ag_ag2004-12_20040823
TRANSCRIPT
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 1/22
SCHWEITZER ENGINEERING LABORATORIES2350 NE Hopkins Court • Pullman, WA • 99163-5603 • USAPhone: (509) 332-1890 • Fax: (509) 332-7990E-mail: [email protected] • Internet: www.selinc.com
Application Guide Volume III AG2004-12
Implementation of Voltage, Frequency,
and Power Elements in the SEL-451 RelayUsing SELOGIC Control Equations
Jacob Reidt
INTRODUCTION
The SEL-451 Relay has the speed, power, and flexibility to combine the control and protection ofmany substation devices into one economical system. Programmable logic and math operatorsavailable in the SEL-451 allow the relay to implement a number of functions common todistribution relaying: under- and overvoltage elements, under- and overfrequency elements, andpower elements.
Phase under- and overvoltage elements are useful for the creation of a number of protection andcontrol schemes such as:
• Torque control for the overcurrent protection.
• Hot-bus (line), dead-bus (line) recloser control.
• Blown transformer high-side fuse detection logic.
• Trip/alarm or event report triggers for voltage sags and swells.
• Undervoltage load shedding scheme.
• Control schemes for capacitor banks.
Independently set positive-, negative-, and zero-sequence voltage elements provide for additionalprotection and control applications including transformer bank single-phase trip schemes anddelta-load back-feed detection scheme for dead-line recloser control.
Under- and overfrequency elements detect true frequency disturbances. Use a time-delayedoutput of these elements to shed load or trip local generation. Phase undervoltage supervisionprevents undesired frequency element operation during faults. Use multiple under- andoverfrequency levels to implement an internal multistage frequency trip/restore scheme at eachbreaker location. This avoids the cost of wiring a complicated trip and control scheme from aseparate frequency relay.
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 2/22
2 SEL Application Guide 2004-12 Date Code 20040823
Single-phase and three-phase power elements can be enabled to detect real or reactive power inthe forward or reverse directions. With SELOGIC® control equations, the power elements provide
a wide variety of protection and control applications. Typical applications are as follows:
• Overpower and/or underpower protection and control.
•Reverse power protection and control.
• VAR control for capacitor banks.
PROTECTION ELEMENTS
Programmable logic and math operators available in the SEL-451 allow the relay to implementthe protection elements outlined in the previous section.
Method
Analog registers hold filtered measurements taken from the SEL-451 potential and current inputs.
The SEL-451 has six ac current inputs and six ac voltage inputs available for protection, allowingfor a number of different connections to the power system. This application guide was writtenusing a single circuit breaker connection (see the AC/DC Connection Diagrams subsection inSection 2 of the SEL-451 User’s Guide).
Protection Math Variables and Automation Math Variables can hold setting values or measuredanalog quantities. In this application guide, we use the Protection Math Variables to holdmeasured analog quantities or mathematically adjusted analog quantities, and the AutomationMath Variables are used to hold constants used as element settings. Protection Math Variablesare processed every relay processing interval, so these stored analog quantities accurately reflectthe system parameters. Automation Math Variables are processed as time permits (but at leastonce per second). Automation Math Variables are therefore ideal for storing fixed setting values,whereas, Protection Math Variables are better suited for storing quantities that can change quicklyor must be rapidly evaluated.
Driven by the free-form logic settings, the SEL-451 produces logic results through mathmanipulations and comparisons of the measured analog signals to settings. The relay can usethese logic results in intermediate logic, such as Protection SELOGIC Variables or ProtectionConditioning Timers. Math comparisons, manipulations, and logic developments occur in theSEL-451 free-form logic setting area. The logic results generated in this free-form area can beprogrammed to operate the trip equation, output contacts, front-panel targets, and front-panelLEDs. The following sections explain how to build these logic settings.
