advances in sprinkler technology - international · pdf fileadvances in sprinkler technology...

164
Advances in Sprinkler Technology

Upload: buitram

Post on 07-Feb-2018

215 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

Advances inSprinkler Technology

Page 2: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Modules

• Evolution of FM Global Fire Protection Standards

• Changes in Terminology for Sprinkler Categories

• Movement Away from Density and Demand Area

• Data Sheet 2-0 Installation Guidelines for Automatic Sprinklers

• Data Sheet 8-9 & Changes in Protection Tables

Page 3: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Page 4: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

Evolution of FM Global Fire Protection Standards

Page 5: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Who is FM Global?

• FM Global was established in 1835

• Zachariah Allen, New England mill owner

• Factory Mutual Insurance Company

Page 6: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Who is FM Global?

Page 7: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Who is FM Global?

• FM Global’s market share includes:– 45% of the Fortune 100 companies– 42% of the Fortune 500 companies

• FM Global is a recognized industry leader in property insurance

• FM Global has been recognized as:– Best Global Property Insurer– Best Global Property Insurer – North

America

Page 8: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Research FM ApprovedProducts Engineering

Majority of Losses are Preventable

Practical and ProvenGlobal Loss Prevention Engineering Solutions

Page 9: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Investment in Engineering & Research• World’s largest full-scale fire test lab

and research campus• Dedicated to the study of loss

prevention

Page 10: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Materials Lab

Electrical Lab

Hydraulics Lab

Large Burn Lab Improvements• Two Movable Ceilings• Humidity Control

Multimedia Center

Fire Technology Lab

Natural Hazards Lab• 70,000 ft2

• EQ Lab

Research Campus

Page 11: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Full Scale Fire Tests

• Two moveable ceilings up to 60 ft (18.3 m)

• Test storage arrays from 5 ft (1.5 m) to 55 ft (16.8 m)

Page 12: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Example of Full Scale Fire Testing• Evaluate existing European Codes at

that time• Protection of rack storage • 55 ft (16.5 m) rack storage • 60 ft (18 m) ceiling height• Cartoned unexpanded plastic• Standard response in-rack sprinklers

Page 13: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

55 ft (16.5 m) rack storage –test fails

Page 14: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

55 ft (16.5 m) rack storage –test passes

Page 15: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Confidence that a product installed in your facility will perform as intended!

Reducing your Risks

FM Approvals

Page 16: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

FM Approvals test products ….

Page 17: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

FM Approvals Testing Standards

• Over 250 standards

• Based on Research

• Publicly available on www.fmapprovals.com

• ANSI, ASTM, SCC, BSI Recognized

Page 18: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

FM Approved Products ….

• Over 50,000 products• Publicly available for free – on line • Recognized world wide

Page 19: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

What are FM Global Data Sheets?

Page 20: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

What are FM Global Data Sheets?

• Offer best advice on how to minimize property damage and business interruption

• Written by the Engineering Standards division

• Supported by the Research division • Used to evaluate loss potentials at our

insured clients• Recommendations offered when hazards

encountered are not protected in accordance with appropriate data sheet

Page 21: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

History of FM Global & Fire Protection

Page 22: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

2010

Page 23: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

History of FM Global & Fire Protection

Page 24: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Pipe Schedule

• Pipe schedule was categorized based on occupancy hazard as either:– Light Hazard– Ordinary Hazard– Extra Hazard

Page 25: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Pipe Schedule

• Sizing requirements for an ordinary hazard pipe schedule sprinkler system:

Page 26: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Change in Industrial Practices

End of World War II:– Steel construction for buildings– Forklift trucks– Storage racks constructed of steel– Increase in plastic materials stored

Page 27: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

FM Global Research on Sprinkler Protection

Page 28: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Standard Spray Sprinkler K5.6 (K80)

Standard Spray Sprinkler

Density over Demand Area design concept

Page 29: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Conventional and Spray Sprinklers

Page 30: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

20101950’s

Conventional

Spray

Page 31: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Standard Spray Sprinkler K5.6 (K80)

Large Orifice Sprinkler

Large Orifice Sprinkler

K8.0 (K115)

