Levitor IIAIR COOLED CONDENSER AND FLUID COOLER
Technical Bulletin
Products that provide lasting solutions.
Levitor II Air Cooled Condenser
Table of Contents
LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
Benefits and Features 1
System Selection 2
Levitor Application 3
Model Key 4
LAVE/LEVE Condenser Performance Data, One and Two Fans Wide 5
LAVA/LEVA Condenser Performance Data, One and Two Fans Wide 7
LAVC/LEVC Condenser Performance Data, One and Two Fans Wide 9
LAVF/LEVF Condenser Performance Data, One and Two Fans Wide 11
Dimensional Drawings 13
LAVB Condenser Performance Data, One and Two Fans Wide 14
Dimensional and Electrical Data 15
Control Panel Nomenclature 16
Standard Fan Cycling/Control Arrangements 17
Low Ambient Controls 18
Fan Cycling Sequence 18
Mounted Receivers 19
Mounted Receiver Diagrams 20
Wiring Diagram 22
Replacement Parts 23
12_FIN_KRACK_LEVITOR_COV_2009 8/21/12 4:45 PM Page 3
Levitor II Air Cooled Condenser
LEVITOR II AIR COOLED CONDENSER 1Specifications subject to change without notice.
Benefits and Features
Low Sound Quietor Fann The “swept-wing” blade design offers lower noise levels atthe same fan speed. For example, the QUIETOR fan bladeon a 575-rpm motor will be much quieter (8 dBA) than theold 575-rpm fan.
n Lower noise condensers can translate into savings for yourcustomer by minimizing the need of costly noise barriers.
n Quietor fan not available on 18” models.
Exclusive 3-year Limited Warrantyn We’re so confident about our new suspended coil design that it is protected by a 3-year limited warranty on workmanship and material. It gives you extra protection from premature tube wear. Seewww.krack.ingersollrand.com for complete warranty.
Computerized Circuitingn Our computerized coil circuiting program is designed tominimize the condenser refrigerant charge and maximizesubcooling. Every condenser will be custom circuited toprecisely meet your application needs.
Modular Designn Arranged for vertical or horizontal air discharge. Multi-fan sections compartmented to allow individual fancycling while preventing off-fan “windmilling”. Largeclean-out access doors standard.
Corrosion Resistantn All models employ mill galvanized steel fan sections and coil side baffles. Legs are heavy gauge mill galvanized steel.
High Efficiency Coiln Copper tubes are mechanically expanded intocorrugated full collared aluminum fins spaced 8, 10 or 12 per inch. Coils are helium leak and pressuretested with 400 psig. dry air, shipped pressurized with dry nitrogen.
n Optional fin materials are copper, heresite, electrofin or polyester coated aluminum. Multi-circuited coils areavailable. Liquid subcooling circuits are available.
Direct Driven Propeller Fansn Quiet multi-bladed propeller fans provide uniform airdistribution through the coil. Venturi fan orificesoptimize efficiency.
Weather Resistant Fan Motorsn Outdoor condenser motors designed with ball bearingsinherent overheat protection in each phase; shaftslingers; enclosure, hardware, and lubrication for allweather conditions. Each motor lead is wired toterminals in an electrical enclosure.
Versatile Fan Cycling Control Methods
n Temperature fan cycling.n Pressure fan cycling.n Temperature and pressure fan cycling.n Electronic relay boards.n Variable speed header end fans.n Inverter ready motors.
LEVITOR Coil Design Eliminates Refrigerant Tube Wear
Environmental concerns and spiraling cost of refrigerants have led tothe development of direct drive remote air-cooled condensers with theLEVITOR coil support system. This innovative design uses dedicated
stainless steel tubes and a unique coil support system to isolaterefrigerant tubes from the unit. Coil support is transferred from the finsto the stainless tubes and truncated tube plates which ride freely in “C”channels. Tubes expand and contract without interference. The result,
contact and friction wear are eliminated.
Quiet by Design
LEVITOR coil design does more than just eliminate tube wear. Soundreduction is an added benefit. Unlike traditional air-cooled condensers,
fan and coil vibration are isolated from the cabinet, so it is nottransmitted to the unit frame and building supports.
The LEVITOR system addresses refrigerant coil wear and leaks due to vibration and thermal stress.
Rooftop condensers have to operate in some of thetoughest conditions imaginable. Temperature extremesresult in constant expansion and contraction of refrigeranttubes as fans cycle and loads vary.
The consequences are costly: rapid tube wear results inleaks, system breakdown and loss of costly refrigerant.
US
Levitor II Air Cooled Condenser
System Selection
THR Total Heat of Rejectionn Condenser total heat of rejection (BTU/h) is the sum of the evaporator refrigeration effect and the heat of compression which varies with compressor type and operating conditions.
THR Calculation Methodn THR = Open Reciprocating Compressor Capacity (BTU/h) + (2545 x BHP)
n THR = Suction Gas Cooled Hermetic Reciprocating Compressor Capacity (BTU/h) + (3413 x kW)
THR Estimated Methodn THR may be estimated by multiplying the rated compressor BTU/h capacity by the compressor operating condition factor shown in Table 1 or 2. Multiply result by altitude factor when applicable.
Multi-Circuit Selectionn Condenser coils may be divided into several individual refrigeration circuits or systems; each sized for a specific refrigerant,THR capacity and TD. Systems are tagged for identification from left to right; facing the connection end. Avoid locatinghigh TD sections next to low TD sections. Add excess circuits to low TD sections next to High TD sections. Add excesscircuits to outboard sections. Thermal Fantrol fan cycling is recommended with multi-circuited condensers.
Selectionn LAVA-15310 Rated at THR of 459.1 MBH with R-22 at 15°F TD. LAVA-15310 Unit lists 34 Circuits.
n Sample Calculation: THR Req’d./Circuit = 434984 ÷ 34 = 12784. LAVA-15310 = 459100 ÷ 34 = 13503 (Available THR/Circuit).
n Circuits Req’d. = Select THR ÷ THR/Circuit. Example: 57648 ÷ 13503 = 4.3 Circuits.
n Assign Number of Circuits System and System Number Left to Right. Actual TD = (Circuits Req’d ÷ Assign Circuits) x Design TD.Example: 4.3 ÷ 4 x 15 = 16.1.
EVAPORATORTEMP (˚F)
-40-30-20-100510152025304050
901.661.571.491.421.361.331.311.281.261.241.221.181.14
1001.731.621.531.461.401.371.341.321.291.271.251.211.17
1101.801.681.581.501.441.411.381.351.331.311.281.241.20
1202.001.801.651.571.501.461.431.401.371.351.321.271.23
130***
1.641.561.521.491.461.431.401.371.311.26
140****
1.621.591.551.521.491.451.421.351.29
CONDENSING TEMPERATURE (˚F)HERMETIC COMPRESSOR
TABLE 1
*Beyond the normal limits for single stage compressor application.
FEET1,0002,0003,0004,000
FACTOR1.021.051.071.10
FEET5,0006,0007,0008,000
FACTOR1.121.151.171.24
ALTITUDETABLE 3
EVAPORATORTEMP (˚F)
-30-20-1001020304050
901.371.331.281.241.211.171.141.121.09
1001.421.371.321.281.241.201.171.151.12
1101.471.421.371.321.281.241.201.171.14
120*
1.471.421.371.321.281.241.201.17
130**
1.471.411.361.321.271.231.20
140***
1.471.421.371.321.281.24
CONDENSING TEMPERATURE (˚F)OPEN COMPRESSOR
TABLE 2
SAMPLE CALCuLATIOn: 95°F AMBIEnT-SuCTIOn COOLED SEMI-HERMETIC RECIPROCATInG COMPRESSORS
*Beyond the normal limits for single stage compressor application.
