING WET BULBEWT - ENTERING WATER TEMPERATUREEX - EXPLOSION-PROOFEXH - EXHAUSTEXP - EXPANSIONEXT - EXTERNALEXIST - EXISTING

F - FAHRENHEIT, FIREFBO - FURNISHED BY OTHERSFC - FORWARD CURVEDFCO - FLOOR CLEAN OUTFCS - FLOOR CONTROL STATIONFCU - FAN COIL UNITFD - FLOOR DRAIN, FIRE DAMPERFDC - FIRE DEPARTMENT SIAMESE CONNECTIONFDV - FIRE DEPARTMENT VALVEFH - FIRE HYDRANTFHC - FIRE HOSE CABINETFHR - FIRE HOSE RACKFIN - FINISHEDFIXT - FIXTUREFLA - FULL LOAD AMPSFLEX - FLEXIBLEFL - FLOW LINESFLR - FLOORFM - FACTORY MUTUALFP - FIRE PUMPFPD - FLUID PRESSURE DROPFPI - FINS PER INCHFPM - FEET PER MINUTEFPS - FEET PER SECONDFPT - FAN POWERED TERMINAL UNITF&T - FLOAT AND THERMOSTATICFRZR - FREEZERFS - FLOW SWITCHFSD - FIRE SMOKE DAMPERFSK - FLOOR SINKFT - FOOT, FEETFTG - FOOTINGFU - FIXTURE UNITSFUT - FUTURE

G - GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGBD - GRAVITY BACKDRAFT DAMPERGC - GENERAL CONTRACTORGLV - GLOBE VALVEGND - GROUNDGPD - GALLONS PER DAYGPH - GALLONS PER HOURGPM - GALLONS PER MINUTEGV - GATE VALVE

HB - HOSE BIBBHD - HEAD, HUB DRAINHE - HEAT EXCHANGERHF - HUMIDIFIERHORIZ - HORIZONTALHP - HORSEPOWERHPU - HEAT PUMP UNITHKP - HOUSEKEEPING PADHSC - HORIZONTAL SPLIT CASEHSTAT - HUMIDISTATHT - HEIGHTHTG - HEATINGHTR - HEATERHW - HOT WATERHWC - HOT WATER CIRCULATORHWP - HOT WATER PUMPHWR - HOT WATER RETURNHWS - HOT WATER SUPPLYHZ - HERTZ

ID - INSIDE DIAMETERIE - INVERT ELEVATIONIH - INFRARED HEATERIN - INCHESINSUL - INSULATIONINT - INTERNAL, INTERIORINV - INVERTIW - INDIRECT WATER

JB - JUNCTION BOXJP - JOCKEY PUMP

KEC - KITCHEN EQUIPMENT CONTRACTORKO - KNOCKOUTKVA - KILOVOLT-AMPSKW - KILOWATT

L - LENGTH, LAVATORYLAT - LEAVING AIR TEMPERATURELAV - LAVATORYLB/HR - POUNDS PER HOURLF - LINEAR FEET

L - LENGTH, LAVATORYLAT - LEAVING AIR TEMPERATURELAV - LAVATORYLB/HR - POUNDS PER HOURLF - LINEAR FEETLP - LOW PRESSURELRA - LOCKED ROTOR AMPSLTG - LIGHTINGLVL - LEVELLWB - LEAVING WET BULBLWCO - LOW WATER CUT OFFLWT - LEAVING WATER TEMPERATURE

MAT - MIXED AIR TEMPERATUREMAX - MAXIMUMMBD - MANUAL BALANCING DAMPERMBH - THOUSANDS BTU'S PER HOURMBTUH - THOUSANDS BTU'S PER HOURMC - MECHANICAL CONTRACTORMCA - MINIMUM CIRCUIT AMPACITYMCC - MOTOR CONTROL CENTERMECH - MECHANICALMEP - MECHANICAL, ELECTRICAL, AND PLUMBINGMEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMI - MALLEABLE IRONMIN - MINIMUMMISC - MISCELLANEOUSMP - MEDIUM PRESSUREMS - MOP SINKMTD - MOUNTEDMU - MAKE-UPMVD - MANUAL VOLUME DAMPER

N.C. - NORMALLY CLOSEDNFPA - NATIONAL FIRE PROTECTION ASSOCIATIONNIC - NOT IN CONTRACTN.O. - NORMALLY OPENNO. - NUMBERNPS - NOMINAL PIPE SIZENPSH - NET POSITIVE SUCTION HEADNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE

OA - OUTSIDE AIROAF - OUTSIDE AIR FANOAHU - OUTSIDE AIR HANDLING UNITOBD - OPPOSED BLADE DAMPEROC - ON CENTEROD - OUTSIDE DAMPER, OVERFLOW DRAINOED - OPEN END DUCTOFCU - OUTSIDE AIR FAN COIL UNITOLP - OVERLOAD PROTECTIONOPG - OPENINGOS&Y - OPEN-STEM AND YOLKOV - OUTLET VELOCITY

