air-cooled chillers myths & facts - issue oct-dec 2003

Upload: nedunurimadhav-murthy

Post on 04-Jun-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    1/16

    [Home] Search:

    Theme:

    Issue : October-December 2003

    Air-Cooled Chillers : Myths & Facts

    It is commonly assumed that Air-Cooled Chillers are ineffecient and not suitable for

    the hot climate prevailing in north India. The factual situation is very different, as

    explained in this article.

    By Nirmal C. Gupta

    Gupta Consultants

    New Delhi.

    Nirmal C. Gupta is a mechanical engineer from Oklahoma State University, USA.

    He returned to India in 1957, worked 14 years for Blue Star Ltd. and then started his

    consultancy business where he continues to remain the principal consultant. He is

    currently chairman of ASHRAE India Trust.

    Air-cooled chillers have been used in the USA for a long time with great

    effectiveness, due to their simplicity of design and operation. In view of scarcity of water

    in the Middle East, major manufacturers in the West, have modified the chiller design,

    so that they can work satisfactorily even in the hot and humid climates prevailing there.

    Thus, their use has become quite extensive in the Middle East, with great success, and

    for a variety of applications.

    Their use in India has been slow, because of the general perception that these

    chillers consume too much power and hence are not suitable for Indian conditions. The

    experience gained by their use in the Middle East, has been useful in deciding to use

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    2/16

    aircooled chillers in India. It has been found that these units can withstand both high

    and low temperatures and monsoon rain without affecting their performance.

    Further, detailed analysis which was carried out on some installations has thrown

    up some interesting facts and has established their overall efficiency and suitability,

    regardless of climate conditions. It is also a fact that the use of these chillers, results in

    conserving water resources, which are becoming scarce in many places, and which does

    not have the required quality, hence, requiring extensive treatment.

    The operation of these chillers is simple, because there are fewer parts to operate.

    Maintenance costs are also lower due to fewer components and saving in the water

    treatment plant.

    Power consumption (air-cooled system)

    The main assumption against aircooled chillers is that they consume too much power

    and hence are very inefficient. It is true that at an ambient temperature of 44C their

    power consumption is quite high and is in the range of 1.3 to 1.5 ikW/ton, depending on

    the type of compressors being used.

    The lower figure of 1.3 ikW applies to reciprocating and scroll compressors and the

    higher figure applies to screw compressors, which are otherwise efficient in watercooled

    applications. However, the fact to be noted is that in an aircooled system the output of

    the chiller increases and power consumption falls as the ambient temperature reduces.

    Thus, the power required at 29C (85F) is as low as 0.94 ikW/ton. Overall, the

    power required varies between 0.94 to 1.5 ikW/ ton. The power consumption at 35C is

    quite favorable as compared to watercooled units.

    This brings about two interesting facts :

    The maximum temperature in north India varies from a low of 30C in March to a

    maximum of 44C in May/June and again reduces to 27C in November, during which

    month air conditioning is still required. It also varies from a minimum of 18C in March

    to 31C in May/June and further drops down to 15C in November.

    In the central plains of India, while the maximum temperature is similar to the

    North, the minimum temperature is generally much lower. Also, in these places (such as

    Nagpur, Pune, Indore, Hyderabad, Bhopal etc.) the maximum and minimum

    temperature reduce considerably once the rains start.

    Hence, it is clear that the power consumption will vary not only from month to

    month, but also from day to day, as well as from morning to evening, everyday, and in

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    3/16

    all parts of the country.

    Table 1: Sample hourly calculation

    City :New Delhi

    Operating Time :8AM to 6PM

    Hours per Day :10

    Days per Months 25

    Days per months 25

    F Max

    Temp

    Min.

