Condensing Gas Water Heaters
Indoor and Outdoor
Domestic Hot Water Control
Modulex EXT95-864kw
Tech Data Manual
A Flexible "machine"Modulex EXT
Low Emissionsfully modulatingvery high seasonal efficiencyguarantee of operationcompactnessquiet operationcan be directly used in outdoor installationmaximum accessibility to the components
The DNA of MODULEX EXT.
MODULEX EXT resolves any installation problem,
both, hydraulic and electronic.
MODULEX EXT boasts, the best ratio
.
Wide range formed by ten gas condensing models, with
outputs from 150 to 900 kW.
Very high modulation ratio, up to 1:40, in order to
supply the “correct power”.
Just one
• Pre-assembled thermal elements in
• Patented, electronic management system, to instantly
give the at any modulated
capacity: up to at the least modulated capacity.
Integration of the electronic controller within the
ideal for difficult installations.
thanks to the reduced weight, it allows easy
maneuverability within the boiler house; it can also be
supplied in loose parts and reassembled in the boiler
house.
even at it's maximum capacity, thanks to its
combustion characteristics and to the sophisticated
technology of the new fans, gas valves and multi-gas
burners
between:
output/overall dimensions and weight
always
technological boiler block:
aluminium,
silicon and magnesium casting
maximum efficiency
109%
disappearing panel board.
Compact
Light,
Silent:
Automatic Heating reserves the right to change specifications without notice.
Output(condensing
mode)(kW)
12 ÷ 150
12 ÷ 200
12 ÷ 250
12 ÷ 300
12 ÷ 350
22 ÷ 432
22 ÷ 540
22 ÷ 648
22 ÷ 756
22 ÷ 864
ModelEXT
MX150
MX200
MX250
MX300
MX350
MX
MX
MX
MX
MX
EXT
EXT
EXT
EXT
EXT
440EXT
550EXT
660EXT
770EXT
900EXT
ThermalmodulesN. OFF
3
4
5
6
7
4
5
6
7
8
Modulationratio
1:12
1:16
1:20
1:24
1:28
1:19,6
1:25
1:29
1:34
1:39
Productionof
condensate(kg/h)
23
30,6
38,3
45,9
53,6
73,4
91,7
110
128,4
146,7
Dimensions
(L x P x H)
764 x 770 x 1150
1032 x 770 x 1150
1032 x 770 x 1150
1300 x 770 x 1150
1300 x 770 x 1150
1087 x 946 x 1448
1355 x 946 x 1448
1355 x 946 x 1448
1623 x 946 x 1448
1623 x 946 x 1448
A “Heating Motor” that goes beyondthe simple concept of boiler.
Condensing Water Heaters > Modulex EXT Water Heaters
MODULEX EXT Tech Data Manual2
MODULEX EXT Tech Data Manual 3
8 Points of Difference
Patented design technology
Gfirst generator with modular sections complete
with premix modulating burners
castings thermal elements in lightof the
alloy
cooling water ways in serpentine shape
original fin to increase its exchange surface
standardized flow and return manifolds without
interceptions between every section and hydraulically
balanced
burners, complete with safety devices
non return smoke valve
command and control electronic system with
of one/all the thermal elementsproportional regulation
MODULEX EXT, "OVER TEN YEARS OF PERFECTING,
THROUGH TECHNOLOGICAL ADVANCES HAS
RESULTED IN UNRIVALED SUCCESS"
Condensing Water Heaters > Modulex EXT Water Heaters
The DetailsModulex EXT
Maximum saving and seasonal efficiency
Total safety
Flexibility of installation
Low environmental impact
Exclusive electronic technology
Wide range of dedicated accessories:
High efficiency thanks to:
• certified efficiency up to 109% at the minimum
modulated capacity
• seasonal efficiency: + 30% if compared with the
conventional boilers
• large modulation ratio: UP TO 1:40
• modulating pump directly managed by the boiler
to assure the maximum condensation at all times
• high reliability due to MULTI BURNER composition
and to the low number of parts in movement
• working and safety temperature sensors on every
casting section
• premixing within the fan with non return built-in valve
• auxiliary electronic circuits
• emergency operation in case the E8 controller is out
of service
• outdoor installation: protection degree IP55
• compact, light, of easy connection:
- reversible hydraulic and gas connections
(up to model 350 kW)
- smoke discharge: possible on 3 sides
(for all the models)
• low polluting emissions : <31 ppm Low NOx
(according to EN 15420)
• low acoustic impact <49 dBA
• low chimney flue losses
• premix burners providing constant C02 ratio
• electronic management and thermal regulation
completely automatic and pre-programmed (patented)
• possible cascade installation up to 8 boilers
• predisposition for telemanagement and telecontrol
- Primary ring with additional safety devices kit
- Plate heat exchanger with additional kit
- Acidic condensate neutralizers
- Regulation of additional zones
safety devices
MODULEX EXT Tech Data Manual4
Thanks to itsparticular structure,
synonymous with reliability ofit's time, the MODULEX EXT
boiler body is covered by a5 year guarantee.
