Arion Air circuit breakers

Appendix of the catalogue Air circuit breakers Arion WL (VJ1-2007-A)

by new design of Arion WL11

Any changes reserved

VJ1-2011-A

www.oez.com

www.oez.com

OEZ s.r.o.Šedivská 339561 51 LetohradCzech Republictel.: +420 465 672 111 +420 465 672 101fax: +420 465 672 398 +420 465 672 151e-mail: [email protected]

Arion

1

CONTENT – Commercial information

DATA FOR SELECTION OF CIRCUIT BREAKER AND SWITCH-DISCONNECTOR .........................................................2

DATA FOR SELECTION OF OVERCURRENT RELEASE .....................................................................................................3

MEANING OF TYPE DESIGNATION POSITIONS ..............................................................................................................4

QUICK COMPOSITION OF TYPE DESIGNATION ...............................................................................................................5

COMPOSITION OF TYPE DESIGNATION 3-pole circuit breakers, switch-disconnectors for AC operation Fixed design ..................................................................................................................................................................6 Withdrawable design ....................................................................................................................................................7

COMPOSITION OF TYPE DESIGNATION 4-pole circuit breakers, switch-disconnectors for AC operation Fixed design ..................................................................................................................................................................8 Withdrawable design ....................................................................................................................................................9

BASIC ACCESSORIES - drives, auxiliary releases and switches ............................................................................10

CONTENT – Technical information

AIR CIRCUIT BREAKERS, SWITCH-DISCONNECTORS - specifi cations ............................................................................................................................................................11 - connection ................................................................................................................................................................13 - dimensions ...............................................................................................................................................................14

GLOSSARY ................................................................................................................................................................................17

Arion

2

Size IRated current In 630 A

800 A1000 A1250 A1600 A2000 A

Rated operating voltage Ue 690 V a.c.

Rated frequency fn 50/60 Hz

Rated short-circuit ultimate breaking capacity

Icu N - 55 kA/415 V a.c.S - 66 kA/415 V a.c.H - 85 kA/415 V a.c.

Rated short-time withstand current Icw N - 42 kA /1 sS - 50 kA/1 sH - 66 kA/1 s

Rated short-circuit making capacity Icm N - 121 kA/415 V a.c.S - 145 kA/415 V a.c.H - 187 kA/415 V a.c.

Number of poles 3, 4

Size

I

630

800

1000

1250

1600

2000

Dimensionsfi xed

3/4 pole

N S H

55 66 85

291 / 291

440.5 / 440.5

320 / 410

385 / 385

468.5 / 468.5

320 / 410

withdrawable3/4 pole

Rated short-circuit ultimate breaking capacity

Icu at 415 V [kA] a.c.

depth

height

width

Max. rated current of the circuit breaker I

n [A]

Size IRated current In 630 A

800 A1000 A1250 A1600 A2000 A

Rated operating voltage Ue 690 V a.c.

Rated frequency fn 50/60 Hz

Rated short-circuit making capacity Icm N - 121 kA/415 V a.c.S - 145 kA/415 V a.c.H - 187 kA/415 V a.c.

Rated short-time withstand current Icw N - 42 kA/1 sS - 50 kA/1 sH - 66 kA/1 s

Number of poles 3, 4

Commercial information

DATA FOR SELECTION OF CIRCUIT BREAKERS ››› for AC operation

DATA FOR SELECTION OF SWITCH-DISCONNECTOR ››› for AC operation

NEWSNEWS

Arion

3

DATA FOR SELECTION OF OVERCURRENT RELEASE

Overcurrent release name ETU15B ETU25B ETU27B ETU45B ETU76BOverload protection L + + + + +Short-time delayed short-circuit protection S – + + + +Instantaneous short-circuit protection I + + + + +Neutral conductor protection N – – + + +Earth fault protection G – – +Additional functions +Neutral conductor protection ON/OFF – – +/+ +/+ +/+Short-time delayed short-circuit protection ON/OFF – – – +/+ +/+Instantaneous short-circuit protection ON/OFF – – – +/+ +/+Thermal memory ON/OFF – – – + +Load guarding – – – + +Short-time delayed short-circuit protection switchable to I2t

– – – + +

Instantaneous short-circuit protection adjustable + – – + +Overload protection switchable to I4t – – – + +Overload protection ON/OFF – – – – +Adjustable neutral conductor protection N – – – + +Switchable parameter sets – – – – +Parameterization and displayParameterization by rotary switches (10 positions) + + + + –Parameterization by means of communication (absolute values)

– – – – +

Parameterization by means of menu (absolute values) – – – – +Remote parameterization of basic functions – – – – +Remote parameterization of additional functions – – – + +4-line LCD – – – –Graphic LCD – – – – +Measuring functionMeasuring function Plus – – –CommunicationCubicleBUS – – – + +PROFIBUS-DP/MODBUS – – –Ethernet – – –+ YES, – NO, Optional

Rating Plug

I R

I sd

t sd

Commercial information

Arion

4

MEANING OF TYPE DESIGNATION POSITIONS

Example of type designation: ARION WL1120-3CB36-4GA2-Z K07

Position number: 5 6 - 7 8 9 - 10 11 12 13 14 15 16

Type designation:  ARION WL1 1 20 - 3 CB 3 6 - 4 G A 2 - Z K07

Size                        

                     

Rated current                        

                       

Rated short-circuit ultimate breaking capacity                    

                         

Overcurrent release                  

                           

Number of poles                  

                             

Design and type of connection                

                               

Drive            

                                   

1st auxiliary release            

                                     

2nd auxiliary release          

                                       

Auxiliary switches        

                                         

Accessories (it is possible to fi ll in more codes at a time separated by plus sign)    

                                           

