302 B - 98/04 A Product manual Date: April 1998 Air cooled water chillers ALR HA 120.2÷455.4 cooling capacity from 404 to 1410 kW 50 Hz - refrigerant: HCFC 22, HFC 407C, HFC 134a Supersedes: none high ambient

Upload: others

Post on 16-Aug-2020

8 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 AProduct manual

Date: April 1998

Air cooled water chillers

ALR HA 120.2÷455.4cooling capacity from 404 to 1410 kW50 Hz - refrigerant: HCFC 22, HFC 407C, HFC 134a

Supersedes: none

hig

h a

mb

ien

t

Page 2: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

ALR HA - Air cooled water chillers

302 B - 98/04 A - page 2/28

The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers offer you unsurpassedefficiency, flexibility, reliability, and serviceability in a totalpackage concept. Improved to include the latest heattransfer surface design and the most advanced and efficientreciprocating compressors in the industry, the redesignedALR HA chillers exceed efficiency requirements. TheMcQuay air cooled water chillers are completely factoryassembled, piped, wired and shipped in one piece, readyfor installation. Each unit consists of compressors, insulatedevaporator, condenser coils with independent subcoolercircuits, multiple propeller type direct drive condenser fanswith independent fan motors, heavy-gauge weatherproofcasing and weatherproof electrical control centre containingall necessary and operating controls and motor startingequipment.

Highly flexible designThe ALR HA units is available in 26 sizes covering a rangefrom 404 to 1410 kW nominal cooling capacity with coolanttemperature between +10°C and -8°C. Many optional fea-tures can be added to fit all installation requirements.

Low installation costsThe complete assembly of the units and function testing atthe factory reduces the cost of installation on site. A rigidsteel base distributes the weight of the unit to the supportpoints and allows simple installation by an easy access tothe lifting points. The units are designed with a single pointthree-phase mains connection. All units are suppliedcomplete with refrigerants HCFC 22, HFC 407C or HFC134a.

Low maintenance costsThe microprocessor safety and control system allows thetrouble shooting of any type of functional anomaly,enabling simpler, safer and timely intervention by the unitmaintenance personnel. The oil heater in the sump on eachcompressor and a complete set of controls and safetydevices protect the unit from abnormal operating conditions.

Code requirements All units are designed and manufactured in accordance withapplicable selections of the following which are equivalentto American Air-conditioning industry applicable codes:Rating of chillers: UNI 9018Construction of pressure vessel: TÜV Standards (optional)Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety CodesSafety Codes: CEI-EN 60204-1 CodesManufacturing Quality Stds: ISO 9001

Factory testingEach unit is pressure tested, evacuated and charged withthe refrigerant requested. It is then tested at the factory’stest bench under the design conditions specified by thecustomer. Upon request, a second series of tests can becarried out witnessed by the customer (see option 92).Before shipment, each unit is re-checked for pressure andrefrigerant charge control.

General characteristicsCabinet and structureThe cabinet is made of galvanized steel sheet and paintedto provide a high resistance to corrosion. The unit baseframe has holes to lift the unit with ropes for an easy instal-lation. The weight is uniformly distributed along the profiles

of the base and this facilitates the arrangement of the unit’sbases and the support structures. The electrical and controlequipment is located inside cubicles which can be accessedby key locked doors complete with door interlocking on thepower cabinet.

Semi-hermetic compressorsCompressors are reciprocating type 4, 6 or 8 cylinders withsuction and discharge valves of the disc type. The forced lu-brication is obtained through a reversible gear type pump.The oil heater is automatically switched on when the com-pressor stops to prevent oil dilution from liquid refrigerantand in order to keep the right fluidity. The electrical motorsare protected against thermal over load through thermistorsembedded in each of the three phases of the statoricwindings. The ALR HA units, are equipped with McQuay800 and 900 S compressors.

EvaporatorThe evaporator is a direct expansion shell-and-tube typewith water flowing in the baffled shell side and refrigerantflowing through the tubes. The ALR HA evaporator are de-signed in more separate refrigerant circuits, one for eachcompressor. The evaporator is manufactured with a carbonsteel shell and seamless high efficiency copper tubes. Rollexpansion anchors the refrigerant tubes in the heavy car-bon steel tube sheet. Water baffles are polypropylene to re-sist corrosion. Refrigerant head is in carbon steel and is re-movable to permit access to the tubes. The evaporator iswrapped with closed-cell heat insulation.

Condenser coilsThe new ALR HA units are constructed with internally en-hanced seamless copper tubes arranged in a staggered rowpattern and mechanically expanded into McQuay lancedand rippled aluminium condenser fins with full fin collars.An integral subcooling circuit provided sufficient sub coolingto effectively eliminate liquid flashing and increases in cool-ing capacity up to 8% without increasing in absorbedpower.

Condenser coil fans The condenser fans are of the helical type with wing-profileblades to achieve a better performance. The direct couplingwith the electrical motor eliminates any problems as regardsthe application of transmission devices and reduces the vi-brations caused by the functioning. The motors are suppliedas standard totally enclosed (Insulation class F) and are ofthe three-phase type; they are protected againstoverloading and short circuits by circuit breakers located in-side the electrical control panel. The fans operate informed bell shaped orifices.

Electrical control panel The components of both the power and the control are splitinto two sections of one main panel, accessed by individualkey locked doors to prevent unauthorised entry. The panelis manufactured to insure protection in all weather condi-tions and the doors are fitted with door-stays to prevent ac-cidental closure. The power panel is fitted with a door inter-locked mains isolator to prevent access while it is live.Power section includes: This section of the panel includescontactors, all the fuses for the compressors and thecondenser fans, control circuit transformer. Additional spaceis provided for the installation of the various optional acces-sories provided to enhance the capabilities of the ALR HAunits.

Control section includes: Microprocessor is installed as

Page 3: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 3/28

standard on all the units. Its touch sensitive keypad consistsof keys that can be used to alter unit set points and controlcommands. A display on two lines illustrates the machine'soperating status & programable parameters (setpoints) e.g.temperatures & pressures of fluids (water, refrigerant)controller maximise the McQuay chillers energy efficiencyand reliability characteristics. It uses sophisticated softwarewith predictive logic to select the most energy efficient com-bination of compressor, condenser fan to maintain stableoperating conditions and maximise energy efficiency. Thecompressors are automatically rotated to ensure equal ope-rating hours. Controller intervenes to protect critical compo-nents in response to external signals from its system sen-sors measuring: motor temperatures, refrigerant gas and oilpressures, electrical supply and evaporator.

Refrigerant circuitThe ALR HA units are equipped with a complete refrigerantcircuit charge HCFC22, HFC407C or HFC134a. The circuitconsists of insulated copper pipes on the suction line and iscomplete with filter driers, moisture indicators, liquid sightglass, thermostatic expansion valves.

Acoustic optionsTwo versions are available.• ALR HA ST (Standard)• ALR HA CN (Compressor noise) for a reduced sound le-vel this unit is fitted with sound proofing cabinets around thecompressors insulated with absorbent acoustic material.

Accessories and Options 07. Double set point version (CB) - Dual leaving glycolmixture temperature setpoints. The lower setpoint can godown to -8°C.

11. Compressor thermal overload relays - Safety devicesagainst compressor motor overloading in addition to thenormal protection envisaged by the electrical windings.

15. Phase monitor - The phase monitor controls thevoltage values on the supply line stopping the unit when thecalibration threshold is reached (± 10%). This safety deviceis automatically reset.

16. Ammeter and voltmeter - Digital meters of unit drawnamperes and voltage values, installed on the electricalcontrol panel.

17. Condenser power factor correction - Installed on theelectrical control panel to ensure it conforms to the plantrules. (McQuay advices maximum 0,9).

18. 110 Volt control circuit - The 110 Volt control circuitare supplied by an appropriate current transformer installedon the electrical control panel.

21. Main Switch

22. Transformer - Transformer for auxiliary circuit.

32. Condenser coil guards - Metal protection guards fixedon all the external surface of the condenser coils.

33. Compressor guards - To prevent unauthorised accessto the cooling unit components.

34. Cu-Cu condensing coils - To give better protectionagainst corrosion by aggressive environments.

35. Cu-Cu-Sn condensing coils - To give better protec-tion against corrosion in aggressive environments and bysalty air.

36. Alucoat condensing coils - Fins are protected by aspecial epoxy paint with a high resistance to corrosion.

42. Flow switch - Supplied separately to be wired andinstalled on the evaporator water piping (by the customer).

60. Suction shut-off valve - Suction shut-off valve installedon the suction port (STD on HFC 134a & HFC407C).

61. Gauges - Gauges to control high and low gas pressureand lubricant oil pressure.

70b. MicroTech - Microprocessor (only for two circuit).

80. Spreader bars - Facilitate the lifting of the units keepingthe ropes away from the unit's casing.

82. Wooden box packing - Self-supporting wooden boxinternally insulated and suitable for shipment by sea.

83. Open Cage packing - Protection with polythene andwooden cage for transport and protection before theinstallation.

84. Rubber type antivibration mounts - Suppliedseparately, these are positioned under the base of the unitduring installation. Ideal to reduce the vibrations when theunit is floor mounted.

85. Spring type antivibration mounts - Suppliedseparately, these are positioned under the base of the unitduring installation. Ideal for dampening vibrations for instal-lation on roofs and metallic structures.

88. TUV approval - If required, the cooling units can beTUV tested and certified.

92. Witness tests - The units are normally tested at thetest bench prior to the shipment. On request, a second testcan be carried out, at customer’s presence, in accordancewith the procedures indicated on the test form.

Selection Procedures The procedure for selecting the cooling duty and the powerabsorbed by the compressors of the ALR HA units isindicated below.

1. The tables “Standard ALR HA unit performance” allow todetermine the cooling capacity, power absorbed by thecompressor motors with cooled water temperatures bet-ween +4°C and +9°C, ambient air temperatures between +25°C and +52°C.

2. Although the data can be interpolated, extrapolation is notpermitted. For conditions other than those shown in thetables, contact McQuay Product Group.

3. The performance of the ALR HA units refers to 5°C of ∆tof chilled water. The increase or reduction of the flow rate ofchilled water produces a reduction and an increase in thecooling performance which is negligible. To ensure thecorrect functioning of the exchanger, it is advisable tomaintain the water’s ∆t within 3°C ÷ 6°C.

4. The performance figures are based on Fouling factor of0.044 m2°C/kW. In the event of different values, thecorrection coefficients indicated in Table 2 should be used.

5. The performance is influenced by air density. Table 3gives the correction factors for the various altitudes abovesea level.

6. The power absorbed values given in the standardperformance tables refer to the compressors only. The

Page 4: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 4/28

current absorbed by the fans is given in the electricalcharacteristics table.

8. To obtain the flow resistance through the evaporator, usethe diagrams on page 9.

Example of selection of an ALR HA unitData:

Cooling capacity required: 650 kW

Ambient air temperature: +46°C

Temperature of cooled water: from 12 to 7°C

Refrigerant: HCFC22

Fouling factor: 0.132 m2°C/kW

Altitude above sea level: 900 m

Glycol content: none

1. The cooling capacity correction coefficient for fouling 0.132 m2°C/kW (Table 2) is 0.975.

2. The cooling capacity correction coefficient for installationat 900 m above sea level (Table 3) is 0.979.

3. The corrected cooling capacity is 650 kW/0.975/0.979 = 681 kW.

4. The cooling unit to satisfy this capacity is ALR HA 230.2ST 022. This unit will have the following operating data:

Cooling capacity: 684 kW x 0.975 x 0.979 = 652,9 kW

Power absorbed by compressors: 243,1 kW x 0.986 x 1.015 = 243,3 kW.

Chilled water flow rate: 652,9 kW/4.186/(12-7) = 31,2 l/s.

Pressure drop indicated by the diagram on page 9 with acooled water flow of 31,2 l/s on the straight linecorresponding to the unit ALR HA 230.2 we find a pressuredrop of 32 kPa.

Water content in cooling circuitsThe cooled water distribution circuits should have aminimum water content to avoid excessive intermittentoperation of the compressors. In fact, each time thecompressor starts up, an excessive quantity of oil goes fromthe compressor’s sump and simultaneously there is a rise in

the temperature of the compressor motor’s stator due to theinrush current during the start-up. To prevent damage to thecompressors, McQuay has envisaged the application of adevice to limit frequent stops and restarts.

During the span of one hour there will be no more than 6starts of the compressor. The plant side should thereforeensure that the overall water content allows a more constantfunctioning of the unit and consequently greaterenvironmental comfort. The minimum installation water con-tent envisaged should be calculated with a certainapproximation using this formula:

(1) Q = P x p 25

where:

Q = minimum content of the plant expressed in litres.

P = cooling capacity of the plant expressed in W

p = minimum unloading capacity percentage

A plant with a 445 kW cooling capacity in which the coolingunit ALR 120.2 ST 022 equipped with two compressors isapplied, should have a minimum content of water calculatedon the basis of the minimum cooling capacity, which for thistype of equipment is 25% of the nominal capacity.

Q = 445000 x 0.25 = 4450 l 25

For a more accurate determination of the quantity of water,it is advisable to contact the designer of the plant.When thesum of the water content of the evaporator, the pipes of thehydraulic circuit and the terminals (coils, exchangers, etc.) islower than the value obtained, it would be better to opt for aALR McQuay cooling unit equipped with inertial tank(optional).

