ADDENDUM NO. 1 - OUTLINE AND SUMMARY INFORMATION
Project Name: Renne Library Testing Center Expansion PPA No.: 18-0089
Location: Bozeman, Montana Date: 2/26/2019
To: All Plan Holders of Record
The Plans and Specification prepared by Hip and Humble Architecture dated February 15, 2019, shall be clarified and
added as follow. The bidder proposes to perform all the following clarifications or changes. It is understood that the Base
Bid shall include any modification of Work or Additional Work that may be required by reason of the following change or
clarifications.
The Bidders are to acknowledge the receipt of this Addendum by inserting its number and date into their Bid
Forms. Failure to acknowledge may subject the Bidder to disqualification and rejection of the bid. This
Addendum forms part of the Contract Documents as if bound therein and modifies them as follows:
I. AMENDMENTS TO THE DRAWINGS
A. Please replace the mechanical and electrical drawing sheets with the attached sheets.
II. ATTACHMENTS
A. Drawings M1-1, M2-1, M3-1, E1-2, E1-1, E2-1, E3-1, E4-1.
END OF THE ADDENDUM NO. 1
RAISE DUCTWORK TO APPROXIMATELY 94" AFF. CURRENTLY AT APPROXIMATELY 82".
RELOCATE TEMPERATURE SENSOR. SEE M2.1 FOR NEW LOCATION.
REMOVE EXISTING DUCTWORK AND COMPONENTS AS INDICATED (DARK-DASHED).
KEYED NOTES:
GENERAL NOTES:
1. MINIMUM DRAIN PIPE SIZE = 3/4"
2. REFRIGERANT PIPE SIZES TO BE DETERMINED BY MULTI-SPLIT SYSTEM
MANUFACTURER.
1
2
3
ETS TESTING
ROOM
019F
STORAGE
019G
ADA TESTING
ROOM
019I
DIRECTOR'S
OFFICE
019H
SPECIAL
ACCOMODATIONS
019E
EXIST. WAITING
AREA
019
EXIST. P-VUE
TESTING ROOM
019A
EXIST. PROCTOR
OFFICE
019B
CHECK-IN OFFICE
019C
AC
7
8Ø8Ø
8Ø8Ø
8Ø8Ø
AC
5
6Ø6Ø
8Ø8Ø
T
T
D
D
T
T
8Ø8Ø
8Ø8Ø
RG
RL
6Ø6Ø
8x8
6Ø6Ø
24x14
24x14
8x88x8
4Ø
RG
RL
1
14X10
8Ø
8Ø
EXSITING
BRANCH PROVIDER BOX
RG
RL
RG
RL
4Ø
6Ø
D
M
M
(E) COND. DRAIN
TO SINK
UP
DN
DN
9x8
9x8
9x89x8
12x1212x12
14x10
8Ø8Ø
12Ø12Ø
TT
9x8
9x8
14Ø
14Ø
14Ø14Ø
14X10
14x10
CND
AC UNIT
8Ø
8Ø8Ø
12x1212x12
12x12
12x12
1
4
x
1
0
1
4
x
1
0
14x10
12Ø
12Ø
6Ø6Ø
6Ø6Ø
4Ø4Ø
9x8
9x8
12x8
12x8
REMOVE EXISTING
DUCTORK
REMOVE EXISTING DUCTWORK
EXISTING EXHAUST LOUVER
EXISTING INTAKE LOUVER
AC
6
12x12
32
RELOCATE EXISTING
DUCT HEATER EDC-1
AND CONTROLS
(E)
(E)
(E)
M1-1
MECHANICALDEMOLITION
1/4" = 1'-0"M1-1
1MECHANICAL - DEMOLITION
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089
RELOCATED FREEZE PROTECTION TEMPERATURE SENSOR.
BOTTOM OF DUCT MINIMUM 94" AFF
CONNECT NEW DUCT TO EXISTING LOUVER.
MAINTAIN CLEARANCE FOR EXHAUST FAN MAINTENANCE.