ARION WL1120-3CB36-4GA2-Z K07

Parameters and description of circuit breaker according to positions:5) size I 6 - 7) rated current In = 2000 A8) rated short-circuit ultimate breaking capacity Icu = 80 kA9 - 10) overcurrent release ETU25B11) 3-pole design12) withdrawable design, rear horizontal connection

13) hand and motor drive with closing release for 230 V a.c./220 V d.c.14) shunt trip 230 V a.c./220 V d.c.15) without 2nd auxiliary release16) 2NO + 2NC auxiliary contactsAccessory code - signal switch „switched off by overcurrent release“ - K07

STANDARD EQUIPMENT OF CIRCUIT BREAKER/SWITCH-DISCONNECTOR

Each circuit breaker/switch-disconnector has the following standard equipment

Fixed design Push-button for mechanical ON Push-button for mechanical OFF Hand drive with storage device Mechanical indicator of circuit breaker state - ON/OFF state Mechanical storage device state - wound up/released Mechanical indicator „ready-to-close“ Auxiliary switches - 2NO + 2NC contacts Terminal blocks and connectors for connection of auxiliary circuits -

the circuit breaker/switch-disconnector is always equipped with all necessary terminal blocks and connectors; terminal block has screw terminals

Mechanical indicator of switching off by overcurrent release Mechanical interlocking of reset after switching off by overcurrent release

Withdrawable design - withdrawable design contains additionally: Mechanical indicator of the circuit breaker position in the withdrawable device

Locking device against shifting of circuit breaker using a padlock

Commercial information

Arion

5

QUICK COMPOSITION OF TYPE DESIGNATION

The table can be used for quick and simple selection and composition of type designation of a circuit breaker/switch-disconnector ARION WL. The table contains only common types of circuit breakers/switch-disconnectors. For complete offer, use the catalogue.Type designation  ARION WL1 1 20 - 3 CB 3 6 - 4 G A 2 - Z K07

Size                        size I from 630 to 2000 A 1                        size II from 800 to 3200 A 2                      size III from 4000 to 6300 A 3                      Rated current                        630 A only size I 06                          800 A recommended size I 08                    1000 A recommended size I 10                    1250 A recommended size I 12                    1600 A recommended size I 16                    2000 A only size I 202000 A only size II 20                    2500 A only size II 25                    3200 A only size II 32                    4000 A only size II 404000 A only size III 40                    5000 A only size III 50                    6300 A only size III 63                    Rated short-circuit ultimate breaking capacity                    N – ECO 55 kA for size I, 66 kA for size II 2                            S – STANDARD 80 kA for size II, 66 kA for size I 3                  H – HIGH 85 kA for size I, 100 kA for size II and size III 4                  C – EXTRA 150 kA for size III (3-pole), 130 kA for size III (4-pole) 5Overcurrent release                  without overcurrent release Switch-disconnector AA                              ETU25B  Circuit breaker CB                ETU45B - without display Circuit breaker EB                ETU45B - with display Circuit breaker FB                ETU76B - with graphic display Circuit breaker NB                Design                  3 – pole 3                                4 – pole   4              Design                fi xed rear vertical connection 1                                  fi xed rear horizontal connection 2            fi xed front connection 4            withdrawable rear horizontal connection 6            withdrawable rear vertical connection 7            Drive            hand drive   1                                    hand and motor drive, closing release 230 V a.c./220 V d.c. 4          hand and motor drive, closing release 110 V a.c./d.c. 5          hand and motor drive, closing release 24 V d.c. 6          1st auxiliary release            without 1st auxiliary release   A                                      shunt trip 24 V d.c. B        shunt trip 110 V a.c./d.c. F        shunt trip 230 V a.c./220 V d.c. G        2nd auxiliary release          without 2nd auxiliary release   A                                        shunt trip 24 V d.c. B      shunt trip 110 V a.c./d.c. F      shunt trip 230 V a.c./220 V d.c. G      undervoltage release 24 V d.c. J      undervoltage release 110 V a.c./d.c. M      undervoltage release 230 V a.c./220 V d.c. N      Auxiliary switches        2 NO + 2 NC   2                                          4 NO + 4 NC   4    Accessories (it is possible to fi ll in more codes at a time separated by plus sign)    Electrical ON push-button on the front panel C11                                              Signal switch of the storage device state   C20  Signal switch „ready-to-close”   C22  Signal switch „switched off by release“   K07  Position signal switches in the withdrawable device R15  Door sealing frame   T40  Locking device against unauthorized closing on the front control panel S01  

Example of type designation: ARION WL1120-3CB36-4GA2-Z K07

Commercial information

Arion

6

COMPOSITION OF TYPE DESIGNATION 3P

Fixed design, 3-pole, ACRated current In 1)

[A]Rated short-circuit ultimate breaking capacity Icu /415 V

55 kA – size I 66 kA – size I 85 kA – size IRear horizontal connections

630 ARION WL1106-2 32- ARION WL1106-3 32- ARION WL1106-4 32-800 ARION WL1108-2 32- ARION WL1108-3 32- ARION WL1108-4 32-

1000 ARION WL1110-2 32- ARION WL1110-3 32- ARION WL1110-4 32-1250 ARION WL1112-2 32- ARION WL1112-3 32- ARION WL1112-4 32-1600 ARION WL1116-2 32- ARION WL1116-3 32- ARION WL1116-4 32-2000 ARION WL1120-2 32- ARION WL1120-3 32- ARION WL1120-4 32-

Rear vertical connections630 ARION WL1106-2 31- ARION WL1106-3 31- ARION WL1106-4 31-800 ARION WL1108-2 31- ARION WL1108-3 31- ARION WL1108-4 31-

1000 ARION WL1110-2 31- ARION WL1110-3 31- ARION WL1110-4 31-1250 ARION WL1112-2 31- ARION WL1112-3 31- ARION WL1112-4 31-1600 ARION WL1116-2 31- ARION WL1116-3 31- ARION WL1116-4 31-2000 ARION WL1120-2 31- ARION WL1120-3 31- ARION WL1120-4 31-