Table 1 - Operating limits HCFC 22

ST CN HFC 407C

ST CN HFC 134a

ST CN

Max ambient temperatureMin ambient temperatureMax entering evap. water temp. (without glycol)Min leaving evap. water temp. (without glycol)

°C°C

525

°C°C

154

525

525

154

156

525

525

156

154

525

154

Table 3 - Altitude correction factorElevation above sea level (m)

Barometric pressure (mbar)

0

1013

300

977

600

942

900

908

1200

875

1500

843

1800

812

Cooling cap. correction factor

Power input correction factor

1,000

1,000

0,993

1,005

0,986

1,009

0,979

1,015

0,973

1,021

0,967

1,026

0,960

1,031

Table 2 - Fouling factorFouling

factor

Cooling capacity

correction

Power input

correction

m2°C/kW

0,044

0,132

0,308

factor

1,000

factor

1,000

0,975

0,919

0,986

0,939

Page 5: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 5/28

Installation notes

HandlingAll moving and handling may damage the unit if someconditions are not scrupulously observed. The units shouldbe lifted with a crane using long ropes anchored to theholes on the frame of the unit’s base and by using the upperspacer bars (see accessory 80) to prevent the ropes fromdamaging the condenser coils.

Location The ALR units are produced for outside installation onroofs, floors or below ground level on condition that the areais free from obstacles for the passage of the condensationair. The unit should be positioned on solid foundations andperfectly level; in the case of installation on roofs or floors, itmay be advisable to arrange the use of suitable weightdistribution beams. When the units are installed on theground, a concrete base at least 250 mm wider and longerthan the unit’s footprint should be laid. Furthermore, thisbase should be sufficiently robust to withstand the unitweight mentioned in the technical data table. When theunits are positioned in areas which are easily accessible bypersons or animals, it is advisable to fit guards to protectthe condenser coil guards (see accessory 32) and, whennecessary, also guards to protect the compressor (seeaccessory 33).

Space requirementsThe ALR HA units are air-cooled, hence it is important toobserve the minimum distances which guarantee the bestventilation of the condenser coils. Limitations of space re-

ducing the air flow could cause significant reductions incooling capacity, an increase in electricity consumption and,in some cases, the unit may stop functioning as a result ofthe high condensation pressure. The fans do not allow theuse of ducts which have high flow resistance, hence isshould be ensured that the output air cannot recycle itselfinside the condenser coils. The units should be positionedsuch that there is sufficient distance between the coils andany obstacles to improve ventilation and also to facilitate in-spection. When two or more units are positioned side byside it is recommended that the condenser coils are at least3000 mm distance from one another. Smaller distancescould cause the recirculation of hot air. If the units arepositioned in places surrounded by walls or obstacles of thesame height as the units, the units should be at least 3000mm from said obstacles. For other installation solutions,consult McQuay technicians.

Acoustic protectionThe low noise levels of the ALR units means that they meetmost of the most restrictive regulations, thanks to theavailability of two versions with different sound levels: thestandard version (ST), the version with sound proofing cabi-net on compressors (CN). When the noise level must meetspecial requirements it will be necessary to pay themaximum attention to ensure the perfect insulation of theunit from the support base by applying appropriate vibration-dampening devices (see accessories 84 and 85), applyingvibration-dampening mounts on the water pipes and on theelectrical connections.

Nomenclature

ALR HA 200.2 ST 022Air cooled water chiller

High ambient temperature

Size: 200 Ton

No. of compressor 234

Version: ST Standard versionCN Sound proofing cabinets on compressors

Refrigerant: 022 HCFC 22407 HFC 407C134 HFC 134a

Page 6: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Physical data ALR HA ST, CN 120.2÷235.3

302 B - 98/04 A - page 6/28

"ALR HA ST, CN " Unit size 120.2 135.2 145.2 161.2 171.2Cooling capacity (HCFC 22) (1)

Power input (HCFC 22) (1)

kW

kW

404,6

146,6

443,7

163,4

492,1

176,1

536,2

196,7

558,9

206,5

Cooling capacity (HFC 407C) (1)

Power input (HFC 407C) (1)

kW

kW

Cooling capacity (HFC 134a) (1)

Power input (HFC 134a) (1)

kW

kW

392,5

146,6

430,4

163,4

257,3

90,9

283,4

100,8

477,3

176,1

520,1

196,7

309,9

108,4

321,3

121,7

542,1

206,5

359,3

125,6

McQuay compressor No./Series

No. of refrigerant circuit

Refrigerant charge HCFC 22

No. of reduction steps

kg

Std.

Condenser fans

Opt.

No. / Nominal power

Total air flow

kW

m3/s

904+806

2

806+806

2

34+34

4

34+34

4

806+906

2

906+906

2

37+37

4

37+37

4

5 6

6/2,1

37,4

6/2,1

36,8

6 6

8/2,1

50,7

8/2,1

50,7

906+808

2

37+42

4

6

8/2,1

49,9

Evaporator

No. of evaporator/Water volume l

Max operating pressure

Condenser coil

bar

Coil type

Weight

Operating weight (ALR ST)

Shipping weight (ALR ST)

kg

kg

1/131 1/128

16 16

1/162 1/160

16 16

Lanced fins - Internally spiral wound tubes

3667

3536

3798

3670

4362

4200

4372

4212

Operating weight (ALR CN) (2)

Shipping weight (ALR CN) (2)

kg

kg

3967

3836

4098

3970

4662

4500

4672

4512

1/158

16

4520

4362

4820

4662

"ALR HA ST, CN " Unit size 185.2 200.2 215.2 230.2 235.3Cooling capacity (HCFC 22) (1)

Power input (HCFC 22) (1)

kW

kW

581,7

216,2

627,4

222,6

657,6

231,2

705,2

246,3

775,5

287,0

Cooling capacity (HFC 407C) (1)

Power input (HFC 407C) (1)

kW

kW

Cooling capacity (HFC 134a) (1)

Power input (HFC 134a) (1)

kW

kW

564,2

216,2

608,6

222,6

382,4

135,2

409,0

145,3

637,9

231,2

684,0

246,3

435,6

155,4

479,4

151,5

752,2

287,0

478,0

166,4

McQuay compressor No./Series

No. of refrigerant circuit

Refrigerant charge HCFC 22

No. of reduction steps

kg

Std.

Condenser fans

Opt.

No. / Nominal power

Total air flow

kW

m3/s

808+808

2

808+908

2

42+42

4

50+52

4

908+908

2

908+908

2

52+52

4

52+52

4

6 6

8/2,1

49,1

10/2,1

63,3

6 6

10/2,1

63,3

12/2,1

63,3

2x906+806

3

37+37+34

6

-

12/2,1

76,0

Evaporator

No. of evaporator/Water volume l

Max operating pressure

Condenser coil

bar

Coil type

Weight

Operating weight (ALR ST)

Shipping weight (ALR ST)

kg

kg

1/156 1/153

16 16

1/150 1/150

16 16

4668

4512

4873

4720

Lanced fins - Internally spiral wound tubes

4882

4732

4900

4750

Operating weight (ALR CN) (2)

Shipping weight (ALR CN) (2)

kg

kg

4968

4812

5173

5020

5182

5032

5200

5050

1/279

16

6340

6061

6790

6511

Note: (1) Nominal cooling capacity and power input are based on: 12/7 0C entering/leaving evaporator water temperature; 46 0C ambient temperature.

(2) CN version is the ST one with the sound proof enclosure on the compressors.

Page 7: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 7/28

Physical data ALR HA ST, CN 251.3÷365.4

"ALR HA ST, CN " Unit size 251.3 261.3 270.3 286.3 290.3Cooling capacity (HCFC 22) (1)

Power input (HCFC 22) (1)

kW

kW

820,3

297,4

844,5

307,3

868,4

317,4

892,5

327,3

958,3

341,1

Cooling capacity (HFC 407C) (1)

Power input (HFC 407C) (1)

kW

kW

Cooling capacity (HFC 134a) (1)

Power input (HFC 134a) (1)

kW

kW

795,7

297,4

819,2

307,3

503,6

185,8

527,5

183,6

842,3

317,4

865,7

327,3

550,5

193,2

573,6

202,8

929,6

341,1

600,2

213,0

McQuay compressor No./Series

No. of refrigerant circuit

Refrigerant charge HCFC 22

No. of reduction steps

kg

Std.

Condenser fans

Opt.

No. / Nominal power

Total air flow

kW

m3/s

3x906

3

2x906+808

3

37+37+37

6

37+37+42

6

808+906+808

3

3x808

3

42+42+37

6

42+42+42

6

- -

12/2,1

76,0

12/2,1

75,2

- -

12/2,1

74,4

12/2,1

73,6

2x808+908

3

42+50+52

6

-

14/2,1

87,1

Evaporator

No. of evaporator/Water volume l

Max operating pressure

Condenser coil

bar

Coil type

Weight

Operating weight (ALR ST)

Shipping weight (ALR ST)

kg

kg

1/234 1/270

16 16

1/127 1/263

16 16

6342

6068

6495

6225

6636

6369

6784

6521

Operating weight (ALR CN) (2)

Shipping weight (ALR CN) (2)

kg

kg

6792

6518

6945

6675

7086

6819

7234

6971

1/263

16

7070

6807

7520

7257

"ALR HA ST, CN " Unit size 311.3 325.3 345.4 355.4 365.4Cooling capacity (HCFC 22) (1)

Power input (HCFC 22) (1)

kW

kW

997,2

358,8

1056,1

371,4

1117,8

413,0

1128,5

418,0

1140,6

422,7

Cooling capacity (HFC 407C) (1)

Power input (HFC 407C) (1)

kW

kW

Cooling capacity (HFC 134a) (1)

Power input (HFC 134a) (1)

kW

kW

967,3

358,8

1024,4

371,4

626,7

223,1

658,8

232,9

1084,3

413,0

1096,0

418,0

695,7

241,6

718,7

251,2

1106,4

422,7

741,8

260,9

McQuay compressor No./Series

No. of refrigerant circuit

Refrigerant charge HCFC 22

No. of reduction steps

kg

Std.

Condenser fans

Opt.

No. / Nominal power

Total air flow

kW

m3/s

2x908+808

3

3x908

3

52+52+42

6

52+52+52

6

3x906+808

4

2x906+2x808

4

37+37+42+42

8

37+37+42+42

8

- -

14/2,1

87,9

16/2,1

101,3

- -

16/2,1

100,5

16/2,1

99,8

906+808x3

4

37+42+42+42

8

-

16/2,1

99,0

Evaporator

No. of evaporator/Water volume l

Max operating pressure

Condenser coil

bar

Coil type

Weight

Operating weight (ALR ST)

Shipping weight (ALR ST)

kg

kg

1/295 1/291

16 16

1/545 1/545

16 16

7054

6759

7328

7037

9173

8628

9373

8828

Operating weight (ALR CN) (2)

Shipping weight (ALR CN) (2)

kg

kg

7504

7209

7778

7487

9773

9228

9973

9428

1/545

16

9573

9028

10173

9628

Note: (1) Nominal cooling capacity and power input are based on: 12/7 0C entering/leaving evaporator water temperature; 46 0C ambient temperature.

(2) CN version is the ST one with the sound proof enclosure on the compressors.

Page 8: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Physical data ALR HA ST, CN 375.4÷455.4

302 B - 98/04 A - page 8/28

"ALR HA ST, CN " Unit size 375.4 390.4 405.4 415.4 430.4 455.4Cooling capacity (HCFC 22) (1)

Power input (HCFC 22) (1)

kW

kW

1163,4

432,4

1216,5

437,7

1239,3

447,4

1315,2

462,4

1352,0

480,2

1410,0

492,6

Cooling capacity (HFC 407C) (1)

Power input (HFC 407C) (1)

kW

kW

Cooling capacity (HFC 134a) (1)

Power input (HFC 134a) (1)

kW

kW

1128,5

432,4

1180,0

437,7

764,8

270,5

791,4

280,5

1202,1

447,4

1275,7

462,4

817,9

290,7

844,5

300,8

1311,5

480,2

1368,1

492,6

871,1

310,9

959,0

303,0

McQuay compressor No./Series

No. of refrigerant circuit

Refrigerant charge HCFC 22

No. of reduction steps

kg

Std.

Condenser fans

Opt.

No. / Nominal power

Total air flow

kW

m3/s

4x808

4

3x808+908

4

42+42+42+42

8

42+42+50+52

8

2x808+2x908

4

808+3x908

4

42+42+52+52

8

50+52+52+52

8

- -

16/2,1

98,2

18/2,1

112,4

- -

18/2,1

112,4

20/2,1

126,6

4x908

4

4x908

4

52+52+52+52

8

52+52+52+52

8

- -

20/2,1

126,6

24/2,1

126,6

Evaporator

No. of evaporator/Water volume l

Max operating pressure

Condenser coil

bar

Coil type

Weight

Operating weight (ALR ST)

Shipping weight (ALR ST)

kg

kg

1/545 1/524

16 16

1/524 1/524

16 16

9653

9108

9922

9398

9922

9398

10220

9696

Operating weight (ALR CN) (2)

Shipping weight (ALR CN) (2)

kg

kg

10253

9708

10522

9998

10522

9998

10820

10296

1/524 1/524

16 16

10220

9696

10300

10824

10820

10296

10900

10376

Note: (1) Nominal cooling capacity and power input are based on: 12/7 0C entering/leaving evaporator water temperature; 46 0C ambient temperature.