BRANCH PROVIDER (BP-2). INSTALL PER MANUFACTURERS INSTRUCTIONS. MUST COMPLY
WITH REQUIRED MAXIMUM DISTANCES FROM EQUIPMENT AS INDICATED ON SUBMITTAL.
DIGITAL DUCT TEMPERATURE SENSOR. INTERLOCK WITH HRV-2 TO SHUTDOWN IF TEMP IS
BELOW 40F. SEE SPECIFICATIONS FOR DETAILS.
PROVIDE MOTORIZED DAMPERS WITH DUCT ACCESS DOORS - ON INLET AND EXHAUST OF
EACH HRV. CONTRACTOR MAY REUSE EXISTING ACTUATORS FOR HRV-1.
EXTEND 14X14 DUCT THROUGH EXISTING EXTERIOR WALL OPENING TO HOOD. PROVIDE
20"W X 14"H X 12"D WALL HOOD WITH BIRDSCREEN.
REFRIGERATION PIPING. 1/4" REFR. LIQUID, 1/2" REFR. GAS, INSTALL PER
MANUFACTURERS INSTRUCTIONS.
MAINTAIN SERVICE CLEARANCE AREAS. INSTALL PER MANUFACTURERS WRITTEN
SERVICE CLEARANCE RECOMENDATIONS.
MAINTAIN 2' SERVICE CLEARANCE IN FRONT OF EQUIPMENT.
KEYED NOTES:
GENERAL NOTES:
BALANCE ALL DEVICES TO AIRFLOW INDICATED.
1
2
1.)
3
4
5
7
8
6
9
10
11
AC
7
AC
5
D
D
RG
EXISTING
BRANCH PROVIDER BOX
RG
RL
4Ø
UP
UP
DN
8Ø8Ø
D
D
RG
RL
RG
RL
RG
RL
RG
RL
4Ø
D
(E) COND. DRAIN
UP
UP
DN
9x8
9x8
14x10
14Ø
14Ø
CND
AC UNIT
9x8
9x8
9x8
1
T
2
AC
5
AC
6
10x10
AC
8
EXISTING
HRV-1
ABOVE
EG-E
375
10x10
RG-1
130
10
x6
10
x6
RG-2
100
RG-2
100
RG-2
100
SD-1
195
ETS TESTING
ROOM
019F
STORAGE
019G
ADA TESTING
ROOM
019I
DIRECTOR'S
OFFICE
019H
SPECIAL
ACCOMODATIONS
019E
EXIST. WAITING
AREA
019
EXIST. P-VUE
TESTING ROOM
019A
EXIST. PROCTOR
OFFICE
019B
CHECK-IN OFFICE
019C
SPECIAL
ACCOMODATIONS
019D
300 CFM
SD-2
75
EDH
2
RELOCATED
ELEC DUCT COIL
EDC-1
3
M
M
M
8
4
EXISTING EF
REBALANCE TO AIRFLOW
INDICATED
NEW HRV-2 (BELOW)
EXISTING HRV-1 (ABOVE)
HRV
2
10x1010x10
8x108x10
SD-2
75
SD-2
75
3/4" DRAIN
T
3/4" DRAIN TO EXISTING
CONDENSATE PUMP
14x14
14x14
7
M
14x10 TO EACH
HRV
1
4
x
1
4
1
4
x
1
4
14x1414x14
EXTERIOR INSULATION
BETWEEN EXTERIOR OPENINGS
AND HRV
(OUTSIDE INTAKE
AND EXHAUST AIR)
EXISTING EXHAUST/RELIEF
LOUVER
T
6
5
10x10
10x10
14x10
14x10
8x10
8x10
6Ø6Ø6Ø
6Ø6Ø
10x1010x109
RG
RL
RG
RL
9
8x108x10
6
Ø
6
Ø
8Ø8Ø
8
Ø
8
Ø
T
10
11
11
CONNECT TO EXISTING
CONDENSATE DRAIN
ON WALL
DUCT LINER (TYPICAL))
SERVICE CLEARANCE
10
(E)
(E)
(E)
MODIFY EXISTING FIRE SUPPRESSION SYSTEM
IN THIS AREA AS AS REQUIRED FOR NEW WALLS
AND LAY-IN CEILING,
SEE SPECIFICATIONS FOR DETAILS
ADA TESTING
ROOM
019I
M2-1
MECHANICAL
1/4" = 1'-0"M2-1
