address of premises - newham council
TRANSCRIPT
Chief Executive-London Borough of Newham
13/12/2018 Date of Survey :
The Fire Risk Assessment was undertaken by The assessor detailed in the Assessment Summary below who has the
necessary qualifications, competency and experience in Fire Risk Management that give him/her the status of
“Competent Person” as described in articles 15 and 18 of the ‘Regulatory Reform (Fire Safety) Order 2005', for
properties in England & Wales, and the 'Fire Safety (Scotland) Regulations 2006' for those in Scotland. This legislation
now supersedes all previous fire legislation for England, Wales & Scotland and forms the ‘Fire Regulations'.
General Needs Flatted AccommodationFire Risk Assessment (FRA)
Regulatory Reform (Fire Safety) Order 2005
Responsible person
Address of Premises
1-73 Dunedin House Manwood Street E16 2LA
Assessment Summary
1-73 Dunedin House Manwood Street E16 2LA
Newham
13/12/2018
Head of Housing Works Commissioning
Tolerable
No major additional controls required. However, there might be a need for
improvements that involve minor or limited cost.
Purpose built nineteen storey block with 73 single storey flats . 4 flats are
located on each floor apart from ground floor where there is 1 flats all
accessed from a single protected stairway. There are two passenger lifts
serving all 19 floors. Brick and concrete contruction with flat roof. Two
internal concrete staircase and floors with plaster on hard walls. Floor
covering is a mixture of vinyl and concrete floors throughout.There is a
concierge office at ground floor level. The block is in the process of having
scaffolding remeoved.
Asset Image
Person managing fire safety for the premises:
Risk Level
Risk Description
Site Address:
Ownership:
Date Due:
Date Assessed:
Surveyed By
General Building Description
( Floors, Construction, Staircases etc… )
The purpose of this report is to provide an assessment of the risk to life from fire in these premises, and, where
appropriate, to make recommendations to ensure compliance with fire safety legislation. The report does not
address the risk to property or business continuity from fire. If you have any questions about this Fire Risk
Assessment please contact:
Building Risk Assessor
Direct House, Bridge Road Depot, Abbey Road, London E15 3LX
Tel: DDI - 020 3373 4296 – Int. Ext. 34296
This Fire Risk Assessment should be reviewed by a competent person if it is no longer valid, or if there has been a significant change in the
matters to which it relates, or if a fire occurs.
1. Introduction
This report has been prepared as a written record of the Fire Risk Assessment, carried out at
1.1 The objectives of this Fire Risk Assessment are:
a. To identify all current significant fire hazards to which relevant persons on the premises, or in the immediate
vicinity of the premises, will be exposed.
1-73 Dunedin House Manwood Street E16 2LA under the requirements of the Regulatory Reform (Fire Safety) Order 2005.
b. To reasonably quantify the level of residual fire risk that is attributed to the premises and its use, with regard to
existing (preventive and protective) controlling measures.
c. To advise on the nature and extent of any additional (preventive and protective) controlling measures which
should be implemented in order to counteract this residual risk, in accordance with the ‘Principles of Prevention’ as
defined in Article 10 of The Regulatory Reform (Fire Safety) Order 2005.
1.2 Risk Assessments
Risk Assessments are not a ‘one off’ activity, and are part of a dynamic process. It is thus a requirement under Article
9(3) of The Regulatory Reform (Fire Safety) Order 2005 to review and modify the risk assessment when either:
a. There is reason to suspect that it is no longer valid, perhaps due to a gradual change in the nature of the
tenancy numbers or type, wear & tear on facilities, a large number of small changes, an appreciation of a hazard (e.g.
highlighted by fire evacuation drill), or
b. the occurrence of an incident (e.g. actual fire or near miss), which triggers a need to review, OR there is a
significant change in the matters to which it relates, (i.e. following major organisational changes or any
refurbishment, alterations or extension).