COMPNOMHP
6
9
10
12
REF134a
404A
404A
22
DESIGNTD°F15
10
10
15
SATSUCT°F+20
-20
-20
+20
SATCOND°F110
105
105
110
NETBTU/h40090
45900
50640
104000
MOTORkW4.3
8.1
9.6
9.7
BTU14676
27645
32765
33106
TOTALBTU/h54,766
73,545
83,405
137,106
REFFACTOR0.95
0.98
0.98
1.00
TDFACTOR
1.0
1.5
1.5
1.0
x
x
x
x
=
=
=
=
÷
÷
÷
÷
SELECTTHR57648
112569
127661
137106
434984
CAPPER
CIRCUIT13503
13503
13503
13503
CIRCUITREQ’D4.3
8.3
9.5
10.1
#CIR4
10
10
10
34
SYSTEMNUMBERL TO R
1
2
3
4
ACTUALTD°F
16.1
8.3
9.5
15.1
COMPRESSOR RATING BASED ON R-22 AT 15°FTD
UNIT THR REQ’D
REF FACTORR-22- 1.00
* R-134a- 0.95
**R-404A- 0.98
TD FACTOR10°F-1.50
15°F-1.00
20°F-0.75
25°F-0.60*Usable for R-12**Usable for R-502, R-507
Levitor II Air Cooled Condenser
LEVITOR II AIR COOLED CONDENSER 3Specifications subject to change without notice.
Levitor Application
Locate Condensers no closer than their width from wallsor other condensers. Avoid locations near exhaust fans,plumbing vents, flues or chimneys.
Parallel Condensers should be the same models resultingin the same refrigerant side pressure drops. Compressordischarge lines should have equal pressure drops to eachcondenser.
Condenser Charge will approximate 30% of themaximum flooding charge listed under “Specifications” forsummer design conditions. Low ambient head pressurecontrols require an additional charge, which is difficult topredict with fan cycling and is maximized with holdback.
Receiver Capacity should be sized to store condensersummer charge, plus the condenser low ambientallowance, plus the evaporator charge, plus an allowancefor piping and heat reclaim coil charges.
Compressor Discharge lines should be sized to minimizepressure drops and maintain oil return gas velocities. Eachconnection should be looped to the top of the condenser.
Gravity Liquid Drain Lines should drop from each outlet as low as possible before headering or runninghorizontally. Pitch downhill to receiver.
Off-Line Coil Sections will have refrigerant pressurescorresponding to the ambient. Check valves or isolatingvalves should be installed in the liquid line drains toprevent refrigerant migration and receiver pressure loss.
Liquid Subcooling may be accomplished with a sectionof circuits in the coil. Liquid outlet temperature willapproach the entering air temperature by approximately5°F. Benefit is not economical unless TD is 15°F orhigher.
See Installation & Operating instructions for piping, holdback and fan cycling details.
REFRIGERAnT LInE CAPACITY DATA
n Capacity is compressor suction tons for application between -40°F and +40°F suction at condensingtemperatures between 80°F and 120°F sat.
n For multiple or unloading compressor applications, the vertical discharge riser from the compressor may need to be one size smaller.
n This table data is only to be used as a guide. For exact values, please calculate to your specific job linelengths and design pressure/temp values using ASHRAE handbook or ARI refrigerant tables.
COPPERLINESIZEO.D.
LINE CAPACITY IN TONS
COMPRESSOR DISCHARGE LINE CONDENSER TO RECEIVERLIQUID LINE 100'
LBS. OF REFRIGERANTLIQUID PER 100' OF LENGTH
R-22
1.03.06.515.020.045.075.0
R-404A
0.52.04.57.015.030.045.0
R-134A
0.52.04.57.011.028.043.0
R-22
3.67.412.719.229.047.073.0
R-404A
3.06.010.416.023.040.062.0
R-134A
3.77.713.020.028.546.072.0
R-22
13.025.042.064.090.0160.0245.0
R-404A
11.022.036.055.078.0138.0212.0
R-134A
13.026.043.065.092.0163.0250.0
5/87/81-1/81-3/81-5/82-1/82-5/8
Levitor II Air Cooled Condenser
Model Key
4 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
UNIT TYPE:L = Levitor CondenserF = Fluid Cooler
FIN SPACING:08 = 8 FPI10 = 10 FPI12 = 12 FPI
L A V A 1 2 4 10 M
FAN / MOTOR COMBINATION:A = 1 HP 850 RPM 30"B = 1/2 HP 1140 RPM 24"C = 1-1/2 HP 850 RPM 30"E = 1/2 HP 575 RPM 30"F = 1-1/2 HP 1140 RPM 30"
FANS IN LINE:1234567 = 24" Fan Only
ROWS DEEP:234
FANS WIDE: 1, 2
TUBE DIAMETER:A = 3/8 O.D.E = 1/2 O.D.
FAN DISCHARGE DIRECTIONS:H = HorizontalV = VerticalX = Hinged Vertical*E = Hinged Horizontal*
VOLTAGE:A = 230/1/60**K = 208-230/3/60M = 460/3/60P = 575/3/60U = 380/3/50
NOTE:* Levitor only.
** B units only.
1/2 H.P. 575 RPM - OnE FAn WIDE
NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the entering air temp.to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid. Multiply by 1.14 for R-22.
Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
SHIPWEIGHT(LBS)
43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858
ESTSOUND10’(dBA)
5252525252525252525555555555555555555757575757575757585858585858595959595959606060606060
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
LAVE 112 08LAVE 112 10LAVE 112 12LAVE 113 08LAVE 113 10LAVE 113 12LAVE 114 08LAVE 114 10LAVE 114 12LAVE 122 08LAVE 122 10LAVE 122 12LAVE 123 08LAVE 123 10LAVE 123 12LAVE 124 08LAVE 124 10LAVE 124 12LAVE 132 10LAVE 132 12LAVE 133 08LAVE 133 10LAVE 133 12LAVE 134 08LAVE 134 10LAVE 134 12LAVE 143 08LAVE 143 10LAVE 143 12LAVE 144 08LAVE 144 10LAVE 144 12LAVE 153 08LAVE 153 10LAVE 153 12LAVE 154 08LAVE 154 10LAVE 154 12LEVE 163 08LEVE 163 10LEVE 163 12LEVE 164 08LEVE 164 10LEVE 164 12
10°F33.237.240.443.847.950.653.155.958.166.574.480.987.595.8101.2106.3111.7116.3111.5121.3138.1143.6152.0159.6167.6174.7174.8191.5202.4212.5223.4233.1231.9254.0270.3270.9289.8300.3278.4304.9324.5325.1347.8360.4