1MECHANICAL
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089
1/4" = 1'-0"M2-1
2FIRE SUPPRESSION
#
EQP
##
DIFF
###
ABBREVIATIONS
MECHANICAL LEGEND
CHILLED WATER SUPPLY
CHILLED WATER RETURN
NATURAL GAS
COMPRESSED AIR
LIQUEFIED PROPANE GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
REFRIGERANT HOT GAS BYPASS
HEAT PUMP SUPPLY
HEAT PUMP RETURN
FIRE SPRINKLER
OXYGEN
NITROGEN
NITROUS OXIDE
VACUUM
SCAVENGER VACUUM
DISTILLED WATER
DEIONIZED WATER
REVERSE OSMOSIS
WELL WATER SUPPLY
WELL WATER RETURN
#
EQP
##
DIFF
###
ABBREVIATIONS
MECHANICAL LEGEND
CHILLED WATER SUPPLY
CHILLED WATER RETURN
NATURAL GAS
COMPRESSED AIR
LIQUEFIED PROPANE GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
REFRIGERANT HOT GAS BYPASS
HEAT PUMP SUPPLY
HEAT PUMP RETURN
FIRE SPRINKLER
OXYGEN
NITROGEN
NITROUS OXIDE
VACUUM
SCAVENGER VACUUM
DISTILLED WATER
DEIONIZED WATER
REVERSE OSMOSIS
WELL WATER SUPPLY
WELL WATER RETURN
HUMIDISTAT OR HUMIDITY SENSOR
WITH TAMPERPROOF ENCLOSURE
THERMOSTAT OR TEMPERATURE SENSOR
THERMOSTAT OR TEMPERATURE SENSOR
RETURN/EXHAUST AIR
POSITIVE PRESSURE DUCT SECTION (SUPPLY)
NEGATIVE PRESSURE DUCT SECTION
WYE STRAINER
PIPE CAP
UNION
REDUCER
T
T
H
EXISTING TO BE REMOVED
PRESSURE REDUCING VALVE
DIFFUSER MARK
MISC. AND HVAC SYMBOLS
EQUIPMENT MARK
INDICATES EQUIP#
CEILING SUPPLY DIFFUSER
ELBOW WITH TURNING VANES
(FIRST NUMBER INDICATES FACING SIDE)
CEILING RETURN/EXHAUST REGISTER/GRILLE
ROUND DUCT (18" DIA.)
SHEET METAL DUCT
MISCELLANEOUS EQUIPMENT
VERTICAL SMOKE/FIRE DAMPER
VERTICAL FIRE DAMPER
FLEXIBLE DUCT CONNECTION
SQUARE TO ROUND TRANSITION
MBH
PLUMBING & PIPING SYMBOLS
SYMBOL
HWS
LAV
HWR
HW
FD
FC
(E)
EA
CHECK VALVE
PIPE TURNING UP
PRESSURE REGULATING
VALVE
PIPE TURNING DOWN
BUTTERFLY VALVE
BALL VALVE
RELIEF VALVE
SANITARY VENT
GATE VALVE OR BALL VALVE
PLUG VALVE
GLOBE VALVE
SUPPLY AIR
ROUNDSQUARE
ABOVE GRADE SANITARY WASTE
DOMESTIC HOT WATER
DOMESTIC COLD WATER
RECIRC. HOT WATER
DESCRIPTION
HEATING WATER RETURN
HEATING WATER SUPPLY
DOMESTIC HOT WATER
FLOOR DRAIN
EXHAUST AIR
1000 BTU/HR
LAVATORY
FANCOIL
EXISTING
#
EQP
##
DIFF
###
SYMBOL
FLOW RATE
KEYED NOTE
DESCRIPTION
WATER CLOSET
VOLUME DAMPER
VENT THROUGH ROOF
VOLTAGE
SANITARY VENT
URINAL
SANITARY SEWER
VD
(X)
WC
V OR VOLT
VTR
V
UR
SS
COTG
CONT.