1.3 This Risk Assessment
This risk assessment is a ‘dynamic’ working document that should be used as a guide to planning future actions
aimed at improving Health & Safety for tenants and others who may be affected by a potential fire at the premise.
Notwithstanding the requirements noted in Section 1.2 above, it is a requirement of London Borough of Newham
that Fire Risk Assessments are normally reviewed annually, unless otherwise advised by the Fire Risk Assessment
report. Some reasonable flexibility is permitted to accommodate logistical and financial constraints.
Scope and Methodology
1.4 Statutory Requirement
1.5 Identification of Fire Hazards
1.6 Assessment of Fire Risk
1.7 The Fire Risk Assessment Action Schedule
1.8 Information Source
Article 9 of The Regulatory Reform (Fire Safety) Order 2005 requires every responsible person to make a suitable and sufficient
assessment of the fire risks to which relevant persons are exposed, with respect to premises within their control. This is for the
purpose of identifying the general fire precautions that are needed to comply with the requirements and prohibitions imposed
by the Order. The responsible person, or any other person who has to any extent control of the premises, must ensure that the
duties imposed by the relevant articles of The Regulatory Reform (Fire Safety) Order 2005 are complied with in respect of those
premises, so far as the requirements relate to matters within their control. Where the premises are licensed, an alterations notice
is in force, or the responsible person has five or more employees, it is a requirement to record the significant findings of the fire
risk assessment including the measures which have been or will be taken as a result of the assessment and details of any group of
persons identified by the assessment as being especially at risk. This report therefore incorporates such relevant information,
significant findings and recommended actions that are considered necessary to demonstrate compliance with The Regulatory
Reform (Fire Safety) Order 2005.
In order to identify the significant fire hazards within the premise, a checklist is used which considers the particular fire hazards
associated with this type of building and the nature of the occupancy. The hazard identification process will consider each item
with due regard to the existing ‘control measures’, which are either already inherent within the building fabric design or are
implemented through the management policy procedures for the premise. The answers to all questions should be YES, NO or
NOT APPLICABLE (Na).
Each identified hazard is assessed in accordance with the fire risk-rating matrix detailed in Section 2.0 of this report. This matrix
has due regard to the person or group of persons who are likely to be affected by each hazard, by considering the hazards in
terms of their potential to harm (severity) and their likelihood (probability) of actually occurring. The matrix allows the
assignment of a specific risk rating for each perceived hazard, which subsequently assists in determining the nature and extent of
any necessary additional controlling measures, (both physical and procedural deficiencies), as well as the timescale in which
these measures should be
This Action Schedule details the blend of technical and procedural measures, which are considered necessary to adequately
address the residual risk that has been previously identified, semi-quantified and assigned a ‘risk-rating’. This risk control plan is
essentially an inventory of remedial / advisory actions which should be carried out by London Borough of Newham Group or an
appointed representative, within the recommended timescales. These timescales are suggested purely to aid reasonable
implementation of the Action Schedule, but for the residual risk to be reduced to an acceptable level, it will be necessary to
implement all Action Items on the schedule. It is a requirement of London Borough of Newham that P1 timescales may not be
exceeded without the recorded authorisation of a senior manager, Head of Department or a Director.
Information for the completion of this assessment was obtained by a semi non-invasive physical inspection of the premise,
inspection of records and drawings (where available). For accurate identification of hazard location, digital photographs are
enclosed to ‘pin-point’ the specified hazard.
2. Risk Assessment Details 2.1 Fire Risk Rating Matrix
Level0
1
2
3
Score Degree
0
1-3
4
6
9
The following risk rating matrix is used to enable semi-quantification of the itemised fire safety deficiencies (hazards)
that were found during the recent survey of the premise.
The matrix allows the identified significant fire hazards to be classified in terms of the harmful or unwanted
consequences (severity) that the hazard would cause, if it were to occur and also the likelihood (probability) that
such harm will occur. These factors are considered with due regard to the existing fire safety features and
procedures (controlling measures), which are either incorporated within the building design or procedurally
implemented within the premise.