15°F49.855.860.665.771.875.979.683.887.199.7111.6121.3131.2143.7151.8159.4167.5174.4167.2181.9207.1215.4228.0239.4251.4262.0262.2287.2303.6318.7335.1349.6347.8381.0405.4406.3434.7450.4417.6457.3486.7487.6521.7540.6
20°F66.474.480.887.695.8101.2106.2111.8116.2133.0148.8161.8175.0191.6202.4212.6223.4232.6223.0242.6276.2287.2304.0319.2335.2349.4349.6383.0404.8425.0446.8466.2463.8508.0540.6541.8579.6600.6556.8609.8649.0650.2695.6720.8
25°F83.093.0101.0109.5119.7126.5132.7139.7145.2166.2186.0202.2218.7239.5253.0265.7279.2290.7278.7303.5345.2359.0380.0399.0419.0436.7437.0478.7506.0531.2558.5582.7579.7635.0675.7677.2724.5750.7696.0762.2811.2812.7869.5901.0
10°F32.336.239.342.646.647.251.754.456.664.772.378.785.193.298.4103.4108.7113.2108.5118.0134.3139.8147.9155.3163.0170.0170.0186.3197.0206.8217.4226.8225.6247.1263.0263.6282.0292.2270.8296.6315.7316.3338.4350.6
15°F48.454.358.963.969.970.877.581.684.997.0108.4118.0127.6139.8147.6155.1163.0169.8162.7177.0201.4209.7221.8232.9244.5255.0255.0279.4295.5310.2326.1340.2338.4370.6394.5395.4423.0438.3406.2444.9473.5474.4507.6525.9
20°F64.672.478.685.293.294.4103.4108.8113.2129.4144.6157.4170.2186.4196.8206.8217.4226.4217.0236.0268.6279.6295.8310.6326.0340.0340.0372.6394.0413.6434.8453.6451.2494.2526.0527.2564.0584.4541.6593.2631.4632.6676.8701.2
25°F80.790.5 98.2106.5116.5118.0129.2136.0141.5161.7180.7196.7212.7233.0246.0258.5271.7283.0271.2295.0335.7349.5369.7388.2407.5425.0425.0465.7492.5517.0543.5567.0564.0617.7657.5659.0705.0730.5677.0741.5789.2790.7846.0876.5
AIRFLOW(CFM)
6480642063606300620061006105597558351296012840127201260012400122001226011950116701926019080189001860018300183151792517505252002480024400244202390023340315003100030500305252887529175378003720036600366303585035010
AVAILCIRCUITS
3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434
CONDENSERCHARGE R-404A
(LBS)
SUMMER
5557778889991212121515151414181818232323232323292929272727353535585858757575
WINTER
1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310
Levitor II Air Cooled Condenser
LAVE/LEVE Performance Data
Levitor II Air Cooled Condenser
LAVE/LEVE Performance Data
1/2 H.P. 575 RPM - TWO FAnS WIDE
ELECTRICAL DATA - OnE FAn WIDE
SHIPWEIGHT(LBS)
1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
LAVE 222 08LAVE 222 10LAVE 222 12LAVE 223 08LAVE 223 10LAVE 223 12LAVE 224 08LAVE 224 10LAVE 224 12LAVE 232 10LAVE 232 12LAVE 233 08LAVE 233 10LAVE 233 12LAVE 234 08LAVE 234 10LAVE 234 12LAVE 243 08LAVE 243 10LAVE 243 12LAVE 244 08LAVE 244 10LAVE 244 12LAVE 253 08LAVE 253 10LAVE 253 12LAVE 254 08LAVE 254 10LAVE 254 12LEVE 263 08LEVE 263 10LEVE 263 12LEVE 264 08LEVE 264 10LEVE 264 12
10°F133.0148.8161.8175.0191.6202.4212.6223.4232.6223.0242.6276.2287.2304.0319.2335.2349.4349.6383.0404.8425.0446.8466.2463.8508.0540.6541.8579.6600.6556.8609.8649.0650.2695.6720.8
15°F199.5223.2242.7262.5287.4303.6318.9335.1348.9334.5363.9414.3430.8456.0478.8502.8524.1524.4574.5607.2637.5670.2699.3695.7762.0810.9812.7869.4900.9835.2914.7973.5975.31043.41081.2
20°F266.0297.6323.6350.0383.2404.8425.2446.8465.2446.0485.2552.4574.4608.0638.4670.4698.8699.2766.0809.6850.0893.6932.4927.61016.01081.21083.61159.21201.21113.61219.61298.01300.41391.21441.6
25°F332.5372.0404.5437.5479.0506.0531.5558.5581.5557.5606.5690.5718.0760.0798.0838.0873.5874.0957.51012.01062.51117.01165.51159.51270.01351.51354.51449.01501.51392.01524.51622.51625.51739.01802.0
10°F129.4144.6157.4170.2186.4196.8206.8217.4226.4217.0236.0268.6279.6295.8310.6326.0340.0340.0372.6394.0413.6434.8453.6451.2494.2526.0527.2564.0584.4541.6593.2631.4632.6676.8701.2
15°F194.1216.9236.1255.3279.6295.2310.2326.1339.6325.5354.0402.9419.4443.7465.9489.0510.0510.0558.9591.0620.4652.2680.4676.8741.3789.0790.8846.0876.6812.4889.8947.1948.91015.21051.8
20°F258.8289.2314.8340.4372.8393.6413.6434.8452.8434.0472.0537.2559.2591.6621.2652.0680.0680.0745.2788.0827.2869.6907.2902.4988.41052.01054.41128.01168.81083.21186.41262.81265.21353.61402.4
25°F323.5361.5393.5425.5466.0492.0517.0543.5566.0542.5590.0671.5699.0739.5776.5815.0850.0850.0931.5985.01034.01087.01134.01128.01235.51315.01318.01410.01461.01354.01483.01578.51581.51692.01753.0
AIRFLOW(CFM)
2592025680254402520024800244002442023900233403852038160378003720036600366303595035010504004960048800488404780046680630006200061000610505975058350756007440073200732607170070020
AVAILCIRCUITS
6868686868686868686868686868686868686868686868686868686868686868686868
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
3.46.810.213.617.020.4
460/3/60
1.73.45.16.88.5
10.2
575/3/60
1.22.43.64.86.07.2
LAVE-11***LAVE-12***LAVE-13***LAVE-14***LAVE-15***LEVE-16***
ELECTRICAL DATA - TWO FAnS WIDE
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
13.620.427.234.040.8
460/3/60
6.810.213.617.020.4
575/3/60
4.87.29.612.014.4
LAVE-22***LAVE-23***LAVE-24***LAVE-25***LEVE-26***
NOTE: Ratings are based on85°F-115°F entering air
temperature. The temperaturedifference is between the
saturated condensing temp. andthe entering air temp. to the
condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer
charge based on 25% ofcondenser volume with 86°F
liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.
CONDENSERCHARGE R-404A
(LBS)
SUMMER
1818182424243030302727373737464646464646585858555555707070116116116150150150
WINTER
6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620
ESTSOUND10’(dBA)
5858585858585858586060606060606060616161616161626262626262636363636363
LEVITOR II AIR COOLED CONDENSER 7Specifications subject to change without notice.