CONN.
EXH
DF
DDC
CWR
CWS
CO
CA
AHU
AFF
AD
AC
ABBREVIATIONS
MECHANICAL LEGEND
DRINKING FOUNTAIN
DIRECT DIGITAL CONTROL
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CLEAN OUT TO GRADE
CONTINUATION
COMBUSTION AIR
AIR HANDLING UNIT
EXHAUST
CONNECTION
CLEAN OUT
ABOVE FINISHED FLOOR
ACCESS DOOR
AIR CONDITIONING
SHOWER
SMOKE/FIRE DAMPER
SUPPLY FAN
SUPPLY AIR
ROOF DRAIN LEADER
RETURN AIR
ON CENTER
OUTSIDE AIR
NORMALLY OPEN
SK
SH
SFD
SF
SA
RM
SINK
ROOM
RDL
RA
PRV
OC
OA
NO
NORMALLY CLOSED
MOP SINK
NC
(N)
MS
NEW
HEATING WATER SUPPLY
HEATING WATER RETURN
ACID WASTE
ACID VENT
CHILLED WATER SUPPLY
CHILLED WATER RETURN
NATURAL GAS
COMPRESSED AIR
LIQUEFIED PROPANE GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
REFRIGERANT HOT GAS BYPASS
HEAT PUMP SUPPLY
HEAT PUMP RETURN
FIRE SPRINKLER
OXYGEN
NITROGEN
NITROUS OXIDE
VACUUM
SCAVENGER VACUUM
BELOW GRADE SANITARY WASTE
BELOW GRADE STORM SEWER
ABOVE GRADE STORM SEWER
DISTILLED WATER
DEIONIZED WATER
REVERSE OSMOSIS
WELL WATER SUPPLY
WELL WATER RETURN
(EXHAUST OR RETURN)
TYPICALTYP
BDD BACKDRAFT DAMPER
FLOOR CLEAN OUTFCO
WALL CLEAN OUTWCO
ELEC. ELECTRIC/ELECTRICAL
TEMPERATURE CONTROLTC
MECHANICALMECH.
AT THIS POINT
CONNECT NEW PIPE OR DUCT TO EXISTING
RECIRCULATING HOT WATERRHW
REVERSE ACTING THERMOSTAT
T
MOTORIZED DAMPER
M
TO BE DETERMINEDTBD
FSD FIRE/SMOKE DAMPER
HUMIDISTAT OR HUMIDITY SENSOR
WITH TAMPERPROOF ENCLOSURE
THERMOSTAT OR TEMPERATURE SENSOR
THERMOSTAT OR TEMPERATURE SENSOR
RETURN/EXHAUST AIR
POSITIVE PRESSURE DUCT SECTION (SUPPLY)
NEGATIVE PRESSURE DUCT SECTION
WYE STRAINER
PIPE CAP
UNION
REDUCER
T
T
H
EXISTING TO BE REMOVED
PRESSURE REDUCING VALVE
DIFFUSER MARK
MISC. AND HVAC SYMBOLS
EQUIPMENT MARK
INDICATES EQUIP#
CEILING SUPPLY DIFFUSER
ELBOW WITH TURNING VANES
(FIRST NUMBER INDICATES FACING SIDE)
CEILING RETURN/EXHAUST REGISTER/GRILLE
ROUND DUCT (18" DIA.)