Degree Probability of Exposure to Harm
Likely to occur at some stage in the foreseeable future
Very likely to occur frequently and/or in the near future unless actively prevented
Medium Risk
Very High Risk
The product of the severity and probability factors will equate to a specific risk rating for each identified hazard. The
following band matrix can then be used to assign a comparative degree of risk (Very Low , Low, Medium or Very
High) to each individual fire safety deficiency. This will assist in determining the extent of any necessary additional
controlling measures, as well as the timescale in which these measures should be implemented.
Trivial
Considerable resources might have to be allocated to reduce the risk. If the
building is unoccupied, it should not be occupied until the risk has been
reduced. If the building is occupied, urgent action should be taken.
Substantial
Intolerable Building (or relevant area) should not be occupied until the risk is reduced.
Unlikely to occur, but still possible
No known instances of such an event occurring
Probability Level
Very Low Risk
Low Risk
Consequence
No action is required and no detailed records need to be kept.
It is essential that efforts are made to reduce the risk. Risk reduction measures
should be implemented within a defined time period. Where moderate risk is
associated with consequences that constitute extreme harm, further
assessment might be required to establish more precisely the likelihood of harm
as a basis for determining the priority for improved control measures.
No major additional controls required. However, there might be a need for
improvements that involve minor or limited cost.
Risk Control Plan
Tolerable
Moderate
Very High Risk A 9
High Risk B 6
Medium Risk C 4
Low Risk D 1 to 3
Very Low Risk M 0 to 0
Internal and External Communal areas including but not limited to the following:
Within 12 months
No set timescale
Timescales for Remedial Action( maximum time limits )
Within 1 Month
Within 6 Months
Degree of RiskPriority
Level for
Risk
Rating
The table details the systematic approach that has been taken to assess the individual level of risk that is inherent in
each identified hazard / fire safety deficiency, recorded during the inspection of this premise.
Each hazard (item) has been considered with regard to the specific group of people that it threatens; its potential
severity and its probability of being realised. Existing control measures are taken into account before determining
the nature and extent of any additional control measures deemed necessary to contend with the residual fire risk
that remains.
The table below provides timescales for remedial action proportionate to the risk.
2.2 Assessment of Fire Risk
Entrances, Exits , Escape Stairs, Landings, Lobbies, Electrical Intake/service cupboards, Pram shed areas, Refuse
areas.
2.6 How are occupants who warrant special consideration identified?
In the event of an emergency any vulnerability information is obtainable from the Housing database which is available
to the LBN Emergency Officer.
Management/ procedural
2.3 Sheltered Accommodation Containing Vulnerable Persons
The same method is used but the overall fire risk rating is adjusted up one level. For example, if the individual risk
ratings on the itemised schedule is a Low Risk then the fire risk rating for the premises is categorised as Moderate
Risk.
2.4 Exceptional Circumstances
Where the assessor risk or receiving manager feels the method of calculation has arrived at a grossly
disproportionate fire risk rating, the matter should be referred to the Director for consideration and advice.
2.5 Extent of Common Areas
Priority Description
A When an unacceptable risk to fire safety is present
BWithin 6 months. These items are regarded as important but a lead time to
organise is recognised to be necessary.
C
Where an immediate risk to fire safety is not present but
improvements/actions are necessary to maintain the essential systems and
standards.
DWorks to be considered in future improvements or ongoing/rolling
maintenance programmes.
MRelates to continuing managerial responsibility or recognised best practice
guidance.
Premises:
Question
Yes/
No/
n/a
Priority Ownership Action Comments
(to include location and any required remedial works)Additional Comments Photo ref.