MODULEX EXT Tech Data Manual 5
Pre-assembledThermal Elements
MODULEX EXT is an assembly of thermal modules, together making a complete unit.
Every unit is constituted by pre-assembled thermal elements, in
Every element supplies, in continuous and progressive way, from 12 to 50 kW for the models
up to 350 kW, and from 22 up to 108 kW for larger models.
Al/Si/Mg.
More than 10 years experience assure:
resistance to the corrosion of the acidic condensate
very high thermal efficiency
Key:
1 -
2 -
3 -
4 -
5 -
6 -
7 -
8 -
9 -
10 -
11 -
12 -
13 -
14 -
15 -
16 -
17 -
18 -
19 -
20 -
Gas valve
Burner cover
Gas pipe
Ignition electrode
Ionization probe
Local NTC temperature sensor
Limit thermostat
Aluminium alloy heat exchanger
Condensate level sensor
Condensate & smoke
tray– chimney connection
Frame
Fan
Burner
Automatic air vent
Global NTC flow temperature
sensor
Central Heating flow
Global NTC return temperature
sensor
Central Heating return
Drain tap
Condensate evacuation
The basic element is formed by two aluminium alloy
castings that, on the smoke side, have dense fins,
with increasing height toward the smoke discharge,
placed in lower part of the casting, in order to increase
its exchange surface.
Inside the castings there are the water channels that,
always with more reduced section, zigzag cross the
casting, granting an exceptional heat transfer from
combustion gases to the water.
Every thermal element is equipped with:
The smoke and acidic condensate of the thermal elements
are collected in a stainless steel tray.
• premix modulating burner
• two stage modulating gas valve
• electronic ignition and ionization
• NTC working temperature sensor
• safety thermostats
• flame sight glass.
Condensing Water Heaters > Modulex EXT Water Heaters
Radiation Combustion
Main protagonist for a perfect combustion and therefore the maximum
efficiency, is the modulating fan (1000-6000 rpm) of which every unit
is equipped.
The number of rpm of the fan, together with the opening of the valve gas
and the flame control, is directly programmed and controlled by the
electronics of every burner (BMM Burner Modular Module) and, in their
turn, they are managed by the E8 controller.
The output modulation depends on the speed of the fan and the difference
between the required temperature, and the maximum one.
Total Premix
The opening of the gas valve is produced by the
in the Cochlea of the fan and the air and gas mixture
happens inside before being introduced to the combustion
chamber (premix).
This perfect “mixing” combines the air and gas in parts
always in proportion through the multi-gas burner.
This system, characterized by the issue of electromagnetic
radiations, is most efficient for the transmission of thermal
energy.
The wide surface, on which the combustion happens,
guarantees:
•
long lasting burner structure
quiet operation
simple maintenance thanks to the use of few components
and easy accessibility
larger quantity of transmitted energy in comparison to a
traditional burner with the same flame temperature
absolute working safety for the absence of turbulences
very small production of pollutants due to the complete
oxidation of the gas molecules;
• excellent combustion efficiency: maximum CO2= 9,3%
• efficiency optimization thanks to the low
smoke temperature and the limited “air excess”
• very low pollutant emissions: NOX<53,8
mg/kWh (pondered value according to
• reduced turbulence
with the following advantages:
“Venturi
effect”
low combustion temperature
EN 15420).