Page 32: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

20101950’s

Conventional

SprayLargeOrifice

Standard

Page 33: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

1970’s Research Projects

• “Residential” sprinkler & quick response thermal element

• Water penetration through fire plume (fire suppression)

Page 34: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Resulted in -

• The K11.2 (K160) “Large-Drop” Sprinkler • Design format changed - Number of

sprinklers at minimum pressure

Installation guidelines for these sprinklers evolved into DS 2-7

Page 35: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

20101950’s

Conventional

SprayLargeOrifice

Standard

1970’s

Residential

LargeDrop

Page 36: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Large Drop Sprinkler

• Large Drop Sprinkler improved protection options but…

• Fire tests showed suppression not always possible

Page 37: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

This lead to …

• First Early Suppression Fast Response (ESFR) Sprinkler

• K14.0 (K200) pendent

Page 38: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Am

ount

of w

ater

Time

RDD

ADD

Suppressionachieved inthis zone

ADD > RDD Concept

RTI

Page 39: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Example of ADD and deflector design

Page 40: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Example of ADD Testing and Deflectors

Page 41: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Suppression Mode Sprinkler Installation Guidelines

Page 42: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

20101950’s

SprayLargeOrifice

Standard

1970’s

Residential

LargeDrop

ESFR

1980’s

Conventional

Page 43: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Advances in Sprinkler Technology

• Orifice size increasing• Various Orientations• Different Deflector

designs evolved

• Various Finishes• Quicker response

time• Area Spacing EC

K5.6 (K80) K25.2 (K360)

Page 44: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

We had -• A bunch of Control Mode Density Area (CMDA)

sprinklers…– Standard Orifice (1/2”) Sprinkler– Large Orifice (17/32”) Sprinkler– Extra Large Orifice (ELO) Sprinkler– Very Extra Large Orifice (VELO) Sprinkler– Really Ginormous Orifice (RGO) Sprinkler

Installation guidelines for these sprinklers evolved into DS 2-8N

Page 45: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

We had …

• A bunch of Control Mode Specific Application (CMSA) sprinklers – K16.8 (K240), K19.6 (K280), K25.2 (K360),

K25.2EC (K360EC)

Page 46: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

We had …

• A bunch of Suppression Mode (SM) sprinklers– K14 (K200) upright, K16.8 (K240)upright,

K16.8 (K240) pendent, K22.4 (K320) pendent, & K25.2 (K360) pendent

Installation standard for these sprinklers was DS 2-2

Page 47: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

1950’s

SprayLargeOrifice

Standard

1970’s

Residential

LargeDrop

ESFR

1980’s

Conventional

1990’s 2010

Page 48: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

So where we were in 2009?

• Three different sprinkler categories• Three sets of installation guidelines• Terminology implies performance• Two different design formats

Page 49: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

So where we were in 2009?

• Terminology:• CMDA – Control Mode Density Area• CMSA – Control Mode Specific

Application• SM – Suppression Mode

Page 50: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

1950’s

SprayLargeOrifice

Standard

1970’s

Residential

LargeDrop

ESFR

1980’s

Conventional

1990’s 20102000’s

SM

CMSA

CMDA

Page 51: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

Changes in Terminology for Sprinkler Categories

Page 52: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Changes in Terminology for Sprinkler Categories• Sprinkler compatibility with occupancy

hazards unclear• Old terminology misleading • Actual performance can be otherwise

– Control Mode sprinklers → fire suppression– Suppression Mode sprinklers → fire control

Page 53: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Control Mode Sprinkler Achieves Suppression

Page 54: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Suppression Mode Achieves Control

Page 55: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

CMDA vs. CMSA – is there a difference?

CMDA CMSA

Page 56: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

CMDA and CMSA Sprinkler Tests• Objective:

– Determine through large-scale fire testing if the distinction between CMDA Sprinklers and CMSA Sprinklers can be eliminated.