    Temp

    Daily

    Range

    Hours of use upto given temprature

    limits

    C 85 90 95 100 105 110

    Months 29 32 35 38 41 44 Total

    Hours

    March 90

    32

    65

    18

    25

    14

    75 175 -- -- -- -- 250

    April 100

    38

    70

    21

    30

    17

    25 50 175 -- -- -- 250

    May 110

    44

    80

    26

    30

    18

    -- -- 25 50 50 125 250

    June 110

    44

    80

    26

    30

    18

    -- -- 25 50 50 125 250

    July 9535

    7524

    2011

    -- 25 175 50 -- -- 250

    August 95

    35

    75

    24

    20

    11

    -- 25 175 50 -- -- 250

    September 90

    32

    78

    25

    12

    7

    25 225 -- -- -- -- 250

    October 90

    32

    72

    22

    18

    10

    75 175 -- -- -- -- 250

    November 85

    29

    70

    21

    15

    8

    250 -- -- -- -- -- 250

    A) Sub

    Total

    Hours

    X X X 450 675 575 200 100 250 2250

    B) Power

    ikW/ton

    X X X 0.94 1.00 1.10 1.20 1.3 1.4 Total

    ikW/ton

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    4/16

    C) sub-Total

    ikW/ton

    A X B 423 675 632 240 130 350 2450

    Mean

    annual

    ikW/ton

    C(Total)A(Total) 24502250 1.09

    WaterRequired

    If cooling pads arefitted on chillers)

    NAX

    NAX

    NAX

    [top]

    In an office application, the air conditioning system operates for 250 to 300 days in

    a year, depending on the location of the city. Thus, the annual operating hours for

    offices working 10 hours a day, are between 2,500 to 3,000 out of a total of 8,760 hours

    in a year. An hourly chart in Table 1indicates the number of hours for which a system

    operates annually at different ambient temperatures in north India.

    What emerges is that, the hours of operation in excess of 35C ambient are only

    between 500 to 600 or 20% of the total operating time. The system, therefore, operates

    between 27C to 35C for 80% of the time and the power consumption at these points is

    quite favorable. The average power consumption thus varies between 1.0 to 1.1 ikW/ton

    and not 1.3 to 1.5 as it would appear at first glance.

    In cases where a system operates for 12 or 24 hours per day, the percentage of hours

    above 35C will be much less than 20%. This will result in an even lower average ikW/

    ton. This is quite favourable as compared to the water-cooled system as can be seen later

    in this article.

    As the demand reduces the ikW of the chiller compressor reduces and also the

    power used by condenser fans, reduces proportionally because some of the fans shut

    down on reduced demand and also at lower ambient temperatures. Thus, the ikW

    remains nearly constant even at part loads conditions.

    Added benefit

    There is another advantage of aircooled chillers in night application. During night, while

    the building load falls by 20 to 30%, the output of the chiller increases by 20 to 25%.

    Thus, while one air-cooled unit may meet the night requirement, it may be necessary to

    run 1 water-cooled units for the same load.

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    5/16

    Cooling pads on condenser

    Another method which can be adopted to improve the efficiency of the air-cooled units,

    is to provide cooling pads over the condenser. This method has not been tried out

    sufficiently, but there is no reason for any apprehension or doubt about the unit

    performance with pads. The water flow on the cooling pad could be activated, only when

    the ambient temperature crosses 35C (95F).

    The result would be that the maximum ikW/ton will not exceed the ikW obtained at

    35C and in fact will reduce further. This will reduce the Mean ikW/ton by an additional

    5% to 1.04.

    The water required for 500 to 600 hours on the pads, is approximately 10% of the

    water required for a water-cooled system. The increase in generator capacity will only

    be 5% instead of 20% and this can make the air-cooled systems more attractive than

    water-cooled systems in certain cases.

    Power consumption (watercooled systems)

    The power consumption of a water-cooled system is given here for the purpose of

    comparison. The power consumption in a watercooled system is dependent on the

    ambient wet bulb temperature and not the dry bulb temperature. The daily and monthly

    variation in wet bulb temperature is much less than the dry bulb temperature.