Hazard identification - housekeeping
1 Is fire load close to the premises minimised? Yes
Arson- Security
2 Are premises adequately secured against potential arson? Yes
The Bin store located at rear of building is accessed via timber doors that are
locked and secure and needs to be kept locked and secure to avoid any
possibility of arson. No Action Required
32.) Bin Store
doors
3Are there suitably located and secured provisions for the disposal of waste
and recyclable material?Yes 5.) Bin Chute
Combustible Materials - Housekeeping
4Are any potential combustible materials adequately segregated from any
sources of ignition?No A
Resident
Engagement/Client Servs
There are items stored in ground floor staff room cleaners cupboard and locker
cupboard. There are chemical bottles, car battery and aerosol cannisters that
are highly flammable that are not stored in a metal store cupboard that should
be provided. Remove all chemical bottles and aerosol cannisters and store
within a metal cabinet. Remove the car battery from building. Remove all
flammable items and ensure all the electric intake cupboards and store
cupboards are kept clear from debris and stored items.
17,18,19.)
Items stored in
staff cpd
5Are quantities of combustible waste allowed to accumulate in the premises
such as Paper, cardboard, wood shavings, dust?Yes B
Resident
Engagement/Client Servs
There are items in the lift room area stored that need to be removed. There are
items located in the external spiral staircase that need to be removed.
Where scaffolding has been removed there are timber hoardings located within
the bin chute areas. Ensure these are all removed.
27.) Items
stored in tank
room
29.) Items
stored in ext
stairs
41.)Timber in
bin chute area
Fire Detection - Alarms
6 Are fire alarm tests recorded? Yes
There is a fire alarm panel located at ground floor that only serves the ground
floor and concierge area. It is unknown whether fire alarm tests are recorded.
Newham Council to advise
30.) Fire alarm
panel
7Is automatic detection and/or manual alarm provided in the premises?
If yes, describe system.Yes
There is a zoned fire alarm panel with dection throughout all communal areas on
all floors.
39.) Smoke
detection in
lobby
8Is further automatic detection and/or manual alarm provision required?If
yes, state what.No
9 Is the alarm system adequately maintained? Yes All records relating to fire safety are held by the Asset Management team
10 Is the fire alarm system in working order? Yes
1-73 Dunedin House Manwood Street E16 2LA
Management/ procedural
Timescale
Within 1 month
Within 6 months
Within 1 year
No set timescale
Premises:
Question
Yes/
No/
n/a
Priority Ownership Action Comments
(to include location and any required remedial works)Additional Comments Photo ref.
1-73 Dunedin House Manwood Street E16 2LA
Fire Fighting Equipment - Entry
11 Is the fireman's switch working correctly? Yes2.) FIREMANS
SWITCH
12 Are fire extinguishers adequately maintained? n/a
Fire Fighting Equipment - Extinguishers
12 Are fire extinguishers adequately maintained? No AResident
Engagement/Client Servs
There is a Co2 and foam extinguisher located within the concierge office are at
ground floor. Both extinguishers are currently within service date, however one
has been discharged and is now empty and is not in correct posistion.Replace
with new extinguisher or refill. There is an extinguisher located in the lift motor
room area that is out of date. Replace with up to date extinguisher or remove
completely.
20.22)
Extinguishers in
concierge
21.)
Extinguisher
service date
40.) Fire
extinguisher out
of date
13Are other fire extinguishing systems provided/accessible and in good
working condition?n/a .
14Are portable fire extinguishers provided/accessible and in good working
condition?Yes
Fire Fighting Equipment - Other
15 Are all bin chamber doors secure? Yes 32.) Bin Store
doors
Fire Fighting Equipment - Risers
16 Are dry/wet risers in good order? Yes 3.7.) Dry Riser
17 Are rising mains adequately maintained? Yes All records relating to fire safety are held by the Asset Management team
Flammable Substances - Housekeeping
18 Are there any highly flammable substances in the premises? No
General Hazards - Any Other Issues
19 Are there any other issues? Please specify No
Limiting Fire Spread - Compartmentation
20 Are any installed linings appropriate for limiting the spread of fire? No A Asset Management
The majority of flat entrance doors all appear to be FD30s doors wih
intumescent strips and door closers, however, flat 64 is not fire rated and needs
changing with a FD30s fire door fitted. Flat has either no automatic door
closer fitted or they have been dismantledand. It is recommended to replace
these closers and to carry out a full inspection of all doors to determine if any
more are needed to be replaced.The tank room and lift motor room doors are
metal and fully compliant. HThe compartmentation doors and doors leading to
the staircases to all floors have closers and all have intumescent strips fitted,
however the doors on 1st,and 4th floors are not closing properly and need
servicing/adjusting.. The riser doors, bin chute doors and electric intake doors
from the 1st floor to 19th floor are all compliant. The electric intake to the
concierge area on the ground floor are all compliant with intumescent strips and
no action needed. The store room doors to concierge and lobby area at ground
floor do not have intumescent strips fitted.