Page 57: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

CMDA and CMSA Sprinkler Tests• Test Plan:

– Full-Scale Fire Test Comparison

– 16 Total Tests (8 Comparison Tests)

– Open Frame Double-Row Racks with Class 2 or Standard Plastics

– K11.2 (K160), Upright Type

– Low Temperature Nominal 160 F (70 C)

– Standard Response

Page 58: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

CMDA and CMSA Sprinkler Tests

• Total of 8 Comparison Tests (16 Tests Total) Between CMDA and CMSA– Open Sprinkler Differential for Acceptable

Comparisons:• 1 Sprinkler Differential: 3 Comparison Tests• 3 to 4 Sprinklers Differential: 2 Comparison Tests• 10 Sprinklers Differential: 2 Comparison Test• 1 Test Series where both tests terminated early

due to loss of fire control

Page 59: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

CMDA and CMSA Sprinkler TestsTest Conclusions• Ultimate Conclusion: CMDA = CMSA

Provided That:– K-factor– Orientation– Nominal Temperature Rating– Nominal RTI RatingAre The Same

Page 60: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Changes in Terminology for Sprinkler Categories• New terminology based on intended use:

– Storage sprinkler– Non-storage sprinkler– Special protection sprinkler

used by sprinkler manufacturers too

• Approval Guide will include both sets of terminology

Page 61: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Changes in Terminology for Sprinkler Categories• CMDA • CMSA • SM

Storage sprinklers

• Single/common design method• Single/common installation method• Reduces number of protection tables

needed

Page 62: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinkler Development

1874

1881

1950’s

SprayLargeOrifice

Standard

1970’s

Residential

LargeDrop

ESFR

1980’s

Conventional

1990’s 20102000’s

SM

CMDA

Storage

NonStorage

SpecialProtection

CMSA

Page 63: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

Movement Away from Density and Demand Area

Page 64: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Movement away from Density and Demand Area• Prior to 1980’s pipe schedule design• Concept of density born in early 1960s

but did not become commonplace until the 1980’s

• Research testing over the past few years has demonstrated that design density is not the most important factor for sprinkler performance

Page 65: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Density

• What is density?• Average volume of

water hitting the floor over the area of coverage of a sprinkler (rainfall)

• mm/min (sq. m)

Page 66: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Density

• How is density used?– Converted into minimum pressure and flow

at sprinklerQ = D x S x LP = [Q/K]2

Q = K√PQ = Sprinkler flow in gpm (Lpm)P = Sprinkler pressure in psi (bar)D = Density in gpm/ft2 (mm/min)S = Spacing of sprinklers on branchlines ft (m)L = Spacing of sprinklers between branchlines ft (m)K = K-factor (size of sprinkler opening) in gmp/psi0.5 (Lpm/bar0.5)

Page 67: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Density and Sprinkler Spacing

• Density → minimum flow and pressure at sprinkler

• Q = D x S x L, gpm (Lpm)• P = [D x S x L / K]2, psi (bar)

Reducing sprinkler spacing in design can reduce design flow and pressure

Page 68: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Demand Area

• Area at ceiling in which all sprinklers expected to operate during fire

Page 69: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Density/Demand Area Design

• Flow rate per sprinkler • For all sprinklers in design area• Allowance for hydrants• Water supplies - sprinklers and

hydrants for minimum duration

Design Area

Minimum flowrequired fromsprinklers

Page 70: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Density/Demand Area Format

• Full scale fire tests conditions:– Upright standard response sprinkler– Use smallest K-factor allowed for hazard area– Use maximum allowable area spacing of

sprinkler• Protection tables → driven by least

efficient sprinkler

Page 71: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Movement away from Density and Demand Area

Page 72: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K5.6 (K80)

K25.2 (K360)

K Factor

Page 73: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

SR QR

Response Time Index

Page 74: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

SR QR

Response Time Index

Page 75: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

SR QRSRQR

Response Time Index

Page 76: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Orientation

Pendent Upright

Page 77: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Temperature

286 F (140 C)160 F (70 C)

Page 78: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

20 ft (6 m)

cartoned unexpanded plastic

30 ft (9 m)

Movement away from Density and Demand Area

Page 79: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Which test will perform better?