    Further, the variation in water temperature leaving the cooling tower is even lower

    than the variation in wet bulb temperature. Hence, the output and power consumption

    (ikW) of a watercooled chiller does not change appreciably in different ambient

    conditions, throughout the year.

    The total ikW of a water-cooled system also has to include the power consumed by

    the condenser water pumps and the cooling towers. Therefore, the result is that while

    the ikW of the chiller itself reduces proportionately to the reduction in the requirement,

    the kW of pump and cooling tower remains constant. This results in a higher overall ikW

    for the system at part loads.

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    6/16

    Normally an air conditioning system does not operate at full load conditions for

    more then 10% of the operating hours. The system loading usually varies between 40%

    to 90% of the full load for most of the operating time. It is obvious, that the overall ikW

    of the water-cooled system is higher than the ikW of the compressor. In view of the

    above, the net ikW of the two types of system are close and not very different, as is

    generally assumed.

    [top]

    Hourly calculation chart

    An hourly calculation chart has been devised and prepared, to be able to analyze and

    calculate the Mean ikW/ton for an air-cooled chiller. A sample calculation has been

    carried out for the Delhi climate to arrive at the Mean annual ikW per ton. Similar

    calculations can be carried out for any other city using the weather data and daily

    variation chart.

    It will be seen that the maximum and minimum temperatures have been worked out

    for each month based on ISHRAE weather data for monthly variations and the daily

    range each month, based on the Carrier Handbook.

    The daily range is then used in conjunction with the Carrier Handbook chart to

    arrive at the number of hours for which the system is likely to operate upto a given

    ambient temperature which represents the air entering temperature to the chillers. A

    copy of Carrier Chart is given in Table 2.

    Table 2 : Daily temperature variation Ref.: Handbook of Air Conditioning System

    Design by Carrier Air Conditioning Corp., USA.

    Daily Range

    of

    Temperature

    (F)*

    Dry or

    Wet-Bulb

    SUN TIME

    AM+ PM

    8 10 12 2 3 4 6 8 10 12

    10 Dry-BulbWet-Bulb

    -9-2

    -7-2

    -5-1

    -10

    00

    -10

    -2-1

    -5-1

    -8-2

    -9-2

    15 Dry-Bulb

    Wet-Bulb

    -12

    -3

    -9

    -2

    -5

    -1

    -1

    0

    0

    0

    -1

    0

    -2

    -1

    -6

    -1

    -10

    -3

    -14

    -4

    20 Dry-Bulb

    Wet-Bulb

    -14

    -4

    -10

    -3

    -5

    -1

    -1

    0

    0

    0

    -1

    0

    -3

    -1

    -7

    -2

    -11

    -3

    -16

    -4

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    7/16

    25 Dry-Bulb

    Wet-Bulb

    -16

    -4

    -10

    -3

    -5

    -1

    -1

    0

    0

    0

    -1

    0

    -3

    -1

    -8

    -2

    -13

    -3

    -18

    -5

    30 Dry-Bulb

    Wet-Bulb

    -18

    -5

    -12

    -3

    -6

    -1

    -1

    0

    0

    0

    -1

    0

    -4

    -1

    -10

    -3

    -15

    -4

    -21

    -6

    35 Dry-Bulb

    Wet-Bulb

    -21

    -4

    -14

    -4

    -7

    -2

    -1

    0

    0

    0

    -1

    0

    -6

    -1

    -12

    -3

    -18

    -5

    -24

    -7

    40 Dry-Bulb

    Wet-Bulb

    -24

    -7

    -16

    -4

    -8

    -2

    -1

    0

    0

    0

    -1

    0

    -7

    -2

    -14

    -4

    -21

    -6

    -28

    -9

    45 Dry-Bulb

    Wet-Bulb

    -26

    -7

    -17

    -5

    -8

    -2

    -2

    0

    0

    0

    -2

    0

    -8

    -2

    -16

    -4

    -24

    -8

    -31

    -10

    *The daily range of dry-bulb temperature is the difference between the highest and

    lowest dry-bulb temperature during a 24 hour period on a typical design day.