1 H.P. 850 RPM - OnE FAn WIDE
SHIPWEIGHT(LBS)
43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
CONDENSERCHARGE R-404A
(LBS)
LAVA 112 08LAVA 112 10LAVA 112 12LAVA 113 08LAVA 113 10LAVA 113 12LAVA 114 08LAVA 114 10LAVA 114 12LAVA 122 08LAVA 122 10LAVA 122 12LAVA 123 08LAVA 123 10LAVA 123 12LAVA 124 08LAVA 124 10LAVA 124 12LAVA 132 10LAVA 132 12LAVA 133 08LAVA 133 10LAVA 133 12LAVA 134 08LAVA 134 10LAVA 134 12LAVA 143 08LAVA 143 10LAVA 143 12LAVA 144 08LAVA 144 10LAVA 144 12LAVA 153 08LAVA 153 10LAVA 153 12LAVA 154 08LAVA 154 10LAVA 154 12LEVA 163 08LEVA 163 10LEVA 163 12LEVA 164 08LEVA 164 10LEVA 164 12
10°F42.447.551.756.061.265.365.369.772.385.095.1103.4111.8122.4130.3130.5139.4144.6142.6155.1176.6183.6195.4195.8209.1217.0223.6244.9260.6261.1278.8289.2279.5306.1325.7326.4348.5361.5335.3367.3390.9391.6418.2433.8
15°F63.771.377.683.891.897.797.9104.8108.5127.3142.6155.1183.7183.6195.4195.8209.1216.9213.9232.7251.5275.5293.1293.7313.7325.4335.3367.3390.3391.6418.2433.8419.2459.1488.6489.6522.8542.5509.2550.9586.3587.4627.3650.7
20°F84.995.1103.4111.8122.4130.3130.5139.4144.6169.8190.2206.8223.6244.9260.6261.1278.8289.2285.3310.3335.3367.3390.9391.6418.2433.8447.1489.7521.1522.2557.7578.4588.9612.2651.4652.7697.1723.0670.7734.6781.7783.3836.5867.6
25°F106.1118.9129.3139.7153.0162.9163.2174.3180.8212.2237.7258.6279.5306.1325.7326.4348.5361.5356.6387.8419.2459.1488.6489.6522.8542.3588.9612.2651.4652.7697.1723.0698.6765.2814.3815.9871.3903.8838.4918.2977.1979.1
1045.61084.5
10°F41.648.650.754.960.064.064.068.370.983.393.2101.3109.6120.0127.7127.9136.6141.7139.7152.0173.1179.9191.5191.9204.9212.7219.1240.0255.4255.9273.2283.4273.0300.0319.2319.9341.5354.3328.6360.0383.1383.8409.8425.1
15°F62.469.976.082.190.095.795.9102.7106.3124.8139.7152.0180.0179.9191.5191.9204.9212.6209.6228.0246.5270.0287.2287.8307.4318.9328.6360.0382.5383.8409.8425.1410.8449.9478.8479.8512.3531.5492.9539.9574.6575.8614.9637.7
20°F83.293.2101.3109.6120.0127.7127.9136.6141.7166.4186.4202.7219.1240.0255.4255.9273.2283.4279.6304.1328.6360.0383.1383.8409.8425.1438.2479.9510.7511.8546.5566.8547.7600.0638.4639.6683.2708.5657.3719.9766.1767.6819.8850.2
25°F104.0116.5126.7136.9149.9159.6159.9170.8177.2208.0232.9253.4273.9300.0319.2319.9341.5354.3349.5380.0410.8449.9478.8479.8512.3531.5547.7600.0638.4639.6683.2708.5684.6749.9798.0799.6853.9885.7821.6899.8957.6959.51024.71062.8
SUMMER
5557778889991212121515151414181818232323232323292929272727353535585858757575
WINTER
1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310
AIRFLOW(CFM)
9260915190408933876085748582831480251852018302180801786617520171481716416628160502745327120267992628025722257462494224075357323504034296343283325632100446654380042870429104157040125535985256051444514924988448150
AVAILCIRCUITS
3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434
ESTSOUND10’(dBA)
6363636363636363636666666666666666666868686868686868696969696969707070707070717171717171
Levitor II Air Cooled Condenser
LAVA/LEVA Performance Data
NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and theentering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
Levitor II Air Cooled Condenser
LAVA/LEVA Performance Data
1 H.P. 850 RPM - TWO FAnS WIDE
ELECTRICAL DATA - OnE FAn WIDE
SHIPWEIGHT(LBS)
1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
LAVA 222 08LAVA 222 10LAVA 222 12LAVA 223 08LAVA 223 10LAVA 223 12LAVA 224 08LAVA 224 10LAVA 224 12LAVA 232 10LAVA 232 12LAVA 233 08LAVA 233 10LAVA 233 12LAVA 234 08LAVA 234 10LAVA 234 12LAVA 243 08LAVA 243 10LAVA 243 12LAVA 244 08LAVA 244 10LAVA 244 12LAVA 253 08LAVA 253 10LAVA 253 12LAVA 254 08LAVA 254 10LAVA 254 12LEVA 263 08LEVA 263 10LEVA 263 12LEVA 264 08LEVA 264 10LEVA 264 12
10°F169.8190.2206.8223.6244.9260.6261.1278.8289.2285.3310.3335.3367.3390.9391.6418.2433.8447.1489.7521.1522.2557.6578.4558.9612.2651.4652.7697.1723.0670.7734.6781.6783.3836.5867.6
15°F254.7285.3310.3335.3367.3390.9391.6418.2433.8427.9465.4503.0550.9586.3587.5627.4650.7670.7734.6781.7783.3836.5867.6838.4918.2977.1979.11045.61084.51006.01101.91172.61174.91254.71301.5
20°F339.6380.3413.7447.1489.7521.1522.2557.7578.4570.5620.5670.7734.6781.7783.3836.5867.6894.3979.41042.31044.41115.31156.81117.81224.31302.81305.51394.11446.11341.41469.21563.41566.61673.01735.3
25°F424.5475.4517.1558.9612.2651.4652.7697.1723.0713.1775.7838.4918.2977.1979.11045.61084.51117.81224.31302.81305.51394.11446.11397.31530.41628.61631.91742.71807.61676.71836.51954.31958.22091.22169.1
10°F166.4186.4202.7219.1240.0255.4255.9273.2283.4279.6304.1328.6360.0383.1383.8409.8425.1438.2479.9510.7511.8546.4566.8547.7600.0638.4639.6683.2708.5657.3719.9766.0767.6819.8850.2
15°F249.6279.6304.1328.6360.0383.1383.8409.8425.1419.3456.1492.9539.9574.6575.8614.9637.7657.3719.9766.1767.6819.8850.2821.6899.8957.6959.51024.71062.8985.91079.91149.11151.41229.61275.5
20°F322.8372.7405.4438.2479.9510.7511.8546.5566.8559.1608.1657.3719.9766.1767.6819.8850.2876.4959.81021.51023.51093.01133.71095.41199.81276.71279.41366.21417.21314.61439.81532.11535.31639.51700.6
25°F416.0465.9506.8547.7600.0638.4639.6683.2708.5698.8760.2821.6899.8957.6959.51024.71062.81095.41199.81276.71279.41366.21417.21369.41499.81596.01599.31707.81771.41643.21799.81915.21919.02049.42125.7
AIRFLOW(CFM)
37040366043616035732350403429634328332563210054906542405359852560514445149249884481507146470080685926865666512642008930087600857408582083140802501071961051201028881029849976896300
AVAILCIRCUITS
6868686868686868686868686868686868686868686868686868686868686868686868
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
4.48.813.217.622.026.4
460/3/60
2.04.06.08.010.012.0
575/3/60
1.452.94.355.87.258.7
LAVA-11***LAVA-12***LAVA-13***LAVA-14***LAVA-15***LEVA-16***
ELECTRICAL DATA - TWO FAnS WIDE
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
17.626.435.244.052.8
460/3/60
8.012.016.020.024.0
575/3/60
5.88.711.614.517.4
LAVA-22***LAVA-23***LAVA-24***LAVA-25***LEVA-26***
CONDENSERCHARGE R-404A
(LBS)
SUMMER
1818182424243030302727373737464646464646585858555555707070116116116150150150
WINTER
6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620
NOTE: Ratings are based on85°F-115°F entering air
temperature. The temperaturedifference is between the
saturated condensing temp. andthe entering air temp. to the
condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer
charge based on 25% ofcondenser volume with 86°F
liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.
ESTSOUND10’(dBA)
6969696969696969697171717171717171727272727272737373737373747474747474
LEVITOR II AIR COOLED CONDENSER 9Specifications subject to change without notice.