Front connections one series of holes630 ARION WL1106-2 33- ARION WL1106-3 33- -800 ARION WL1108-2 33- ARION WL1108-3 33- -

1000 ARION WL1110-2 33- ARION WL1110-3 33- -1250 ARION WL1112-2 33- ARION WL1112-3 33- -1600 ARION WL1116-2 33- ARION WL1116-3 33- -2000 - - -

Front connections two series of holes630 ARION WL1106-2 34- ARION WL1106-3 34- ARION WL1106-4 34-800 ARION WL1108-2 34- ARION WL1108-3 34- ARION WL1108-4 34-

1000 ARION WL1110-2 34- ARION WL1110-3 34- ARION WL1110-4 34-1250 ARION WL1112-2 34- ARION WL1112-3 34- ARION WL1112-4 34-1600 ARION WL1116-2 34- ARION WL1116-3 34- ARION WL1116-4 34-2000 ARION WL1120-2 34- ARION WL1120-3 34- ARION WL1120-4 34-

1 A A 2 Standard type designation Hand drive with mechanical closingAuxiliary switches: contacts 2200 (2NO + 2NC) (you will find other accessories on page 10)

Switch-disconnector unit (switch-disconnector) 2) AA

Overcurrent release - without earth fault protection (circuit breaker)Overcurrent release ETU15B – protective function LI BBOvercurrent release ETU25B – protective function LSI CBOvercurrent release ETU45B – protective function LSIN 3) EBOvercurrent release ETU45B – protective function LSIN, with display, number of lines 4 3) FBOvercurrent release ETU76B – protective function LSIN, graphic display 3) NB

Overcurrent release - with earth fault protection (circuit breaker)Overcurrent release ETU27B – protective function LSING 3) DGOvercurrent release ETU45B – protective function LSING 3) EGOvercurrent release ETU45B – protective function LSING, with display, number of lines 4 3) FGOvercurrent release ETU76B – protective functionLSING, graphic display 3) NG

1) Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.2) Permissible short-time withstand current Icw and rated short-circuit making capacity Icm of a switch-disconnector see page 12 (only for AC applications).3) Measuring current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40 in the catalogue Air circuit breakers Arion VJ1-2007-A.

For weight see page. 12

��

��

��

��

��

��

��

��

��

���

���

��

������

N S H

Commercial information

Arion

7

COMPOSITION OF TYPE DESIGNATION 3P

Withdrawable design, 3-pole, ACRated current In 1)

[A]Rated short-circuit ultimate breaking capacity Icu /415 V

55 kA – size I 66 kA – size I 85 kA – size IRear horizontal connections

630 ARION WL1106-2 36- ARION WL1106-3 36- ARION WL1106-4 36-800 ARION WL1108-2 36- ARION WL1108-3 36- ARION WL1108-4 36-

1000 ARION WL1110-2 36- ARION WL1110-3 36- ARION WL1110-4 36-1250 ARION WL1112-2 36- ARION WL1112-3 36- ARION WL1112-4 36-1600 ARION WL1116-2 36- ARION WL1116-3 36- ARION WL1116-4 36-2000 ARION WL1120-2 36- ARION WL1120-3 36- ARION WL1120-4 36-

Without withdrawable device630 ARION WL1106-2 35- ARION WL1106-3 35- ARION WL1106-4 35-800 ARION WL1108-2 35- ARION WL1108-3 35- ARION WL1108-4 35-

1000 ARION WL1110-2 35- ARION WL1110-3 35- ARION WL1110-4 35-1250 ARION WL1112-2 35- ARION WL1112-3 35- ARION WL1112-4 35-1600 ARION WL1116-2 35- ARION WL1116-3 35- ARION WL1116-4 35-2000 ARION WL1120-2 35- ARION WL1120-3 35- ARION WL1120-4 35-

Rear vertical connections630 ARION WL1106-2 37- ARION WL1106-3 37- ARION WL1106-4 37-800 ARION WL1108-2 37- ARION WL1108-3 37- ARION WL1108-4 37-

1000 ARION WL1110-2 37- ARION WL1110-3 37- ARION WL1110-4 37-1250 ARION WL1112-2 37- ARION WL1112-3 37- ARION WL1112-4 37-1600 ARION WL1116-2 37- ARION WL1116-3 37- ARION WL1116-4 37-2000 ARION WL1120-2 37- ARION WL1120-3 37- ARION WL1120-4 37-

Rear flanged connections630 ARION WL1106-2 38- ARION WL1106-3 38- ARION WL1106-4 38-800 ARION WL1108-2 38- ARION WL1108-3 38- ARION WL1108-4 38-

1000 ARION WL1110-2 38- ARION WL1110-3 38- ARION WL1110-4 38-1250 ARION WL1112-2 38- ARION WL1112-3 38- ARION WL1112-4 38-1600 ARION WL1116-2 38- ARION WL1116-3 38- ARION WL1116-4 38-2000 ARION WL1120-2 38- ARION WL1120-3 38- ARION WL1120-4 38-

1 A A 2 Standard type designation Hand drive with mechanical closingAuxiliary switches: contacts 2200 (2NO + 2NC) (you will find other accessories on page 10)

Switch-disconnector unit (switch-disconnector) 2) AA

Overcurrent release - without earth fault protection (circuit breaker)Overcurrent release ETU15B – protective function LI BBOvercurrent release ETU25B – protective function LSI CBOvercurrent release ETU45B – protective function LSIN 3) EBOvercurrent release ETU45B – protective function LSIN, with display, number of lines 4 3) FBOvercurrent release ETU76B – protective function LSIN, grafický displej 3) NB

Overcurrent release - with earth fault protection (circuit breaker)Overcurrent release ETU27B – protective function LSING 3) DGOvercurrent release ETU45B – protective function LSING 3) EGOvercurrent release ETU45B – protective function LSING, with display, number of lines 4 3) FGOvercurrent release ETU76B – protective function LSING, graphic display 3) NG

1) Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.2) Permissible short-time withstand current Icw and rated short-circuit making capacity Icm of a switch-disconnector see page 12 (only for AC applications).3) Measuring current transformers for vectorial addition or protection of N conductor shall be ordered separately, see page 40 in the catalogue Air circuit breakers Arion VJ1-2007-A.