SHEET METAL DUCT
MISCELLANEOUS EQUIPMENT
VERTICAL SMOKE/FIRE DAMPER
VERTICAL FIRE DAMPER
FLEXIBLE DUCT CONNECTION
SQUARE TO ROUND TRANSITION
MBH
PLUMBING & PIPING SYMBOLS
SYMBOL
HWS
LAV
HWR
HW
FD
FC
(E)
EA
CHECK VALVE
PIPE TURNING UP
PRESSURE REGULATING
VALVE
PIPE TURNING DOWN
BUTTERFLY VALVE
BALL VALVE
RELIEF VALVE
SANITARY VENT
GATE VALVE OR BALL VALVE
PLUG VALVE
GLOBE VALVE
SUPPLY AIR
ROUNDSQUARE
ABOVE GRADE SANITARY WASTE
DOMESTIC HOT WATER
DOMESTIC COLD WATER
RECIRC. HOT WATER
DESCRIPTION
HEATING WATER RETURN
HEATING WATER SUPPLY
DOMESTIC HOT WATER
FLOOR DRAIN
EXHAUST AIR
1000 BTU/HR
LAVATORY
FANCOIL
EXISTING
#
EQP
##
DIFF
###
SYMBOL
FLOW RATE
KEYED NOTE
DESCRIPTION
WATER CLOSET
VOLUME DAMPER
VENT THROUGH ROOF
VOLTAGE
SANITARY VENT
URINAL
SANITARY SEWER
VD
(X)
WC
V OR VOLT
VTR
V
UR
SS
COTG
CONT.
CONN.
EXH
DF
DDC
CWR
CWS
CO
CA
AHU
AFF
AD
AC
ABBREVIATIONS
MECHANICAL LEGEND
DRINKING FOUNTAIN
DIRECT DIGITAL CONTROL
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CLEAN OUT TO GRADE
CONTINUATION
COMBUSTION AIR
AIR HANDLING UNIT
EXHAUST
CONNECTION
CLEAN OUT
ABOVE FINISHED FLOOR
ACCESS DOOR
AIR CONDITIONING
SHOWER
SMOKE/FIRE DAMPER
SUPPLY FAN
SUPPLY AIR
ROOF DRAIN LEADER
RETURN AIR
ON CENTER
OUTSIDE AIR
NORMALLY OPEN
SK
SH
SFD
SF
SA
RM
SINK
ROOM
RDL
RA
PRV
OC
OA
NO
NORMALLY CLOSED
MOP SINK
NC
(N)
MS
NEW
HEATING WATER SUPPLY
HEATING WATER RETURN
ACID WASTE
ACID VENT
CHILLED WATER SUPPLY
CHILLED WATER RETURN
NATURAL GAS
COMPRESSED AIR
LIQUEFIED PROPANE GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
REFRIGERANT HOT GAS BYPASS
HEAT PUMP SUPPLY
HEAT PUMP RETURN
FIRE SPRINKLER
OXYGEN
NITROGEN
NITROUS OXIDE
VACUUM
SCAVENGER VACUUM
BELOW GRADE SANITARY WASTE
BELOW GRADE STORM SEWER
ABOVE GRADE STORM SEWER
DISTILLED WATER
DEIONIZED WATER
REVERSE OSMOSIS
WELL WATER SUPPLY
WELL WATER RETURN
(EXHAUST OR RETURN)
TYPICALTYP
BDD BACKDRAFT DAMPER
FLOOR CLEAN OUTFCO
WALL CLEAN OUTWCO
ELEC. ELECTRIC/ELECTRICAL
TEMPERATURE CONTROLTC
MECHANICALMECH.
AT THIS POINT
CONNECT NEW PIPE OR DUCT TO EXISTING
RECIRCULATING HOT WATERRHW
REVERSE ACTING THERMOSTAT
T
MOTORIZED DAMPER
M
TO BE DETERMINEDTBD
FSD FIRE/SMOKE DAMPER
M3-1
MECHANICALSCHEDULES
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089
REMOVE EXISTING LIGHT. MAINTAIN ELECTRICAL AS REQUIRED FOR INSTALLATION
OF NEW FIXTURES.
KEYED NOTES:
1
UP
DN
S
S
S
S
S
S
S
S
S
S
S
UP
DN
1
1
S
OFFSET EXISTING CONDUIT & WIRE AS REQUIRED FOR
RAISING OF EXISTING DUCTWORK. (APPROX 12").
COORDINATE WITH HVAC CONTRACTOR.
OS
OS
OS
OS
OS
EXISTING PANEL 'B3'
1
RAISE LIGHT UP TO SURFACE
OF CEILING
E1-2
LIGHTINGDEMOLITION
1/4" = 1'-0"E1-2
1LIGHTING - DEMOLITION
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089
REMOVE AND REINSTALL RECEPTACLES AS REQUIRED FOR WALL WORK.