Movement away from Density and Demand Area

Test 1 • 8 ft aisle • 0.8 gpm/ft2

(32 mm/min)

Test 2• 4 ft aisle• 0.6 gpm/ft2

(24 mm/min)

Page 80: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Page 81: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Movement away from Density and Demand Area

Test 1 - 25 Sprinklers• Upright sprinkler• K11.2 (K160)• Standard Response• Standard Spacing

10 ft x 10ft (3 m x 3 m)

Test 2 - 1 Sprinkler• Pendent sprinkler• K25.2 (K360)• Quick Response• Extended Coverage

14 ft x 14ft (4.2 m x 4.2 m)

Differences between both tests

Loss Expectancy ~ $1,250,000

Loss Expectancy ~ $100,000

Page 82: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Movement away from Density and Demand Area• What does this test show?

– Larger K factor → larger droplets – Orientation → water momentum– Faster response time → smaller fire to

control– Density

Page 83: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Graphs Plots

Page 84: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K11.2 (K160) Pendent @ 60 gpm (230 L/min)

K11.2 (K160) Upright @ 100 gpm (380 L/min)

10 sprinklers operated 32 sprinklers operated

Orientation

Page 85: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K factorK16.8 (K240)@ 80gpm (300 L/min)

K11.2 (K160)@ 80 gpm (300 L/min)

15 sprinklers operated 29 sprinklers operated

Page 86: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K14.0 (K200) QR @ 100 gpm (380 L/min)

K14.0 (K200) SR @ 120 gpm (450 L/min)

11 sprinklers operated 17 sprinklers operated(uncontrolled – test terminated)

Response Time Index

Page 87: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K11.2 (K160) 155 F (68 C)80 gpm (300 L/min)

K11.2 (K160) 286 F (140 C)80 gpm (300 L/min)

24 sprinklers operated(controlled)

43 sprinklers operated(uncontrolled)

Temperature Rating

Page 88: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Empty Plastic Tote Fire Tests

FRONT ELEVATION VIEW

4.1 m (13.5 ft)

N

2.4 m (8 ft)

Plastic Totes (2x8x3 Main)

13.5 ft (4.1 m) high rack storage

30.0 ft (9.0 m) ceiling

ELEVATION VIEW

PLAN VIEW

Page 89: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K16.8 (K240)Upright

Quick Response10 x 10 ft (3 x 3 m)50 psi = 120 gpm

(3.5 bar = 454 L/min)

K14.0 (K200)Pendent

Standard Response10 x 10 ft (3 x 3 m)75 psi = 120 gpm

(5.2 bar = 454 L/min)

Empty Plastic Tote Fire Tests

Page 90: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K16.8 (K240)Upright

Quick Response

K16.8 (K240)Upright

Quick Response

K14.0 (K200)Pendent

Standard Response

K14.0 (K200)Pendent

Standard Response

Empty Plastic Tote Fire Tests

Page 91: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Empty Plastic Tote Fire Tests

Page 92: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Empty Plastic Tote Fire Tests

Page 93: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Empty Plastic Tote Fire Tests

Page 94: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

K16.8 (K240)Upright

Quick Response

K16.8 (K240)Upright

Quick Response

K14.0 (K200)Pendent

Standard Response

K14.0 (K200)Pendent

Standard Response

20 Sprinklers 2,400 gpm

(9,085 L/min)

6 Sprinklers720 gpm

(2,725 L/min)

Empty Plastic Tote Fire Tests

Page 95: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

1970’s Sprinkler Technology

• 20 ft (6.0 m) Storage• 30 ft (9.0 m) Ceiling• Class 4 Commodity• Open-Frame Double-Row Rack• 8 ft (2.4 m) Wide Aisle• K5.6 (K80) Upright Ceiling Sprinkler• Standard-Response• 0.6 gpm/ft2 (24 mm/min)

Page 96: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

1970’s Sprinkler Technology

82 sprinklers open

Page 97: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

2000’s Sprinkler Technology

• 20 ft (6.0 m) Storage• 30 ft (9.0 m) Ceiling• Cartoned Unexpanded Plastic Commodity• Open-Frame Double-Row Rack• 4 ft (1.2 m) Wide Aisle• K25.2EC (K360EC) Pendent Ceiling

Sprinkler• Quick-Response• 0.6 gpm/ft2 (24 mm/min)

Page 98: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

2000’s Sprinkler Technology

1 sprinkler opens

Page 99: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Sprinklers with the proper attributes can: • Provide Better Protection• More Cost Effective• More Sustainable