For weight see page 12

��

��

��

��

��

���

��

��

���

N S H

Commercial information

Arion

8

COMPOSITION OF TYPE DESIGNATION 4P

Fixed design, 4-pole, ACRated current In 1)

[A]Rated short-circuit ultimate breaking capacity Icu /415 V

55 kA – size I 66 kA – size I 85 kA – size IRear horizontal connections

630 ARION WL1106-2 42- ARION WL1106-3 42- ARION WL1106-4 42-800 ARION WL1108-2 42- ARION WL1108-3 42- ARION WL1108-4 42-

1000 ARION WL1110-2 42- ARION WL1110-3 42- ARION WL1110-4 42-1250 ARION WL1112-2 42- ARION WL1112-3 42- ARION WL1112-4 42-1600 ARION WL1116-2 42- ARION WL1116-3 42- ARION WL1116-4 42-2000 ARION WL1120-2 42- ARION WL1120-3 42- ARION WL1120-4 42-

Rear vertical connections630 ARION WL1106-2 41- ARION WL1106-3 41- ARION WL1106-4 41-800 ARION WL1108-2 41- ARION WL1108-3 41- ARION WL1108-4 41-

1000 ARION WL1110-2 41- ARION WL1110-3 41- ARION WL1110-4 41-1250 ARION WL1112-2 41- ARION WL1112-3 41- ARION WL1112-4 41-1600 ARION WL1116-2 41- ARION WL1116-3 41- ARION WL1116-4 41-2000 ARION WL1220-2 41- ARION WL1220-3 41- ARION WL1220-4 41-

Front connections one series of holes630 ARION WL1106-2 43- ARION WL1106-3 43- -800 ARION WL1108-2 43- ARION WL1108-3 43- -

1000 ARION WL1110-2 43- ARION WL1110-3 43- -1250 ARION WL1112-2 43- ARION WL1112-3 43- -1600 ARION WL1116-2 43- ARION WL1116-3 43- -2000 - - -

Front connections two series of holes630 ARION WL1106-2 44- ARION WL1106-3 44- ARION WL1106-4 44-800 ARION WL1108-2 44- ARION WL1108-3 44- ARION WL1108-4 44-

1000 ARION WL1110-2 44- ARION WL1110-3 44- ARION WL1110-4 44-1250 ARION WL1112-2 44- ARION WL1112-3 44- ARION WL1112-4 44-1600 ARION WL1116-2 44- ARION WL1116-3 44- ARION WL1116-4 44-2000 ARION WL1220-2 44- ARION WL1220-3 44- ARION WL1220-4 44-

1 A A 2 Standard type designation Hand drive with mechanical closingAuxiliary switches: contacts 2200 (2NO + 2NC) (you will find other accessories on page 10)

Switch-disconnector unit (switch-disconnector) 2) AA

Overcurrent release - without earth fault protection (circuit breaker)Overcurrent release ETU15B – protective function LI BBOvercurrent release ETU25B – protective function LSI CBOvercurrent release ETU45B – protective function LSIN 3) EBOvercurrent release ETU45B – protective function LSIN, with display, number of lines 4 3) FBOvercurrent release ETU76B – protective function LSIN, graphic display 3) NB

Overcurrent release - with earth fault protection (circuit breaker)Overcurrent release ETU27B – protective function LSING 3) DGOvercurrent release ETU45B – protective function LSING 3) EGOvercurrent release ETU45B – protective function LSING, with display, number of lines 4 3) FGOvercurrent release ETU76B – protective function LSING, graphic display 3) NG

1) Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.2) Permissible short-time withstand current Icw and rated short-circuit making capacity Icm of a switch-disconnector see page 12 (only for AC applications).3) Internal measuring current transformer for protection of N conductor can be ordered with „F23“ code, see page 32 in the catalogue Air circuit breakers Arion VJ1-2007-A.

For weight see page. 12

��

��

��

��

��

��

��

��

��

���

���

��

��

��

��

N S H

Commercial information

Arion

9

COMPOSITION OF TYPE DESIGNATION 4P

Withdrawable design, 4-pole, ACRated current In 1)

[A]Rated short-circuit ultimate breaking capacity Icu /415 V

55 kA – size I 66 kA – size I 85 kA – size IRear horizontal connections

630 ARION WL1106-2 46- ARION WL1106-3 46- ARION WL1106-4 46-800 ARION WL1108-2 46- ARION WL1108-3 46- ARION WL1108-4 46-

1000 ARION WL1110-2 46- ARION WL1110-3 46- ARION WL1110-4 46-1250 ARION WL1112-2 46- ARION WL1112-3 46- ARION WL1112-4 46-1600 ARION WL1116-2 46- ARION WL1116-3 46- ARION WL1116-4 46-2000 ARION WL1120-2 46- ARION WL1120-3 46- ARION WL1120-4 46-

Without withdrawable device630 ARION WL1106-2 45- ARION WL1106-3 45- ARION WL1106-4 45-800 ARION WL1108-2 45- ARION WL1108-3 45- ARION WL1108-4 45-

1000 ARION WL1110-2 45- ARION WL1110-3 45- ARION WL1110-4 45-1250 ARION WL1112-2 45- ARION WL1112-3 45- ARION WL1112-4 45-1600 ARION WL1116-2 45- ARION WL1116-3 45- ARION WL1116-4 45-2000 ARION WL1120-2 45- ARION WL1120-3 45- ARION WL1120-4 45-