P - PUMP, PLUMBING EQUIPMENTPC - PLUMBING CONTRACTORPCF - POUNDS PER CUBIC FOORPCR - PUMPED CONDENSATE RETURNPD - PRESSURE DROPPH - PHASE, POST HYDRANTPIV - POST INDICATOR VALVEPLBG - PLUMBINGPNEU - PNEUMATICPNL - PANELPOC - POINT OF CONNECTIONSPPH - POUNDS PER HOURPRV - PRESSURE RELIEF VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSIA - POUNDS PER SQUARE INCH ABSOLUTEPSIG - POUNDS PER SQUARE INCH GAUGEPVC - POLYVINYL CHLORIDE

QTY - QUANTITY

RA - RETURN AIRRAD - REFRIGERATED AIR DRYERRAF - RETURN AIR FANRAG - RETURN AIR GRILLERAT - RETURN AIR TEMPERATURERCP - REFLECTED CEILING PLAN,

REINFORCED CONCRETE PIPERD - ROOF DRAINRE - REFERENCE, REFERRECIRC - RECIRCULATERED - REDUCERREFR - REFRIGERATORREG - REGISTERREINF - REINFORCINGREQD - REQUIREDREV - REVISION, REVISERF - ROOFRH - RELATIVE HUMIDITYRHG - REFRIGERANT HOT GASRL - REFRIGERANT LIQUIDRLA - RUNNING LOAD AMPSRM - ROOM, REFRIGERATION MACHINERPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTIONRTU - ROOFTOP UNIT

SA - SUPPLY AIRSAF - SUPPLY AIR FANSAG - SUPPLY AIR GRILLESAN - SANITARY SEWERSAR - SUPPLY AIR REGISTERSC - STEAM CONDENSATESCHED - SCHEDULEDSD - STORM DRAINSE - SEWAGE EJECTORSEC - SECONDARYSECT - SECTIONSENS - SENSIBLESF - SQUARE FEETSFCS - SPRINKLER FLOOR CONTROL STATION

SH - SHOWERSHT - SHEETSIM - SIMILARSK - SINKSM - SHEETMETALSP - SUMP PUMP, STATIC PRESSURESPEC - SPECIFICATIONSPR - SPRINKLERSQ - SQUARESS - SERVICE SINKS/S - STAINLESS STEELSSSC - SOLID STATE SPEED CONTROLSTD - STANDARDSTL - STEELSTR - STRAINERSTRUCT - STRUCTURALSURF - SURFACESUSP - SUSPENDSV - SANITARY VENTSW - SOFT WATER

T&P - TEMPERATURE AND PRESSURETA - TRANSFER AIRTC - TEMPERATURE CONTROLTD - TRENCH DRAINTDH - TOTAL DYNAMIC HEADTEMP - TEMPERATURETF - TRANSFER FANTG - TRANSFER GRILLETH BLK - THRUST BLOCKTHERM - THERMOMETERTMV - THERMOSTATIC MIXING VALVETOB - TOP OF BEAMTOD - TOP OF DUCTTOP - TOP OF PIPETOS - TOP OF SLABTP - TRAP PRIMERTPD - TRAP PRIMER DEVICETSP - TOTAL STATIC PRESSURETSTAT - THERMOSTATTW - TEMPERED HOT WATERTWFU - TOTAL WATER FIXTURE UNITSTYP - TYPICAL

U - URINALUCD - UNDER CUT DOORUG - UNDERGROUNDUH - UNIT HEATERUL - UNDERWRITERS LABORATORIES, INC.UNO - UNLESS NOTED OTHERWISEU/F - UNDER FLOORU/S - UNDER SLAB

V - VOLT, VENTVA - VOLT-AMPERE, VALVEVAC - VACUUMVAV - VARIABLE AIR VOLUMEVB - VALVE IN BOXVEL - VELOCITYVOV - VALVE ON VERTICALVP - VACUUM PUMP, VELOCITY PRESSUREVR - VARIABLE AIR VOLUME REHEATVRF - VARIABLE REFRIGERANT FLOWVRV - VARIABLE REFRIGERANT VOLUMEVTR - VENT THRU ROOF

W - WATT, WASTE, WIDTH, WASHERW/ - WITHW/O - WITHOUTWB - WET BULBWC - WATER CLOSET, WATER COLUMNWCO - WALL CLEANOUTWG - WATER GAUGEWF - WASH FOUNTAINWH - WALL HYDRANT, WATER HEATERWM - WATER METERWP - WEATHERPROOFWPD - WATER PRESSURE DROPWWF - WELDED WIRE FABRICWSFU - WATER SUPPLY FIXTURE UNITSWT - WATERTIGHT, WEIGHT

YH - YARD HYDRANTYCO - YARD CLEANOUT

Z - ZONE

MECHANICAL AND PLUMBING ABBREVIATIONS NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS SHOWN HERE ARE USED IN THE DRAWINGS AND MAY NOT APPLY TO THIS PROJECT.