Analog Inputs
Table 1: Analog Quantities Used
Label Description Units
VAFIM, VBFIM, VCFIM Phase filtered instantaneous voltage magnitude V secondary
3V0FIM Zero-sequence instantaneous voltage magnitude V secondary
3V2FIM Negative-sequence instantaneous voltage magnitude V secondary
V1FIM Positive-sequence instantaneous voltage magnitude V secondary
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 3/22
Date Code 20040823 SEL Application Guide 2004-12 3
Label Description Units
LIAFIM, LIBFIM, LICFIM Phase filtered instantaneous current magnitude A secondary
PA_f, PB_f, PC_f Phase fundamental real power MW primary
QA_f, QB_f, QC_f Phase fundamental reactive power MVAR primary
3P_f Three-phase fundamental real power MW primary3Q_f Three-phase fundamental reactive power MVAR primary
FREQ Measured system frequency Hz
Voltage Elements
Table 2: Voltage Elements Settings and Settings Ranges
Device
Voltage Element
(Relay Word Bits)a
Operating
Voltage Pickup Settingb /Range
c
See
Figure
PSV08 VA PSV09 V
B
PSV10 VC
27
PSV11 := PSV08 ANDPSV09 AND PSV10
AMV0050.00–300.00 V secondary
PSV01 VA
PSV02 VB
PSV03 VC
PSV04 := PSV01 ANDPSV02 AND PSV03
AMV0010.00–300.00 V secondary
Figure 1
PSV05 3V0 AMV002
0.00–300.00 V secondary
PSV06 V2 AMV003
0.00–200.00 V secondary
59
PSV07 V1 AMV004
0.00–300.00 V secondary
Figure 2
a Example Protection SELOGIC Variables (PSVs) are shown here. The SEL-451 has 64 PSVs tochoose from (PSV01–PSV64). Select these variables to avoid unintentional duplication.
b Example Automation Math Variables (AMVs) are shown here. The SEL-451 has 256 AMVs tochoose from (AMV001–AMV256). Select these variables to avoid unintentional duplication.
c Pickup setting ranges are not defined in the SEL-451. The pickup settings are Automation MathVariables that are not constrained by any boundary conditions. The ranges given are suggestionsbased on the SEL-351-7 and SEL-351S-7 ranges for the corresponding pickup setting. A valueexceeding this range could be assigned to the corresponding Automation Math Variable ifnecessary.
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 4/22
4 SEL Application Guide 2004-12 Date Code 20040823
PSV08
(27A)
PSV09
(27B)
PSV10
(27C)
PSV11
(3P27)
PSV01
(59A)
PSV02
(59B)
PSV03
(59C)
PSV04
(3P59)
AMV005
(27PP)
PMV01 (V A
)
PMV02 (VB)
PMV03 (VC)
AMV001
(59PP)
PSV01 := PMV01 > AMV001
PSV02 := PMV02 > AMV001
PSV03 := PMV03 > AMV001
PSV04 := PSV01 AND PSV02 AND PSV03
PSV08 := PMV01 < AMV005
PSV09 := PMV02 < AMV005
PSV10 := PMV03 < AMV005
PSV11 := PSV08 AND PSV09 AND PSV10
Figure 1: Single-Phase and Three-Phase Voltage Elements
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 5/22
Date Code 20040823 SEL Application Guide 2004-12 5
AMV002
(59NP)
PSV05
(59N)
PSV06
(59Q)
PSV07
(59V1)
AMV003(59QP)
AMV004
(59V1P)
PMV04 (3V0)
PMV05 (V2)
PMV06 (V1)
+
+
+
PSV05 := PMV04 > AMV002
PSV06 := PMV05 > AMV003
PSV07 := PMV06 > AMV004
Figure 2: Sequence Voltage Elements
Accuracy
Pickup: ±2 V and ±5% of setting
Transient Overreach: ±5% of setting
Voltage Element Operation
Note that the voltage elements are a combination of undervoltage (Device 27) and overvoltage(Device 59) type elements. Undervoltage elements (Device 27) assert when the operating voltagegoes below the corresponding pickup setting. Overvoltage elements (Device 59) assert when theoperating voltage goes above the corresponding pickup setting.
Undervoltage Element Operation Example
Refer to Figure 1 (top of the figure).
Pickup setting AMV005 is compared to the magnitudes of the individual phase voltages VA, V
B,
and VC. The logic outputs in Figure 1 are the following Relay Word bits:
PSV08 = 1 (logical 1), if VA < pickup setting AMV005
= 0 (logical 0), if VA ≥ pickup setting AMV005
PSV09 = 1 (logical 1), if VB < pickup setting AMV005
= 0 (logical 0), if VB ≥ pickup setting AMV005
PSV10 = 1 (logical 1), if VC < pickup setting AMV005
= 0 (logical 0), if VC ≥ pickup setting AMV005
PSV11 = 1 (logical 1), if all three Relay Word bits PSV08, PSV09, and PSV10 are asserted(PSV08 = 1, PSV09 = 1, and PSV10 = 1)
= 0 (logical 0), if at least one of the Relay Word bits PSV08, PSV09, and PSV10 isdeasserted (e.g., PSV08 = 0)
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 6/22
6 SEL Application Guide 2004-12 Date Code 20040823
Overvoltage Element Operation Example
Refer to Figure 1 (bottom of the figure).