The valve is directly mounted on the fan.
Inside its volute the air/gas mixing
calibration takes place.
NEW CONFIGURATION:
MODULEX EXT Tech Data Manual6
MODULEX EXT Tech Data Manual 7
After the time “T1” from the starting, MODULEX EXT succeeds in satisfying the 30% of the load unlikea traditional boiler that, in the same time, is just at 15%.
After the time “T2” MODULEX EXT is at 50% of the load, while the traditional one is at 30%.After the time “T3” MODULEX EXT is at 100% of the load and the traditional one is only to 70%.
This clearly displays the speed of the Modulex EXT Boiler
Radiation Combustion
The MODULEX EXT exceeded all industry
requirements when it was first conceived over a
decade ago. These days the high standards and
benchmark qualities of this groundbreaking boiler are
a must in today's world.
This function enables you to drastically reduce the
number of switching ON and OFF of the boiler.
(Possible customization of the requested output).
• Higher efficiency and lower flue losses when burner
is OFF.
• Longer lasting of the parts in movement and of the
ignition systems.
On average a boiler operates at 50% of the thermal
need of the C.H. installation and can descend below
30%. MODULEX EXT adjusts in real time the output to
meet demand, because it is not influenced by the
thermal inertia, thanks to its low water content and,
being equipped with modulating pump, it further
reduces the electricity used.
This function promotes the production of condensate
and therefore the fast economic recovery of the
investment. All this in order to offer the user the
possibility to save with the maximum comfort both,
for C.H. and D.H.W. production, with a lower noise
level than the traditional boilers.
Setting option according to the thermal needs of
the C.H. system
Advantages:
Very low water content and high modulation
speed with maximum output ratio up to 1:40
Class A, variable speed, electronic pumps, for
the maximum condensate production
Condensing Water Heaters > Modulex EXT Water Heaters
Concealed Panel Board
Modulation in cascadeThe applicable systems of communication: cascademanagement, leaving
eBUS, Mod-bus and canBUS allow the maximum elasticity in thefree choice to the consumer for the last interface of management.
E8 Thermo-controller BCM Boiler Cascade Manager
BCM
CASCADE MANAGED BY PLCCASCADE MANAGED BY E8 CASCADE MANAGED THROUGH BCM
BCM
BMM BMM BMM
BCM
BMM BMM BMM
Modbus
eBUS
eBUSBCM
BMM BMM BMM
BCM
BMM BMM BMMBMM BMM BMM
BCM
BMM BMM BMM
A perfect pneumatic system with gas dampers lifts the tamper proof
cover of MODULEX EXT.
Smart access to the panel board !
FEATURES:
E8
BCM
• external temperature sensor
• flow temperature sensor for mixed zone (zone 1)
• boiler temperature sensor
• D.H.W. storage tank temperature sensor
Thermo-controller
Boiler Cascade Manager
easy access to this controlling unit.
E8 is supplied complete with:
The E8 thermo-controller allows maximum
condensation and output modulation of the system
through complete program management.
MODULEX EXT Tech Data Manual8
MODULEX EXT Tech Data Manual 9
A Clever Brain
E8, the thermo controllerCascade of 2 up to 8 MODULEX EXTWith simple connection.
KIT OF ZONE EXPANSION E8To control 2 direct/mixed zones and a D.H.W. storage tank up to a
maximum of 7 modules that can be connected with a two wire cable.
Remote management and remote control
Through dedicated sof
CO
tware and accessories, with electronic board
.CO.PC and GSM connection.
CommunicationWith the central automation systems (PLC).
For additional information, please contact our pre-sale department.
System optimization
0-10 volt signalthe great flexibility of the E8 alsopermits the MODULEX EXT set pointto be controlled by an external controlsignal. This will enable, having atdisposal an even more complexsystem, to exploit all the heatingcontrol’s functions..