Page 100: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

Data Sheet 2-0Installation Guidelines for Automatic Sprinklers

Page 101: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Why Data Sheet 2-0

• Need to update sprinkler terminology• Opportunity to simplify and improve• Single global installation standard• Remove redundant topics

Based on North American Standards

Total 341 pages

Page 102: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 2-0 - Structure

• 1.0 Scope– 1.1 Changes– 1.2 Superseded Information

• 2.0 Loss Prevention Recommendations– 2.1 Nonstorage Sprinklers– 2.2 Storage Sprinklers– 2.3 Special Protection Sprinklers– 2.4 Sprinkler System Types– 2.5 Sprinkler Piping: Connection, Hanging,

and Bracing– 2.6 Sprinkler System Components

Only reference section relevant for your occupancy

Common to any occupancy

Page 103: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 2-0 - Structure

– 2.7 Plan Review of Sprinkler Systems– 2.8 Sprinkler System Acceptance Tests – 2.9 Operation and Maintenance – 2.10 Ignition Source Control

• 3.0 Support for Recommendations– 3.1 Loss History

• 4.0 References– 4.1 FM Global– 4.2 Other

New Guidance for Contractors

Go to DS 2-81 and DS 10-3

Page 104: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 2-0 Changes

• Sprigs no longer required – Originally recommended to prevent pipe

shadow– Testing indicated that not an issue– Cost savings by removing requirement

Riser Nipple or Sprig

Page 105: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 2-0 Changes

• Sprigs no longer required• Remove area limitation per sprinkler

system– Driven by pipe schedule limitations– No hydraulic basis– Reduce number of risers and control valves

needed can reduce overall cost

Page 106: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 2-0 Changes

• Sprigs no longer required• Remove area limitation per sprinkler

system• Requirements for anti-freeze• Guidelines for objects that obstruct

sprinklers

Page 107: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Non-storage sprinklers • Obstruction guidance has not changed

– Obstruction if object over 4 ft (1.2 m) wide – Solid beam construction may need

sprinklers in every channel

Page 108: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Obstruction to discharge patternPart of structure, sprinkler positioning should be arrangedto accommodate. Some exceptions.

Page 109: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Obstruction to discharge pattern

Non Storage Sprinklers - < 1.2m OK, >1.2m need AS underStorage Sprinklers obstruction start at 20mm up to 600mm

Page 110: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

• Storage Sprinklers– Guidelines in DS 2-0 generally no change

from DS 2-2 except that also applicable to standard response sprinklers

– All upright sprinklers follow previous guidance from DS 2-2 (DS 2-2, 2-7 requirements have not changed)

Page 111: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

• Storage Sprinklers– All pendent sprinklers follow previous

guidance from DS 2-2 except for:• New figures with relaxed requirements (Fig 35 &

37)

Page 112: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Previously

24 inches

(600mm)

DS 2-0 Obstruction Guidelines

Page 113: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Previously36 inches(900mm)

DS 2-0 Obstruction Guidelines

Page 114: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

• Storage Sprinklers– All pendent sprinklers follow previous

guidance from DS 2-2 except for:• New figures with relaxed requirements (Fig 35 &

37)• Additional figures to support text (Fig 38, 39, 40)

Page 115: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Page 116: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Page 117: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Page 118: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

• Storage Sprinklers– All pendent sprinklers follow previous

guidance from DS 2-2 except for:• New figures with relaxed requirements (Fig 35 &

37)• Additional figures to support text (Fig 38, 39, 40)• Obstructions ≤ ¾ in. (20 mm) wide (Fig 34)

Page 119: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Page 120: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

• Storage Sprinklers– All pendent sprinklers follow previous

guidance from DS 2-2 except for:• New figures with relaxed requirements (Fig 35 &

37)• Additional figures to support text (Fig 38, 39, 40)• Obstructions ≤ ¾ in. (20 mm) wide (Fig 34)• New options to deal with existing obstructions

– Saves on cost of installing barriers and maintaining

Page 121: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Page 122: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 2-0 Obstruction Guidelines

Page 123: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Automatic Smoke and Heat Vents

Page 124: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Exhaust and Ridge Vents