Pickup setting AMV001 is compared to the magnitudes of the individual phase voltages VA, V
B,
and VC. The logic outputs in Figure 1 are the following Relay Word bits:
PSV01 = 1 (logical 1), if VA > pickup setting AMV001
= 0 (logical 0), if VA ≤ pickup setting AMV001
PSV02 = 1 (logical 1), if VB > pickup setting AMV001
= 0 (logical 0), if VB ≤ pickup setting AMV001
PSV03 = 1 (logical 1), if VC > pickup setting AMV001
= 0 (logical 0), if VC ≤ pickup setting AMV001
PSV04 = 1 (logical 1), if all three Relay Word bits PSV01, PSV02, and PSV03 are asserted(PSV01 = 1, PSV02 = 1, and PSV03 = 1)
= 0 (logical 0), if at least one of the Relay Word bits PSV01, PSV02, and PSV03 is
deasserted (e.g., PSV01 = 0)
Voltage Element Analog Quantity Metering
Protection Math Variables were chosen to store the measured analog quantities in order to allow
for direct metering of the measure secondary voltages by utilizing the MET PMV A command.Should direct metering not be necessary for commissioning practices, the voltage comparisonlogic can be made using the analog quantities, e.g., PSV01 := VAFIM > AMV001.
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 7/22
Date Code 20040823 SEL Application Guide 2004-12 7
Frequency Elements
The SEL-451 relay measures power system frequency based on fixed rate sampled voltages. Therelay measures the time between zero crossings, filters the time measurement, and processes themeasurement with an algorithm to remove line anomalies.
The SEL-451 automatically provides necessary frequency tracking while there is no pole opencondition, there is no loss-of-potential condition, and there is no fault.
Frequency tracking in the SEL-451 is limited by the specified range: 40–65 Hz. Slew rates of10.0 Hz/s or greater also disable frequency tracking. Measured system frequency (analogquantity FREQ) reverts to the nominal frequency setting value (Global setting NFREQ) whenfrequency tracking thresholds have been exceeded.
Frequency Element Settings
AMV021
(27B81P)
PMV01 (V A)
PMV02 (VB)
PMV03 (VC)
ToFrequencyElementLogic
PCT01Q
(27B81)
PSV21 := PMV01 < AMV021 OR PMV02 < AMV021
PCT01IN := PSV21
OR PMV03 < AMV021
PSV21
Figure 3: Undervoltage Block for Frequency Elements
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 8/22
8 SEL Application Guide 2004-12 Date Code 20040823
Undervoltage Condition
q
ASV021
AMV022
PCT01Q
(27B81)
PSV22
(81D)Over-Frequency
Under-
Frequency
(MeasuredSystem
Frequency
in HZ)
PMV21
PCT02PU(81DD)
0
PCT02Q
(81DT)
PSV22 := (ASV021 AND (PMV21 > AMV022) OR NOT (ASV021)
AND (PMV21 <= AMV022)) AND NOT (PCT01Q)
PCT02IN := PSV22
(81DP)
q From Figure 3
Figure 4: Frequency Element
Table 3: Frequency Elements Settings and Settings Ranges
Setting Definition Range
ASV021 Select frequency element 1 (Overfrequency), 0 (Underfrequency)
AMV021 Undervoltage frequency elementblock pickup
25.00–300.00 V secondary
AMV022 Frequency element pickup 40.10–64.90 Hz
AMV023 Frequency element time delay 2.00–16000.00 cycles
Table 4: Frequency Element Relay Word Bits
Relay Word Bit Description
PCT01Q Undervoltage frequency element block
PCT02Q Frequency element
Accuracy
Pickup: ± 0 .01 Hz
Create Over- and Underfrequency Elements
Refer to Figure 4.