(2) CN version is the ST one with the sound proof enclosure on the compressors.

Page 9: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 9/28

Water pressure drop evaporator

ALR HA 120.2ALR HA 135.2

ALR HA 171.2 - 185.2 - 200.2ALR HA 161.2

ALR HA 145.2 - 235.3ALR HA 215.2 - 230.2ALR HA 286.3 - 290.3

ALR HA 430.4 - 455.4ALR HA 345.4 - 355.4 - 365.4 - 375.4ALR HA 390.4 - 405.4 - 415.4

ALR HA 251.3 - 261.3ALR HA 270.3 - 311.3

ALR HA 325.3

100

80

60

40

30

20

10

Pre

ssur

e dr

op (

kPa)

6 8 10 20 30

50

70

90

7 9 40 50 60 80 10070 90

Water flow rate (l/s)

140

Page 10: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 10/28

Electrical data ALR HA ST, CN 120.2÷455.4 (HCFC 22, HFC 407C)

"ALR HA ST, CN" Unit size 120.2 135.2 145.2 161.2 171.2Standard voltage

Max absorbed current compr. (FLA) (2) A 277,0 310,0

400 V - 3f - 50 Hz (1)

333,0 356,0 388,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

585,0

28,8

585,0

28,8

305,8

718,4

338,8

751,4

620,0

38,4

620,0

38,4

371,4

790,2

394,4

813,2

750,0

38,4

426,4

943,2

Note: (1) Allowed voltage tolerance ±10%.

(2) Absorbed current max condition.

"ALR HA ST, CN" Unit size 185.2 200.2 215.2 230.2 235.3Standard voltage

Max absorbed current compr. (FLA) (2) A 420,0

400 V - 3f - 50 Hz (1)

445,0 470,0 470,0 511,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

750,0

38,4

750,0

48,0

458,4

975,2

493,0

979,0

750,0

48,0

750,0

57,6

518,0

1004,0

527,6

1004,0

620,0

57,6

568,6

983,4

"ALR HA ST, CN" Unit size 251.3 261.3 270.3 286.3 290.3Standard voltage

Max absorbed current compr. (FLA) (2) A 534,0

400 V - 3f - 50 Hz (1)

566,0 598,0 630,0 635,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

620,0

57,6

750,0

57,6

591,6

1006,4

623,6

1136,4

750,0

57,6

750,0

57,6

655,6

1168,4

687,6

1200,4

750,0

67,2

702,2

1205,4

"ALR HA ST, CN" Unit size 311.3 325.3 345.4 355.4 365.4Standard voltage

Max absorbed current compr. (FLA) (2) A 680,0

400 V - 3f - 50 Hz (1)

705,0 744,0 776,0 808,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

750,0

67,2

750,0

76,8

747,2

1230,5

781,8

1260,5

750,0

76,8

750,0

76,8

820,8

1329,6

852,8

1361,6

750,0

76,8

884,8

1393,6

"ALR HA ST, CN" Unit size 375.4 390.4 405.4 415.4 430.4 455.4Standard voltage

Max absorbed current compr. (FLA) (2) A 840,0

865,0

400 V - 3f - 50 Hz (1)

890,0 915,0 940,0 940,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

750,0

76,8

750,0

86,4

916,8

1431,3

951,4

1431,4

750,0

86,4

750,0

96,0

976,4

1456,3

1011,0

1487,0

750,0

96,0

750,0

115,2

1036,0

1512,0

1055,2

1512,0

Page 11: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 11/28

Electrical data ALR HA ST, CN 120.2÷455.4 (HFC 134)

"ALR HA ST, CN" Unit size 120.2 135.2 145.2 161.2 171.2Standard voltage

Max absorbed current compr. (FLA) (2) A 182,0

400 V - 3f - 50 Hz (1)

220,0 220,0 220,0 265,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

585,0

22,8

585,0

22,8

204,8

668,4

242,8

706,4

620,0

30,4

620,0

30,4

250,4

745,2

250,4

745,2

750,0

30,4

295,4

875,2

Note: (1) Allowed voltage tolerance ±10%.

(2) Absorbed current max condition.

"ALR HA ST, CN" Unit size 185.2 200.2 215.2 230.2 235.3Standard voltage

Max absorbed current compr. (FLA) (2) A 310,0

400 V - 3f - 50 Hz (1)

310,0 310,0 310,0 330,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

750,0

30,4

750,0

38,0

340,4

920,2

348,0

924,0

750,0

38,0

750,0

45,6

348,0

924,0

355,6

924,0

620,0

45,6

375,6

870,4

"ALR HA ST, CN" Unit size 251.3 261.3 270.3 286.3 290.3Standard voltage

Max absorbed current compr. (FLA) (2) A 330,0

400 V - 3f - 50 Hz (1)

375,0 420,0 465,0 465,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

620,0

45,6

750,0

45,6

375,6

870,4

420,6

1000,4

750,0

45,6

750,0

45,6

465,6

1045,4

510,6

1090,4

750,0

53,2

518,2

1095,5

"ALR HA ST, CN" Unit size 311.3 325.3 345.4 355.4 365.4Standard voltage

Max absorbed current compr. (FLA) (2) A 465,0

400 V - 3f - 50 Hz (1)

465,0 485,0 530,0 575,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

750,0

53,2

750,0

60,8

518,2

1095,5

525,8

1100,5

750,0

60,8

750,0

60,8

545,8

1125,5

590,8

1170,6

750,0

60,8

635,8

1215,6

"ALR HA ST, CN" Unit size 375.4 390.4 405.4 415.4 430.4 455.4Standard voltage

Max absorbed current compr. (FLA) (2) A 620,0 620,0

400 V - 3f - 50 Hz (1)

620,0 620,0 620,0 620,0

Max bigger compressors inrush current

Absorbed current fans

A

A

Max unit absorbed current

Max unit inrush current

A

A

750,0

68,4

750,0

68,4

688,1

1266,3

688,4

1266,3

750,0

68,4

750,0

76,0

688,4

1266,3

696,0

1272,0

750,0

76,0

750,0

91,2

696,0

1272,0

711,2

1272,0

Page 12: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Sound pressure level ALR HA ST 120.2÷455.4

302 B - 98/04 A - page 12/28

ALR HA ST Sound pressure leve l a t 1 m f rom the uni t in f ree f ie ld ( r i f . 2 x 10 - 5 )

Unit size

120.2

63 Hz

76,5

125 Hz

78,5

250 Hz

79,5

500 Hz

79,5

1000 Hz

78,0

2000 Hz

74,5

4000 Hz

71,0

8000 Hz

69,5

dBA

82,5

135.2

145.2

161.2

171.2

76,5

77,5

78,5

79,5

77,5

77,5

79,5

79,5

79,5

80,5

79,5

80,5

80,5

80,5

80,5

80,5

78,0

79,0

74,5

75,5

79,0

79,0

75,5

75,5

71,0

72,0

69,5

70,5

72,0

72,0

70,5

70,5

82,5

83,5

83,5

83,5

185.2

200.2

215.2

230.2

77,5

77,5

79,5

79,5

77,5

77,5

79,5

79,5

235.3

251.3

261.3

270.3

77,5

77,5

79,5

79,5

77,5

77,5

79,5

79,5

80,5

80,5

80,5

81,5

80,5

80,5

81,5

81,5

79,0

80,0

75,5

76,0

80,0

80,0

76,0

76,0

80,5

80,5

81,5

81,5

80,5

80,5

80,5

80,5

80,0

80,0

76,0

76,0

79,0

79,0

75,5

75,5

72,0

72,0

70,5

70,5

72,0

72,0

70,5

70,5

83,5

83,5

83,5

83,5

72,0

72,0

70,5

70,5

72,0

72,0

70,5

70,5

84,0

84,0

84,0

84,0

286.3

290.3

311.3

325.3

77,5

77,5

79,5

79,5

77,5

77,5

79,5

79,5

345.4

355.4

365.4

375.4

77,5

77,5

79,5

79,5

77,5

77,5

79,5

79,5

80,5

80,5

80,5

80,5

80,5

80,5

80,5

80,5

79,0

79,0

75,5

75,5

79,0

79,0

75,5

75,5

80,5

80,5

80,5

80,5

80,5

80,5

80,5

80,5

79,0

79,0

75,5

75,5

79,0

79,0

75,5

75,5

390.4

405.4

415.4

430.4

77,5

77,5

79,5

79,5

77,5

77,5

79,5

79,5

455.4 77,5 79,5

80,5

80,5

80,5

80,5

80,5

80,5

80,5

80,5

79,0

79,0

75,5

75,5

79,0

79,0

75,5

75,5

80,5 80,5 79,0 75,5

72,0

72,0

70,5

70,5

72,0

72,0

70,5

70,5

84,0

84,0

84,0

84,0

72,0

72,0

70,5

70,5

72,0

72,0

70,5

70,5

83,5

83,5

83,5

83,5

72,0

72,0

70,5

70,5

72,0

72,0

70,5

70,5

83,5

83,5

83,5

83,5

72,0 70,5 83,5

Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.

Page 13: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 13/28

Sound pressure level ALR HA CN 120.2÷455.4

ALR HA CN Sound pressure leve l a t 1 m f rom the uni t in f ree f ie ld ( r i f . 2 x 10 - 5 )

Unit size

120.2

63 Hz

73,5

125 Hz

75,5

250 Hz

76,5

500 Hz

76,5

1000 Hz

75,0

2000 Hz

71,5

4000 Hz

68,0

8000 Hz

66,5

dBA

79,5

135.2

145.2

161.2

171.2

73,5

74,5

75,5

76,5

74,5

74,5

76,5

76,5

76,5

77,5

76,5

77,5

77,5

77,5

77,5

77,5

75,0

76,0

71,5

72,5

76,0

76,0

72,5

72,5

68,0

69,0

66,5

67,5

69,0

69,0

67,5

67,5

79,5

80,5

80,5

80,5

185.2

200.2

215.2

230.2

74,5

74,5

76,5

76,5

74,5

74,5

76,5

76,5

235.3

251.3

261.3

270.3

74,5

74,5

76,5

76,5

74,5

74,5

76,5

76,5

77,5

77,5

77,5

78,5

77,5

77,5

78,5

78,5

76,0

77,0

72,5

73,0

77,0

77,0

73,0

73,0

77,5

77,5

78,5

77,5

77,5

77,5

77,5

77,5

77,0

76,0

73,0

72,5

76,0

76,0

72,5

72,5

69,0

69,0

67,5

67,5

69,0

69,0

67,5

67,5

80,5

80,5

80,5

81,0

69,0

69,0

67,5

67,5

69,0

69,0

67,5

67,5

81,0

81,0

81,0

81,0

286.3

290.3

311.3

325.3

74,5

74,5

76,5

76,5

74,5

74,5

76,5

76,5

345.4

355.4

365.4

375.4

74,5

74,5

76,5

76,5

74,5

74,5

76,5

76,5

77,5

77,5

77,5

77,5

77,5

77,5

77,5

77,5

76,0

76,0

72,5

72,5

76,0

76,0

72,5

72,5

77,5

77,5

77,5

77,5

77,5

77,5

77,5

77,5

76,0

76,0

72,5

72,5

76,0

76,0

72,5

72,5

390.4

405.4

415.4

430.4

74,5

74,5

76,5

76,5

74,5

74,5

76,5

76,5

455.4 74,5 76,5

77,5

77,5

77,5

77,5

77,5

77,5

77,5

77,5

76,0

76,0

72,5

72,5

76,0

76,0

72,5

72,5

77,5 77,5 76,0 72,5

69,0

69,0

67,5

67,5

69,0

69,0

67,5

67,5

81,0

81,0

81,0

80,5

69,0

69,0

67,5

67,5

69,0

69,0

67,5

67,5

80,5

80,5

80,5

80,5

69,0

69,0

67,5

67,5

69,0

69,0

67,5

67,5

80,5

80,5

80,5

80,5

69,0 67,5 80,5

Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.