A. LOCATIONS, SIZES, CONSTRUCTION, AND ORIENTATION OF THE MECHANICAL EQUIPMENT AND SYSTEMS SHOWN IN THESE DRAWINGS WAS OBTAINED FROM PREVIOUS DESIGN DOCUMENTS AND FIELD OBSERVATIONS. ACTUAL FIELD

CONDITIONS MAY VARY. MECHANICAL CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH THE ACTUAL FIELD CONDITIONS PRIOR TO ORDERING, FABRICATING, OR SELECTION MECHANICAL EQUIPMENT OR MATERIALS. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY OF SIGNIFICANT DEVIATION FROM PLANS.

B. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES.

C. PIPING AND DUCTWORK ON DRAWINGS ARE SCHEMATIC ONLY. COORDINATE WITH OTHER TRADES FOR PIPING AND DUCTWORK ROUTING. OFFSET AND RUN PIPING/DUCTWORK INSIDE THE STRUCTURE IF REQUIRED. PROVIDE ALL NECESSARY PIPING, DUCTWORK, FITTINGS, INSULATION, AND OTHER ACCESSORIES.

D. CONTRACTOR SHALL COORDINATE WITH STRUCTURAL CONDITIONS AT THE SITE AND PROVIDE ALL CLEARANCES AS REQUIRED.

E. COORDINATE LOCATIONS OF FLOOR AND WALL OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER.

F. MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR PRIOR TO ACTUAL INSTALLATION OF TEMPERATURE SENSORS, THERMOSTATS, CO2 SENSORS, AND SMOKE DETECTORS.

G. LOCATE ALL THERMOSTATS A MINIMUM OF SIX INCHES FROM WALL CORNERS, DOOR FRAMES, AND OTHER DEVICES. MOUNT THERMOSTATS AT 48" AFF. COORDINATE THE EXACT LOCATION OF ALL THERMOSTATS WITH OWNER AND ARCHITECT PRIOR TO INSTALLATION.

H. COORDINATE THE EXACT HEIGHTS OF ALL SIDEWALL GRILLES WITH ARCHITECT AT JOBSITE.

I. COORDINATE ALL FLOOR AND ROOF PENETRATIONS WITH STRUCTURAL DRAWINGS.

J. RECTANGULAR AND RIGID ROUND SUPPLY DUCTS TO BE PAINT-LOCK GALVANIZED STEEL WITH INTERIOR LINED INSULATION. MOUNT DIRECTLY BELOW BAR JOISTS USING PRE-MANUFACTURED DUCT HANGERS.

K. RETURN AIR DUCT SHALL BE LINED PAINT-LOCK GALVANIZED STEEL RECTANGULAR DUCT. MOUNT DIRECTLY BELOW BAR JOISTS USING PRE-MANUFACTURED DUCT HANGERS.

L. MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.

M. ALL ELBOWS IN RECTANGULAR SUPPLY DUCT TO HAVE TURNING VANES.

N. CONTROL WIRING TO BE RUN INSIDE WALLS OR IN CONDUIT.

O. ALL PIPING, WIRING, AND DUCTWORK TO BE CONCEALED ABOVE CEILINGS OR WALLS.

P. DUCT SIZES SHOWN ON DRAWINGS ARE FINAL SIZES AFTER LINER, IF ANY, IS INSTALLED.

Q. FILTERS SHALL BE 2" THICK MERV 8, UNLESS OTHERWISE NOTED, PROVIDE NEW.

R. INDEPENDENT MECHANICAL CONTRACTOR TO BALANCE ALL DIFFUSERS TO CFM SHOWN ON PLANS, PER SPEC 23 05 93..

S. ALL DUCT SHALL BE CONSTRUCTED PER SMACNA CONSTRUCTION STANDARDS.

T. RTU'S SHALL BE A MINIMUM OF 10'-0" FROM THE ROOF EDGE.

U. PROVIDE INSULATION FOR ALL PIPING AND DUCTWORK PER THE LATEST EDITION OF THE INTERNATIONAL ENERGY CONSERVATION CODE AS SPECIFIED.

V. FASTEN AND SEAL ALL DUCTWORK JOINTS, LONGITUDINAL AND TRAVERSE SEAMS AND CONNECTIONS PER ASHRAE 90.1 SECTION 6.4.4.2.1. DUCT SEALANT SHALL BE INSPECTED PRIOR TO DUCTWORK BEING INSULATED.

W. COORDINATE EXACT LOCATION OF ALL AIR DEVICES WITH ARCHITECT PRIOR TO INSTALLATION.

X. PROVIDE SPIN-IN CONNECTION FOR ALL ROUND DUCTWORK CONNECTED TO RECTANGULAR DUCT.

Y. EXACT LOCATIONS OF MECHANICAL UNITS, GRILLES, AND DAMPERS SHALL BE FIELD COORDINATED WITH OTHER TRADES TO AVOID CONFLICTS AND ALLOW ADEQUATE CLEARANCES.