The paint is delaminating on walls and ceilings within the communal lobby
corridors . Prepare and redecorate using "type 0" paint.
It was not confirmed whether the walls and ceiling paint is fire rated "O" type
paint. It is advised at the next redecoration programme to ensure that correct "O
" type fire retardent paint is used within communal areas.
8.9.10.11.) Flat
Entrance Door
6.) Dry
Riser/tank room
doordoor
12.13.14.)
Compartmentati
on Doors
15.) Concierge
Door
25.) Grnd floor
electric intake
door
23.) Lift Motor
room door
36.) Electric
intake room
door
35.) Paint
Delaminating
Premises:
Question
Yes/
No/
n/a
Priority Ownership Action Comments
(to include location and any required remedial works)Additional Comments Photo ref.
1-73 Dunedin House Manwood Street E16 2LA
21 Is the current level of compartmentation adequate for the premise? No A Asset Management
Doors as above (Question 20.)
The tank room and lift motor room doors are metal and fully compliant. However
there is an issue with compartmentation to the service room door as there is a
breach in compartmentation above the door. It is recommended to fit appropriate
fire stopping with fire retardent materials to provide correct compartmentation.
The Georgian wire glazing that forms part of the compartmentation on 1st, 7th
and 9th floor is either loose or incorrect silicone and metal gaskets fitted. Ensure
correct fire retardent glazing gaskets are fitted.
28.) Breach in
compartmentati
on
43.)Georgian
glazing gasket
13
Limiting Fire Spread - Dampers
22 Where required, are dampers provided? n/aIt was not determined whether dampers where fitted to extraction and other
plant throughout. Newham to advise.
26.) Extraction
plant
Maintenance Checks - General
23 Are appropriate building maintenance checks undertaken regularly? Yes All records relating to fire safety are held by the Asset Management team
24 Are lifts adequately maintained? Yes
25 Are the premises generally well maintained? Yes
26Have all installed or portable electrical appliances been tested in
accordance with regulations?Yes Items in the concierge area where checked and found to be "in date"
16.) Concierge
Pat tested items
27 Is the lightning protection system adequately maintained? Yes All records relating to fire safety are held by the Asset Management team
28 Is the sprinkler system adequately maintained? n/a
Premises:
Question
Yes/
No/
n/a
Priority Ownership Action Comments
(to include location and any required remedial works)Additional Comments Photo ref.
1-73 Dunedin House Manwood Street E16 2LA
Means Of Escape - Lighting
29Are all exits and exit routes adequately illuminated (internal and
external)?Yes
30 Are any other areas as required adequately illuminated? Yes Emergency lighting fitted in communal areas.
31 Are emergency escape lighting tests recorded? Yes All records relating to fire safety are held by the Asset Management team
32 Is the emergency escape lighting adequately maintained? Yes All records relating to fire safety are held by the Asset Management team
33Where fitted, is the emergency escape lighting in good working
order?Yes All records relating to fire safety are held by the Asset Management team
Means Of Escape - Routes
34 Are all escape routes clear and unobstructed? No AResident
Engagement/Client Servs
There items stored in communal lobby areas. Remove Items.Flat has metal
security gate fitted within landlords demise. Ensure theis is removed to maintain
escape route.