Page 125: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Air Blowers

• False Ceiling with protection under• Flame Detection covering 3m radius for all affected

sprinklers and/or fire plume• Heat/Line detection in racks under affected sprinklers• (Alt. Sol. Aspirated Smoke Detection shut all blowers down)

Page 126: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Draft Curtains

• DS 1-19 discrepancy with old DS 2-2• 600mm deep parallel with roof is

acceptable – next revision will cover

600mm

Hard up against the underside of roof

Page 127: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Obstructed and Unobstructed Ceilings? Typical Australian Warehouse

• Purlinsexceed limit of 100mm

• Exception applies

QR330 or425mm

Page 128: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Distance Sprinkler to underside of ceiling 2.2.3.4• Confusion with uppermost and

lowermost portion of ceiling wording

x

y

Use a ifX = min 75mmX > 2 x yZ = max 75mmOtherwise use bz ab

Page 129: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Distance Sprinkler to underside of ceiling 2.2.3.4 - Virtual Ceilings?

Max allowed

Ceiling Jet

Page 130: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Mezzanines and walkways

• Preference – Solid with sprinklers• Provide QR sprinklers same K factor,

orientation, spacing and pipe size as ceiling

• Exceptions– Min 70% open– Max 6mm thick– Max only 1 grid– Min 900mm clearance– No possibility of materials falling and

obstructing ceiling sprinklers

Page 131: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

What is the impact of pushing the limits in DS 2-0• Roof Slope• Building Height/Storage Height• Clearance from roof• Obstructions at ceiling• Obstructions below sprinklers• Spacing• Design Number of Sprinklers• Commodity (Flammable Liquids)

Page 132: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

What is the impact of pushing the limits in DS 2-0• Simple advice – DON’T• We cannot tell you what the impact

would be!• Under no circumstances alter the

required design criteria• Final decision – Certifier and Building

Surveyor

Page 133: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

• Note Nice even flue spacing 150mm long. 190mm transverse

• Homogeneous and uniform commodity

• Placement of ignition

• Position of sprinklers

• Flat Ceiling• Repeatability• Unrealistic

Page 134: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Example of absolute limit

• K14 and K 16.8 in 13.5m building

• Offset ignition –overtaxed the system

• I level of in rack sprinklers mandatory

• K 22 and K 25 sprinklers OK

• K 14, K16.8 lower building height 12m without in rack sprinklers

Page 135: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Spare Sprinklers

• Spares for each type installed including applicable wrenches

• Min needed of each type based on their largest demand area– Say manufacturing design is for 25

sprinklers – need 25– Say for warehousing design is for 15

sprinklers – need 15 of those

Page 136: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

Data Sheet 8-9 & Changes in Protection Tables

Page 137: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Existing DS 8-9

• Three different protection tables– One for CMDA sprinklers– One for CMSA sprinklers, and– One for Suppression Mode sprinklers

Page 138: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Existing DS 8-9

• Three different protection tables• Two different design methods

– Density / Operating Area for CMDA sprinklers

– No. of Sprinklers / Minimum Operating Pressure for CMSA & SM sprinklers

Page 139: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Existing DS 8-9

• Three different protection tables• Two different design methods• Design dependent on the least efficient

sprinkler

Page 140: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Why Revise Data Sheet 8-9

• Need to update sprinkler terminology• Need to replace density in design

criteria• Opportunity to simplify and improve

Page 141: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• Grouping of commodity hazard

– Class 1 – 3– Class 4 – Cartoned Unexpanded Plastics– Cartoned Expanded Plastics– Uncartoned Unexpanded Plastics– Uncartoned Expanded Plastics

Class 3Cartoned Expanded

Plastics

Page 142: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Why group Class 1 up through Cartoned Plastics?• Back in 2006, a K5.6 (K80) sprinkler

protecting open-frame DRR to 15 ft (4.5 m) under a 30 ft (9.0 m) ceiling requires the following pressures at most remote sprinkler:– Class 1: 12 psi– Class 2: 17 psi– Class 3: 22 psi– Class 4: 39 psi– Cartoned Plastics: 115 psi– Cartoned Plastics (2008): 204 psi

Page 143: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Why group Class 1 up through Cartoned Plastics?• Cartoned plastics in open-frame DRR to