Z. EQUIPMENT SIZES, DIMENSIONS, AND REQUIRED CONNECTIONS SHALL BE VERIFIED WITH THE MANUFACTURER DRAWINGS AND CUT SHEETS BEFORE FABRICATING OF DUCTWORK, PIPING, OR POURING OF CONCRETE HOUSEKEEPING PADS.

AA. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF ALL OUTSIDE AIR INTAKES TO MAINTAIN 10 FEET DISTANCE BETWEEN OUTSIDE AIR INTAKES AND ANY EXHAUST AIR OUTLET, FLUES, OR PLUMBING VENTS.

BB. MECHANICAL CONTRACTOR SHALL COORDINATE WITH PLUMBING CONTRACTOR FOR ALL CONDENSATE DRAIN PIPES.

CC. VENTILATION REQUIREMENTS DUE TO THE RENOVATION REMAINS UNCHANGED. RTUs SHALL MAINTAIN THE SAME VENTILATION AS PRIOR TO THE RENOVATION.REPORT TO ENGINEER MINIMUM EXISTING VENTILATION SETTINGS. RESET AS ENGINEER DETERMINES.

MECHANICAL GENERAL NOTES MECHANICAL LEGEND

1

1

1

10/06/2020

150 CFMS-3 / 48"L

210 CFMS-3 / 10x6

210 CFM S-1 / 8"

75 CFM S-3 / 10"x6"

300 CFM S-3 /12X8

260 CFM S-3 /10X8

280 CFM S-3 /10X8

100 CFM S-3 /10x4

70 CFM S-3 /10x4

200 CFM S-3 /10X8

135 CFM S-3 /10x8

135 CFM S-3 /10x8

120 CFMS-3 / 10X6

120 CFMS-3 / 10X6

120 CFMS-3 / 10X6

75 CFMS-3 / 10X4

50 CFM S-3 / 10X4

75 CFM S-3 / 10X4

185 CFMS-3 / 10X8

215 CFMS-3 / 10X8

75 CFM S-3 / 10X4

100 CFM S-3 / 10X6

75 CFM S-3 / 10"x4"

160 CFM S-3 / 10X6

240 CFM S-3 / 10X8

220 CFM S-3 / 10X8

100 CFM S-3 /10x4 100 CFM

S-3 /10x4

100 CFM S-3 /10x4

70 CFM S-3 /10x4

180 CFM S-3 / 10X6

150 CFM S-3 / 10X6+

120 CFM S-3 / 10X6

175 CFM S-3 / 10X6

140 CFM S-3 / 10X6

140 CFM S-3 /10X6

115 CFM S-3 /10x6

185 CFM S-3 /10x8

185 CFM S-3 /10x8

185 CFM S-3 /10x8

115 CFM S-3 /10x6

130 CFM S-1 / 8

75 CFM S-3 / 10X4

115 CFM S-3 /10x6

115 CFM S-3 /10x6

115 CFM S-3 /10x6

115 CFM S-3 /10x6

80 CFM S-3 / 10X4

250 CFM S-3 / 10"x8"

230 CFMS-3 / 10X8

200 CFMS-3 / 10x8

RTU-10

RTU-9

RTU-14

RTU-12

RTU-13

RTU-11

10"x

10"

20"x10"

12"x

6"

12"x

6"

24"x

12"

26"x

12"

18"x10"

10"x

6"

14"x

10"

14"x

10"

24"x

12"

18"x

10"

24"x

10"

10"x

8"

10"x

8"1

0"x

8"

10"x

8"

14"x

10"

10"x

10"

16"x

10"

145

TEAM LEADER OFFICE

146

MEETING / CLINIC

144

NURSES OFFICE

143

COMMON SPACE

147

BREAK ROOM

148

WORK ROOM

143

COMMON SPACE

155

OFFICE 156

OFFICE

157

OFFICE

154

FLEX SPACE

158

MEETING

141

CORRIDOR

150

STORAGE

149

UNISEX

151

ATRIUM

140

CRT

138

COMMON SPACE

136

OFFICE

137

UNISEX

139

OFFICE

134

COMMON SPACE

135

INTAKE OFFICE

131

INTAKE OFFICE

130

INTAKE OFFICE

129

INTAKE OFFICE

127

JAN.