Rear vertical connections630 ARION WL1106-2 47- ARION WL1106-3 47- ARION WL1106-4 47-800 ARION WL1108-2 47- ARION WL1108-3 47- ARION WL1108-4 47-

1000 ARION WL1110-2 47- ARION WL1110-3 47- ARION WL1110-4 47-1250 ARION WL1112-2 47- ARION WL1112-3 47- ARION WL1112-4 47-1600 ARION WL1116-2 47- ARION WL1116-3 47- ARION WL1116-4 47-2000 ARION WL1120-2 47- ARION WL1120-3 47- ARION WL1120-4 47-

Rear flanged connections630 ARION WL1106-2 48- ARION WL1106-3 48- ARION WL1106-4 48-800 ARION WL1108-2 48- ARION WL1108-3 48- ARION WL1108-4 48-

1000 ARION WL1110-2 48- ARION WL1110-3 48- ARION WL1110-4 48-1250 ARION WL1112-2 48- ARION WL1112-3 48- ARION WL1112-4 48-1600 ARION WL1116-2 48- ARION WL1116-3 48- ARION WL1116-4 48-2000 ARION WL1120-2 48- ARION WL1120-3 48- ARION WL1120-4 48-

1 A A 2 Standard type designation Hand drive with mechanical closingAuxiliary switches: contacts 2200 (2NO + 2NC) (you will find other accessories on page 10)

Switch-disconnector unit (switch-disconnector) 2) AA

Overcurrent release - without earth fault protection (circuit breaker)Overcurrent release ETU15B – protective function LI BBOvercurrent release ETU25B – protective function LSI CBOvercurrent release ETU45B – protective function LSIN 3) EBOvercurrent release ETU45B – protective function LSIN, with display, number of lines 4 3) FBOvercurrent release ETU76B – protective function LSIN, graphic display 3) NB

Overcurrent release - with earth fault protection (circuit breaker)Overcurrent release ETU27B – protective function LSING 3) DGOvercurrent release ETU45B – protective function LSING 3) EGOvercurrent release ETU45B – protective function LSING, with display, number of lines 4 3) FGOvercurrent release ETU76B – protective function LSING, graphic display 3) NG

1) Rated current is determined by the rated current module (rating plug). The module delivered with standard version corresponds to the maximum rated current of the circuit breaker. If a smaller rated current is required, its change is possible, see page 31 in the catalogue Air circuit breakers Arion VJ1-2007-A.2) Permissible short-time withstand current Icw and rated short-circuit making capacity Icm of a switch-disconnector see page 12 (only for AC applications).3) Internal measuring current transformer for protection of N conductor can be ordered with „F23“ code, see page 32 in the catalogue Air circuit breakers Arion VJ1-2007-A.

For weight see page 12

��

��

��

��

��

���

��

��

���

N S H

Commercial information

Arion

10

BASIC ACCESSORIES 3P 4P

Selected type designation ARION WL1 - -

Hand drives with mechanical closing 1

Hand drives with electrical closing – closing release: load factor 100 %110 V a.c./110 V d.c. 2230 V a.c./220 V d.c. 3

Motor and hand drives with electrical closing – closing release: load factor 100 % - for permanent load230 V a.c./220 V d.c. 4110 V a.c./d.c. 524 V d.c. 6- diff erent operating voltages for motor drive and closing release

1st auxiliary releaseWithout 1st auxiliary release AShunt trips – load factor 100 % - for permanent load24 V d.c. B30 V d.c. C48 V d.c. D60 V d.c. E110 V a.c./d.c. F230 V a.c./220 V d.c. G

2nd auxiliary releaseWithout 2nd auxiliary release AShunt trips – load factor 100 % - for permanent load24 V d.c. B30 V d.c. C48 V d.c. D60 V d.c. E110 V a.c./d.c. F230 V a.c./220 V d.c. GUndervoltage releases – short-time delayed 80 or 200 ms24 V d.c. J30 V d.c. K48 V d.c. L60 V d.c. U110 V a.c./d.c. M230 V a.c./220 V d.c. N400 V a.c. PUndervoltage releases – delayed 0.2 ÷ 3.2 s48 V d.c. Q110 V a.c./d.c. R230 V a.c./220 V d.c. S400 V a.c. T

Auxiliary switches2NO + 2NC 24NO + 4NC 46NO + 2NC 75NO + 3NC 8

Commercial information

Arion

11

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS - AC OPERATION 3P 4P

Specifi cationsType ARION WL11...

Size I

Standards EN 60947-2IEC 60947-2

DIN VDE 0660 section 101

Approval marks

Number of poles 3, 4

Rated current In 630 A800 A

1000 A1250 A1600 A2000 A

Rated operating voltage Ue 690 V a.c.

Rated frequency fn 50/60 Hz

Rated pulse voltage - main current path Uimp 12 kV

- auxiliary circuits 4 kV

- control circuits 2.5 kV

Rated insulation voltage Ui 1000 V

Utilization category (selectivity) B

Rated short-time withstand current Icw See the table on page 12

Rated short-circuit ultimate breaking capacity Icu See the table on page 12

Rated short-circuit service breaking capacity Ics 100% Icu

Rated short-circuit making capacity Icm See the table on page 12

Switching off time at Icu 50 ms 1)

Mechanical switching on time 35 ms

Mechanical switching off time 38 ms

Switching off time by shunt trip 73 ms

Switching off time by undervoltage release 73 ms

Switching on time by closing release 80 ms

Power loss at In See the table on page 12

Mechanical endurance (for Icu 55, 66 kA/415 V a.c.)

- without maintenance 10 000 cycles

- with maintenance 3) 20 000 cycles (up to 1600 A), 15 000 cycles (2000 A)

Electrical endurance(for Icu 55, 66 kA/415 V a.c.)