Page 14: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Standard ratings ALR HA ST,CN 120.2÷235.3 (HCFC 22)

302 B - 98/04 A - page 14/28

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

45

418,0431,6

InputkW

capacitykW

125,9127,9

395,9408,8

InputkW

capacitykW

132,8134,8

382,3394,7

InputkW

capacitykW

136,8138,8

368,5380,4

InputkW

capacitykW

140,7142,6

359,1370,6

InputkW

capacitykW

143,2145,1

340,3351,0

InputkW

148,2150,1

ALR HA120.2

67

445,3459,0

89

472,8486,2

ALR HA135.2

45

459,8474,6

67

489,5504,4

129,9131,8

421,8434,9

133,7135,6

448,1461,5

136,8138,8

407,3420,0

140,7142,5

432,8445,8

140,8143,1

435,2449,2

145,3147,5

463,3477,5

148,3150,6

420,1433,5

152,8155,0

447,1460,8

140,8142,7

392,4404,6

144,7146,5

417,1429,6

144,6146,6

382,3394,2

148,5150,4

406,3418,6

152,6154,9

404,8417,5

157,1159,3

430,5443,7

156,8159,0

394,4406,7

161,2163,4

419,3432,1

147,1149,0

362,1373,4

150,9152,8

384,7396,6

152,1153,8155,7157,6

159,5161,7

373,6385,1

163,9166,0

396,9408,9

164,9167,1169,3171,2

89

519,4534,5

45

505,6521,9

ALR HA145.2

67

537,9554,2

89

570,6587,0

149,7151,7

491,8506,3

150,6152,9

480,2495,7

157,2159,3

474,7488,7

159,2161,6

464,5479,4

155,3157,5

511,3527,0

159,7161,8

542,4558,2

163,9166,2

494,5509,8

168,5170,7

525,1540,2

ALR HA161.2

45

553,4571,1

67

589,0606,8

89

624,7642,6

45

577,1595,3

168,9171,6

524,6541,5

174,2176,7

558,5575,6

178,2180,9

506,9523,1

183,6186,1

539,6556,1

179,1181,5

592,8610,1

177,4180,2

547,6564,8

188,6191,1

572,9589,8

187,2190,0

529,3545,9

161,4163,6

457,1470,7

164,2166,6

448,5462,8

165,5167,7

445,1458,4

169,1171,5

437,6451,5

168,9171,2

477,4492,1

173,5175,8

507,0522,0

173,8176,1

465,7480,0

178,4180,6

494,6509,3

168,2170,3

421,1433,8

172,3174,7

415,8428,9

173,6175,5178,7181,1

177,0179,3

442,3455,8

181,5183,7

469,8483,9

183,4185,7187,7189,9

183,6186,3

488,8504,3

189,0191,5

520,1536,2

188,9191,6

476,5491,6

194,2196,7

506,9522,5

194,1196,6

552,4568,8

192,8195,6

510,6526,5

199,3201,8

538,4554,5

198,3201,1

498,0513,3

192,3194,9

451,9466,2

197,5200,1

480,5495,1

199,1201,5204,1206,9

202,6205,1

510,4525,9

201,9204,7

472,8486,9

209,2211,7209,1211,9

ALR HA171.2

67

613,4631,6

89

649,2667,4

ALR HA185.2

45

600,9619,4

67

637,8656,3

182,9185,5

582,1599,5

188,2190,7

617,0634,6

192,7195,4

562,6579,5

198,0200,6

596,6613,7

185,9188,8

570,5588,1

191,6194,3

605,8623,5

196,1199,0

551,8568,7

201,9204,6

585,7602,9

89

673,8692,2

45

647,1668,2

ALR HA200.2

67

689,5710,9

89

731,8753,5

197,3200,0

641,3659,1

191,0194,0

613,3633,3

207,4210,1

620,3637,7

201,5204,6

592,7611,8

196,9199,8

653,4673,8

202,8205,6

694,4715,1

207,6210,5

631,2650,9

213,4216,2

670,8690,9

198,4201,0

542,6558,9

203,7206,3

575,5592,2

203,8206,5

529,0544,9

209,1211,7

561,0577,4

202,0204,9

532,5548,7

207,8210,6

565,1581,7

207,8210,6

519,4535,1

213,5216,2

551,0567,2

207,3210,0

501,8516,9

212,6215,2

532,0547,8

214,3217,0219,6222,2

211,5214,4

493,2507,9

217,1219,9

522,8538,2

218,9222,0224,3227,3

213,3216,0

598,5615,5

207,7210,7

571,6589,9

219,0221,7

583,6600,2

213,7216,7

557,4575,1

213,7216,6

608,5627,4

219,5222,4

646,6666,2

219,6222,6

593,1611,5

225,4228,3

630,2649,3

222,6225,3

553,8569,6

217,6220,5

529,0545,5

229,8232,5225,4228,1

223,5226,4

562,3579,7

229,2232,1

597,4615,5

231,3234,0236,8239,7

ALR HA215.2

45

677,6699,6

67

721,7744,0

89

765,8788,3

45

725,1748,4

198,3201,4

642,7663,4

204,4207,4

684,4705,6

209,3212,4

621,3641,2

215,5218,6

661,4681,9

210,6213,4

727,0748,6

210,8214,1

688,6710,7

221,6224,5

702,6723,5

222,7226,1

666,2687,5

ALR HA230.2

67

771,9795,4

89

818,0841,8

ALR HA235.3

45

800,8827,8

67

853,3879,6

217,3220,5

733,0755,4

223,9226,9

778,1800,9

229,4232,6

708,9730,6

235,7238,8

752,6774,8

238,9242,7

758,4783,2

246,3249,9

808,2833,5

251,9255,7

732,3756,2

259,5263,1

780,4804,8

215,7218,9

599,5618,5

222,0225,0

637,9657,6

222,0225,1

584,7603,1

228,2231,2

621,9641,0

228,0231,0

677,6697,8

229,7233,1

643,5663,8

234,2237,1

660,5680,3

236,6239,9

628,0647,6

226,1229,1

555,1572,3

232,2235,2

589,9607,8

234,3237,1240,2243,2

238,2241,1

626,3645,3

241,0244,3

597,0615,2

246,2249,1249,8253,1

236,3239,6

684,3705,2

242,7245,9

726,4747,9

243,1246,3

667,6687,9

249,5252,6

708,6729,6

259,5263,3

705,7728,6

267,0270,7

751,9775,5

266,8270,6

687,7709,9

274,3278,0

732,5755,4

247,5250,7

634,2653,3

253,8256,9

673,0693,0

256,3259,5262,4265,5

271,6275,3

651,7672,5

279,0282,7

693,7715,2

281,2284,7288,4292,1

89

906,1932,6

253,4256,8

858,9884,5

266,7270,3

829,5854,5

274,3277,9

799,4823,6

281,6285,2

778,8802,6

286,3289,9

737,6760,6

295,7299,3

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

Page 15: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 15/28

Standard ratings ALR HA ST, CN 251.3÷365.4 (HCFC 22)

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

45

848,8876,8

InputkW

capacitykW

256,0260,0

802,9829,3

InputkW

capacitykW

269,7273,8

774,8800,2

InputkW

capacitykW

277,6281,7

746,3770,5

InputkW

capacitykW

285,4289,4

727,0750,5

InputkW

capacitykW

290,4294,4

688,4710,5

InputkW

300,4304,4

ALR HA251.3

67

905,1933,7

89

962,5991,5

ALR HA261.3

45

874,3902,9

67

931,7960,9

264,0268,0

856,1883,2

271,8275,6

910,6938,3

277,8281,8

826,0852,1

285,8289,6

878,6905,5

264,7268,9

827,2854,2

273,1277,2

881,4909,0

278,8283,1

798,4824,3

287,3291,4

850,5877,1

285,8289,8

795,2820,3

293,7297,6

845,9871,9

293,4297,4

774,4798,8

301,3305,2

823,7849,1

287,0291,2

769,1793,8

295,4299,5

818,9844,5

295,0299,1

749,4773,2

303,3307,3

797,5822,3

298,3302,3

732,8755,8

306,2310,0

779,3803,5

308,1312,1316,0319,6

300,1304,3

710,0732,0

308,3312,4

754,7777,9

310,3314,7318,3322,6

89

990,21.019,8

45

899,5928,7

ALR HA270.3

67

958,1987,8

89

1.017,61.047,7

281,2285,1

937,0965,2

273,5277,9

851,3878,8

295,5299,5

904,1931,5

288,0292,4

821,8848,1

282,2286,4

906,5934,6

290,5294,6

963,0991,8

296,7301,0

874,8901,9

305,2309,3

929,3957,1

ALR HA286.3

45

925,0954,8

67

984,71.014,9

89

1.045,31.076,0

45

990,11.022,1

282,2286,8

875,6903,6

291,2295,6

931,9960,5

297,1301,7

845,4872,2

306,1310,6

899,3926,9

299,9304,1

989,41.018,6

293,3297,9

938,0968,3

314,9319,2

954,8983,1

309,1313,8

906,2935,2

303,6307,6

870,5896,9

296,4300,8

791,8816,8

311,4315,4

847,6873,5

304,6308,9

771,5795,7

305,1309,3

842,4868,4

313,5317,7

894,8921,7

313,1317,4

820,4845,6

321,5325,6

871,3897,6

316,4320,4

801,8826,7

309,9314,2

730,9753,5

326,4330,4320,5324,8

318,3322,5

776,4800,0

326,6330,7

824,3849,4

328,7332,7336,8340,9

305,8310,3

814,6840,1

314,7319,1

866,1892,5

314,2318,6

793,8818,4

323,0327,3

843,5869,1

323,4327,7

919,4946,7

318,4323,1

873,7901,5

331,6335,9

895,3922,0

327,4332,0

851,8878,6

319,7324,0

752,2775,0

328,3332,6

798,3822,3

330,7334,8338,9343,2

336,8341,1

847,1872,6

333,3337,8

808,0832,8

347,2351,5345,1349,4

ALR HA290.3

67

1.054,41.087,0

89

1.119,31.152,2

ALR HA311.3

45

1.030,51.063,5

67

1.096,71.130,2

302,5307,0

998,91.029,8

311,5315,8

1.061,01.092,6

318,5323,0

964,6994,4

327,5331,9

1.024,71.055,3

308,5313,4

976,81.007,9

318,3323,0

1.039,31.071,1

325,2330,2

943,8973,7

335,0339,8

1.003,91.034,6

89

1.163,91.196,6

45

1.087,51.122,4

ALR HA325.3

67

1.157,51.192,8

89

1.227,91.262,3

327,6332,6

1.103,21.135,6

318,3323,3

1.032,21.065,2

344,5349,2

1.065,61.097,0

336,1341,2

998,31.030,0

328,2333,0

1.098,51.132,1

337,9342,8

1.166,11.200,3

346,1351,0

1.062,11.094,6

355,8360,5

1.127,51.160,7

327,7332,2

929,6958,3

336,7341,1

987,41.017,0

336,6341,1

905,9933,7

345,5349,9

962,1991,0

335,0339,9

910,3938,8

344,7349,5

967,7997,2

344,5349,3

887,6915,1

354,1358,8

943,1971,7

342,3346,8

858,5884,5

351,2355,5

911,5939,0

353,7358,2362,6366,7

350,6355,4

842,2867,7

360,1364,8

893,9920,7

362,8367,6372,1376,8

354,2358,8

1.027,11.057,4

346,5351,6

963,7994,1

363,4368,1

1.000,81.030,5

356,7361,7

940,3969,6

356,5361,4

1.024,81.056,1

366,2370,9

1.087,81.120,0

366,6371,4

999,51.029,9

376,2380,9

1.060,81.092,2

369,4374,0

948,2976,7

363,3368,2

893,5920,6

381,4385,8376,5381,2

373,1377,9

948,9977,5

382,6387,3

1.006,81.036,6

386,1390,9395,4400,1

ALR HA345.4

45

1.154,21.190,6

67

1.226,81.263,2

89

1.298,41.334,8

45

1.165,21.202,0

354,8360,4

1.095,21.129,6

365,8371,0

1.164,21.199,0

374,4380,0

1.058,61.091,8

385,4390,8

1.125,21.159,0

376,4381,4

1.234,01.269,2

359,1364,1

1.105,71.140,4

396,0401,2

1.193,21.227,4

378,9384,6

1.068,71.102,3

ALR HA355.4

67

1.238,51.275,3

89

1.310,81.347,6

ALR HA365.4

45

1.178,01.214,7

67

1.251,21.287,9

370,2375,5

1.175,31.210,5

381,0386,0

1.245,81.281,3

390,1395,5

1.136,01.170,1

400,8406,1

1.204,61.239,1

363,3369,0

1.118,11.152,9

374,5379,8

1.187,91.223,0

383,3389,0

1.081,11.114,6

394,6400,0

1.148,31.182,4

385,6391,2

1.021,21.053,0

396,8402,0

1.085,21.117,8

396,6402,2

996,01.026,6

407,6413,0

1.058,01.089,8

407,4412,6

1.151,01.184,4

390,3395,9

1.031,01.063,1

418,2423,4

1.122,01.154,8

401,4407,1

1.005,51.036,4

403,8409,4

945,6973,8

414,6420,0

1.003,61.033,8

418,2423,8428,6434,0

425,2430,4

1.064,01.095,6

408,7414,4

954,5983,0

439,2444,4423,3429,0

401,6406,9

1.095,61.128,5

412,3417,6

1.162,01.195,7

412,5418,0

1.068,11.100,2

423,3428,5

1.132,71.165,9

394,8400,5

1.043,11.075,2

406,2411,6

1.107,71.140,6

406,1411,7

1.017,41.048,4

417,3422,7

1.080,01.112,1

419,6425,1

1.013,11.043,6

430,3435,6

1.074,11.106,3

433,8439,3444,3449,8

413,4419,1

966,0994,8

424,4429,9

1.024,61.055,1

428,0433,9438,6444,3

89

1.323,01.359,6

385,5390,7

1.258,31.293,7

405,4410,7

1.216,91.251,4

417,0422,3

1.174,01.207,7

428,1433,4

1.144,61.177,6

435,2440,5

1.085,81.117,4

449,4454,7

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C

4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

Page 16: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Standard ratings ALR HA ST,CN 375.4÷455.4 (HCFC 22)