Regular checks to ensure that walkways are kept clear of obstructions is
reccommended
37.) Items
stored in lobby
area
31.)Security
Grill fitted
35 Are all floors free from slipping/tripping hazards? Yes
36 Are corridors sub-divided (where appropriate)? Yes
37Are doors on escape routes easily opened and do they open in the
correct direction?Yes
Main Entrance and exit doors are all in fair condition and open in direction of
travel
34.) External
Exit Door
38Are there reasonable arrangements in the building for means of
escape for disabled people?Yes
LBN in liaison with the LFB have a stay put policy. Dutyholder to confirm if
provisions for disabled access is required.
39 Are travel distances to fire exits satisfactory - single and two-way? Yes
40 Do all escape routes lead to a place of safety? Yes
41Does the escape route design meet the necessary Home Office
guidelines?n/a
42Is adequate separation evident on all escape routes (as
appropriate)?Yes
43 Is the number and provision of exits adequate? Yes
44 Is there adequate protection provided/installed to all escape routes? Yes
Means Of Escape - Signage
45 Are signs clearly visible and not obstructed? Yes
46 Is there adequate provision of fire safety signs and notices? No BResident
Engagement/Client ServsThere is a damaged "No smoking "sign on 11th floor
42.) Damaged
"No smoking"
Sign
Other Issues - General
47 Are there any other issues to specify? No
Premises Management - Records And Security
48 Are there appropriate fire safety procedures in place? Yes All records relating to fire safety are held by the Asset Management team.
49Are there provisions in place for liaison to take place with the local
fire and rescue service?Yes LBN in liaison with the LFB have a stay put policy
50 Is there an available and suitable record of fire safety arrangements? No All records relating to fire safety are held by the Asset Management team
Premises:
Question
Yes/
No/
n/a
Priority Ownership Action Comments
(to include location and any required remedial works)Additional Comments Photo ref.
1-73 Dunedin House Manwood Street E16 2LA
Records - Fire Maintenance
51 Are fire safety maintenance records available for the premises? No All fire safety maintenance records are held by the Asset Management team
Sources Of Ignition - Smoking
52Is there evidence of any smoking related activities taking place in
non designated areas?No
Training - Evacuation
53Where fire evacuation safety drills are considered appropriate, are
they carried out at regular intervals?n/a
Training - Trained Personnel
54 Are staff trained in fire safety via induction and/or annual refreshers? n/a
55 Is fire safety training recorded? n/a
Priority Description
A When an unacceptable risk to fire safety is present
BWithin 6 months. These items are regarded as important but a lead time to organise is
recognised to be necessary.
CWhere an immediate risk to fire safety is not present but improvements/actions are necessary to
maintain the essential systems and standards.
D Works to be considered in future improvements or ongoing/rolling maintenance programmes.
M Relates to continuing managerial responsibility or recognised best practice guidance.
Premises:
Question Action to be taken Priority Ownership Additional Comments / Review Notes
1
2
3
4
There are items stored in ground floor staff room cleaners cupboard and locker
cupboard. There are chemical bottles, car battery and aerosol cannisters that are
highly flammable that are not stored in a metal store cupboard that should be provided.
Remove all chemical bottles and aerosol cannisters and store within a metal cabinet.
Remove the car battery from building. Remove all flammable items and ensure all the
electric intake cupboards and store cupboards are kept clear from debris and stored
items.
A
Resident
Engagement/Client
Servs
5
There are items in the lift room area stored that need to be removed. There are items
located in the external spiral staircase that need to be removed.
Where scaffolding has been removed there are timber hoardings located within the
bin chute areas. Ensure these are all removed.
B
Resident
Engagement/Client
Servs
6
1-73 Dunedin House Manwood Street E16 2LA
Fire Risk Assessment Action Plan
No set timescale
Management/ procedural
Timescale
Within 1 month
Within 6 months
Within 1 year
Premises:
Question Action to be taken Priority Ownership Additional Comments / Review Notes
1-73 Dunedin House Manwood Street E16 2LA
7
8
9
10
11
12
13 .