CONTRACTOR MAY REUSE EXISTING BOXES AND PLATES.
KEYED NOTES:
1
ETS TESTING
ROOM
019F
STORAGE
019G
ADA TESTING
ROOM
019I
DIRECTOR'S
OFFICE
019H
SPECIAL
ACCOMODATIONS
019E
EXIST. WAITING
AREA
019
EXIST. P-VUE
TESTING ROOM
019A
EXIST. PROCTOR
OFFICE
019B
CHECK-IN OFFICE
019C
SPECIAL
ACCOMODATIONS
019D
UP
DN
(E) AC-5
EXISTING
J-HOOKS
EXISTING
DATA CABLE
TRAY
HRV-1
CCTV CAMERA
(TYPICAL)
F
F
F
F
F
F
EXISTING
PANEL B3
F
F
F
F
F
F
UP
DN
AC UNIT
1
1
1
EXISTING BRANCH
DIVIDER BOX
REMOVE RECEPTACLE
REMOVE/RELOCATE EXISTING HORN/STROBE
AS REQUIRED FOR NEW WALL
(E) AC-7
PANEL 'B2'
PANEL 'B1'
DISTRIBUTION PANEL
(E) AC-6
B3-3,5,7
RELOCATE EXISTING
ELECTRIC DUCT HEATER
E1-1
POWERDEMOLITION
1/4" = 1'-0"E1-1
1POWER - DEMOLITION
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089
NEW FIRE ALARM - HORN/STROBE.
ALTERNATE #3: PROVIDE POWER TO NEW POWERED ADA DOOR. 115V-6.6A (15 AMP
BRACH CIRCUIT PROTECTION.
PROVIDE POWER FOR NEW AC UNIT. POWER FED FROM BRANCH DIVIDER BOX.
POWER FOR HRV-2 FED FROM EXISTING CIRCUIT FEEDING HRV-1.
KEYED NOTES:
1
2
3
4
UP
DN
UP
DN
F
F
F
F
F
F
F
F
F
F
F
UP
DN
AC UNIT
UP
DN
UP
DN
AC UNIT
F F F
1 1 1
B3-8
J
B2-2
2
CAMERA - TYPICAL
(BY OTHERS)
RELOCATED POWER
RECEPTACLES
NEW BRANCH DIVIDER
BOX (BY MECH)
3
4
CONNECT TO EXISTING
BRANCH DIVIDER BOX
208V/.1MCA
1
2
" C. (3) #12 & #14 GND
B3-37
CONNECT TO EXISTING
RECEPTACLE
F
1
AC-8
B2-9,11,13
HRV-2
(BELOW)
DATA CABLE PATH
PROVIDE J-HOOKS
SEE SPECS
PANEL 'B2'
208V/.1MCA
1
2
" C. (3) #12 & #14 GND
B2-3,5,7
EDH-2
EDH-1
E2-1
ELECTRICALPOWER
1/4" = 1'-0"E2-1
1ELECTRICAL - POWER
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089
CONNECT NEW LIGHT FIXTURES TO EXISTING LIGHTING CIRCUIT SERVING SPACE.
KEYED NOTES:
1
ADA TESTING
ROOM
019F
STORAGE
019G
ETS TESTING
ROOM
019I
DIRECTOR'S
OFFICE
019H
SPECIAL
ACCOMODATIONS
019E
EXIST. WAITING
AREA
019
EXIST. P-VUE
TESTING ROOM
019A
EXIST. PROCTOR
OFFICE
019B
CHECK-IN OFFICE
019C
SPECIAL
ACCOMODATIONS
019D
UP
DN
UP
DN
S
S
OC
S
OC
S
OC
S
OC
S
S
S
S
OC1
S
S
UP
DN
UP
DN
UP
DN
EB
S
D
S
D
S
D
S
D
1
J
OS
OS
OS OS OS
S
A
B B B
B
A
AA
A A
XE
RAISE EXISTING LIGHTS UP TO
SURFACE OF CEILING
E3-1
ELECTRICALLIGHTING
1/4" = 1'-0"E3-1
1ELECTRICAL - LIGHTING
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089
MMOTOR
S
OS
S
M
A
MOTOR SENTINEL - FRACTIONAL H.P.