    Equation: Outside Design temperature at any time = Standard Outside Designtemperature + correction from above table.

    The power consumption and output at different air entering temperatures are

    available from chiller manufacturers. The ikW/ton and hours at each condition have

    been multiplied to arrive at the total ikW/hours at each temperature. This data has been

    used to work out the Mean ikW/ton for the whole year.

    It will thus be seen that the average ikW/ton is only 1.09 which is not very high. In

    the case of a water- cooled system, the net ikW/ ton even at full load works out to 0.95

    for reciprocating, scroll and small size screw compressor and at part load this figure

    increases to 1.0 ikW.

    Design of air-cooled chillers

    Air-cooled chillers usually contain more then one compressor, except in units of very

    small capacity. This is true for all units with different types of compressors i.e. scroll,

    reciprocating and screw. The compressors are either connected to separate chillers or a

    single chiller with upto three independent circuits.

    Thus, the units operate as multiple separate circuits, in which case the problem or

    failure in one circuit does not affect the performance of the other circuit or circuits. This

    provides for built-in redundancy and in many cases, in small installations a single unit

    can provide a certain margin of safety.

    The condenser coils are also divided in the same number of circuits as the

    compressor to provide total separation. There are multiple propeller/axial fans for

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    8/16

    removing condenser heat.

    The whole system is operated by either a microprocessor or advanced

    electro/mechanical control system. This cycles the operation of fans in proportion to the

    demand and helps in maintaining the lowest possible discharge pressure in relation to

    the prevailing ambient dry bulb temperatures. This process saves on condenser fan

    power and also tries to achieve optimum ikW/ton based on the prevailing ambient

    conditions.

    All the components are mounted on a sturdy composite steel frame work. The

    weight of the components is distributed evenly for nearly equal loading on the structure.

    The frame work is large enough, so that the overall loading of the unit does not exceed

    500 kg/m2. This loading suits all standard RCC construction.

    All the electrical components are encased in a weather-proof housing. In addition,

    all components, frame work etc. are treated with protective processes to be able to

    withstand all types of extreme weather conditions including heat, dust, sea breeze, rain

    etc. All the operational components are connected to an electro-mechanical control

    system or a microprocessor- based control system.

    The function of the control system is many fold as given below :

    Pre-start check up of all components and system.

    Sequential start of condenser fans and compressors.

    To maintain design head pressure at varying ambient temperature.To maintain design chilled water temperature.

    Protect the components from damage due to high/low pressure, freeze up etc.

    The operation of the multiple condenser fans is decided by the ambient

    temperature so that the head pressure of the system remains as low as possible at

    a given ambient temperature and is consistent with the safety of the compressors.

    Generally, the head pressure is not allowed to fall below the pressure

    corresponding to an ambient temperature of 28C.

    The control of head pressure is achieved by cycling the number of condenser

    fans.

    The operation of the number of these fans also allows the ikW to remain

    proportional even at part load, unlike water-cooled units, where the power of

    condenser water pumps and cooling towers remains constant even at part loads.

    [top]

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    9/16

    Heat pumps

    The use of air cooled chillers offers another advantage in places where both cooling and

    heating are required. These units can efficiently provide both cooling in extreme hot

    weather and heating in extreme cold weather, when the machines are configured in a

    "Heat Pump" mode.

    In winter, the air-cooled condenser becomes the evaporator to extract heat from the

    atmosphere. The unit chiller then acts as a shelland- tube condenser, to produce hot

    water, which can be used for providing heating in the premises. The outlet temperature

    of the hot water can be as high as 55C, but is usually designed for 50C to achieve a

    reasonable balance between cooling efficiency and heating demand.