Domestic hot water productionThere are many programmes which control thedomestic hot water production. You can choosefrom the maximum of comfort to the maximum fuelsaving. In order to permit the storage cylinder tosupply hot water rapidly, the heating controller bringsthe boiler’s temperature to the maximum set value.
Anti LegionellaEvery 20th heating start-up or once a weekon Saturday at 01:00 hrs, the storage tank isheated up to 60°C. This function will eliminateany eventual pathogens which have formedin the DHW.
DHW optimization (loading pump)The DHW loading pump is switched on only if the
boiler temperature exceeds the tank temperature
by 5°C. It is deactivated when the boiler temperature
drops below the storage tank temperature or if the
storage tank temperature is higher than the nominal
temperature.
DHW controlProgramme settingThe heating programmes can be setdaily or weekly, with more than oneOn-Off ring times or temperaturereductions during the day.
Multiple zone controlWith the same heating control deviceyou can control 2 independentcircuits with different characteristics,though having ensured allthe described functions, includingthe deep sliding temperaturefunction.
Management of up to 15mixed circuitscontrolled by the outdoor sensor
Setting
Integration withrenewable energy sourcesFor example: solar systemsand/or solid fuel fired boilers.
Energy sourcescontrol
Boiler heating OptimizationThe heating controllerthe timer/heating programme set by the useronce the system’s characteristics have beenevaluated, will activate the function forautomatically bringing forignition time so as to ensure that the settemperature is reached at the time requestedby the user
, on the basis of,
ward the heating
.
Fast set temperatureThis is obtained by calculating the optimumignition starbe carthe outdoor temperature or the roomtemperature.
t-up time. This calculation canried out taking into consideration
Overheating protectionThe boilervia the pump’s overrid of any ther
’s safety temperature is controlledrun time in order to get
mal inertia.
Self AdaptationThrough the elaboration of data transmittedby the room sensor, this function adjuststhe boiler’s output to the building’scharacteristics, ensuring a constantmonitoring of the indoor temperatureon the basis of the variation of the outdoortemperature, keeping in considerationthe building’s thermal inertia andthe contribution of “free” heat (solarradiation, internal heat sources etc).
Slope offset (heating slope distance)The boiler temperature that is requiredfor a mixed circuit is calculated by addingto the calculated temperature settingfor the heating circuit temperaturethe heating slope distance.The heating slope distance compensatesfor sensor tolerances and heat loss up tothe mixer.
Valve opening timeBased on the characteristics ofthe servomotor.
Number of burner ignitionsIt stabilizes the number of ignitionsof each burner.
Burner run hoursIt stabilizes the run hours of each burner.
Frost protection modeThe frost protection operation mode preventsthe CH system from freezing by automaticallyswitching heating operation on. In the frostprotection mode, the room temperaturefor all the heating circuits is set to 5°C andthe storage tank sensor frost protectionis activated when the temperature dropsbelow 10°C.
Swimming pool heating function
Condensing Water Heaters > Modulex EXT Water Heaters
Boiler Cascade Manager BCM
BCM, powerful electronic module:
Managing the inside cascade of the boiler thermal elements
Supplying double certainty of operation (emergency operation
in case of breakdown to the thermo-controller E8, with activation
of the heat request at constant setpoint with maximum capacity
of 50%)
Managing the modulating pump of the primary rings (Analogical
outlet 0-10 V) with significant efficiency increase at part loads
Monitoring the state of working temperatures
Planning the parameters
Managing and resetting the alarms
Remoting alarm signals through relay.
Cascade Installations
With the cascade installation, the boiler output range can be
widened well over 900 kW, multiplying output and
modulation in order to satisfy any design demand. The space
saving (in particular it can be installed up to 40 cm from the
boiler house walls) features of the Modulex Boiler are tailored
specifically with service and easy access in mind.
Replacement of old obsolete boilers is also another benefit that a
small footprint allows.
Allowing the integration in the
boiler house automation systems,
realized with industrial PC / lonWorks
/ Modbus for Building Automation
Checking the heat demand: temperature setpoint and modulation level
MODULEX EXT Tech Data Manual10
MODULEX EXT Tech Data Manual 11
Eco - Logic
MODULEX EXT has a certified efficiency
that, for all models above 350 kW, when
working in condensation, progressively
increase up to when the output
is reduced.