1-1/2 H.P. 850 RPM - OnE FAn WIDE
SHIPWEIGHT(LBS)
43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
CONDENSERCHARGE R-404A
(LBS)
LAVC 112 08LAVC 112 10LAVC 112 12LAVC 113 08LAVC 113 10LAVC 113 12LAVC 114 08LAVC 114 10LAVC 114 12LAVC 122 08LAVC 122 10LAVC 122 12LAVC 123 08LAVC 123 10LAVC 123 12LAVC 124 08LAVC 124 10LAVC 124 12LAVC 132 10LAVC 132 12LAVC 133 08LAVC 133 10LAVC 133 12LAVC 134 08LAVC 134 10LAVC 134 12LAVC 143 08LAVC 143 10LAVC 143 12LAVC 144 08LAVC 144 10LAVC 144 12LAVC 153 08LAVC 153 10LAVC 153 12LAVC 154 08LAVC 154 10LAVC 154 12LEVC 163 08LEVC 163 10LEVC 163 12LEVC 164 08LEVC 164 10LEVC 164 12
10°F46.251.555.660.165.369.169.473.776.392.3102.9111.3120.3130.7138.2138.8147.3152.5154.3166.9180.4196.0207.3208.1221.0238.7240.5261.3276.3277.5294.6305.0300.6326.7345.5346.9368.3381.3360.7392.1414.5416.3441.9457.5
15°F69.377.283.490.298.0103.6104.1110.5114.4138.5154.3166.9180.4196.0207.3208.2221.0228.8231.5250.3270.6294.0310.9312.2331.5343.1360.8392.0414.5416.3441.9457.5430.9490.1518.2520.4552.4571.9541.1588.1621.8624.5662.9686.3
20°F92.4102.9111.3120.3130.7138.2138.8147.3152.5184.7205.7222.5240.5261.4276.4277.6294.6305.0308.6333.8360.8392.0414.5416.2441.9457.5481.0522.7552.7555.1589.2610.0601.3653.4690.9693.9736.6762.5721.5784.1829.1832.7883.9915.0
25°F115.4128.6139.1150.3163.4172.7173.5184.1190.6230.9257.2278.1300.6326.7345.5346.9368.3381.3385.8417.2450.9490.1518.2520.4552.4571.9601.3653.4690.9693.9736.6762.5751.6816.8863.6867.4920.7953.2901.9980.1
1036.41040.81104.81143.8
10°F45.350.454.558.964.067.768.072.274.790.5100.8108.0117.9128.1135.4136.0144.4149.5151.2163.5176.8192.1203.1204.0216.6224.2235.7256.1270.8272.0288.7298.9294.6320.2338.6340.0360.9373.6353.5384.2406.2408.0433.1448.4
15°F67.975.781.788.496.0101.5102.0103.8112.3135.7151.2163.6176.8192.1203.2204.0216.6224.2226.9245.3265.2288.1304.7306.0324.9336.2353.6384.2406.2408.0433.1448.4441.9480.3507.8510.0541.4560.5530.3576.3609.4612.0649.6672.6
20°F90.6
100.8109.1117.9128.1135.4136.0144.4149.5181.0201.6218.1235.7256.2270.9272.0288.7298.9302.4327.1353.6384.2406.2408.0433.1448.4471.4512.2541.6544.0577.4597.8589.3640.3677.1680.0721.9747.3707.1768.4812.5816.0866.2896.7
25°F113.1126.0136.3147.3160.1169.2170.0180.4186.8226.3252.1272.5294.6320.2338.6340.0360.9373.7378.1408.9441.9480.3507.8510.0541.4560.5589.3640.3677.1680.0721.9747.3736.6800.5846.3850.1902.3934.1883.9960.51015.71020.01082.71120.9
SUMMER
5557778889991212121515151414181818232323232323292929272727353535585858757575
WINTER
1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310
AIRFLOW(CFM)
10967106821040910159978594419449903186602193421364208182031819570188821889818062173203204631227304772935528323283472709325980406363914037764377963612434640259982824729861300053185032974609545771056646566945418651960
AVAILCIRCUITS
3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434
ESTSOUND10’(dBA)
6565656565656565656868686868686868687070707070707070717171717171727272727272737373737373
Levitor II Air Cooled Condenser
LAVC/LEVC Performance Data
NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and theentering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
Levitor II Air Cooled Condenser
LAVC/LEVC Performance Data
1-1/2 H.P. 850 RPM - TWO FAnS WIDE
ELECTRICAL DATA - OnE FAn WIDE
SHIPWEIGHT(LBS)
1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
LAVC 222 08LAVC 222 10LAVC 222 12LAVC 223 08LAVC 223 10LAVC 223 12LAVC 224 08LAVC 224 10LAVC 224 12LAVC 232 10LAVC 232 12LAVC 233 08LAVC 233 10LAVC 233 12LAVC 234 08LAVC 234 10LAVC 234 12LAVC 243 08LAVC 243 10LAVC 243 12LAVC 244 08LAVC 244 10LAVC 244 12LAVC 253 08LAVC 253 10LAVC 253 12LAVC 254 08LAVC 254 10LAVC 254 12LEVC 263 08LEVC 263 10LEVC 263 12LEVC 264 08LEVC 264 10LEVC 264 12
10°F184.7205.7222.5240.5261.3276.3277.5294.6305.0308.6333.7360.7392.1414.5416.3441.9457.5481.0522.7552.7555.1589.3610.0601.3653.4690.9693.9736.5762.5721.5784.1829.1832.7883.9915.0
15°F277.1308.6333.8360.8392.0414.5416.3441.9457.5462.9500.6541.1588.1621.8624.5662.9686.3721.6784.1829.1832.7883.9915.0901.9980.11036.41040.81104.81143.81082.31176.11243.61249.01325.81372.5
20°F369.4411.5445.0481.0522.7552.7555.1589.2610.0617.2667.5721.5784.1829.1832.7883.9915.0962.01045.41105.51110.21178.51220.01202.51306.81381.81387.81473.11525.01443.01568.21658.21665.31767.71830.0
25°F461.8514.4556.3601.3653.4690.9693.9736.6762.5771.5834.4901.9980.11036.41040.81104.81143.81202.61306.81381.81387.81473.11525.01503.21633.51727.31734.71841.41906.31803.81960.22072.72081.62209.72287.6
10°F181.0201.6218.1235.7256.1270.8272.0288.7298.9302.4327.1353.5384.2406.2408.0433.1448.4471.4512.3541.7544.0577.5597.8589.2640.3677.1680.8721.8747.3707.0768.4812.5816.0866.2896.7
15°F271.6302.4327.1353.6384.2406.2408.0433.1448.4453.6490.6530.3576.3609.4612.0649.6672.6707.2768.4812.5816.0866.2896.7883.9960.51015.71020.01082.71120.91060.71152.61218.71224.01299.31345.1
20°F362.0403.3436.1471.4512.2541.6544.0577.4597.8604.9654.2707.1768.4812.5816.0866.2896.7942.81024.51083.41088.01154.91195.61178.51280.71354.21360.01443.61494.51414.11536.81625.01632.01732.31793.4
25°F452.6504.1545.2589.3640.3677.1680.0721.9747.3756.1817.7883.9960.51015.71020.01082.71120.91178.61280.71354.21360.01443.61494.51473.11600.81692.81700.01804.61868.21767.71921.02031.22040.02165.52241.8
AIRFLOW(CFM)
43868427284163640636391403776437796361243464064092624546095458710566465669454186519608127278280755287559272248692801015909785094410944909031086600121908117420113292113388108372103920
AVAILCIRCUITS
6868686868686868686868686868686868686868686868686868686868686868686868
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
6.012.018.024.030.036.0
460/3/60
3.06.09.012.015.018.0
575/3/60
2.55.07.510.012.515.0
LAVC-11***LAVC-12***LAVC-13***LAVC-14***LAVC-15***LEVC-16***
ELECTRICAL DATA - TWO FAnS WIDE
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
24.036.048.060.072.0
460/3/60
12.018.024.030.036.0
575/3/60
10.015.020.025.030.0
LAVC-22***LAVC-23***LAVC-24***LAVC-25***LEVC-26***
CONDENSERCHARGE R-404A
(LBS)
SUMMER
1818182424243030302727373737464646464646585858555555707070116116116150150150
WINTER
6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620
NOTE: Ratings are based on85°F-115°F entering air
temperature. The temperaturedifference is between the
saturated condensing temp. andthe entering air temp. to the
condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer
charge based on 25% ofcondenser volume with 86°F
liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.
ESTSOUND10’(dBA)
7171717171717171717373737373737373747474747474757575757575767676767676
LEVITOR II AIR COOLED CONDENSER 11Specifications subject to change without notice.