302 B - 98/04 A - page 16/28

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

45

1.201,81.238,8

InputkW

capacitykW

371,8377,6

1.141,01.176,2

InputkW

capacitykW

392,2398,0

1.103,61.137,4

InputkW

capacitykW

404,0409,8

1.065,01.097,4

InputkW

capacitykW

415,6421,2

1.038,81.070,2

InputkW

capacitykW

423,0428,8

986,41.015,8

InputkW

437,8444,0

ALR HA375.4

67

1.275,61.312,6

89

1.347,61.384,4

ALR HA390.4

45

1.254,71.294,9

67

1.335,11.375,6

383,2388,6

1.211,61.247,0

394,6400,0

1.282,61.318,2

403,8409,2

1.171,41.205,8

414,8420,2

1.240,61.275,4

375,7381,6

1.190,31.228,2

387,3392,9

1.266,51.305,1

396,5402,4

1.150,61.187,1

408,2414,0

1.224,01.261,4

415,6421,2

1.130,21.163,4

426,6432,0

1.197,01.231,0

427,0432,4

1.102,01.134,4

438,0443,4

1.167,21.200,4

408,5414,5

1.110,11.145,0

420,4426,0

1.180,51.216,5

420,3426,2

1.082,71.116,4

432,0437,7

1.150,91.185,9

434,2439,8

1.045,61.076,4

445,2450,6

1.107,61.139,2

448,6454,6459,6465,0

428,0433,8

1.027,91.059,2

439,5445,2

1.091,71.124,7

443,4449,0454,5460,2

89

1.415,01.455,7

45

1.278,51.319,0

ALR HA405.4

67

1.359,51.400,3

89

1.439,61.480,5

398,8404,1

1.344,01.383,2

384,2390,2

1.213,21.251,5

419,6425,1

1.299,21.337,2

405,4411,4

1.173,11.209,9

396,0401,7

1.290,21.329,1

407,9413,4

1.368,31.407,7

417,4423,2

1.247,11.284,8

429,0434,6

1.322,91.361,2

ALR HA415.4

45

1.355,21.399,2

67

1.443,41.488,0

89

1.531,61.576,6

45

1.393,91.438,7

396,6402,8

1.285,41.326,8

408,8414,8

1.368,81.411,2

418,6424,8

1.242,61.282,4

431,0437,2

1.322,81.363,8

421,2426,8

1.454,01.497,2

412,0418,5

1.322,41.364,6

443,2449,0

1.405,21.447,0

434,8441,4

1.278,61.319,2

431,7437,3

1.253,11.290,0

417,7423,8

1.132,01.167,2

443,3448,8

1.221,51.257,7

429,8435,7

1.104,11.138,2

429,8435,6

1.203,01.239,3

441,3447,0

1.276,11.313,3

441,7447,4

1.172,91.208,2

453,2458,8

1.244,11.280,5

450,8456,3

1.158,31.193,1

437,6443,5

1.048,31.080,2

465,8471,3453,2459,1

449,3455,1

1.112,71.146,0

460,8466,4

1.180,11.214,9

464,5470,5476,0481,6

431,4437,8

1.199,01.237,0

444,0450,0

1.275,81.315,2

444,0450,2

1.169,41.206,2

456,4462,4

1.243,81.282,0

456,0462,0

1.355,21.395,6

448,1454,7

1.234,01.272,7

468,4474,2

1.321,01.360,6

461,2467,6

1.203,71.241,1

452,2458,2

1.110,21.144,6

464,4470,4

1.179,81.215,6

468,6474,2480,4486,4

476,4482,2

1.252,61.290,6

469,7475,9

1.143,11.177,9

492,4498,2486,7492,5

ALR HA345.4

67

1.483,71.529,1

89

1.572,91.618,6

ALR HA455.4

45

1.450,21.496,8

67

1.543,81.590,8

424,9431,1

1.407,41.450,5

437,8443,8

1.494,01.537,9

447,8454,2

1.360,31.401,9

460,4466,5

1.444,01.486,5

421,6428,2

1.377,21.421,4

434,6441,0

1.466,01.510,8

445,4452,2

1.332,41.375,0

458,8465,2

1.417,81.461,2

89

1.636,01.683,6

447,8453,8

1.556,21.601,8

471,4477,6

1.505,21.549,6

461,2467,4

1.312,11.352,1

473,7479,9

1.392,71.433,9

474,0480,2

1.279,31.318,1

486,5492,5

1.357,71.398,0

459,4466,2

1.287,01.327,6

472,6479,2

1.368,61.410,4

473,2479,8

1.256,01.295,2

486,2492,6

1.335,21.375,8

482,3488,5

1.213,71.250,1

494,7500,7

1.287,71.326,2

498,9505,1511,1517,1

482,0488,6

1.194,01.230,4

495,0501,4

1.268,41.306,6

499,6506,2512,6519,0

485,4491,8

1.452,81.495,8

499,0505,2

1.417,21.459,2

507,6513,8

1.346,01.386,0

524,8531,0

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

Page 17: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 17/28

Standard ratings ALR HA ST, CN 120.2÷235.3 (HFC 407C)

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

4*5*

405,5418,7

InputkW

capacitykW

125,9127,9

384,0396,5

InputkW

capacitykW

132,8134,8

370,8382,9

InputkW

capacitykW

136,8138,8

357,4369,0

InputkW

capacitykW

140,7142,6

339,4350,2

InputkW

capacitykW

145,7147,6

330,4340,8

InputkW

148,3150,2

ALR HA120.2

67

431,9445,2

89

458,6471,6

ALR HA135.2

4*5*

446,0460,4

67

474,8489,3

129,9131,8

409,1421,9

133,7135,6

434,7447,7

136,8138,8

395,1407,4

140,7142,5

419,8432,4

140,8143,1

422,1435,7

145,3147,5

449,4463,2

148,3150,6

407,5420,5

152,8155,0

433,7447,0

140,8142,7

380,6392,5

144,7146,5

404,6416,7

144,6146,6

361,3372,5

148,5150,4

383,9395,6

152,6154,9

392,7405,0

157,1159,3

417,6430,4

156,8159,0

372,7384,3

161,2163,4

396,1408,2

149,6151,4

351,6362,6

153,3155,2

373,6385,1

152,2153,9155,8157,7

162,2164,4

362,8374,0

166,6168,6

385,4397,1

165,0167,2169,4171,3

89

503,8518,5

4*5*

490,4506,2

ALR HA145.2

67

521,8537,6

89

553,5569,4

149,7151,7

477,0491,1

150,6152,9

465,8480,8

157,2159,3

460,5474,0

159,2161,6

450,6465,0

155,3157,5

496,0511,2

159,7161,8

526,1541,5

163,9166,2

479,7494,5

168,5170,7

509,3524,0

ALR HA161.2

4*5*

536,8554,0

67

571,3588,6

89

606,0623,3

4*5*

559,8577,4

168,9171,6

508,9525,3

174,2176,7

541,7558,3

178,2180,9

491,7507,4

183,6186,1

523,4539,4

179,1181,5

575,0591,8

177,4180,2

531,2547,9

188,6191,1

555,7572,1

187,2190,0

513,4529,5

161,4163,6

443,4456,6

164,2166,6

435,0448,9

165,5167,7

420,4433,0

169,1171,5

414,2427,3

168,9171,2

463,1477,3

173,5175,8

491,8506,3

173,8176,1

440,7454,2

178,4180,6

468,0482,0

170,9172,9

408,9421,3

175,6178,0

403,7416,4

173,7175,6178,8181,2

180,3182,6

429,4442,6

184,7186,9

456,1469,8

183,5185,8187,8190,0

183,6186,3

474,1489,2

189,0191,5

504,5520,1

188,9191,6

450,6464,8

194,2196,7

479,2493,9

194,1196,6

535,8551,7

192,8195,6

495,3510,7

199,3201,8

509,0524,3

198,3201,1

471,1485,4

195,8198,3

438,8452,7

200,9203,6

466,6480,8

199,2201,6204,2207,0

206,0208,5

495,6510,6

205,6208,4

459,1472,8

209,3211,8209,2212,0

ALR HA171.2

67

595,0612,7

89

629,7647,4

ALR HA185.2

4*5*

582,9600,8

67

618,7636,6

182,9185,5

564,6581,5

188,2190,7

598,5615,6

192,7195,4

545,7562,1

198,0200,6

578,7595,3

185,9188,8

553,4570,5

191,6194,3

587,6604,8

196,1199,0

535,2551,6

201,9204,6

568,1584,8

89

653,6671,4

4*5*

627,7648,2

ALR HA200.2

67

668,8689,6

89

709,8730,9

197,3200,0

622,1639,3

191,0194,0

594,9614,3

207,4210,1

601,7618,6

201,5204,6

574,9593,4

196,9199,8

633,8653,6

202,8205,6

673,6693,6

207,6210,5

612,3631,4

213,4216,2

650,7670,2

198,4201,0

526,3542,1

203,7206,3

558,2574,4

203,8206,5

500,3515,3

209,1211,7

530,5546,1

202,0204,9

516,5532,2

207,8210,6

548,1564,2

207,8210,6

491,4506,2

213,5216,2

521,1536,5

210,9213,6

487,2501,9

216,2218,8

516,6531,9

214,4217,1219,7222,3

215,3218,3

478,9493,2

220,8223,7

507,6522,6

219,0222,1224,4227,4

213,3216,0

580,5597,0

207,7210,7

554,5572,2

219,0221,7

552,0567,7

213,7216,7

527,2543,9

213,7216,6

590,2608,6

219,5222,4

627,2646,2

219,6222,6

560,7578,1

225,4228,3

595,8613,8

226,3229,0

537,7553,1

221,6224,4

513,6529,7

229,9232,6225,5228,2

227,5230,3

546,0562,9

233,1236,0

580,1597,7

231,4234,1236,9239,8

ALR HA215.2

4*5*

657,3678,6

67

700,0721,7

89

742,8764,7

4*5*

703,3725,9

198,3201,4

623,4643,5

204,4207,4

663,9684,4

209,3212,4

602,7622,0

215,5218,6

641,6661,4

210,6213,4

705,2726,1

210,8214,1

667,9689,4

221,6224,5

681,5701,8

222,7226,1

646,2666,9

ALR HA230.2

67

748,7771,5

89

793,5816,5

ALR HA235.3

4*5*

776,8803,0

67

827,7853,2

217,3220,5

711,0732,7

223,9226,9

754,8776,9

229,4232,6

687,6708,7

235,7238,8

730,0751,6

238,9242,7

735,6759,7

246,3249,9

784,0808,5

251,9255,7

710,3733,5

259,5263,1

757,0780,7

215,7218,9

581,5599,9

222,0225,0

618,8637,9

222,0225,1

553,2570,4

228,2231,2

588,1606,1

228,0231,0

657,3676,9

229,7233,1

624,2643,9

234,2237,1

624,5643,3

236,6239,9

594,5612,8

230,3233,2

539,0555,7

236,3239,3

572,8590,2

234,4237,2240,3243,3

242,3245,2

608,1626,6

245,5248,8

579,6597,3

246,3249,2249,9253,2

236,3239,6

663,8684,0

242,7245,9

704,6725,5

243,1246,3

631,8650,9

249,5252,6

670,5690,4

259,5263,3

684,5706,7

267,0270,7

729,3752,2

266,8270,6

650,1670,9

274,3278,0

692,2713,7

252,0255,2

615,8634,3

258,2261,3

653,4672,9

256,4259,6262,5265,6

276,5280,1

632,8653,0

283,8287,5

673,6694,5

281,3284,8288,5292,2

89

878,9904,6

253,4256,8

833,1858,0

266,7270,3

804,6828,9

274,3277,9

775,4798,9

281,6285,2

736,0758,7

291,1294,7

716,2738,6

295,8299,4

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C

4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

(*) 10% glycol must be added.

Page 18: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Standard ratings ALR HA ST,CN 251.3÷365.4 (HFC 407C)