The genius of the thermo-controller E8
is that it keeps ON the
as possible, working at the
(as shown in
the examples beside).
The system will always work in the
conditions of maximum possible
efficiency, independently from the
supplied output.
When the requested output is less than
the capacity available the design of the
Modulex regulates evenly reducing the
output of each module to suit. Once the
minimum level for a module is reached
it is disabled in cascade sequence.
This modular system is such that as the
number of modules used decreases - the
efficiency increases. The flexibility of this
modular conception is ground breaking
and brings vast cost savings through
increased efficiency.
To avoid one element module being
over used more than others, the
thermo-controller automatically
alternates usage of all element
modules evenly.
109%
greatest number
of elements
smallest possible output
Output flexibilityand efficiency
Output sharing of MODULEX EXT of 4 modules of 50 kW
OFF OFF
Condensing Water Heaters > Modulex EXT Water Heaters
The Right Solution....
The designers of heating systems have worked closely with
Modulex to give us this energy efficient unit which offers the following:
Comfort and low consumption
Small size installations (downsizing)
Control of the investment cost (cost of the life cycle)
Integration of the renewable sources
Instant response command function
Reduction of the maintenance costs
• Primary system for installation interface plant with mixing header
• Primary with plate heat exchanger
• Zone satellites system
Modulex EXT is fully integrable with various systems such as:
automated control benefits
system
The integrated design of the building-installations system:from the boiler to the integrated system
Floor Insulation Panels
Various system solutions available
allow maximum flexibility and
adaptability. Use of low temperature
heating fluid combined with heat
stratification results in significant
energy savings
MODULEX EXT Tech Data Manual12
MODULEX EXT Tech Data Manual 13
Modulex EXT working within
a solar driven system supplies
up to 70% of your hot water !!
With the thermal solar panels
the whole heat of the sun
is captured: 20 years warranty
offered with accredited installer
PEXAL PIPING
The Pexal Pipe is perfect for
use with the Modulex EXT,
offering increased heat output
and reduced risk of oxygen
infiltration to the system
... for a Perfect Installation
" Please schedule an appointment with our team of experts
to find a solution that fits your needs - Today!! "
The range of storage tanks
with high efficiency coils
allow an elevated heat
exchange and optimize
the integration through
the thermal solar panels.
VERSATILITY
The brain of the Modulex EXT
is capable of splitting energy
to suit your particular
requirements. eg apartment
situations
THERMOMEX
Condensing Water Heaters > Modulex EXT Water Heaters
Primary Rings withMixing Header
MODULEX EXT is a low water content boiler and therefore a
low thermal inertia boiler:
• high speed of output supply
• immediate answer to the load variations
• minimal heat losses.
The great variations of flow rate and temperature that follow
are, therefore, conveniently balanced by the so-called
hydraulic separator, before reaching these ultramodern
“heating engines”.
Modulex EXT introduces
Complete system, developed and tested in our laboratories
Rapidity of putting into service
Class A modulating pump
OGNITEMPO EXT, a special casing for coverage of the
primary rings in outdoor installations (class IPX5D).
Advantages:
the new range of 5 primaryrings with ultra-compact hydraulic separators.
Example of Primary Ring with mixing
header and adjustable height
The balance between supplied output
and the water flowrate is controlled via
the modulating pump. The BCM card
collates the data relating to flow return
and the low water level, and depending
on this it will either increase or decrease
the flowrate to suit the thermal jump
requirement.
The Modulex EXT will always operate
with the return temperature as low as
possible.
Class A modulating pump
Primary rings pre-assembledand with jacket
Modulex EXT Boilers
Ideal hydraulic balance
Crossing speed near to zero
1.
2.