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 9/22
Date Code 20040823 SEL Application Guide 2004-12 9
Overfrequency Element
For example, make settings:
ASV021 := 1 (select overfrequency element)
AMV022 := 61.25 (frequency element pickup)
The overfrequency part of the frequency element logic is enabled. PSV22 operates as aninstantaneous overfrequency element. For actual protection, SEL recommends the use ofconditional timer output PCT02Q.
Underfrequency Element
For example, make settings:
ASV021 := 0 (select underfrequency element)
AMV022 := 59.65 (frequency element pickup)
The underfrequency part of the frequency element logic is enabled. PSV22 operates as aninstantaneous underfrequency element. For actual protection, SEL recommends the use ofconditional timer output PCT02Q.
Frequency Element Operation
Refer to Figure 4.
Overfrequency Element Operation
With the previous overfrequency element example settings, if the system frequency is less than orequal to 61.25 Hz (AMV022 = 61.25 Hz), the frequency element outputs:
PSV22 = logical 0
If the system frequency is greater than 61.25 Hz (AMV022 = 61.25 Hz), the frequency elementoutputs:
PSV22 = logical 1
Underfrequency Element Operation
With the previous underfrequency element example settings, if the system frequency is less thanor equal to 59.65 Hz (AMV022 = 59.65 Hz), the frequency element outputs:
PSV22 = logical 1
If the system frequency is greater than 59.65 Hz (AMV022 = 59.65 Hz), the frequency elementoutputs:
PSV22 = logical 0
Frequency Element Voltage Control
Refer to Figure 3 and Figure 4.
The frequency element is controlled by the undervoltage element conditioning timer PCT01.Relay Word bit PCT01Q asserts to logical 1 and blocks the frequency element operation if any
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 10/22
10 SEL Application Guide 2004-12 Date Code 20040823
voltage (VA, V
B, or V
C) goes below voltage pickup AMV021. This control prevents erroneous
frequency element operation following fault inception.
Power Elements
Either single-phase power elements or three-phase power elements may be enabled. Each power
element can be set to detect real power or reactive power in the forward or reverse direction. Thepower element type settings are made in reference to the load convention:
+WATTS: positive or forward real power–WATTS: negative or reverse real power+VARS: positive or forward reactive power (lagging)–VARS: negative or reverse reactive power (leading)
Power Elements Settings
Table 5: Single-Phase Power Element Settings and Setting Ranges
Settings Definition Range
ASV041 Power element type 1 (Watt), 0 (Var)
AMV041 Power element direction 1.0 (+), –1.0 (–)
AMV042 Power element pickup 2.00–13000.00 VA secondary, single-phase
AMV043 Power element time delay 0.0–16000.00 cycles
Table 6: Three-Phase Power Element Settings and Setting Ranges
Settings Definition Range
ASV042 Power element type 1 (Watt), 0 (Var)
AMV044 Power element direction 1.0 (+), –1.0 (–)
AMV045 Power element pickup 6.00–39000.00 VA secondary, three-phase
AMV046 Power element time delay 0.00–16000.00 cycles
Table 7: Single-/Three-Phase Power Element Relay Word Bits
Relay Word Bits Description
PCT03Q A-phase power element
PCT04Q B-phase power element
PCT05Q C-phase power element
PCT06Q Three-phase power element
Power Element Calculations
The numeric method used in the power elements uses 10-cycle average line-to-neutral voltageand phase current quantities. Each phase is calculated separately, with the resulting power
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 11/22
Date Code 20040823 SEL Application Guide 2004-12 11
quantities subject to the minimum voltage and current tests shown in the lower half of Figure 5. The three-phase power is the sum of the single-phase powers.