STARTER-COMBINATION MAGNETIC
EXISTING DEVICE TO REMAIN
RECEPTACLE ABOVE COUNTER
OUTLET, GROUND FAULT INTERRUPTER
N
E
OUTLET, PHONE ONLY
OUTLET, PHONE/DATA
OUTLET, PHONE/DATA (DUPLEX)
TELECOMMUNICATIONS
DESCRIPTION
EXIT LIGHTS (WALL OR CEILING)
SYMBOL
J
JUNCTION BOX
PANEL OR LOAD CENTER
STARTER-MAGNETIC
DISCONNECT SWITCH
NEW DEVICE
GFI
EMERGENCY LIGHT FIXTURE
PENDANT OR SURFACE MOUNTED
FLUORESCENT LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
RECESSED LIGHT FIXTURE
DESCRIPTION
FLUORESCENT LIGHT FIXTURE (RECESSED)
FLUORESCENT LIGHT FIXTURE (SURFACE)
SYMBOL
OUTLET, DUPLEX
SPECIAL POWER OUTLET
OUTLET, FOURPLEX
RECEPTACLE - SIMPLEX
SWITCH - WITH OCCUPANCY SENSOR
ELECTRICAL LEGEND
S
D
S
MC
S
P
S
T
S
3
SWITCH - MOMENTARY CONTACT
DEVICE & POWERMISCELLANEOUS
BRANCH CIRCUIT CONCEALED IN WALL OR CEILING
BRANCH CIRCUIT CONCEALED IN OR UNDER FLOOR
HOMERUN TO PANEL. NUMBER OF ARROWS
INDICATES NUMBER OF CIRCUITS.
CIRCUIT, NUMBER OF HASH MARKS INDICATES
NUMBER OF CONDUCTORS. NO HASH MARKS
INDICATE TWO CONDUCTORS.
LIGHTING
DESCRIPTIONSYMBOL
SWITCH - DIMMER
SWITCH - WITH PILOT
SWITCH - TIMER
SYMBOL
SWITCH, THREE WAY
SWITCH, SINGLE POLE
DESCRIPTION
ELECTRICAL CONTRACTOR
ABOVE FINISHED FLOOR
EC
C CONDUIT
CIRCUITS 2,4,6
PANELBOARD BN1L,
a,b,c, etc.
BN1L-2,4,6
AG
AFF
SWITCH DESIGNATION
ABOVE GROUND
CIRCUIT DESIGNATION,
WITH
UNDER GROUND
WEATHER PROOF
NIGHT LIGHT
W/
UG
WP
NL
GENERAL CONTRACTOR
GROUND
MANUAL TRANSFER SWITCH
MECHANICAL CONTRACTOR
GC
MTS
MC
GND
ABBREVIATIONS
S
J
OUTLET, DATA ONLY
E4-1
ELECTRICALSCHEDULES
REV. DESCRIPTION DATEREVIEWED BY:DRAWN BY:
SHEET
DATE
SHEET TITLE
MO
NT
AN
AST
AT
E U
NIV
ER
SIT
Y
MSU-CPDCMONTANA STATE UNIVERSITY
BOZEMAN, MONTANAPHONE: 406.994.5413
FAX: 406.994.5665
RE
NN
E L
IB.
TE
ST
ING
CE
NT
ER
EX
PA
NS
ION
BID
DO
CUM
ENTS
02-15-2019
MO
NT
AN
A S
TA
TE
UN
IVE
RS
ITY
AMJT
Th
re
e R
ive
rs
En
gin
ee
rin
g,
Inc
.
ME
CH
AN
ICA
L,
EL
EC
TR
ICA
L,
EN
ER
GY
24
S.
Wil
ls
on
Av
e,
ST
E A
1
Bo
ze
ma
n,
MT
5
97
15
40
6-5
82
-82
88
ww
w.t
re
mt
.co
m
A/E#00-00-00Consultant #:
PPA#18-2089