104A

RECEPTION STORAGE

105

MEN

105

MEN

126

CORRIDOR

123

TREATMENT ROOM

122

TREATMENT ROOM121

TREATMENT ROOM

120

TREATMENT ROOM

119

TREATMENT ROOM

113

NURSES STATION

116

TREATMENT ROOM

110

PAP OFFICE

109

NP OFFICE

108

DR. OFFICE

107

RN MANAGER OFFICE

112

CORRIDOR

102

WOMEN

102

WOMEN

124

UNISEX

151

ATRIUM

1

1

1

1

1

1

2

EF-170 CFM

EF-170 CFM

EF-2200 CFM

EF-2ON ROOF

2

EF-170 CFM

2

2EF-170 CFM

EF-2200 CFM

EF-2ON ROOF

8"ø

130 CFM

S-1

3

3

3

3

3

3

180 CFMS-3 / 10X6

R-3

R-3

R-3

R-3

R-3

R-3

R-3

R-3R-3

R4 / 24"X12"

R4 / 24"X12"

R-3

R-3

R4 / 24"X12"

160 CFM S-3 / 10"X6"

50 CFM S-3 /10X4

100 CFM S-3 / 10X6

10"x

10"

20"x10"

12"x

10"

16"x10"

22"x10"

22"x10"

22"x10"

20"x

10"

R-3

R-3

R-3 R-3

R-3

R-3 R-3 R-3 R-3 R-3

R-3

R-3

R-3

R-3

R-3

R-3

R-3

R-3

R-3

10"x10"

250 CFMS-3 / 10X8

240 CFM S-3 / 10X8

240 CFM S-3 / 10X8

200 CFM S-3 / 10X8

210 CFMS-3 / 10X8

100 CFMS-3 / 10X4

115 CFM S-3 /10x6

280 CFM S-3 /10X8

280 CFM S-3 /10X8

350 CFM S-3 /12X8

100 CFM S-3 /10x4

4

4

R4 / 24"X12"

R4 / 12"X12"

26"x12"

26"x12"

R4 / 10"X10"

R4 / 10"X6"

70 CFM S-3 / 10X4

10"x

10"

R-1

R-1

16"x10" 24"x10"

26"x

10"

R-5R-5

R-5

R-5

R-5 R-5

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

SCAL

E

PROJ

ECT #

DESIG

NED

DRAW

N

CHEC

KED

DATE

NO.

SHEET

SEQ. OF

BAR

IS ON

E INC

H IN

LENG

TH O

N OR

IGINA

L DRA

WING

.CH

ECK S

CALE

AND

ADJU

ST AC

CORD

INGL

Y.

---

---

---

---

---

---

---

---

---

REVIS

ION

ISSUED FOR BID

ABILE

NE,

TXWE

ATHE

RFOR

D, TX

LUBB

OCK,

TX

TBPE

FIRM

# 2

448

TBAE

FIRM

# BR

226

1TB

PELS

FIRM

# 10

1944

93 -A

BILEN

ETB

PELS

FIRM

# 10

1945

90 -W

EATH

ERFO

RD

1/8" =

1'-0

"

1852

4

M1.0

BETT

Y HA

RDW

ICK

INTE

RIOR

REN

OVAT

ION

MEC

HANI

CAL-

FIRST

FLOO

R PL

AN

1A

DD

EN

DU

M #

110

-06-

2020

Desig

ner

Auth

or

Chec

ker

X KEYED NOTES

A. LOCATIONS, SIZES, CONSTRUCTION, AND ORIENTATION OF THE MECHANICAL EQUIPMENT AND SYSTEMS SHOWN IN THESE DRAWINGS WAS OBTAINED FROM PREVIOUS DESIGN DOCUMENTS AND FIELD OBSERVATIONS. ACTUAL FIELD CONDITIONS MAY VARY. MECHANICAL CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH THE ACTUAL FIELD CONDITIONS PRIOR TO ORDERING, FABRICATING, OR SELECTION MECHANICAL EQUIPMENT OR MATERIALS. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY OF SIGNIFICANT DEVIATION FROM PLANS.

B. CONTRACTOR IS WARNED ABOUT SCALING DIRECTLY FROM THE MECHANICAL DRAWINGS. PIPING AND DUCTWORK ON DRAWINGS ARE SCHEMATIC ONLY. COORDINATE WITH OTHER TRADES FOR PIPING AND DUCTWORK ROUTING. OFFSET AND RUN PIPING/DUCTWORK INSIDE THE STRUCTURE IF REQUIRED. PROVIDE ALL NECESSARY PIPING, DUCTWORK, FITTINGS, INSULATION, AND OTHER ACCESSORIES.

C. FIELD VERIFY EXACT LOCATION OF EXISTING CHASES AND VERTICAL DUCTWORK. NEW HORIZONTAL DUCTWORK TO CONNECT TO EXISTING VERTICAL DUCTWORK.

D. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES.

E. CONTRACTOR SHALL COORDINATE WITH STRUCTURAL CONDITIONS AT THE SITE AND PROVIDE ALL CLEARANCES AS REQUIRED.

F. COORDINATE LOCATIONS OF FLOOR AND WALL OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER.

G. DEMO ALL UNUSED DUCTWORKING ABOVE CEILING BACK TO MAIN.

H. REFERENCE ARCHITECTURAL PLANS, A2.1 & A2.2, FOR DEMOLITION REQUIREMENTS.

I. BALANCING DAMPERS SHALL BE INSTALLED PER DETAIL DUCT TAKE OFF AND ELBOWS. DIFFUSERS SHALL HAVE AN ADJUSTABLE DAMPER AT EACH DIFFUSER LOCATION.