Power Element Logic Operation
_
+
_ +
_
+
_
+
PMV01 (|V A|)10 V sec
|I A
|
0.1 • INOM
PMV01 (|V A
|)
40 V sec
|I A
|
0.01 • INOM
_
+
10-cycle
average
Phase A
Reactive Power
10-cycle
averagePhase A
Real Power
Switch in this
position if
ASV041 := 1
multiply by -1
• (–1)
Switch in this
position if
ASV041 := 0
Switch in this
position if
AMV041 := 1.0
Switch in this
position if
AMV041 := –1.0
Single-phase VA pri
AMV054
Sufficient
Signal
PSV47
INOM
= 1 A sec or 5 A sec
Repeat for Phases B and C
PSV41
PCT03Q
(PWRA)
PCT03PU(PWRD)
0
PSV41 := PMV01 > 40 AND LIAFIM > AMV056
OR PMV01 > 10 AND LIAFIM > AMV057
PSV47 := (PMV41 > AMV054) AND PSV41
PCT03IN := PSV47
PMV41
(PWRP pri)
Figure 5: Single-Phase Power Element Logic (+VARS Example Shown)
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 12/22
12 SEL Application Guide 2004-12 Date Code 20040823
10 Cycle
Average
Real Power
(Three-Phase)
Reactive Power
(Three-Phase)
1
2
PSV50multiply by –1
AMV055(3PWRP pri)
Switch A Switch B
2• (–1)
1
Sufficient
Signal
PSV46
PMV01 (⏐V A⏐)
PMV02 (⏐VB⏐)
PMV03 (⏐VC⏐)
10 V
⏐I A⏐
⏐IB⏐
0.1 • INOM
40 V
⏐IC⏐
⏐IB⏐
⏐I A⏐
⏐IC⏐
PMV01 (⏐V A⏐)
PMV02 (⏐VB⏐)
PMV03 ( |VC| )
0.01 • INOM
INOM = 1 A sec or 5 A sec
AMV044
ASV042Switch APosition
Switch BPosition
–1.0
1.0
10
12
2
1
PMV44
PCT06Q
(3PWR)
PSV45
PSV44
AND LIAFIM > AMV056 AND LIBFIM > AMV056
AND LICFIM > AMV056
PSV44 := PMV01 > 40 AND PMV02 > 40 AND PMV03 > 40
PSV45 := PMV01 > 10 AND PMV02 > 10 AND PMV03 > 10 AND LIAFIM > AMV057 AND LIBFIM > AMV057
AND LICFIM > AMV057PSV46 := PSV44 OR PSV45PSV50 := PMV44 > AMV055 AND PSV46PCT06IN := PSV50
PCT06PU(PWRD)
0
Figure 6: Three-Phase Power Element Logic
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 13/22
Date Code 20040823 SEL Application Guide 2004-12 13
Reactive
Power
Real
Power
Power
Element
Pickup
Power
Element
Pickup
Reactive
Power
Power
Element
Pickup
Power
Element
Pickup
Real
Power
52
SEL-
451
Set as Reactive Power Element
reverse
(leading)
forward
(lagging)
52
SEL-
451
Set as Real Power Element
reverse forward
-WATTS +WATTS
-VARS
+VARS
Figure 7: Power Element Operation in the Real/Reactive Power Plane
Figure 5 shows an example for +VARS.
In Figure 7, if the Phase A reactive power level is above the power element pickup threshold,
Relay Word bit PSV47 asserts (PSV47 = logical 1), subject to the “sufficient signal” conditions.
The “sufficient signal” conditions in Figure 5 require at least 1 percent nominal current if thecorresponding phase voltage is greater than 40 V secondary. If the voltage is between 10 and40 V secondary, at least 10 percent nominal current is required. This check has been added to thelogic in order to replicate the functionality of the SEL-351-7. Should individual practice dictate adifferent constraint, the logic (PSV41, PSV42, PSV43, and PSV46) can be modified as necessary.
Pickup setting AMV042 is always a positive number value (see Table 5). Thus, if –WATTS or–VARS are chosen with settings AMV041 and ASV041, the corresponding real or reactive powervalues have to be multiplied by –1 so that element PSV47 asserts for negative real or reactivepower.
Power Element Time Delay Considerations
Power elements are time-delayed using Protection Conditioning Timers (PCTs). The SEL-451Relay has 16 PCTs to choose from (PCT01–PCT16). Select these timers to avoid unintentionalduplication. For protection applications involving the power elements, SEL recommends aminimum time delay of 5.00 cycles for general applications. The classical power calculation is aproduct of voltage and current, to determine the real and reactive power quantities. During asystem disturbance, because of the high sensitivity of the power elements, the changing systemphase angles and/or frequency shifts may cause transient errors in the power calculation.