1-1/2 H.P. 1140 RPM - OnE FAn WIDE
SHIPWEIGHT(LBS)
43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
CONDENSERCHARGE R-404A
(LBS)
LAVF 112 08LAVF 112 10LAVF 112 12LAVF 113 08LAVF 113 10LAVF 113 12LAVF 114 08LAVF 114 10LAVF 114 12LAVF 122 08LAVF 122 10LAVF 122 12LAVF 123 08LAVF 123 10LAVF 123 12LAVF 124 08LAVF 124 10LAVF 124 12LAVF 132 10LAVF 132 12LAVF 133 08LAVF 133 10LAVF 133 12LAVF 134 08LAVF 134 10LAVF 134 12LAVF 143 08LAVF 143 10LAVF 143 12LAVF 144 08LAVF 144 10LAVF 144 12LAVF 153 08LAVF 153 10LAVF 153 12LAVF 154 08LAVF 154 10LAVF 154 12LEVF 163 08LEVF 163 10LEVF 163 12LEVF 164 08LEVF 164 10LEVF 164 12
10°F47.553.458.363.870.375.576.082.386.795.1106.8116.5127.6140.7150.9152.1164.5173.3160.3174.8191.4211.1226.3228.1246.7259.9255.3281.4301.7304.1329.0346.5319.1351.8377.2380.1411.3433.2382.9422.1452.6456.2493.5519.8
15°F71.380.187.495.7105.5113.2114.0123.4130.0142.6160.2174.8191.4211.1226.3228.1246.7259.9240.4262.2287.1316.6339.5342.1370.1389.9382.9422.1452.6456.2493.5519.8478.6527.7565.8570.2616.9649.8574.3633.2678.9684.3740.2779.7
20°F95.1106.8116.5127.6140.7150.9152.1164.5173.3190.2213.7233.1255.2281.4301.8304.1329.0346.5320.5349.6382.9422.1452.6456.2493.5519.8510.5565.8603.5608.3658.0693.1638.1703.6754.4760.3822.5866.4765.7844.3905.3912.4987.0
1039.6
25°F118.9135.5145.7159.5175.9188.8190.1205.6216.6237.7267.1291.3319.1351.8377.2380.2411.2433.2400.6437.0478.6527.7565.8570.2616.9649.8638.1703.6754.4760.3822.5866.4797.6879.5943.0950.4
1028.11083.0957.2
1055.31131.61140.51233.71299.5
10°F46.652.357.162.568.974.074.580.684.993.2104.7114.2125.0137.9147.8149.0161.2169.8157.1171.3187.6206.8221.8223.5241.8254.7250.2275.8295.7298.1322.4339.6312.7344.8369.7372.5403.0424.5375.2413.7433.5447.1483.6509.4
15°F69.978.585.793.8103.4110.9111.7120.9127.4139.7157.0171.3187.6206.9221.8223.5241.8254.7235.6257.0281.4310.3332.7335.3362.7382.1375.2413.7443.5447.1483.6509.4469.0517.1554.5558.8604.6636.8562.8620.5665.3670.6725.4764.1
20°F93.2104.7114.2125.0137.9147.9149.1161.2169.8186.4209.4228.4250.1275.8295.8298.0322.4339.6314.1342.6375.2413.7443.5447.1483.6509.4500.3551.5591.4596.1644.8679.2625.3689.5739.3745.1806.1849.1750.4827.4887.2894.2967.31018.8
25°F116.5130.8142.8156.3172.4184.8186.3201.5212.3232.9261.8285.5312.7344.8369.7372.6403.0424.5392.6428.3469.0517.1554.5558.8604.6636.8625.3689.5739.3745.1806.1849.1781.6861.9924.1931.41007.51061.3938.11034.21109.01117.71209.01273.5
SUMMER
5557778889991212121515151414181818232323232323292929272727353535585858757575
WINTER
1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310
AIRFLOW(CFM)
1164911541114301132311147109691097410730104862329823082228602264622294219382194821460209723462334290339693344132907329223219031458452924458843876438964292041944566155573554845548705365052430679386688265814658446438062916
AVAILCIRCUITS
3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434
ESTSOUND10’(dBA)
7272727272727272727575757575757575757777777777777777787878787878797979797979808080808080
Levitor II Air Cooled Condenser
LAVF/LEVF Performance Data
NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and theentering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.
Levitor II Air Cooled Condenser
LAVF/LEVF Performance Data
1-1/2 H.P. 1140 RPM - TWO FAnS WIDE
ELECTRICAL DATA - OnE FAn WIDE
SHIPWEIGHT(LBS)
1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366
MODEL
TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507
TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE
LAVF 222 08LAVF 222 10LAVF 222 12LAVF 223 08LAVF 223 10LAVF 223 12LAVF 224 08LAVF 224 10LAVF 224 12LAVF 232 10LAVF 232 12LAVF 233 08LAVF 233 10LAVF 233 12LAVF 234 08LAVF 234 10LAVF 234 12LAVF 243 08LAVF 243 10LAVF 243 12LAVF 244 08LAVF 244 10LAVF 244 12LAVF 253 08LAVF 253 10LAVF 253 12LAVF 254 08LAVF 254 10LAVF 254 12LEVF 263 08LEVF 263 10LEVF 263 12LEVF 264 08LEVF 264 10LEVF 264 12
10°F190.2213.7233.1255.3281.4301.7304.1329.0346.5320.5349.6382.9442.1452.6456.2493.5519.8510.5562.9603.5608.3658.0693.1638.1703.5754.4760.3822.5866.3765.7884.3905.3912.4986.9
1039.6
15°F285.3320.5349.6382.9422.1452.6456.2493.5519.8480.7524.4574.3633.2678.9684.3740.2779.7765.7844.3905.3912.4987.01039.6957.21055.31131.61140.51233.71299.51148.61266.41357.91368.61480.41559.4
20°F380.3427.3466.1510.5562.8603.5608.3658.0693.1641.0699.2765.7844.3905.3912.4987.01039.61021.01125.71207.01216.51316.01386.21276.21407.11508.81520.61644.91732.71531.51688.51810.51824.81973.92079.3
25°F475.4534.2582.7638.1703.6754.4760.3822.5866.4801.2874.0957.21055.31131.61140.51233.71299.51276.21407.11508.81520.61644.91732.71595.31758.91886.01900.82056.22165.91914.32110.72263.12281.02467.42599.1
10°F186.4209.4228.4250.2275.8295.7298.1322.4339.6314.1342.6375.2413.7443.5447.1483.6509.4500.3551.6591.5596.1644.8679.2625.4689.5739.3745.1806.0849.0750.4827.4887.2894.2967.21018.9
15°F279.6314.1342.6375.2413.7443.5447.1483.6509.4471.1513.9562.8620.5665.3670.6725.4764.1750.4827.4887.2894.2967.31018.8938.11034.21109.01117.71209.01273.51125.61241.11330.71341.21450.81528.2
20°F372.7418.8456.8500.3551.5591.4596.1644.8679.2628.2685.2750.4827.4887.2894.2967.31018.81000.61103.21182.91192.21289.71358.51250.71379.01478.61490.21612.01698.01500.91654.71774.31788.31934.42037.7
25°F465.9523.5571.0625.3689.5739.3745.1806.1849.1785.2856.5938.11034.21109.01117.71209.01273.51250.71379.01478.61490.21612.01698.01563.41723.71848.31862.82015.12122.61876.02068.52217.82235.42418.12547.1
AIRFLOW(CFM)
465564582445096444124336442344423764105639808687366764466618650466351663564615845971288824867288468884752821127961611103010841010586010594010264099520133236130092127032127128123168119424
AVAILCIRCUITS
6868686868686868686868686868686868686868686868686868686868686868686868
***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
7.014.021.028.035.042.0
460/3/60
3.57.010.514.017.521.0
575/3/60
2.44.87.29.612.014.4
LAVF-11***LAVF-12***LAVF-13***LAVF-14***LAVF-15***LEVF-16***
ELECTRICAL DATA - TWO FAnS WIDE
FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60
28.042.056.070.084.0
460/3/60
14.021.028.035.042.0
575/3/60
9.614.419.224.028.8
LAVF-22***LAVF-23***LAVF-24***LAVF-25***LEVF-26***
CONDENSERCHARGE R-404A
(LBS)
SUMMER
1818182424243030302727373737464646464646585858555555707070116116116150150150
WINTER
6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620
NOTE: Ratings are based on85°F-115°F entering air
temperature. The temperaturedifference is between the
saturated condensing temp. andthe entering air temp. to the
condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer
charge based on 25% ofcondenser volume with 86°F
liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.