J. RETURN AIR GRILLES SHALL BE INSTALLED 6" FROM THE BOTTOM OF THE CEILING OR THE JOISTS.

GENERAL NOTES

FIRST FLOOR MECHANICAL PLAN

1EXISTING ROOFTOP UNIT (RTU) TO REMAIN AND BE RE-USED. CONTRACTOR TO FIELD VERIFYEXACT LOCATION OF ANY EXISTING DUCTWORK TO REMAIN AND BE RE-USED. CONTRACTOR TORE-USE EXISTING VERTICAL MAIN DUCTS BETWEEN RTU AND FIRST FLOOR TO MAXIMUM EXTENT POSSIBLE. CONNECT NEW DUCT TO EXISTING VERTICAL MAIN DUCTS. IF EXISTING SMOKE DETECTORS ARE NOT INPLACE, CONTRACT SHALL INSTALL DETECTORS ON SUPPLY AND RETURN DUCT WORK PER 2012 IMC.

2NEW CEILING MOUNTED EXHAUST FAN AS SCHEDULED. ROUTE 6" ROUND DUCT UP THROUGH CHASE TO ROOF. GOOSENECK DUCT ON ROOF WITH BIRDSCREEN. PROVIDE 5-MINUTE TIME DELAY WALL SWITCH.

3 PROVIDE A RETURN GRILLE (R-2) ON THE RTU RETURN DUCT. SEE ROOFTOP UNIT RETURN DETAIL (SEE SHEET M3.0)

4 NEW ROOF MOUNTED EXHAUST FAN AS SCHEDULED. ROUTE 10" X 8" DUCT UP TO ROOF . PROVIDE OCCUPANCY SENSORTO CONTROL OPERATIONOF THE EXHAUST FAN.

E-1

E-1

110/06/2020

RTU-1

RTU-9 RTU-3

RTU-2

RTU-13

RTU-12

RTU-14RTU-8

RTU-10

RTU-4

RTU-5RTU-11

RTU-6 RTU-7

EF-2

EF-1

EF-1

EF-1

EF-1

2

1

21

1

1

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

SCAL

E

PROJ

ECT #

DESIG

NED

DRAW

N

CHEC

KED

DATE

NO.

SHEET

SEQ. OF

BAR

IS ON

E INC

H IN

LENG

TH O

N OR

IGINA

L DRA

WING

.CH

ECK S

CALE

AND

ADJU

ST AC

CORD

INGL

Y.

---

---

---

---

---

---

---

---

---

REVIS

ION

ISSUED FOR BID

ABILE

NE,

TXWE

ATHE

RFOR

D, TX

LUBB

OCK,

TX

TBPE

FIRM

# 2

448

TBAE

FIRM

# BR

226

1TB

PELS

FIRM

# 10

1944

93 -A

BILEN

ETB

PELS

FIRM

# 10

1945

90 -W

EATH

ERFO

RD

1/8" =

1'-0

"

1852

4

M2.0

BETT

Y HA

RDW

ICK

INTE

RIOR

REN

OVAT

ION

MEC

HANI

CAL -

ROOF

PLA

N

1A

DD

EN

DU

M #

110

-06-

2020

Desig

ner

Auth

or

Chec

ker

MECHANICAL ROOF PLAN

X KEYED NOTES

GENERAL NOTES

EF-2

NEW CEILING MOUNTED EXHAUST FAN AS SCHEDULED.

NEW ROOF MOUNTED EXHAUST FAN AS SCHEDULED.

1

2

A. LOCATIONS, SIZES, CONSTRUCTION, AND ORIENTATION OF THE MECHANICAL EQUIPMENT AND SYSTEMS SHOWN IN THESE DRAWINGS WAS OBTAINED FROM PREVIOUS DESIGN DOCUMENTS AND FIELD OBSERVATIONS. ACTUAL FIELD CONDITIONS MAY VARY. MECHANICAL CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH THE ACTUAL FIELD CONDITIONS PRIOR TO ORDERING, FABRICATING, OR SELECTION MECHANICAL EQUIPMENT OR MATERIALS. NOTIFY ARCHITECT/ENGINEER IMMEDIATELY OF SIGNIFICANT DEVIATION FROM PLANS.

B. CONTRACTOR IS WARNED ABOUT SCALING DIRECTLY FROM THE MECHANICAL DRAWINGS. PIPING AND DUCTWORK ON DRAWINGS ARE SCHEMATIC ONLY. COORDINATE WITH OTHER TRADES FOR PIPING AND DUCTWORK ROUTING. OFFSET AND RUN PIPING/DUCTWORK INSIDE THE STRUCTURE IF REQUIRED. PROVIDE ALL NECESSARY PIPING, DUCTWORK, FITTINGS, INSULATION, AND OTHER ACCESSORIES.