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 14/22
14 SEL Application Guide 2004-12 Date Code 20040823
Accuracy
Single-Phase Power Elements
Pickup: ±0.025 A • (voltage secondary) and ±5% of setting at unity power factor (for +WATTSor –WATTS) or power factor = 0 (for +VARS or –VARS) (5 A nominal phase current)
±0.005 A • (voltage secondary) and ±5% of setting at unity power (for +WATTS or–WATTS) or power factor = 0 (for +VARS or –VARS) (1 A nominal phase current)
Three-Phase Power Elements
Pickup: ±0.025 A • (voltage secondary) and ±5% of setting at unity power factor (for +WATTSor –WATTS) or power factor = 0 (for +VARS or –VARS) (5 A nominal phase current)
±0.005 A • (voltage secondary) and ±5% of setting at unity power (for +WATTS or–WATTS) or power factor = 0 (for +VARS or –VARS)(1 A nominal phase current)
Settings
Protection and Automation Free-Form Logic Settings
This is where the SEL-451 uses the set free-form logic to implement voltage comparisons,frequency comparisons, power calculations, and logic operation.
Variable Assignment Within the SEL-451 Relay
See Table 13 for a detailed listing of the SEL-351-7 Relay Word bit allocation used within theSEL-451 for this application.
FILTERING
The SEL-451 provides advanced filtering. This application uses the available fundamentalquantities with all harmonics removed.
CONCLUSION
Through use of the programmable free-form logic area, the SEL-451 provides for the creation ofcertain protection elements common in the protection and control of distribution systems. TheSEL-451 uses math variable comparison, manipulation, and logic equations to implementprotection functions.
In addition, the extensive monitoring and recording features of the SEL-451 provide improvedperformance monitoring and use of substation equipment.
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 15/22
Date Code 20040823 SEL Application Guide 2004-12 15
SUPPLEMENTAL TABLES
Table 8: Protection Free-Form Logic Settings (SET L Command)
Protection Code #Commentsa
PMV01 := VAFIM VA magnitude
PMV02 := VBFIM VB magnitude
PMV03 := VCFIM VC magnitude
PMV04 := 3V0FIM 3V0 magnitude
PMV05 := 3V2FIM / 3 V2 magnitude
PMV06 := V1FIM V1 magnitude
PSV01 := PMV01 > AMV001 59A
PSV02 := PMV02 > AMV001 59B
PSV03 := PMV03 > AMV001 59C
PSV04 := PSV01 AND PSV02 AND PSV03 3P59
PSV05 := PMV04 > AMV002 59N
PSV06 := PMV05 > AMV003 59Q
PSV07 := PMV06 > AMV004 59V1
PSV08 := PMV01 < AMV005 27A
PSV09 := PMV02 < AMV005 27B
PSV10 := PMV03 < AMV005 27C
PSV11 := PSV08 AND PSV09 AND PSV10 3P27
PMV21 := FREQ Frequency magnitude
PSV21 : = PMV01 < AMV021 OR PMV02 <AMV021 OR PMV03 < AMV021
Undervoltage frequencyelement block
PCT01PU := 0.0
PCT01DO := 5.0
PCT01IN := PSV21 Undervoltage frequencyelement block dropout timer
PSV22 := (ASV021 AND (PMV21 >
AMV022) OR NOT(ASV021) AND (PMV21<= AMV022)) AND NOT (PCT01Q)
81D
PCT02PU := AMV023 81DD
PCT02DO := 0.0
PCT02IN := PSV22
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 16/22
16 SEL Application Guide 2004-12 Date Code 20040823
Protection Code #Commentsa
PSV41 := PMV01 > 40 AND LIAFIM >AMV056 OR PMV01 > 10 AND LIAFIM >AMV057
Sufficient Signal A-phase
PSV42 := PMV02 > 40 AND LIBFIM >AMV056 OR PMV02 > 10 AND LIBFIM >AMV057
Sufficient Signal B-phase
PSV43 := PMV03 > 40 AND LICFIM >AMV056 OR PMV03 > 10 AND LICFIM >AMV057
Sufficient Signal C-phase
PSV44 := PMV01 > 40 AND PMV02 > 40AND PMV03 > 40 AND LIAFIM > AMV056AND LIBFIM > AMV056 AND LICFIM >AMV056
Sufficient Signal Three Phase –Part 1