3.
follow rigorous sizing criteria, in
terms of:
• (interference almost nothing
between primary and secondary ring)
• (minimal temperature
increase on the boiler return to safeguard the condensing
and the decanting effect)
To make independent the connected circuits
“Deslimer”, allowing the collection of the mud of the
circuits
“Deaerator”, to allow the automatic evacuation of the air.
developing three fundamental functions:
Mixing Headers
MODULEX EXT Tech Data Manual14
MODULEX EXT Tech Data Manual 15
Installation ComponentsPRIMARY RING composition
MIXING HEADER KitUpdated ADDITIONALSAFETIES Kit
“Y SHAPED” filter MODULATING PUMP
PRIMARY RINGSMIXING HEADER
combination with MODULEX EXT
Maximumcontrolled output
(kW)
Code
150 150 00361944
200 - 250 250 00361945
300 - 350 350 00361946
400 - 770 756 00361994
900* 864 00361995
* For higher capacities further sizings ar
Some additional safety devices ar
on the installation type.
e available on demand.
e not supplied because their sizing depends
MIXING HEADER KITcombination with MODULEX EXT
150 - 350 350 00361976
440 - 900 864 00361997
> 900 - 2700* 2700 00361501
ADDITION SAFETYDEVICES KIT
combination with MODULEX EXT
150 - 350 350 00361980
440 - 770 756 00361998
900 864 00361999
Coverage OGNITEMPO EXTfor MIXING HEADER
combination with MODULEX EXT
150 - 350 00362008
440 - 900 00362069
Maximumcontrolled output
(kW)
Code
Maximumcontrolled output
(kW)
Code
Code
* For information contact our pre-sale office.
UPDATED ADDITIONAL SAFETIES ASSEMBLY
All safety requirements are not only met, but exceeded.
UPDATED ADDITIONAL SAFETIES ASSEMBLY
CONTROL DEVICES
1 -
2 -
3 -4 -5 -6 -7 -
Pressure gauge with shock absorber and a cock for manometer: it shows the actual
pressure in the boiler, it must have the dial graduated in “bar”, the bottom of the dial
correlated to the maximum working pressure and be equipped with a three way cock
for the connection of a master pressure gauge.
Thermometer: it shows the real temperature of the water contained in the boiler; its
dial must be graduated in centigrades, with bottom of the dial not greater than 120°C.
Bulb holder: for master thermometer.
Stub pipes R 1 1/4’’: for the insertion safety valves.
Y shaped filter.
Modulating pump.
Mixing header.
• Certified expansion vessel: it allows to absorb the volume increase of the C.H. system
water following the temperature increase; the design pressure has not to be higher
than the setting pressure of the safety valve.
• Purging valve and drain cock.
Some parts need to be sized according to the characteristics of the installation:
8 -
9 -
10 -11 -
Safety thermostat: it has the function to stop the boiler in case the limit thermostats,
fitted in the boiler sections, are out of order. Its setting must NOT be changeable and
must be lower than 100°C.
Minimum water pressure switch: it has the function to stop the boiler in case the
minimal working pressure is below (0,5 - 1.7 bar). It has to be of manual reset type.
Additional stub pipe R 1’’.
Safety pressure switch: it has the function to stop the boiler in case of attainment of
the maximum working pressure (5 bar). Adjustable 1 to 6 bar.
Condensing Water Heaters > Modulex EXT Water Heaters
Primary System with PlateHeat Exchanger
For the completion of the installation interfaces,
we propose a
physical separation: hydraulic circulation
is not present among the 2 circuits, the primary
of boiler and secondary of the installation
- possible different working pressure between
primary and secondary circuit (for example:
closed expansion vessel for the boiler and open
expansion vessel for the C.H. circuit)
boiler installation on old, obsolete C.H. circuits
with potential risks of sludge or water leaks,
with consequent frequent water reinstatements
external installation with primary circuit
protected against freezing and secondary circuit
with untreated water
variation of exchange parameters in case of C.H.
system modifications, by adding or removing
plates
new range of 6 primary ringswith plate heat exchanger.