- without maintenance (Ue = 1000 V) 10 000 cycles (up to 1600 A), 7 500 cycles (2000 A)

- with maintenance 3) 20 000 cycles (up to 1600 A), 15 000 cycles (2000 A)

Mechanical endurance (for Icu 85 kA/415 V a.c.)

- without maintenance 10 000 cycles

- with maintenance 3) 15 000 cycles

Electrical endurance(for Icu 85 kA/415 V a.c.)

- without maintenance 7 500 cycles

- with maintenance 3) 15 000 cycles (3P), 10 000 cycles (4P)

Switching frequency Ue = 690 V a.c. (1000 V a.c.) 60 cycles/h

Minimum dwell between circuit breaker switching off by overcurrent release and subsequent reclosing

80 ms 2)

Degree of protection IP20, IP41 with sealing frame, IP55 with transparent cover

Reference ambient temperature 40 °C

Ambient temperature range operation -25 °C ÷ +70 °C

(it is necessary to observe special conditions for LCD) storage -40 °C ÷ +70 °C

Sea level 2000 m

Climatic resistance IEC 68 section 30-20

Weight m See the table on page 121) - with ETU15B switching off time is 85 ms2) - only with automatic reset of reclosing blocking - circuit breakers of size I with Icu = H can operate in IT networks up to 690 a.c.3) - at replacement of main contacts and arc chutes

Size I

Technical information

Arion

12

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS - AC OPERATION 3P 4P

Parameters

Rated short-time withstand current Icw 1)

Size - Type I – ARION WL11…Designation of breaking capacity N S H0,5 s 50 kA 66 kA 751 s 42 kA 50 kA 662 s 29.5 kA 35 kA 463 s 24 kA 29 kA 371) - at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)

Rated short-circuit ultimate breaking capacity Icu 1)

Size - Type I – ARION WL11…Designation of breaking capacity N S H415 V a.c., 500 V a.c. 55 kA 66 kA 85 kA690 V a.c. 42 kA 50 kA 66 kA1) - at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)

Rated short-circuit ultimate making capacity Icm 1)

Size - Type I – ARION WL11…Designation of breaking capacity N S H415 V a.c., 500 V a.c. 121 kA 145 kA 187 kA690 V a.c. 88 kA 105 kA 145 kA1) - at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)

Rated conditional short-circuit current Icc 1)

Size - Type I – ARION WL11…Designation of breaking capacity N S H500 V a.c. 55 kA 66 kA 75 kA690 V a.c. 42 kA 50 kA 66 kA1) - at reverse connection the values do not change (input terminals 2, 4, 6, output terminals 1, 3, 5)

Losses at In - per 3 poleType Fixed design Withdrawable designARION WL1106… 100 W 195 WARION WL1108… 100 W 195 WARION WL1110… 100 W 195 WARION WL1112… 105 W 205 WARION WL1116… 150 W 350 WARION WL1120… 240 W 440 W

WeightType 3-pole 4-pole

Fixed designWithdrawable circuit breaker

+ withdrawable deviceFixed design

Withdrawable circuit breaker + withdrawable device

ARION WL1106… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kgARION WL1108… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kgARION WL1110… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kgARION WL1112… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kgARION WL1116… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kgARION WL1120… 43 kg 45 + 25 = 70 kg 50 kg 54 + 30 = 84 kg

Maximum load of the circuit breaker/switch-disconnector depending on ambient temperatureType 55 °C 60 °C 70 °CARION WL1106… 630 A 630 A 630 AARION WL1108… 800 A 800 A 800 AARION WL1110… 1000 A 1000 A 1000 AARION WL1112… 1250 A 1250 A 1210 AARION WL1116… 1600 A 1600 A 1490 AARION WL1120… 2000 A 1930 A 1780 A

Technical information

Arion

13

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P

Connection and installation

Recommended dimensions of main connections and min. cross-sections

TypeDimensions

Cu busbars [mm]Min. cross-section [mm2]

ARION WL1106... 1x 60 x 10 600

ARION WL1108... 1x 60 x 10 600

ARION WL1110... 1x 60 x 10 600

ARION WL1112... 2x 40x10 800

ARION WL1116... 2x 50 x 10 1000

ARION WL1120... 3x 50x10 1500

Main (power) circuit- is connected by Cu busbars- to extend connection options, use connecting sets see „types of main connections“- reverse connection is possible (inversion of input and output terminals) without limitation

of rated ultimate short-circuit breaking capacity Icu

- we recommend to coat the busbars with paint- input and output conductors/busbars must be reinforced mechanically to eliminace transfer

of electrodynamic forces into circuit breaker/switch-disconnector at short-circuits see fi g.

Rear horizontal connection Rear vertical connection Rear fl anged connection

��

��

��

��

��

������

��

��

��

��

��

������

��

������

��

���

��

��

�����

��

������

Front connection one series of holesFront connection two series of holes

��

��

��

��

Types of main connectionsFixed design

Withdrawable design

Rear horizontal connection Front connection one series of holes - custom delivery

Front connection two series of holes

Rear vertical connection

Rear horizontal connection Front connection one series of holes - custom delivery

Front connection two series of holes

Rear vertical connection Rear fl anged connection- custom delivery

Technical information

Arion

14

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P

Dimensions - size I - fixed design

Rear horizontal connection

15270300 10

390

123,

544

0,5

275

5) 4)

NS

E00

611

437,

5

60 90 90 90

b

3)

NSE00619

��

��

��

��

���

��

��

��

���

��

��������

���

���

��

���

��

��

���

��

����

15270300 10

390

123,

544

0,5

275

5) 4)

NS

E00

611

437,

5

15270300 10

390

123,

544

0,5

275

5) 4)

NS

E00

611

437,

5

15270300 10

390

123,

544

0,5

275

5) 4)

NS

E00

611

437,

5

��

���

������

��

��

����

��

��

��

��

��

���

��

� ��

� �

���

���

������� �

Front connection one series of holes

Front connection two series of holes

Rear vertical connection

Rated current Dimension a b c

up to 1000 A 10 10 10

1250 ÷ 2000 A 15 15 15

4-pole design1) Installation space for replacement of arc chutes.2) Deionization space, space for connection of auxiliary circuits.4) Connectors of auxiliary circuits with screw terminals (SIGUT).5) Connectors of auxiliary circuits with spring terminals.6) Dimension to internal surface of closed switchboard door.7) Fastening points for circuit breaker installation.8) Locking device against unauthorized closing, on the front control panel.9) Locking device against mechanical ON/OFF.11) Contact area.