PSV45 := PMV01 > 10 AND PMV02 > 10
AND PMV03 > 10 AND LIAFIM > AMV057AND LIBFIM > AMV057 AND LICFIM >AMV057
Sufficient Signal Three Phase –
Part 2
PSV46 := PSV44 OR PSV45 Sufficient Signal Three Phase
PMV41 := AMV041 * (PA_F * ASV041 +QA_F * NOT ASV041)
Phase A Power magnitude
PMV42 := AMV041 * (PB_F * ASV041 +QB_F * NOT ASV041)
Phase B Power magnitude
PMV43 := AMV041 * (PC_F * ASV041 +QC_F * NOT ASV041)
Phase C Power magnitude
PSV47 := (PMV41 > AMV054) AND PSV41 Phase A Power comparison
PSV48 := (PMV42 > AMV054) AND PSV42 Phase B Power comparison
PSV49 := (PMV43 > AMV054) AND PSV43 Phase C Power comparison
PMV44 := AMV044 * (3P_F * ASV042 +3Q_F * NOT ASV042)
Three Phase Power magnitude
PSV50 := (PMV44 > AMV055) AND PSV46 Three Phase Power comparison
PCT03PU := AMV043 PWRD
PCT03DO := 0.0
PCT03IN := PSV47 PWRA
PCT04PU := AMV043 PWRD
PCT04DO := 0.0
PCT04IN := PSV48 PWRB
PCT05PU := AMV043 PWRD
PCT05DO := 0.0
PCT05IN := PSV49 PWRC
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 17/22
Date Code 20040823 SEL Application Guide 2004-12 17
Protection Code #Commentsa
PCT06PU := AMV046 PWRD
PCT06DO := 0.0
PCT06IN := PSV50 3PWR
a Free-form logic settings can include comments in order to facilitate good documentationpractices. Comments are preceded by the “#” character, e.g.,
PMV01 := VAFIM #VA magnitude.
Table 9: Automation 1 Free-Form Logic Settings (SET A 1 Command)
Automation Code #Comments
AMV001 := [user entered] 59 Phase Pickup (59PP)
AMV002 := [user entered] 59 3V0 Pickup (59NP)AMV003 := [user entered] 59 V2 Pickup (59QP)
AMV004 := [user entered] 59 V1 Pickup (59V1P)
AMV005 := [user entered] 27 Phase Pickup (27PP)
Table 10: Automation 2 Free-Form Logic Settings (SET A 2 Command)
Automation Code #Comments
ASV021 := [user entered] Frequency Element Type: (1) forOverfrequency, (0) for Underfrequency
AMV021 := [user entered] Undervoltage Block Pickup (27B81P)
AMV022 := [user entered] Frequency Element Pickup (81DP)
AMV023 := [user entered] Frequency Element Time Delay (81DD)
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 18/22
18 SEL Application Guide 2004-12 Date Code 20040823
Table 11: Automation 3 Free-Form Logic Settings (SET A 3 Command)
Automation Code #Comments
AMV041 := [user entered] Single Phase Direction Selection: (1.0)for (+), (–1.0) for (–)
ASV041 := [user entered] Single Phase Power Element Type: (1)for Watts, (0) for Vars (PWRT)
AMV042 := [user entered] Single Phase Power Element Pickup(PWRP)
AMV043 := [user entered] Single Phase Power Element TimeDelay (PWRD)
AMV044 := [user entered] Three Phase Direction Selection: (1.0)for (+), (–1.0) for (–)
ASV042 := [user entered] Three Phase Power Element Type: (1)for Watts, (0) for Vars (PWRT)
AMV045 := [user entered] Three Phase Power Element Pickup(3PWRP)
AMV046 := [user entered] Three Phase Power Element Time Delay(PWRD)
Table 12: Automation 4 Free-Form Logic Settings (SET A 4 Command)
Automation Code #Comments
AMV051 := [user entered] Nominal Relay Current (INOM)
AMV052 := [user entered] Group Setting CTRW
AMV053 := [user entered] Group Setting PTRY
AMV054 := (AMV042 * AMV052 *AMV053) / 1E6
Single Phase Power Element Pickup(PWRP) converted to Primary units
AMV055 := (AMV045 * AMV052 *AMV053) / 1E6
Three Phase Power Element Pickup(3PWRP) converted to Primary units
AMV056 := 0.01 * AMV051 1% of Nominal Current
AMV057 := 0.1 * AMV051 10% of Nominal Current
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 19/22
Date Code 20040823 SEL Application Guide 2004-12 19