    The advantage of the heat pump is that it produces the same amount of hot water as

    an electric boiler by using less then approximately 40% of electricity as compared to an

    electric boiler. This can reduce the overall cost of winter heating by 50% as compared toan electric hot water system.

    A further provision in the aircooled chiller or heat pump is that of a superheat (or

    auxiliary) condenser to generate hot water. This auxiliary condenser removes the excess

    superheat from the discharge gas, before it goes to the condenser without affecting the

    performance of the refrigeration cycle. This heat from the discharge gas is available both

    in cooling cycle and the heating cycle. The bonus hot water thus becomes available both

    in summer and winter or for nearly 10 months in a whole year.

    The hot water produced by this extra condenser can be used to meet the hot water

    requirements of the kitchen and toilets without any additional operating cost. This

    bonus heat improves the overall performance of the air-cooled system.

    Heat pumps for winter

    Heat Pumps are also available for providing maximum efficiency during the heating

    cycle. These heat pumps represent an ideal solution for places which require heating

    only in winter and where electricity is the main source of energy.

    The addition of an auxiliary condenser can meet the other hot water requirements

    during winter months.

    As stated earlier, the use of heat pumps for winter heating would reduce energy

    consumption by over 50% and thus pay back the extra cost within a short time.

    Cost of air-cooled system

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    6 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    10/16

    The cost of this system is generally quite favourable, for capacities of upto 1,000 ton.

    This is evident from the fact that in an aircooled system, one single unit (the chiller)

    replaces the following components of a water-cooled system:

    Induced draft cooling tower.

    Condenser water pump.

    Condenser water piping, valves and fittings.

    Electricals i.e. panel, cables etc. to connect the cooling tower and the condenser

    water pump.

    Water treatment plant.

    Underground and overhead storage tanks for the treated water and its pumping

    system.

    Several comparative analysis have found that the cost of an air-cooled system varies

    between 95% to 105% of a similar water-cooled system. The variation in the cost of the

    two types of system depends on the size of the plant and whether indigenous or

    imported chillers are selected.

    There is however, an additional cost due to a bigger D.G. set capacity, but this is not

    significant in the overall context.

    Comparative chart

    A chart showing the advantages and disadvantages of an air-cooled and water-cooled

    system is given in Table 3.

    Table 3 : Comparison of the Air-cooled and Water-cooled Chilling Units. (Based on

    100 TR)

    S. No. Description Water-Cooled Air-Cooled

    1. Water Requirement Water consumption will

    be @ 12 LPH / ton or

    12,000 litres / hour for

    225 days in a year.

    Not Required

    2. Power Consumption Lower power

    consumption at full load

    capacity. However, the

    difference reduces at part

    load as the pumps and

    cooling tower consume

    Slightly higher by

    approximately 9%

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    16 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    11/16

    constant power.

    3. Installed Power capacity Less then air cooled by

    20%.

    20% higher capacity is

    required.

    4. Covered space

    requirement

    Covered space is required

    for all equipments e.g.

    chiller, pumps, electricalpanel etc. approximately

    150 m2.

    Covered space is required

    only for pumps and

    Electrical panelapproximately 15 m2.

    5. Space for Cooling Tower

    on ground or Terrace

    Space for cooling tower is

    required, approximately

    80 m2.

    No cooling tower is

    required. Space to

    accommodate chillers

    will be 120 m2.

    6. D.G. Set size D.G. set of lower capacity

    is required.

    D.G. set of higher

    capacity is required as

    the power demand of the

    system is higher at full

    load.

    7. Staff for Maintenance

    and Operation

    More number of staff is

    required because of more

    number of equipments.

    50% less staff is required

    because of less number of

    equipments to operate

    and maintain.

    8. Descaling of condenser

    tube

    Descaling of condenser

    tube is

    required twice a season.

    Descaling of condenser is

    not required.