Advantages: C.H. FLOW
C.H. RETURNRETURN INTOTHE BOILER
FLOW FROMTHE BOILER
fixed front plate
plates assembly
movable rear plate
MODULEX EXT Tech Data Manual16
MOUDLEX EXT Tech Data Manual 17
PRIMARY RINGSPLATE HEATEXCHANGER
combination with MODULEX EXT
CODE Maximumcontrolled
output
(kW)
PRIMARYworking
temperatures
(°C)
SECONDARYworking
temperatures
(°C)
PRIMARYFLOW RATE
m 3F/R 80°/65°
SECONDARYFLOW RATE
m 3F/R 80°/65°
OGNITEMPO EXT for coverage
of PLATE HEAT EXCHANGER
combination with MODULEX EXT
CODE
Thanks to the modulating pump all the advantages
already seen for the models with mixing header are
maintained:
for all the outputs
OGNITEMPO EXT for coverage of primary rings,
suitable for external installations (class IPX5D).
• Efficacy in the condensating power• Energy recovery.
The supply, in parts to be assembled on site,foresees:
optional:
stainless steel AISI 316 L plate heat exchanger, withsealing gaskets in NBR, suitable for temperatures-15°C to 135 °C
additional safety devices kit
modulating pump
mechanical filtration system for the sludge
accessories, connections and basement
• t nearly constantΔ
150 ÷ 350 00362113
440 ÷ 900 00362120
Condensing Water Heaters > Modulex EXT Water Heaters
Optional Accessories
To complete installation supports are available to help
sustain the weight of the smoke channel.
REAR SMOKE DISCHARGE KIT FOR MODULEX EXT 150 TO 350
Cod. 00362076
FLUE TERMINAL SUPPORT KIT
Cod. 00362075
Neutralizers optional KitThe condensate, produced during the combustion process, reacts with the
NOX forming acidic molecules (PH = 4,5). It could be demanded that the
condensate is neutralized before its immersion in the sewerage. In the respect
of the ecosystem, proposes the neutralizers of condensate NH.Modulex EXT
KIT NH 300 - for boilers up to 300 kW
Kit NH 1500-P - for boilers up to 1500 kW
RECHARGE:Neutralizing material 25 kgs: Refill NH
(cod. 00262827): the neutralization happens
according to the principle of the passage of the
acidic condensate through the granular
neutralization material. The passage happens
upward from the lower part.
(cod. 00262829): in the system NH 1500-P
the condensate flows through a patented run in a
zone filled with granular neutralizing material, in
which an integrated filtering layer is also found.
At the exit from such a zone the neutralized
condensate reaches a level controlled pump,
operating also as a lifting system, that push it
towards the evacuation duct.
This system is able to treat up to 550 l/h of
condensate, for boilers up to 1500 kW.
MAXIMUM FLOW RATE
MAXIMUM BOILER OUTPUT
MANOMETRIC HEAD
STAGNATION HEIGHT
NEUTRALIZING MATERIAL
DURATION OF NEUTRALIZING MATERIAL
DIMENSIONS (L x W x H)
INLET/OUTLET CONNECTIONS
INLET/OUTLET HEIGHT
OVERFLOW HEIGHT
ELECTRICAL CONNECTION
ABSORBED ELECTRICAL POWER
ABSORBED CURRENT
PROTECTION DEGREE
l/h
kW
m
mm
mm
mm
mm
mm
W
A
70
300
-
95
Calcium carbonate
12 months (1500 working hrs)
410x310x220
25
30/100
-
-
-
-
-
550
3
90
Calcium carbonate
12 months (1500 working hrs)