C. FIELD VERIFY EXACT LOCATION OF EXISTING CHASES AND VERTICAL DUCTWORK. NEW HORIZONTAL DUCTWORK TO CONNECT TO EXISTING VERTICAL DUCTWORK.

D. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES.

E. CONTRACTOR SHALL COORDINATE WITH STRUCTURAL CONDITIONS AT THE SITE AND PROVIDE ALL CLEARANCES AS REQUIRED.

F. COORDINATE LOCATIONS OF FLOOR AND WALL OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER.

G. DEMO ALL UNUSED DUCTWORKING ABOVE CEILING BACK TO MAIN.

H. REFERENCE ARCHITECTURAL PLANS, A2.1 & A2.2, FOR DEMOLITION REQUIREMENTS.

I. BALANCING DAMPERS SHALL BE INSTALLED PER DETAIL DUCT TAKEOFF AND ELBOWS. DIFFUSERS SHALL HAVE AN ADJUSTABLE DAMPER AT EACH DIFFUSER LOCATION.

J. RETURN AIR GRILLES SHALL BE INSTALLED 6" FROM THE BOTTOM OF THE CEILING OR THE JOISTS.

1

10/06/2020

AIR DEVICE SCHEDULE

MARK SERVICE TYPE

S-1 SUPPLY

MATERIAL

STEEL

FINISH

PER ARCHITECT

MFG & MODEL

TITUS - TMSA

FRAME

LAY-INCEILING

SIZE/PATTERN

4-WAY

TITUS - 300RLPER ARCHITECTSURFACE MOUNTSIDE WALLSUPPLYS-3

E-1 EXHAUST CEILING LAY-IN

SIZE

PER PLANS STEEL

STEEL PER ARCHITECT TITUS - PAR

EXHAUST FAN SCHEDULE

MARK CFM TYPE

EF-1

200EF-2

70 CEILING

MFG & MODEL

GREENHECK G-070-VG

ELECTRICAL

120V/1PHROOF MOUNTED

MOTOR

1/6 HP

45.1 W120V/1PH GREENHECK SP-B070

R-2 RETURN DUCT MOUNTED SURFACE VERIFY

DUCT SIZESTEEL PER ARCHITECT TITUS - 350RL

R-3

R-4

RETURN WALL MOUNTED SURFACE 6" X 14" STEEL PER ARCHITECT POTTORF MODEL Z 4-14

RETURN WALL MOUNTED SURFACE STEEL PER ARCHITECT TITUS - 350RL-NC20SIZE

PER PLANS

R-1 RETURN WALL MOUNTED SURFACE STEEL PER ARCHITECT TITUS - 350RLSIZE

PER PLANS

R-5 RETURN WALL MOUNTED SURFACE STEEL PER ARCHITECT10" X 14" POTTORF MODEL U 7-14

24" X 24"

24" X 24"

NOTES

2,5

1,2,5

5

5

3,5,6

4,5

3,5

3,5,6

NOTES:

1. DIFFUSER SAME SIZE AS DUCT.

2. PROVIDE WITH OPPOSED BLADE DAMPER.

3. LOCATE HIGHER GRILLE 6" BELOW CEILING OR BAR JOIST, WITH HIGHER GRILLE IN COMMON SPACE/AREA.

4. TWO R-4 GRILLES ARE REQUIRED AT EACH LOCATION. PROVIDE GALVANIZED METAL SLEEVE THROUGH WALL. INSTALL TOP 6" BELOW CEILING OR BAR JOIST.

5. SHOP DRAWING SUBMITTALS REQUIRED FOR ALL AIR DEVICES SHOWN IN THE SCHEDULE.

6. TWO R-2 GRILLES ARE REQUIRED AT EACH LOCATION..

EXHAUST FAN MOUNTING DETAILNO SCALE

EXHAUST FAN

BACKDRAFT DAMPER

SEE ARCHITECTURALDRAWINGS FOR

FLASHING DETAILS

EXHAUST DUCTREFER TO PLAN FOR SIZE

SCREWS (MIN 2 EACH SIDE)STAINLESS STEEL MOUNTING

ROOF

FACTORY FABRICATEDCURB SECURED TO ROOF

ROOFTOP UNIT RETURN DETAILNOT TO SCALE

RTU RETURN DUCT UP THRU SECOND FLOOR CHASE TO RTU.

RETURN GRILLE (R-2) 20" X 10".

2ND FLOOR ABOVE

CAP BOTTOM OF DUCT AND INSTALL

FLUSH WITH JOISTS.

EXISTING JOIST

HOLE SIZE

(SEE BELOW-TYP.)