    9. Water Softening plant

    requirement

    Water softening plant is

    required.

    Water softening plant is

    not required.

    [top]

    Water saving

    The water-cooled system requires approximately 12 litres of water per hour per ton

    capacity. This water has to be of a reasonably good quality as per factors given below:

    It should not be turbid or contain suspended impurities.

    The PH value must be between 6.5 and 7.5 to prevent salt deposition when it is

    alkaline or corrosion when PH value is acidic.

    The total permanent, CaCo3 hardness should be below 120 PPM, otherwise the

    scaling on condenser tubes will require very frequent cleaning.

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    16 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    12/16

    Since most available water has impurities and high hardness level, the water has to

    be filtered and softened, with a water softener for the make-up water system. If the

    water is not softened, it will cause deposition of salts on the tubes of the water-cooled

    condenser, which reduces heat transfer and raises the ikW of the chiller.

    As the air-cooled system does not use water, all the above processes of descaling etc.

    become unnecessary and irrelevant. In addition, there is a saving of water of nearly 120

    litres per day per ton or 12,000 litres per day for a small 100 ton system.

    Simple operating system

    The high side equipment in an air-cooled system consists of only two main components

    i.e the air-cooled chillers and chilled water pumps. This is, in contrast to the high side

    equipment of the water-cooled system which not only requires water-cooled chillers and

    chilled water pumps, but also requires:

    Condenser water pumps

    Cooling towers

    Additional condenser water piping

    Additional electrical equipment

    Water storage for cooling towers

    Water treatment plant

    Pumping system for make up water

    It is obvious that the additional equipment requires more steps to put the plant in

    operation. It also requires greater effort to make sure that there is adequate quantity of

    suitable quality of water in the cooling tower at all times and that the water treatment

    system is always functional.

    If there is a shortage of water, the system may stop in mid-operation, and poor

    water quality will lead to scaling in the pipes, condenser etc.

    It is clear that to operate the aircooled system, no such care is required. The system

    can simply be put in operation in just two steps of starting the water pumps and the

    chiller at any time. The conclusion of simplicity of operation is obvious.

    Ease of maintenance

    Air-cooled systems are also simple to maintain, as there are fewer components, in view

    of the fact, that the condenser water pumps and cooling towers are not required.

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    16 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    13/16

    The cooling towers require periodic cleaning to remove the sludge which

    accumulates in the sump. It is necessary to make sure that there is sufficient quantity of

    water in the cooling tower at all times to ensure proper functioning of the system.

    The water treatment plant requires constant attention, so that the makeup water is

    always below the required hardness. There is also a need for regular descaling of the

    condenser tubes, so that the condenser efficiency is maintained near its peak.

    In comparison, the air-cooled condenser does not scale and therefore, it only

    requires annual cleaning with hot water to function properly. It is quite clear that there

    are very few components or functions which need to be checked in an aircooled system.

    Therefore, fewer number of staff are required for the operation and maintenance of

    the air-cooled system.

    Space saving

    The air-cooled chiller has to be installed in an open space without any roof cover on top.

    Therefore, these units are installed either on the roof of a building or in an open space,

    outside the building. The space required for them is 50% to 80% more than the space

    normally required for installing cooling towers of the water-cooled systems.

    This means that these plants do not require a covered plant room either within the

    building or adjacent to the building, thereby saving usable space and the cost of

    constructing such spaces. A small pump room is however required for the air-cooled

    system, which is built near the place where the air-cooled chillers are installed. The size

    of pump room requires approximately 10 to 15% of the size of a regular plant room.

    Thus, the total space required is much less and usually does not represent prime

    usable space.

    [top]

    Case studies

    A few case studies are given to illustrate various applications. These are :1. Videocon Plaza, New Delhi.The largest air-cooled installation in north

    India.(950 tons)

    2. Apartment Building, Laburnum, Gurgaon. A system providing summer

    cooling, winter heating and hot water throughout the year. (120 tons)

    3. Tala Hydel Authorities Gedu, Bhutan. Winter heating only for offices and

    club house building. (6,75,000 Kcal/hr.)