670X470X280
25 / 10
30
100
230V/50Hz
74
0,33
IP 54
MODULEX EXT Tech Data Manual18
KIT NH-300 KIT NH-1500P
1500
MOUDLEX EXT Tech Data Manual 19
Modulex Ext 150 -350 Modulex Ext 440 - 900FRONT VIEW
RIGHT SIDEDelivery condition for right hand side connection
TOP VIEW
Gas inletDrain
GS
LEFT SIDE VIEW
PRE-CUT PARTFLOWLEFT SIDE
PRE-CUT PARTRETOURLEFT SIDE
PRE-CUT PARTGASLEFT SIDE
Water deliverySystem Return
MR
Gas inletDrain
GS
Water deliverySystem Return
MR
Dimensions
MODULEX EXT
NOMINAL INPUT on N.C.V. kW
NOMINAL OUTPUT in condensation 30° / 50°C kW
MINIMAL INPUT in condensation 30° / 50°C kW
NOMINAL OUTPUT in std. conditions 60° / 80°C kW
EFFICIENCY CLASS (directive EEC 92/42)
WATER EFFICIENCY at nom. load in condensation %
WATER EFFICIENCY at part load in condensation %
MAX. CONDENSATE PRODUCTION kg/h
NO x EMISSIONS (pondered value according to EN 15420) mg/kWh
WATER CONTENT l
Min.-Max WATER PRESSURE bar
WIDTH (L) mm
WIDTH (L1) mm
CHIMNEY CONNECTION mm
GAS CONNECTION G mm (inch)
C.H. FLOW / RETURN M / R mm (inch)
PROTECTION DEGREE IP
MAXIMUM ABSORBED POWER W
STAND-BY CONSUMPTION W
GROSS WEIGHT kg
150
150,1
12,5
146,1
100,8
106,8
23
53,8
14,2
0,5 - 6
764
706
150
50 (2)
64 (2½)
X5D
210
10
236
150
200
200,4
12,5
195,2
100,8
106,8
30,6
53,8
18,3
0,5 - 6
1032
974
150
50 (2)
64 (2½)
X5D
290
10
295
200
250
251,3
12,5
244,5
100,5
106,8
38,3
53,8
22,4
0,5 - 6
1032
974
200
50 (2)
64 (2½)
X5D
362
10
325
250
300
302,7
12,5
294
100,9
106,8
45,9
53,8
26,5
0,5 - 6
1300
1242
200
50 (2)
64 (2½)
X5D
435
10
386
300
348
354,6
12,5
342,2
101,9
106,8
53,6
53,8
30,6
0,5 - 6
1300
1242
200
50 (2)
64 (2½)
X5D
507
10
419
350
432
445
23,9
424,35
104
109
73,4
49
67
0,5 - 6
1087
1039
250 (2)
80 (3)
100 (4)
X5D
626
20
585
440
540
557,8
23,9
530,44
104
109
91,7
49
80
0,5 - 6
1355
1307
250
80 (3)
100 (4)
X5D
783
20
643
550
648
670,1
23,9
636,53
104
109
110
49
94
0,5 - 6
1355
1307
300
80 (3)
100 (4)
X5D
940
20
707
660
756
783,2
23,9
742,62
104
109
128,4
49
108
0,5 - 6
1623
1575
300
80 (3)
100 (4)
X5D
1096
20
806
770
864
900,3
23,9
849,05
104
109
146,7
49
122
0,5 - 6
1623
1575
300
80 (3)
100 (4)
X5D
1252
20
858
900
Telephone FacsimileEmail
1800 337 959 +61 3 9310 [email protected]
P.O. Box 35 Epping VIC 3076 Australiawww.automaticheating.com.au
DISTRIBUTED BY
Autom
atic Heating P
ty LtdA
BN
90 446 545 923
Dimensional Data
Model Width Depth Height Connections Connections Gas Flue
L C Flow Return Connections Diametermm mm mm mm mm mm mm
MX150EXT 764 770 1150 50(2)64 (2 ½) 150*/20064 (2 ½)
50(2)64 (2 ½)64 (2 ½)MX200EXT 1032 770 1150 150*/200
MX250EXT 1032 770 1150 50(2)64 (2 ½) 20064 (2 ½)
MX300EXT 1300 770 1150 50(2)64 (2 ½) 20064 (2 ½)
MX350EXT 1300 770 1448 50(2)64 (2 ½) 20064 (2 ½)
(*) the flue connection adapter Ø200/250 is included in the boiler delivery
MX440EXT 1087 946 1448 80(3)100 (4) 300100 (4)
MX550EXT 1355 946 1448 80(3)100 (4) 300100 (4)
MX660EXT 1355 946 1448 80(3)100 (4) 300100 (4)
MX770EXT 1623 946 1448 80(3)100 (4) 300100 (4)
MX900EXT 1623 946 1448 80(3)100 (4) 300100 (4)