Technical information

60.5

13.5

13.5

13.5

13.5113.5128.5

267.

5

127.

5

33.5

5.5

327.

5

541.

5

440.

544

0.5

440.

544

0.5

123.

512

3.5

123.

512

3.5

437.

543

7.5

437.

543

7.5

461.

5

Arion

15

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P

Dimensions - size I - withdrawable design

Rear horizontal connection

Front connection one series of holes

Front connection two series of holes

Rated current Dimension a b c

up to 1000 A 10 10 10

1250 ÷ 2000 A 15 15 15

4-pole design4) Connectors of auxiliary circuits with screw terminals (SIGUT).5) Connectors of auxiliary circuits with spring terminals.6) Dimension to internal surface of closed switchboard door.7) ARION WL in operating position.8) ARION WL in test position.9) ARION WL in disconnected position.10) Holes for fastening screws, diameter 10 mm.11) Contact area.

55

270

3013210

300

320

4)5)

10)

123,

527

546

8,5

NS

E00

621

551590 90 90

3)

10)10)

NSE00630

��������� ���

��������

�� ����

���

����

���

��

��

� �

���

������ �

������

���

��

��

��

��

���

������

��

��

��

��

55

270

3013210

300

320

4)5)

10)

123,

527

546

8,5

NS

E00

621

55

270

3013210

300

320

4)5)

10)

123,

527

546

8,5

NS

E00

621

Technical information

468.

546

8.5

468.

5

327.

5

367.5

121.5140.5

88.5

13.5

13.5

13.5

382.5

169.5

169.5

62.5

62.5

123.

512

3.5

123.

5

Arion

16

CIRCUIT BREAKERS, SWITCH-DISCONNECTORS 3P 4P

Dimensions - size I - withdrawable design

Rated current Dimension a b c

up to 1000 A 10 10 10

1250 ÷ 2000 A 15 15 15

55

270

3013210

300

320

4)5)

10)

123,

527

546

8,5

NS

E00

621

15 90 90 90

b

3)

NSE00629

121

NS

E00

631

90 9015 90

55 55 55 55

3)

Ø M 12

142,

5

5959

2633

NSE00632

282,

5

���

���

����

���

��

��������

�����

���

Rear vertical connection

Rear fl anged connection

55

270

3013210

300

320

4)5)

10)

123,

527

546

8,5

NS

E00

621

4-pole design4) Connectors of auxiliary circuits with screw terminals (SIGUT).5) Connectors of auxiliary circuits with spring terminals.6) Dimension to internal surface of closed switchboard door.7) ARION WL in operating position.8) ARION WL in test position.9) ARION WL in disconnected position.10) Holes for fastening screws, diameter 10 mm.11) Contact area.

Technical information

468.

546

8.5

267.

5

282.

5

127.

5

142.

5

13.5

123.

512

3.5

Arion

17

GLOSSARYNote: Precise wording of defi nitions and texts relating to a given term are detailed in the respective standards (see Name).

Title Symbol Explanation

Rated operating voltageEN 60947-1; 4.3.1.1

UeVoltage fi xed by the manufacturer. Several pertinent tests relate to its determination, as may also the utilization category. Along with the rated (operating) current, it determines the device’s utilization. The highest value of rated operating voltage may in no case be greater than the value of the rate insulation voltage Ui.

Rated insulation voltageEN 60947-1; 4.3.1.2

UiVoltage measure to which are related tests of dielectric strength and creepage distance.

Rated currentEN 60947-2; 4.3.2.3

InCurrent value of particular circuit breaker that can be handled uninterruptedly. The highest current valued tripping the circuit breaker in conformity with a specifi cally stated tripping characteristic.

Reduced rated current IRSpecifi cally established, reduced value of In current for a regulated time-dependent (thermal) release, and that the circuit breaker can handle continuously. Maximum setting is at value equal to In. Changing Ir shifts the release’s tripping characteristic along the current axis. Ir = k x In holds where k ≤ 1

Tripping time at a given Ir multiple tR Time after which circuit breaker will trip, if a current fl ows through it that is equal to the given multiple of Ir.Changing tr shifts the tripping characteristic along the time axis.

Release current of independent time-delayed (selective) release

IsdMinimum current value causing the release’s time-independent delay to actuate.

Delay of time-independent delayed release tsdIf a current fl ows through the circuit breaker equal to at least Irmv but not reaching Irm the circuit breaker will trip with time delay tv. Total switching off time is infl uenced by the tripping of the circuit breaker itself and is about 10 ÷ 20 ms longer.

Release current of independent instantaneous (short-circuit) release

IiMinimum current value causing the time-independent instantaneous release to actuate.

Rated operating currentEN 60947-1; 4.3.2.3

IeRated operating current of device (switch-disconnector) is fi xed by the manufacturer with consideration for the rated operating voltage, rated frequency, rated operation, utilization category and type of protective cover, if that comes into consideration.

Rated normal currentEN 60947-1; 4.3.2.4

IuCurrent value set by the manufacturer, and which the device can handle in continuous operation,i.e. during a period longer than 8 hours (weeks, months, or longer).