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    16 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    14/16

    Videocon Plaza, New Delhi-(capacity-950 tons)

    This is a 16-story office complex located in New Delhi near Karolbagh. It has a built up

    area of 19,500 m2and is air conditioned by nine, air-cooled chillers each of 106 tons

    capacity at 44C.

    The total plant capacity is 954 tons. All the chillers are installed on the terrace of the

    building. The pumps and electric hot water boilers are also installed on the terrace in a

    room of 50 m2.

    This system has saved 1,20,000 litres of water per day and approximately 200 m2of

    space in the basement. The system requires a staff of only three people to operate.

    Laburnum Apartments (capacity-120 tons) Gurgaon, Haryana

    This building has 17 high end apartments varying in size from 1-bed studio to 5-bed

    room set. It is located as part of a housing complex in Gurgaon, a satellite town of Delhi.

    All apartments are centrally air conditioned . There is provision for equitable

    payment through a Building Automation System, so that each user pays according to the

    quantum of air conditioning that is used. The use of air-cooled heat pumps, with

    provision for hot water, was chosen for the complex, since a simple, reliable,

    maintenance-free system was required.

    Accordingly, two air-cooled units of 60 TR each cooling capacity (total 120 TR) were

    installed. In winter, the total heat output is 500 kW which is three times the

    requirement. The auxiliary condensers provide hot water for toilets and kitchens of all

    apartments. Standby heaters are provided in the hot water calorifiers to heat the water

    during mild season when neither heating or cooling is required.

    The system is controlled by a BAS, so that start-up is instant and operation is

    automatic with minimum operational problems.

    Tala Hydel project - 750 kW heating output, Bhutan

    This installation is located at Gedu, Bhutan at an elevation of 2,700 m above M.S.L.

    Summers are comfortable and winters are long and cold (for nearly 5 to 6 months).

    Hence, only a heating system is required.

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    16 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    15/16

    The requirements called for central heating of an office complex measuring 7,000

    m2and club house and auditorium facility measuring 3,000 m2i.e. a total of 10,000 m2.

    Electricity was the referred medium since these offices were meant for a new 1,000 mW

    hydel project and Bhutan is surplus in electricity.

    The requirement was assessed at 6,75,000 kcal/hr requiring electric hot water

    boilers of 750 kW or 780 kW including pumps, AHUs etc. The use of heat pumps was

    suggested as an alternative, even through the initial cost increase was nearly 50% over aconventional system.

    The advantage of the above system was that it reduced the electric demand from

    780 kW to 280 kW which meant a release of 0.5 mW electricity for better use else

    where.

    The system is operated with five, air-cooled heat pumps each of 150 kW heat output

    totaling 750 kW. All the units together require input electricity of 250 kW. The heat

    pumps will give the design output of 50C at 5C ambient and are equipped with a

    defrost arrangement for the evaporator.

    The system is in its first year of operation and is functioning satisfactorily. This is the

    first installation in this region, where pure heating is being done using heat pumps

    resulting in considerable saving of electricity.

    Conclusion

    It will be seen that the air-cooled chillers represent a fairly efficient and cost effective

    alternative to the watercooled system. These chillers can be used very effectively for

    installations upto 1,000 tons.

    In the milder climate of south India, there is no practical limit to the overall plant

    capacity.

    They are very useful for heating /cooling applications as well as pure heating

    applications.

    [top]

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic

    16 01/07/20

  • 8/13/2019 Air-Cooled Chillers Myths & Facts - Issue Oct-Dec 2003

    16/16

    ooled Chillers : Myths & Facts - Issue Oct-Dec 2003 http://www.ishrae.in/journals/2003oct/artic