Table 13: SEL-351-7 Relay Word Bits and SEL-451 Equivalent
SEL-351-7 Relay
Word Bit
SEL-451 Relay
Word Bit Function
59A PSV01 A-phase Overvoltage
59B PSV02 B-phase Overvoltage
59C PSV03 C-phase Overvoltage
3P59 PSV04 3-phase Overvoltage
59N PSV05 3V0 Overvoltage
59Q PSV06 V2 Overvoltage
59V1 PSV07 V1 Overvoltage
27A PSV08 A-phase Undervoltage
27B PSV09 B-phase Undervoltage
27C PSV10 C-phase Undervoltage
3P27 PSV11 3-phase Undervoltage
27B81 PCT01Q Undervoltage Block
81DT PCT02Q Frequency
PWRA PCT03Q A-phase Power
PWRB PCT04Q B-phase Power
PWRC PCT05Q C-phase Power
3PWR PCT06Q 3-phase Power
Table 14: Protection SEL Variables
Variable Application Use
PSV01 59A
PSV02 59B
PSV03 59C
PSV04 3P59
PSV05 59N
PSV06 59Q
PSV07 59V1
PSV08 27A
PSV09 27B
PSV10 27C
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 20/22
20 SEL Application Guide 2004-12 Date Code 20040823
Variable Application Use
PSV11 3P27
PSV21 Frequency Element PhaseVoltage magnitude check
PSV22 81D
PSV41 Power Element Sufficient Signal A-phase
PSV42 Power Element Sufficient Signal B-phase
PSV43 Power Element Sufficient Signal C-phase
PSV44 Power Element Sufficient SignalThree Phase – Part 1
PSV45 Power Element Sufficient SignalThree Phase – Part 2
PSV46 Power Element Sufficient Signal Three Phase
PSV47 A-phase Power comparison
PSV48 B-phase Power comparison
PSV49 C-phase Power comparison
PSV50 3-phase Power comparison
Table 15: Automation SEL Variables
Variable Application Use
ASV021 Select Frequency Element
ASV041 Single phase PWRT
ASV042 Three phase PWRT
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 21/22
Date Code 20040823 SEL Application Guide 2004-12 21
Table 16: Protection Math Variables
Variable Application Use
PMV01 VAFIM
PMV02 VBFIM
PMV03 VCFIM
PMV04 3V0FIM
PMV05 3V2FIM / 3
PMV06 V1FIM
PMV21 FREQ
PMV41 A-phase Power (PA_f or QA_f)
PMV42 B-phase Power (PB_f or QB_f)
PMV43 C-phase Power (PC_f or QC_f)
PMV44 3-phase Power (3P_f or 3Q_f)
Table 17: Automation Math Variables
Variable Application Use
AMV001 59PP
AMV002 59NP
AMV003 59QP
AMV004 59V1P
AMV005 27PP
AMV021 27B81P
AMV022 81DP
AMV023 81DD
AMV041 Single-phase Power Direction Setting
AMV042 PWRP
AMV043 PWRD
AMV044 Three-phase Power Direction Setting
AMV045 3PWRP
AMV046 PWRD
AMV051 INOM
AMV052 CTRW
8/11/2019 AG_AG2004-12_20040823
http://slidepdf.com/reader/full/agag2004-1220040823 22/22
Variable Application Use
AMV053 PTRY
AMV054 PWRP converted to Primary units
AMV055 3PWRP converted to Primary units
AMV056 1% of Nominal Current
AMV057 10% of Nominal Current
Table 18: Protection Conditioning Timers
Variable Application Use
PCT01Q Undervoltage Frequency Element block
PCT02Q Time-delayed Frequency Element
PCT03Q Time-delayed A-phase Power Element
PCT04Q Time-delayed B-phase Power Element
PCT05Q Time-delayed C-phase Power Element
PCT06Q Time-delayed Three-phase Power Element
FACTORY ASSISTANCE
We appreciate your interest in SEL products and services. If you have questions or comments,please contact us at:
Schweitzer Engineering Laboratories, Inc.2350 NE Hopkins CourtPullman, WA USA 99163-5603Telephone: (509) 332-1890Fax: (509) 332-7990Internet: www.selinc.com
All brand or product names appearing in this document are the trademark or registered trademark of their respective holders.
ACSELERATOR, Connectorized, CONSELTANT, Job Done, MIRRORED BITS, Schweitzer Engineering Laboratories, , SEL, SELOGIC, and SEL-PROFILE, areregistered trademarks of Schweitzer Engineering Laboratories, Inc.
Copyright © SEL 2004 (All rights reserved) Printed in USA.