302 B - 98/04 A - page 18/28

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

4*5*

823,3850,5

InputkW

capacitykW

256,0260,0

778,8804,4

InputkW

capacitykW

269,7273,8

751,6776,2

InputkW

capacitykW

277,6281,7

723,9747,4

InputkW

capacitykW

285,4289,4

687,0709,1

InputkW

capacitykW

295,5299,5

668,5689,9

InputkW

300,5304,5

ALR HA251.3

67

877,9905,7

89

933,6961,8

ALR HA261.3

4*5*

848,1875,8

67

903,7932,1

264,0268,0

830,4856,7

271,8275,6

883,3910,2

277,8281,8

801,2826,5

285,8289,6

852,2878,3

264,7268,9

802,4828,6

273,1277,2

855,0881,7

278,8283,1

774,4799,6

287,3291,4

825,0850,8

285,8289,8

771,3795,7

293,7297,6

820,5845,7

293,4297,4

731,5754,5

301,3305,2

778,0802,1

287,0291,2

746,0770,0

295,4299,5

794,3819,2

295,0299,1

708,3730,5

303,3307,3

753,4776,7

303,3307,3

711,6733,9

311,2314,9

756,8780,3

308,2312,2316,1319,7

305,3309,6

689,4710,8

313,4317,6

732,9755,4

310,4314,8318,4322,7

89

960,5989,2

4*5*

872,5900,8

ALR HA270.3

67

929,4958,2

89

987,11.016,3

281,2285,1

908,9936,2

273,5277,9

825,8852,4

295,5299,5

877,0903,6

288,0292,4

797,1822,7

282,2286,4

879,3906,6

290,5294,6

934,1962,0

296,7301,0

848,6874,8

305,2309,3

901,4928,4

ALR HA286.3

4*5*

897,3926,2

67

955,2984,5

89

1.013,91.043,7

4*5*

960,4991,4

282,2286,8

849,3876,5

291,2295,6

903,9931,7

297,1301,7

820,0846,0

306,1310,6

872,3899,1

299,9304,1

959,7988,0

293,3297,9

909,9939,3

314,9319,2

926,2953,6

309,1313,8

879,0907,1

303,6307,6

844,4870,0

296,4300,8

768,0792,3

311,4315,4

800,5825,2

304,6308,9

729,2751,9

305,1309,3

817,1842,3

313,5317,7

868,0894,0

313,1317,4

775,0798,7

321,5325,6

823,0847,9

321,5325,5

778,6802,8

315,3319,6

709,7731,7

326,5330,5320,6324,9

323,6327,7

753,9776,9

331,8335,9

800,5824,8

328,8332,8336,9341,0

305,8310,3

790,2814,9

314,7319,1

840,1865,7

314,2318,6

766,8790,4

323,0327,3

814,4839,0

323,4327,7

891,8918,3

318,4323,1

847,5874,5

331,6335,9

864,3890,2

327,4332,0

805,5830,6

325,3329,5

755,2778,1

333,7338,0

801,5825,6

330,8334,9339,0343,3

342,1346,4

850,5876,1

339,3343,7

784,6808,7

347,3351,6345,3349,6

ALR HA290.3

67

1.022,81.054,4

89

1.085,71.117,6

ALR HA311.3

4*5*

999,61.031,6

67

1.063,81.096,3

302,5307,0

968,9998,9

311,5315,8

1.029,21.059,8

318,5323,0

935,7964,6

327,5331,9

994,01.023,6

308,5313,4

947,5977,7

318,3323,0

1.008,11.039,0

325,2330,2

915,5944,5

335,0339,8

973,81.003,6

89

1.129,01.160,7

4*5*

1.054,91.088,7

ALR HA325.3

67

1.122,81.157,0

89

1.191,11.224,4

327,6332,6

1.070,11.101,5

318,3323,3

1.001,21.033,2

344,5349,2

1.033,61.064,1

336,1341,2

968,4999,1

328,2333,0

1.065,51.098,1

337,9342,8

1.131,11.164,3

346,1351,0

1.030,21.061,8

355,8360,5

1.093,71.125,9

327,7332,2

901,7929,6

336,7341,1

957,8986,5

336,6341,1

856,3882,4

345,5349,9

909,3936,7

335,0339,9

883,0910,6

344,7349,5

938,7967,3

344,5349,3

839,5865,2

354,1358,8

891,6918,4

348,1352,6

833,6858,9

357,0361,2

885,1911,8

353,8358,3362,7366,8

356,8361,6

817,8842,5

366,2370,9

868,0894,0

363,0367,8372,3377,0

354,2358,8

996,31.025,7

346,5351,6

934,8964,3

363,4368,1

945,9974,2

356,7361,7

889,9917,3

356,5361,4

994,11.024,4

366,2370,9

1.055,21.086,4

366,6371,4

945,6974,2

376,2380,9

1.003,41.033,1

375,5380,0

920,7948,4

370,0374,8

867,5893,9

381,5385,9376,7381,4

379,7384,5

921,3949,1

389,1393,8

977,61.006,5

386,3391,1395,6400,3

ALR HA345.4

4*5*

1.119,61.154,9

67

1.190,01.225,3

89

1.259,41.294,8

4*5*

1.130,21.239,2

354,8360,4

1.062,31.095,7

365,8371,0

1.129,31.163,0

374,4380,0

1.026,81.059,0

385,4390,8

1.091,41.124,2

376,4381,4

1.197,01.231,1

359,1364,1

1.072,51.175,7

396,0401,2

1.157,41.190,6

378,9384,6

1.036,61.136,4

ALR HA355.4

67

1.276,81.314,7

89

1.351,31.389,3

ALR HA365.4

4*5*

1.142,71.178,3

67

1.213,71.249,3

370,2375,5

1.211,61.247,9

381,0386,0

1.284,31.320,9

390,1395,5

1.171,11.206,3

400,8406,1

1.241,91.277,4

363,3369,0

1.084,61.118,3

374,5379,8

1.152,31.186,3

383,3389,0

1.048,71.081,2

394,6400,0

1.113,91.146,9

385,6391,2

990,61.021,4

396,8402,0

1.052,61.084,3

396,6402,2

942,3970,8

407,6413,0

1.000,51.030,6

407,4412,6

1.116,51.148,9

390,3395,9

1.000,11.096,0

418,2423,4

1.060,91.092,2

401,4407,1

975,31.068,5

411,1416,7

918,1945,5

421,7427,1

974,51.003,8

418,4424,0428,8434,2

432,3437,5

1.033,11.063,8

408,7414,4

963,0992,4

439,4444,6400,0405,5

401,6406,9

1.129,51.163,4

412,3417,6

1.197,91.232,7

412,5418,0

1.101,11.134,2

423,3428,5

1.167,71.202,0

394,8400,5

1.011,81.042,9

406,2411,6

1.074,51.106,4

406,1411,7

962,6991,6

417,3422,7

1.021,41.051,8

419,6425,1

1.022,71.053,5

430,3435,6

1.084,51.116,5

410,5415,8420,8426,0

420,8426,6

937,9965,9

431,6437,2

994,91.024,5

428,2434,1438,8444,5

89

1.283,31.318,8

385,5390,7

1.220,61.254,9

405,4410,7

1.180,41.213,9

417,0422,3

1.138,81.171,5

428,1433,4

1.082,51.113,8

442,4447,7

1.054,31.085,0

449,6454,9

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

(*) 10% glycol must be added.

Page 19: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 19/28

Standard ratings ALR HA ST, CN 375.4÷455.4 (HFC 407C)

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

4*5*

1.165,71.201,6

InputkW

capacitykW

371,8377,6

1.106,81.140,9

InputkW

capacitykW

392,2398,0

1.070,51.103,3

InputkW

capacitykW

404,0409,8

1.033,11.064,5

InputkW

capacitykW

415,6421,2

982,81.012,4

InputkW

capacitykW

430,5436,5

957,7986,3

InputkW

438,0444,2

ALR HA375.4

67

1.237,31.273,2

89

1.307,21.342,9

ALR HA390.4

4*5*

1.217,11.256,1

67

1.295,01.334,3

383,2388,6

1.175,31.209,6

394,6400,0

1.244,11.278,7

403,8409,2

1.136,31.169,6

414,8420,2

1.203,41.237,1

375,7381,6

1.154,61.191,4

387,3392,9

1.228,51.265,9

396,5402,4

1.116,11.151,5

408,2414,0

1.187,31.223,6

415,6421,2

1.096,31.128,5

426,6432,0

1.161,11.194,1

427,0432,4

1.042,31.072,9

438,0443,4

1.104,01.135,4

408,5414,5

1.076,81.110,7

420,4426,0

1.145,11.180,0

420,3426,2

1.024,31.055,9

432,0437,7

1.088,41.121,4

441,5447,3

1.015,31.045,2

452,5457,9

1.075,51.106,1

448,8454,8459,8465,2

435,8441,5

998,01.028,5

447,1452,8

1.060,01.092,1

443,6449,2454,7460,4

89

1.372,61.412,0

4*5*

1.240,11.279,4

ALR HA405.4

67

1.318,71.358,3

89

1.396,41.436,1

398,8404,1

1.303,71.341,7

384,2390,2

1.176,81.214,0

419,6425,1

1.260,21.297,1

405,4411,4

1.137,91.173,6

396,0401,7

1.251,51.289,2

407,9413,4

1.327,31.365,5

417,4423,2

1.209,71.246,3

429,0434,6

1.283,21.320,4

ALR HA415.4

4*5*

1.314,51.357,2

67

1.400,11.443,4

89

1.485,71.529,3

4*5*

1.352,11.395,5

396,6402,8

1.246,81.287,0

408,8414,8

1.327,71.368,9

418,6424,8

1.205,31.243,9

431,0437,2

1.283,11.322,9

421,2426,8

1.410,41.452,3

412,0418,5

1.282,71.323,7

443,2449,0

1.363,01.403,6

434,8441,4

1.240,21.279,6

431,7437,3

1.215,51.251,3

417,7423,8

1.098,01.132,2

443,3448,8

1.155,01.189,4

429,8435,7

1.044,61.076,6

429,8435,6

1.166,91.202,1

441,3447,0

1.237,81.273,9

441,7447,4

1.109,21.142,5

453,2458,8

1.176,51.211,1

458,4463,9

1.124,71.158,5

445,5451,4

1.017,91.048,8

466,0471,5453,4459,3

457,0462,9

1.080,41.112,8

468,5474,1

1.145,91.179,6

464,7470,7476,2481,8

431,4437,8

1.163,01.199,9

444,0450,0

1.237,51.275,7

444,0450,2

1.106,31.140,9

456,4462,4

1.176,21.212,1

456,0462,0

1.314,51.353,7

448,1454,7

1.197,01.234,5

468,4474,2

1.249,01.286,7

461,2467,6

1.138,91.174,0

460,6466,3

1.078,01.111,4

472,5478,5

1.145,61.180,4

468,8474,4480,6486,6

484,5490,3

1.216,31.253,2

478,4484,3

1.109,91.143,7

492,6498,4486,9492,7

ALR HA345.4

67

1.439,21.483,2

89

1.525,71.570,0

ALR HA455.4

4*5*

1.406,71.451,9

67

1.497,51.543,1

424,9431,1

1.365,21.407,0

437,8443,8

1.449,21.491,8

447,8454,2

1.319,51.359,8

460,4466,5

1.400,71.441,9

421,6428,2

1.335,91.378,8

434,6441,0

1.422,01.465,5

445,4452,2

1.292,41.333,8

458,8465,2

1.375,31.417,4

89

1.586,91.633,1

447,8453,8

1.509,51.553,7

471,4477,6

1.460,01.503,1

461,2467,4

1.272,71.311,5

473,7479,9

1.350,91.390,9

474,0480,2

1.209,91.246,4

486,5492,5

1.283,91.322,1

459,4466,2

1.248,41.287,8

472,6479,2

1.327,51.368,1

473,2479,8

1.189,01.225,7

486,2492,6

1.263,51.301,8

490,7496,9

1.178,51.213,8

503,0509,0

1.250,31.287,7

499,1505,3511,3517,3

491,0497,6

1.159,31.194,6

504,0510,4

1.231,51.268,6

499,8506,4512,8519,2

485,4491,8

1.409,21.450,9

499,0505,2

1.341,01.380,8

516,3522,5

1.306,91.345,7

525,0531,2

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C

4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

(*) 10% glycol must be added.

Page 20: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Standard ratings ALR HA ST,CN 120.2÷235.3 (HFC 134a)