15 ft (4.5 m) under a 30 ft (9.0 m) ceiling requires 0.80 gpm/ft2 (32 mm/min) over 3,000 ft2 (280 m2).– K5.6 (K80) AS: 115 psi– K8.0 (K115) AS: 100 psi– K11.2 (K160) AS: 50 psi– K16.8 (K240) AS: 22 psi– K25.2 (K360) AS: 10 psi

Page 144: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• Number of protection tables reduced

Page 145: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• Number of protection tables reduced • → all protection options in one table• Design based on actual performance • Makes it easier to see which are better

options

Page 146: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• Protection tables based on

– No. heads at minimum pressure (6 to 24)– Ceiling height– RTI (standard or quick response)– Orientation (upright or pendent)– Sprinkler K factor (~ nozzle size)

Page 147: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• No storage heights in tables

– promote flexibility– insignificant pressure differential

Page 148: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• No aisle width in tables

– design to minimum aisle width– promote flexibility by not locking aisle

width

Page 149: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• No favorable factors

– difficult to maintain over life of building

Page 150: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Data Sheet 8-9 & Changes in Protection Tables• The number of sprinklers in the design

criteria will lead to– Hose stream demand– Water supply duration

Page 151: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

In rack sprinklers

• Layout and positioning rationalised and simplified

• Fewer levels required

• Flow charts and plan view diagrams

7.5m

6.0m

4.5m

Page 152: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

In rack sprinklers

• Layout and positioning rationalised and simplified

• Fewer levels required

• Flow charts and plan view diagrams

7.5m

6.0m

4.5m

Page 153: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

In rack sprinklers

• Two positions (Plan view)– EO Every other flue space– E Every flue space

• Very High Hazard – Flue and Face• Scheme 8-9A Exceptional Hazards –

Aerosols, High Flash Flammable Liquids etc

Page 154: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

In rack sprinklers

Rack Storage

In-rack Sprinkler

Minimum clearance 150mm – deflector to top of storage

Page 155: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Excessive Clearance

> 6m

OK

Page 156: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Excessive Clearance

> 6m

NeedsIn-rack AS

Page 157: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Excessive Clearance

• False Ceiling• In Rack Sprinklers

– If already exist – extra level at top of rack– If ceiling only protection – section 2.3.4.6

and 2.3.4.7• If building too high – same solution

applies• Does not apply when ceiling only

options available

Page 158: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Ceiling Slopes

• Quick Response – max 10 degrees• Standard Response

– Ceiling only – max 10 degrees– In rack Sprinklers – Max 20 degrees

• Otherwise– False Ceiling– For Rack Storage treat as for excessive

clearance• Slope > 5 degrees – locate sprinkler

within 900mm of peak

Page 159: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Flue Spaces – 2.2.3.1.2, 2.2.3.1.4Issue with Multiple row racks• Provide 150mm

longitudinal flue every 4.8m

• Problem Area • Recommendation• Further Research• Discussing with

Rack Manufacturers

Page 160: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

Tanks Size per FM Standards?

• Highest sprinkler demand at site• Flow of most remote sprinkler at

specified pressure• Times the number of sprinklers• Plus 10% • Times duration• Or• Highest calculated most remote

demand times duration

Page 161: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

AnomoliesData Sheet 8-9 & Changes in Protection Tables

Page 162: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

DS 8-9 Future Vision (next 5 years)• Eliminate the 10 ft. limitation on storage

above the highest in-rack sprinklers • Establish new in-rack sprinkler protection

schemes based on– Sprinkler K factor– Available pressure

• Eliminate requirement to balance ceiling and in-rack demands

• Add new technology, research and testing

Page 163: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

New Technology and Cost of Installations• Compared to previous standards the

new technology and design philosophy leads to:– Lower number of sprinklers in design

requirements– Lower hose demands – Lower duration demands

Page 164: Advances in Sprinkler Technology - International · PDF fileAdvances in Sprinkler Technology • Orifice size increasing • Various Orientations • Different Deflector designs evolved

© 2010 FM Global. All rights reserved.

The Bottom Line…

Through these changes FM Global is poised to provide our clients with the most effective protection options, which are not only simpler and cheaper to install, but a more sustainable choice.