Rated short-circuit ultimate breaking capacityEN 60947-2; 2.15.1; 4.3.5.2.1

IcuUltimate short-circuit breaking capacity value expressed as the RMS value of the alternating component of the assumed short-circuit current, that the circuit breaker must be able to manage in the mode: 1x switching off of the short-circuit and a following 1x make-break sequence. After testing, the circuit breaker need not be able to conduct the rated current uninterruptedly. Icu is set for the rated operating voltage at the rated frequency and at the established power factor for alternating current or at the time constant for direct current. Must fulfi l the condition: Icu ≥ Ik

Rated short-circuit service breaking capacityEN 60947-2; 2.15.2; 4.3.5.2.2

IcsValue of the operating short-circuit breaking capacity expressed as the rms value of the alternating component of the assumed short-circuit current, that the circuit breaker must be able to manage in the mode: 1x switching off of the short-circuit and a following 2x make-break sequence. May also be expressed as a percentage of Icu.After testing, the circuit breaker must be able uninterruptedly to conduct the rated current and to switch off the overcurrent. Temperature increase of the main terminals may be greater. Ics is set for the rated operating voltage at the rated frequency and at the established power factor for alternating current or at the time constant for direct current. Permitted: Ics ≥ Ik“

Rated short-time withstand currentEN 60947-1; 4.3.6.1EN 60947-2; 4.3.5.4EN 60947-3; 4.3.6.1

IcwValue of short-time withstand current specifi ed by the manufacturer, that the device is able to handle without damage during a designated time period (short-time delay). In case of alternating current, it is the rms value of the alternating component of the assumed short-circuit current Ip.

Rated conditional short-circuit currentEN 60947-1; 4.3.6.4EN 60947-2; Supplement L; L.4.2

IccThe prospective short-circuit value given by the producer that can be transferred by the device, protected against short-circuit by protective device, within its operation. Must fulfi l the condition: Icc ≥ Ik“

Technical information

Arion

18

GLOSSARYNote: Precise wording of defi nitions and texts relating to a given term are detailed in the respective standards (see Name).

Title Symbol Explanation

Rated short-circuit making capacityEN 60947-1; 4.3.6.2EN 60947-2; 4.3.5.1EN 60947-3; 4.3.6.2

IcmValue of short-circuit making capacity specifi ed by the manufacturer for the rated operating voltage at the rated frequency and at the established power factor for alternating current or at the time constant for direct current. It is expressed as the maximum assumed peak current.Must fulfi l the condition: Icm ≥ ip

Initial peak short-circuit currentEN 60909-0; 1.3.5

Ik“ Short-circuit current value at the moment of its arising at a given point in the electrical distribution expressed as

the RMS value of the alternating symmetrical component of the assumed short-circuit current.

Surge short-circuit currentEN 60909-0; 1.3.8

ipMaximum possible momentary value of the assumed short-circuit current. (Corresponds to the moment the short arises, as a result of which there occurs the peak value of the short-circuit current.)

Prospective short-circuit currentEN 60947-1; 2.5.5EN 60909-0; 1.3.3

IpShort-circuit current value, which would fl ow through the circuit if the protection device were replaced and a short-circuit were experienced by conductors with negligible impedance (In a three-phase distribution, it is assumed that the short-circuit is simultaneous in all phases.)

Rated impulse withstand voltageEN 60947-1; 4.3.1.3

UimpPeak value of the voltage impulse of the prescribed form and polarity, which the device is able to withstand without failure at the established conditions and pertinent to which is the value of the separating air distance. Uimp of the device must be equal to or higher than the value established for momentary overvoltage at the point in the circuit (overvoltage category) where the device is used.

Overvoltage categoryEN 60947-1; 2.5.60

Numerically defi ned level of momentary overvoltage, i.e. overvoltage having its origin in atmospheric or switching. Standard EN 60664-1 establishes for electrical equipment the overvoltage categories:Overvoltage category IV - wiring entrance, outside leadOvervoltage category III - fi xed wiringOvervoltage category II - appliancesOvervoltage category I - light-current appliances

Rated frequencyEN 60947-1; 4.3.3

fnFrequency of the supply network for which the device is proposed and that corresponds to its other characteristics values.

Utilization category (circuit breakers – time selectivity)EN 60947-2; 4.4

Utilization category of circuit breaker establishes whether or not the circuit breaker specifi cally is intended for providing selectivity by means of intentional time delay (time selectivity) with other protective devices connected in series on the load side in short-circuiting conditions.Utilization category: A - circuit breakers are not specifi cally intended for providing time selectivity B - circuit breakers are specifi cally intended for providing time selectivity

Utilization category (switch-disconnectors – switching mode)EN 60947-3; 4.4

Utilization category defi ned the assumed use of switch devices (switch-disconnectors). Characterized by values of current and voltage, expressed as multiples of rated operating current and rated operating voltage, and further by power factors or time constants of the circuit.Utilization category: AC-21B (DC-21B) - infrequent switching of resistive loads, including moderate overloadingAC-22B (DC-21B) - infrequent switching of mixed resistive and inductive loads, including moderate overloadingAC-23B (DC-23B) - infrequent switching of motor loads or other highly inductive loads

Pollution degreeEN 60947-1; 2.5.58; 6.1.3.2

Pollution degree relates to the conditions of the surrounding environment for which the device is intended.Pollution degree:1 - No contamination will occur, or only dry, non-conducting contamination.2 - Normally occurs only non-conducting contamination, but sometimes there may occur temporary conductibility

due to condensation.3 - There occurs conductive contamination or dry non-conducting contamination that with the eff ect of condensation

will become conductive.4 - Contamination generates continuous conductibility, by means of, for example, conductive dust, rain or snow.

Technical information

NOTES

Arion

19

NOTES

Arion

20