302 B - 98/04 A - page 20/28

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

45

265,4273,8

InputkW

capacitykW

78,079,2

251,6259,6

InputkW

capacitykW

82,183,4

243,3251,0

InputkW

capacitykW

84,685,9

235,0242,5

InputkW

capacitykW

87,188,4

229,5236,8

InputkW

capacitykW

88,890,0

218,4225,4

InputkW92,193,4

ALR HA120.2

67

282,2290,7

89

299,2307,2

ALR HA135.2

45

292,4301,6

67

310,8320,1

80,481,6

267,5275,5

82,884,1

283,6291,7

84,685,8

258,7266,4

87,088,1

274,3282,5

86,587,9

277,1285,9

89,390,6

294,6303,4

91,292,5

268,0276,5

93,995,2

284,9293,4

87,188,3

249,9257,3

89,590,6

264,9273,2

89,690,9

244,1251,2

92,093,0

258,7267,0

93,995,3

258,9267,1

96,798,0

275,3283,4

96,798,1

252,8260,8

99,4100,8

268,8276,7

91,392,5

232,3239,1

93,794,6

246,2254,6

94,695,997,197,9

98,699,9

240,6248,2

101,3102,7

255,9263,3

102,3103,6105,0106,4

89

329,5338,4

45

319,7329,7

ALR HA145.2

67

339,8350,0

89

360,3370,0

91,993,3

312,4321,3

93,094,5

303,0312,6

96,697,8

302,1311,1

98,099,4

293,0302,3

95,997,3

322,2331,8

98,8100,3

341,5351,3

100,9102,4

311,6320,8

103,8105,1

330,3340,1

ALR HA161.2

45

331,5341,9

67

352,4363,0

89

373,6383,6

45

370,7382,4

104,4106,1

314,2324,1

107,7109,3

334,0344,0

110,0111,6

303,8313,4

113,3114,9

323,1332,7

110,9112,6

354,1364,3

107,8109,5

351,4362,5

116,5118,0

342,5352,7

113,6115,3

339,8350,6

99,4100,5

291,8300,9

101,0102,4

283,0292,0

102,2103,2

284,9294,1

104,0105,4

276,4285,1

103,9105,4

301,0309,9

106,8108,1

319,0329,0

106,9108,4

293,9302,5

109,8111,0

311,5321,5

104,0105,0

271,2280,4

105,9107,4

263,1271,4

107,8108,7109,9111,4

108,9110,4

279,8287,9

111,8112,9

296,5306,6

112,8114,4115,8116,8

113,4115,0

293,5302,8

116,6118,3

312,1321,3

116,7118,3

286,6295,7

120,0121,7

304,7313,7

119,9121,3

330,8341,1

117,0118,7

328,2338,6

123,3124,6

323,0333,4

120,5122,2

320,5330,7

118,9120,6

272,8281,4

122,2123,9

290,1298,6

123,4125,0126,7128,4

125,5126,8

307,4317,9

122,8124,5

305,1314,8

130,0131,1127,4129,1

ALR HA171.2

67

394,1405,9

89

417,8429,1

ALR HA185.2

45

394,5406,9

67

419,4432,0

111,2112,8

373,6384,8

114,5116,3

396,1407,4

116,9118,6

361,3372,1

120,3121,9

383,0394,5

116,1117,9

373,9385,7

119,7121,5

397,6409,4

122,3124,1

361,6373,0

125,9127,7

384,5395,9

89

444,6456,6

45

421,9435,2

ALR HA200.2

67

448,5462,0

89

475,5488,3

123,2125,2

421,5433,6

124,7126,6

399,9412,6

129,5131,2

407,6419,8

131,4133,3

386,7399,0

128,6130,5

425,2437,9

132,4134,5

450,8463,7

135,3137,2

411,2423,4

139,1141,0

435,9448,9

120,4122,1

349,0359,3

123,8125,2

370,0381,5

123,9125,6

340,8350,9

127,3128,6

361,2372,9

126,0127,8

349,3360,3

129,6131,5

371,4382,4

129,7131,5

341,1351,9

133,4135,2

362,7373,4

126,2127,9

324,4333,9

129,6130,9

343,8355,6

130,8132,6134,2135,3

132,2134,0

324,6334,9

135,8137,7

345,2355,3

137,2139,0140,8142,8

133,3134,8

393,7406,0

135,4137,3

373,6385,4

137,0138,5

384,4396,8

139,4141,3

364,8376,3

139,3141,3

397,2409,0

143,2144,9

421,0434,2

143,3145,3

387,9399,3

147,2148,8

411,1424,4

139,5140,9

365,9378,4

142,0144,0

347,2358,2

144,5145,7147,4149,3

145,9148,0

369,2380,0

149,9151,4

391,3404,7

151,3153,4155,3156,6

ALR HA215.2

45

449,3463,5

67

477,7492,1

89

506,5520,1

45

494,6510,2

133,4135,5

425,9439,4

137,6139,6

452,9466,4

140,5142,6

411,9424,9

144,7146,8

438,0451,0

141,6143,8

480,1493,9

130,0132,1

468,8483,6

148,8150,8

464,3478,2

137,0139,0

453,4467,7

ALR HA230.2

67

525,8541,6

89

557,5572,4

ALR HA235.3

45

493,1508,7

67

524,2540,0

134,1136,1

498,4513,3

138,0140,2

528,4543,6

141,0143,1

482,0496,4

145,1147,0

511,0526,3

142,8145,1

467,4482,2

147,3149,5

497,0511,8

150,5152,7

452,0466,3

154,9157,2

480,6494,9

144,8146,9

397,9410,5

149,0151,1

423,1435,6

149,1151,2

388,5400,8

153,3155,4

413,1425,3

153,1155,0

448,4462,4

141,1143,2

437,9451,8

157,5159,1

437,9452,0

145,3147,4

427,6441,2

151,9154,0

369,8381,5

156,1158,3

393,3404,8

157,6159,7161,8164,1

160,3161,9

416,8431,0

148,1150,1

407,0419,9

166,1167,5153,7155,7

145,2147,3

465,6479,4

149,3151,0

493,6509,0

149,4151,5

454,7468,1

153,5155,1

481,9497,4

155,0157,3

436,6450,5

159,5161,8

464,3478,0

159,6161,9

426,4439,9

164,1166,4

453,4466,7

152,2154,3

432,8445,5

156,3157,8

458,7474,4

157,7159,9161,9163,2

162,7164,9

405,8418,7

167,1169,5

431,6444,2

168,8171,0173,3175,7

89

555,8570,7

151,6154,0

526,9542,0

159,3161,4

509,5524,7

164,0165,9

492,1507,5

168,6170,4

480,5496,0

171,7173,4

457,4473,0

177,8179,3

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

Page 21: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 21/28

Standard ratings ALR HA ST, CN 251.3÷365.4 (HFC 134a)

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

45

519,6536,0

InputkW

capacitykW

159,5162,0

492,5508,1

InputkW

capacitykW

168,0170,5

476,3491,3

InputkW

capacitykW

173,1175,6

460,0474,6

InputkW

capacitykW

178,2180,7

449,2463,5

InputkW

capacitykW

181,7184,2

427,6441,1

InputkW

188,5191,0

ALR HA251.3

67

552,3568,9

89

585,6601,3

ALR HA261.3

45

544,2561,3

67

578,5595,9

164,5166,9

523,6539,3

169,3172,0

555,1571,0

173,0175,5

506,4521,4

177,9180,3

536,8552,9

157,5160,0

515,8532,1

162,5164,9

548,4564,8

166,0168,4

498,8514,6

170,9173,4

530,4546,2

178,1180,7

489,2503,6

183,1185,3

518,5534,7

183,2185,8

477,7491,8

188,3190,3

506,3522,6

171,0173,5

481,8497,1

176,0178,5

512,4527,5

176,1178,6

470,5485,4

181,0183,6

500,3515,1

186,7189,3

454,7468,0

191,7193,6

481,9498,4

193,5196,2198,6200,2

179,5181,9

447,8462,1

184,4187,0

476,3490,2

186,2188,7191,1193,8

89

613,4629,8

45

568,0585,9

ALR HA270.3

67

603,8621,9

89

640,2657,3

167,3169,9

581,4598,1

165,8168,4

538,4555,4

175,8178,1

562,2579,1

174,7177,3

520,6537,1

171,0173,5

572,4589,5

176,0178,8

606,8624,2

179,9182,5

553,6570,0

185,0187,4

586,8604,4

ALR HA286.3

45

591,8610,4

67

629,1648,0

89

667,0684,9

45

619,1638,7

174,1176,8

561,0578,7

179,5182,2

596,4614,2

183,4186,1

542,5559,6

188,8191,6

576,8593,9

184,8187,7

632,3650,4

182,8185,6

586,9605,4

194,2196,8

611,4629,7

192,5195,4

567,6585,5

180,9183,0

543,1560,0

180,0182,6

502,9518,8

186,0187,9

530,3547,4

185,3187,9

491,1506,6

185,2187,8

534,7550,5

190,4192,6

566,8584,5

190,5193,2

522,2537,6

195,7197,8

553,4571,3

189,4191,2

504,7522,0

188,9191,5

467,4482,2

196,2197,8196,0198,6

194,1196,8

497,1511,6

199,3201,3

526,8544,8

201,2203,9206,5208,2

189,0191,7

524,0540,6

194,4197,2

557,2573,6

194,5197,3

511,7527,9

200,0202,8

544,1560,1

199,8202,2

590,6609,0

198,4201,3

548,2565,6

205,5207,7

576,7595,2

204,3207,1

535,3552,3

198,3201,0

487,0502,5

203,7206,6

517,9533,1

205,7208,4211,2214,1

209,2211,3

548,9567,6

208,2211,0

509,5525,7

216,7218,5216,0218,9

ALR HA290.3

67

658,2678,0

89

697,9716,6

ALR HA311.3

45

646,6667,0

67

687,3708,0

188,5191,3

624,0642,6

194,0197,1

661,5680,5

198,3201,1

603,4621,4

203,9206,6

639,7658,8

191,4194,4

612,9632,3

197,4200,4

651,6671,1

201,7204,7

592,7611,4

207,7210,7

630,2648,9

89

728,8748,3

45

679,6701,0

ALR HA325.3

67

722,5744,2

89

766,0786,6

203,3206,5

690,8710,6

199,9203,0

644,2664,6

213,6216,4

668,0688,0

210,5213,7

623,0642,7

206,1209,2

684,9705,4

212,2215,5

726,1746,9

216,8219,9

662,4682,1

223,0225,9

702,1723,2

204,1207,0

582,9600,2

209,8212,3

617,9637,2

210,0213,0

569,2586,0

215,7218,0

603,3622,7

207,8210,8

572,5590,6

213,8216,9

608,7626,7

214,0217,0

559,0576,7

220,0223,1

594,4612,0

213,9216,9

541,9557,7

219,7221,8

574,2593,9

221,7224,8227,6229,4

218,1221,1

532,1549,0

224,1227,2

565,9582,4

226,3229,3232,3235,5

219,8222,4

645,2665,4

217,0220,1

601,7620,8

226,0228,4

630,0650,3

223,4226,5

587,6606,2

223,2226,4

639,8658,8

229,5232,2

678,2699,4

229,6232,9

624,8643,2

235,9238,4

662,2683,5

230,1232,4

599,7620,2

227,6230,8

559,3577,0

238,4240,4236,2239,3

233,9237,2

594,8612,2

240,2242,6

630,3651,9

242,5245,8248,9250,9

ALR HA345.4

45

717,7740,3

67

762,9785,9

89

808,9830,6

45

741,4764,8

207,3210,6

680,3701,8

213,8217,0

723,3744,9

218,4221,7

657,9678,7

224,9228,2

699,5720,3

220,2223,6

766,8788,8

215,6219,0

702,8725,0

231,3234,4

741,5763,7

227,1230,5

679,6701,1

ALR HA355.4

67

788,2811,9

89

835,7858,1

ALR HA365.4

45

765,3789,4

67

813,5838,0

222,4225,6

747,2769,5

228,9232,5

792,2814,9

233,9237,3

722,6744,1

240,6243,7

766,0789,0

223,9227,4

725,4748,3

230,9234,3

771,2794,3

235,8239,3

701,5723,7

242,9246,4

745,9768,0

225,1228,3

635,4655,6

231,6234,9

675,7695,7

231,7235,0

620,5640,2

238,2241,6

659,8679,3

238,1240,9

716,2738,6

234,1237,4

656,5677,3

244,8247,4

699,3721,8

241,0244,4

641,0661,4

236,2239,4

590,6609,3

242,7246,1

628,1646,4

245,1248,3251,6255,0

249,2251,7

665,6688,4

245,6249,0

610,2629,5

258,2260,3254,8258,2

240,8244,3

698,1718,7

247,5250,5

739,9763,0

247,7251,2

681,7701,7

254,5257,2

722,5745,7

243,0246,5

677,6699,0

250,0253,6

720,5741,8

250,2253,7

661,6682,6

257,2260,9

703,6724,3

252,3255,9

648,9667,9

259,2261,7

687,7711,2

261,6265,2268,5270,7

255,0258,5

629,8649,8

262,0265,7

669,7689,3

264,6268,1271,6275,3

89

862,6885,7

237,7241,4

817,6841,1

249,8253,1

790,6814,3

257,0260,1

763,7787,5

264,3267,1

745,7769,7

269,1271,7

709,7734,0

278,8281,1

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C

4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

Page 22: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

Standard ratings ALR HA ST,CN 375.4÷455.4 (HFC 134a)

302 B - 98/04 A - page 22/28

ALR HAST, CN Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power

unit size capacitykW

45

789,0813,9

InputkW

capacitykW

232,1235,8

747,9771,6

InputkW

capacitykW

244,5248,2

723,3746,1

InputkW

capacitykW

252,0255,6

698,6720,7

InputkW

capacitykW

259,4263,1

682,2703,8

InputkW

capacitykW

264,4268,0

649,3669,9

InputkW

274,3278,0

ALR HA375.4

67

838,8864,0

89

889,3913,2

ALR HA390.4

45

816,4842,2

67

867,9894,0

239,4242,9

795,2818,9

246,5250,3

843,0867,2

251,8255,5

769,0791,9

259,0262,4

815,2839,6

240,8244,5

773,9798,4

248,3252,0

822,8847,4

253,6257,4

748,4772,1

261,2265,0

795,8819,4

259,3263,0

742,9764,8

266,5269,7

787,4812,0

266,7270,5

725,4746,8

274,0276,9

768,9793,6

261,4265,1

722,9745,8

268,9272,7

768,7791,4

269,1272,9

705,9728,3

276,6280,5

750,6772,7

271,7275,5

690,5710,7

279,0281,8

731,8756,8

281,6285,5289,0291,4

274,2278,0

671,9693,2

281,8285,7

714,5735,4

284,5288,3292,1296,1

89

920,3944,9

45

843,8870,4

ALR HA405.4

67

897,0924,0

89

951,1976,6

255,6259,6

872,3897,3

249,4253,4

799,9825,1

268,6272,2

843,5868,8

262,8266,7

773,5798,0

257,3261,1

850,4875,8

264,9269,0

901,5927,4

270,6274,5

822,4846,9

278,3282,0

871,8897,9

ALR HA415.4

45

871,2898,7

67

926,2954,0

89

982,01.008,3

45

898,7927,0

258,1262,2

825,9851,9

266,2270,2

878,0904,2

271,9276,0

798,6823,9

280,0284,1

849,1874,4

274,1278,4

930,8957,6

266,8271,0

851,9878,8

288,0291,8

900,1927,1

281,1285,2

823,8849,9

276,4279,7

814,8840,2

270,8274,7

747,1770,8

284,2287,2

795,6821,2

278,8282,7

729,6752,7

278,6282,6

794,4817,9

286,4289,8

842,1868,4

286,6290,7

775,8798,6

294,5297,6

822,2848,7

289,4292,2

757,2783,1

284,1288,0

694,4716,4

299,8302,3294,8298,7

292,0296,0

738,5760,1

299,8302,8

782,6809,4

302,6306,8310,6313,2

280,2284,3

771,4795,8

288,3292,4

820,3844,5

288,5292,6

753,3777,1

296,6300,8

801,0824,6

296,4299,9

869,4896,6

289,6293,8

795,7820,9

304,7308,0

849,0876,3

298,2302,4

777,0801,6

294,0298,1

717,0739,7

302,1306,4

762,5784,8

305,1309,1313,2317,5

310,3313,3

808,0835,7

303,9308,1

739,6763,0

321,4324,1315,3319,5

ALR HA345.4

67

955,4984,1

89

1.013,01.040,1

ALR HA455.4

45

989,31.020,5

67

1.051,71.083,4

275,2279,2

905,7932,8

283,3287,7

960,2987,7

289,4293,6

875,9901,9

297,7301,6

928,5956,3

260,0264,1

937,8967,4

268,2272,1

997,11.026,8

273,9278,0

906,9935,6

282,1286,2

964,3992,9

89

1.115,11.145,0

276,1280,4

1.057,01.087,4

290,1294,0

1.022,21.052,8

298,0302,2

846,1871,1

306,3309,9

896,8924,9

306,5310,9

826,3850,6

314,9318,3

875,7903,9

282,3286,4

876,0903,7

290,4294,6

931,5959,0

290,6294,7

855,4882,5

298,8303,0

909,6936,4

312,2316,6

786,5809,5

320,7323,8

833,5862,0

323,7328,1332,2335,0

296,2300,3

814,2840,0

304,3308,6

865,9891,2

307,3311,4315,5319,8

298,5302,1

987,31.018,2

307,0310,2

964,1995,1

312,6315,6

917,6949,0

323,8326,5

35 46 48 52AMBIENT TEMPERATURE - 0 C

Leav

ing

chille

dw

ater

tem

p.- 0

C4 0 43

Notes: (1) Ratings based on: evaporator fouling factor of 0,044 m2 °C/kW, evaporator temperature drop of 5°C and sea level altitude.