ESTSOUND10’(dBA)
7878787878787878788080808080808080818181818181828282828282838383838383
AL
ELECTRICAL BOX ELECTRICAL BOX
LB C
W
BL
AIR
H
AL
A
AL
B A
AIR
H
WC
A A AL
ELECTRICAL BOX ELECTRICAL BOX
ELECTRICAL BOX
ELECTRICAL BOX
B B
(2)
OnE FAn WIDE
CONNECTIONSOD IN(1)
W
58112166220274328
H
54545454
58-1/258-1/2
A
-108108108108108
B
54-54-54-
W
45-1/445-1/445-1/445-1/445-1/445-1/4
C
41-1/441-1/441-1/441-1/441-1/441-1/4
INLET
1-3/81-5/82-1/82-1/82-1/82-5/8
OUTLET
1-3/81-5/82-1/82-1/82-1/82-5/8
LAV*-11***LAV*-12***LAV*-13***LAV*-14***LAV*-15***LEV*-16***
TWO FAn WIDE
CONNECTIONSOD IN(1)
W
112166220274328
H
545454
58-1/258-1/2
A
108108108108108
B
-54-54-
W
90-1/290-1/290-1/290-1/290-1/2
C
86-1/286-1/286-1/286-1/286-1/2
INLET
(2)1-5/8(2)2-1/8(2)2-1/8(2)2-1/8(2)2-5/8
OUTLET
(2)1-5/8(2)2-1/8(2)2-1/8(2)2-1/8(2)2-5/8
LAV*-22***LAV*-23***LAV*-24***LAV*-25***LEV*-26***
Levitor II Air Cooled Condenser
LEVITOR II AIR COOLED CONDENSER 13Specifications subject to change without notice.
Dimensional Drawings
*Indicates fan/motor combination. Includes standard 22" legs.(1) Connections are approximate. Exact size is determined by computerized circuiting program.
(2) 1 X 3 has six legs; 2 x 3 has eight legs.2 columns of "W" need to
change one to L and W
Levitor II Air Cooled Condenser
LAVB Performance Data
14 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
1/2 H.P. 1140 RPM
ONE FANMODEL
TWO FANMODEL
RATING BASED ON 85°-115°F ENTERING AIR TEMPERATURE TD IS SATURATED CONDENSING TEMP. MINUS ENTERING AIR TEMP.
TOTAL HEAT OF REJECTION CAPACITY (MBH)
R-22 TD R-404A, R-507A TD
LAVB 112 10LAVB 113 10LAVB 114 10LAVB 122 10LAVB 123 10LAVB 124 10LAVB 133 10LAVB 134 10LAVB 143 10LAVB 144 10LAVB 153 10LAVB 154 10LAVB 163 10LAVB 164 10LAVB 173 10LAVB 174 10
15°F30.239.445.460.578.990.9118.3136.3157.8181.7197.2227.1236.7272.6276.1318.0
20°F45.459.168.290.7118.3136.3177.8204.5236.7272.6295.9340.7355.0408.8414.2477.0
25°F60.578.990.9121.0157.8181.7236.7272.6315.6363.4394.5454.3473.3545.1552.2636.0
10°F29.438.444.258.976.788.4115.1132.6153.5176.8191.9221.0230.2265.2268.6309.4
15°F44.257.666.483.3115.1132.6172.7199.0230.2265.2287.8331.5345.5397.8403.0464.1
20°F58.976.788.4117.8153.5176.8230.2265.2307.1353.6383.3441.9460.5530.4537.3618.8
AIRFLOWCFM67506400600013500128001200019200180002560024000320003000038400360004480042000
ROWSDEEP2342343434543434
# OFFANS1112223344556677
AVAILCIRCUITS
30303030303030303030303030303030
WGT INCLFLOODCHARGE(LBS)1811852003523724005596008409008619501070115013491450
WINTERFLOODCHARGE(LBS)10141919293943586486629786116107144
LAVB 222 10LAVB 223 10LAVB 224 10LAVB 233 10LAVB 234 10LAVB 243 10LAVB 244 10LAVB 253 10LAVB 254 10LAVB 263 10LAVB 264 10LAVB 273 10LAVB 274 10
121.0157.8181.7236.7272.6315.6363.4394.5454.3473.3545.1552.2636.0
181.5236.7272.6355.0408.8473.3545.1591.7681.4710.0817.7828.3953.9
242.0315.6363.4473.3545.1631.1726.8788.9908.5946.7
1090.21104.51271.9
117.8153.5176.8230.2265.2307.1353.6383.8441.9460.6530.4537.3618.8
176.5230.2265.2345.5397.8460.6530.4575.7663.0690.8795.6806.0928.2
235.4307.1353.6460.6530.4614.1707.1767.6884.0921.21060.81074.71237.5
27000256002400038400360005120048000640006000076800720008960084000
ESTSOUND10’(dBA)65656568686870707171727273737474
71717173737474757576767777
2443434343434
4446688101012121414
60606060606060606060606060
6548659251118122517051825172219252095222527252925
38648686116126172124194172232214288
NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between thesaturated condensing temp. and the entering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a.Not available with Quietor fan blades.
AL
ELECTRICAL BOX
49
Side ViewsHeader End View
11
12, 22
13, 23
14, 24
15, 25
16, 26
17, 27
AL
AL A
L
LA
LL
A A
A
A
A A
A
A
A
AL
A
H
BW
H
BW
DIMEnSIOnAL DATA
Includes standard 18" legs.(1) Connections are approximate. Exact size is determined by computerized circuiting program.
ONE FAN WIDE
L
3975111147183219262
H
41-1/441-1/441-1/441-1/441-1/441-1/441-1/4
W
45-1/445-1/445-1/445-1/445-1/445-1/445-1/4
B
43-1/443-1/443-1/443-1/443-1/443-1/443-1/4
A
367210872/72
72/36/7272/72/72
72/72/36/72
LAVB-11***LAVB-12***LAVB-13***LAVB-14***LAVB-15***LAVB-16***LAVB-17***
ELECTRICAL DATA
ONE FAN WIDE
FAN MOTOR TOTAL RATED FULL LOAD AMPS CONNECTIONS OD IN.(1)
208/230/1
4.28.412.616.821.025.229.4
INLET
1-1/81-3/81-3/81-5/82-1/82-1/82-5/8
OUTLET
1-1/81-3/81-3/81-5/82-1/82-1/82-5/8
208/230/3
2.85.68.411.214.016.819.6
460/3
1.32.63.95.26.57.89.1
575/3
0.761.522.283.043.84.565.32
Levitor II Air Cooled Condenser
LEVITOR II AIR COOLED CONDENSER 15Specifications subject to change without notice.
Dimensional and Electrical Data
Levitor II Air Cooled Condenser
Control Panel Nomenclature
16 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
TYPE OF APPLICATION:1 = Standard2 = 50% Winter Reduction Relay
(Split Condenser)3 = 50/50 Split Dual Panel
(for Two Indep. Slabs)4 = No Control Operation
(Terminal Blocks Only)
RELAY BOARDCONTROLS:
NC = No ControlsPT = Pressure ControlsTF = Temp. ControlsTP = Temperature and
Pressure ControlPV = Pressure Control
w/Variable SpeedHead Fans
TV = Temp. Controlw/Variable SpeedHeader End Fans
VN = No Controlsw/Variable SpeedHeader End Fans
FAN/MOTOR COMBINATION:
A = 1 HP 850 RPM 30"
B = 1/2 HP 1140 RPM 24"
C = 1-1/2 HP 850 RPM 30"
E = 1/2 HP 575 RPM 30"
F = 1-1/2 HP 1140 RPM 30"
FANS WIDE:1 or 2
FANS IN LINE:1 to 7(7 Fans on “B” Units Only)
CONTROL VOLTAGE:A = 208/230V F = 115V w/o TransformerB = 115V G = No Control VoltageC = No Control Voltage w/o TransformerD = 24V H = 24V w/o TransformerE = 208/230V w/o Transformer
CONTROL MANUFACTURER:1 = Johnson Mechanical3 = Johnson Electronic4 = No Controls
POWER VOLTAGE:A = 208/230/1/60K = 208/230/3/60M = 460/3/60P = 550/575/3/60U = 380/3/50
FUSES AND BREAKERS:1 = Individual Fuses and Contactors2 = Individual Circuit Breakers
and Contactors per each Fan3 = Fuses and Contactors per Pair of Fans4 = Terminal Blocks Only5 = Circuit Breaker and Contactor
per Pair of Fans6 = Fuses per Motor
AMBIENT AIR SENSOR FOR SPLIT(50% Winter Reduction):
T = Sensor ProvidedN = Sensor Not Required
PT A 2 6 M B 3 3 1 N
n Thermal Fantrol-Electronic temperature controlcycles fans in response to entering air temperature.Set points and differential for each step areadjustable.