14
15
16
17
18
19
20
The majority of flat entrance doors all appear to be FD30s doors wih intumescent strips
and door closers, however, flat 64 is not fire rated and needs changing with a FD30s
fire door fitted. Flat has either no automatic door closer fitted or they have been
dismantledand. It is recommended to replace these closers and to carry out a full
inspection of all doors to determine if any more are needed to be replaced.The tank
room and lift motor room doors are metal and fully compliant. HThe compartmentation
doors and doors leading to the staircases to all floors have closers and all have
intumescent strips fitted, however the doors on 1st,and 4th floors are not closing
properly and need servicing/adjusting.. The riser doors, bin chute doors and electric
intake doors from the 1st floor to 19th floor are all compliant. The electric intake to the
concierge area on the ground floor are all compliant with intumescent strips and no
action needed. The store room doors to concierge and lobby area at ground floor do
not have intumescent strips fitted.
The paint is delaminating on walls and ceilings within the communal lobby corridors .
Prepare and redecorate using "type 0" paint.
A Asset Management
Premises:
Question Action to be taken Priority Ownership Additional Comments / Review Notes
1-73 Dunedin House Manwood Street E16 2LA
21
Doors as above (Question 20.)
The tank room and lift motor room doors are metal and fully compliant. However there
is an issue with compartmentation to the service room door as there is a breach in
compartmentation above the door. It is recommended to fit appropriate fire stopping
with fire retardent materials to provide correct compartmentation.
The Georgian wire glazing that forms part of the compartmentation on 1st, 7th and 9th
floor is either loose or incorrect silicone and metal gaskets fitted. Ensure correct fire
retardent glazing gaskets are fitted.
A Asset Management
22
23
24
25
26
27
28
29
30
31
32
33
34
There items stored in communal lobby areas. Remove Items.Flat has metal
security gate fitted within landlords demise. Ensure theis is removed to maintain
escape route.
A
Resident
Engagement/Client
Servs
35
36
Premises:
Question Action to be taken Priority Ownership Additional Comments / Review Notes
1-73 Dunedin House Manwood Street E16 2LA
37
38
39
40
41
42
43
44
45
46 There is a damaged "No smoking "sign on 11th floor B Resident
47
48
49
50
51
52
53
54
55
Photographs
Premises:
1.) Front Elevation 2.) Firemans Switch 3.) Dry Riser
4.) Bin Chute Room 5.) Bin Chute 6.) Dry Riser/tank room door
7.) Dry Riser 8.) Flat Entrance Door 9.) Flat Entrance Door
10.) Flat Entrance Door 11.) Flat Entrance Door 12.) Compartmentation Doors
1-73 Dunedin House Manwood Street E16 2LA
Photographs
Premises: 1-73 Dunedin House Manwood Street E16 2LA
13.) Compartmentation Doors 14.) Compartmentation Doors 15.) Concierge Door
16.) Concierge Pat tested items 17.) Items stored in staff cpd 18.) Items stored in staff cpd
19.) Items stored in staff cpd 20.) Extinguishers in concierge 21.) Extinguisher service date
22.) Extinguishers in concierge 23.) Lift Motor room door 24.) Lobby riser
Photographs
Premises: 1-73 Dunedin House Manwood Street E16 2LA
25.)Grnd floor electric intake door 26.) Extraction plant 27.) Items stored in tank room
28.) Breach in compartmentation 29.) Items stored in ext stairs 30.) Fire alarm panel
31.)Security Grill fitted 32.) Bin Store doors 33.) Bin Store room
34.) External Exit Door 35.) Paint Delaminating 36.) Electric intake room door
Photographs
Premises: 1-73 Dunedin House Manwood Street E16 2LA
37.) Items stored in lobby area 39.) Smoke detection in lobby 40.) Fire extinguisher out of date
41.)Timber in bin chute area 42.) Damaged "No smoking" Sign 43.)Georgian glazing gasket