(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.

(3) The power input is for compressors only.

Page 23: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 23/28

ALR HA 120.2-135.2 ST, CN

Legend1 Condenser coil2 Evaporator3 Evaporator water inlet4 Evaporator water outlet5 5" victaulic connections for 139,7 O.D. tube6 Operating and control panel7 No. 4 lifting holes Ø 70 mm 8 No. 4 isolator mounting holes Ø 22 mm9 Compressor enclosure (std. on CN versions)10 360x160 slot for power and control panel connection

ALR HA 145.2÷185.2 ST, CN

Legend1 Condenser coil2 Evaporator3 Evaporator water inlet4 Evaporator water outlet5 8" victaulic connections for 219,1 O.D. tube6 Operating and control panel7 360x150 slot for power and control connection8 No. 4 lifting holes Ø 90 mm9 No. 6 isolator mounting holes Ø 25 mm10 Compressor enclosure (std. on CN versions)11 Coil protection guards (optional)

Page 24: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 24/28

AL

R H

A 2

35.3

-286

.3 S

T, C

N

AL

R H

A 2

00.2

-230

.2 S

T, C

N

Leg

end

1C

onde

nser

coi

l2

Eva

pora

tor

3E

vapo

rato

r w

ater

inle

t4

Eva

pora

tor

wat

er o

utle

t5

8" v

icta

ulic

con

nect

ions

for

219,

1 O

.D. t

ube

6O

pera

ting

and

cont

rol p

anel

736

0x15

0 sl

ot fo

r po

wer

and

con

trol

con

nect

ion

8N

o. 4

lifti

ng h

oles

Ø 9

0 m

m9

No.

8 is

olat

or m

ount

ing

hole

s Ø

25

mm

10C

ompr

esso

r en

clos

ure

(std

. on

CN

ver

sion

s)11

Coi

l pro

tect

ion

guar

ds (

optio

nal)

Page 25: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 25/28

AL

R H

A 3

11.3

ST

, CN

AL

R H

A 2

90.3

ST

, CN

Leg

end

1C

onde

nser

coi

l2

Eva

pora

tor

3E

vapo

rato

r w

ater

inle

t4

Eva

pora

tor

wat

er o

utle

t5

8" v

icta

ulic

con

nect

ions

for

219,

1 O

.D. t

ube

6O

pera

ting

and

cont

rol p

anel

736

0x15

0 sl

ot fo

r po

wer

and

con

trol

con

nect

ion

8N

o. 4

lifti

ng h

oles

Ø 9

0 m

m9

No.

8 is

olat

or m

ount

ing

hole

s Ø

25

mm

10C

ompr

esso

r en

clos

ure

(std

. on

CN

ver

sion

s)11

Coi

l pro

tect

ion

guar

ds (

optio

nal)

Page 26: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 26/28

AL

R H

A 3

45.4

÷375

.4 S

T, C

N

AL

R H

A 3

25.3

ST

, CN

Leg

end

1C

onde

nser

coi

l2

Eva

pora

tor

3E

vapo

rato

r w

ater

inle

t4

Eva

pora

tor

wat

er o

utle

t5

8" v

icta

ulic

con

nect

ions

for

219,

1 O

.D. t

ube

6O

pera

ting

and

cont

rol p

anel

736

0x15

0 sl

ot fo

r po

wer

and

con

trol

con

nect

ion

8N

o. 4

lifti

ng h

oles

Ø 9

0 m

m9

No.

12

isol

ator

mou

ntin

g ho

les

Ø 2

5 m

m10

Com

pres

sor

encl

osur

e (s

td. o

n C

N v

ersi

ons)

11C

oil p

rote

ctio

n gu

ards

(op

tiona

l)

Page 27: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

302 B - 98/04 A - page 27/28

AL

R H

A 4

15.4

÷455

.4 S

T, C

N

AL

R H

A 3

90.4

-405

.4 S

T, C

N

Leg

end

1C

onde

nser

coi

l2

Eva

pora

tor

3E

vapo

rato

r w

ater

inle

t4

Eva

pora

tor

wat

er o

utle

t5

8" v

icta

ulic

con

nect

ions

for

219,

1 O

.D. t

ube

6O

pera

ting

and

cont

rol p

anel

736

0x15

0 sl

ot fo

r po

wer

and

con

trol

con

nect

ion

8N

o. 4

lifti

ng h

oles

Ø 9

0 m

m9

No.

12 is

olat

or m

ount

ing

hole

s Ø

25

mm

10C

ompr

esso

r en

clos

ure

(std

. on

CN

ver

sion

s)11

Coi

l pro

tect

ion

guar

ds (

optio

nal)

Page 28: Air cooled water chillers HA...ALR HA - Air cooled water chillers 302 B - 98/04 A - page 2/28 The newly redesigned McQuay ALR HA (high ambient tem-perature) air cooled water chillers

We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.

McQuay Italia S.p.A.S.S. Nettunense, km 12+300 - 00040 Cecchina (Roma) Italia - Tel. (06) 937311 - Fax (06) 9374014 - E-mail: [email protected] - Tlx 611349 MCQUAY I

To supply and install, where specified in the project n° ..... unit(s)aircooled water chiller with cooling capacity of ..... kW, to cool .....m3/sec. of water from ..... °C to ..... working with ..... °C ambienttemperature. The unit should work with electricity at ..... V. 3ph.50Hz. The electrical power absorbed should not overcome ..... kW.The units COP will be at least ..... at the working conditions of theproject. Part load COP will be at least ..... at the working conditionsof the project. For the units with 2, 3 and 4 compressors the chil-lers wll have (2), (3) or (4) indipendent refrigerant circuits, with therespective electronic microprocessor will alow the starting of thecompressors. Each chiller will be factory assembled on a robustbaseframe made of zinc coated steel, with zinc coated panels, pro-tected by an epoxy coated paint. The painting of the chillers to con-form to the 500 hours salt spray test method 6061 (no. 141 STD)The unit will be tested at full load in the factory at the nominal wor-king conditions and water temperatures. Before shipment a full testwill be held to avoid any losses, and the units will be filled with oiland 134a refrigerant. Units will have the following components:

General - All units are designed and manufactured in accordan-ce with applicable selections of the following which are equivalentto American Air-conditioning industry applicable codes:Rating of chillers: UNI 9018Construction of pressure vessel: TÜV Standards (optional)Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety CodesSafety Codes: CEI-EN 60204-1 CodesManufacturing Quality Stds: ISO 9001Compressors - will incorporate ..... compressor(s) McQuay's alter-native semihermetic compressor(s) with many cylinders and platevalves, a crankcase heater, a protection spring for the valvesagainst liquid carryover, interchangeable cylinder jackets, overdi-mensioned oil filter with a fine mesh, on the suction line, with anadditional oil filter on the oil discharge and sight glass. The com-pressor will be supplied with a forced lubrication system with a re-versible pump and will be fully charged. Solenoid valves will beprovided to activate the cylinder by-pass between suction and dis-charge of the cylinder heads. Part winding / single speed compres-sor will be 1450 RPM or less.Compressor motor - the motors of the compressors cooled by thesuction gas and will be available in two versions: part winding anddouble speed. The part winding motor will have the windings divi-ded into two sections in order to reduce the inrush current which al-lows the reduced dimension of power supply. The double speedmotor will be built with two stator windings (4 and 8 poles) and willallow a better efficiency at low speed with better energy saving.Both motors will be thermally protected from high temperatures bysensors that are inserted in each of the phases of the windings.Evaporator - the units will be supplied with (1) or (2) direct expan-sion evaporators with refrigerant inside the tubes and water outsi-de, (shell side) with carbon steel tube sheets, with straight coppertubes that are spirally wound internally for higher efficiencies, ex-panded on the tube plates. Each evaporator will have two refrige-rant circuits (units with 2 or 4 compressors) or 3 refrigerant circuits(units with 3 compressors) one for each compressor. Testing andoperation pressure, refrig. side working pressure 15 Bar and waterside 10 Bar.Condenser coil - the condenser coils are constructed with inter-nally enchanced seamless copper tubes having a "W" configurationand arranged in a staggered row pattern and mechanically expan-ded into lanced and rippled aluminium fins with full fin collars for hi-gher efficiencies. The spacing between the fins are given by a col-lar that will increase the surface area in connection with the tubes,protecting them from ambient corrosion. The coils will have an inte-gral sybcooler circuit which provides sufficient subcooling to effecti-vely eliminate the possibility of liquid flashing and increase the

units efficiency up to 8% without an increase in power absorbed,and the surface area will be dimensioned in a way to permit an airvelocity not greater than 2,5 m/sec. Leak tested at 10 Bar and pres-sure tested at 30 Bar.Condenser fans - the fans are used in conjunction with the con-denser coils, they are of the impeller type with aerofoil polypropyle-ne blades for higher efficiencies and lower noise. The air dischargeis vertical and each fan will be coupled to the electrical motor, withthe casing made in aluminium and supplied as standard totalyenclosed with 6 poles and capable to work to ambient temperaturesof -40°C to +55°C. Each fan will be controlled by the condensingpressure of the relevent cooling circuit. There is also an accidentprotection within the motors. Condenser motors with Class F mo-tors. Cast aluminium condenser fan blades will be supplied asoption.Thermostatic expansion valve - each refrigerant circuit will beequipped with all the necessary components in order to ensure theworkings and service (dehydration filter, liquid sight glass, shut offvalve, load connection and pressure switch etc). Thermostatic ex-pansion valve regulates the injection of refrigerant liquid intoevaporators. Injection is controlled by the refrigerant superheat.Control panel - field power connection, control interlock terminals,and unit control system shall be centrally located in a weatherproofcabinet accessible through a key locked door. Power and startingcontrols shall be separate from safety and operating controls in dif-ferent compartments of the same panel.Power and starting com-partment shall be protected by a plastic cover. Power and startingcontrols shall include fuses and contactors for each compressorwinding and fan motors. Operating and safety controls shall includeenergy saving control; emergency stop switch; solid-state protec-tion for compressor motor; differential oil pressure safety switch (foreach compressor); high and low pressure cut-out switch (for eachrefrigerant circuit); anti-freeze thermostat; compressor lead-lagswitch (on 2 compressor units only); cut-out switch for each com-pressor; operating hour meter (for each compressor).Regulation of cooling capacity - each unit will have a controllerfor the control and operation of the unit with 4, 6 or 8 steps of capa-city control depending on the number of compressors. All of the in-formation regarding the unit will be reported on the controller dis-play with 32 characters and with the internal built in calender andclock this will switch the unit ON/OFF during day time all year long.The microprocessor permits a "soft start" function throughout an ex-ternal signal will allow a load reduction of the unit when there arepeaks of absorbed current. In addition a connection to a BMSsystem can be made via an "open protocol" or an interface via amodem to a personnal computer. All general alarms can be memo-rised by an easy analysis of the faults and their causes.High and low temperature function - the units will be providedwith an automatic control for condensing pressure which ensuresthe working at low external temperatures down to +5°C, because ofthe working cycle of the condenser fans, in respect to the conden-sing pressure. The unit needs to be able to work with high externalambient temperatures up to 52°C and capable of starting at 46°C atfully loaded condition. Low temperature starting with fantrol (stan-dard) will be less than 0°C and with speedtrol (option) this will be -18 °CRefrigerant piping - refrigerant circuit shall include a factory insu-lated suction line, manual liquid line shut-off valve with chargingconnection; refrigerant filter drier with replaceable core; liquid sightglass/moisture indicator; liquid line solenoid valve; thermostatic ex-pansion valve, and 27 bar relief valve. Records for the refrigerantpressure manometer and oil will be placed inside the control cabi-net. Flexible refrigerant piping hot gas muffler, though not required,can also be offered as option.

Technical specification