n Pressurtrol-Electronic pressure control with single point pressure transducer cycles fans in response to condenser pressure. Set points and differential for each step are adjustable.
n Thermal Pressure Fantrol-Electronic temperature control cycle fans in response to entering air temperature, except for header end fan(s). Header end fan(s) are controlled by pressure control.
n Variable Speed Control-Header end fan(s) arecontrolled with a speed controller in response tohead pressure. Electronic pressure control cycles thebalance of fans.
n Fan cycling Sequence-Fans are cycled offindividually or side-by-side in pairs in sequencefrom the end opposite the header to the headerend. Header end fans run continuously ifcompressors are operating.
Control Paneln Standard weather resistant enclosure is mounted on the opposite end of the unit when looking at theheaders.
n Control power is 24, 115 or 230 volts. A transformer is factory installed when required.
n Fan contactor with branch circuit fuse protection. Each motor or bank of motors protected by fuses.
n For horizontal airflow application, consult factory.n Disconnect not included, but may be required tomeet local codes.
Optional Arrangementsn Fan motor contactor and fuses only.n Fan motor contactor and fuses only which operatevia a customer specified solid state board. Circuitboard is factory mounted and wired.
n 50/50 split with two fan wide models. Each side is controlled separately with individual control panels oneach side.
n 50% winter reduction with two fan wide models.The right side fans are isolated in winter. Fans arelocked out via a relay or switch during shutdown.
Levitor II Air Cooled Condenser
LEVITOR II AIR COOLED CONDENSER 17Specifications subject to change without notice.
Standard Fan Cycling/Control Arrangements
Levitor II Air Cooled Condenser
Low Ambient Controls (Head Pressure Control System)
Fan Cycling Sequence
18 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
TABLE A
Piping Schematic For Winter Controln Head Pressure Control for systems with air-cooled condenser is accomplished with two pressureregulating valves designed specifically for this typeof application. When low ambient conditions areencountered during winter operation on air-cooledsystems with a resultant drop in condensingpressure, the Head Pressure control’s purpose is to hold back enough of the condenser liquidrefrigerant so that some of the condenser surface is rendered inactive. This reduction of activecondensing surface results in a rise in thecondensing pressure and sufficient liquid linepressure for normal system operation.
Fan Cycling Controlsn Factory installed and tested fan cycling controlpanels (optional, see below for details).
Eternal Equalizer
Evaporator
Distributor
Condenser
CompressorGas Check Valve
HM Valve LLDrier
Receiver
SolenoidValve
TEV
1st Stage(Not Cycling)
2nd Stage
3rd Stage
4th Stage
5th Stage
6th Stage
CAPACITY MULTIPLIERWITH HEADER FANSRUNNING
1.00 0.55 0.40 0.33 0.28 0.24 0.55 0.40 0.33 0.28 0.24
NOTE:
Data given in table “A” is based on zero wind velocity. If condensers are subjected to wind effect, these multipliers will increase.
Levitor is available with a mounted receiver for applications where a remote receiver is desired.Included in the option are a heavy-duty base, extended legs, receiver, a 3-way valve, relief valve(s),rotalocks, ball valves, and ORI/ORD valves. Optional heated and/or oversized receivers available.
Receiver models are 12” taller than standard models. Add the following to weights:
SIZE
10-3/4” x 48”10-3/4” x 60”12-3/4” x 72”14-3/4” x 96”
R-22(LBS)
128162275444
R-404A(LBS)
114144245395
RECEIVER CAPACITIES @ 80% FuLL
# OF FANS1 x 11 x 21 x 31 x 41 x 51 x 61 x 72 x 22 x 32 x 42 x 52 x 62 x 7
1350440530620820910100052062072091010201120
2550640730820112012101300700800910121013201420
ADDITIOnAL unIT WEIGHTS
Levitor II Air Cooled Condenser
LEVITOR II AIR COOLED CONDENSER 19Specifications subject to change without notice.
Mounted Receivers
# OF RECEIVERS
Levitor II Air Cooled Condenser
Mounted Receiver Diagram (One Receiver)
20 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
ELECTRICAL
BOX
Levitor II Air Cooled Condenser
LEVITOR II AIR COOLED CONDENSER 21Specifications subject to change without notice.
Mounted Receiver Diagram (Two Receivers)
Levitor II Air Cooled Condenser
Wiring Diagram
22 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
(-311) Single Fans
(-331) Pairs of Fans
Levitor II Air Cooled Condenser
Replacement Parts
L_VE unITL_VC unIT
L_VA unIT
DESCRIPTION
MOTOR: 1 HP, 850 RPM, 208-230/460/3/60
MOTOR: 1 HP, 850 RPM, 575/3/60
FAN: 30” DIA. CW 5/8” BORE
GUARD: FOR 30” FAN
PART #
4410138
4410180
4780320
4910218
LAVB unIT
DESCRIPTION
MOTOR: 1/2 HP, 1140 RPM, 208-230/460/3/60
MOTOR: 1/2 HP, 1140 RPM, 575/3/60
FAN: 24” DIA. CW 5/8” BORE
GUARD: FOR 24” FAN
PART #
4410179
CALL
4780141
4914792
DESCRIPTION
MOTOR: 1-1/2 HP, 850 RPM, 208-230/460/3/60
MOTOR: 1-1/2 HP, 850 RPM, 575/3/60
FAN: 30” DIA. CW 5/8” BORE
GUARD: FOR 30” FAN
PART #
4410179
4410313
4780662
4910218
DESCRIPTION
MOTOR: 1/2 HP, 575 RPM, 208-230/460/3/60
MOTOR: 1/2 HP, 575 RPM, 575/3/60
FAN: 30” DIA. CW 5/8” BORE
GUARD: FOR 30” FAN
PART #
4410184
4410315
4780142
4910218
L_VF unIT
DESCRIPTION
MOTOR: 1-1/2 HP, 1140 RPM, 208-230/460/3/60
MOTOR: 1-1/2 HP, 1140 RPM, 575/3/60
FAN: 30” DIA. CW 5/8” BORE
GUARD: FOR 30” FAN
PART #
4410139
4410314
4780142
4910218
OTHER COMMOn PARTS
DESCRIPTION
1/2 HP, 208-230/1/60 FOR VARIABLE SPEED
3/4 HP, 208-230/1/60 FOR VARIABLE SPEED
MOTOR CONTACTOR WITH 24 VOLT COIL
MOTOR CONTACTOR WITH 110 VOLT COIL
MOTOR CONTACTOR WITH 230 VOLT COIL
P352AB-3C PRESSURE CONTROLLER
S352AA-2C ADDER MODULE (PRESSURE)
P399BAC-1C PRESSURE TRANSDUCER
A350AB-1 TEMPERATURE CONTROLLER
PART #
4410176
CALL
4480824
4481721
CALL
4481838
4481839
4481840
4481731
LEVITOR II AIR COOLED CONDENSER 23Specifications subject to change without notice.
Levitor II Air Cooled Condenser
Notes
24 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.
Krack Corporation 1300 North Arlington Heights Rd., Suite 130Itasca, IL 60143Ph: 630.629.7500
krack.com
Printed in U.S.A. ©2012 Krack Corporation Levitor II_K_082012