DUCT TAKEOFFS AND ELBOWS DETAILNO SCALE

VOLUME DAMPER

WITH BEARINGS

VOLUME DAMPER

WITH BEARINGSVOLUME DAMPER

WITH BEARINGS

NOTE:

ALTERNATE FITTINGS SHALL BE USED WHEN

DUCT HEIGHTS DOES NOT PERMIT THE USE

OF THE PREFERRED FULL SIZE BELLMOUTH

VOLUME DAMPER

WITH BEARINGS

PREFERRED

TAKE-OFF DETAIL

ALTERNATE

TAKE-OFF DETAIL

ALTERNATE

TAKE-OFF DETAIL

STANDARD

RECTANGULAR

CONNECTION

(ONLY WHEN

OTHERS DO

NOT FIT)

DUCT SIZE

(SEE PLANS)

MAIN DUCT

AIR FLOW

STANDARD 90° RECTANGULAR TO

ROUND BOOT CONNECTION

"BUCKLEY" MODEL 33000

(CONTINUOUSLY WELDED)

MINI-BELLMOUTH

CONNECTION SIMILAR TO

"BUCKLEY" MODEL MBMD

(SEAMLESS)

BELLMOUTH CONNECTION

SIMILAR TO "BUCKLEY"

MODEL BMD (SEAMLESS)

THIS DETAIL APPLIES TO SINGLE TAKEOFFS

TO DIFFUSER AS WELL AS BRANCH

TAKEOFFS. IT ALSO APPLIES TO TAKEOFFS IN

THE HORIZONTAL AS WELL AS VERTICAL

DIRECTION.

90 DEGREE VANED ELBOWS TO

BE CONSTRUCTED

AND INSTALLED AS

DETAILED BY

SMACNA

RECTANGULAR DUCT

TAKE-OFF DETAIL

BUCKLEY AIR-TITE BELLMOUTH TAKE-OFF WITH DAMPER, MODEL

#RBMD

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

S

SAXEF TOTE

AT

P

RE

ENIGNELNOISSEF

OR

A

L DESNECI

137667

LANCE W. LINDLEY

SCAL

E

PROJ

ECT #

DESIG

NED

DRAW

N

CHEC

KED

DATE

NO.

SHEET

SEQ. OF

BAR

IS ON

E INC

H IN

LENG

TH O

N OR

IGINA

L DRA

WING

.CH

ECK S

CALE

AND

ADJU

ST AC

CORD

INGL

Y.

---

---

---

---

---

---

---

---

---

REVIS

ION

ISSUED FOR BID

ABILE

NE,

TXWE

ATHE

RFOR

D, TX

LUBB

OCK,

TX

TBPE

FIRM

# 2

448

TBAE

FIRM

# BR

226

1TB

PELS

FIRM

# 10

1944

93 -A

BILEN

ETB

PELS

FIRM

# 10

1945

90 -W

EATH

ERFO

RD

1/8" =

1'-0

"

1852

4

M3.0

BETT

Y HA

RDW

ICK

INTE

RIOR

REN

OVAT

ION

MEC

HANI

CAL-

SCH

EDUL

ES A

ND D

ETAI

LS

1A

DD

EN

DU

M #

110

-06-

2020

Desig

ner

Auth

or

Chec

ker

EXISTING RTU SCHEDULE

Mark Manufacturer Model # Tons Voltage Phase MCA MOCP

RTU-1 Rheem RKKA-A060CK10E 5 208/240 V 3 PH 30 A 45 A

RTU-2 Rheem RKNL-A048CK10E 5 208/240 V 3 PH 23 A 35 A

RTU-3 Rheem RKNL-A060CK10E 5 208/240 V 3 PH 30 A 40 A

RTU-4 Rheem RKKA-A060CK13E 5 208/240 V 3 PH 30 A 45 A

RTU-5 Rheem RKKA-A048CK10E 4 208/240 V 3 PH 24 A 35 A

RTU-6 Rheem RKKA-A060CK10E 5 208/240 V 3 PH 30 A 45 A

RTU-7 Rheem RKNL-A060CK10E 5 208/240 V 3 PH 30 A 40 A

RTU-8 Rheem RKNL-A048CK10E 4 208/240 V 3 PH 23 A 35 A

RTU-9 Rheem RKKA-A060CK10E 5 208/240 V 3 PH 30 A 45 A

RTU-10 Rheem RKNN-A048CK10E 4 208/240 V 3 PH 22 A 35 A

RTU-11 Rheem RKKA-A060CK10E 5 208/240 V 3 PH 30 A 45 A

RTU-12 Rheem RKNL-A060CK10E 5 208/240 V 3 PH 30 A 40 A

RTU-13 Rheem RKNN-A060CK10E 5 208/240 V 3 PH 27 A 40 A

RTU-14 Rheem RKNL-A060CK10E 5 208/240 V 3 PH 30 A 40 A

NOTE:

1. PROVIDE NEW PROGRAMMABLE WIFI-ENABLED THERMOSTATS THAT ARE COMPATIBLE WITH EXISTING RTU'S.

1

1

1